tt silent m booklet 2016 10 eng
TRANSCRIPT
2016
2 VENTS. SOUND-INSULATED VENTILATION | TT SILENT-M| 10-2016
Offi ces
Kindergartens
Restaurants
Sport halls Shops
Schools
Libraries
Conference halls
WWW.VENTILATION-SYSTEM.COM
3VENTS. SOUND-INSULATED VENTILATION | TT SILENT-M| 10-2016
«NOISY LIFE »
Our life is daily fi lled with millions of various words, voices and sounds. We are surrounded by all kinds
of sounds in the offi ce, outside and even at home. Loud natural sounds are rare and do not last long.
However, the voice of nature is hardly audible in the modern urbanized world as is often lost in industrial noises.
This sound pollution has become an unwanted integral part of our lives. Numerous investigations prove the negative eff ects of noise pressure on human health. Lasting exposure to acoustic waves is not only unfavourable for auditory organs, but may provoke decrease of auditory sensitivity, heart disorders, high pressure, headaches, rapid fatigability, nervous stress and other unpleasant symptoms that may lead to severe complications.
We perceive sound in diff erent ways depending on age, health state, mood and ambient conditions. As most daily time we spend at work, the labour conditions infl uence our acoustic apparatus most of all.
The many sources of noise irritants include loud human voices, working equipment, telephone rings, outside noise that comes through open windows, etc.
Comfortable job climate means not only admissible indoor noise level but also fresh permanently circulating air.
Natural air circulation created by open windows and doors is always combined with unhealthy draughts, various smells, dust, allergens that come to the premise. But even more preferable mechanical ventilation is also associated with increased acoustic discomfort because of sounds generated by working equipment.
20-30 dB is the natural noise level that is harmless for the human health and makes the natural noise background in our life.
DO YOU NEED EFFICIENT SILENT VENTILATION IN YOUR
ROOM? WE HAVE A SOLUTION!
The latest developments in ventilation industry resulted in the invention of a totally sound-insulated casing that provides an absolutely silent fan operation.
The noise level generated by the operating fan with minimum air fl ow does not exceed 29 dB(A) and 40 dB(A) at maximum air fl ow respectively.
The noise produced by the fan is commeasurable with the natural comfortable sound level.
Integration of sound-insulated fans into air handling units is the best solution for various premises requiring low noise ventilation, such as banks, archives, museums, kindergartens, education facilities, libraries, theatres, public institutions, record studios, etc.
WW
the negative effects of noise
avBao
fb
WW
f d l d f h dl h b l ff
4 VENTS. SOUND-INSULATED VENTILATION | TT SILENT-M| 10-2016
Series
VENTS TT Silent-M
SOUND-INSULATED FANS
The new TT Silent-M fan is covered by a specially designed heat- and sound-insulated casing that provides low-noise operation.
The VENTS TT Silent-M fans combine wide capabilities and high performance characteristics of both axial and centrifugal fans, thus providing powerful air stream and high pressure.
The VENTS TT Silent-M fan is recommended for effi cient supply and exhaust ventilation of various commercial and industrial premises with high requirements to noise level, i.e. in libraries, conference halls, educational institutions, kindergartens, etc.
The VENTS TT Silent-M fan is compatible with round air ducts from Ø 100 up to 450 mm and produce maximum air fl ow 6510 m3/h.
Casing
the outer casing is made of black polymer coated steel;heat and sound insulation with 50 mm mineral wool layer;the inner casing perforation let sound waves pass through the holes and fall at a specifi c angle to the
sound-absorbing layer thus providing sound attenuation in a broad frequency band; the inner casing and the impeller are made of high-quality durable ABS plastic;the conic impeller with special blade profi ling, the diff user and the directing vanes at the casing outlet increase air
fl ow speed and provide higher pressure and air capacity as compared to standard axial fans; power supply though the external airtight terminal box on the fan casing;
Motor
single-phase energy effi cient double-speed motor with low energy demand;
thermal switches ensure the motor overheating protection;
extended motor service life up to 40 000 hrs. due to ball bearings;
IPX4 ingress protection rating.
Mounting
mounting at any place and at any angle within the ductwork system;
several fans in one system: parallel mounting to attain higher air capacity, mounting in series to boost operating pressure;
fi xing brackets for fastening the fan to the fl oor, wall or ceiling.
Accessories
Panel fi lters
FB FBV
Silencer
SR (round)Bag fi lters
FBKElectric heaters
NKWater heaters
NKVBack valves
KOM
WWW.VENTILATION-SYSTEM.COM
5VENTS. SOUND-INSULATED VENTILATION | TT SILENT-M| 10-2016
Speed control
The double-speed motors are controlled with a built-in switch («V» option) or an external switch for multi-speed fans (available upon separate order);
TT Silent-M fan with a three-position
speed switch
A built-in speed controller («P» option), an external TRIAC or autotransformer speed controller (available upon separate order) enable smooth motor speed control when connected to the maximum speed terminal;
TT Silent-M fan with a built-in
speed controller
«T» option models are equipped with an adjustable turn-off delay timer, adjustable from 2 to 30 minutes.
The fan with electronic module of the tem pe-
rature sensor and speed controller («U» option)
The front panel of the electronic module has the following controls:
• speed control knob for setting the motor speed;
• thermostat control knob for setting the tem pe-rature set point;• thermostat indicator light.TT Silent-M…U fan with the electronic temperature
and speed control module provides automatic control of the motor speed (air capacity) depending on the air temperature in the air duct or in the room.
TT Silent-M…U is available in two modifi cations:• with a temperature sensor integrated inside thefan air duct («U/U1» option);• with an external temperature sensor fi xed on thecable, 4 m long («Un/U1n» option).
TT Silent-M…U with a with a temperature
sensor integrated inside the fan air duct
(«U/U1» option);
TT Silent-M…U with an external temperature sensor
fi xed on the cable, 4 m long
(«Un/U1n» option).
TT Silent-M…U with an external temperature sensor
Control logic of the fan with the electronic
temperature and speed control module («U»
option):
• Set the desired air temperature (set point of the thermostat) with the thermostat control knob;
• Set the required minimum impeller speed (air fl ow)
with the speed control knob;• The motor switches to maximum speed (maximum
air fl ow) as air temperature reaches and exceeds the set temperature set point.
• The motor switches to the pre-set lower speed as air temperature drops down below the set temperature point.
To avoid the frequent motor speed changes, e.g.
when the temperature in the supply air duct is
equal to the threshold value, the switching delay
time is activated:
• option 1. The temperature sensor-based switch delay («U/U1» option): the motor switches to higher speed as air temperature exceeds 2°C above the set thermostat set point. The motor revers to the pre-set lower speed as air temperature drops down below the thermostat set point. This control logic is used to keep air temperature to within 2°C. In this case the motor speed switches are rare.
• option 2. The timer-based switch delay (Un /
U1n option): as air temperature exceeds the set thermostat set point, the motor switches to higher speed and the switch delay timer is activated for 5 min. The motor reverts to lower speed as the air temperature drops down below the thermostat set point and only after the delay timer countdown. This pattern is used for exact air temperature control. The speed switches for the fan with U1 option are more frequent as compared to the fan with U option, however the minimum operating cycle at one speed is 5 minutes.
Clamps
C CZ
CZK
Temperature controllers
RTS-1-400RTSD-1-400
Speed switches
P2-1-300Air shutters
КРSensor
T-1,5 H TH-1,5 H
TF-1,5 H, TP-1,5 H
Air shutters
VENTS. SOUND-INSULATED VENTILATION | TT SILENT-M| 10-20166
SOUND-INSULATED FANS
Technical data:
VENTS TT Silent-M
VENTS TT Silent-M
VENTS TT Silent-M
VENTS TT Silent-M
Sound-power level Octave-frequency band [Hz]Hz Gen 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 42 19 18 29 35 39 39 31 24LwA to outlet dBA 45 20 19 30 38 42 35 35 23LwA to environment dBA 34 15 14 17 25 29 21 22 14
Sound-power level Octave-frequency band [Hz]Hz Gen 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 61 25 33 49 55 53 55 53 39LwA to outlet dBA 59 35 36 51 55 55 55 50 42LwA to environment dBA 39 19 22 39 35 36 33 24 21
Sound-power level Octave-frequency band [Hz]Hz Gen 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 47 19 21 35 38 42 41 35 28LwA to outlet dBA 46 21 24 35 39 41 43 37 29LwA to environment dBA 35 17 20 23 27 28 22 21 15
Sound-power level Octave-frequency band [Hz]Hz Gen 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 62 26 38 54 57 58 55 52 48LwA to outlet dBA 65 28 42 48 62 60 62 50 44LwA to environment dBA 45 22 30 31 38 41 42 29 22
Pre
ssu
re,
P [
Pa
]
0
20
40
60
80
100
120
140
160
0 50 100 150 200 250
TT Silent-M 100
Air capacity, [m3/h]
Pre
ssu
re,
P [
Pa
]
0
50
100
150
200
250
0 100 200 300 400 500 600
TT Silent-M 150TT Silent-M 160
Air capacity, [m3/h]
Pre
ssu
re,
P [
Pa
]
0
20
40
60
80
100
120
140
160
0 50 100 150 200 250 300 350
TT Silent-M 125
Air capacity, [m3/h]
Pre
ssu
re,
P [
Pa
]
0
50
100
150
200
250
300
350
0 200 400 600 800 1000
TT Silent-M 200
Air capacity, [m3/h]
TT Silent-M
100*
TT Silent-M
125*
TT Silent-M 150*
TT Silent-M 160*
Speed min max min max min maxVoltage [V / 50/60 Hz] 1~ 230 1~ 230 1~ 230
Power [W] 24 26 25 29 45 52Current [A] 0.10 0.11 0.11 0.13 0.20 0.23
Max. air capacity [m3/h] 170 240 230 340 405 555RPM [min-1] 2030 2630 1650 2310 1970 2645
Noise level at 3 m [dBA] 24 29 23 28 26 33Max. transported air temperature [°C] 60 60 60
SEC class** D D C
Protection rating IP X4 IP X4 IP X4* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum effi ciency is < 125W. ** The EC norm 1254/2014 does not apply if maximum air capacity is >1000 m3/h
WWW.VENTILATION-SYSTEM.COM
7VENTS. SOUND-INSULATED VENTILATION | TT SILENT-M| 10-2016
Technical data:
VENTS TT Silent-M VENTS TT Silent-M
Sound-power level Octave-frequency band [Hz]Hz Gen 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 65 29 41 57 60 61 58 55 51LwA to outlet dBA 75 31 45 58 65 73 65 53 47LwA to environment dBA 55 25 33 48 41 53 49 41 29
Sound-power level Octave-frequency band [Hz]Hz Gen 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 69 35 47 62 61 64 67 58 55LwA to outlet dBA 75 40 53 69 69 70 65 55 51LwA to environment dBA 58 25 32 41 51 55 52 49 37
Pre
ssu
re,
P [
Pa
]
0
100
200
300
400
500
0 200 400 600 800 1000 1200 1400
TT Silent-M 250
Ƞmax
Air capacity, [m3/h]
Pre
ssu
re,
P [
Pa
]
0
100
200
300
400
500
600
700
0 500 1000 1500 2000
TT Silent-M 315
Ƞmax
Air capacity, [m3/h]
TT Silent-M
200*
TT Silent-M
250
TT Silent-M
315
Speed min max min max min max
Voltage [V / 50/60 Hz] 1~ 230 1~ 230 1~ 230
Power [W] 78 110 127 178 213 313Current [A] 0.35 0.49 0.52 0.79 0.93 1.41
Max. air capacity [m3/h] 810 1020 1050 1330 1530 1950
RPM [min-1] 2015 2445 1965 2495 1975 2545
Noise level at 3 m [dBA] 31 36 34 38 36 40
Max. transported air temperature [°C] 60 60 60
SEC class** C - -
Protection rating IP X4 IP X4 IP X4* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum effi ciency is < 125W. ** The EC norm 1254/2014 does not apply if maximum air capacity is >1000 m3/h
, [%] MC EC N VSD [kW] [A] [m3/h] [Pa] [RPM] SR
30.9 A Static 49.4 No 0.174 0.8 803 236 2505 1
, [%] MC EC N VSD [kW] [A] [m3/h] [Pa] [RPM] SR
32.4 A Static 48.2 No 0.317 1.43 1112 326 2320 1
Fan overall dimensions:
Type Dimensions [mm] Weight
[kg] Fig. no.D B B1 L H
TT Silent-M 100 98 215 243 505 237 4,6 1
TT Silent-M 125 123 215 243 474 237 4,6 1
TT Silent-M 150 147 247 274 580 260 6,1 1
TT Silent-M 160 157 247 274 580 260 6,1 1
TT Silent-M 200 198 293 386 550 295 8 2
TT Silent-M 250 248 358 445 658 360 15 2
TT Silent-M315 313 432 520 780 434 25 2
TT Silent-M 355-4E 353 460 540 1320 510 33 3
TT Silent-M 355-4D 353 460 540 1320 510 33 3
TT Silent-M 400-4E 397 460 540 1320 510 35 3
TT Silent-M 400-4D 397 460 540 1320 510 35 3
TT Silent-M 450-4E 447 460 640 1425 610 51 3
TT Silent-M 450-4D 447 460 640 1425 610 51 3
Fig .1
Fig .2
Fig .3
Technical data:
VENTS TT Silent-M VENTS TT Silent-M
VENTS TT Silent-M
0
30
60
90
120
150
180
210
240
270
0 500 1000 1500 2000 2500 3000 3500
ТТ Silent-M 355-4EТТ Silent-М 355-4D
Pre
ssur
e, Δ
Р [P
a]
Air capacity, [m3/h]
0
30
60
90
120
150
180
210
240
270
0 500 1000 1500 2000 2500 3000 3500 4000
Pre
ssur
e, Δ
Р [P
a]
Air capacity, [m3/h]
ТТ Silent-M 400-4EТТ Silent-М 400-4D
0
50
100
150
200
250
300
350
400
450
0 1000 2000 3000 4000 5000 6000 7000
Pre
ssu
re,
ΔР
[P
a]
Air capacity, [m3/h]
ТТ Silent-M 450-4EТТ Silent-М 450-4D
TT Silent-M
355-4E*
TT Silent-M
355-4D*
TT Silent-M
400-4E*
TT Silent-M
400-4D*
TT Silent-M
450-4E
TT Silent-M
450-4D
Voltage [V / 50/60 Hz] 1~ 230 3~ 400 1~ 230 3~ 400 1~ 230 3~ 400
Power [W] 578 585 580 590 1200 1230
Current [A] 3,42 1,77 3,43 1,78 7,72 3,43
Max. air capacity [m3/h] 3310 3430 3545 3670 6260 6510
RPM [min-1] 1480 1490 1480 1490 1475 1490
Noise level at 3 m [dBA] 49 49 50 50 59 59
Max. transported air temperature [°C] 60 60 60 60 60 60
SEC class** - - - - - -
Protection rating IP X4 IP X4 IP X4 IP X4 IP X4 IP X4
* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum effi ciency is < 125W. ** The EC norm 1254/2014 does not apply if maximum air capacity is >1000 m3/h
SOUND-INSULATED FANS
8