CO M P . L A B 5066 5066A E 1 3 WOMEN E 1 0 MEN E 8 E 9 E 7 C L E 6 E 3 E 1 1 E 2 5005A E 1 2 ECON. G E OL. L AB 5044 H I G H P R ESS U RE LAB 5056 LAB 5046 O F FICE O F FICE 5064A 5060A 5051 PREP. RM LAB 5005B 5042 O F FICE X-R A Y & CRYSTALL O G. L A B 50 5 0B 5065B 5 06 1A 5016A 5 03 4 A 5026A 501 7B O F FICE 5000 O F FICE 5002 L A B 5003 R E SE AR CH L A B 5007 R E SE AR CH L A B 5010 R E SE AR CH L A B 5014 5010A 5014A RESEARCH L A B 5008 O F FICE 5008A O F FICE 50 0 8B O F FICE 501 6B O F FICE 5012 RESEARCH L A B 5016 CO L D ROOM 501 6C RESEARCH L A B 5017 5017A L A B 5022 L A B 5022A L A B 5026 DK RM 50 2 6B A U TO - CL A VES 5026 D RESEARCH L A B 5028 O F FICE 5028A O F FICE 50 2 8B L A B 5029 L A B 5029A L A B 50 2 9B O F FICE 50 2 9C O F FICE 5029 D L A B 5034 OFF. 5036 OFF. 5038 O F FICE 5064 L A B 5060 O F FICE 5040 O F FICE 5041A O F FICE 5041 GR AD UATE OFFICES 5043 O F FICE 5045 L A B 5050 O F FICE 5057A O F FICE 5057 G EOCHE M L A B 5061 L A B 5067 L A B 5067A HYD R OTH E RMAL LAB 5065 A STAIRS E 5 UP RE S . 50 0 8C STAIRS E1 DN C ORRID O R C R -5A C ORRID O R C R -5A LOBBY CR-5B C ORRID O R CR-5C C ORRID O R CR-5D O F FICE 5049 CO M P . ROOM 5053 L A B 5042A O F FICE 5044A O F FICE 5048 R E SE AR CH L A B 5005 TECH VIRGINIA RO AD LOCATION MAP: M AIN STREE T S OUT HGATE D R IVE 460 BYPASS U.S. R OU T E PRI C ES F OR K DRI L L FIELD W ASHINGTON STREET WEST CAMPUS DRIVE NORTH WORK AREAS (TYP.) DERRING HALL - FIFTH FLOOR N KEY PLAN: 1" = 50' - 0" DERRING HALL SHEET INDEX T1 COVER SHEET T2 GENERAL NOTES + INFORMATION LS1 LIFE SAFETY PLAN + BUILDING CODE DATA A1.1 DEMO PLANS + NOTES A1.2 NEW WORK - PLANS, PARTIAL PLANS, NOTES A1.3 NEW WORK - PARTIAL PLANS A1.4 NEW WORK - REFLECTED CEILING PLAN A2.1 SCHEDULES A2.2 EQUIPMENT SCHEDULE + EQUIPMENT PLAN A3.1 ELEVATIONS, SECTIONS + DETAILS .PD1.1 PARTIAL FIFTH FLOOR DEMOLITION PLAN - PLUMBING P0.1 PLUMBING LEGEND, NOTES, DETAILS + FIXTURE SCHEDULE P0.2 PLUMBING SPECIFICATIONS P1.1 PARTIAL FIFTH FLOOR NEW WORK PLAN - PLUMBING .MD1.1 PARTIAL FIFTH FLOOR DEMOLITION PLAN - DUCTWORK M0.1 MECHANICAL LEGEND, DETAILS + EQUIPMENT NOTES M0.2 MECHANICAL SPECIFICATIONS M0.3 MECHANICAL SPECIFICATIONS M1.1 PARTIAL FIFTH FLOOR PLAN - DUCTWORK + PIPING M1.2 PARTIAL PENTHOUSE FLOOR NEW WORK PLAN - PIPING .ED1.1 PARTIAL FIFTH FLOOR DEMOLITION PLAN - LIGHTING .ED1.2 PARTIAL FIFTH FLOOR DEMOLITION PLAN - POWER E0.1 ELECTRICAL LEGEND, DETAILS, SCHEDULES + ABBREVIATIONS E0.2 ELECTRICAL GENERAL NOTES, SPECIFICATIONS + DETAILS E1.1 PARTIAL FIFTH FLOOR NEW WORK PLAN - LIGHTING E1.2 PARTIAL NEW WORK FLOOR PLAN - POWER E1.3 PARTIAL FIFTH FLOOR PLAN - PANELBOARD LOCATIONS AN ASBESTOS INSPECTION WILL BE PERFORMED PRIOR TO WORK. A COPY OF THE DETAILED REPORT WILL BE INCLUDED IN THE CONSTRUCTION DOCUMENTS. THE OWNER WILL COORDINATE THE REMOVAL OF ASBESTOS MATERIALS PRIOR TO THE WORK BEING PERFORMED. IF A SUSPECT ASBESTOS MATERIAL IS ENCOUNTERED IN THE COURSE OF THE WORK THAT IS NOT DISCUSSED AS PART OF THE REPORT, THE WORK MUST BE STOPPED IMMEDIATELY AND VIRGINIA TECH RENOVATIONS SHALL BE CONTACTED IMMEDIATELY AT 231-6101 . A LEAD PAINT INSPECTION WILL BE PERFORMED PRIOR TO WORK. A COPY OF THE DETAILED REPORT WILL BE INCLUDED IN THE CONSTRUCTION DOCUMENTS. IF LEAD PAINT OR OTHER LEAD MATERIALS ARE IDENTIFIED IN THE AREA OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE OSHA LEAD STANDARD, 29 CFR 1926.62 AND SHALL EXERCISE DUE DILIGENCE TO AVOID THE CREATION OF LEAD DUST. IF SUSPECT LEAD MATERIALS ARE ENCOUNTERED IN THE COURSE OF WORK THAT IS NOT DISCUSSED AS PART OF THE REPORT, THE WORK MUST BE STOPPED AND VIRGINIA TECH RENOVATIONS SHALL BE CONTACTED IMMEDIATELY AT 231-6101. THE CONTRACTOR SHALL SUBMIT A COPY OF THEIR LEAD COMPLIANCE PROGRAM, AS REQUIRED BY 29 CFR 1926.62(E), WITH REQUIRED SUPPORTING DOCUMENTATION, TO EHSS FOR PRIOR REVIEW AND APPROVAL. THIS SUBMITTAL SHALL BE MADE SUFFICIENTLY IN ADVANCE OF CONSTRUCTION TO AVOID DELAY OF THE PROJECT. A COPY OF ANY PERSONAL AIR SAMPLES TAKEN DURING THE COURSE OF THE WORK SHALL BE PROVIDED TO UNIVERSITY DESIGN AND CONSTRUCTION SERVICES. ASBESTOS AND LEAD NOTE: colley architects pc design community environment SUITE 301 620 N. MAIN STREET BLACKSBURG, VA . 24060 P. 540.953.ARCH (2724) F. 540.953.2725 CONTACT: TIM COLLEY . AIA [email protected] design community environment architects pc colley VIRGINIA POLYTECHNI C INSTITUTE & STATE UNIVERSITY SHEET PREPARED BY: BUILDING # REVISI ONS WORK ORDER # BID SET VIRGINIA TECH RENOVATIONS T1 DERRING HALL FI FTH FLOOR LABORATORIES DERRING HALL FIFTH FLOOR LABORATORIES SEPTEMBER . 30 . 2016 SEP TEMBER . 30 . 2016 RENOVATIONS TO RENOVATIONS TO 155 G843-16-219956 DATE IFB # 0047615

Upload: others

Post on 03-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

COMP.

LAB

5066

5066A

E13

WOMEN

E10

MEN

E8

E9

E7

CL

E6

E3

E11

E2

5005A

E12

ECON. GEOL. LAB

5044

HIG

H

PRESSURE LAB

5056

LAB

5046

OFFIC

E

OFFIC

E

5064A

5060A

5051

PREP. RM

LAB

5005B

5042

OFFIC

E

X-RAY &

CRYSTALL

OG.

LAB

5050B

5065B 5061A

5016

A5034A

5026A

5017B

OFFIC

E

5000

OFFIC

E

5002

LAB

5003

RESEARCH

LAB

5007

RESEARCH

LAB

5010

RESEARCH

LAB

5014

5010

A

5014

A

RESEARCH LAB

5008

OFFIC

E

5008A

OFFIC

E

5008B

OFFIC

E

5016B

OFFIC

E5012

RESEARCH LAB

5016

COLD

ROOM

5016C

RESEARCH LAB

5017

5017

A

LAB

5022

LAB

5022A

LAB

5026

DK RM

5026B

AUTO-

CLAVES

5026D

RESEARCH LAB

5028

OFFIC

E

5028A

OFFIC

E

5028B

LAB

5029

LAB

5029A

LAB

5029B

OFFIC

E

5029C

OFFIC

E

5029D

LAB

5034

OFF.

5036

OFF.

5038

OFFIC

E

5064

LAB

5060

OFFIC

E

5040

OFFIC

E

5041A

OFFIC

E5041G

RADUATE

OFFIC

ES

5043

OFFIC

E

5045

LAB

5050

OFFIC

E

5057A

OFFIC

E

5057

GEOCHEM

LAB

5061

LAB

5067

LAB

5067A

HYDROTHERMAL LAB

5065

ASTAIRS

E5

UP

RES.

5008C

STAIRS

E1

DN

CORRIDOR

CR-5A

CORRIDOR

CR-5A

LOBBY

CR-5B

CORRIDOR

CR-5C

CORRIDOR

CR-5D

OFFIC

E

5049

COMP.

ROOM

5053

LAB

5042A

OFFIC

E

5044A

OFFIC

E

5048

RESEARCH

LAB

5005

TECH

VIRGINIA

ROAD

LOCATION MAP:

MAIN ST

REET

SOUT

HGAT

E DRIVE

460 BYPASS

U.S. ROUTE

PRICES

FORK

DRILL

FIELD

WASHINGTO

N STREET

WEST CAMPUS

DRIVE

NORTH

WORK AREAS (TYP.)

DERRING HALL - FIFTH FLOOR

N

KEY PLAN:1" = 50' - 0"

DERRING HALL

SHEET INDEX

T1 COVER SHEET

T2 GENERAL NOTES + INFORMATION

LS1 LIFE SAFETY PLAN + BUILDING CODE DATA

A1.1 DEMO PLANS + NOTES

A1.2 NEW WORK - PLANS, PARTIAL PLANS, NOTES

A1.3 NEW WORK - PARTIAL PLANS

A1.4 NEW WORK - REFLECTED CEILING PLAN

A2.1 SCHEDULES

A2.2 EQUIPMENT SCHEDULE + EQUIPMENT PLAN

A3.1 ELEVATIONS, SECTIONS + DETAILS

.PD1.1 PARTIAL FIFTH FLOOR DEMOLITION PLAN - PLUMBING

P0.1 PLUMBING LEGEND, NOTES, DETAILS + FIXTURE SCHEDULE

P0.2 PLUMBING SPECIFICATIONS

P1.1 PARTIAL FIFTH FLOOR NEW WORK PLAN - PLUMBING

.MD1.1 PARTIAL FIFTH FLOOR DEMOLITION PLAN - DUCTWORK

M0.1 MECHANICAL LEGEND, DETAILS + EQUIPMENT NOTES

M0.2 MECHANICAL SPECIFICATIONS

M0.3 MECHANICAL SPECIFICATIONS

M1.1 PARTIAL FIFTH FLOOR PLAN - DUCTWORK + PIPING

M1.2 PARTIAL PENTHOUSE FLOOR NEW WORK PLAN - PIPING

.ED1.1 PARTIAL FIFTH FLOOR DEMOLITION PLAN - LIGHTING

.ED1.2 PARTIAL FIFTH FLOOR DEMOLITION PLAN - POWER

E0.1 ELECTRICAL LEGEND, DETAILS, SCHEDULES + ABBREVIATIONS

E0.2 ELECTRICAL GENERAL NOTES, SPECIFICATIONS + DETAILS

E1.1 PARTIAL FIFTH FLOOR NEW WORK PLAN - LIGHTING

E1.2 PARTIAL NEW WORK FLOOR PLAN - POWER

E1.3 PARTIAL FIFTH FLOOR PLAN - PANELBOARD LOCATIONS

AN ASBESTOS INSPECTION WILL BE PERFORMED PRIOR TO WORK. A COPY OF THEDETAILED REPORT WILL BE INCLUDED IN THE CONSTRUCTION DOCUMENTS. THEOWNER WILL COORDINATE THE REMOVAL OF ASBESTOS MATERIALS PRIOR TO THEWORK BEING PERFORMED. IF A SUSPECT ASBESTOS MATERIAL IS ENCOUNTERED INTHE COURSE OF THE WORK THAT IS NOT DISCUSSED AS PART OF THE REPORT, THEWORK MUST BE STOPPED IMMEDIATELY AND VIRGINIA TECH RENOVATIONS SHALL BECONTACTED IMMEDIATELY AT 231-6101 .

A LEAD PAINT INSPECTION WILL BE PERFORMED PRIOR TO WORK. A COPY OF THEDETAILED REPORT WILL BE INCLUDED IN THE CONSTRUCTION DOCUMENTS. IFLEAD PAINT OR OTHER LEAD MATERIALS ARE IDENTIFIED IN THE AREA OF WORK, THECONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTSOF THE OSHA LEAD STANDARD, 29 CFR 1926.62 AND SHALL EXERCISE DUEDILIGENCE TO AVOID THE CREATION OF LEAD DUST. IF SUSPECT LEAD MATERIALSARE ENCOUNTERED IN THE COURSE OF WORK THAT IS NOT DISCUSSED AS PART OFTHE REPORT, THE WORK MUST BE STOPPED AND VIRGINIA TECH RENOVATIONSSHALL BE CONTACTED IMMEDIATELY AT 231-6101. THE CONTRACTOR SHALL SUBMITA COPY OF THEIR LEAD COMPLIANCE PROGRAM, AS REQUIRED BY 29 CFR 1926.62(E),WITH REQUIRED SUPPORTING DOCUMENTATION, TO EHSS FOR PRIOR REVIEW ANDAPPROVAL. THIS SUBMITTAL SHALL BE MADE SUFFICIENTLY IN ADVANCE OFCONSTRUCTION TO AVOID DELAY OF THE PROJECT. A COPY OF ANY PERSONAL AIRSAMPLES TAKEN DURING THE COURSE OF THE WORK SHALL BE PROVIDED TOUNIVERSITY DESIGN AND CONSTRUCTION SERVICES.

ASBESTOS AND LEAD NOTE:

colleyarchitects pc

design community environment

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725CONTACT: TIM COLLEY . [email protected]

de

sig

ncom

mu

nity

en

viro

nm

en

t

arc

hitects

pc

co

lley

VIR

GIN

IA P

OL

YT

EC

HN

I C IN

ST

ITU

TE

& S

TA

TE

UN

IVE

RS

ITY

SHEET

PREPARED BY:

BUILDING #

RE

VIS

I ON

S

WORK ORDER #

BID SET

VIRGINIA TECH RENOVATIONS

T1

DE

RR

ING

HA

LL

FI F

TH

FLO

OR

LA

BO

RA

TO

RIE

SDERRING HALLFIFTH FLOOR LABORATORIES

SEPTEMBER . 30 . 2016

SE

PT

EM

BE

R . 3

0 . 2

016

RENOVATIONS TO

RE

NO

VA

TIO

NS

TO155

G843-16-219956

D

AT

E

IFB # 0047615

Page 2: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

@ACTADJAFFAHUALTALUMAPPRAVGAWP

BLDGBLKBOTBRKBTWN

CABCJCLGCLOSCLRCMUCOLCONCCONTCTLCT

DEMODEPTDFDIAGDIMDNDWG

EAEIFS

ELECEPSEQEQUIPEXISTEXT

FDFFFLRFLURFTFURR

GAGALGALVGBGCGFCMU

GLGYP

HBDHDRHMHRHTHVACHW

ININFOINST

INSULINT

KIT

LAMLAVLBSLFLVR

MAT'LMAXMECHMFRMINMIRMISCMTLNICNONOMNTS

OCOFCI

PCPERFPLAMPLYWDPNLPREFABPREFINPREPPT

QTQTY

RBRDREFREFGREQDRMRT

SIMSPECSQSSSTDSTLSTORSUSP

THKTYP

VACVB

VCT

VEST

WBWCWGLWHW/OWSCTWT

ATACOUSTICAL CEILING TILEADJUSTABLEABOVE FINISHED FLOORAIR HANDLING UNITALTERNATEALUMINUMAPPROXIMATEAVERAGEACOUSTICAL WALL PANEL

BUILDINGBLOCKBOTTOMBRICKBETWEEN

CABINETCONTROL JOINTCEILINGCLOSETCLEARCONCRETE MASONRY UNITCOLUMNCONCRETECONTINUOUSCARPET TILECERAMIC TILE

DEMOLISH, DEMOLITIONDEPARTMENTDRINKING FOUNTAINDIAGONALDIMENSIONDOWNDRAWING

EACHEXTERIOR INSULATIONAND FINISH SYSTEMELECTRICALEXPANDED POLYSTYRENEEQUALEQUIPMENTEXISTINGEXTERIOR

FLOOR DRAINFINISHED FLOORFLUORESCENT

FOOT, FEETFURRING

GAUGEGALLONGALVANIZEDGRAB BARGENERAL CONTRACTORGROUND FACE CONCRETEMASONRY UNITGLASSGYPSUM

HARDBOARDHEADERHOLLOWHOURHEIGHTHEATING, VENTILATING,AIR CONDITIONINGHOT WATER

INCHINFORMATIONINSTALLATION

INSULATIONINTERIOR

KITCHEN

LAMINATELAVATORYPOUNDSLINEAR FOOT/FEETLOUVER

MATERIALMAXIMUMMECHANICALMANUFACTURERMINIMUMMIRRORMISCELLANEOUSMETALNOT IN CONTRACTNUMBERNOMINALNOT TO SCALE

ON CENTEROWNER FURNISHEDCONTRACTORINSTALL

PRECASTPERFORATEDPLASTIC LAMINATEPLYWOODPANELPREFABRICATEDPREFINISHEDPREPAREPAINT

QUARRY TILEQUANTITY

RUBBER BASEROOF DRAINREFERENCEREFRIGERATORREQUIREDROOMRUBBER TILE

SIMILARSPECIFICATIONSQUARESTAINLESS STEELSTANDARDSTEELSTORAGESUSPENDED

THICKNESSTYPICAL

VACUUMVAPOR BARRIER/VINYL BASEVINYL COMPOSITIONTILEVESTIBULE

WOOD BASEWATER CLOSETWIRE GLASSWATER HEATERWITHOUTWAINSCOTWEIGHT

ABBREVIATIONS GENERAL NOTES GENERAL NOTES

DESIGN STANDARDS:

VIRGINIA TECH DESIGN GUIDELINES AND CONSTRUCTION STANDARDSVUSBC VIRGINIA UNIFORM STATEWIDE BUILDING CODEANSI 117.1-2009 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIESAGA AMERICAN GAS ASSOCIATIONAMCA AIR MOVEMENT AND CONTROL ASSOCIATIONANSI AMERICAN NATIONAL STANDARDS INSTITUTEARI AIR-CONDITIONING AND REFRIGERATION INSTITUTEASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR

CONDITIONING ENGINEERSASPE AMERICAN SOCIETY OF PLUMBING ENGINEERSASSE AMERICAN SOCIETY OF SANITARY ENGINEERINGASME AMERICAN SOCIETY OF MECHANICAL ENGINEERSASTM AMERICAN SOCIETY FOR TESTING AND MATERIALSIEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERSMCA MECHANICAL CONTRACTORS ASSOCIATIONNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNFPA NATIONAL FIRE PROTECTION ASSOCIATIONPDI PLUMBING AND DRAINAGE INSTITUTESMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS

NATIONAL ASSOCIATIONUL UNDERWRITERS LABORATORIES, INC.

1. CONTRACTOR SHALL DELIVER ALL SOLID WASTE COLLECTED ONVIRGINIA TECH PROPERTIES TO MONTGOMERY REGIONAL SOLID WASTE AUTHORITYTRANSFER STATION.

DISPOSAL OF MATERIALS

1. CONTRACTOR SHALL VERIFY ALL CONDITIONS IN THE FIELD PRIOR TOSUBMITTING A BID.

2. DIMENSIONS SHOWN ARE FROM FACE OF EXISTING CONSTRUCTION TO FACE OFEXISTING CONSTRUCTION. NEW CONSTRUCTION DIMENSIONS ARE TO ROUGHFRAMING.

3. MATCH THICKNESS OF NEW AND COMPLETED/EXISTING CONSTRUCTION.

4. PATCH AND REPAIR ALL EXISTING DAMAGED SURFACES WITH SIMILAR MATERIALSTO MATCH NEW WORK, INCLUDING LEVEL OF FINISH.

5. THE OWNER SHALL BE RESPONSIBLE FOR THE FINAL SELECTION OF ALLFIXTURES, FINISHES, PATTERNS, COLORS, AND STYLES FROM THE FULL RANGE OFMANUFACTURER'S AVAILABLE STANDARDS.

6. COORDINATE WITH OWNER THE EXACT TYPE AND FINISHED LOCATION OF ANYEQUIPMENT, FIXTURES, ACCESSORIES, OUTLETS, SWITCHES, ETC.

7. WOOD PRODUCTS SHALL BE FROM SUSTAINABLE SOURCES, SUCH AS FSCCERTIFIED WOOD OR REGIONALLY HARVESTED OR MANUFACTURED WOOD FROMABUNDANT SPECIES. WOOD PRODUCTS SHALL BE FREE OF UREA-FORMALDEHYDEBINDERS, COPPER OR ARSENIC.

8. ALL CONCEALED WOOD SHALL BE FIRE RESISTANT TREATED WOOD.

ARCHITECTURAL

GENERAL:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR, MATERIALS, EQUIPMENT,ANCHORAGE TO STRUCTURE, AND CONNECTIONS REQUIRED FOR THEINSTALLATION OF A COMPLETE AND FUNCTIONAL SYSTEM.

2. CONTRACTOR SHALL COORDINATE WORK WITH THE INSTALLED WORK OFOTHER TRADES.

3. VERIFY "ROUGH-IN" LOCATIONS WITH OWNER PRIOR TO FINAL INSTALLATION.

4. PIPING, DUCTWORK, AND OTHER EQUIPMENT SHALL BE SUPPORTED BY ORANCHORED TO THE BUILDING STRUCTURE. NON-STRUCTURAL CEILINGCONSTRUCTION, NEW OR EXISTING, SHALL NOT BE USED FOR ANCHORING ANYWORK.

5. SYSTEMS AND ACCESSORIES SHALL BE INSTALLED IN A NEAT MANNERCONSISTENT WITH INDUSTRY STANDARDS OF QUALITY AND CARE.

6. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ANY & ALL PIPES, CONDUIT,ELECTRICAL OR OTHER INFRASTRUCTURE ITEMS AS A RESULT OF THEIR BEINGUNCOVERED DURING EXECUTION OF THE WORK.

PLUMBING:

1. PLUMBING DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE2012 EDITION OF THE INTERNATIONAL PLUMBING CODE (IPC), INCLUDINGREFERENCED CODES AND STANDARDS, AND THE REQUIREMENTS OF LOCALBUILDING OFFICIALS.

2. PLUMBING CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LOCATIONS, ANDFIELD CONDITIONS PRIOR TO INSTALLATION.

3. CONTRACTOR SHALL COORDINATE WATER SHUTOFF WITH VIRGINIA TECHPROJECT MANAGER & VIRGINIA TECH UTILITIES FOR INSTALLATION OF VALVES.NOTIFY OWNER 3 DAYS IN ADVANCE.

4. UPON COMPLETION OF WORK, PLUMBING CONTRACTOR SHALL CONDUCT ATEST. IN THE PRESENCE OF OWNER/ARCHITECT WITH ALL EQUIPMENT ANDCONTROLS IN NORMAL OPERATING POSITION. THE SYSTEM SHALL OPERATEQUIETLY & PROPERLY. ADJUSTMENTS AND CORRECTIONS SHALL BE MADE UNTILSATISFACTORY OPERATION IS ACHIEVED.

5. NOTE NOT USED.

MECHANICAL:

1. MECHANICAL DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITHTHE 2012 EDITION OF THE INTERNATIONAL MECHANICAL CODE (IMC), INCLUDINGREFERENCED CODES AND STANDARDS, AND THE REQUIREMENTS OF LOCALBUILDING OFFICIALS.

2. MECHANICAL EQUIPMENT LOCATIONS SHOWN FOR DESIGN INTENT ONLY.CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LOCATIONS, AND FIELDCONDITIONS PRIOR TO INSTALLATION.

3. SHOP DRAWINGS TO BE PROVIDED FOR APPROVAL FOR ALL DUCTWORK.

ELECTRICAL:

1. COORDINATE WITH ARCHITECT THE EXACT LOCATION OF ANY FIXTURES,ACCESSORIES, OUTLETS, SWITCHES, ETC. PRIOR TO INSTALLATION.

2. ELECTRICAL DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE2011 EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), INCLUDINGREFERENCED CODES AND STANDARDS, UTILITY COMPANY REGULATIONS, AND THEREQUIREMENTS OF LOCAL BUILDING OFFICIALS.

3. ELECTRICAL EQUIPMENT LOCATIONS SHOWN FOR DESIGN INTENT ONLY.CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LOCATIONS, AND FIELDCONDITIONS PRIOR TO INSTALLATION.

4. ALL NON-LED LIGHT FIXTURES SHALL BE INSTALLED WITH LAMPS. PROVIDE 10%,BUT NOT LESS THAN FIVE (5), ADDITIONAL LAMPS FOR EACH FIXTURE TYPE FORFUTURE USE.

5. PROVIDE MEANS OF EGRESS LIGHTING AS INDICATED. MEANS OF EGRESSILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOT-CANDLE AT FLOOR LEVEL.AN EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OFNOT LESS THAN 90 MINUTES AND SHALL ILLUMINATE EXIT ACCESS CORRIDORS,PASSAGEWAYS, AISLES, AND PORTION OF EXTERIOR EXIT DISCHARGEIMMEDIATELY ADJACENT TO EXIT DISCHARGE DOORWAYS.

6. CONTRACTOR TO PROVIDE & INSTALL REQUIRED INFRASTRUCTURE TOACCOMMODATE CNS DEVICES, WIRELESS & OTHERWISE. COORDINATELOCATIONS WITH VA TECH. CONDUITS SHALL EITHER BE CONTINUOUS "HOME-RUN" FROM THE TELECOMMUNICATIONS OUTLET BOX TO THE EQUIPMENT ROOM,OR SHALL BE RUN FROM THE OUTLET BOX AND STUBBED OUT WITHIN ONE FOOT (1FT.) OF A CABLE TRAY THAT RUNS CONTINUOUSLY TO THE EQUIPMENT ROOM. INTHE CASE OF A RENOVATION WHERE THERE IS NO CABLE TRAY AVAILABLE, THECONDUIT FOR THE OUTLET BOX SHOULD BE ROUTED TO AN ACCESSIBLE CEILINGAREA IN THE CORRIDOR. THE CONTRACTOR SHALL COMPLY WITH "VIRGINIA TECHTELECOMMUNICATIONS INFRASTRUCTURE DESIGN GUIDELINES" WHICH ISINCORPORATED HEREIN BY REFERENCE. THE GUIDELINES MAY BE DOWNLOADEDFROM HTTP://WWW.CNS.VT.EDU/CABLING_STANDARDS.HTML.

7. EXPOSED CONDUIT AND RACEWAY LOCATIONS TO BE COORDINATED WITHARCHITECT PRIOR TO INSTALLATION. ALL VERTICAL RUNS TO BE HELD TIGHT TOINSIDE CORNERS TO THE GREATEST EXTENT POSSIBLE.

8. ALL EXIST. VISIBLE OUTLETS, SWITCHES, & DATA CONNECTORS WITHIN SCOPEOF WORK TO REMAIN SHALL RECEIVE NEW STAINLESS STEEL FACE PLATES &BLACK DEVICES. ORIENT SCREW HEADS VERTICALLY.

PLUMBING / MECHANICAL / ELECTRICAL1. ALL CONSTRUCTION, MATERIALS, AND WORKMANSHIP SHALL COMPLY WITH THEBUILDING & PROJECT CODE DATA REFERENCED ON SHEET LS1.

2. ALL WORK TO COMPLY WITH THE VIRGINIA TECH DESIGN AND CONSTRUCTIONSTANDARDS, REVISED AUGUST 2006.

3. CONTRACTOR MUST FAMILIARIZE THEMSELVES WITH THE PROJECT SITE PRIORTO SUBMITTING THEIR BID. AS PART OF THE BASE BID CONTRACTOR SHALLINCLUDE PATCHING ANY EXISTING HOLES & PENETRATIONS THROUGH FIRE ANDSMOKE WALLS AND BARRIERS IN AREAS OF WORK TO MEET OR EXCEED THEREQUIRED FIRE ASSEMBLY RATING. THIS WORK SHALL INCLUDE PROVIDING &INSTALLING REQ'D. FIRE DAMPERS IN EXISTING AND NEW DUCTS WHICHPENETRATE THE RATED ASSEMBLIES.

4. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND ACCESSORIES FORWORK INDICATED HEREIN, UNLESS NOTED OTHERWISE. WORK SHALL BECOMPLETE AND IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS,MANUFACTURER'S RECOMMENDATIONS, GENERALLY ACCEPTED INDUSTRYSTANDARDS OF WORKMANSHIP AND CARE, AND AS REQUIRED FOR A FINISHEDINSTALLATION AND TO OBTAIN A CERTIFICATE OF OCCUPANCY.

5. SUBMITTALS ARE REVIEWED ONLY AS TO GENERAL CONFORMITY WITH DESIGNCONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATIONGIVEN IN THE CONTRACT DOCUMENTS. CORRECTIONS AND/OR COMMENTS MADEAS PART OF THIS SUBMITTAL REVIEW DO NOT RELIEVE THE CONTRACTOR OFRESPONSIBILITY FROM CONFORMANCE WITH THE CONTRACT DOCUMENTS,APPLICABLE CODES, AND LAWS - ALL OF WHICH HAVE PRIORITY OVER SPECIFICSUBMITTAL. THE DESIGN PROFESSIONAL DOES NOT WARRANT OR REPRESENTTHAT THE INFORMATION WITHIN THE SUBMITTAL IS EITHER ACCURATE ORCOMPLETE. SOLE RESPONSIBILITY FOR CORRECT DESIGN, DETAILS, ANDDIMENSIONS SHALL REMAIN WITH THE PARTY PROVIDING THE SUBMITTAL.CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, QUANTITIES, ANDPERFORMANCE REQUIREMENTS TO BE CONFIRMED AND CORRELATED AT THE JOBSITE; FOR ALL INFORMATION THAT PERTAINS SOLELY TO THE FABRICATIONPROCESSES OR TO THE TECHNIQUES OF CONSTRUCTION; FOR ALLCOORDINATION OF THE WORK OF ALL TRADES; FOR ASSURING CONSISTENCYWITH THE CONTRACT DOCUMENTS; AND FOR PERFORMING THE WORK IN A SAFEAND SATISFACTORY MANNER.

6. EXISTING SQUARE FOOTAGES, DIMENSIONS, TYPES/LOCATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES, AND SIZES/LOCATIONS OF EXISTING EQUIPMENTARE APPROXIMATE. CONTRACTOR IS RESPONSIBLE FOR THE FIELD VERIFICATIONOF ALL SITE CONDITIONS PRIOR TO SUBMITTING A BID. IF CONDITIONS IN FIELDDIFFER FROM THOSE SHOWN, NOTIFY OWNER/ARCHITECT IMMEDIATELY.

7. PROJECT PERMIT WILL BE ISSUED LOCALLY AND INSPECTED BY VIRGINIA TECHPERSONNEL.

8. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS,METHODS, SEQUENCING, SITE SAFETY, AND SECURITY FOR THE DURATION OF THEPROJECT.

9. CONTRACTOR SHALL VERIFY THE AVAILABILITY OF EXISTING FACILITIES ANDUTILITIES AT THE PROJECT SITE PRIOR TO SUBMITTING A BID. COSTS ASSOCIATEDWITH THE USE OF EXISTING UTILITIES SHALL BE THE CONTRACTOR'SRESPONSIBILITY.

10. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF WORK WITH THEOWNER'S ACTIVITIES AND OTHER TRADES INVOLVED WITH WORK AT THE PROJECTSITE. CONTRACTOR SHALL COORDINATE WORK INCLUDING BUT NOT LIMITED TOADDITION TO/MODIFICATION OF EXISTING MECHANICAL, ELECTRICAL, PLUMBING,AUTOMATIC SPRINKLER, FIRE ALARM AND FIRE DETECTION SYSTEMS AS REQUIREDFOR A FINISHED AND FULLY FUNCTIONAL INSTALLATION.

11. FIRE-RESISTANCE ASSEMBLIES REQ'D. IN ACCORDANCE WITH ASTME 814(UL1479) & ASTME 1966 (UL 2079). FIRESTOPPING EQUAL TO 3M COMPANY TYPECP-25WB+ (WATER BASED AND HALOGEN FREE) NO SAG INTUMESCENT FIREBARRIER SEALANT, TYPE FS-195+ PIPE WRAP/ STRIP FIRE BARRIER OR CS-195COMPOSITE SHEET FIRE BARRIER. CONTRACTOR TO INSTALL REQUIRED RATEDASSEMBLY MATERIALS IN STRICT ADHERENCE TO ONE OF THE FOLLOWING ULRATED ASSEMBLIES: C-AJ-1044, C-AJ-1176, C-AJ-1556, C-AJ-2006, C-AJ-2228, C-AJ-3030, C-AJ-3096, C-AJ-5001, C-AJ-7016, W-L-1001, W-L-1054, W-L-2003, W-L-3001, W-L-3065, W-L-5001, W-L-7008, W-L-7051, W-L-7130, OR W-L-8079. THE CONTRACTORSHALL NOTIFY THE ARCHITECT IMMEDIATELY IF THEY ENCOUNTER A CONDITIONNOT COVERED BY ONE OF THE UL ASSEMBLIES LISTED ABOVE. THE APPROPRIATEAMOUNT OF RATED ASSEMBLY MATERIALS SHALL BE BASED ON THE FIRESEPARATION RATINGS LISTED ON THE BUILDING & PROJECT CODE DATA SHEETLS1 AND THE ATTACHED DRAWINGS. PROVIDE RESTRAINING COLLARS,FASTENERS, AND ALL OTHER COMPONENTS REQUIRED FOR A UL LISTEDTHROUGH-PENETRATION FIRESTOPPING ASSEMBLY SUITABLE FOR USE IN RATEDCONSTRUCTION. CONTRACTOR SHALL SUBMIT UL DESIGNS AND PRODUCTINFORMATION FOR ALL COMPONENTS OF ALL PROPOSED FIRESTOPPINGASSEMBLIES TO THE ARCHITECT & VIRGINIA TECH UNIVERSITY BUILDING OFFICIALFOR APPROVAL PRIOR TO INCORPORATION INTO WORK. ALL THROUGH-PENETRATION FIRESTOPPING SYSTEMS SHALL BE INSTALLED IN STRICTACCORDANCE WITH ALL DETAILS OF THE UL LISTING. CONTRACTOR TO RETAINALL UL ASSEMBLY INSTRUCTIONS USED IN PROJECT ON SITE AT ALL TIMES.

12. CONTRACTOR SHALL LABEL ALL CONCEALED FIRE WALLS, VERTICAL FIRESEPARATION ASSEMBLIES, FIRE BARRIERS, FIRE PARTITIONS AND SMOKEBARRIERS ON ASSEMBLIES ABOVE CEILINGS AND ON INSIDE SURFACES OF ALLCEILING ACCESS DOORS PROVIDING ACCESS TO SUCH FIRE RATED ASSEMBLIES.REFERENCE DRAWINGS FOR ASSEMBLY RATING DESIGNATIONS AND TYPES. ALLLETTERING TO BE IN A CONTRASTING AND HIGHLY VISIBLE COLOR TO SURFACE, 3IN. TALL (1 INCH MIN.) CAPITAL CASE, AND PROVIDED AT HORIZONTAL INTERVALSOF NO MORE THAN 8 FEET.

13. CONTRACTOR TO PROVIDE & INSTALL REQUIRED INFRASTRUCTURE TOACCOMMODATE HOKIE PASSPORT SERVICES (HPS) DEVICES, WIRELESS &OTHERWISE. LOCATIONS TO BE COORDINATED WITH VA TECH. CONDUITS SHALLEITHER BE CONTINUOUS "HOME-RUN" FROM THE CARD READER AND ELECTRONICDOOR HARDWARE TO THE HEAD END ROOM, OR SHALL BE RUN FROM THE CARDREADER AND ELECTRONIC DOOR HARDWARE AND STUBBED OUT WITHIN ONEFOOT (1 FT.) OF A CABLE TRAY THAT RUNS CONTINUOUSLY TO THE HEAD ENDROOM. IN THE CASE OF A RENOVATION WHERE THERE IS NO CABLE TRAYAVAILABLE, THE CONDUIT FOR THE CARD READER AND ELECTRONIC DOORHARDWARE TO BE ROUTED TO AN ACCESSIBLE CEILING AREA IN THE CORRIDORAND J HOOKS & D RINGS SHALL BE PROVIDED & INSTALLED FOR THE PATH TO THEHEAD END ROOM. IF A NEW HEAD END ROOM IS REQUIRED, THE SYSTEM WILLREQUIRE A MINIMUM 4' X 4' WALL SPACE IN A SECURE CLOSET WITH A 20 AMP QUADOUTLET ON AN EMERGENCY PANEL & A CNS NETWORK PORTAL. THE ROUGH-IN ATTHE DOOR BY THE CONTRACTOR SHALL INCLUDE A QUAD JUNCTION BOX ABOVETHE DOOR WITH 3/4" CONDUIT TO THE NECESSARY LOCATIONS FOR THEELECTRONIC ACCESS SYSTEM (CARD READER, ELECTRONIC HARDWARE, ANDDOOR POSITION SWITCH). THE CONTRACTOR SHALL COMPLY WITH "VIRGINIA TECHELECTRONIC DOOR ACCESS CONTROL STANDARD".

GENERAL NOTES

1. EXISTING DIMENSIONS, SQUARE FOOTAGES, AND SIZES/LOCATION OFEXISTING EQUIPMENT IS APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY ALLSITE CONDITIONS PRIOR TO SUBMITTING A BID. IF CONDITIONS IN FIELD DIFFERFROM THOSE SHOWN, NOTIFY OWNER/ARCHITECT IMMEDIATELY.

2. CONTRACTOR SHALL VERIFY THE AVAILABILITY OF EXISTING FACILITIES ANDUTILITIES AT THE PROJECT SITE PRIOR TO SUBMITTING A BID. COSTSASSOCIATED WITH THE USE OF EXISTING UTILITIES SHALL BE THECONTRACTOR'S RESPONSIBILITY.

3. CONTRACTOR SHALL NOTIFY ALL UTILITIES, INCLUDING BUT NOT LIMITED TOWATER/ SEWER, ELECTRIC, GAS, TELEPHONE, HAVING SERVICE CONNECTIONSTO THE EXISTING BUILDING PRIOR TO DEMOLITION TO ENSURE THAT ANYEQUIPMENT HAS BEEN PROPERLY REMOVED, UNPLUGGED, CAPPED/PLUGGED,OR SEALED AS REQUIRED FOR DEMOLITION AND/OR NEW WORK. CONTRACTORSHALL BE RESPONSIBLE FOR THE PROPER REMOVAL, CAPPING/PLUGGING, ANDSEALING OF SERVICES REMAINING IN WORK AREAS AS REQUIRED FORDEMOLITION AND/OR NEW WORK.

4. REMOVE EXISTING ITEMS/MATERIALS TO SUBSTRATE AS INDICATED ANDREQUIRED FOR NEW WORK.

5. REMOVE DEMOLISHED MATERIALS FROM SITE DAILY AFTER ALLOWING OWNERFIRST RIGHT OF REFUSAL FOR ANY SALVAGEABLE MATERIALS.

6. COORDINATE DEMOLITION AND ITEMS TO BE REMOVED WITH NEW WORK ANDITEMS TO BE REPLACED OR RELOCATED.

7. ANY DOOR LOCK HARDWARE & CORES REMOVED SHALL BE TURNED OVER TOTHE VIRGINIA TECH KEY SHOP.

8. EXISTING ITEMS TO BE RELOCATED/REINSTALLED SHALL BE REMOVED,STORED, AND PROTECTED BY CONTRACTOR DURING DEMOLITION ACTIVITIES ASREQUIRED FOR REINSTALLATION. ITEMS DAMAGED BY CONTRACTOR SHALL BEREPLACED WITH EQUAL ITEMS APPROVED BY THE OWNER AT CONTRACTOR'SEXPENSE.

9. EXISTING ITEMS AND ADJACENT CONSTRUCTION TO REMAIN SHALL BEPROTECTED DURING DEMOLITION ACTIVITIES. ITEMS DAMAGED BY CONTRACTORSHALL BE REPLACED AT CONTRACTOR'S EXPENSE.

10. PATCH AND REPAIR ANY DAMAGED EXISTING SURFACES TO REMAIN WITHSIMILAR MATERIALS AS REQUIRED TO MATCH NEW WORK.

11. CONTRACTOR SHALL PROVIDE ADEQUATE BRACING OF STRUCTURALMEMBERS AND EXISTING/TEMPORARY STRUCTURES, AND PROVIDE ADDITIONALSHORING DURING DEMOLITION OF EXISTING WALLS, ETC. AS REQUIRED FOR THEDURATION OF THE PROJECT.

12. NO EXISTING STRUCTURAL MEMBERS ARE TO BE CUT, PENETRATED, OROTHERWISE ALTERED WITHOUT PRIOR WRITTEN APPROVAL OFARCHITECT/ENGINEER.

13. THE OWNER SHALL BE RESPONSIBLE FOR THE RELOCATION AND STORAGEOF NON-FIXED EQUIPMENT AND FURNISHINGS OF THEIR CHOOSING PRIOR TOTHE START OF WORK, UNLESS OTHERWISE INDICATED. CONTRACTOR SHALLREMOVE ANY REMAINING ITEMS AS REQ'D. TO ACCOMMODATE THE WORK.

14. THE BUILDING WILL BE IN USE FOR THE DURATION OF THE PROJECT.CONTRACTOR IS RESPONSIBLE FOE THE COORDINATION OF WORK WITHOWNER'S ACTIVITIES AND OTHER TRADES INVOLVED WITH WORK AT THEPROJECT SITE. DISRUPTIVE ACTIVITIES TO BE COORDINATED WITH VIRGINIATECH PROJECT MANAGER.

15. CONTRACTOR TO PROVIDE A RATED TEMPORARY DUST PARTITION TO LIMITDUST & DIRT MIGRATION TO AREAS NOT UNDER THE CONTROL OF THECONTRACTOR. COORDINATE FINAL PARTITION LOCATIONS W/ ARCHITECT &OWNER. SEAL ANY EXISTING DOOR NOT IN SCOPE OF WORK LOCATED WITHINVESTIBULE OR ADJACENT TO VESTIBULE TO MINIMIZE DUST INFILTRATION.- 3 5/8" 20GA. MTL. WALLS WITH 5/8" TYPE X GYP. BD. AND TAPED JOINTS ONEACH SIDE- DO NOT ATTACH TEMPORARY WALLS TO FLOOR OR CEILING- CONTRACTOR SHALL REPAIR ANY DAMAGE DUE TO DUST PARTITION WALL TOSURROUNDING EXIST. SURFACES AND FINISHES TO MATCH EXISTING ADJACENTSURFACES.- DOORS TO BE 3' - 0" WIDTH W/ SELF CLOSING DEVICES.

16. CONTRACTOR SHALL PROVIDE AND MAINTAIN CLEAR PATHS OF EGRESS FORTHE DURATION OF THE WORK.

17. ANY REQUIRED MECHANICAL, ELECTRICAL, AND PLUMBING DEMOLITION TOBE PERFORMED IN, OR AFFECTING THE USE OF, ADJACENT SPACES IN THEBUILDING SHALL BE COORDINATED WITH THE OWNER PRIOR TO THE START OFWORK. A MINIMUM OF FIVE (5) DAYS NOTICE IS REQUIRED PRIOR TO ANY UTILITYSHUTDOWN.

18. MAINTAIN WORKING CONDITION OF ANY EXISTING EMERGENCY & FIRE ALARMSYSTEMS AND COMPONENTS FOR THE DURATION OF THE WORK.

19. MAINTAIN ANY EXISTING FIRE RESISTANCE RATINGS OF STRUCTURALELEMENTS AND FIRE SEPARATION ASSEMBLY RATINGS INDICATED BETWEENNEW WORK AND EXISTING AREAS AND OCCUPANCIES FOR THE DURATION OFTHE PROJECT.

20. ALL ROOMS & AREAS ADJOINING WORK AREA TO BE PROTECTED DURINGDEMOLITION WORK. CONTRACTOR RESPONSIBLE TO REPAIR, REPLACE ANDRESTORE ANY DAMAGE RESULTING FROM WORK TO THE SATISFACTION OFOWNER.

DEMOLITION

GENERAL NOTES14. ALL WORK THAT REQUIRES DISABLING OF FIRE AND OTHER EMERGENCY SYSTEMSSHALL BE COORDINATED THROUGH THE VIRGINIA TECH PROJECT MANAGER AND ALLRESPECTIVE VIRGINIA TECH DEPARTMENTS HAVING JURISDICTION PRIOR TOCOMMENCING. CONTRACTOR SHALL PROVIDE FIRE ALARM SYSTEM MODIFICATIONSAND FINAL TESTING, INCLUDING VERIFICATION OF THE FINAL CONNECTION ANDINTERACTIONS WITH THE EXISTING EMERGENCY AND FIRE SUPPRESSION SYSTEMSAND DEVICES. FINAL TESTING SHALL BE PROVIDED & COORDINATED BY CONTRACTORAND OBSERVED BY THE DEPUTY STATE FIRE MARSHALL & VIRGINIA TECH UNIVERSITYBUILDING OFFICIAL.

15. MAINTAIN ANY EXISTING FIRE RESISTANCE RATINGS OF STRUCTURAL ELEMENTSAND FIRE SEPARATION ASSEMBLY RATINGS INDICATED BETWEEN NEW WORK ANDEXISTING AREAS AND OCCUPANCIES FOR THE DURATION OF THE PROJECT.

16. IF A CONFLICT BETWEEN CONSTRUCTION DOCUMENTS, CODE REQUIREMENTS,AND/OR MANUFACTURER'S DATA SHOULD ARISE, THE MORE STRINGENT SHALL PREVAIL.

17. CONTRACTOR SHALL PROVIDE ADEQUATE BRACING OF STRUCTURAL MEMBERS ANDEXISTING & TEMPORARY STRUCTURES AS REQUIRED FOR THE DURATION OF THE WORK.IF CONDITIONS IN FIELD DIFFER FROM THOSE SHOWN, NOTIFY ARCHITECT/ENGINEERIMMEDIATELY.

18. CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEANUP AND REMOVAL OFDEBRIS FROM SITE.

19. THE CONTRACTOR SHALL COMPLY WITH "VIRGINIA TECH'S SAFETY REQUIREMENTSFOR CONTRACTORS AND SUBCONTRACTORS" PROGRAM WHICH IS INCORPORATEDHEREIN BY REFERENCE. A COPY OF THIS PROGRAM IS AVAILABLE FROM THE OWNEROR ENVIRONMENTAL, HEALTH AND SAFETY SERVICES AND MAY BE DOWNLOADEDFROM WWW.EHSS.VT.EDU.

20. CONTRACTOR SHALL ENFORCE THE USE OF PERSONAL PROTECTIVE EQUIPMENT ASREQUIRED BY OSHA FOR INDUSTRIAL HIGH NOISE AREAS.

21. CONTRACTOR'S PERSONNEL SHALL CONDUCT THEMSELVES PROPERLY & MAINTAINPROPER ATTIRE AT ALL TIMES.

22. NO ASBESTOS CONTAINING MATERIALS SHALL BE USED IN THE COURSE OF THISWORK.

23. CONTRACTOR SHALL PROTECT COMPLETED WORK FROM DAMAGE FROM ADJACENTACTIVITIES OR INCLEMENT WEATHER AT ALL TIMES. ITEMS DAMAGED BY CONTRACTORSHALL BE REPLACED AT CONTRACTOR'S EXPENSE.

24 ALL ROOMS & AREAS ADJOINING WORK AREA TO BE PROTECTED DURINGDEMOLITION WORK. CONTRACTOR RESPONSIBLE TO REPAIR, REPLACE AND RESTOREANY DAMAGE RESULTING FROM WORK TO THE SATISFACTION OF OWNER.

25. PRIOR TO ANY CORE DRILLING, CONTRACTOR SHALL PROPERLY SURVEY THEEXISTING FLOOR USING X-RAY, GPR, OR OTHER ACCEPTABLE METHOD TO LOCATEREBAR, STRUCTURAL MEMBERS, IN-SLAB UTILITIES, OR OTHER IN-SLAB OBSTRUCTIONS.ALL CORES TO BE RETAINED & PROVIDED TO THE UNIVERSITY BUILDING OFFICIAL FORINSPECTION. NOTIFY VIRGINIA TECH RENOVATIONS PROJECT MANAGER ANDUNIVERSITY BUILDING OFFICIAL IF ANY REBAR IS CUT OR DAMAGED. ANY STRUCTURALREMEDIATION REQUIRED DUE TO CONTRACTOR'S NEGLIGENCE SHALL BE PERFORMEDBY CONTRACTOR AT NO ADDITIONAL CHARGE TO VA TECH.

26. SURFACE FLATNESS FOR ALL CONCRETE SUBFLOORS IN AREAS RECEIVING NEWFLOORING: GENERAL CONTRACTOR SHALL PATCH AND REPAIR ALL CRACKS, VOIDS ANDOTHER IMPERFECTIONS WITH HIGH STRENGTH PORTLAND CEMENT BASED PATCHINGMATERIALS. THIS WORK SHALL ALSO INCLUDE REMOVAL OF HIGH SPOTS. GENERALCONTRACTOR SHALL PROVIDE A SMOOTH, FLAT, FINISH-READY CONCRETE FLOOR WITHA MAXIMUM TOLERANCE OF +/- 1/8 INCH IN A 10 FOOT RADIUS, PER ASTM F170.

27. ALL NEW & EXIST. GLAZING IN AREAS OF SCOPE OF WORK SHALL BEPROFESSIONALLY CLEANED ON ALL SIDES. CLEANLINESS OF GLAZING TO BEMAINTAINED THROUGH SUBSTANTIAL COMPLETION.

28. INSTALLATION OF METAL FRAMING & MODIFICATIONS TO FRAMING MEMBER SHALLCOMPLY WITH VUSBC SECTIONS 2210 & 2211. ALL FRAMING MEMBERS SHALL BECONTINUOUS LENGTH SINGLE MEMBERS. SPLICING SHALL BE PER ENGINEEREDSPECIFICATION & REQUIRES APPROVAL OF UNIVERSITY BUILDING OFFICIAL PRIOR TOINSTALLATION.

CLOSE OUT DOCUMENTS1. CONTRACTOR SHALL PROVIDE ONE (1) COMPREHENSIVE SET OF AS-BUILTDRAWINGS DOCUMENTING IN RED INK ALL AS-BUILT CONDITIONS. AS-BUILT DRAWINGSMARKUPS SHALL BE CLEARLY LEGIBLE ON THE ORIGINAL, UNIVERSITY BUILDINGOFFICIAL APPROVED AND STAMPED CONTRACT DOCUMENTS, AND MAINTAINED INGOOD ORDER AND GOOD CONDITION. MARKUPS TO INCLUDE ALL REPRESENTEDDISCIPLINES ON THEIR SPECIFIC SHEETS. AS-BUILT DRAWINGS TO INCLUDE, BUT NOTLIMITED TO, ALL DEVIATIONS FROM CONTRACT DOCUMENT LAYOUTS; LOCATIONS &QUANTITIES OF PIPING, UTILITIES, DEVICES, FIXTURES, ETC.; SPECIFICATIONS, ETC.;RATED ASSEMBLIES, FIRE DAMPERS, ETC.; RFI'S, CHANGE ORDERS, ETC.

2. CONTRACTOR TO PROVIDE OWNER WITH THREE (3) COPIES OF ALL REQUIREDOPERATION AND MAINTENANCE MANUALS PRIOR TO PROJECT COMPLETION. MANUALSTO BE IN HARD BACKED, VINYL, 3-RING BINDERS W/ ONE INCH MINIMUM SPINE.MANUALS SHALL INCLUDE, BUT NOT LIMITED TO, ALL APPROVED SUBMITTAL ITEMS,APPROVED SHOP DRAWINGS, RFI'S W/ ANSWERS, TAB REPORTS & OTHER ITEMSAPPROPRIATE FOR A COMPREHENSIVE REFERENCE DOCUMENT FOR THE LIFE OF THEBUILDING AREA, ETC. GENERAL CONTRACTOR TO PROVIDE O&M MANUAL IN DIGITALFORMAT ON A SINGLE CD, TWO (2) COPIES, DIGITAL FORMAT SHALL BE IDENTICAL TOMANUAL FORMAT. MANUAL FORMAT TO INCLUDE :A - COVER PAGE WITH PROJECT TITLE, PROJECT NUMBER, GENERAL CONTRACTOR,DATE MANUALS PROVIDED.B - TABLE OF CONTENTS W/ CATEGORIES FOR ARCHITECTURAL, PLUMBING,MECHANICAL & ELECTRICAL ITEMS.C - TABBED SEPARATIONS FOR EACH CATEGORY. TABBED SECTIONS TO INCLUDEMANUFACTURER CUT SHEETS FOR ALL FIXTURES, DEVICES, CONTROLS, ACCESSORIES,FINISHES, ADHESIVES/MORTARS/GROUTS.

3. CONTRACTOR TO PROVIDE OWNER WITH COMPLETED CO-13 AFFIDAVIT OFPAYMENT OF CLAIMS, HECO-13.2 CERTIFICATE OF COMPLETION BY CONTRACTOR,HECO-13.2A CERTIFICATE OF PARTIAL OR SUBSTANTIAL COMPLETION BYCONTRACTOR.

4. CONTRACTOR SHALL PROVIDE ADDITIONAL ATTIC STOCK OF FINISH MATERIALS FORFUTURE USE AND ONE (1) COMPREHENSIVE ATTIC STOCK LIST AS STIPULATED BELOW.ALL ATTIC STOCK MATERIALS AND ATTIC STOCK LIST SHALL BE DELIVERED TO OWNERAT ONE TIME AND SHALL BE SIGNED BY GENERAL CONTRACTOR AND PROJECTMANAGER AT THAT TIME. ATTIC STOCK LIST SHALL INDICATE DESCRIPTIONS ANDREQUIRED QUANTITIES OF MATERIALS LISTED BELOW :A - ONE (1) GAL OF EACH PAINT, STAIN, & POLYURETHANE TYPE, COLOR, & FINISH.B - FULL TILES OF CERAMIC & PORCELAIN FINISHES EQUAL TO AT LEAST FIVE PERCENT(5%) OF EACH TYPE, SIZE, & COLOR, BUT NOT LESS THAN FIVE (5) FULL TILES OF EACHTYPE, SIZE, & COLOR.C - FULL TILES OF FLOORING FINISHES EQUAL TO AT LEAST FIVE PERCENT (5%) OFEACH TYPE, SIZE & COLOR, BUT NOT LESS THAN FIVE (5) FULL TILES OF EACH TYPE,SIZE, & COLOR.D - FULL WIDTH OF ROLLED GOODS OF FLOORING FINISHES EQUAL TO AT LEAST FIVEPERCENT (5%) OF EACH TYPE, SIZE & COLOR, BUT NOT LESS THAN SIX FEET(6 FT.) IN LENGTH OF FULL WIDTH OF EACH ROLLED GOOD.E - FIVE PERCENT (5%) MINIMUM OF EACH RUBBER BASE SIZE, TYPE & COLOR, BUTNOT LESS THAN TEN (10) LINEAR FEET OF EACH SIZE, TYPE & COLOR.F - FULL CEILING PANELS EQUAL TO AT LEAST FIVE PERCENT (5%) OF EACH TYPE, SIZE& COLOR, BUT NOT LESS THAN FIVE (5) FULL PANELS OF EACH TYPE, SIZE & COLOR.

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

T2

GE

NE

RA

L N

OT

ES

+IN

FO

RM

AT

ION

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

Page 3: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

LEGEND

AREA OF WORK

2 HR FIRE RESISTANCE RATING

MAX. EGRESS OCCUPANT LOAD#

EGRESS PATH OF TRAVEL

250

250

CR-5B

5000

5002

5014

5008

5008A5008B5016B

5012

5016

5017

5026

5028

5028A5028B

50365038

E05

E01CR-5A

CR-5B

CR-5C

E10

E08

E09 E07

E11E06

E02E03

5008C

5034 5026

5022

5022A

5014A

5007

5003

5029 5029B 50055005B

UPDN

DN

TRAVEL DISTANCE = 124 FT.TRAVEL DISTANCE = 111 FT.

TRAVEL DISTANCE = 86 FT.

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

LS1

LI F

E S

AF

ET

Y P

LA

N +

BU

ILD

ING

CO

DE

DA

TA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

BUILDING & PROJECT CODE DATA

REFERENCE CODES: 2012 VIRGINIA REHABILITATION CODE, (VRC, VOLUME II OF THE VUSBC), WORK AREA COMPLIANCE METHOD,LEVEL TWO RENOVATION

2012 INTERNATIONAL EXISTING BUILDING CODE (IEBC)2012 INTERNATIONAL BUILDING CODE (IBC), AS REFERENCED IN 2012 VRC

BUILDING NAME: DERRING HALLBUILDING NUMBER: 115SCOPE OF WORK: RENOVATION OF LABS ON 5TH FLOOR, LEVEL 2 RENOVATIONBUILDING OCCUPANCY USE GROUP: BOCCUPANT LOAD SERVED, AREA OF WORK: B USE - LABORATORIES - OCC. = 50 S.F. PER OCCUPANT

LAB 5005 + 5005B = 21 OCC. @ 1030 S.F.LAB 5014 = 13 OCC. @ 630 S.F.LAB 5016 = 18 OCC. @ 892 S.F.LAB 5026 = 0 OCC. @ 170 S.F. (NOT OCCUPIABLE SPACE)LAB 5034 = 6 OCC. @ 262 S.F.LAB 5029 = 22 OCC. @ 1095 S.F.

SEPARATED MIXED USE: NON SEPARATED MIXED USECONSTRUCTION TYPE: IBBUILDING AREA, GROSS: 207,929 SQ. FT. (ALL FLOORS)FLOOR AREA, GROSS: 51,745 SQ. FT. (5TH FLOOR)PROJECT AREA, GROSS: 4082 SQ. FT. (COMBINED AREA FOR LABS LISTED ABOVE)FIRE SUPPRESSION: NOFIRE ALARMS: YES

REFERENCE CODES: VIRGINIA FIRE SAFETY REGULATIONS (VFSR), AS ADOPTED BY THE STATE BOARD OF HOUSING AND COMMUNITYDEVELOPMENT, EFFECTIVE JULY 16, 1982, PART ONE BUILDINGS CONSTRUCTED BETWEEN APRIL 12, 1949 ANDSEPTEMBER 1, 1973.

ORIGINAL BUILDING CONSTRUCTED - BLDG. 155 : 1966 (APPROXIMATELY)OCCUPANCY CLASS: GROUP A BUILDING, SECTION 300-1CONSTRUCTION TYPE: SEMI-FIREPROOF, SECTION 301-1 (C)BUILDING HEIGHT LIMITS - TABLE 2 SEMI-FIREPROOF, GROUP A BLDG. - 6 STORIESFLOOR AREA, GROSS: 51,745 SQ. FT.OCCUPANT LOAD, FLOOR: 1293 @ 40 SQ. FT GROSS (SECTION 401-3)

BUILDING DATA

REQUIRED FIRE RESISTANCE RATINGS OF STRUCTURAL ELEMENTS - TABLE 1 (SEMI-FIREPROOF) :EXTERIOR BEARING WALLS 3 HOURSEXTERIOR NON-BEARING WALLS 0 HOURS 30 FT. OR MORE FROM LOT LINE OR OTHER STRUCTUREINTERIOR BEARING WALLS & PARTITIONS 3 HOURSCOLUMNS, GIRDERS, BEAMS, TRUSSES 3 HOURS SUPPORTING MORE THAN ONE FLOOR CONSTRUCTIONFLOOR CONSTRUCTION 2 HOURSROOF CONSTRUCTION, ROOF TRUSSES, ROOF FRAMING 1.5 HOURS HEIGHT TO LOWER CHORD AT HIGHEST FLOOR IS 15 FT. OR LESS

INTERIOR EXIT STAIRWAYS - SECTION 404ENCLOSURE - SECTION 404-2(B) 2 HOURS INTERIOR STAIRWAYS IN UNSPRINKLERED BUILDINGS FOUR STORIES OR MORE IN HEIGHT

NOTE: FIRE PARTITIONS, RATINGS, & SHAFTWAYS ARE BASED ON REQUIREMENTS OF VFSR, AT THE TIME THE BUILDING WAS CONSTRUCTED AND HISTORICALDOCUMENTS AVAILABLE. THESE AREAS HAVE NOT BEEN SURVEYED FOR COMPLIANCE WITH THE VFSR, AND ARE NOT IN THE CONTRACTORS SCOPE OF WORK.

LIFE SAFETY PLAN

PROJECT DATA

N

THE INTENT OF THIS PROJECT IS TO RENOVATE EXISTING, NON-ADAAG COMPLIANT TEACHING LAB SPACES #5010, 5014, 5016, AND 5029 TO PROVIDE ADAAG COMPLIANTRESEARCH LABS. ROOMS # 5024, 5024B, AND 5036 WILL BE RENOVATED AS ADAAG COMPLIANT SUPPORT SPACES TO THE RESEARCH LABS. THE SCOPE OF WORK WILLINCLUDE NEW FINISHES; NEW AND MODIFIED EXISTING CASEWORK AND PLUMBING FIXTURES; NEW LIGHTING; NEW POWER; NEW AND MODIFIED HVAC WORK. SOME MINORRENOVATION WORK WILL OCCUR IN EXISTING RESEARCH LAB 5005 TO PROVIDE ADAAG COMPLIANT COUNTERS, BUT THE REMAINDER OF THIS SPACE WILL REMAIN AS IS.

DESIGN NARRATIVE

ADAAG PROVISIONS :ALL RENOVATED LABS AND SPACES TO RECEIVE THE FOLLOWING ADAAG-COMPLIANT FEATURES, WHERE NONE CURRENTLY EXIST :1. DOOR MANEUVERING CLEARANCES TO THE GREATEST POSSIBLE EXTENT2. DOOR LEVER HARDWARE3. FRONT APPROACH WORKSTATIONS - SOME WITH SINKS, FAUCETS, AND EYE WASH FIXTURES.4. LIGHTING & HVAC CONTROLS

1" = 10'-0"LS1LS1

1 LIFE SAFETY PLAN - FIFTH FLOOR

DERRING HALL - FIFTH FLOOR

ACCESSIBILITY VRC SECTION 705.2 EXISTING, ACCESSIBLE ROUTE TO PRIMARY FUNCTION TO REMAIN

MEANS OF EGRESS VRC SECTION 805.1 EXISTING, ACCESSIBLE MEANS OF EGRESS TO REMAIN

DOOR SWING SECTION 805.4.2 NOT REQ'D. DOOR SWING IN DIRECTION OF EXIT TRAVEL FOR OCC. > 50

ACTUAL ALLOWABLE OCCUPANCY LOAD

LABORATORY VUSBC TABLE 1004.1.2 50 SQ. FT. OF FLOOR AREA PER OCCUPANT - NET, VOCATIONAL USE

TRAVEL DISTANCE ALLOWED VUSBC TABLE 1016.2 200 FEET MAXIMUM: B USE GROUP WITHOUT SPRINKLER SYSTEM

ACTUAL TRAVEL DISTANCE VARIES SEE LIFE SAFETY PLAN, THIS SHEET

ACCESSIBLE ROUTE - EMPLOYEE WORK AREAS VUSBC SECTION 1104.3.1 EXC. 1 COMMON USE CIRCULATION PATHS, LOCATED IN EMPLOYEE WORKAREAS LESS THAN 1000 S.F. IN SIZE AND DEFINED BY PERMANENTLYINSTALLED PARTITIONS, COUNTERS, CASEWORK OR FURNISHINGS,SHALL NOT BE REQ'D. TO BE ACCESSIBLE ROUTES.

1. PER VFSR REQUIREMENTS AT THE TIME OF CONSTRUCTION OF THE BUILDING, CORRIDORS CR-5A & CR-5B ON THE FIFTH FLOOR ARE NOT REQUIRED TOHAVE RATED PARTITIONS, EXCEPT WHERE SHOWN.

CODE DATA NOTE :

INFORMATION REMOVED

50055029B5029

5034 50265014

5016

5016B

REVISIONS DATE

Page 4: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

OFFICE

5081C

5081B

5106

5103

5098

COPY RM.

OFFICE

5099

OFFICE

5095

5090

OFFICE

5091

WORK RM.

5083 5079

E24

E26

5077

E21 WOMEN MEN E19

CL

E17

E20 E18

E22

E23

E14

5069

E15COMP.

LAB

5066

5066A

E13

WOMENE10 MEN E8

E9 E7

CL

E6

E3E11

E2

5005A

E12

ECON. GEOL. LAB

5044

HIGH

PRESSURE LAB

5056HIGH TEMP. LAB

5068

OFFICE

5070C

5070A5100A

5092L

LAB

5046

5070B

5070D

OFFICE

LAB LAB

SEC.

SEC.

LAB

LAB

LAB

OFFICE OFFICE

5064A 5060A

SEC.

5051

PREP. RM

LAB

5005B

5042

OFFICE

OFFICE

5100C

X-RAY &

CRYSTALLOG.

LAB

5050B

5065A5065B

5061A

5016A

5034A

5026A

5017B

OFFICE

5000

OFFICE

5002

LAB

5003

RESEARCH

LAB

5007

RESEARCH

LAB

5010

RESEARCH

LAB

5014

5010A5014A

RESEARCH LAB

5008

OFFICE

5008A

OFFICE

5008B

OFFICE

5016B

OFFICE

5012

RESEARCH LAB

5016

COLDROOM

5016C

RESEARCH LAB

5017

5017A

LAB

5022

LAB

5022A

LAB

5026

DK RM

5026B

AUTO-

CLAVES

5026D

RESEARCH LAB

5028

OFFICE

5028A

OFFICE

5028B

LAB

5029

LAB

5029A

LAB

5029B

OFFICE

5029C

OFFICE

5029D

LAB

5034

OFF.

5036

OFF.

5038OFFICE

5064

LAB

5060

HEAD

SECRETARY

5088

DEPT.

HEAD

OFFICE

5088A

LAB

5100

5100B

SEC.

5100D

READING

ROOM

5086

5086A

OFFICE

5107

OFFICE

5040

OFFICE

5041A

OFFICE

5041

GRADUATE

OFFICES

5043

OFFICE

5045

LAB

5050

OFFICE

5057A

OFFICE

5057

GEOCHEM

LAB

5061

LAB

5067

LAB

5067A

HYDROTHERMAL LAB

5065

STAIR

E25

DN

LAB

5093K

LAB

Q

LAB

P

LAB

NOFFICE

5105

LAB

5093L

LAB

R

OFFICE

5093JOFFICE

5093H

OFFICE

5093G

OFFICE

5093A

OFFICE

5093B

LAB

5093COFFICE

5093D

OFFICE

5093E

OFFICE

5093F

HALL

5093

LAB

5081

OFFICE

OFFICE

LAB

J

LAB

K

STAIR

E16

UP

A

STAIRS

E5

UP

RES.

5008CSTAIRS

E1

DNCORRIDOR

CR-5A

CORRIDOR

CR-5A

LOBBY

CR-5B

CORRIDOR

CR-5C

CORRIDOR

CR-5D

LOBBY

CR-5E

CORRIDOR

CR-5F

CORRIDOR

CR-5F

OFFICE

5049

COMP.

ROOM

5053

LAB

5042A

OFFICE

5044A

OFFICE

5048

LAB

5066B

RESEARCH

LAB

5005

SEC.

5082

OFFICE

5102

CONF.

ROOM

5109

OFFICE

5081A

OFFICE

5094

PSYCHO-

PHYSIOLOGY

CLASS-LAB

5092

HALL

5092M

M

LAB

5076A

LAB

5076F

LAB

5076E5076B

LAB

H

J

OFFICE

5076C

OFFICE

5076D

5076

5076G

COPY

5078

OFFICE

5071

FIFTH FLOOR

EXIST. TO REMAIN

EXIST. TO BE DEMOLISHED

AREA OF WORK

2 HR FIRE RESISTANCE RATING

EXIST. FIXTURES TO BE DEMOLISHED- SEE ELECTRICAL

EXIST. FIXTURES TO REMAIN- SEE ELECTRICAL

LEGEND:

EXIST. FIXTURES TO BE DEMOLISHED- SEE ELECTRICAL

EXIST. FIXTURES TO REMAIN- SEE ELECTRICAL

LAB

5026

LAB

5026

ICE

E03

LAB

5014

LAB

5016

OFFICE

5016B

OFFICE

5014A

LAB

5029B

LAB

5005

LAB

5005B

LAB

5010

LAB

5029

LAB

5034

CORRIDOR

CR-5A

CORRIDOR

CR-5B

LAB

5017

192

142

10

142

10

142

10

142

10

192

142

10

142

10

142

10

10

10 9

9

9

9 9

9

9

1 94

12

1

14

5026B

15

11

ICE

E03

LAB

5007

CORRIDOR

CR-5A

LAB

5000

JANITOR

E06

CORRIDOR

CR-5C

LAB

5017

LAB

5005

LAB

5005B

LAB

5029B

LAB

5029

LAB

5034

LAB

5026

LAB

5026

LAB

5014

LAB

5010

OFFICE

5014A

LAB

5016

OFFICE

5016B

HO

OD

HO

OD

HO

OD

HOODHOOD

CORRIDOR

CR-5B

3 5 3 5

3 5

3 5

3 5

3

5

3 5

3 5 3 5

3 5

3 5

6 6

6

6 6

66

66

6

6

7 7

7 7

7

7

7

7

7

7

88

8

8

8 8

8

7

11

2' -

8"

13

3

3

3

3

7

16

17

18

18 18

17

18

18

18 18

19

1918

17 19

17 19 17 19

WORK AREAS (TYP.)DERRING HALL - FIFTH FLOOR

N

KEY PLAN

N

N

0 16 24 328

1/8" = 1' - 0"

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A1.1

DE

MO

PLA

NS

+ N

OT

ES

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

N

DEMO WORK KEYED NOTES :1. DEMO EXIST. LIGHT FIXTURES, HANGERS, ETC. PATCH &PREP FOR NEW WORK.- SEE ELECTRICAL

2. DEMO EXIST. EXIT SIGNS, HANGERS, ETC. PATCH & PREPFOR NEW WORK.- SEE ELECTRICAL

3. DEMO EXIST. FLOORING & RUBBER BASE. REMOVE ALLADHESIVES, ETC. PATCH & PREP FOR NEW WORK.

4. DEMO EXIST. GRID & ACT, INCLUDING ALL HANGERS, ETC.PATCH & PREP FOR NEW WORK.

5. DEMO EXIST. SURFACE RACEWAY, BOXES, AND DEVICES.PATCH & PREP FOR NEW WORK.- SEE ELECTRICAL

6. DEMO EXIST. DOORS, HARDWARE & LOCKSETS. RETURNLOCKSET CORES TO OWNER. EXIST. FRAMES TO REMAIN.PREP FOR NEW WORK.

7. REMOVE EXIST. BASE & WALL CASEWORK. PATCH & PREPFOR NEW WORK.- REMOVED CASEWORK TO BE STORED FOR POSSIBLE RE-USE. CONTRACTOR TO USE CARE DURING DEMO.- SEE PLUMBING

8. DEMO EXIST. COUNTERTOPS & ANY EXIST. SINKS. EXIST.BASE CASEWORK TO REMAIN. PATCH & PREP FOR NEWWORK.- SEE PLUMBING

9. DEMO EXIST. GRD'S. PREP FOR NEW WORK.- SEE ELECTRICAL - HVAC

10. MODIFY EXIST. HVAC SYSTEMS AS REQ'D. FOR NEW WORK.- SEE MECHANICAL

DEMO WORK GENERAL NOTES :1. CONTRACTOR SHALL PROTECT ALL ADJACENT AREAS TODEMO WORK, INCLUDING THOSE ABOVE OR BELOW AREAS OFWORK. DAMAGE RESULTING FROM DEMO WORK TO BEREPAIRED OR REPLACED AT SOLE COST TO CONTRACTOR & TOSATISFACTION OF OWNER.

2. COORDINATE W/ CNS FOR ALL DEMOED, RELOCATED, ETC.CNS WORK PRIOR TO CONDUCTING WORK- SEE ELECTRICAL

3. CONTRACTOR SHALL STORE & PROTECT ALL ITEMS TO BEREFINISHED, REINSTALLED, ETC. ANY NEW DAMAGE TO ITEMS INCONTRACTOR'S CARE TO BE REPAIRED TO OWNER'SSATISFACTION, INCLUDING POSSIBLE REPLACEMENT OF ITEM.

4. PATCH, FILL, REPAIR ALL EXISTING HOLES, DEFICITS, ETC. INALL EXPOSED SURFACES WITH SIMILAR MATERIALS. ALL WORKTO BE SIMILAR IN TEXTURE & FINISH TO ADJACENT SURFACESTO GREATEST POSSIBLE EXTENT FOR A UNIFORM FINISH. (TYP.)

X

1/8" = 1'-0"A1.1A1.1

2 REFLECTED CEILING PLAN - DEMO 1/8" = 1'-0"A1.1A1.1

1 DEMO PLAN

11. DEMO EXIST. WALK-IN COOLER & ALL ASSOCIATEDACCESSORIES, UTILITIES, FLOORING, BULKHEAD VENTILATIONSCREENS, ETC. PATCH AFFECTED SURFACES TO MATCHADJ. SURFACES & PREP FOR NEW WORK.- SEE ELECTRICAL

12. DEMO EXIST. STAND ALONE HVAC UNIT IN ITS ENTIRETY.REPAIR ROOF PENETRATION AS REQ'D. TO MATCH ADJ.SURFACES, PROVIDE A WEATHERTIGHT REPAIR & MAINTAINCURRENT ROOF WARRANTIES. (TYP.)- SEE MECHANICAL & ELECTRICAL

13. DEMO EXIST. CMU WALL & PARTIAL WALL AS REQ'D. TOACCOMMODATE NEW WORK. PREP EXIST. WALL TO REMAINTO RECEIVE NEW BULLNOSE CMU. (TYP.)

14. DEMO EXIST. BULKHEAD IN ITS ENTIRETY. PATCH & PREPFOR NEW WORK (TYP.)

15. DEMO EXISTING WALL A/C UNIT IN ITS ENTIRETY. PATCH &PREP AFFECTED SURFACES AND WINDOW FRAME AS REQ'D.TO MATCH ADJ. SURFACES. PREP FOR NEW WORK.

16. REMOVE EXISTING EMERGENCY SHOWER/EYE WASHSTATION FOR RE-USE.- SEE PLUMBING

17. DEMO EXISTING DRYING RACKS, UNLESS NOTEDOTHERWISE. PATCH & PREP FOR NEW WORK (TYP.)

18. DEMO EXISTING PAPER TOWEL HOLDERS. PATCH & PREPFOR NEW WORK (TYP.)

19. DEMO EXISTING CORKBOARDS & SHELVING. RETURNCORKBOARDS TO OWNER FOR RIGHT OF FIRST REFUSAL.PATCH SURFACES TO MATCH ADJACENT SURFACES & PREPFOR NEW WORK. (TYP.)

REVISIONS DATE

Page 5: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

EXISTING TO REMAIN

LEGEND:

2 HR FIRE RESISTANCE RATING

AREAS OF WORK

OWNER PROVIDED LAB EQUIPMENT- SEE EQUIPMENT SCHEDULE

ADAAG CLEAR FLOOR AREAS- WORK STATIONS + TURNING CIRCLE

X

ADAAG MANEUVERING CLEARANCE,X = INCHES

X"

X"

LAB

5026

ICE

E03

LAB

5005

LAB

5029B

CORR

CR-5B

LAB

5016

OFFICE

5016B

LAB

5034

LAB

5014

LAB

5005B

LAB

5029

CORR

CR-5A

2

A1.2 A1.3

3

A1.2 A1.3

1

A1.2 A1.3

3

A1.2 A1.2

2

A1.2 A1.2

12

17

13

13

20

LAB

5014

OFFICE

5014A

2' - 7" 8' - 5"

EX

IST

.4

' - 6

1/4

"E

XIS

T.

2' -

7"

16

' - 6

" (E

XIS

T.)

CORR

CR-5A

CORR

CR-5B

23

' - 1

1/4

" (E

XIS

T.)

18

5014

5014-1

5014-3 5014-2

5014A

(EX

IST

.)

6' -

1 3

/4"

2' -

8"

8' - 6"

EQ

.E

Q.

2"

NEW COUNTERTOP-FULL WIDTH

3

A3.1A1.2

SUPPORT BRACKETS,BELOW- SEE CAB. NOTES

10' - 11 3/4" (EXIST.)

31' - 6" (EXIST.)

1

A3.1A1.2

16

8

17

17

17

1

1

4

2

A3.1A1.2

2

2

3

7

7

7 7

12

54

48

115

18

18 1918

54

48

48

48

EXIST.CONDITION

48

48

54

48

48

48

EXIST.CONDITION

LAB

5005B

12

12

14

14

16

15

13

LAB

5005

CORR

CR-5B

LAB

5017

EXIST.HOOD

6' - 0" 15' - 0"

3

A3.1A1.2SUPPORT BRACKETS,BELOW- SEE CABINETRYNOTES

EXIST.HOOD 2" EQ. EQ. EQ. 2"

27' - 5" (EXIST.)7' - 6" (EXIST.)

30

' - 1

1 3

/4"

(EX

IST

.)

4

EXIST.HOOD

EXIST. TOREMAIN

EXIST. TOREMAIN

EXIST. TOREMAIN

EX

IST

. T

O R

EM

AIN

5 12

5

REFURBISH EXIST.EMERGENCY SHOWERTO REMAIN- SEE PLUMBING

54

48

48

48

54

48

48

48

54

48

48

48

EXIST. CONDITION EXIST. CONDITION

EX

IST

. C

ON

DIT

ION

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A1.2

NE

W W

OR

K -

PLA

NS

,P

AR

TIA

L P

LA

NS

, N

OT

ES

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

N

1/16" = 1'-0"A1.2A1.2

1 NEW WORK - PLAN

1/4" = 1'-0"A1.2A1.2A1.2

3 NEW WORK - PARTIAL PLAN - LAB 5014

N

1/4" = 1'-0"A1.2A1.2A1.2

2 NEW WORK - PARTIAL PLAN - LAB 5005

0 8 12 164

1/4" = 1' - 0"

N

NEW WORK - GENERAL NOTES

1. CONTRACTOR SHALL PROTECT ADJ. SPACES,INCLUDING ABV. & BELOW AREAS OF WORK.CONTRACTOR SHALL REPAIR ALL DAMAGE RESULTINGFROM NEW WORK TO SATISFACTION OF OWNER & ATCONTRACTOR'S SOLE EXPENSE.

2. MODIFY EXIST. STRUCTURE AS REQ'D. TOACCOMMODATE NEW WORK. PATCH, REPAIR & FINISHWITH SIMILAR MATERIALS TO MATCH ADJ. SURFACES &STRUCTURE.

3. CONTRACTOR SHALL PROTECT ALL EXIST. SURFACES &FINISHES FROM DAMAGE DURING NEW WORK. DAMAGEDURING NEW WORK SHALL BE REPAIRED & REPLACED TOMATCH EXIST. AT CONTRACTOR'S EXPENSE & TOTHE SATISFACTION OF THE OWNER.

4. ALL GLAZING SHALL BE PROFESSIONALLY CLEANED ONBOTH SIDES AT SUBSTANTIAL COMPLETION.

NOTE :CONTRACTOR TO FIELD VERIFY EXIST. STRUCTURALCONDITIONS AT LOCATIONS SHOWN FOR NEWPENETRATIONS. CONTRACTOR TO VERIFY EXIST.CONDITIONS W/ GROUND PENETRATING RADAR (GPR) ORSIMILAR PRIOR TO WORK REQUIRING PENETRATIONS.- CONTACT ARCHITECT IMMEDIATELY IF EXIST.CONDITIONS WILL NOT ACCOMMODATE THE DRAWINGS.

NEW WORK - KEYED NOTES

1. PROVIDE & INSTALL NEW COUNTERTOPS ON EXIST.CABINETRY TO REMAIN. (TYP.)- SEE CABINETRY NOTES

2. PROVIDE & INSTALL NEW SINK & FIXTURES- SEE PLUMBING

3. PROVIDE & INSTALL NEW REAGENT SHELVING- SEE CABINETRY NOTES

4. PROVIDE & INSTALL NEW WORKSTATIONS (TYP.)- SEE CASEWORK NOTES & DETAILS

5. PROVIDE & INSTALL NEW FLOORING & BASE.- SEE FINISH SCHEDULE

6. PROVIDE & INSTALL NEW GRID & ACT- SEE FINISH SCHEDULE

7. PROVIDE & INSTALL NEW DOOR & HDWR IN EXIST.FRAME TO REMAIN- SEE DOOR SCHEDULE

8. RELOCATE DEMOED LAUNDRY SINK FROMLAB 5036 & PROVIDE ALL HOOKUPS. (TYP.)- SEE PLUMBING

9. INSTALL OWNER PROVIDED CASEWORK & MAKEFINAL HOOK UPS- SEE ELECTRICAL & PLUMBING

10. REPAIR & REPLACE GLAZING AND EXIST. WINDOWFRAME @ DEMOED A/C UNIT- ALL WORK TO MATCH ADJACENT SURFACES INAPPEARANCE & MATERIAL

11. REFINISH EXIST. WOOD CASEWORK TO REMAIN.RE-USE APPROVED COMPONENTS SALVAGED DURINGDEMO WORK. CONTRACTOR TO PROVIDE NEW IFSALVAGED IS NOT USEABLE. COORDINATE W/ARCHITECT DURING DEMOLITION.- REPAIR & REFINISH SALVAGED COMPONENTS TOMATCH REFINISHED CASEWORK TO REMAIN- PROVIDE & INSTALL NEW PULLS- SEE FINISH & CABINETRY NOTES

12. CONTRACTOR TO MAKE ALL FINAL HOOKUPS TOOWNER PROVIDED EQUIPMENT- SEE PLUMBING & ELECTRICAL- SEE EQUIPMENT SCHEDULE & PLANS

13. THOROUGHLY CLEAN EXIST. HOODS TO REMAIN. ENSUREPROPER WORKING CONDITION OF ALL COMPONENTS & MAKEREMEDIES AS REQ'D.- SEE ELECTRICAL, PLUMBING & MECHANICAL

14. PROVIDE & INSTALL NEW GRD'S- SEE MECHANICAL

15. PROVIDE & INSTALL NEW LIGHT FIXTURES.- SEE ELECTRICAL

16. PROVIDE & INSTALL NEW BULLNOSE CMU AT END OFEXIST. WALL TO REMAIN. TOOTH NEW BULLNOSE CMU INTOEXIST. CMU FOR A SEAMLESS FINISHED INSTALLATION. PREPFOR NEW FINISHES.

17. INSTALL OWNER PROVIDED WORKSTATIONS (TYP.)

18. PROVIDE & INSTALL NEW PAPER TOWEL HOLDERS.COORDINATE FINAL LOCATIONS & MOUNTING HEIGHTS WITHARCHITECT.- SEE FINISH SCHEDULE

19. PROVIDE & INSTALL NEW DRYING RACKS. COORDINATEFINAL LOCATIONS & MOUNTING HEIGHTS WITH ARCHITECT.- SEE FINISH SCHEDULE

20. RELOCATE EXIST. EMERGENCY SHOWER TO NEWLOCATION- SEE PLUMBING

21. EXIST. COUNTERTOP & INTEGRAL SINK TO REMAIN. CLEANTO RESTORE ALL SURFACES TO ORIGINAL FINISHES TOGREATEST EXTENT POSSIBLE. (TYP.)

22. CLEAN & RELAMP EXIST. FIXT. TO REMAIN (TYP.)- SEE ELECTRICAL

23. PROVIDE & INSTALL NEW CEILING UTILITIES PANELS- SEE ELECTRICAL & PLUMBING

24. PROVIDE & INSTALL NEW EMERGENCY SHOWER FIXT.- SEE PLUMBINGNOT TO SCALE

REVISIONS DATE

Page 6: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

12

LAB

5016

OFFICE

5016B

13

13

1824

EXIST.HOOD

14

23

25

4' - 2" 4' - 6" 5' - 0" 4' - 6" 4' - 0"

7' -

10

1/2

" (E

XIS

T.)

7' -

10

" (E

XIS

T.)

31' - 5" (EXIST.) 15' - 6" (EXIST.)

2' -

7"

4' -

10 1

/2"

12

' - 5

1/2

"2

' - 7

"

7' -

2"

(EX

IST

.)

20

CORR

CR-5A

5016-25016-1

5016B

2

A3.1A1.2

5' - 0" 5' - 0" 8' - 0"

3

A3.1A1.2

NEW COUNTERTOP- FULL WIDTH

SUPPORTBRACKETS, BELOW- SEE DETAILS

2"

EQ

.E

Q.

EQ

.2"

12

12

' - 0

"

1

A3.1A1.2

4 1 1

1 1

33

1 21

13

2

2 2

48

48

48

48

12115

5

7 7

1918

18

54

48

48

48

EXIST.CONDITION

54

48

54

48

48

48

EX

IST

.C

ON

DIT

ION

7 2

1

1

1

1

3

1

4

5

6 7

5

810

11

9

LAB

5034

LAB

5026

11' - 5" 7' - 7 1/2"

23

' - 1

"

CORR

CR-5A

CORR

CR-5B

ICE

E03

ADAAG

4' -

3"

4

3' -

7"

3' - 3 1/4"5' - 1 3/4"

5034-1

5034-2

4

1212

2

12

5

5

21

EXIST. EMERGENCYSHOWER TO REMAIN- SEE PLUMBING

7

7

1819

54

48

48

48

EXIST.CONDITION

54

48

48

48

EXIST. CONDITION

2' -

7"

3' -

11 3

/4"

5' -

3"

6' -

6"

5' -

3"

5' -

0"

2' -

7"

5"

25

' - 5

"

12

CLR.

4' - 0"

LAB

5029B

21

2213

18

23

2' - 7" 4' - 1 3/4" 10' - 0" 4' - 1"

23' - 5 1/2" (EXIST.) 11' - 5 1/2" (EXIST.)

31

' - 1

3/4

" (E

XIS

T.)

31

' - 1

3/4

" (E

XIS

T.)

EXIST.HOOD

20

14

CORR

CR-5B

13

12

LAB

5029

1

A3.1A1.2

2

A3.1A1.2

5029B

5029-1 5029-2

1

4

9

9

9

9

9

9

2

2

1

54

48

36

48

5 12

13

10

12 5

7 7

7

18

18

18

18

19

19

19

1

54

48

48

48

EXIST. CONDITION

54

48

48

48

EXIST. CONDITION

EXISTING TO REMAIN

LEGEND:

2 HR FIRE RESISTANCE RATING

OWNER PROVIDED LAB EQUIPMENT- SEE EQUIPMENT SCHEDULE

ADAAG CLEAR FLOOR AREAS @WORK STATIONS + TURNING CIRCLE

X

ADAAG MANEUVERING CLEARANCE,X = INCHES

X"

X"

0 8 12 164

1/4" = 1' - 0"

N

NEW WORK - GENERAL NOTES

1. CONTRACTOR SHALL PROTECT ADJ. SPACES,INCLUDING ABV. & BELOW AREAS OF WORK.CONTRACTOR SHALL REPAIR ALL DAMAGE RESULTINGFROM NEW WORK TO SATISFACTION OF OWNER & ATCONTRACTOR'S SOLE EXPENSE.

2. MODIFY EXIST. STRUCTURE AS REQ'D. TOACCOMMODATE NEW WORK. PATCH, REPAIR & FINISHWITH SIMILAR MATERIALS TO MATCH ADJ. SURFACES &STRUCTURE.

3. CONTRACTOR SHALL PROTECT ALL EXIST. SURFACES &FINISHES FROM DAMAGE DURING NEW WORK. DAMAGEDURING NEW WORK SHALL BE REPAIRED & REPLACED TOMATCH EXIST. AT CONTRACTOR'S EXPENSE & TOTHE SATISFACTION OF THE OWNER.

4. ALL GLAZING SHALL BE PROFESSIONALLY CLEANED ONBOTH SIDES AT SUBSTANTIAL COMPLETION.

NOTE :CONTRACTOR TO FIELD VERIFY EXIST. STRUCTURALCONDITIONS AT LOCATIONS SHOWN FOR NEWPENETRATIONS. CONTRACTOR TO VERIFY EXIST.CONDITIONS W/ GROUND PENETRATING RADAR (GPR) ORSIMILAR PRIOR TO WORK REQUIRING PENETRATIONS.- CONTACT ARCHITECT IMMEDIATELY IF EXIST.CONDITIONS WILL NOT ACCOMMODATE THE DRAWINGS.

NEW WORK - KEYED NOTES

1. PROVIDE & INSTALL NEW COUNTERTOPS ON EXIST.CABINETRY TO REMAIN. (TYP.)- SEE CABINETRY NOTES

2. PROVIDE & INSTALL NEW SINK & FIXTURES- SEE PLUMBING

3. PROVIDE & INSTALL NEW REAGENT SHELVING- SEE CABINETRY NOTES

4. PROVIDE & INSTALL NEW WORKSTATIONS (TYP.)- SEE CASEWORK NOTES & DETAILS

5. PROVIDE & INSTALL NEW FLOORING & BASE.- SEE FINISH SCHEDULE

6. PROVIDE & INSTALL NEW GRID & ACT- SEE FINISH SCHEDULE

7. PROVIDE & INSTALL NEW DOOR & HDWR IN EXIST.FRAME TO REMAIN- SEE DOOR SCHEDULE

8. RELOCATE DEMOED LAUNDRY SINK FROMLAB 5036 & PROVIDE ALL HOOKUPS. (TYP.)- SEE PLUMBING

9. INSTALL OWNER PROVIDED CASEWORK & MAKEFINAL HOOK UPS- SEE ELECTRICAL & PLUMBING

10. REPAIR & REPLACE GLAZING AND EXIST. WINDOWFRAME @ DEMOED A/C UNIT- ALL WORK TO MATCH ADJACENT SURFACES INAPPEARANCE & MATERIAL

11. REFINISH EXIST. WOOD CASEWORK TO REMAIN.RE-USE APPROVED COMPONENTS SALVAGED DURINGDEMO WORK. CONTRACTOR TO PROVIDE NEW IFSALVAGED IS NOT USEABLE. COORDINATE W/ARCHITECT DURING DEMOLITION.- REPAIR & REFINISH SALVAGED COMPONENTS TOMATCH REFINISHED CASEWORK TO REMAIN- PROVIDE & INSTALL NEW PULLS- SEE FINISH & CABINETRY NOTES

12. CONTRACTOR TO MAKE ALL FINAL HOOKUPS TOOWNER PROVIDED EQUIPMENT- SEE PLUMBING & ELECTRICAL- SEE EQUIPMENT SCHEDULE & PLANS

1/4" = 1'-0"A1.3A1.3A1.2

1 NEW WORK - PARTIAL PLAN - LAB 5016

1/4" = 1'-0"A1.3A1.3A1.2

2

NEW WORK - PARTIAL PLAN -LAB 5026 + LAB 5034

1/4" = 1'-0"A1.3A1.3A1.2

3 NEW WORK - PARTIAL PLAN - LAB 5029

N

N

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A1.3

NE

W W

OR

K -

PA

RT

IAL P

LA

NS

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

13. THOROUGHLY CLEAN EXIST. HOODS TO REMAIN. ENSUREPROPER WORKING CONDITION OF ALL COMPONENTS & MAKEREMEDIES AS REQ'D.- SEE ELECTRICAL, PLUMBING & MECHANICAL

14. PROVIDE & INSTALL NEW GRD'S- SEE MECHANICAL

15. PROVIDE & INSTALL NEW LIGHT FIXTURES.- SEE ELECTRICAL

16. PROVIDE & INSTALL NEW BULLNOSE CMU AT END OFEXIST. WALL TO REMAIN. TOOTH NEW BULLNOSE CMU INTOEXIST. CMU FOR A SEAMLESS FINISHED INSTALLATION. PREPFOR NEW FINISHES.

17. INSTALL OWNER PROVIDED WORKSTATIONS (TYP.)

18. PROVIDE & INSTALL NEW PAPER TOWEL HOLDERS.COORDINATE FINAL LOCATIONS & MOUNTING HEIGHTS WITHARCHITECT.- SEE FINISH SCHEDULE

19. PROVIDE & INSTALL NEW DRYING RACKS. COORDINATEFINAL LOCATIONS & MOUNTING HEIGHTS WITH ARCHITECT.- SEE FINISH SCHEDULE

20. RELOCATE EXIST. EMERGENCY SHOWER TO NEWLOCATION- SEE PLUMBING

21. EXIST. COUNTERTOP & INTEGRAL SINK TO REMAIN. CLEANTO RESTORE ALL SURFACES TO ORIGINAL FINISHES TOGREATEST EXTENT POSSIBLE. (TYP.)

22. CLEAN & RELAMP EXIST. FIXT. TO REMAIN (TYP.)- SEE ELECTRICAL

23. PROVIDE & INSTALL NEW CEILING UTILITIES PANELS- SEE ELECTRICAL & PLUMBING

24. PROVIDE & INSTALL NEW EMERGENCY SHOWER FIXT.- SEE PLUMBING

REVISIONS DATE

Page 7: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

EQ. EQ.

CLR

.

3' -

0"

9' - 0"A.F.F.

EXIST.

EQ. EQ.

ALIGN

9' - 0"A.F.F. LAB

5026

LAB

5034

ICE

E03

LAB

5014

OFFICE

5014A

LAB

5016

LAB

5029

LAB

5029B

LAB

5005

LAB

5005B

LAB

5017

9' - 0"A.F.F.

CLR

.

3' -

0"

EQ. EQ.

ALIGN

9' - 0"A.F.F.

EXIST.

9' - 0"A.F.F.

EXIST.

EXIST.

EXIST.

EXIST.

CORR

CR-5A

CORR

CR-5B

CORR

CR-5B

EXIST.

4

A3.1A1.4

4

A3.1A1.4

(TYP.)

(TYP.)

NEW BULKHEAD- SEE DETAILS

NEW BULKHEAD- SEE DETAILS

EXIST.

OPEN TO DECK

OPEN TO DECK

14

22

22

22

22

6

14

6

22

EQ. EQ.

ALIGN

EQ

.E

Q.

14

15

23

15

O1 O1O1

O1

O1

O1

6

15

15

6

10

EQ.EQ.

14 156

24

24

14

23

2214

24

EQ

.E

Q.

EXISTING TO REMAIN

LIGHT FIXTURE- SEE ELECTRICAL

SUPPLY AIR DIFFUSER- SEE MECHANICAL

RETURN AIR GRILLE- SEE MECHANICAL

OCC. SENSOR & CEILING SERVICE PANEL- SEE ELECTRICAL

EMERGENCY SHOWER- SEE PLUMBING

LEGEND:

2 HR FIRE RESISTANCE RATING

NEW WORK

O1

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A1.4

NE

W W

OR

K -

RE

FLE

CT

ED

CE

I LIN

G P

LA

N

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

1/8" = 1'-0"A1.4A1.4

1 NEW WORK - REFLECTED CEILING PLAN

0 16 24 328

1/8" = 1' - 0"

N

NEW WORK - GENERAL NOTES

1. CONTRACTOR SHALL PROTECT ADJ. SPACES,INCLUDING ABV. & BELOW AREAS OF WORK.CONTRACTOR SHALL REPAIR ALL DAMAGE RESULTINGFROM NEW WORK TO SATISFACTION OF OWNER & ATCONTRACTOR'S SOLE EXPENSE.

2. MODIFY EXIST. STRUCTURE AS REQ'D. TOACCOMMODATE NEW WORK. PATCH, REPAIR & FINISHWITH SIMILAR MATERIALS TO MATCH ADJ. SURFACES &STRUCTURE.

3. CONTRACTOR SHALL PROTECT ALL EXIST. SURFACES &FINISHES FROM DAMAGE DURING NEW WORK. DAMAGEDURING NEW WORK SHALL BE REPAIRED & REPLACED TOMATCH EXIST. AT CONTRACTOR'S EXPENSE & TOTHE SATISFACTION OF THE OWNER.

4. ALL GLAZING SHALL BE PROFESSIONALLY CLEANED ONBOTH SIDES AT SUBSTANTIAL COMPLETION.

NOTE :CONTRACTOR TO FIELD VERIFY EXIST. STRUCTURALCONDITIONS AT LOCATIONS SHOWN FOR NEWPENETRATIONS. CONTRACTOR TO VERIFY EXIST.CONDITIONS W/ GROUND PENETRATING RADAR (GPR) ORSIMILAR PRIOR TO WORK REQUIRING PENETRATIONS.- CONTACT ARCHITECT IMMEDIATELY IF EXIST.CONDITIONS WILL NOT ACCOMMODATE THE DRAWINGS.

NEW WORK - KEYED NOTES

1. PROVIDE & INSTALL NEW COUNTERTOPS ON EXIST.CABINETRY TO REMAIN. (TYP.)- SEE CABINETRY NOTES

2. PROVIDE & INSTALL NEW SINK & FIXTURES- SEE PLUMBING

3. PROVIDE & INSTALL NEW REAGENT SHELVING- SEE CABINETRY NOTES

4. PROVIDE & INSTALL NEW WORKSTATIONS (TYP.)- SEE CASEWORK NOTES & DETAILS

5. PROVIDE & INSTALL NEW FLOORING & BASE.- SEE FINISH SCHEDULE

6. PROVIDE & INSTALL NEW GRID & ACT- SEE FINISH SCHEDULE

7. PROVIDE & INSTALL NEW DOOR & HDWR IN EXIST.FRAME TO REMAIN- SEE DOOR SCHEDULE

8. RELOCATE DEMOED LAUNDRY SINK FROMLAB 5036 & PROVIDE ALL HOOKUPS. (TYP.)- SEE PLUMBING

9. INSTALL OWNER PROVIDED CASEWORK & MAKEFINAL HOOK UPS- SEE ELECTRICAL & PLUMBING

10. REPAIR & REPLACE GLAZING AND EXIST. WINDOWFRAME @ DEMOED A/C UNIT- ALL WORK TO MATCH ADJACENT SURFACES INAPPEARANCE & MATERIAL

11. REFINISH EXIST. WOOD CASEWORK TO REMAIN.RE-USE APPROVED COMPONENTS SALVAGED DURINGDEMO WORK. CONTRACTOR TO PROVIDE NEW IFSALVAGED IS NOT USEABLE. COORDINATE W/ARCHITECT DURING DEMOLITION.- REPAIR & REFINISH SALVAGED COMPONENTS TOMATCH REFINISHED CASEWORK TO REMAIN- PROVIDE & INSTALL NEW PULLS- SEE FINISH & CABINETRY NOTES

12. CONTRACTOR TO MAKE ALL FINAL HOOKUPS TOOWNER PROVIDED EQUIPMENT- SEE PLUMBING & ELECTRICAL- SEE EQUIPMENT SCHEDULE & PLANS

13. THOROUGHLY CLEAN EXIST. HOODS TO REMAIN. ENSUREPROPER WORKING CONDITION OF ALL COMPONENTS & MAKEREMEDIES AS REQ'D.- SEE ELECTRICAL, PLUMBING & MECHANICAL

14. PROVIDE & INSTALL NEW GRD'S- SEE MECHANICAL

15. PROVIDE & INSTALL NEW LIGHT FIXTURES.- SEE ELECTRICAL

16. PROVIDE & INSTALL NEW BULLNOSE CMU AT END OFEXIST. WALL TO REMAIN. TOOTH NEW BULLNOSE CMU INTOEXIST. CMU FOR A SEAMLESS FINISHED INSTALLATION. PREPFOR NEW FINISHES.

17. INSTALL OWNER PROVIDED WORKSTATIONS (TYP.)

18. PROVIDE & INSTALL NEW PAPER TOWEL HOLDERS.COORDINATE FINAL LOCATIONS & MOUNTING HEIGHTS WITHARCHITECT.- SEE FINISH SCHEDULE

19. PROVIDE & INSTALL NEW DRYING RACKS. COORDINATEFINAL LOCATIONS & MOUNTING HEIGHTS WITH ARCHITECT.- SEE FINISH SCHEDULE

20. RELOCATE EXIST. EMERGENCY SHOWER TO NEWLOCATION- SEE PLUMBING

21. EXIST. COUNTERTOP & INTEGRAL SINK TO REMAIN. CLEANTO RESTORE ALL SURFACES TO ORIGINAL FINISHES TOGREATEST EXTENT POSSIBLE. (TYP.)

22. CLEAN & RELAMP EXIST. FIXT. TO REMAIN (TYP.)- SEE ELECTRICAL

23. PROVIDE & INSTALL NEW CEILING UTILITIES PANELS- SEE ELECTRICAL & PLUMBING

24. PROVIDE & INSTALL NEW EMERGENCY SHOWER FIXT.- SEE PLUMBING

REVISIONS DATE

Page 8: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

DOOR TYPES

A

4" 6"

10"

SEE DOORSCHEDULE

SE

E D

OO

R S

CH

ED

ULE

2' -

10

"

CONTRACTOR TO PROVIDE SHOP DRAWINGS.

1. MATERIALS:A. LUMBER SHALL BE PROPERLY AIR DRIED & SCIENTIFICALLY KILN-DRIED TO A MOISTURE CONTENT OF 6% TO 8%, THEN TEMPERED BEFORE FABRICATION.B. ALL PLYWOOD TO HAVE EXPOSED SURFACES W/ VENEER SPECIES AND GRAIN TO MATCH EXIST. PLYWOOD AS MANUFACTURED BY COLUMBIA FOREST PRODUCTS, ORAPPROVED EQUAL.

2. EXIST. CASEWORK TO REMAIN OR BE RELOCATED TO REFINISHED W/ STAIN FINISHES TO MATCH EXIST. NEW WOOD CASEWORK, WOOD TRIM, ETC. TO BE STAINED TO MATCHEXIST.

3. ALL CASEWORK TO RECEIVE PULLS AS MANUFACTURED BY HAFELE, ITEM NO. 117.05.620, OR SIMILAR. VERIFY FINAL STYLE, FINISH, AND LENGTHS W/ ARCHITECT. FINISHES TOBE DETERMINED BY ARCHITECT FROM FULL RANGE OF MANUFACTURER'S OPTIONS. ALL VERTICALLY INSTALLED PULLS TO BE 9 1/2" LONG OVERALL, UNLESS OTHERWISEINDICATED.

4. ALL NEW COUNTERTOPS, BACKSPLASHES, SIDE SPLASHES, APRONS, ETC. TO HAVE PLASTIC LAMINATE FINISHES.

5. COUNTERTOPS : 1 1/2" THICK HIGH DENSITY CORES WITH PLAM FINISH. REFER TO DRAWINGS FOR COUNTERTOP EDGE PROFILES (TYP.)- COUNTERTOPS TO HAVE FULL LENGTH BACKSPLASHES, SIDESPLASHES, AND APRONS. BACKSPLASHES AND SIDESPLASHES MAY BE ON THREE SIDES, REFER TO DRAWINGS.- BACKSPLASHES, SIDESPLASHES, AND APRONS TO HAVE SELF EDGE PROFILES.

6. PLAM AS MANUFACTURED BY WILSONART. COLORS TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF STANDARD COLORS.

7. HVY. DTY. BRACKETS TO BE EH SERIES - COUNTERTOP SUPPORT ALUMINUM BRACKETS, MODEL EH-1824, AS MANUFACTURED BY RAKKS, OR APPROVED EQUAL. BRACKETSTO SUPPORT MINIMUM 300 LBS EACH. COORDINATE FINISH W/ ARCHITECT.

8. WALL MOUNTED LABORATORY PEGBOARD DRYING RACKS AS MANUFACTURED BY KEWAUNEE. 30" X 30" WITH DRIP TROUGHS, AND KEMRESIN FINISH. PROVIDE & INSTALL ALLREQ'D. MOUNTING EQUIPMENT AND APPURTENANCES BY SAME MANUFACTURER. ONE PEGBOARD PER SINK, EITHER WALL MOUNTED OR MOUNTED ON REAGENT SHELVING.INSTALL PER MANUFACTURER'S SPECIFIC INSTRUCTIONS. COORDINATE FINAL LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECT.

9. REAGENT SHELVES AS MANUFACTURED BY KEWAUNEE. ALPHA SYSTEM CENTER BENCH SHELVING WITH TWO ADJUSTABLE SHELVES, 42" TALL. SHELVES TO HAVE INTEGRALLIP GUARDS. PROVIDE & INSTALL ALL REQ'D. MOUNTING EQUIPMENT AND APPURTENANCES BY SAME MANUFACTURER. FINISHES AND COLORS TO BE SELECTED BY ARCHITECTFROM MANUFACTURER'S FULL RANGE OF OPTIONS. INSTALL PER MANUFACTURER'S SPECIFIC INSTRUCTIONS. COORDINATE FINAL LOCATIONS WITH ARCHITECT. PROVIDE &INSTALL ALL REQ'D. BLOCKING IN WALLS OR CASEWORK. COORDINATE W/ OTHER TRADES AS REQ'D.

PLASTIC LAMINATE FINISHES:

PL1 - COUNTERTOPS, BACKSPLASHES, SIDESPLASHES, AND APRONS TO BE CHEMSURF LAMINATE, AS MANUFACTURED BY WILSONART. COLOR TO BE BLACK.

CABINETRY SPECIFICATIONS:

DOOR HARDWARE NOTES1. PROVIDE & INSTALL CLOSER.

2. PROVIDE & INSTALL CLASSROOM SET.

3. PROVIDE & INSTALL PASSAGE SET.

4. PROVIDE & INSTALL KICK PLATES.

5. PROVIDE & INSTALL DOOR BUMPERS.

6. PROVIDE & INSTALL FLOOR MOUNTED DOOR STOP.

7. PROVIDE & INSTALL TRANSITION STRIP.

DOOR NOTES:

A. DOORS-

1. WOOD DOORS TO BE MOHAWK, PREMIUM 200 SERIES, ORAPPROVED EQUAL.

2. WOODS & VENEERS TO BE FSC CERTIFIED.

3. VENEERS & CORES TO IMPLEMENT FORMALDEHYDE-FREEASSEMBLY PROCESSES AND USE ADHESIVES CONTAINING NO ADDEDFORMALDEHYDE.

4. VENEER TO BE "SELECT WHITE" BIRCH, PREMIUM GRADE, PLAINSLICED, SLIP MATCHED.

5. DOORS SHALL BE FACTORY PRE-FINISHED; STAIN COLOR TO BESELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OFSTD FINISHES. CONTRACTOR TO PROVIDE 6"X6" PHYSICAL FINISHSAMPLE ON SPECIFIED WOOD SPECIES.

6. FINISH SHALL BE WDMA TR-6 UV CURED URETHANE.POLYURETHANE SHALL BE UV CURED TO PRODUCE A FINISH PERWDMA I.S. 1-A. TOP & BOTTOM RAILS SHALL BE COMPLETELYSEALED W/ AN APPROVED WOOD SEALER.

7. WOOD DOORS WITH GLAZING SHALL HAVE LITE MOULDING EQUALTO VT INDUSTRIES VT7. COORDINATE WITH ARCHITECT.

8. PRE-FIT FOR OPENING SIZE AND PRE-MACHINE FOR HARDWARE ASSPECIFIED.

9. FIRE RESISTANCE RATED DOORS & FRAMES REQUIRE METALAPPLIED LABEL INDICATING RATING DESIGNATION. CONTRACTORSHALL COORDINATE ALL FIRE PROTECTIVE ASSEMBLYCOMPONENTS TO MEET OR EXCEED SPECIFIED RATINGS.COMPONENTS TO INCLUDE, BUT NOT LIMITED TO, DOOR SLABS &EDGE REINFORCEMENTS, TRANSOM COMPONENTS, LOCKSETS,HDWR, GLAZING, FIRE DAMPERS, ETC.

10. DOORS SHALL BE INTERNALLY REINFORCED FOR ATTACHMENTOF HARDWARE WITHOUT USE OF THROUGH BOLTS.

B. DOOR HARDWARE-

1. DOOR HARDWARE TO BE McKINNEY, SERIES TA 2714, TA 2314, T4A3786, T4A 3386.

2. OUTSWINGING LOCKABLE DOORS SHALL HAVE NRP HINGES.

3. WIDTH OF HINGES SHALL BE SUFFICIENT TO CLEAR TRIM ANDWALL CONDITIONS AS SHOWN IN THE DRAWINGS.

4. SIZE: 4 1/2" X 4 1/2" FOR DOORS UP TO 3'-0" IN WIDTH, 5" X 4 1/2"FOR DOORS OVER 3-0" IN WIDTH. PROVIDE HEAVY WEIGHT HINGES(.180).

5. CLOSER: LCN 4040XP SERIES WITH METAL COVER OR APPROVEDEQUAL.

6. FLOOR MOUNTED STOPS: ROCKWOOD 441 DOME STYLE, FINISHTO BE SELECTED BY OWNER FROM MANUFACTURER'S FULL RANGEOF FINISHES. CONFIRM LOCATION WITH OWNER & ARCHITECT PRIORTO INSTALLATION.

7. KICK PLATES: ROCKWOOD, K1062 HEAVY DUTY, 10" TALL & 2"LESS DOOR WIDTH, FINISH TO BE SELECTED BY OWNER FROMMANUFACTURER'S FULL RANGE OF FINISHES.

DOOR NOTES (CONT'D.) :

C. LOCKSETS AND LATCHSETS-

1. BEST, 9K SERIES, 16D TRIM DESIGN

2. LOCKSETS MUST BE EXTRA HEAVY DUTY CYLINDRICAL TYPE WITH 2-3/4"BACKSET, OR GREATER AS SPECIFIED, WITH 9/16" THROW LATCHBOLT.

3. LOCKSETS AND LATCHSETS MUST CONFORM TO ANSI A156.2, SERIES4000, GRADE 1, AND BE UL LISTED.

4. DOOR HARDWARE TO BE LEVER STYLE AND ADA COMPLIANT. COORDINATESTYLE WITH OWNER AND ARCHITECT.

5. KEYED LEVER TO BE REMOVABLE ONLY AFTER CORE IS REMOVED, BYAUTHORIZED CONTROL KEY, TO ALLOW ACCESS TO LEVER "KEEPER".

6. LEVERS MUST BE ZINC MATERIAL WITH A MINIMUM WALL THICKNESS OF.060 INCHES.

7. LOCKSETS MUST BE AVAILABLE WITH TACTILE LEVER FORIDENTIFICATION OF HAZARDOUS AREAS.

8. PERMANENT CORE FACE MUST BE THE SAME FINISH AS THE LOCKSETFINISH.

9. IF THROUGH-BOLTING IS REQUIRED FOR ADDED STRENGTH OFINSTALLATION. MANUFACTURER WILL PACK A THROUGH BOLT DRILL JIGWITH EACH LOCKSET TO AID INSTALLER.

10. LOCKSETS AND LATCHSETS SHALL BE NON-HANDED BY DESIGN.

D. CYLINDERS AND KEYING

1. PROVIDE (ALL BRASS OPTION) CONSTRUCTION CORES AND KEYS DURINGTHE CONSTRUCTION PERIOD. CONSTRUCTION, CONTROL AND OPERATING KEYSAND CORES SHALL NOT BE PART OF THE OWNERS PERMANENT KEYINGSYSTEM. PERMANENT KEYING WILL BE WORKED BETWEEN THE OWNER ANDTHE LOCAL BEST REPRESENTATIVE. PERMANENT CORES AND KEYSPREPARED ACCORDING TO THE ACCEPTED KEYING SCHEDULE WILL BEFURNISHED TO THE OWNER BY THE LOCAL BEST REPRESENTATIVE PRIOR TOOCCUPANCY. THE OWNER OR OWNER'S AGENT WILL INSTALL THEPERMANENT CORES AND RETURN THE CONSTRUCTION CORES TO THE BESTFACTORY REPRESENTATIVE. 2. ALL CYLINDERS SHALL BE BEST 7-PIN, INTERCHANGEABLE CORE ANDKEYED INTO AN EXISTING FACTORY REGISTERED GRAND MASTER KEYSYSTEM.

E. GLAZING

1. ALL DOOR GLAZING & SIDELITE GLAZING SHALL BE SAFETY GLAZING.

2. RATED DOOR GLAZING & SIDELITE GLAZING ASSEMBLIES TO BE FIRELITENT PREMIUM GRADE OR APPROVED EQUAL, TO MEET PROTECTED DOORASSEMBLY RATING.

3. SAFETY GLAZING TO COMPLY WITH TESTING REQUIREMENTS IN 16 CFR1201 & ANSI Z97.1. SAFETY GLAZING SHALL BE PROVIDED IN ALLHAZARDOUS LOCATIONS DEFINED IN VCC SECTION 2406.

DOOR SCHEDULEDOOR

NO.

DOOR DOORFRAME JAMB HD'W. REMARKSTYPE W H T MAT'L. GLASS

5014 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5014-1 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5014-2 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5014-3 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5016-1 A 3' - 4" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5016-2 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5016B A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. / SURFACE HINGES 1,2,4,5,6,7 FACTORY FINISH

5029-1 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5029-2 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5029B A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 3,4,5,6 FACTORY FINISH

5034-1 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

5034-2 A 3' - 0" 6' - 8" 0' - 1 3/4" WOOD SAFETY EXIST. EXIST. 1,2,4,5,6,7 FACTORY FINISH

FINISH SCHEDULE

ROOM NO. ROOM NAMEFLOORFINISH

BASEMATERIAL

WALL CEILING

MATERIAL FINISH MATERIAL HEIGHT

5005 LAB VET RUBBER EXIST. PAINT EXIST. EXIST.

5005B LAB VET RUBBER EXIST. PAINT EXIST. EXIST.

5014 LAB VET RUBBER EXIST. PAINT GRID + ACT 9' - 0"

5014A OFFICE VET RUBBER EXIST. PAINT EXIST. EXIST.

5016 LAB VET RUBBER EXIST. PAINT GRID + ACT 9' - 0"

5016B OFFICE CARPET RUBBER EXIST. PAINT EXIST. EXIST.

5026 LAB VET RUBBER EXIST. PAINT GRID + ACT 9' - 0"

5029 LAB VET RUBBER EXIST. PAINT GRID + ACT 9' - 0"

5029B LAB VET RUBBER EXIST. PAINT EXIST. EXIST.

5034 LAB VET RUBBER EXIST. PAINT NEW ACT IN EXIST. GRID EXIST.

E03 ICE VET RUBBER EXIST. PAINT GRID + ACT 9' - 0"

GENERAL DOOR NOTE :ALL EXIST. DOORS TO REMAIN IN SCOPE OF WORK :- REMOVE ALL NAILS, SCREWS & OTHER EXIST. PROTRUSIONS.- SMOOTH, FILL OR REPLACE ALL SURFACE DELAMINATIONS, GOUGES & SIMILAR IMPERFECTIONS LARGER THAN ONE INCHDIAMETER TO MATCH ADJACENT SURFACES & FINISHES.

1. ALL NEW DOOR HARDWARE & LOCKSETS TO BE ADAAG COMPLIANT LEVERS, SS W/ BRUSHED SATIN FINISHES.2. EXISTING & NEW DOOR FRAMES TO BE FREE OF DRIPS & BUILD UPS, ETC. TO PROVIDE A SMOOTH, PROFESSIONALAPPEARANCE.3. PAINT FRAMES TO MATCH FINISHES ON EACH SIDE OF FRAME, IF FINISHES ARE DIFFERENT ON EACH SIDE OF FRAME,COORDINATE WITH ARCHITECT. SEE FINISH SCHEDULE.

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A2.1

SC

HE

DU

LE

S

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

1. ACT & GRID:- ACT1 - ARMSTRONG - CIRRUS SQUARE LAY-IN 584, TEGULAR, HUMIGUARD PLUS, 24" X 24", 15/16" PRELUDE GRID, COLOR = WHITE.

2. FLOORING:- F1 – JOHNSONITE, VET (VINYL ENHANCED TILE), COLOR ESSENCE, COLOR TBD. TRANSITION STRIPS TO BE FROM SAME MANUFACTURER. COLOR & PROFILE TO BESELECTED BY ARCHITECT FROM MANUFACTURER’S FULL RANGE OF COLORS AND PROFILES.A. CONTRACTOR TO PREPARE SURFACES PER MANUFACTURER’S SPECIFIC INSTRUCTIONS.B. INSTALL PER MANUFACTURER’S SPECIFIC INSTALLATION INSTRUCTIONS.C. TRANSITION STRIPS TO BE INSTALLED & CENTERED BELOW DOOR IN CLOSED POSITION. COORDINATE FINAL LOCATIONS W/ ARCHITECT, INCLUDING DOOR FRAMESWITHOUT DOORS.- F2 - SHAW GROUP, 24" X 24" CARPET TILES. STYLE AND COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF OPTIONS.

3. RUBBER BASE:- B1 - CASEWORK - JOHNSONITE TRADITIONAL WALL BASE, 4". COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS.- B2 - WALL - JOHNSONITE TRADITIONAL WALL BASE, 6". COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS.

4. PAINT:- P1 - WALLS - SHERWIN WILLIAMS, EGG SHELL, COLOR TO BE SELECTED FROM MANUFACTURER'S FULL RANGE OF COLOR OPTIONS.- P2 - DOOR FRAMES - SHERWIN WILLIAMS, SEMI-GLOSS, COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLOR OPTIONS.- P3 - CEILINGS - SHERWIN WILLIAMS, FLAT, COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLOR OPTIONS.A. ALL EXISTING AND NEW EXPOSED PIPING, CONDUIT, STRUCTURE, INSULATION, ETC. ASSOCIATED WITH THE WORK SHALL BE PAINTED TO MATCH ADJACENT SURFACES.COORDINATE W/ ARCHITECT.B. ALL NON-STAINLESS STEEL, EXISTING AND NEW ACCESS PANELS & ACCESS DOORS IN AREAS OF WORK SHALL BE PAINTED TO MATCH ADJACENT SURFACES.COORDINATE COLORS & SHEENS W/ ARCHITECT.C. ALL PAINTED SURFACES TO RECEIVE ONE (1) COAT NO/LOW VOC PRIMER & TWO (2) COATS NO/LOW VOC PAINT.D. SURFACES TO REMAIN & RECEIVE NEW FINISHES TO BE FREE OF ALL EXIST. OR NEW BUILD-UPS, DRIPS, ETC. TO PROVIDE FINISHES WITH A SMOOTH, PROFESSIONALAPPEARANCE.E. EXISTING DOOR FRAMES TO REMAIN & RECEIVE NEW PAINT FINISHES SHALL BE CLEANED OF EXIST. DRIPS OR BUILD UPS PRIOR TO PAINTING. ABANDONED HINGE, STRIKE,ETC. RECESSES TO BE PATCHED FLUSH & WITH NO GAPS WITH MAIN SURFACES OF FRAME. (TYP.)

5. WOOD STAIN :ALL EXISTING & NEW WOOD CASEWORK AND TRIM TO BE SANDED, PREPPED AND STAINED TO MATCH EXISTING. COORDINATE FINAL STAIN COLOR WITH ARCHITECT.- S1 - SHERWIN WILLIAMS WOOD STAIN. COLORS TO BE SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF STD FINISHES.A. ALL STAINED SURFACES TO RECEIVE 2 COATS SHERWIN WILLIAMS WATER BASED POLYURETHANE, SATIN FINISH.

6. MINI-BLINDS TO BE SELECTED FROM HUNTER DOUGLAS DECOR COLLECTION, OR APPROVED EQUAL. 262 STEEL WIND BRUSHED FINISH, WITH 1" BLADES.

7. PAPER TOWEL DISPENSERS AS MANUFACTURED BY BOBRICK, B-263, W/ STAINLESS STEEL FINISH. ONE DISPENSER AT EACH SINK LOCATION. COORDINATE FINALMOUNTING LOCATION & HEIGHT WITH ARCHITECT.

8. ALL EXIST. RADIATORS TO RECEIVE ONE COAT HIGH TEMPERATURE PRIMER & TWO FINISH COATS HIGH TEMPERATURE PAINT. PAINT TO BE SHERWIN WILLIAMS, SATINFINISH. COLORS TO BE SELECTED BY OWNER FROM MANUFACTURER'S FULL RANGE OF STD COLORS.

MATERIAL FINISH NOTES

NOTE : CONTRACTOR TO CONFIRM DIMENSIONS OF ALL EXISTING DOOR FRAMES TO REMAIN.

DOOR SCHEDULE NOTES :

NOTE:PRIOR TO CORE DRILLING, CONTRACTOR SHALL PROPERLY SURVEY THE EXISTING FLOOR USING X-RAY, GPR, OR OTHER ACCEPTABLE METHOD TO LOCATE REBAR, STRUCTURAL MEMBERS, IN-SLABUTILITIES, OR OTHER IN-SLAB OBSTRUCTIONS. ALL CORES TO BE RETAINED AND PROVIDED TO THEUBO FOR INSPECTION. ANY STRUCTURAL REMEDIATION REQUIRED DUE TO CONTRACTOR'SNEGLIGENCE SHALL BE PERFORMED BY CONTRACTOR AT NO ADDITIONAL CHARGE TO VA TECH.

1. ALL VISIBLE CMU, CONCRETE, VENEER PLASTER & GYP. BD. SURFACES IN AREAS OF WORK SHALL BE PAINTED TO MATCH ADJACENT SURFACES, UNLESSNOTED OTHERWISE. COORDINATE W/ ARCHITECT.

2. ALL NEW CEILING HEIGHTS TO BE AS HIGH AS POSSIBLE. LISTED HEIGHTS ARE MINIMUMS UNLESS NOTED OTHERWISE.

3. ALL NEW & EXIST. VENEER PLASTER FINISHES AND NEW & EXIST. GYP. BD. SURFACES TO BE MINIMUM LEVEL 4 FINISH PER USG OR NATIONAL GYPSUMSTANDARDS, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL RENDER ALL SUCH SURFACES TO SPECIFIED LEVEL OF FINISH.

GENERAL FINISH NOTES

REVISIONS DATE

Page 9: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

# - EQUIPMENT SCHEDULE

MANUFACTURER

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

MARK DESCRIPTION PROVIDED BY

-80°C FREEZER

REFRIGERATED SHAKER/INCUBATOR

ULTRACENTRIFUGE

DRYING OVEN

ICE MAKER

SONICATOR

SHAKER/INCUBATOR

DISHWASHER

VWR

HIGH-SPEED CENTRIFUGE

PLANT GROWTH CHAMBER

FRENCH PRESS

AUTOCLAVE

-20/-30°C FREEZER REVCO

4°C REFRIGERATOR THERMO

INSTALLED BY

CONTRACTOR

CONTRACTOR

OWNER

OWNER

MODELWIDTH

SIZE

DEPTH VOLTS PHASE AMPS HP KW

ELECTRICAL

HW CW IW

PLUMBING

SIZE BTU/HR

GAS

INCUBATOR - STATIC

SHAKER/INCUBATOR

REVCO ULT1875-5-A12 40" 34" CONTRACTOROWNER

CONTRACTOROWNER

CONTRACTOROWNER

FISHER 500

HEIGHT

76"

1380FM

CONTRACTOROWNER

CONTRACTOROWNER

STEELCO VS 6/1 CONTRACTOROWNER

BECKMAN OPTIMA L90K

CONTRACTOROWNER

G7883AE

CONTRACTOROWNERSCOTTSMAN F0822

CONTRACTOROWNER

CONTRACTOROWNER

BARNSTEAD MAXQ5000 CONTRACTOROWNER

BECKMAN

NEW BRUNSWICK

NEW BRUNSWICK

CONTRACTOROWNER

MIELE

ULT3030A19

RFS214 A15

E-30B

650D

PERCIVAL

FISHER

18

ANAEROBIC CHAMBER

THERMO FA-087A

-80°C FREEZER NEW BRUNSWICK U570-86HEF

4°C CHROMATOGRAPHY CABINET FISHER MH49PA-GAEE-FS

OWNER CONTRACTOR

19

20

COY LCD, 8' AIRLOCK

ANAEROBIC CHAMBER21 COY LCD, 6' AIRLOCK

CONTRACTOROWNER

CONTRACTOROWNER

22

HIGH-SPEED CENTRIFUGE BECKMAN

CONTRACTOROWNER

J26-XP

CONTRACTOROWNER

STERILIZING OVEN VWR 1365 220V

MILLIQ WATER POLISHER MILLIPORE BIOCEL

23 OWNER CONTRACTOR

OWNER CONTRACTOR24 SHAKER/INCUBATOR NEW BRUNSWICK INNOVA 4300

25 HPLC AGILENT

OWNER

OWNER

OWNER

CONTRACTOR

CONTRACTOR

CONTRACTOR

OWNER CONTRACTOR

JE

EXCELLA 325

COMMENTS

NOTE: CONTRACTOR TO STORE AND PROTECT ANY EQUIPMENT ANDCASEWORK PROVIDED BY OWNER UNTIL READY FOR INSTALLATION.

40" 34" 76"

37" 27" 48"

44" 51" 75"

36" 28" 33"

37" 35" 48"

32" 24" 40"

23" 24" 24"

VERIFY

9.5" 16" 7.5"

34" 33" 81"

30" 30" 70"

52" 32" 78"

32" 41" 41"

32" 25" 36"

25" 29" 37"

50" 41" 32"

31" 24" 46"

26" 26" 32"

72" 36" 30"

84" 36" 30"

28" 34" 34"

43" 28" 37"

24" 24"

EXPOSED UNDERCOUNTERINSTALLATION; 1/2" DI, 1/2" WASTETEMPERING

FLOOR UNIT

EXISTING

VERIFY VERIFY EXISTING, WALL MOUNTED

VERIFY VERIFY VERIFY TABLE TOP UNIT

INNOVA 4200

FLOOR UNIT

FLOOR UNIT

1200

120 1 12

120 1 12

208 1 24

120 1 9.3 1

208 3 18.3

208 1 15.5

208 1 10.7

2.9

2.0

EXISTING

120 1 3.0

120 1 4.6 0.5

120 1 10

120 1 13.3

120 1 13.3

120 1 16

120 1 12

208 1 24

120 1 0.7

120 1 0.8

120 1 9

120 1 7

120 1 15

120 1 15

120 1

120 1 7

208 1 24

0.7

1/2" 1/2" 7/8"

3/8"

LAB

5005B

12

12

14

14

16

15

13

LAB

5005LAB

5017

EXIST.HOOD

NEW WORK - PARTIAL PLAN - LAB 5005

EXIST.HOOD

EXIST.HOOD

12

17

13

13

LAB

5014

OFFICE

5014A

CORR

CR-5A

CORR

CR-5B

18

18

NEW WORK - LAB 5014

12

LAB

5016

OFFICE

5016B

13

13

1824

EXIST.HOOD

14

23

25

20

CORR

CR-5A

12

NEW WORK - LAB 5016

2

1

1

1

1

3

1

4

6 7

8

LAB

5034

LAB

5026

CORR

CR-5A

CORR

CR-5B

ICE

E03

4

NEW WORK - LAB 5026 + LAB 5034

59

510

11

12

LAB

5029B

21

2213

18

23

20

14

CORR

CR-5B

13

12

LAB

5029

EXIST.HOOD

NEW WORK - LAB 5029

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A2.2

EQ

UIP

ME

NT

SC

HE

DU

LE

+E

QU

IPM

EN

T P

LA

N

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

Page 10: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

EXIST. CONC. BEAM TO REMAIN

EXIST. STRUCTURE TO REMAIN

5/8" GYP. BD. ALL VISIBLE SURFACES

NEW CEILING GRID & ACT- SEE FINISH SCHED.

3 5/8" 20 GA. MTL. FRAMING @24" O.C. (TYP.)

EXTEND FRAMING TIGHTTO DECK. (TYP.)

3 5/8" 20 GA. MTL. BRACINGAS REQ'D. @ 4' - 0" O.C.EXTEND & SECURE TO DECK

3' - 0" CLR.

EXIST. WINDOW TO REMAIN

1"

1' -

0"

MIN

.

LAB

(VARIES)

EXIST. STRUCTURE TO REMAINFLOORING & BASE- SEE FINISH SCHED.

2X P.T. WOOD CLEATS, 3SIDES (TYP.)- SEE CABINETRY SPECS

PLAM COUNTERTOP (PL1)W/ FULL BULLNOSE- SEE CABINETRY SPECS

4" PLAM (PL1) BACKSPLASH &SIDESPLASHES- SEE CABINETRY SPECS

2' -

10

"

2' - 1"

1 1/2"

EXIST. STRUCTURE

HVY. DTY. BRACES- SEE CABINETRY SPECS

ADAAG KNEE & TOECLEARANCES

4 1

/2"

NEW ADAAG SINK,FAUCET & EYEWASH- SEE PLUMBING- SEE CABINETRY SPECS

NEW FLOORING & BASE- SEE FINISH SCHEDULE

EXIST. STRUCTURE

2X P.T. WOOD CLEATS ASREQ'D., ALL SIDES (TYP.)- SECURE TO EXIST.CASEWORK & STRUCTUREAS REQ'D. W/ GALV.FASTENERS

NEW PLAM (PL1)COUNTERTOP,BACKSPLASH & APRON- SEE CABINETRY SPECS

EXIST. CABINETRY,BEYOND (VERIFY)- SEAL NEW WORKWHERE ABUTS EXIST.

3 HVY. DTY. BRACES- SEE CABINETRY SPECS

ADAAG KNEE & TOECLEARANCES

1" 2"

4 1

/2"

2' -

10

"

PLAM (PL1) COUNTERTOP,BACKSPLASH & APRON W/EASED EDGES- SEE CABINETRY SPECS EXIST. & NEW CASEWORK,

EA. SIDE (VERIFY)- MODIFY CASEWORK,COUNTERTOPS, SUPPORTS,ETC. AS REQ'D TO ACCOM.NEW WORK.- MATERIALS & FINISHES TOMATCH EXIST.

NEW BASE- SEE FINISH SCHEDULE

EXIST. WALL, BEYOND

NEW SINK, EYE WASH & FAUCET- SEE PLUMBING

EXIST. SURFACE, BEYOND- PATCH AS REQ'D W/SIMILAR MATERIALS TOMATCH ADJ. SURFACES

NEW HVY. DTY. BRACES- SEE CABINETRY SPECS

2' -

10

"4"

NEW FLOORING- SEE FINISH SCHEDULE

LAB(VARIES)

CLR. TO FLANGE

2' - 8" MIN. 3"

4' - 2" (TYP.)

2

A3.1A1.2

0 4 6 82

1/2" = 1' - 0"

3/4" = 1'-0"A3.1A3.1A1.4

4 SECTION 3/4" = 1'-0"A3.1A3.1A1.2

3 SECTION 1" = 1'-0"A3.1A3.1A1.2

2 SECTION

colle

yarc

hitects

pc

desig

ncom

munity

envir

onm

ent

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BID SET

BLA

CK

SB

UR

G . V

IRG

INIA

A3.1

ELE

VA

TIO

NS

, S

EC

TIO

NS

+D

ET

AIL

S

SEPTEMBER . 30 . 2016

G843-16-219956

1618

JRW

DE

RR

ING

HA

LL

FIF

TH

FLO

OR

LA

BO

RA

TO

RIE

S

RE

NO

VA

TIO

NS

TO

1/2" = 1'-0"A3.1A3.1A1.2

1 ELEVATION - ADAAG WORKSTATION

0 2 3 41

1" = 1' - 0"

REVISIONS DATE

Page 11: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR DEMOLITION PLAN - PLUMBINGSCALE: 1/8" = 1'-0"

EX. FD

EX. SUMP

EX. ES

EX. FD

EXISTING PLUMBING SINKS, EYEWASH,

FAUCETS AND PIPING TO REMAIN

PLUMBING APPURTENANCES SHALL INCLUDE BUT NOT LIMITED TO

THE FOLLOWING: ALL FITTINGS, HANGERS AND SUPPORTS, BOLT

CAPS, VALVE SUPPLIES, TRAPS, TRIM SUCH AS ESCUTCHEONS,

PIPING COVERS, TRAP WRAP AND LOOSE KEY ANGLE STOPS.

LAB

5005

LAB

5005B

LAB

5017

LAB

5029BLAB

5029

LAB

5029A

OFFICE

5029C

ICE

E03

CORRIDOR

CR-5B

OFFICE

5014A

LAB

5014 LAB

5010

LAB

5000

LAB

5007

LAB

5034

LAB

5026

LAB

5026

LAB

5016

JANITOR

E06

CORRIDOR

CR-5C

OFFICE

5016B

CORRIDOR

CR-5A

23

23

1

14

12 13

12 13

16 17

14 18

3 6 7 19

12 13

16 17 14

3 7 20 24

1

5

25 8 24

910

5

2 33 7 20

24

1512 13

15 7 12

13 21

26

12 1312 1326

14

14

14

14

14

14

11

2820 21 22

4

CONFIRM WITH NEW WORK SHEET P1.1 THAT EXISTING WATER,

GAS AND AIR LINES BEING REMOVED FOR DEMOLITION ARE NOT

NEEDED FOR NEW WORK.

EX. ES

23

EX. FD

EX. FD

EX. HOOD

1-HR FIRE WALL (TYP.)

2-HR FIRE WALL (TYP.)

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

CAD

DEMOLITION NOTES:

1. EXISTING EMERGENCY SHOWER EYEWASH SHALL REMAIN. SEE SHEET P1.1 FOR

SHOWER SUPPLY MODIFICATION. REMOVE EXISTING SUPPLY TO ABOVE CEILING

AND CAP. PATCH CEILING TO MATCH EXISTING CONDITIONS.

2. REMOVE EXISTING 2-BOWL LAUNDRY TUB FIXTURE, RETAIN FOR REUSE IN LAB

ROOM 5014. CONTRACTOR SHALL VERIFY LOCATION WITH OWNER/ARCHITECT.

REMOVE EXISTING WASTE LINE FROM EXISTING FIXTURE TO WITHIN WALL AND CAP.

CAP VENT PIPING ABOVE CEILING. CONTRACTOR SHALL VERIFY WHETHER EXISTING

VENT THRU ROOF IS USED BY ANOTHER FIXTURE. IF NOT, CAP WEATHERTIGHT THE

EXISTING VTR ABOVE THE ROOF. PATCH THE WALL AND CEILING TO MATCH

EXISTING CONDITIONS.

3. REMOVE EXISTING HOT AND COLD WATER PIPING TO WITHIN WALL AND CAP. PATCH

THE WALL TO MATCH EXISTING CONDITIONS.

4. REMOVE EXISTING FLOOR DRAIN TO BELOW FLOOR. FILL DRAIN WITH SHRINK

PROOF GROUT FLUSH WITH SURROUNDING FLOOR AND PATCH FLOOR TO MATCH

EXISTING CONDITIONS.

5. REMOVE EXISTING AIR AND GAS PIPING TO WITHIN WALL AND CAP. PATCH WALL TO

MATCH EXISTING CONDITIONS.

6. REMOVE EXISTING SINK, FAUCETS AND APPURTENANCES.

7. REMOVE EXISTING WASTE LINE FROM EXISTING FIXTURE TO WITHIN WALL OR

BELOW FLOOR AND CAP. CAP VENT PIPING ABOVE CEILING. CONTRACTOR SHALL

VERIFY WHETHER EXISTING VENT THRU ROOF IS USED BY ANOTHER FIXTURE. IF

NOT, CAP WEATHERTIGHT THE EXISTING VTR ABOVE THE ROOF. PATCH WALL,

FLOOR AND CEILING TO MATCH EXISTING CONDITIONS.

8. SCOTMAN ICE MACHINE IN E03 DRAINING TO THIS FLOOR DRAIN WILL BE RETAINED.

REMOVE PVC PIPING FROM ICE MACHINE TO FLOOR DRAIN. SEE SHEET P1.1 FOR

NEW DRAIN ROUTING.

9. REMOVE EXISTING EMERGENCY SHOWER. REMOVE EXISTING COLD/TEMPERED

WATER SUPPLY TO ABOVE CEILING AND CAP. PATCH CEILING TO MATCH EXISTING

CONDITIONS.

10. REMOVE EXISTING AUTOCLAVE STEAM CONDENSATE PIPING FROM EQUIPMENT TO

SUMP. CONTRACTOR SHALL COORDINATE WITH NEW WORK PLAN P1.1 WHETHER

NEW WASTE PIPING FROM LT-1 WILL REQUIRE SUMP TO BE MODIFIED.

11. REMOVE EXISTING EMERGENCY EYEWASH.

12. REMOVE EXISTING SINKS, FAUCETS AND APPURTENANCES.

13. REMOVE EXISTING P-TRAPS AND TAILPIECES.

14. REMOVE EXISTING GAS, AIR AND VACUUM VALVES.

15. REMOVE EXISTING GAS VALVES.

16. REMOVE EXISTING WASTE PIPING TO WITHIN WALL OR BELOW FLOOR AND CAP.

17. REMOVE EXISTING HOT, COLD AND DEIONIZED WATER PIPING TO WITHIN WALL AND

CAP.

18. REMOVE EXISTING GAS PIPING TO WITHIN WALL AND CAP.

19. REMOVE EXISTING DEIONIZED WATER PIPING TO STUB-OUT AT WALL AND CAP FOR

NEW WORK. PATCH WALL TO MATCH EXISTING CONDITION.

20. REMOVE EXISTING SINK, BASE CABINET, FAUCET AND APPURTENANCES.

21. REMOVE EXISTING HOT AND COLD WATER PIPING TO BELOW FLOOR AND CAP

ABOVE CEILING AT FLOOR BELOW. PATCH FLOOR TO MATCH EXISTING CONDITIONS.

22. REMOVE EXISTING WASTE PIPING TO BELOW FLOOR. PATCH FLOOR TO MATCH

EXISTING CONDITIONS. CAP DEIONIZED WATER DRAIN ABOVE CEILING OF 4TH

FLOOR.

23. EXISTING SINK SHALL REMAIN.

24. REMOVE EXISTING GAS, VACUUM, COMPRESSED AIR AND WATER VALVES.

25. REMOVE EXISTING MILLIPORE WATER TREATMENT EQUIPMENT AND REMOVE PIPING

TO WITHIN WALL AND CAP. RETAIN EQUIPMENT FOR RELOCATION IN SAME ROOM.

COORDINATE LOCATION WITH OWNER/ARCHITECT.

26. REMOVE EXISTING EMERGENCY SHOWER ES. SEE SHEET P1.1 FOR NEW LOCATION

AND SUPPLY MODIFICATION. REMOVE EXISTING SUPPLY PIPING FROM CEILING TO

WITHIN CABINET AND CAP. PATCH CEILING TO MATCH EXISTING CONDITIONS.

27. REMOVE EXISTING PVC TUBING ROUTED ABOVE FLOOR FROM ICE MAKER TO FLOOR

DRAIN. SEE NEW WORK NOTE 25.

28. CONTRACTOR SHALL VERIFY WHETHER EXISTING VENT THRU ROOF IS USED BY

ANOTHER FIXTURE. IF NOT, CAP WEATHERTIGHT THE EXISTING VTR ABOVE THE

ROOF. CAP VENT PIPING ABOVE CEILING.

0 16 24 328

1/8" = 1' - 0"

LEGEND:

1-HR FIRE WALL

2-HR FIRE WALL

Page 12: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PLUMBING LEGEND

ACCESS DOOR ADR

ACID VENT PIPE, NEW AV AV

EXISTING TO REMAIN AV EX AV

ACID WASTE PIPE, NEW AW AW

EXISTING TO REMAIN EXAW AW

CEILING CLG

CLEANOUT CO

COMPRESSED AIR PIPE, NEW CA A

DEIONIZED WATER PIPE DE DEDIRECTION OF FLOW

DIRECTION OF SLOPE DOWN

DOMESTIC COLD WATER PIPE, NEW CW

DOMESTIC HOT WATER PIPE, NEW HW

DOMESTIC HOT WATER CIRCULATING PIPE, NEW HWR

EXISTING TO REMAIN HWR EXDRAIN PIPE D DEMERGENCY EYE WASH EEW

EMERGENCY EYE WASH/SHOWER EEWS

EXISTING EX

FLOOR DRAIN FD FD

FROM FR

GAS COCK

GATE VALVE GV

GATE VALVE (IN VERTICAL)

HOT AND COLD WATER H&CW

INDIRECT WASTE PIPE IW IWINLET WITH P-TRAP

PIPING INDICATION WITH RESPECT

TO WATER FLOW

CONNECTION (BOTTOM,TEE OR TOP)

TOP TAKEOFF

TURN DOWN OR FROM BELOW

TURN UP OR DOWN

TURN UP OR FROM ABOVE

SANITARY WASTE PIPE, NEW SW

SHOCK ABSORBER SA

SINK SK

UNION

VACUUM PIPE VP VP

VENT PIPE, NEW V

EXISTING TO REMAIN V EX

TEMPERED WASTE TW

CONDENSER WATER CD CD

EMERGENCY SHOWER ES

MARK FIXTURE WASTE VENT COLD HOT REMARKS

FIXTURE CONNECTION SCHEDULE

# INSTALLATION SHALL MEET 2010 AMERICANS WITH DISABILITIES ACT (ADAAG) ACCESSIBILITY GUIDELINES

FOR BUILDINGS AND FACILITIES.

SK-1 SINK (SINGLE

COMPARTMENT)

1 1/2" 1 1/2" 1/2" 1/2" COUNTER TOP, HANDICAPPED#

LT-1 SINK (SINGLE

COMPARTMENT)

2" 1 1/2" 1/2" 1/2" MOLDED STONE WALL MOUNT

LT-2 SINK (TWO

COMPARTMENT)

2" 1 1/2" 1/2" 1/2" RELOCATED EXISTING FIXTURE

SK-2 SINK (SINGLE

COMPARTMENT)

1 1/2" 1 1/2" 1/2" 1/2" COUNTER TOP, DEEP WELL

GLASSWARE WASHERS DRAIN DETAILNO SCALE

GLASSWARE

WASHER #2

MIN. 18" ABV.

TRAP WIER

6" MIN.

3" STANDPIPE LOCATED IN SPACE

BEHIND GLASSWARE WASHER

EXTEND DRAIN TO

VENTED RISER IN WALL

P-TRAP ABOVE FLOOR

CO

NOTE:

STANDPIPE SHALL BE PROVIDED

ACCESS FOR RODDING

GLASSWARE

WASHER #1

7/8" I.D. FLEX HOSE. CONTRACTOR

SHALL SPECIAL ORDER LONGER

THAN STANDARD (5'-0") FLEX. HOSE

(AVAILABLE IN LENGTH UP TO 13')7/8" I.D. FLEX HOSE. 5'-0" LONG,

DISHWASHER MFGR. SHALL

PROVIDE NON-RETURN VALVE

(TYP.) (BALL CHECK)

AIR GAP

LOOP HOSE

BEHIND CABINET

GLASSWARE PIPING CONNECTIONS DETAILNO SCALE

WAREWASHER

(TYP. FOR 2)

TWD

I

SA-A (TYP.)

BFP

CD

NOTE:

PER MANUFACTURER, INTERNAL WATER INLET

ABOVE FLOOR LEVEL OF UNIT. NO BACKFLOW

PREVENTER NECESSARY

1

DETAIL NOTES:

1. UNIT PROVIDED 7/8" I.D. FLEX DRAIN HOSE WITH NON-RETURN

BALL CHECK VALVE, 5'-0" LONG (GLASSWASHER #2 - SPECIAL

ORDER LENGTH).

2. UNIT PROVIDED 1/2" I.D. FLEX HOSE WITH 3/4" FEMALE THREAD,

5'-0" LONG WITH LARGE SURFACE AREA FILTERS AND DUAL

CHECK VALVE EACH.

3. PROVIDE WAREWASHER DRAIN COOL DOWN KIT (TEMPER

WASTE TO MAXIMUM 140 DEG. F).

4. CONTRACTOR PROVIDED STOP VALVES WITH 3/4" MALE HOSE

THREAD OUTLETS (TYPICAL).

5. CONTRACTOR SHALL ROUGH-IN PIPING CONNECTIONS TIGHT

TO WALL.

6. EXTEND NEW DEIONIZED PIPING TO EXISTING DEIONIZED

PIPING OF 1" SIZE.

7. EXTEND NEW CONDENSER WATER PIPING TO EXISTING COLD

WATER PIPING OF 1" SIZE.

8. UNIT PROVIDED 3/4" MALE THREAD UNION (TYPICAL).

9. LARGE SURFACE AREA FILTERS (TYPICAL).

10. DUAL CHECK VALVE (TYPICAL).

11. CONNECT WASTE TEMPERING VALVE CW SUPPLY TO CW

SUPPLY TO WAREWASHER WITH MIELE PROVIDED Y FITTING.

12. EXTEND NEW COLD WATER PIPING TO EXISTING CW PIPING OF

1" SIZE.

2

3

4

5

6

12

78

9

10

11

DI

CD

Y-FITTING

EMERGENCY EYEWASHPIPING CONNECTION DETAILNO SCALE

TV-2 MOUNTED ON CABINET

WALL BELOW COUNTERTOP

1/2"

1/2" TO EEW

RUNOUTS TO

SINK FAUCET

1/2"H&CW RUNOUTS

FOR SINK AND EEW

EXISTING ICE

MACHINE AND BIN

(OWNER PROVIDED)

1/2" WATER SUPPLY WITH NEW

WATTS 9D BACKFLOW PREVENTER

3/4" DRAIN

HARD COPPER

2" AIR GAP

NEW

4" FD

FLOOR6"

AIR VENT

(TYP.)

3/4" BIN DRAIN

HARD COPPERWATER SUPPLY DRAIN

VALVE. EXTEND TO DRAIN

WALL

1/2"

1/2" WATER

INLET

IM

EXISTING ICE MACHINECONNECTION DETAILNO SCALE

NOTES:

1. ONE TV-2 PER EMERGENCY EYEWASH.

2. DEAD LEGS SHALL BE LESS THAN 10 FEET.

SUMP DRAIN

CONNECTIONS AT EMERGENCYEYEWASH/SHOWER EEWSNEW, RELOCATED AND MODIFIED EXISTINGNO SCALE (EMERGENCY SHOWER ES SIMILAR LESS EYEWASH)

FINISHED FLOOR

1 1/4" DRAIN

1/2" STAY-OPEN VALVE

EYEWASH

PUSH HANDLE

TRIANGULAR HANDLE

1 1/4"

TW

TW1 1/4"

FROM LEONARD MODEL

TM-800-STSTL-EXP-LF-BWE-EXP

TEMPERING VALVE, REFER

TO FLOOR PLANS

WALL

STAY-OPEN

VALVE

1"10"Ø SHOWER HEAD

PULL ROD

60"

69"

MINIMUM 20"Ø SPRAY

COLUMN AT 60" ABV FL

CENTER LINE OF SPRAY

PATTERN MINIMUM 16"

FROM OBSTRUCTIONS

84"

UNINTERRUPTIBLE

WATER SUPPLY

SOURCE. VALVES

LOCKED OPEN

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

CAD

GENERAL PLUMBING NOTES:

1. MAKE PIPING CONNECTIONS AS REQUIRED TO ALL FIXTURES AND EQUIPMENT EVEN

THOUGH ALL BRANCH MAINS, ELBOWS AND CONNECTIONS ARE NOT SHOWN.

2. CHECK WITH ARCHITECTURAL WORKING DRAWING BEFORE ROUGHING-IN PLUMBING

FIXTURES.

3. SLOPES AND INVERT ELEVATIONS OF PIPING, ETC., SHALL BE ESTABLISHED AND

VERIFIED BY CONTRACTOR BEFORE ANY PIPING IS INSTALLED IN ORDER THAT

PROPER SLOPE WILL BE MAINTAINED AND NECESSARY INVERT ELEVATIONS

OBTAINED.

4. ALL PIPES SHALL BE COORDINATED WITH OTHER NEW AND EXISTING DUCTS, PIPES,

LIGHTS, STRUCTURAL SYSTEM, CEILING SUPPORTS AND FRAMING BEFORE

INSTALLATION. MINOR PIPE OFFSETS SHALL BE PROVIDED AS REQUIRED.

MEASUREMENTS FOR VERTICAL CLEARANCES SHALL BE TAKEN AT THE JOB SITE

BEFORE INSTALLATION OF ANY PIPING.

5. WASTE PIPE BELOW FLOOR, VENT PIPING ABOVE CEILING, PIPING OFFSET FOR

CLARITY.

6. DOMESTIC WATER PIPING SHALL BE INSTALLED ABOVE CEILINGS UNLESS NOTED

OTHERWISE. DOMESTIC WATER PIPING SHOWN IN PIPE CHASE WALLS SHALL BE

INSTALLED IN CHASE SPACE, PIPING OFFSET FOR CLARITY.

7. DOMESTIC WATER PIPING SHALL NOT BE INSTALLED IN LOCATIONS SUBJECT TO

FREEZING OR SPACES EXTERIOR TO BUILDING INSULATION.

8. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S

PUBLISHED INSTRUCTIONS.

9. MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL CODES, APPLICABLE

PROVISIONS OF LATEST EDITION OF NATIONAL FIRE PROTECTION ASSOCIATION,

LOCAL UTILITY REGULATIONS AND GOVERNMENTAL DEPARTMENTS HAVING

JURISDICTION.

10. WHERE PIPE CONNECTIONS ARE SHOWN CONNECTING TO EXISTING, CONTRACTOR

SHALL DETERMINE EXACT LOCATIONS AND CONNECTION SIZES PRIOR TO

INSTALLATION.

11. LIMITS OF CONTRACT: DOMESTIC WATER SERVICE, SANITARY AND STORM WATER

PIPING SHALL BE EXTENDED UNDER THIS SECTION OF THE SPECIFICATIONS TO

POINTS WITHIN THE BUILDING, UNLESS OTHERWISE INDICATED ON THE DRAWINGS,

WHERE THE PIPES SHALL BE CAPPED OR PLUGGED AND LEFT READY FOR

CONNECTION AND EXTENSION BY OTHERS, AND THE LOCATIONS MARKED WITH

APPROVED MEANS.

12. INFORMATION ON EXISTING PLUMBING SHOWN WAS OBTAINED FROM PLANS DATED

NOVEMBER 4, 1969. THE CONTRACTOR SHALL ADJUST WORK AS REQUIRED TO SUIT

ACTUAL LOCATIONS IF DIFFERENT FROM CONTRACT DOCUMENTS.

13. RETURN AIR PLENUM NOTE: ALL MATERIAL LOCATED IN THE RETURN AIR PLENUMS

SHALL MEET THE REQUIREMENTS OF THE INTERNATIONAL MECHANICAL CODE,

SECTION 602.2.1.

14. PIPING SHALL NOT BE INSTALLED ABOVE ELECTRICAL PANELS. COORDINATE

INSTALLATION OF PIPES WITH ELECTRICAL PANELS WHEN SHOWN NEAR PANELS OR

OVER ELECTRICAL ROOMS.

15. CONTRACTOR SHALL VERIFY THAT ALL NEW AND EXISTING DRAINS WITHIN AREAS

OF WORK AND LINES ARE FREE OF CLOGS OR OBSTRUCTIONS. IF PROBLEMS EXIST,

CONTRACTOR SHALL REMOVE POTENTIAL OBSTRUCTIONS AND CLEAN DRAINS FOR

FREE FLOW.

Page 13: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

CAD

1. CODES, STANDARDS AND REGULATIONS : MATERIALS, EQUIPMENT, INSTALLATION, DISINFECTION AND TESTING SHALL BE

IN COMPLIANCE WITH, BUT NOT LIMITED TO, THE FOLLOWING CODES AND STANDARDS:

A. LOCAL CODES OR ORDINANCES.

B. VIRGINIA CONSTRUCTION CODE (VCC).

C. PIPING, FITTINGS, PUMP SYSTEMS, EQUIPMENT AND FIXTURES THAT ARE CONNECTED TO POTABLE WATER SYSTEM

SHALL MEET THE 1996 SAFE WATER DRINKING ACT AND WHERE APPLICABLE SHALL MEET NSF STANDARD 61 AND

SHALL BE LABELED AND CERTIFIED.

2. SHOP DRAWINGS: FURNISH SIX COPIES OF PLUMBING MATERIALS AND EQUIPMENT TO ARCHITECT FOR REVIEW.

3. DESCRIPTION OF WORK:

A. THE WORK INCLUDES PROVIDING A COMPLETE PLUMBING SYSTEM INCLUDING, BUT NOT NECESSARILY RESTRICTED

TO, THE FOLLOWING:

(1) EXTENSION OF EXISTING SANITARY SEWER SYSTEM OR EXISTING ACID WASTE PIPING SYSTEM TO NEW

EQUIPMENT AS INDICATED ON PLANS.

(2) EXTENSION OF EXISTING DOMESTIC WATER SYSTEM TO NEW EQUIPMENT AS INDICATED ON PLANS.

(3) MODIFICATIONS TO EXISTING NATURAL GAS, STEAM, COMPRESSED AIR, VACUUM, AND DEIONIZED WATER

SYSTEM AS INDICATED ON PLANS.

(4) INSTALLATION AND CONNECTIONS TO EQUIPMENT FURNISHED BY OWNER.

(5) CONNECTIONS TO FIXTURES AND EQUIPMENT PROVIDED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS.

(6) MISCELLANEOUS WORK AS DESCRIBED HEREIN, AS SHOWN ON DRAWINGS, AND AS REQUIRED FOR A

COMPLETE SYSTEM.

4. PIPE SUPPORTS, PIPE SLEEVES AND WALL CEILING PLATES :

A. PROVIDE IN ACCORDANCE WITH THE VIRGINIA CONSTRUCTION CODE.

5. WASTE AND VENT PIPING (DEIONIZED) :

A. HIGH SILICON CAST IRON SOIL PIPE AND FITTING: PIPE SHALL BE BELL AND SPIGOT OR MODIFIED HUB, EXTRA

HEAVYWEIGHT CLOSED GRAIN ACID RESISTING AS REQUIRED BY SELECTED JOINTING METHOD. PIPE AND FITTINGS

SHALL BE MARKED WITH THE COLLECTIVE TRADEMARK OF THE CISPI.

(1) MATERIAL (PIPE AND FITTINGS): ASTM A-518-86, ASTM A-861-86, CONTAINING 14.5% SILICON (DURIRON).

(2) JOINTS: PROVIDE ANY ONE OF THE FOLLOWING TYPES TO SUIT PIPE FURNISHED.

A. MECHANICAL, COMPRESSION-TYPE (ASTM C564) MOLDED NEOPRENE GASKET. GASKETS SHALL SUIT

CLASS OF PIPE BEING JOINTED. DUAL-SERVICE GASKETS WILL NOT BE ACCEPTED.

B. MECHANICAL: MECHANICAL JOINT COUPLING CISPI 310 SHALL CONSIST OF A STAINLESS STEEL COUPLING

AND NEOPRENE GASKETS (ASTM C564) (CSA CAN/CSA-B602). DO NOT INSTALL BELOW GRADE.

B. PLASTIC PIPE: MAY BE USED FOR PIPING ABOVE GROUND IN ACCESSIBLE LOCATIONS. FOAM CORE PIPING IS NOT

ACCEPTABLE. ALL PLASTIC PIPE, FITTINGS AND COMPONENTS SHALL BE THIRD PARTY CERTIFIED TO NSF 14. CPVC

TYPE IV GRADE 1 SHALL NOT BE USED IN RETURN AIR PLENUMS.

(1) PIPE: CPVC TYPE IV GRADE 1 SCHEDULE 40 DWV, ASTM F 2618.

(2) FITTINGS: CPVC TYPE IV GRADE 1 SCHEDULE 40 ASTM D3311 FITTINGS FOR SOLVENT JOINTS.

(3) JOINTS: ASTM F656 PURPLE PRIMER, SOLVENT ASTM F493 (NOT PURPLE IN COLOR), JOINTS MADE IN

ACCORDANCE WITH ASTM D2855.

C. POLYPROPYLENE: ORION

(1) ABOVE GRADE NON-FIRE RATED PIPING: SCHEDULE 40 FLAME RETARDANT POLYPROPYLENE TO ASTM F1412

TOLERANCES, SHALL CONFORM TO ASTM D4101.

(2) ABOVE GRADE FIRE RATED PIPING: SCHEDULE 40 POLYVINYLIDENE FLUORIDE PVDF CONFORMING TO ASTM

F1673, SHALL CONFORM TO ASTM D3322 AND UL-723, ASTM E-84.

(3) FITTINGS:

A. ABOVE GROUND NON-FIRE RATED AREAS: SCHEDULE 40 FLAME RETARDANT POLYPROPYLENE

CONFORMING TO ASTM D4101 AND ASTM F1412, ASTM D3311. PROVIDE MECHANICAL JOINT. EACH

COUPLING SHALL HAVE AN OUTER BAND OF 300 SERIES STAINLESS STEEL PER ASTM B117. THE

MECHANICAL JOINT SHALL CONFORM TO ASTM F1412.

B. ABOVE GROUND FIRE RATED AREAS: SCHEDULE 40 POLYVINYLIDENE FLUORIDE PVDF PER ASTM F1673

CONFORMING TO ASTM D3322. MATERIAL SHALL MEET UL-723 (ASTM E84). FITTINGS SHALL CONFORM TO

ASTM D3311 AND ASTM F1673. THE JOINING SYSTEM SHALL BE MECHANICAL JOINT. EACH COUPLING

SHALL HAVE AN OUTER BAND OF 300 SERIES STAINLESS STEEL PER ASTM B117. THE JOINT SHALL

CONFORM TO ASTM F1412.

6. INTERIOR DOMESTIC WATER PIPING: (EXCLUDE DEIONIZED WATER)

A. COPPER TUBE AND FITTINGS:

(1) TUBE: ASTM B88, TYPE L, HARD DRAWN.

(2) FITTINGS: WROUGHT COPPER, ASME B16.22 OR CAST COPPER ALLOY ASME B16.18.

(3) JOINTS: ABOVE GROUND FLOOR: ASTM B32 LEAD FREE SOLDER, ASTM B813 LEAD FREE FLUX. LEAD FREE

SHALL MEAN LESS THAN 0.2 PERCENT LEAD.

7. PURE WATER PIPING: (INTERIOR DEIONIZED) (ALL PIPING, FITTINGS, VALVES, AND SOLVENT CEMENT SHALL BE PROVIDED

BY SAME MANUFACTURER):

A. LOW EXTRACTABLE POLYVINYL CHLORIDE (PVC) WITH A CELL CLASSIFICATION OF 12343.

(1) PIPE AND FITTINGS: ABOVE GRADE NON-FIRE RATED PRESSURE PIPE SCHEDULE 80 HARVEL LXT PVC ASTM

D1785 CUT TO LENGTHS IN FACTORY, PURGED WITH CLEAN FILTERED AIR TO REMOVE SHAVINGS. ALL PIPES

TO BE DOUBLE BAGGED IMMEDIATELY AFTER MANUFACTURE IN FDA APPROVED ANTI-STATIC POLYETHYLENE

SLEEVES THAT ARE HEAT SEALED. PIPING SYSTEM IS INTENDED FOR USE IN AMBIENT TEMPERATURES WHERE

THE FLUID DOES NOT EXCEED 140 DEG. F. THIS PRODUCT SHALL CARRY A TYPE 11 PRESSURE RATING AND

CONSISTENTLY MEET OR EXCEED THE APPLICABLE QUALITY ASSURANCE TEST REQUIREMENTS OF THESE

STANDARDS WITH REGARD TO WORKMANSHIP, BURST PRESSURE, FLATTENING RESISTANCE AND END

PRODUCT QUALITY. PIPING SHALL BE TRANSLUCENT ALLOWING FOR VISUAL JOINT INTEGRITY INSPECTION.

PIPING SHALL HAVE ULTRA-SMOOTH INTERIOR TO MINIMIZE BACTERIAL GROWTH. PIPE IDENTIFICATION

MARKING SHALL BE PROVIDED ON THE EXTERIOR PIPE SURFACE NOT EXCEEDING 5 FEET IN LENGTH MARKING

IDENTIFICATION SHALL INCLUDE THE MATERIAL DESIGNATION HARVEL LXT, PIPE SIZE, DIMENSIONS (SCHEDULE

80) AND PRODUCTION LOT FOR PRODUCT TRACEABILITY.

(2) VALVES: ALL VALVES SHALL BE HARVEL LXT MANUFACTURED FROM SAME LOW EXTRACTABLE POLYVINYL

CHLORIDE (PVC) WITH A CELL CLASSIFICATION OF 12343. VALVES SHALL BE TRUE UNION STYLE QUARTER

TURN BALL VALVES, SEATS SHALL BE PTFE, VALVE O-RINGS SHALL BE EPDM OR VITON. ALL VALVE UNION NUTS

SHALL HAVE BUTTRESS STYLE THREADS. ALL VALVE COMPONENTS SHALL BE REPLACEABLE. TRUE UNION

BALL VALVES SIZES 1/2” - 2” SHALL CARRY A MAXIMUM WORKING PRESSURE RATING OF 235 PSI NON-SHOCK @

73 DEG. F. VALVES SHALL BE PURGED WITH CLEAN FILTERED AIR TO REMOVE SHAVINGS. ALL VALVES TO BE

DOUBLE BAGGED IMMEDIATELY AFTER MANUFACTURER IN FDA APPROVED ANTI-STATIC POLYETHYLENE

SLEEVES THAT ARE HEAT SEALED.

(3) JOINING: ALL HARVEL LXT PIPING SHALL BE JOINED UTILIZING HARVEL ONE-STEP UPW GRADE SOLVENT

CEMENT. WELDS SHALL BE MADE UP IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

THE USE OF ANY OTHER MANUFACTURER'S PRIMERS OR SOLVENT CEMENT IS UNACCEPTABLE.

(4) ALL SYSTEM COMPONENTS SHALL BE MANUFACTURED IN THE USA BY AN ISO CERTIFIED MANUFACTURER.

(5) ALL ELBOWS SHALL BE DOUBLE 45 DEGREES TO REDUCE FRICTION LOSS.

8. ACCESS PANELS:

A. THE CONTRACTOR SHALL PROVIDE ACCESS PANELS IN ALL LOCATIONS WHERE REQUIRED FOR ACCESS TO

CONCEALED VALVES, JOINTS OR ANY OTHER EQUIPMENT OR MATERIALS REQUIRING INSPECTION OR MAINTENANCE.

ACCESS PANELS SHALL BE OF ADEQUATE SIZE AND PROPERLY LOCATED SO CONCEALED ITEMS WILL BE READILY

ACCESSIBLE FOR SERVICING OR FOR REMOVING AND REPLACING IF NECESSARY. ACCESS PANELS ARE NOT

REQUIRED IN CEILINGS FORMED OF REMOVABLE ACOUSTICAL PANELS. ACCESS PANELS SHALL BE MILCOR OR

EQUAL, METAL WITH CAM LOCK, CONTINUOUS HINGE AND MOUNTING TRIM. FINISH TO BE SELECTED BY ARCHITECT

FROM MANUFACTURER'S FULL RANGE OF FINISHES INCLUDING STAINLESS STEEL.

9. FAUCETS: (DEIONIZED WATER)

A. PURE WATER FAUCET SHALL BE WATER SAVER FAUCET CO. MODEL L7833 (DECK MOUNTED APPLICATIONS) FOR

DEIONIZED WATER, FORGED BRASS EXTERIOR CASING WITH POLISHED CHROME PLATED FINISH, INERT

POLYPROPYLENE INTERIOR LINING, DIAPHRAGM TYPE VALVE WITH BRASS VALVE STEM AND BONNET WITH INERT

ELASTOMER DIAPHRAGM, MANUAL ON/OFF CONTROL, BLACK NYLON KNURLED HANDLE WITH COLOR-CODED INDEX

DISC, 6 INCH BRASS RISER, 3/8 INCH IPS CONNECTION, SERRATED PLASTIC HOSE END. EACH FAUCET SHALL BE

FULLY ASSEMBLED AND TESTED AT THE FACTORY PRIOR TO SHIPMENT.

10. COMPRESSED AIR PIPING:

A. PIPE: 2 INCH AND SMALLER; STEEL ASTM A53 SEAMLESS OR TYPE F SCHEDULE 40 OR COPPER ASTM B88 TYPE K;

NIPPLES: STEEL FOR STEEL PIPING; FITTINGS: MALLEABLE IRON CLASS 150 CAST IRON; WROUGHT COPPER; JOINTS:

THREADED, BRAZED.

11. INTERIOR NATURAL GAS PIPING:

A. PIPE: BLACK STEEL, ASTM A 53 GRADE B OR A 106, SCHEDULE 40.

B. NIPPLES: STEEL, ASTM A733, SCHEDULE 40.

C. FITTINGS, 2 INCHES AND SMALLER: MALLEABLE IRON, SCHEDULE 40, ASME B16.3. (THREADED)

D. JOINTS: THREADED ENDS (ASME B1.20.1). PIPE-JOINT COMPOUND OR TAPE APPLIED TO MALE THREADS ONLY;

WELDED. DO NOT USE GAS FITTERS CEMENT, EXCEPT ON OUTLET CAPS.

E. GAS PIPING INSTALLED IN CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING FITTINGS OR RUNNING

THREADS.

12: VALVES: (NATURAL GAS)

A. 4" AND SMALLER: BRONZE 2 PIECE BALL VALVE, CHROME-PLATED BALL, CSA &UL LISTED.

B. GAS VALVES WITH NIPPLES: CHICAGO FORGED BRASS QUARTER TURN 3/8" WITH CHECK VALVE, COLOR CODED

LEVER HANDLE, ADA.

13. VACUUM PIPING:

A. PIPE: SEAMLESS COPPER TYPE L OR ACR, ASTM B280, HARD TEMPER. COPPER, BRASS OR BRONZE FITTINGS MADE

FOR BRAZED JOINING. BRAZED JOINTS, AWS A5.8 FILLER MATERIAL.

14. VALVES: (DOMESTIC WATER) (EXCLUDE DEIONIZED WATER)

A. BALL VALVES: VALVES 2 1/2 INCH AND SMALLER SHALL BE RATED 150 PSI SWP AND 600 PSI NON-SHOCK WOG AND

SHALL HAVE 2 PIECE CAST BRONZE BODIES, TFE SEATS, FULL PORT, SEPARATE PACKNUT WITH ADJUSTABLE STEM

PACKING, ANTI-BLOWOUT STEMS AND CHROME-PLATED BRASS/BRONZE BALL. VALVE ENDS SHALL HAVE FULL

DEPTH ANSI THREADS OR FLANGED AND BE MANUFACTURED TO COMPLY WITH MSS-SP110. [NIBCO T585-70

(THREADED)

NOTE: WHERE PIPING IS INSULATED, BALL VALVES SHALL BE EQUIPPED WITH 2” EXTENDED HANDLES OF

NON-THERMAL CONDUCTIVE MATERIAL. ALSO, PROVIDE A PROTECTIVE SLEEVE THAT ALLOWS OPERATION OF

THE VALVE WITHOUT BREAKING THE VAPOR SEAL OR DISTURBING THE INSULATION. MEMORY STOPS, WHICH

ARE FULLY ADJUSTABLE AFTER INSULATION IS APPLIED, SHALL BE INCLUDED. [NIBCO T585/70NS (THREADED)

B. SHOCK ABSORBERS: JOSAM "ABSORBOTRON" SERIES 75000 OR EQUAL. (SA-A MAX. 11 SFU). PROVIDE ON HOT AND

ALL COLD WATER BRANCHES INCLUDING TEMPERED WATER, CONDENSER WATER AND DEIONIZED WATER. JOB

FABRICATED AIR CHAMBERS WILL NOT BE PERMITTED. (ASME/ANSI A112.26.1 OR ASSE 1010)

15. TEMPERING VALVE: (LEONARD OR EQUAL)

A. CABINET ASSEMBLY FOR COMBINATION EMERGENCY SHOWER: TV-1, LEONARD TM-800-STSTL-EXP WITH DURA-TROL

SOLID BIMETAL THERMOSTAT AND INTERNAL COLD WATER BYPASS. LOCKING TEMPERATURE REGULATOR TO

PREVENT ACCIDENTAL MOVEMENT, SET FOR 85 DEG. F. (29 DEG. C.). MIXING VALVE SHALL CLOSE DOWN ON FAILURE

OF COLD WATER SUPPLY AND HAVE SPECIAL INTERNAL COLD WATER BYPASS CAPABLE OF 20 GPM AT 30 PSI UPON

FAILURE OF HOT WATER SUPPLY. FULL 1" TOP OR BOTTOM INLETS AND 1 1/4" TOP OUTLET. INTEGRAL WALL

SUPPORT AND DIAL THERMOMETER (RANGE 0 TO 140 DEG. F., -10 TO 60 DEG. C.). ROUGH BRONZE FINISH. EXPOSED

STAINLESS STEEL CABINET WITH HINGED DOOR AND CYLINDER LOCK.

B. INDIVIDUAL FIXTURE TEMPERING VALVES: TV-2

(1) PROVIDE CALEFFI MODEL 5213 UNDER-SINK ASSE 1070 AND CSA B-125 PRESSURE BALANCED THERMOSTATIC

TEMPERING VALVE WITH SCALD PROTECTION FOR SINGLE LAVATORY AND HAND SINK APPLICATIONS. PROVIDE

AT ALL LAVATORY AND HAND SINK LOCATIONS INCLUDING KITCHEN HAND SINKS. SET VALVE TO 110 DEG. F.

16. VALVES: (COMPRESSED & VACUUM AIR)

A. GENERAL: ALL VALVES AND SPECIALTIES SHALL BE SUITABLE FOR 125 PSI WORKING PRESSURE EXCEPT AS

OTHERWISE INDICATED. EACH ITEM SHALL HAVE THREADED OR FLANGED CONNECTIONS AS APPLICABLE TO MATCH

JOINTS SPECIFIED FOR ITS RESPECTIVE SERVICE.

B. ACCEPTABLE MANUFACTURERS SUBJECTED TO COMPLIANCE WITH REQUIREMENTS ARE NIBCO, CRANE, APOLLO,

CENTER LINE, POWELL, AND MCDONALD.

(1) BALL VALVES: VALVES 2 1/2 INCH AND SMALLER SHALL BE XOMOX CLASS 150 RATED 600 PSI COLD WORKING

PRESSURE AND SHALL HAVE 2-PIECE CAST BRONZE BODIES, FTE SEATS, FULL PORT, SEPARATE PACKNUT WITH

ADJUSTABLE STEM PACKING, ANTI-BLOWOUT STEMS AND CHROME-PLATED BRASS/BRONZE BALL. VALVE ENDS

SHALL HAVE FULL DEPTH ANSI THREADS AND BE MANUFACTURED TO COMPLY WITH MSS SP100. WHERE

APPLICABLE FOR ISOLATION, VALVES SHALL BE IN COMPLIANCE WITH OSHA LOCKOUT/TAGOUT STANDARD

1910-147 AND SHALL BE DESIGNED TO VENT AIR TO ATMOSPHERE UPON CLOSURE. VALVES SHALL BE FITTED

WITH LOCKING DEVICE SO VALVES CAN BE LOCKED IN OPEN OR CLOSED POSITION.

(2) GATE VALVES: VALVES 2-1/2 INCH AND LARGER SHALL BE CLASS 125 IRON BODY AND BONNET, CONFORMING

TO ASTM A-126 CLASS B CAST IRON, BRONZE MOUNTED WITH BRONZE RING IN EACH SEAT, FLANGED END, WITH

ARAMID FIBERS WITH GRAPHITE PACKING AND GLAND ASSEMBLY.

(3) GLOBE VALVES: VALVES 2 INCH AND SMALLER SHALL BE CLASS 150, BODY AND BONNET OF ASTM B-62 CAST

BRONZE COMPOSITION, THREADED ENDS, SILICON BRONZE ALLOY STEM, REPLACEABLE TEFLON DISC, BRASS

PACKING GLAND, TEFLON-IMPREGNATED PACKING AND MALLEABLE HANDWHEEL.

D. QUICK DISCONNECTS FOR COMPRESSED AIR CONNECTIONS AS DIRECTED BY THE OWNER.

17. CLEANOUTS:

A. SAME SIZE AS PIPE SERVED UP TO 4 INCHES. CLEANOUTS SHALL BE EASILY ACCESSIBLE. ALL CLEANOUT PLUGS

SHALL BE BRONZE, SET IN GRAPHITE GREASE. (ASTM A74, ASME A112.3.1, ASME A112.36.2M) COVERS SHALL BE SET

FLUSH WITH FINISHED FLOOR OR WALL.

(1) HORIZONTAL PIPES ABOVE GRADE: CLEANOUTS SHALL BE FERRULE WITH BRONZE SCREW PLUG IN FITTING OR

TAPPED CAST IRON FERRULE WITH BRONZE PLUG.

(2) FLOORS: FLOOR CLEANOUTS SHALL HAVE CAST IRON BODY, BRONZE PLUG, AND ABS OR CAST IRON FRAME

WITH ROUND OR SQUARE ADJUSTABLE HEAVY-DUTY SCORIATED SECURED NICKEL BRONZE TOP.

A. MECHANICAL ROOMS AND HEAVY TRAFFIC FLOORS: JOSAM SERIES 55000-X-2-SD CAST IRON FLOOR

CLEANOUT WITH SECURED HEAVY-DUTY ROUND BRONZE TRACTOR COVER.

B. LIGHT TRAFFIC FLOORS: JOSAM SERIES 55000 CAST IRON FLOOR CLEANOUT WITH (SECURED)(VANDAL

RESISTANT) COVERS OF SATIN BRONZE FOR FINISHED CONCRETE FLOORS AND SATIN FINISH NIKALOY

ELSEWHERE.

C. FOR ACID WASTE SYSTEM : (DEIONIZED WATER) SHALL BE OF THE SAME MATERIAL USED FOR THE ACID

WASTE PIPING SYSTEM WITH COUNTER-SUNK PLUG, ADJUSTABLE TOP NICKEL BRONZE COVER WITH

“AWCO” (ACID WASTE CLEANOUT) CAST IN COVER.

18. FLOOR DRAINS: FOR LT-1 AND ICE MACHINE: JOSAM SERIES 30000-E1 CAST IRON FLOOR DRAIN BODY, FLASHING COLLAR,

AND SECURED NIKALOY ADJUSTABLE EXTENDED RIM STRAINER. SET TOP OF RIM FLUSH WITH FINISHED FLOOR.

19. PLUMBING FIXTURES:

A. GENERAL: FIXTURES EQUAL TO THOSE AS HEREINAFTER SPECIFIED SHALL BE FURNISHED AND INSTALLED

COMPLETE WITH ALL SUPPLIES, WASTE AND VENT CONNECTIONS, ALL FITTINGS, ALL NECESSARY HANGERS AND

SUPPORTS, BOLT CAPS, FAUCETS, VALVES AND TRAPS. ALL TRIM SHALL BE BRASS WITH POLISHED CHROMIUM

PLATED FINISH WITH CHROME SETSCREW ESCUTCHEON AT WALL, EXCEPT FIXTURE SUPPLY PIPES MAY BE

CHROMIUM PLATED COPPER WITH CHROME SETSCREW ESCUTCHEONS AT WALL. TRAPS SHALL BE (17 GAUGE) CAST

BRASS WITH CLEANOUT PLUG. FASTENERS SHALL REMAIN OUT OF SIGHT.

B. PROVIDE LOCK-SHIELD, LOOSE-KEY OR SCREW DRIVER PATTERN POLISHED CHROMIUM PLATED ANGLE STOPS, WITH

EACH SINK FAUCET.

DESIGNATION STANDARD FIXTURE TYPE

SK-2 COUNTER BY OWNER. ELKAY LUSTERTONE DLR222212, 12" DEEP. PROVIDE POLISHED

CHROME FAUCET FOR DOMESTIC WATER EQUAL TO CHICAGO MODEL 930-317XKCP MIXING

FAUCET WITH MODEL GN2BVB 6" SWING GOOSENECK SPOUT WITH ATMOSPHERIC VACUUM

BREAKER WITH LEVER HANDLES, 6 3/4" HIGH ARC SWIVEL SPOUT, 1.5 GPM AT 60 PSI

DISCHARGE, ROSETTA SPRAY NON-AERATED FLOW DEVICE AND LK-35 STRAINER.

LT-1 LAUNDRY TUB: FIAT MODEL L-1 SINGLE COMPARTMENT LAUNDRY TUB, MOLDED STONE,

WALL MOUNTED WITH HEAVY GAGE GALVANIZED STEEL BRACKETS, SIDE FILLERS AND

BOTTOM TUB SUPPORT, A-1 FAUCET WITH SWING SPOUT, GRID STRAINER AND TAILPIECE.

LT-2 LAUNDRY TUB: OWNER PROVIDED 2-COMPARTMENT LAUNDRY TUB. OWNER PROVIDED

FAUCET. CONTRACTOR PROVIDED APPURTENANCES.

DESIGNATION HANDICAPPED FIXTURE TYPE (ADA)

SK-1 COUNTER BY OWNER. ELKAY LUSTERTONE LRAD1522, 6 1/2" DEEP, 18 GAGE. PROVIDE

POLISHED CHROME FAUCET FOR DOMESTIC WATER EQUAL TO CHICAGO FAUCET MODEL

929-317XKCP ADA WITH 4" LEVER HANDLES, 6 3/4" HIGH-ARCH SWIVEL SPOUT, 1.5 GPM AT

60.0 PSI DISCHARGE, ROSETTA SPRAY NON-AERATED FLOW DEVICE AND LK-35 STRAINER.

EEWS COMBINATION EMERGENCY EYE/FACE DRENCH SHOWER: ENCON MODEL 01050251

BARRIER-FREE 1 1/4" STAINLESS STEEL COMBINATION SUPPLY, 10" DIAMETER ABS PLASTIC

20 GPM SHOWER HEAD, 1" STAY-OPEN CP BALL VALVE, PROVIDE 20 GPM FLOW THRU

CIRCUIT SETTER, WITH STAINLESS STEEL PULL ROD AND HANDLE ASSEMBLY, 10" DIAMETER

ABS PLASTIC WASH BOWL, EYE WASH SPRAY HEAD WITH SELF-ADJUSTING REGULATOR TO

FLOW 3.2 GPM, ACETEL HEADS WITH HINGED COVERS, BCP WYE, 1/2" STAY-OPEN VALVE.

PROVIDE 1 1/4" WASTE CONNECTION FOR BOWL DRAIN. PROVIDE LEONARD

TM-800-STSTL-EXP-LF-BWE-EXP WITH DURA-TROL SOLID BIMETAL THERMOSTAT AND

INTERNAL COLD WATER BYPASS SET FOR 85 DEG. F (29 DEG. C), MIXING VALVE SHALL

CLOSE DOWN ON FAILURE OF COLD WATER SUPPLY AND HAVE SPECIAL INTERNAL COLD

WATER BYPASS CAPABLE OF 20 GPM AT 30 PSI UPON FAILURE OF HOT WATER SUPPLY, DIAL

THERMOMETER (RANGE 0 TO 140 DEG. F, -10 TO 60 DEG. C) ROUGH BRONZE FINISH.

ES EMERGENCY EYE SHOWER: ENCON MODEL 01052522 BARRIER-FREE 1 1/4" STAINLESS

STEEL COMBINATION SUPPLY, 10" DIAMETER ABS PLASTIC 20 GPM SHOWER HEAD, 1"

STAY-OPEN CP BALL VALVE, PROVIDE 20 GPM FLOW THRU CIRCUIT SETTER, WITH

STAINLESS STEEL PULL ROD AND HANDLE ASSEMBLY. PROVIDE LEONARD

TM-800-STSTL-EXP-LF-BWE-EXP WITH DURA-TROL SOLID BIMETAL THERMOSTAT AND

INTERNAL COLD WATER BYPASS SET FOR 85 DEG. F (29 DEG. C), MIXING VALVE SHALL

CLOSE DOWN ON FAILURE OF COLD WATER SUPPLY AND HAVE SPECIAL INTERNAL COLD

WATER BYPASS CAPABLE OF 20 GPM AT 30 PSI UPON FAILURE OF HOT WATER SUPPLY, DIAL

THERMOMETER (RANGE 0 TO 140 DEG. F, -10 TO 60 DEG. C) ROUGH BRONZE FINISH.

EEW-1 EYEWASH: COUNTER MOUNT EYEWASH/DRENCH HOSE STATION GUARDIAN MODEL G5022

SWIVEL EYEWASH HEADS WITH HINGED COVERS. RETRACTABLE 8 FEET LONG RUBBER

HOSE, SQUEEZE LEVER HANDLE, UNIVERSAL LANGUAGE SIGN AND MOUNTING BRACKET.

PROVIDE ATMOSPHERIC VACUUM BREAKER WATTS NO. 288A-C. PROVIDE LAWLER MODEL

911EF PRESSURE COMPENSATING THERMOSTATIC MIXING VALVE (ASSE 1071), SET

TEMPERATURE TO 85 DEG. F.

20. INSULATION:

A. ALL DOMESTIC WATER PIPING SHALL BE INSULATED. INSULATION SHALL BE JOHNS MANVILLE, OWENS CORNING, OR

ARMSTRONG. ALL MATERIALS AND PVC TYPE FITTING COVERS USED SHALL HAVE COMPOSITE FLAME-SPREAD

RATING NOT EXCEEDING 25 AND A SMOKE-DEVELOPED RATING NOT EXCEEDING 50, AS TESTED UNDER PROCEDURE

ASTM E-84, NFPA 90A AND 90B.

B. PIPING INSULATION: FIBERGLASS INSULATION SHALL BE 1 INCH THICK AND SHALL HAVE A MINIMUM THERMAL

RESISTANCE (R) OF 4.0 PER INCH OF THICKNESS AT A MEAN TEMPERATURE OF 75 DEG. F. FIBERGLASS INSULATION

SHALL HAVE A WHITE KRAFT BONDED TO ALUMINUM FOIL, REINFORCED WITH FIBERGLASS YARN JACKET, LAP

JOINTS, TAPE AND SEAL.

21. INSTALLATION:

A. GENERAL:

(1) SUSPENDED HORIZONTAL PIPING SHALL BE SUPPORTED BY ADJUSTABLE WROUGHT STEEL CLEVIS HANGERS.

WHERE SUPPORTS BEAR ON COPPER PIPE, THEY SHALL BE COPPER PLATED. WHERE SUPPORTS BEAR ON

INSULATED PIPING, PROVIDE INSULATION SHIELD. CHAIN, STRAP, WIRE OR OTHER MAKESHIFT DEVICES WILL

NOT BE PERMITTED AS HANGERS OR SUPPORTS.

(2) MAXIMUM HANGER SPACING FOR REVERSE OSMOSIS PIPING SHALL CONFORM TO THE FOLLOWING

MANUFACTURER'S REQUIREMENTS (BASED ON SYSTEM OPERATING TEMPERATURE OF 73 DEGREES F):

PIPE SIZE (IN.) SPACING (FT.)

1/2 5

3/4 5-1/2

1 6

1-1/4 6

1-1/2 6-1/2

2 7

(3) INSTALL BRANCH PIPING FOR WATER, DEIONIZED WATER, COMPRESSED AIR, NATURAL GAS AND WASTE, FROM

THE RESPECTIVE PIPING SYSTEMS AND CONNECT TO ALL VALVES, COCKS, OUTLETS, CASEWORK, CABINETS

AND EQUIPMENT, INCLUDING THOSE FURNISHED BY THE OWNER OR SPECIFIED IN OTHER SECTIONS OF THESE

SPECIFICATIONS.

(4) INSTALL TRIM AND FITTINGS PROVIDED WITH CASEWORK, CABINETS AND LABORATORIES, INCLUDING THOSE

FURNISHED BY THE OWNER, BUT NOT INSTALLED AT POINT OF FABRICATION.

(5) WELDED JOINTS SHALL BE FUSION WELDED BY QUALIFIED WELDERS IN ACCORDANCE WITH ANSI B31.1

SECTION 6, UNLESS OTHERWISE REQUIRED. MITERING OR NOTCHING PIPE TO FORM ELBOWS AND TEES, AND

DRILLING OR PUNCHING TO MAKE CONNECTIONS WILL NOT BE PERMITTED.

(6) COMPRESSION GASKET JOINTS FOR CAST IRON SEWER PIPE SHALL BE MADE WITH NEOPRENE COMPRESSION

GASKETS CONFORMING TO ASTM C564.

(7) NO-HUB JOINTS FOR CAST IRON PIPES SHALL BE MADE WITH NEOPRENE GASKETS (ASTM C564) AND STAINLESS

STEEL CLAMPS CONFORMING TO CISPI STANDARD 310.

(8) MECHANICAL JOINTS ELASTOMERIC SEALING SLEEVE FOR CAST IRON PIPE SHALL BE IN ACCORDANCE WITH

ASTM C564.

(9) SOLVENT CEMENT FOR PVC PIPING SHALL BE HANDLED IN ACCORDANCE WITH ASTM F402.

(10) PLASTIC PIPE SHALL NOT BE LOCATED IN RETURN AIR CEILING PLENUMS.

(11) PLASTIC PIPE SHALL NOT PENETRATE A FIRE ASSEMBLY OR SMOKESTOP.

(12) PROVIDE CHROME PLATED ESCUTCHEONS AT ALL LOCATIONS WHERE PIPING PENETRATES FLOORS, WALLS

AND CEILINGS IN EXPOSED LOCATIONS, EXCEPT IN MECHANICAL ROOMS.

B. PIPING SHALL CONFORM TO THE FOLLOWING:

(1) WASTE PIPING:

A. SLOPE WASTE PIPING AS FOLLOWS:

PIPE SIZE MINIMUM PITCH

WASTE AND VENT

2-1/2 INCH & SMALLER 1/4" TO THE FOOT

3 INCH & LARGER 1/8" TO THE FOOT

B. CHANGES IN DIRECTION OF PIPING SHALL BE MADE WITH FITTINGS.

C. CONTRACTOR IS CAUTIONED TO VERIFY INVERT OF SANITARY SEWER AND TO COORDINATE INVERTS OF

NEW WORK TO SUIT CONDITIONS ENCOUNTERED.

D. SANITARY SEWER SHALL BE PROVIDED COMPLETE WITH ALL PLUMBING FIXTURES, DRAINS, ETC.,

PROPERLY CONNECTED AND VENTED IN ACCORDANCE WITH THE APPLICABLE CODES.

(2) DOMESTIC WATER:

A. GRADE ALL LINES TO FACILITATE DRAINAGE.

B. CONNECT BRANCH LINES AT BOTTOM OF MAIN SERVING FIXTURES BELOW AND PITCH DOWN SO THAT

MAIN MAY BE DRAINED THROUGH FIXTURE.

(3) GAS:

A. INSTALL GAS PIPING WITH PLUGGED DRIP POCKETS AT LOW POINTS AND AHEAD OF THE CONNECTION TO

EACH PIECE OF EQUIPMENT. ENTIRE GAS PIPING INSTALLATION SHALL BE IN ACCORDANCE WITH

REQUIREMENTS OF VIRGINIA CONSTRUCTION CODE.

B. MINIMUM SLOPE SHALL BE 1/4 INCH PER FIFTEEN FEET IN DIRECTION OPPOSITE FLOW.

C. SHUT-OFF COCK SHALL BE PROVIDED AT EACH BURNER, IF NOT PROVIDED WITH THE RESPECTIVE

EQUIPMENT.

22. TESTS:

A. GENERAL: CONTRACTOR SHALL PROVIDE ALL INSTRUMENTS, MATERIALS, AND LABOR REQUIRED. TESTS SHALL BE

MADE IN THE PRESENCE OF THE OWNER OR AUTHORITY HAVING JURISDICTION, OR AS OTHERWISE DIRECTED BY,

THE ARCHITECT, WHO SHALL BE GIVEN FIVE (5) DAYS NOTICE BY THIS CONTRACTOR OF HIS READINESS TO

PERFORM SUCH TESTS. ANY LEAKS THAT DEVELOP DURING THE TESTS SHALL BE REPAIRED BY REMAKING THE

JOINT OR REPLACING PIPE AND FITTINGS. TEMPORARY CAULKING WILL NOT BE PERMITTED. NO PIPING SHALL BE

INSULATED OR CONCEALED UNTIL IT HAS BEEN TESTED, WITH RESULTS ACCEPTABLE TO THE ARCHITECT. AIR

TESTING WILL BE ACCEPTABLE WHERE PERMITTED BY THE VIRGINIA CONSTRUCTION CODE. TEST SYSTEMS EITHER

IN ITS ENTIRETY OR IN SECTIONS.

B. WASTE AND VENT SYSTEMS: CONDUCT TESTS BEFORE FIXTURES ARE CONNECTED. CONDUCT WATER TEST AS

DIRECTED IN ACCORDANCE WITH THE VIRGINIA CONSTRUCTION CODE AND THIS SPECIFICATION.

(1) WATER TEST: IF ENTIRE SYSTEM IS TESTED, TIGHTLY CLOSE ALL OPENINGS IN PIPES EXCEPT HIGHEST

OPENING AND FILL SYSTEM WITH WATER TO POINT OF OVERFLOW. IF SYSTEM IS TESTED IN SECTIONS,

TIGHTLY PLUG EACH OPENING EXCEPT HIGHEST OPENING OF SECTION UNDER TEST, FILL EACH SECTION WITH

WATER AND TEST WITH AT LEAST 10-FOOT HEAD OF WATER. IN TESTING SUCCESSIVE SECTIONS, TEST AT

LEAST UPPER 10 FEET OF NEXT PRECEDING SECTION SO THAT EACH JOINT OR PIPE EXCEPT UPPERMOST

10-FOOT HEAD OF WATER. KEEP WATER IN SYSTEM, OR IN PORTION UNDER TEST, FOR AT LEAST 15 MINUTES

BEFORE INSPECTION STARTS. SYSTEM SHALL THEN BE TIGHT AT ALL JOINTS.

C. POTABLE WATER SYSTEM: TEST AFTER INSTALLATION OF PIPING AND DOMESTIC WATER HEATERS, BUT BEFORE

PIPING IS CONCEALED, BEFORE COVERING IS APPLIED AND BEFORE PLUMBING FIXTURES ARE CONNECTED. FILL

SYSTEMS WITH WATER AND MAINTAIN HYDROSTATIC PRESSURE OF 125 PSIG OR AT 50 PERCENT HIGHER THAN

ACTUAL OPERATING PRESSURE WHICH EVER IS GREATER FOR ONE HOUR DURING INSPECTION AND PROVE TIGHT

WITHOUT ANY LOSS OF PRESSURE.

D. GAS SYSTEM: GAS PIPING SHALL BE TESTED AND INSPECTED IN ACCORDANCE WITH VIRGINIA CONSTRUCTION

CODE.

E. VACUUM SYSTEM: PRESSURE TEST AND CROSS-CONNECTION TEST SHALL COMPLY WITH PARAGRAPH 4-10, NFPA

99, HEALTH CARE FACILITIES.

23. DISINFECTION: AFTER TESTS HAVE BEEN SUCCESSIVELY COMPLETED, THOROUGHLY FLUSH AND DISINFECT THE NEW

INTERIOR DOMESTIC WATER DISTRIBUTION SYSTEM PIPING IN ACCORDANCE WITH THE VIRGINIA CONSTRUCTION CODE.

24. CLEANING:

A. REMOVE TRASH, PLASTER, DUST, PAINT SPOTS AND ALL FOREIGN MATTER FROM INSIDE AND OUTSIDE OF ALL

FIXTURES AND EQUIPMENT.

B. THE CONTRACTOR SHALL CHECK EACH LENGTH OF PIPE BEFORE IT IS PUT IN PLACE TO MAKE CERTAIN THERE IS

NOT FOREIGN MATERIAL (STONES, SAND, ETC.) IN THE SYSTEMS. PROVIDE TEMPORARY BYPASS AROUND

EQUIPMENT IF OR AS REQUIRED. ALL PLUMBING PIPES SHALL BE THOROUGHLY FLUSHED WITH WATER TO REMOVE

CONSTRUCTION DEBRIS BEFORE FINAL CONNECTIONS ARE MADE TO EQUIPMENT AND FIXTURES.

25. REPORTS: REPORT OF CLEANING, STERILIZING AND TESTING: CONTRACTOR SHALL VERIFY IN WRITING BEFORE

COMPLETION OF THE JOB THAT ALL SPECIFIED CLEANING PROCEDURES, TESTS AND STERILIZING HAVE BEEN

PERFORMED, WITH RESULTS AS SPECIFIED OR AS REQUIRED BY CODES.

26. CATALOG DATA FOR OWNER: FURNISH ONE BOUND COPY OF CATALOG DATA ON EACH MANUFACTURED ITEM OF

EQUIPMENT USED IN THE PLUMBING WORK, COMPLETE WITH INDEX LISTING THE PRODUCTS ALPHABETICALLY

BY NAME, TOGETHER WITH THE NAMES AND ADDRESSES OF MANUFACTURERS, SALES, AND SERVICE

REPRESENTATIVES. PROVIDE TWO (2) BOUND COPIES OF OPERATING AND MAINTENANCE INSTRUCTIONS OF

EACH ITEM OF EQUIPMENT, AND ONE DIGITAL COPY ALL IN SAME FORMAT, CONTENT AND SEQUENCE.

PLUMBING SYSTEM NOTES AND SPECIFICATIONS

Page 14: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR NEW WORK PLAN - PLUMBINGSCALE: 1/8" = 1'-0"

LAB

5029LAB

5029B

CORRIDOR

CR-5B

LAB

5005BLAB

5005

ICE

E03

LAB

5014

CORRIDOR

CR-5A

LAB

5034

LAB

5026

LAB

5016

OFFICE

5016B

EXISTING PLUMBING SINKS, EYEWASH,

FAUCETS AND PIPING TO REMAIN

1

1 2

2

2

2

2

2

2

2 2

2

2

2

2

22

1

PLUMBING APPURTENANCES SHALL INCLUDE BUT NOT LIMITED TO

THE FOLLOWING: ALL FITTINGS, HANGERS AND SUPPORTS, BOLT

CAPS, VALVE SUPPLIES, TRAPS, TRIM SUCH AS ESCUTCHEONS,

PIPING COVERS, TRAP WRAP AND LOOSE KEY ANGLE STOPS.

3 51

6

6

3 5

18 21

2

2

2

EX 3"W DN,

2"VTR

3"W, 2"V

10

3" STANDPIPE

EX 1"CW 11

EX 1"HW 11

9

EX 3"W,

2"VTR

DI

2"W, 2"V

6 8

2"

7

EX 3"W DNSA-A

DI

13

GA

13

DIG

A

6 8EX 2"W, 2"V

SA-A

2"W

16

16

14

GLASSWARE

WASHER #1

GLASSWARE

WASHER #2

12

17 20

AUTOCLAVE

19

3 5

6

3 5 7

21 23

18 21

8

6 8

3 5 7 31 378

3 5 7

18 23 31

23

25

23

18 21 23

3 5 7

22 23

18

31

7

31

7

27

37

18 31

EX. 2"VTR29 3028 312"W, 2"V

5 26

23

18

18

LT-1

28 29 30

31 32

2"W, 2"V

G

1/2"

1/2"

1"

1/2"

1/2"

G

G1"

1/2"

1/2"

1/2"

1613

1613

LT-2

15

12 17 2015

1/2" 33

7

1/2"

33

1"

1/2"

2"W 34

ABV FL

4

EX 2"W,

2"VTR

NEW FD

EX FD

EX EEWS

TO REMAIN35

1 1/4"TW DN

1"H&CW DN 31

1/2"

2"CW

1 1/2"HW

1 1/4"TW DN

EEWS

TW

NEW ES

1 1/4"TW

35

1"H&CW DN31

1"

ES RELOCATED

1 1/4"TW35

1"H&CW DN

31

1/2"

CS-3

EX 2"CW

RISER

EX 1 1/2"HWEX 1/2"HWR DN

2"

1 1/2"

CS-1 1/2"

1/2"

2"

CS-21/2"

1"H&CW DN 31

1 1/4"TW DN

EX EEWS

TO REMAIN35

36

36

ADR

SK-1

SK-1

8

SK-2

7

31

SK-1

3 5 7

8 18 21 31

EX

HOOD

14

SK-2

SK-2 SK-2

LAB

5017

35

1"H&CW DN 31

NEW ES

1"

5014A

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

DHH/CAD

PLAN NOTES:

1. MAINTAIN EXISTING DEIONIZED WATER.

2. NO NEW PLUMBING WORK THIS ROOM.

3. PROVIDE NEW FAUCETS, TAILPIECE, TRAP AND APPURTENANCES FOR

COMPLETE ASSEMBLY.

4. MODIFY EXISTING DRIP DRAIN. PROVIDE NEW RAISED RIM FLOOR DRAIN IN

SAME LOCATION.

5. PROVIDE WATTS SERIES USG-B-M1 UNDER SINK GUARDIAN ASSE 1070 AND CSA

B-125 THERMOSTATIC TEMPERING VALVE FOR SINGLE SINK DOMESTIC WATER

APPLICATIONS.

6. PROVIDE NEW NATURAL AND COMPRESSED AIR GAS VALVES.

7. PROVIDE NEW VALVED HOT, COLD AND DEIONIZED WATER PIPING FROM NEW

FIXTURE FAUCET TO EXISTING WATER PIPING WITH MINIMUM 1/2" SIZE.

8. PROVIDE NEW NATURAL GAS AND COMPRESSED AIR PIPING FROM VALVES TO

EXISTING GAS AND AIR PIPING WITH MINIMUM 1/2" SIZE.

9. SEE GLASSWARE DRAIN DETAIL SHEET P0.1.

10. EXTEND NEW 3" WASTE TO EXISTING 3" WASTE PIPING DOWN.

11. EXTEND 1/2" VALVED HOT AND COLD WATER PIPING FROM GLASSWASHERS (2)

TO EXISTING 1" HOT AND COLD PIPING. CONTRACTOR SHALL VERIFY LOCATION

IN FIELD. EXTEND 1/2" VALVED COLD WATER PIPING FROM EXISTING 1"CW

PIPING FOR CONDENSATE WATER AND TEMPERED WASTE. SEE GLASSWARE

PIPING CONNECTION DETAIL SHEET P0.1.

12. EXTEND 1/2" VALVED DEIONIZED WATER PIPING FROM GLASSWASHERS (2) TO

EXISTING 1" DEIONIZED PIPING. CONTRACTOR SHALL VERIFY LOCATION IN

FIELD. UNIT PROVIDED 1/2" HOSE WITH 3/4" FEMALE CONNECTION.

13. CEILING SERVICE PANEL. SEE CEILING SERVICE PANEL DETAIL SHEET E1.3.

EACH PANEL SHALL SUPPLY TWO QUICK CONNECTIONS FOR NATURAL GAS.

14. PROVIDE NEW GAS, VACUUM, COMPRESSED AIR AND WATER VALVES.

CONNECT TO EXISTING LINES.

15. CONTRACTOR SHALL VERIFY COLD WATER AND HOT WATER PRESSURE IN

FIELD. IF COLD WATER PRESSURE LESS THAN 14.5 PSI, IF HOT WATER

PRESSURE 5.8 PSI, THEN CONTRACTOR SHALL ALERT ENGINEER FOR

POSSIBLY BOOSTING PRESSURE. IF EITHER HOT OR COLD WATER PRESSURE

ARE IN EXCESS OF 145 PSI, THEN CONTRACTOR SHALL ALERT ENGINEER FOR

POSSIBLY REDUCING PRESSURE WITH A VALVE.

16. PROVIDE 3/8" BRAIDED STAINLESS STEEL HOSE WITH 3/8" FEMALE INLET AND

3/8" MALE OUTLET FROM PANEL TO WORK STATION, 72" LENGTH FOR NATURAL

GAS CONNECTION (2) PER PANEL. PROVIDE QUICK-CONNECT FITTINGS COLOR

CODED FOR SERVICE AND KEYED TO PREVENT CONNECTION TO THE WRONG

SERVICE.

17. PROVIDE ATMOSPHERIC VACUUM BREAKER ASSE 1001 WATTS MODEL NO.

288A-C FOR GLASSWARE WASHER'S HOT WATER, COLD WATER AND DEIONIZED

WATER CONNECTIONS. MOUNT MINIMUM 6 FEET ABOVE FINISHED FLOOR.

18. PROVIDE WATTS MODEL NO. LF7 LEAD-FREE DUAL CHECK BACKFLOW

PREVENTER FOR EYEWASH LOCATIONS. PLACE IN TEMPERED WATER LINE

IMMEDIATELY AFTER TEMPERING VALVE.

19. PROVIDE WATTS SPILL RESISTANT BACKFLOW PREVENTER LF 289 FOR ALL

WATER CONNECTIONS (HOT WATER, COLD WATER, DEIONIZED WATER).

INSTALL 6" ABOVE WATER LEVEL.

20. INSTALL MILLIQ WATER POLISHER IN DEIONIZED WATER PIPING AHEAD OF

DISHWASHERS. EXTEND INDIRECT DRAIN ALONG WALL BEHIND EQUIPMENT TO

MODIFIED DRAIN. SEE NOTE 4.

21. PROVIDE NEW STAINLESS STEEL DROP-IN SINK SK.

22. EXISTING INTEGRAL SINK REMAINS.

23. PROVIDE NEW HAND HELD EEW-1 EYEWASH WITH BFP AND TEMPERING VALVE.

24. NOT USED.

25. SEE DEMO NOTES 8 AND 27 ON SHEET PD1.1. ROUTE NEW WASTE PIPING FOR

NEW RAISED RIM FD IN E03 AT CEILING OF 4TH FLOOR TO CONNECT TO

EXISTING FD IN LAB 5026, MAINTAIN SLOPE FOR DRAINAGE. EXTEND INDIRECT

DRAINS FROM ICE MAKER TO NEW FLOOR DRAIN IN RM E03.

26. CONTRACTOR SHALL RELOCATE 2-COMPARTMENT LAUNDRY SINK FROM LAB

5034.

27. SEE GLASSWARE WASHER DRAIN DETAIL SHEET P0.1.

28. EXTEND NEW 2"W INDIRECT DRAIN TO EXISTING DRIP DRAIN LOCATION.

TERMINATE DRAIN ABOVE FLOOR DRAIN RIM.

29. EXTEND 2" VENT TO EXISTING 2" VENT THRU ROOF.

30. PROVIDE NEW VALVED HOT AND COLD WATER PIPING FROM NEW FIXTURE

FAUCET TO EXISTING WATER PIPING WITH MINIMUM 1/2" SIZE.

31. PROVIDE SHOCK ABSORBER SA-A FOR EACH SUPPLY.

32. PROVIDE NEW SINGLE BOWL LAUNDRY TUB, LT-1.

33. EXTEND NEW PIPING TO EXISTING PIPING OF ADEQUATE SIZING (1 SIZE

LARGER THAN NEW PIPING).

34. EXTEND NEW 2" WASTE TO EXISTING 3" WASTE PIPING DOWN.

35. WALL MOUNTED EXPOSED LOCKABLE BOX WITH TEMPERING VALVE.

36. PROVIDE LOCKABLE BALL VALVE IN RISER WITH TAG THAT STATES "VALVE

SHALL REMAIN LOCKED OPEN UNLESS IN REPAIR". KEY TO BE PROVIDED TO

HEAD OF MAINTENANCE.

37. OWNER PROVIDED CASEWORK AND SINK RELOCATED.FUME HOOD NOTE:

(TYPICAL ALL HOODS)

IF FUME HOOD HAS A SINK, PROVIDE NEW STOPS, SUPPLIES AND

APPURTENANCES. VERIFY THAT FAUCET AND SINK ARE IN WORKABLE

CONDITION AND IF NOT, PROVIDE PARTS AND REPAIR TO INSURE PROPER

FUNCTION.

IF FUME HOOD HAS NATURAL GAS CONNECTIONS, VERIFY THAT GAS

VALVES ARE IN WORKABLE CONDITION AND IF NOT, PROVIDE PARTS AND

REPAIR TO INSURE PROPER FUNCTION.0 16 24 328

1/8" = 1' - 0"

Page 15: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR DEMOLITION PLAN - DUCTWORKSCALE: 1/8" = 1'-0"

1

1

12

3

4

4

4

4

5

4

44

4

4

6

6

6

6

6

6

15x18

43x1639x16

37x14 30x12

30

x8

34x20 38x14

27

x14

32x12

27

x12

16x12

12x10

27x18

30x1833x1843x18

27x12

16x12

16x12

27

x18

16

x18

18

x8

34x20

27

x11

27

x14

15

x14

16

x12

LAB

5005

LAB

5005B

LAB

5017

LAB

5029B

LAB

5029LAB

5029A

OFFICE

5029C

ICE

E03

CORRIDOR

CR-5B

OFFICE

5014A

LAB

5014LAB

5010LAB

5000

LAB

5007

LAB

5034

LAB

5026

LAB

5026

LAB

5016

JANITOR

E06

CORRIDOR

CR-5C

OFFICE

5016B

CORRIDOR

CR-5A

1

1

CS135CS

139

VS121

VS120VS118

VS125VS123VS122

VE84 VE86 VE88

VS126

VS124

VS130 VS133

CS140

VS127

1 1

4 6 4 6

1

762

PARTIAL FIFTH FLOOR DEMOLITION PLAN - PIPINGSCALE: 1/8" = 1'-0"

LAB

5005

LAB

5005B

LAB

5017

LAB

5029B

LAB

5029LAB

5029A

OFFICE

5029C

ICE

E03

CORRIDOR

CR-5B

OFFICE

5014A

LAB

5014

LAB

5010LAB

5000

LAB

5007

LAB

5034

LAB

5026

LAB

5016

JANITOR

E06

CORRIDOR

CR-5C

OFFICE

5016B

CORRIDOR

CR-5A

EXISTING 1-1/2"

LP STEAM

1-1/2" LP

1-1/2" LP

1" LP

3/4" LP

1

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

MEH

DEMOLITION NOTES:

1. REMOVE EXISTING CEILING DEVICE, ASSOCIATED ACCESSORIES, INSULATION, AND SUPPORTS. CLEAN AND

PREPARE DUCT FOR CONNECTION TO NEW WORK. SEAL EXISTING OPENING AIR TIGHT.

2. THOROUGHLY CLEAN EXISTING FUME HOOD. EXISTING FUME HOOD IS HAZARDOUS AND CHEMICAL LADEN.

CONTRACTOR SHALL TAKE PROPER SAFETY PRECAUTIONS IN ACCORDANCE WITH CURRENT OSHA AND

ENVIRONMENTAL HEALTH AND SAFETY STANDARDS WHEN CLEANING FUME HOOD AND ASSOCIATED

ACCESSORIES. COORDINATE CLEANING CLOSELY WITH THE UNIVERSITY ENVIRONMENTAL HEALTH AND

SAFETY DEPARTMENT.

3. REMOVE EXISTING SPLIT SYSTEM HEAT PUMP INDOOR AND OUTDOOR UNIT, ASSOCIATED REFRIGERANT,

PIPING ACCESSORIES, CONTROLS, WIRING, CONDUIT, AND SUPPORTS.

4. REMOVE EXISTING DUCTWORK, CEILING DEVICES, AND SUPPORTS TO THE EXTENT SHOWN. CLEAN AND

PREPARE DUCTWORK FOR CONNECTION TO NEW WORK. SEAL EXISTING OPENING AIR-TIGHT.

5. REMOVE EXISTING WINDOW AIR CONDITIONING UNIT, ASSOCIATED DUCTWORK, PIPING AND CONTROLS.

6. EXISTING EXHAUST DUCT, AIR DEVICES, AND ACCESSORIES ARE POTENTIALLY HAZARDOUS AND CHEMICAL

LADEN. CONTRACTOR SHALL TAKE PROPER SAFETY PRECAUTIONS IN ACCORDANCE WITH CURRENT OSHA

AND ENVIRONMENTAL HEALTH AND SAFETY STANDARDS WHEN HANDLING DURING DEMOLITION.

COORDINATE CLOSELY WITH THE UNIVERSITY ENVIRONMENTAL HEALTH AND SAFETY DEPARTMENT.

7. DISCONNECT EXISTING HOOD FROM EXISTING FUME EXHAUST DUCT AND PREPARE HOOD FOR

RELOCATION. CLEAN FUME EXHAUST DUCT AND CAP AND PREPARE FOR CONNECTION TO NEW WORK.

COORDINATE WITH PLUMBING, ELECTRICAL, AND ARCHITECTURAL PLANS.

DEMOLITION NOTES:

1. REMOVE EXISTING LOW PRESSURE STEAM PIPING, INSULATION, ACCESSORIES AND CONNECTION TO

EXISTING AUTOCLAVE. CAP PIPING AND PREPARE FOR CONNECTION TO NEW WORK.

0 16 24 328

1/8" = 1' - 0"

LEGEND:

1-HR FIRE WALL

2-HR FIRE WALL

Page 16: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

GENERAL NOTES:

1. ALL DUCTWORK AND PIPES SHALL BE COORDINATED WITH OTHER NEW AND EXISTING DUCTS, PIPES, LIGHTS, STRUCTURAL

SYSTEM, CEILING SUPPORTS AND FRAMING BEFORE INSTALLATION. MINOR DUCT AND PIPE OFFSETS AND MINOR DUCT

TRANSITIONS SHALL BE PROVIDED AS REQUIRED. WHERE TRANSITIONS ARE REQUIRED, CROSS SECTIONAL AREA OF DUCT

SHALL NOT BE REDUCED. MEASUREMENTS FOR VERTICAL CLEARANCES OF DUCTWORK SHALL BE TAKEN AT THE JOB SITE

BEFORE FABRICATION OF ANY DUCTWORK.

2. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTRUCTIONS.

3. MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL CODES, APPLICABLE PROVISIONS OF LATEST EDITION OF

NATIONAL FIRE PROTECTION ASSOCIATION, LOCAL UTILITY REGULATIONS AND GOVERNMENTAL DEPARTMENTS HAVING

JURISDICTION.

4. CONTRACTOR SHALL SEAL PENETRATIONS IN EXISTING WALLS AS REQUIRED TO COMPLY WITH EXISTING WALL RATINGS.

5. VERIFY WALL OPENINGS WITH STRUCTURE.

6. VERIFY THE FINAL LOCATION OF ALL THERMOSTATS, TEMPERATURE SENSORS, PANELS AND CONTROL INSTRUMENTS WITH

THE ARCHITECT AND OWNER PRIOR TO ROUGH-IN.

7. VERIFY LOCATIONS OF NEW AND EXISTING EQUIPMENT AND ROUTE OF DUCTWORK WITH EXISTING CONDITIONS.

8. ALL CUTTING AND PATCHING FOR THE INSTALLATION OF NEW WORK IN EXISTING BUILDING SHALL BE DONE BY THE GENERAL

CONTRACTOR.

9. REFER TO ARCHITECTURAL, STRUCTURAL AND ELECTRICAL DRAWINGS TO COORDINATE THE EXACT LOCATIONS OF

DIFFUSERS, REGISTERS, GRILLES, PIPING AND OTHER MECHANICAL EQUIPMENT WITH CEILING GRID, LIGHTS, BEAMS AND

OTHER BUILDING COMPONENTS.

10. CONTRACTOR SHALL PROVIDE AND INSTALL ALL SUPPORTS REQUIRED TO MOUNT MECHANICAL EQUIPMENT, PIPING AND

DUCTWORK.

11. WHERE PIPE AND DUCT CONNECTIONS ARE SHOWN CONNECTING TO EXISTING, CONTRACTOR SHALL DETERMINE EXACT

LOCATIONS AND CONNECTION SIZES PRIOR TO INSTALLATION.

12. DUCTWORK SHALL BE ZINC-COATED SHEET STEEL OR ALUMINUM, CONSTRUCTED AND INSTALLED AS RECOMMENDED BY THE

LATEST EDITION OF SMACNA "HVAC DUCT CONSTRUCTION STANDARDS". COAT ALL INTERIOR SURFACES OF RIGID

FABRICATED AND PRE-MANUFACTURED DUCT AND ACCESSORIES WITH ONE COAT OF FOSTER 40-20 FUNGICIDAL PROTECTIVE

FINISH AS MANUFACTURED BY FOSTER PRODUCTS CORPORATION OR PROVIDE DUCTWORK WITH AGION ANTI-MICROBIAL

COATED STEEL/ALUMINUM.

13. FLEXIBLE DUCTS SHALL BE FLEXIBLE METAL OR METAL AND NEOPRENE-COATED CANVAS HOSE INSULATED WITH 1" THICK

FIBERGLASS WITH VINYL VAPOR BARRIER. ALL ROUND DUCT TAKE-OFFS SHALL BE MADE WITH SPIN-IN FITTINGS WITH 45 DEG.

EXTRACTOR AND BALANCING DAMPER. THE DUCT DIAMETER SHALL MATCH THE AIR DIFFUSER SIZE UNLESS OTHERWISE

INDICATED.

14. PROVIDE FLEXIBLE DUCT CONNECTIONS BETWEEN THE SUPPLY AND RETURN DUCTS FROM THE AIR UNITS. FLEXIBLE

CONNECTIONS SHALL BE WEATHERTIGHT WHEN EXPOSED.

15. PROVIDE AIR TIGHT SEAL BETWEEN DUCTWORK AND FIRE PARTITIONS/WALLS WITH FIRE RESISTANT MATERIAL.

16. SUPPLY AIR DUCTWORK SHALL BE INSULATED WITH 1 LB. DENSITY, FLEXIBLE TYPE, 1-1/2" THICK WITH FACTORY APPLIED

FACING OF 0.7 MIL FOIL-SCRIM-WHITE KRAFT PAPER JACKET EFFECTIVELY VAPOR SEALED.

17. NEW DUCT AND PIPE INSULATION SHALL BE AS SPECIFIED AND SHALL BE SEALED TO EXISTING. INSULATION THAT IS DAMAGED

OR REMOVED FOR NEW WORK SHALL BE REPLACED, REPAIRED AND SEALED AS REQUIRED.

18. ALL CEILING DIFFUSERS SHALL BE 4-WAY THROW TYPE UNLESS NOTED OTHERWISE.

19. CEILING DIFFUSERS SHALL BE PRICE SQUARE LOUVER FACE, LAY-IN, ADJUSTABLE TYPE COMPLETE

WITH EQUALIZING DEFLECTORS AND VOLUME CONTROL UNITS. FINISH SHALL BE WHITE.

20. RETURN GRILLES AND REGISTERS SHALL BE PRICE SERIES 635, 45 DEGREE DEFLECTION. DAMPERS FOR REGISTERS SHALL

BE FACE OPERATED AND OPPOSED BLADE TYPE.

21. AIR DEFLECTORS SHALL BE INSTALLED IN ALL SQUARE ELBOWS.

22. CEILING GRID AND OTHER ITEMS SHALL NOT BE SUPPORTED FROM OR IN CONTACT WITH MECHANICAL EQUIPMENT. CONDUIT,

WIRING, PIPING AND SUPPORTS SHALL NOT BE LOCATED IN FRONT OF FAN COIL ACCESS PANELS.

23. DUCTWORK AND PIPING SHALL NOT BE INSTALLED ABOVE ELECTRICAL PANELS. COORDINATE INSTALLATION OF DUCTWORK

AND PIPING WITH ELECTRICAL PANELS WHEN SHOWN NEAR PANELS OR OVER ELECTRICAL ROOMS.

24. INSTRUCT THE OWNER IN THE PROPER OPERATION AND MAINTENANCE OF THE MECHANICAL SYSTEMS UNTIL THE OWNER IS

FULLY PREPARED TO OPERATE AND MAINTAIN THE MECHANICAL SYSTEM. HOWEVER, LENGTH OF INSTRUCTION TIME SHALL

BE LIMITED TO ONE DAY.

25. EQUIPMENT, MATERIALS AND LABOR REQUIRED BY THESE CONTRACT DRAWINGS SHALL BE GUARANTEED TO BE FREE FROM

DEFECTIVE MATERIALS OR WORKMANSHIP FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE PROJECT UNLESS SPECIFIED

OTHERWISE. DEFECTIVE MATERIALS OR WORKMANSHIP OCCURRING DURING THIS PERIOD SHALL BE CORRECTED AT NO

ADDITIONAL COST.

26. ALL NEW RIGID SUPPLY AND EXHAUST DUCTWORK SHALL BE INTERNALLY COATED WITH ANTI-MICROBIAL PAINT IN STRICT

ACCORDANCE WITH THE UNIVERSITY'S CURRENT STANDARDS.

HVAC LEGENDABOVE ABV

ABOVE FINISHED FLOOR AFF

AIR CONDITIONING UNIT AC

AIR HANDLING UNIT AHU

ANCHOR

BELOW BEL

BETWEEN BET

CAPACITY CAP

CEILING CLG

CEILING GRILLE CG

CEILING REGISTER CR

CHECK VALVE

CHILLED WATER RETURN PIPE CWRCWR

CHILLED WATER SUPPLY PIPE CWS CWS

CIRCUIT SETTERCS(GPM)

CLEANOUT COCO

COMMON C

CONTROL SWITCH S

COOLING COIL CONDENSATE DRAIN PIPE CCCD DCUBIC FEET PER MINUTE CFM

DEGREES FAHRENHEIT °F

DIAMETER DIA

DIRECTION OF FLOW

DIRECTION OF SLOPE DOWN

DOWN DN

DRY BULB DB

DUCT SLOPE DOWN DN

DUCT SLOPE UP UP

DUCT TRANSITION

DUCTWORK (NEW)

ACOUSTIC LINED

RETURN & EXHAUST

SUPPLY WATERTIGHT

DUCTWORK (EXISTING TO REMAIN) EX RETURN EX R EXHAUST EX E

SUPPLY EX S

DUCTWORK (EXISTING TO BE REMOVED)

EACH EA

ENTERING AIR TEMPERATURE EAT

ENTERING WATER TEMPERATURE EWT

EXISTING, REMOVE FROM THIS POINT

FAN COIL UNIT FC

FEET FT

FEET PER MINUTE FPM

FIRE DAMPER FD

FIRE/SMOKE DAMPER FSD

FIRESTAT FS

FLEXIBLE DUCT CONNECTION

FLEXIBLE DUCT RUNOUT

FLEXIBLE PIPE CONNECTION

FLOOR FL

FLOW SWITCH FSW FSW

FREEZE PROTECTION FP

FROM FRM

GALLONS GAL

GALLONS PER MINUTE GPM

GLOBE VALVE GBV

HEATING WATER RETURN PIPE HWR HWR

HEATING WATER SUPPLY PIPE HWS HWS

HORIZONTAL UNIT HEATER HUH

HORSEPOWER HP

HOUR HR

HUMIDISTAT HINCH IN

INLINE EXHAUST FAN IEF

KILOWATT KW

LEAVING AIR TEMPERATURE LAT

LEAVING WATER TEMPERATURE LWT

MANUAL AIR VENTMAV

MANUAL DAMPER MD

MOTOR OPERATED DAMPER MOD

NEW CONNECTED TO EXISTING

NORMALLY CLOSED NC

NORMALLY OPEN NO

OUTDOOR AIR OA

PIPING INDICATION WITH RESPECT

TO FLOW

BOTTOM TAKEOFF

SIDE CONNECTION

TOP TAKEOFF

TURN DOWN OR FROM BELOW

TURN UP OR DOWN

TURN UP OR FROM ABOVE

POUNDS LBS

POUNDS PER SQUARE INCH GAGE PSIG

PRESSURE DROP PD

PRESSURE GAUGE

PRESSURE REDUCING VALVE (FILL VALVE) PRV

PRESSURE RELIEF VALVE

R

RETURN AIR RA

REVOLUTIONS PER MINUTE RPM

SERVICE VALVE

STATIC PRESSURE SP

STRAINER

SUPPLY AIR SA

THERMOMETER

THERMOSTAT OR TEMPERATURE SENSOR T'STAT TTHOUSAND BTU PER HOUR MBH

THREE-SPEED FAN SWITCH S

THREE-WAY CONTROL VALVE

TWO-WAY CONTROL VALVE

UNION

WALL HEATER WH

WET BULB WB

RETURN/EXHAUST CFM

REGISTER WIDTH

REGISTER HEIGHT

200/0808

CR

AIR DEVICE TYPE

NOTE: SIZING FOR GRILLES SIMILAR

REGISTER SIZINGNO SCALE

LATERAL BRANCHDUCT DETAILSCHEMATIC

NOTE:

PROVIDE MD ONLY WHERE INDICATED ON DRAWINGS.

SINGLE LINE

REPRESENTATION

AIR

FLOW

AIR

FLOWMD

L = 1/4W, 4" MIN.

L

DUCT SIZE AS

SHOWN ON PLAN

MANUAL

DAMPER

AIR

FLOWW

45°AIR FLOW

SUPPLY CFM DIFFUSER NECK SIZEDIFFUSER FACE SIZE

300/0824

DIFFUSER SIZINGNO SCALE

SCOOP

SEAL ALL AROUNDWITH DUCT MASTIC

DUCTSUPPLYRIGID

1" INSULATION

MD

NO SCALE

SPIN-IN FITTING DETAIL

METAL BAND CLAMP

WITH INSULATIONFLEXIBLE DUCT

ALL AROUNDSEAL AIR TIGHT

AIR

FLO

W

PIPE INSULATION

(WHERE REQUIRED)

WALL

GALVANIZED

STEEL PIPE

SLEEVE

WALL

PIPE

1/4" SPACE BETWEEN

SLEEVE & INSULATION

NOTE:

WHERE PIPES PENETRATE FIRE-RATED WALLS, FILL SPACE BETWEEN PIPE

AND SLEEVE WITH A FIRE-RESISTANT MATERIAL WITH SUFFICIENT RATING TO

MAINTAIN THE FIRE RATING OF THE WALL. WHERE PIPE PENETRATE

EXTERIOR WALLS, FILL SPACE BETWEEN PIPE AND SLEEVE WITH FIBERGLASS

INSULATION AND AS REQUIRED FOR NEW AND EXISTING FIRE RATINGS.

WALL PIPE SLEEVE DETAILNO SCALE

CHILLED WATER UNIVERSAL MOUNT FAN COIL UNITS: MULTI-AQUA

INDOOR FAN COIL UNIT MARK FC-5 FC-6

SUPPLY FAN

AIRFLOW, CFM (MAX/MIN) 870/800/575 879/750/650

COOLING

TOTAL CAPACITY, MBH 35.2 28.9

SENSIBLE CAPACITY, MBH 25.3 21.8

ENT. AIR TEMP, ° F, DB 80.0 80.0

ENT. AIR TEMP, ° F, WB 67.0 67.0

ENT. WATER TEMP, ° F 45.0 45.0

WATER FLOWRATE (GPM) 7.5 7.0

WATER PRESSURE DROP (FT W.G.) 6.9 7.2

FILTERS (TYPE) WASHABLE WASHABLE

UNIT ELECTRICAL (V/Hz/Ph) 208/60/1 208/60/1

MOTOR (kW) 0.26 0.087

MCA / MOP (A) 2.0 / 3.0 1.06 / 3.0

FULL LOAD AMPS (A) 1.5 0.85

UNIT MODEL MHCFC4W-12-01 CFFWA4P-08-1-U

CONFIGURATION 4-WAY RECESSED CEILING SUSPENDED

ESTIMATED UNIT WEIGHT (LBS) 90 95

NOTES

1. COOLING CAPACITY BASED ON 45°F ENTERING WATER TEMPERATURE.

2. REFER TO PLANS FOR UNIT QUANTITIES.

3. ALL UNITS SHALL INCLUDE GRILLE KIT (CEILING RECESSED) AND FACTORY INSTALLED

CONDENSATE PUMP.

4. UNIT PERFORMANCE SELECTED AT MEDIUM FAN SPEED.

PIPE PENETRATION FIRESTOP DETAILNO SCALE

System No. W-J-5140

SECTION A-A

1. Wall Assembly — Min 3-3/4 in. (95 mm) and 5 in. (127 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600 2400 kg/m³) concrete for 1 and 2 hr rated

assemblies, respectively. Wall may also be constructed of any UL Classified Concrete Blocks*. The max diam of the opening is dependent upon the type through

penetrant installed within the firestop system as shown in Item 4.

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Steel Sleeve — (Optional) Max 18 in. (457 mm) diam Schedule 40 (or heavier) steel pipe sleeve cast in or grouted into wall, flush with both surfaces of wall assembly.

3. Through Penetrant — One metallic pipe or tubing installed concentrically or eccentrically within the firestop system. Pipe or tube to be rigidly supported on both sides of

wall assembly. The following types and sizes of metallic pipes or tube may be used:

A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe. When steel pipe is used, T Rating is 1/2 hr.

B. Copper Tube — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube. When copper tube is used, T Rating is 1/2 hr and 1 hr when installed in 1

and 2 hr rated walls, respectively.

C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When copper pipe is used, T Rating is 1/2 and 1 hr when installed in 1 and

2 hr rated walls respectively.

4. Pipe Covering* — Max. 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m³) glass fiber units, jacketed on the outside with an all service jacket.

Longitudinal joints sealed with metal fasteners or factory-applied SSL tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product.

When pipe covering thickness is less than 2 in., T Rating is 0 hr.

See Pipe and Equipment Covering-Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the

above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.

The min and max annular space of the firestop system is dependent on the type and max diam of the through penetrant used as shown in the table below:

A

F Ratings — 1 and 2 Hr (See Items 1 and 4)T Ratings — 0, 1/2, and 1 Hr (See Item 3 and 4)

6. Fill, Void or Cavity Material*-Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of

wall. At point contact, an additional 1/2 in. (13 mm) bead of sealant shall be applied to the insulated pipe/wall interface on both surfaces of

wall.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as

Canada), respectively.

C

CLA

SS I F IED

Classified byUnderwriters Laboratories, Inc.to UL 1479 and CAN/ULC-S115

US

Through Penetrant

Type

Max Diam,

In., (mm)

Min Annular

Space, In. (mm)

Max Annular

Space, In. (mm)

Steel Pipe 12 (305) 0 (0) 1/2 (13)

Copper Pipe or Tube 6 (152) 0 (0) 1-7/8 (48)

A

1

2

54

3

2

CS

MAV IN COIL

WATER COIL

CCCD

DRAIN PAN

CWR

CWS

FAN COIL UNIT COILCONNECTION DETAILNO SCALE

1/2"HOSE-END DRAIN VALVE,

(PROVIDE ON LOWEST PIPE

CONNECTION TO COIL)

DEMOLITION NOTES:

1. THE CONTRACTOR SHALL REMOVE OR ALTER AS NECESSARY ALL EXISTING PIPING, EQUIPMENT, EQUIPMENT FOUNDATIONS,

AND APPURTENANCES THAT ARE NOT REQUIRED FOR THE EXISTING SYSTEMS TO REMAIN. CONTRACTOR SHALL VISIT THE

SITE TO DETERMINE THE SCOPE OF THIS WORK AND VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS.

2. EXISTING EQUIPMENT SHALL BE TURNED OVER TO THE OWNER, UNLESS DIRECTED OTHERWISE AND LOCATED AS DIRECTED

BY THE OWNER. ALL OTHER ITEMS TO BE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND REMOVED

FROM THE PREMISES.

3. INSULATION ON EXISTING PIPING THAT IS DAMAGED OR REMOVED DUE TO THE DEMOLITION WORK SHALL BE REPLACED AND

SEALED AS REQUIRED TO PROVIDE CONTINUOUS COVERAGE.

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

MEH

Page 17: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

MEH

1. SCOPE OF THE WORK: WORK SHALL INCLUDE COMPLETE HVAC SYSTEMS. PROVIDE SUPERVISION,

LABOR, MATERIAL, EQUIPMENT, MACHINERY, PLANT AND ITEMS NECESSARY FOR COMPLETE SYSTEMS

TESTED AND READY FOR OPERATION.

2. REGULATIONS: MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL CODES, APPLICABLE

PROVISIONS OF LATEST EDITION OF NATIONAL FIRE PROTECTION ASSOCIATION, LOCAL UTILITY

REGULATIONS AND GOVERNMENTAL DEPARTMENTS HAVING JURISDICTION.

3. DRAWINGS: THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF

SYSTEMS AND WORK INCLUDED. WHERE VARIANCES OCCUR INCLUDE THE ITEMS OF BETTER QUALITY,

GREATER QUANTITY OR HIGHER COST.

4. COORDINATION OF WORK: THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION AND

PROPER RELATION OF HIS WORK TO THE BUILDING STRUCTURE AND TO THE WORK OF OTHER TRADES.

CONTRACTOR SHALL PROVIDE DIMENSIONS AND LOCATIONS OF ALL OPENINGS, SHAFTS AND SIMILAR

ITEMS TO THE PROPER TRADES AND SHALL INSTALL WORK AS REQUIRED SO AS NOT TO DELAY THE

BUILDING CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY HIS WORK OR

WORKMEN. REPAIRING OF DAMAGED WORK SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL

COST.

5. VISITING THE SITE: EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE SITE BEFORE

PRICING THE JOB TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS TO BE MET IN THE

EXECUTION OF THE WORK UNDER THIS CONTRACT. NO ADDITIONAL COMPENSATION WILL BE ALLOWED

RELATING TO SITE CONDITIONS.

6. INTERRUPTION OF SERVICES: INTERRUPTIONS OF SERVICE TO EXISTING SYSTEMS SHALL BE

COORDINATED WITH THE OWNER AS TO TIME AND DURATION. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR ANY INTERRUPTIONS TO SERVICE AND SHALL REPAIR ANY DAMAGES TO EXISTING

SYSTEMS CAUSED BY HIS OPERATIONS.

7. WORK IN OCCUPIED AREAS: WORK IN OCCUPIED AREAS SHALL BE COORDINATED WITH THE OCCUPANT

AND OWNER AS TO TIME AND DURATION. THE CONTRACTOR SHALL PROTECT THE OCCUPIED AREA AND

SHALL BE RESPONSIBLE FOR CLEANING AND REPAIRING ANY DAMAGES CAUSED BY HIS WORK. SAFETY

OF BUILDING OCCUPANTS SHALL BE ASSURED AT ALL TIMES. TOOLS, MATERIAL, DIRT AND DEBRIS SHALL

BE REMOVED FROM OCCUPIED AREAS WHENEVER WORK AREAS ARE LEFT UNATTENDED.

8. ACCESSIBILITY: LOCATE EQUIPMENT WHICH MUST BE SERVICED OR MAINTAINED IN FULLY ACCESSIBLE

POSITIONS WHERE POSSIBLE. OTHERWISE, FURNISH ACCESS PANELS OF SUFFICIENT SIZE AND

LOCATED SO THAT THE CONCEALED EQUIPMENT CAN BE SERVICED.

9. FOUNDATION PADS AND ROUGH-IN: PROVIDE 4-INCH HIGH CONCRETE FOUNDATION PADS FOR

FLOOR-MOUNTED EQUIPMENT. ROUGH-IN OPENINGS SHALL ALIGN VERTICALLY AND HORIZONTALLY WITH

BUILDING STRUCTURE. WALL-MOUNTED THERMOSTATS SHALL BE MOUNTED 5'-4" ABOVE FINISHED

FLOOR TO BOTTOM OF THERMOSTAT.

10. SLEEVES: LOCATE SLEEVES DURING NORMAL COURSE OF WORK. PROVIDE SLEEVES FOR PIPING

PASSING THROUGH CONCRETE FLOOR SLABS AND CONCRETE, MASONRY, TILE AND GYPSUM WALL

CONSTRUCTION. SLEEVES SHALL NOT BE REQUIRED FOR PIPING EMBEDDED IN CONCRETE OR SLAB ON

GRADE, EXCEPT THAT COPPER PIPING SHALL REQUIRE SLEEVES THROUGH SLABS ON GRADE. SLEEVES

PLACED IN EXTERIOR WALLS BELOW GRADE SHALL BE WATERTIGHT. WHERE SLEEVES ARE LOCATED

THROUGH FIRE-RATED WALLS OR FLOORS, THE SLEEVE ASSEMBLIES SHALL MAINTAIN THE FIRE RATING

OF THE WALL OR FLOOR. SLEEVES SHALL BE CONSTRUCTED OF 20 GAUGE GALVANIZED STEEL WITH

LOCK SEAM JOINTS FOR ALL SLEEVES SET IN CONCRETE FLOOR SLABS. ALL OTHER SLEEVES SHALL BE

CONSTRUCTED OF GALVANIZED STEEL PIPE.

11. CUTTING AND PATCHING: THE CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING NECESSARY

TO INSTALL HIS WORK. PATCHING SHALL MATCH ADJACENT SURFACES. NO STRUCTURAL MEMBERS

SHALL BE CUT WITHOUT THE APPROVAL OF THE ARCHITECT.

12. CLEANING: EQUIPMENT AND PIPING SHALL BE CLEANED TO REMOVE FOREIGN MATERIALS. PROVIDE

TEMPORARY FILTERS FOR AIR UNITS THAT ARE OPERATED DURING CONSTRUCTION. PLUG OR CAP

OPENINGS IN EQUIPMENT, DUCTWORK, PIPING AND MATERIALS UNTIL CONNECTION IS MADE TO THE

SYSTEM. REMOVE FROM THE PREMISES ALL UNUSED MATERIAL AND DEBRIS RESULTING FROM THE

PERFORMANCE OF HVAC WORK.

13. WIRING: STARTERS THAT ARE SPECIFIED TO BE FURNISHED AS AN INTEGRAL PART OF THE MECHANICAL

EQUIPMENT SHALL BE COMPLETE WITH PROPERLY SIZED OVERLOAD HEATERS. TEMPERATURE

CONTROL WIRING, EQUIPMENT CONTROL WIRING AND CONTROL INTERLOCK WIRING FOR MECHANICAL

EQUIPMENT SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. CONTROL WIRING SHALL NOT

INCLUDE ANY WIRING WHICH CARRIES MOTOR CURRENT. ALL WIRING SHALL BE IN METAL CONDUIT AND

SHALL COMPLY WITH THE ELECTRICAL SPECIFICATIONS.

14. START-UP: ALL MAJOR PIECES OF HVAC EQUIPMENT, INCLUDING, BUT NOT LIMITED TO, CHILLERS,

CONDENSING UNITS, BOILERS, BURNERS, AND PUMPS SHALL INCLUDE FACTORY START-UP AND

VERIFICATION BY TRAINED AND CERTIFIED FACTORY REPRESENTATIVE OF THE EQUIPMENT

MANUFACTURER. START-UP AND VERIFICATION REPORTS SHALL BE INCLUDED WITH BOUND SETS OF

OPERATING AND MAINTENANCE INSTRUCTIONS.

15. QUIET OPERATION: SYSTEMS SHALL OPERATE UNDER CONDITIONS OF LOAD WITHOUT UNUSUAL OR

EXCESSIVE NOISE OR VIBRATION. UNUSUAL OR EXCESSIVE NOISE OR VIBRATION SHALL BE CORRECTED.

16. TESTING AND BALANCING: THE CONTRACTOR SHALL PROVIDE THE SERVICES OF AN INDEPENDENT FIRM

CERTIFIED BY THE AABC OR NEBB TO ADJUST AND BALANCE THE HVAC EQUIPMENT TO ASSURE THAT

THE PROPER SEQUENCE OF CONTROL IS ESTABLISHED AND OPERATING IN A SAFE MANNER. THE AABC

OR NEBB CERTIFIED FIRM SHALL BALANCE WATER FLOW FOR ALL EQUIPMENT, CHILLERS, PUMPS,

BOILERS, MAIN CHILLED WATER LOOP, MAIN HEATING WATER LOOP, AND SHALL BE BALANCED FOR THE

GPM AS INDICATED ON THE DRAWINGS. THE AABC OR NEBB CERTIFIED FIRM SHALL GUARANTEE THAT

ALL TESTING ADJUSTING AND BALANCING WORK SHALL BE PERFORMED IN ACCORDANCE WITH NEBB

PRCEDURAL STANDARDS FOR TESTING AND ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS.

SHOP DRAWING REQUIRED FOR TESTING AND BALANCING REPORT.

17. INSTRUCTIONS TO OWNER: INSTRUCT THE OWNER IN THE PROPER OPERATION AND MAINTENANCE OF

THE MECHANICAL SYSTEMS UNTIL THE OWNER IS FULLY PREPARED TO OPERATE AND MAINTAIN THE

SYSTEMS. HOWEVER, LENGTH OF INSTRUCTION TIME SHALL BE LIMITED TO ONE (1) FULL DAY.

18. OPERATING AND MAINTENANCE: PROVIDE THE OWNER WITH TWO (2) BOUND SETS OF OPERATING AND

MAINTENANCE INSTRUCTIONS FOR ALL HVAC EQUIPMENT AND CONTROLS AND ONE (1) DIGITAL COPY IN

THE SAME FORMAT AND SEQUENCE.

19. GUARANTEE: EQUIPMENT, MATERIALS AND LABOR REQUIRED BY THESE CONTRACT DRAWINGS SHALL BE

GUARANTEED TO BE FREE FROM DEFECTIVE MATERIALS OR WORKMANSHIP FOR ONE (1) YEAR AFTER

FINAL ACCEPTANCE OF THE PROJECT UNLESS SPECIFIED FOR A LONGER PERIOD IN OTHER PORTIONS OF

THE SPECIFICATIONS. DEFECTIVE MATERIALS OR WORKMANSHIP OCCURRING DURING THIS PERIOD

SHALL BE CORRECTED AT NO ADDITIONAL COST.

20. PAINTING: GENERAL - PAINT MECHANICAL EQUIPMENT AND MATERIALS (WHERE NOT CONCEALED).

PAINTING (IN CONCEALED SPACES) SHALL BE LIMITED TO EQUIPMENT AND MATERIALS NOT OTHERWISE

PROTECTED FROM RUSTING SUCH AS HANGERS AND SUPPORTS. PAINT SHALL BE PRODUCTS OF

SHERWIN-WILLIAMS, PITTSBURGH, PRATT-LAMBERT OR EQUAL. SURFACE PREPARATION, PRIMING AND

PAINT APPLICATION SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.

GALVANIZED SURFACES SHALL BE PRETREATED WITH A PHOSPHORIC ACID CLEANING SOLUTION AND

PRIMED. AFTER PREPARATION EACH ITEM SHALL BE PAINTED, EXCEPT COLOR OF PAINT FOR EQUIPMENT

AND MATERIAL WHERE NOT CONCEALED SHALL BE AS SELECTED BY THE ARCHITECT. ITEMS NOT

CONCEALED IN ROOMS SHALL BE PAINTED OF THE SAME COLOR TO MATCH ADJACENT WALLS OR

CEILINGS. PAINTING IS NOT REQUIRED OF ITEMS WITH A FACTORY-FINISH COAT- FINISH TO BE SELECTED

BY ARCHITECT FROM MANUFACTURER FULL RANGE OF OPTIONS, INCLUDING STAINLESS STEEL. PATCH

PAINTING IS REQUIRED OF ANY DAMAGED AREAS TO MATCH FACTORY-FINISH COAT NAMEPLATES ON

EQUIPMENT SHALL NOT BE PAINTED.

21. IDENTIFICATION OF PIPES AND EQUIPMENT: EACH MAJOR PIECE OF EQUIPMENT, SUCH AS PIPING SHALL

BE IDENTIFIED BY MARKING THAT WILL READ THE SAME AS THE IDENTIFICATION SHOWN ON THE

DRAWINGS. STENCIL LETTERS SHALL BE 2 INCHES HIGH UPPER CASE PAINTED WITH WHITE ENAMEL ON

EQUIPMENT AND BLACK ENAMEL ON PIPING AND CONDUIT. IDENTIFICATION SHALL BE PAINTED ON EACH

PIPE OR CONDUIT WHERE EXPOSED OR ACCESSIBLE AND SHALL BE PLACED EVERY 15 FEET ALONG THE

PIPE OR CONDUIT.

22. PIPING:

A. STEAM, CONDENSATE AND PUMPED CONDENSATE PIPING: BLACK STEEL: ASTM A 53 GRADE B ERW OR

SEAMLESS SCHEDULE 40 STANDARD WEIGHT FOR STEAM AND ASTM A53 GRADE B ERW OR SEAMLESS

SCHEDULE 80 EXTRA HEAVY FOR CONDENSATE AND PUMPED CONDENSATE.

B. CHILLED WATER PIPING (2-1/2 INCH AND LARGER): BLACK STEEL: ASTM A 53 SCHEDULE 40 STANDARD

WEIGHT. CHILLED WATER PIPING, AND HEAT PUMP WATER PIPING (2-INCH AND SMALLER): BLACK STEEL:

ASTM A 53 SCHEDULE 40 STANDARD WEIGHT.

C. COPPER WATER TUBE OPTION: ASTM B 88, TYPE L, HARD DRAWN. EXCEPT UNDERGROUND LINES SHALL

BE TYPE K HARD DRAWN COPPER TUBING.

D. COOLING COIL CONDENSATE DRAIN LINES SHALL BE PVC OR TYPE 'M' HARD DRAWN COPPER TUBING.

PROVIDE WATER SEAL FROM EACH AIR HANDLING UNIT OF SUFFICIENT DEPTH TO PREVENT BLOW OUT

OR SIPHONING OF WATER.

E. FITTINGS FOR STEEL PIPE 2-1/2 INCH AND LARGER SHALL BE WELDED, OR FLANGED JOINTS SUITABLE

FOR 125 PSI SERVICE. BUTT WELD FITTINGS SHALL BE ANSI B16.9 WITH SAME WALL THICKNESS AS

CONNECTING PIPING. ELBOWS SHALL BE LONG RADIUS TYPE UNLESS OTHERWISE NOTED. WELDING

FLANGES AND BOLTING SHALL BE ANSI B16.5 FOR WATER SERVICE, WELD NECK OR SLIP-ON PLAIN FACE,

WITH 1/8-INCH THICK FULL FACE NEOPRENE GASKET SUITABLE FOR 220 DEG. F. FLANGE BOLTINGSHALL

BE CARBON STEEL MACHINE BOLTS OR STUDS AND NUTS, ASTM A 307, GRADE B.

F. FITTINGS FOR STEEL PIPE 2-INCH AND SMALLER: THREADED OR WELDED, SUITABLE FOR 125 PSI

SERVICE. BUTT WELD FITTINGS SHALL BE ANSI B16.9 WITH SAME WALL THICKNESS AS CONNECTING

PIPING. FORGED STEEL, SOCKET WELDING OR THREADED SHALL BE ANSI B16.11. THREADED SHALL BE

150 POUND MALLEABLE IRON, ASTM B16.3. BUSHING REDUCTION OF A SINGLE PIPE SIZE, OR USE OF

CLOSE NIPPLES, IS NOT ACCEPTABLE. UNIONS SHALL BE FED. SPEC. WW-U-531. WATER HOSE

CONNECTION ADAPTER SHALL BE BRASS, PIPE THREAD TO 3/4-INCH GARDEN HOSE THREAD, WITH HOSE

CAP NUT. WELDED BRANCH AND TAP CONNECTIONS SHALL BE FORGED STEEL WELDOLETS AND

THREDOLETS MAY BE USED FOR BRANCH CONNECTIONS UP TO ONE PIPE SIZE SMALLER THAN THE MAIN.

FORGED STEEL HALF-COUPLINGS, ANSI B16.11 MAY BE USED FOR DRAIN, VENT AND GAGE CONNECTIONS.

G. FITTINGS FOR COPPER TUBING: SOLDER JOINT SHALL BE WROUGHT COPPER, ANSI B16.22. SOLDER FOR

DRAIN PIPING SHALL BE 95-5 TIN-ANTIMONY, ASTM B 32 (95TA). BRONZE FLANGES AND FLANGED FITTINGS

SHALL BE ANSI B16.24.

H. DIELECTRIC FITTINGS: PROVIDE WHERE COPPER AND FERROUS METAL ARE JOINED. 2 INCH AND LESS:

THREADED DIELECTRIC UNION. 2-1/2 INCH AND LARGER: FLANGE UNION WITH DIELECTRIC GASKET AND

BOLT SLEEVES.

I. THREADED JOINTS: PIPE THREAD: ANSI B2.1. LUBRICANT OR SEALANT: OIL AND GRAPHITE OR OTHER

COMPOUND APPROVED FOR THE INTENDED SERVICE.

J. VALVES: VALVES SHALL BE STOCKHAM, MILWAUKEE, OR NIBCO. ALL VALVES SHALL BE SUITABLE FOR 125

PSI WORKING PRESSURE UNLESS NOTED OTHERWISE. VALVES SHALL HAVE THREADED OR GROOVED

CONNECTIONS, EXCEPT WHERE FLANGES ARE SPECIFIED THEY SHALL HAVE FLANGED CONNECTIONS OR

WHERE INSTALLED IN HARD DRAWN COPPER LINES THEY MAY HAVE SWEAT CONNECTIONS.

SERVICE VALVES 2-1/2 INCH AND SMALLER SHALL BE GATE OR BALL VALVE. GATE VALVE SHALL BE ASTM

B-62 BRONZE BODY AND SOLID WEDGE DISC, RISING STEM MSS SP-80, CLASS 125. BALL VALVE SHALL BE

ASTM B-584 ALLOY 844 BRONZE BODY AND STAINLESS STEEL BALL WITH TEFLON SEATS, CONVENTIONAL

PORT, AND BLOWOUT PROOF STEMS MSS SP-110, 150 PSI/600 PSI NON-SHOCK. PROVIDE EXTENDED STEM

PER APPLICATION.

SERVICE VALVES 3 INCH AND LARGER FOR WATER SERVICE SHALL BE ASTM A-536 DUCTILE IRON BODY

BUTTERFLY, ASTM B-148 ALLOY 954/955 DISC, EPDM SEATS, CLASS 200, LOCKING_TYPE MANUAL LEVER.

SERVICE VALVES FOR STEAM SERVICE (LOW PRESSURE) SHALL BE IRON BODY GATE, SOLID BRONZE

WEDGE DISC, FLANGED, OUTSIDE SCREW AND YOKE, MSS SP-70, BRONZE MOUNTED, CLASS 1 (125 PSIG).

GLOBE VALVES 2-INCH AND SMALLER SHALL BE ASTM B-62 BRONZE BODY AND DISC, MSS SP-80, CLASS

125. 2-1/2 INCH AND LARGER: SIMILAR TO ABOVE, BUT ASTM A-126 FLANGED CAST IRON BODY, WITH

BRONZE TRIM, BOLT BONNET, OS & Y, RENEWABLE SEAT AND DISC.

CHECK VALVES IN SIZES UP TO AND INCLUDING 2 INCH SHALL BE ALL BRONZE, SWING TYPE, WITH

REGRINDING DISC CAPABLE OF BEING REGROUND WITHOUT REMOVING THE VALVE BODY FROM THE

LINE. SIZES 2-1/2 INCH AND LARGER SHALL BE IRON BODY, BRONZE-TRIMMED, REGRINDING SEAT, SWING

TYPE, FOR WATER SERVICE.

K. BALANCING COCKS: COMBINATION BALANCING AND SHUT-OFF VALVES SHALL INCORPORATE A POSITION

INDICATOR AND MEMORY STOP OR LOCKING DEVICE SO THE VALVE CAN BE CLOSED WITHOUT

DISTURBING THE SETTING, AND BE RETURNED TO THE BALANCED POSITION WITHOUT FURTHER

ADJUSTMENT. 4-INCH AND LARGER: BUTTERFLY VALVES OR PLUG VALVES. 3-INCH AND SMALLER:

RESILIENT FACED ECCENTRIC PLUG OR LUBRICATED PLUG TYPE, IRON OR STEEL BODY, BRONZE PLUG

AND BEARINGS, WRENCH OPERATED, RATED 175 PSIG AT 200 DEG. F.

L. STRAINERS: MUELLER STEAM SPECIALTY CO. NO. 351 Y TYPE.

STEAM SERVICES: RATED 150 PSIG SATURATED STEAM AT 450 DEGREES F. 2-1/2 INCH AND LARGER:

FLANGED, IRON BODY. 2-INCH AND SMALLER: BRONZE.

WATER SERVICES: RATED 125 PSIG SATURATED STEAM AT 450 DEG. F. 2-1/2 INCH AND LARGER:

FLANGED, IRON BODY, BASKET TYPE (NO. 165). 2-INCH AND SMALLER: BRONZE, THREADED ENDS, Y TYPE

(NO. 351).

SCREENS: BRONZE, MONEL METAL OR 18-8 STAINLESS STEEL, FREE AREA NOT LESS THAN 2-1/2 TIMES

PIPE AREA, WITH PERFORATIONS AS FOLLOWS:

STEAM SERVICE: 0.045-INCH DIAMETER PERFORATIONS.

WATER SERVICE:

2-1/2 INCH AND LARGER: 1/16-INCH DIAMETER PERFORATIONS.

2 INCH AND SMALLER: 1/32-INCH DIAMETER PERFORATIONS.

PROVIDE BLOW OFF OUTLET WITH PIPE NIPPLE AND GATE VALVE.

M. FLEXIBLE PIPE JOINTS SHALL BE FLEXONICS MODEL PCS, STAINLESS STEEL BRAIDED HOSE, PIPE LINE

SIZE, FLANGED, MINIMUM 125 PSI WORKING PRESSURE AT 250 DEGREES F.

N. STEAM TRAPS SHALL BE SARCO, WEBSTER, OR HOFFMAN THERMOSTATIC, INVERTED BUCKET, OR FLOAT

AND THERMOSTAT TYPE AS INDICATED. TRAPS SHALL BE SIZED BY THE TRAP MANUFACTURER TO PASS

CONDENSATE AT 2_1/2 TIMES THE CONDENSATION RATE OF THE CONNECTED HEATING APPLIANCE (AT 1

PSI DROP ON LOW PRESSURE SYSTEM) (AT 5 PSI DROP ON MEDIUM PRESSURE SYSTEMS). STEAM MAIN

DRIP TRAPS SHALL BE 3/4" BUCKET TRAPS, OR YARWAY SERIES 130 IMPULSE TRAP MAY BE USED IN LIEU

OF STRAINER AND BUCKET TRAP. TRAPS SHALL BE RATED FOR 15 PSI SERVICE ON LOW PRESSURE

SYSTEMS.

O. REDUCING VALVES FOR STEAM SERVICE SHALL BE LESLIE, SPENCE, OR AERCO SELF-CONTAINED,

EXTERNAL PILOT, PISTON, OR DIAPHRAGM-OPERATED CAST IRON OR BRONZE BODY WITH

SINGLE_SEATED STAINLESS STEEL VALVE FOR DEAD_END SERVICE. VALVES SHALL BE ADJUSTABLE

OVER A 2 TO 35 PSI RANGE AND SHALL PROVIDE NOT LESS THAN 75% ACCURACY OF REGULATION AT 10%

OF THE RATED CAPACITY.

P. STEAM PRESSURE RELIEF VALVES FOR REDUCING STATIONS SHALL BE CONSOLIDATED, BRONZE OR

CAST IRON BODY, MANUAL TEST LEVER, AND SUITABLE FOR STEAM SERVICE OF SUFFICIENT CAPACITY

TO RELIEVE THE FULL DISCHARGE CAPACITY OF THE CONNECTED REDUCING VALVE. DISCHARGE PORT

OF RELIEF VALVES SHALL BE PIPED FULL SIZE TO 6" ABOVE FLOOR DRAIN OR FLOOR AND SHALL BE

SUPPORTED SO THAT NO STRAIN IS ON THE VALVE.

Q. WATER FLOW MEASURING DEVICES:

CIRCUIT SETTERS SHALL BE BELL AND GOSSETT BRONZE BALANCE VALVE WITH PROVISIONS FOR

CONNECTING A PORTABLE DIFFERENTIAL PRESSURE METER. METER CONNECTIONS SHALL HAVE

BUILT_IN CHECK VALVES. AN INTEGRAL POINTER SHALL REGISTER DEGREE OF VALVE OPENING. EACH

BALANCE VALVE SHALL BE CONSTRUCTED FOR 125 LBS. WORKING PRESSURE AT 250 DEG. F. FURNISH

ONE DIFFERENTIAL METER MODEL RO-5 COMPLETE WITH METER, CUTOFFS, PIPING, FITTING, AND HOSE.

THE VALVE PRESSURE DROP AND THE SETTING SHALL DETERMINE THE ACTUAL SYSTEM FLOW RATE.

AUTOMATIC FLOW CONTROL VALVES SHALL BE GRISWOLD, AUTOFLOW, HAYS OR EQUAL AND SHALL BE

PROVIDED AT ALL FAN COIL UNITS. VALVES SHALL BE AUTOMATIC PRESSURE COMPENSATING

TYPE AND FACTORY SET TO PROVIDE SPECIFIED FLOW RATES WITHIN FIVE (5) PERCENT REGARDLESS OF

SYSTEM PRESSURE. VALVES SHALL BE SELECTED TO PROVIDE SPECIFIED FLOW RATES WITH A

MINIMUM PRESSURE DIFFERENTIAL OF 2 PSIG AND MAXIMUM PRESSURE DROP OF 10 FEET OF WATER.

WHERE SYSTEM DIFFERENTIAL EXCEEDS 32 PSIG, VALVES SHALL BE SELECTED FOR A RANGE OF 4-57

PSIG. VALVE BODY SHALL BE SUITABLE FOR USE WITH PIPING SYSTEM AND INTERNAL WORKING PARTS

SHALL BE STAINLESS STEEL, NICKEL PLATED BRASS OR ELASTOMERIC DIAPHRAGM. ALL VALVES SHALL

BE PROVIDED WITH UNION AND PRESSURE TEMPERATURE TEST PORTS SUITABLE FOR CONNECTING

DIFFERENTIAL PRESSURE MEASURING DEVICES. ALL VALVES SHALL BE WYE CONFIGURATION FOR

REMOVAL OF CONTROLLING ELEMENT WITHOUT REMOVING VALVE FROM PIPING. EACH VALVE SHALL BE

IDENTIFIED AS TO DIRECTION OF FLOW AND FLOW RATE. ONE DIFFERENTIAL PRESSURE METER SHALL

BE PROVIDED COMPLETE WITH DUAL HOSE KIT, VALVES, FLOW CONVERSION CHART AND CARRYING

CASE. METER AND ACCESSORIES SHALL BE TURNED OVER TO THE OWNER UPON FINAL ACCEPTANCE OF

THE PROJECT.

R. PIPE SUPPORTS: SUSPENDED HORIZONTAL PIPING SHALL BE SUPPORTED BY ADJUSTABLE WROUGHT

STEEL CLEVIS HANGERS, EXCEPT THAT STRAIGHT RUNS OF PIPING WITH 40 FEET OR MORE BETWEEN

ANCHOR AND EXPANSION DEVICE SHALL BE SUPPORTED ON ROLLER TYPE HANGERS OR SUPPORTS.

PROTECTION SADDLE, WELDED TO PIPE, SHALL BE PROVIDED AT EACH ROLLER SUPPORT. ALL

SUPPORTS SHALL BE ATTACHED TO THE BUILDING STRUCTURE AND SHALL IN NO WAY BE ATTACHED TO

THE SUPPORTS OR OTHER EQUIPMENT, PIPING, OR DUCTWORK. WHERE SUPPORTS BEAR ON COPPER

PIPE, THEY SHALL BE COPPER PLATED. CHAIN, STRAP, OR OTHER MAKESHIFT DEVICES WILL NOT BE

PERMITTED AS HANGERS OR SUPPORTS. MAXIMUM PIPE SUPPORT SPACING SHALL BE 10'-0" ON CENTER,

EXCEPT WHERE GROOVED COUPLINGS ARE USED, NO PIPE LENGTH SHALL BE LEFT UNSUPPORTED

BETWEEN ANY TWO GROOVED COUPLINGS. SUPPORTS ON CONDENSATE DRAIN LINES SHALL BE

PROVIDED WITH A 12" LONG SECTION OF HYDROUS CALCIUM SILICATE, WHICH SHALL HAVE JOINTS

SEALED AND COVERED WITH A VAPOR BARRIER JACKET. HANGER RODS SHALL BE 3/8" DIAMETER SIZE

FOR PIPES UP THROUGH 2" AND 1/2" DIAMETER SIZE FOR 1_1/2" THROUGH 3." PIPE HANGER RODS SHALL

BE ATTACHED TO THE TOP CHORD ONLY ON STEEL JOISTS AND BEAMS BY JOIST OR BEAM CLAMPS

WITHOUT WELDING. WELDING OF SUPPORT RODS AND CONNECTION AT ANY PLACE OTHER THAN THE

TOP CHORD WILL NOT BE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED BY THE ARCHITECT.

S. ANCHORS FOR PIPE SHALL BE PROVIDED AS INDICATED OR AS REQUIRED AT THE JOB SITE TO LOCALIZE

EXPANSION AND CONTRACTION OF PIPE.

T. VERTICAL PIPING SHALL BE GUIDED OR SUPPORTED IN THE CENTER OF EACH RISER AND NOT OVER 15'-0"

ON CENTER AND SHALL BE SUPPORTED AT THE BASE OF EACH RISER.

U. INSTALLATION: INSTALL PIPING GENERALLY PARALLEL TO WALLS AND COLUMN CENTERLINES, UNLESS

SHOWN OTHERWISE ON THE DRAWINGS. SPACE PIPING, INCLUDING INSULATION, TO PROVIDE ONE INCH

MINIMUM CLEARANCE BETWEEN ADJACENT PIPING OR OTHER SURFACE. PIPE SHALL BE INSTALLED TO

PERMIT FREE EXPANSION AND CONTRACTION WITHOUT DAMAGE TO JOINTS OR HANGERS. ALL PIPING

SHALL BE INSTALLED WITH SUFFICIENT PITCH TO INSURE ADEQUATE DRAINAGE AND VENTING.

CONDENSATE DRAIN LINES SHALL SLOPE 1/8" PER FOOT IN DIRECTION OF FLOW. ALL TAKE-OFFS/PIPING

RUN-OUTS SHALL BE INSTALLED ON THE SIDE OR ON THE TOP OF THE MAIN PIPE TO WHICH IT IS

CONNECTED.

V. COPPER TUBING SHALL BE CUT SQUARE, ENDS REAMED, AND ALL FILINGS AND DUST WIPED FROM

INTERIOR OF PIPE. JOINTS SHALL BE SOLDERED WITH SOLDER DRAWN THROUGH THE FULL FITTING

LENGTH. EXCESS SOLDER SHALL BE WIPED FROM JOINT BEFORE SOLDER HARDENS. SOLDER SHALL BE

95/5 COMPOSITION; 50/50 WILL NOT BE ALLOWED.

W. DIELECTRIC FITTINGS SUCH AS COUPLINGS, UNIONS OR FLANGES SHALL BE INSTALLED TO ISOLATE

PIPES OF NON-FERROUS METAL WHERE CONNECTION IS MADE TO FERROUS METAL.

X. A HYDROSTATIC TEST AT 1.5 TIMES DESIGN PRESSURE FOR 4 HOURS. FACTORY TESTED EQUIPMENT

(CONVERTERS, EXCHANGERS, COILS, ETC.) NEED NOT BE FIELD TESTED. AVOID EXCESSIVE PRESSURE

ON MECHANICAL SEALS AND SAFETY DEVICES.

23. THERMAL COVERING (SHOP DRAWING REQUIRED):

A. INSULATION SHALL BE JOHNS MANVILLE, OWENS CORNING, ARMSTRONG OR EQUAL. INSULATION SHALL

NOT BE APPLIED UNTIL AFTER THE EQUIPMENT, PIPES OR DUCTS TO BE INSULATED HAVE PROVEN

SATISFACTORY UNDER TESTS. ALL MATERIALS USED SHALL HAVE COMPOSITE FLAME-SPREAD RATING

NOT EXCEEDING 25 AND A SMOKE-DEVELOPED RATING NOT EXCEEDING 50.

B. PIPING: INSULATION SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

C. FIBERGLASS PIPE INSULATION SHALL HAVE A WHITE KRAFT BONDED TO ALUMINUM FOIL, REINFORCED

WITH FIBERGLASS YARN JACKET. ELASTOMERIC INSULATION SHALL BE CONSTRUCTED OF A CLOSED

CELL STRUCTURE TO EFFECTIVELY RETARD THE FLOW OF MOISTURE VAPOR AND SERVE AS A VAPOR

BARRIER. INSULATION THICKNESS AND TYPE FOR VARIOUS PIPING SYSTEMS SHALL BE AS INDICATED IN

THE FOLLOWING TABLE (PIPE SIZE/INSULATION THICKNESS).

PIPE SIZE/INSULATION THICKNESS (1)

SYSTEM TEMP. RUNOUTS 1-1/2" & 2" 8" & INS.

RANGE 1" OR LESS LESS TO 8" ABOVE TYPE

(DEG. F) (3) (A,B)

LOW

PRESSURE 201-250 1.5 1.5 3.0 3.0 A

STEAM

DOMESTIC

HOT WATER 90-159 1.0 1.0 1.0 1.0 A

DOMESTIC

COLD 56-79 1.0 1.0 1.0 1.0 A

WATER

CHILLED

WATER 40-55 1.0 1.0 1.5 2.0 A

CONDENSATE

DRAIN 45-75 0.5 0.5 1.0 1.0 A,B

STEAM

CONDENSATE ANY 1.0 1.0 1.5 2.0 A

NOTES:

(1) MINIMUM THICKNESS FOR INSULATION LISTED IN THE PRECEDING TABLE IS BASED ON THERMAL

CONDUCTIVITY, 'K' NOT EXCEEDING 0.27 BTU PER INCH/HR X SQ. FT. X DEG. F. BASED ON MEAN

TEMPERATURE OF 75 DEG. F. INSULATION WITH GREATER THERMAL CONDUCTIVITY SHALL HAVE

INCREASED THICKNESS TO PROVIDE SAME PERFORMANCE CHARACTERISTICS AS SPECIFIED.

MINIMUM ELASTOMERIC INSULATION THICKNESS SHALL BE INCREASED FOR MATERIAL HAVING

THERMAL RESISTANCE (R) VALUES LESS THAN 3.7 PER INCH THICKNESS.

(2) A - FIBERGLASS TYPE INSULATION; B - ELASTOMERIC TYPE INSULATION.

(3) RUNOUTS TO INDIVIDUAL TERMINAL UNITS (NOT EXCEEDING 12 FT. IN LENGTH).

D. ELASTOMERIC INSULATION SHALL BE ARMSTRONG ARMAFLEX II PIPE INSULATION, FED. SPEC. HH-I-573

AND HH-I-1751/2, K=0.27, FLAME SPREAD NOT OVER 25, SMOKE DEVELOPED NOT OVER 50 (1/2-INCH THICK

TEST MATERIAL), FOR TEMPERATURES FROM MINUS 40 DEG. F. TO 211 DEG. F.

E. FIBERGLASS PIPE INSULATION FITTINGS SHALL BE COVERED WITH PREMOLDED PVC FITTING COVERS.

JACKETS ON FIBERGLASS PIPE INSULATION BELOW 80 DEG. F. SHALL BE VAPOR SEALED USING

SELF-SEALING LAP, LAP SEAL GUN OR ADHESIVE. ALL INSULATION JOINTS, LAPS, VOIDS, PUNCTURES

AND END TAPERS SHALL BE SEALED WITH 1/32" THICKNESS OF VAPOR ADHESIVE. A 12" LONG, 1/2

SECTION OF HYDROUS CALCIUM SILICATE OR FOAMGLAS INSULATION SHALL BE USED BETWEEN

HANGERS AND PIPING. ON PIPE, SIZES 1-1/2" AND BELOW, HYDROUS CALCIUM SILICATE OR FOAMGLAS

WILL NOT BE REQUIRED. ALL PIPING SHALL HAVE LOAD-DISTRIBUTING GALVANIZED 16 GAUGE METAL

SHIELDS INSTALLED AROUND THE LOWER HALF OF THE INSULATION.

F. ELASTOMERIC PIPE INSULATION SEAMS, VOIDS AND BUTT JOINTS SHALL BE SEALED WITH A VAPOR

BARRIER ADHESIVE OR TAPED WITH 1-1/2 INCH WIDE 3M #471 TAPE.

G. FLEXIBLE ELASTOMERIC INSULATION EXPOSED TO OUTDOOR CONDITIONS SHALL BE PROTECTED WITH

ALUMINUM JACKETS. ALUMINUM JACKETS SHALL BE ASTM B 209, TEMPER H14, .016-INCH THICK, SMOOTH.

SECURE JACKETS IN PLACE WITH ALUMINUM OR STAINLESS STEEL BANDS AND SCREWS. FINISH ELBOWS

AND FITTINGS WITH FACTORY-FABRICATED METAL COVERS. COVERS SHALL BE THE SAME THICKNESS

AND MATERIALS AS JACKETS ON ADJACENT PIPING. SECURE METAL COVERS IN PLACE WITH METAL

BANDS AND SEAL WITH A WEATHER-PROOF COATING. PROTECT FITTINGS WITH A WEATHERPROOF

COATING PRIOR TO INSTALLATION OF METAL COVERS.

23. CHILLED WATER FAN COIL UNITS (SHOP DRAWING REQUIRED):

A. GENERAL: UNIT SHALL BE FACTORY ASSEMBLED, WIRED AND TESTED WATER FAN COIL UNIT AS

MANUFACTURED BY MULTI-AQUA, EMI, OR AIREDALE COMPLETE WITH WATER COIL, PIPING, FAN, FILTER,

DRAIN PAN, INSULATION, CABINET COVER, AND CONTROLS. UNIT SHALL BE ETL CERTIFIED IN

ACCORDANCE WITH UL 95, MANUFACTURED IN AN ISO 9002 REGISTERED FACILITY, FULLY LOAD TESTED

AT THE FACTORY, AND SHIPPED IN DAMAGE RESISTANT PACKAGING.

B. UNIT CABINET SHALL BE CONSTRUCTED OF GALVANIZED SHEET METAL AND SHALL BE INTERNALLY AND

EXTERNALLY INSULATED FOR QUIET OPERATION. COVER SHALL BE COMPOSED OF HIGH IMPACT

POLYMERS AND SHALL HAVE MANUALLY ADJUSTABLE DISCHARGE LOUVERS FOR AIR DISTRIBUTION.

C. FAN MOTOR (208/230-1-60) SHALL BE TOTALLY ENCLOSED, THREE SPEED, DIRECT DRIVE, AND PSC TYPE

WITH INTERNAL OVERLOAD PROTECTION. RADIAL BLOWER WHEEL SHALL BE DYNAMICALLY BALANCED.

D. WATER COILS SHALL BE COPPER TUBING MECHANICALLY BONDED TO ALUMINUM FINS, TESTED TO 300

PSIG, AND DESIGNED TO ACCEPT AN ENTERING WATER TEMPERATURE NOT TO EXCEED 160°F. FLOW

CONTROL SHALL NOT EXCEED MAX FLOW FOR EACH COIL.

E. UNIT DRAIN PAN SHALL BE CONSTRUCTED OF INJECTION MOLDED POLYSTYRENE.

F. UNIT FILTERS SHALL BE WOVEN PANEL WASHABLE TYPE.

G. UNIT SHALL BE FACTORY WIRED AND TESTED AND SHALL INCLUDE TERMINAL BLOCK CAPABLE OF

INCORPORATING 24 VAC, FIELD SUPPLIED HARD WIRED THERMOSTAT. WIRING SHALL BE RATED

ACCORDING TO CURRENT UL LISTING. SAFETIES SHALL INCLUDE A RENEWABLE FUSE ON THE LOW

VOLTAGE SIDE OF THE TRANSFORMER.

27. CHILLED WATER FAN COIL UNIT CONTROLS (SHOP DRAWING REQUIRED):

A. GENERAL: THE CONTROLS SYSTEM SHALL BE AN EXTENSION OF THE OWNER'S EXISTING SIEMENS

BUILDING AUTOMATION SYSTEM FOR DERRING HALL AND IN KEEPING WITH THE CURRENT VT

STANDARDS. EXISTING NETWORK PROTOCOL SHALL BE EXTENDED TO THE NEW EQUIPMENT PROVIDED

FOR THIS PROJECT. INCLUDE GRAPHICS ON THE EXITSING SIEMENS CENTRAL SERVER IN STERRETT

COMPLEX.

B. APPROVED MANUFACTURERS: FURNISH AND INSTALL AUTOMATIC TEMPERATURE CONTROLS (ATC) AS

SHOWN ON THE CONTRACT DRAWINGS AND HEREINAFTER SPECIFIED, FOR A COMPLETE AND

FUNCTIONING SYSTEM. SYSTEM SHALL BE AN EXTENSION OF THE EXISTING SIEMENS INDUSTRIES, INC.

CONTROLS SYSTEM NETWORK. PROVIDE ALL EQUIPMENT AND MATERIALS AS REQUIRED TO

ACCOMPLISH THE SEQUENCE OF CONTROL. MANUFACTURER SHALL BE SIEMENS BUILDING

TECHNOLOGIES, INC. ONLY. INSTALLER'S QUALIFICATIONS REQUIRES FIRMS SPECIALIZING AND

EXPERIENCED IN ELECTRIC/ELECTRONIC CONTROL SYSTEM INSTALLATIONS FOR NOT LESS THAN 3

YEARS. PROVIDE ELECTRICAL PRODUCTS WHICH HAVE BEEN TESTED, LISTED AND LABELED BY UL AND

COMPLY WITH NEMA STANDARDS. COMPLY WITH NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR

CONDITIONING AND VENTILATING SYSTEMS" WHERE APPLICABLE TO CONTROLS AND CONTROL

SEQUENCES.

C. QUALITY ASSURANCE: THE BAS SYSTEM SHALL BE DESIGNED AND INSTALLED, COMMISSIONED AND

SERVICED BY MANUFACTURER EMPLOYED, FACTORY TRAINED PERSONNEL. MANUFACTURER SHALL

HAVE AN IN-PLACE SUPPORT FACILITY WITHIN 2 HOURS RESPONSE TIME OF THE SITE WITH TECHNICAL

STAFF, SPARE PARTS INVENTORY AND NECESSARY TEST AND DIAGNOSTIC EQUIPMENT. DISTRIBUTORS

OR LICENSED INSTALLING CONTRACTORS ARE NOT ACCEPTABLE. THE MANUFACTURER SHALL PROVIDE

FULL TIME, EXPERIENCED PROJECT MANAGER FOR THIS WORK, RESPONSIBLE FOR DIRECT SUPERVISION

OF THE DESIGN, INSTALLATION, START UP AND COMMISSIONING OF THE BAS SYSTEM. MATERIALS AND

EQUIPMENT SHALL BE THE CATALOGUED PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN

PRODUCTION AND INSTALLATION OF AUTOMATIC TEMPERATURE CONTROL SYSTEMS AND SHALL BE

MANUFACTURER'S LATEST STANDARD DESIGN THAT COMPLIES WITH THE SPECIFICATION

REQUIREMENTS. ALL BAS PEER-TO-PEER NETWORK CONTROLLERS, CENTRAL SYSTEM CONTROLLERS

AND LOCAL USER DISPLAYS SHALL BE UL LISTED UNDER STANDARD UL 916, CATEGORY PAZX. ALL

ELECTRONIC EQUIPMENT SHALL CONFORM TO THE REQUIREMENTS OF FCC REGULATION, PART 15,

GOVERNING RADIO FREQUENCY ELECTROMAGNETIC INTERFERENCE AND BE SO LABELED. CONTROL

SYSTEM SHALL BE ENGINEERED, PROGRAMMED AND SUPPORTED COMPLETELY BY REPRESENTATIVE'S

LOCAL OFFICE THAT MUST BE WITHIN 100 MILES OF PROJECT SITE.

D. WARRANTY: WARRANTY SHALL COVER ALL COSTS FOR PARTS, LABOR, ASSOCIATED TRAVEL, AND

EXPENSES FOR A PERIOD OF ONE YEAR FROM COMPLETION OF SYSTEM ACCEPTANCE. HARDWARE AND

SOFTWARE PERSONNEL SUPPORTING THIS WARRANTY AGREEMENT SHALL PROVIDE ON-SITE OR

OFF-SITE SERVICE IN A TIMELY MANNER AFTER FAILURE NOTIFICATION TO THE VENDOR. THE MAXIMUM

ACCEPTABLE RESPONSE TIME TO PROVIDE THIS SERVICE AT THE SITE SHALL BE 24 HOURS MONDAY

THROUGH FRIDAY, 48 HOURS ON SATURDAY AND SUNDAY. THIS WARRANTY SHALL APPLY EQUALLY TO

BOTH HARDWARE AND SOFTWARE.

E. EQUIPMENT: PROVIDE AUTOMATIC TEMPERATURE CONTROL PRODUCTS IN SIZES AND CAPACITIES

INDICATED, CONSISTING OF DAMPERS, SENSORS, AND OTHER COMPONENTS AS REQUIRED FOR A

COMPLETE INSTALLATION. THE NEW CONTROLS SHALL BE SIEMENS INDUSTRIES, INC. DDC TYPE

NETWORKED WITH THE EXISTING SIEMENS BUILDING TECHNOLOGIES, INC. SYSTEM TO PROVIDE

FACILITY-WIDE ACCESS AND SHARING OF INFORMATION. EXCEPT AS OTHERWISE INDICATED, PROVIDE

MANUFACTURER'S CONTROL SYSTEM COMPONENTS AS INDICATED BY PUBLISHED PRODUCT

INFORMATION, DESIGNED AND CONSTRUCTED SIMILAR TO EXISTING INSTALLED DDC SYSTEM. PROVIDE

CONTROL SYSTEMS WITH FUNCTIONAL AND CONSTRUCTION FEATURES AS INDICATED. THE BUILDING

AUTOMATION SYSTEM SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING COMPONENTS:

THE OPERATOR INTERFACE SHALL CONSIST OF HARDWARE AND SOFTWARE THAT ALLOWS FULL USER

MONITORING AND ADJUSTMENT OF SYSTEM PARAMETERS.

SYSTEM APPLICATION CONTROLLERS SHALL MANAGE THE ENERGY AND BUILDING MANAGEMENT

CAPABILITIES OF THE AUTOMATION SYSTEM AS WELL AS FACILITATE REMOTE COMMUNICATIONS AND

CENTRAL MONITORING.

THE DATA COMMUNICATIONS CAPABILITY SHALL ALLOW DATA TO BE SHARED BETWEEN THE VARIOUS

CONTROLLERS IN THE ARCHITECTURE.

END DEVICES SUCH AS SENSORS, ACTUATORS, DAMPERS, VALVES AND RELAYS.

THE FAILURE OF ANY SINGLE COMPONENT SHALL NOT INTERRUPT THE CONTROL STRATEGIES OF OTHER

OPERATIONAL DEVICES. SYSTEM EXPANSION SHALL BE THROUGH THE ADDITION OF END DEVICES,

CONTROLLERS, AND OTHER DEVICES DESCRIBED IN THIS SPECIFICATION.

COMMUNICATION: ALL BUILDING CONTROLLERS SHALL HAVE A COMMUNICATIONS PORT FOR

CONNECTIONS WITH THE OPERATOR INTERFACES.

CONTROL WIRING: PROVIDE CONTROL AND INTERLOCK WIRING, ASSOCIATED CONTROL SYSTEM WIRING,

AND PILOT CIRCUIT WIRING TO ACCOMPLISH ANY CONTROL SEQUENCE OR FUNCTION SHOWN ON THE

DRAWINGS, OR MECHANICAL SYSTEMS AND EQUIPMENT SPECIFICATION. ASSOCIATED CONTROL SYSTEM

WIRING IS DEFINED AS THAT WIRING THAT POWERS OR CONTROLS ANY CONTROL DEVICE PROVIDED FOR

CONTROL OF MECHANICAL SYSTEMS AND EQUIPMENT. PILOT CIRCUIT WIRING IS DEFINED AS THAT

WIRING THAT POWERS OR CONTROLS ANY STARTER AND OTHER CONTROLLER FURNISHED AS A

COMPONENT OF MECHANICAL SYSTEMS AND EQUIPMENT AND THAT IS INTERPOSED IN THE POWER

WIRING; E.G., WIRING FROM A SAFETY DEVICE TO THE STARTER, AND WIRING FROM ONE STARTER TO

ANOTHER FOR CONTROL INTERLOCKS.

F. OPERATOR INTERFACE: BAS SUPPLIER SHALL PROVIDE ACCESS TO THE SYSTEM AS PART OF STANDARD

INSTALLATION. USER SHALL BE ABLE TO ACCESS ALL DISPLAYS OF REAL-TIME DATA THAT ARE PART OF

THE BAS SERVER ON THE OWNER'S NETWORKED PC.

TIME SCHEDULE ADJUSTMENT: ACCESS SHALL ALLOW USER TO VIEW AND EDIT ALL SCHEDULES IN THE

SYSTEM. THIS INCLUDES STANDARD, AND EVENT SCHEDULES. DISPLAY OF SCHEDULES SHALL SHOW

INTERACTION OF ALL SCHEDULES ON A SINGLE DISPLAY SO USER SEES AN OVERVIEW OF HOW ALL

WORK TOGETHER. USER SHALL BE ABLE TO EDIT SCHEDULES FROM THIS DISPLAY.

DISPLAY OF ALL SCHEDULES MUST SHOW ALL ON TIMES FOR STANDARD, AND EVENT SCHEDULES IN

DIFFERENT COLORS ON A GIVEN DAY. IN ADDITION, OFF TIMES FOR EACH MUST ALSO BE SHOWN IN

ADDITIONAL COLORS.

SCHEDULE LIST SHALL SHOW ALL SCHEDULES CURRENTLY DEFINED. THIS LIST SHALL INCLUDE ALL

STANDARD, AND EVENT SCHEDULES. IN ADDITION, USER SHALL BE ABLE TO SELECT A LIST THAT SHOWS

ALL SCHEDULED POINTS AND ZONES.

LOGGING OF INFORMATION: USER SHALL USE STANDARD BROWSER TECHNOLOGY TO VIEW ALL TREND

LOGS IN SYSTEM. USER SHALL BE ABLE TO VIEW LOGGED DATA IN TABULAR FORM OR GRAPHICAL

FORMAT. USER SHALL BE ABLE TO ADJUST TIME INTERVAL OF LOGGED DATA VIEWED AND SHALL BE

ABLE TO ADJUST Y AXIS OF DATA VIEWED IN GRAPHICAL FORMAT. USER SHALL ALSO BE ABLE TO

DOWN-LOAD DATA THROUGH THE WEB INTERFACE TO LOCAL COMPUTER. DATA SHALL BE IN CSV

FORMAT.

ALARM HANDLING: OPERATOR INTERFACE SHALL DISPLAY ALARMS AS THEY OCCUR. USER SHALL BE

ABLE TO ACKNOWLEDGE ALARMS USING BROWSER TECHNOLOGY. IN ADDITION, USER SHALL BE ABLE TO

VIEW HISTORY OF ALARM OCCURRENCE OVER A USER SELECTED TIME FRAME. IN ADDITION, THOSE

ALARMS MAY BE FILTERED FOR VIEWING PER USER SELECTED OPTIONS.

A SINGLE SELECTION SHALL DISPLAY ALL ALARMS THAT HAVE NOT BEEN ACKNOWLEDGED.

PASSWORD SECURITY AND ACTIVITY LOG: ANY AND ALL CHANGES THAT ARE MADE SHALL BE TRACKED

BY THE BAS SYSTEM. THE USER SHALL BE ABLE TO CHANGE ONLY THOSE ITEMS THAT THE USER HAS

AUTHORITY TO CHANGE. A USER ACTIVITY REPORT SHALL SHOW ANY AND ALL ACTIVITY OF THE USERS

THAT HAVE LOGGED IN TO THE SYSTEM REGARDLESS OF WHETHER THOSE CHANGES WERE MADE USING

A BROWSER OR VIA THE BAS WORKSTATION.

BACNET - MS/TP: ETHERNET - MS/TP MODULE SHALL AS A MINIMUM SUPPORT MS/TP AND ETHERNET

BACNET LAN TYPES. IT SHALL COMMUNICATE DIRECTLY VIA THESE BACNET LANS AS A NATIVE BACNET

DEVICE AND SHALL SUPPORT SIMULTANEOUS ROUTING FUNCTIONS BETWEEN ALL SUPPORTED LAN

TYPES. GLOBAL CONTROLLER SHALL BE A BACNET CONFORMANCE CLASS 3 DEVICE AND SUPPORT ALL

BACNET SERVICES NECESSARY TO PROVIDE THE SEQUENCE OF CONTROL.

G. SENSORS AND MISCELLANEOUS DEVICES

TEMPERATURE SENSORS: ALL TEMPERATURE SENSORS TO BE SOLID STATE ELECTRONIC,

FACTORY-CALIBRATED TO WITHIN 0.5°F, TOTALLY INTERCHANGEABLE WITH HOUSING APPROPRIATE FOR

APPLICATION. WALL SENSORS TO BE INSTALLED AS INDICATED ON DRAWINGS. MOUNT 48 INCHES ABOUT

FINISHED FLOOR. DUCT SENSORS TO BE INSTALLED SUCH THAT THE SENSING ELEMENT IS IN THE MAIN

AIR STREAM. IMMERSION SENSORS TO BE INSTALLED IN WELLS PROVIDED BY CONTROL CONTRACTOR,

BUT INSTALLED BY MECHANICAL CONTRACTOR. IMMERSION WELLS SHALL BE FILLED WITH THERMAL

COMPOUND BEFORE INSTALLATION OF IMMERSION SENSORS. OUTSIDE AIR SENSORS SHALL BE

INSTALLED AWAY FROM EXHAUST OR RELIEF VENTS, NOT IN AN OUTSIDE AIR INTAKE AND IN A LOCATION

THAT IS IN THE SHADE MOST OF THE DAY.

NETWORK CONNECTION TOOL: NETWORK CONNECTION TOOL SHALL ALLOW TECHNICIAN TO CONNECT A

LAPTOP TO ANY MS/TP NETWORK OR AT ANY MS/TP DEVICE AND VIEW AND MODIFY ALL INFORMATION

THROUGHOUT THE ENTIRE BACNET NETWORK. LAPTOP CONNECTION TO TOOL SHALL BE VIA ETHERNET

OR PTP. PROVIDE QUICK CONNECT TO MS/TP LAN AT EACH CONTROLLER. TOOL SHALL BE ABLE TO

ADJUST TO ALL MS/TP BAUD RATES SPECIFIED IN THE BACNET STANDARD.

H. ELECTRONIC ACTUATORS AND VALVES: UL LISTED STANDARD 873 AND C.S.A. CLASS 4813 02 CERTIFIED.

NEMA 2 RATED ENCLOSURES FOR INSIDE MOUNTING, PROVIDE WITH WEATHER SHIELD FOR OUTSIDE

MOUNTING. FIVE-YEAR MANUFACTURERS WARRANTY. TWO-YEAR UNCONDITIONAL AND THREE-YEAR

PRODUCT DEFECT FROM DATE OF INSTALLATION.

EXECUTION DETAILS FOR ACTUATORS AND VALVES: EACH DDC ANALOG OUTPUT POINT SHALL HAVE AN

ACTUATOR FEEDBACK SIGNAL, INDEPENDENT OF CONTROL SIGNAL, WIRED AND TERMINATED IN THE

CONTROL PANEL FOR TRUE POSITION INFORMATION AND TROUBLESHOOTING. OR THE ACTUATOR

FEEDBACK SIGNAL MAY BE WIRED TO THE DDC AS AN ANALOG INPUT FOR TRUE ACTUATOR POSITION

STATUS.

ACTUATORS FOR CONTROL VALVES ½" TO 6" SHALL BE ELECTRIC UNLESS OTHERWISE SPECIFIED,

PROVIDE ACTUATORS AS FOLLOWS:UL LISTED STANDARD 873 AND CANADIAN STANDARDS ASSOCIATION

CLASS 481302 SHALL CERTIFY ACTUATORS. NEMA 2 RATED ACTUATOR ENCLOSURES. 5 YEAR

MANUFACTURERS WARRANTY. TWO-YEAR UNCONDITIONAL + THREE YEAR PRODUCT DEFECT FROM DATE

OF INSTALLATION. MECHANICAL SPRING SHALL BE PROVIDED WHEN SPECIFIED. CAPACITORS OR OTHER

NON-MECHANICAL FORMS OF FAIL-SAFE ARE NOT ACCEPTABLE. POSITION INDICATOR DEVICE SHALL BE

INSTALLED AND MADE VISIBLE TO THE EXPOSED SIDE OF THE ACTUATOR. FOR DAMPER SHORT SHAFT

MOUNTING, A SEPARATE INDICATOR SHALL BE PROVIDED TO THE EXPOSED SIDE OF THE ACTUATOR.

OVERLOAD PROTECTION: ACTUATORS SHALL PROVIDE PROTECTION AGAINST ACTUATOR BURNOUT BY

USING AN INTERNAL CURRENT LIMITING CIRCUIT OR DIGITAL MOTOR ROTATION SENSING CIRCUIT.

CIRCUIT SHALL INSURE THAT ACTUATORS CANNOT BURN OUT DUE TO STALLED DAMPER OR MECHANICAL

AND ELECTRICAL PARALLELING. END SWITCHES TO DEACTIVATE THE ACTUATOR AT THE END OF

ROTATION ARE ACCEPTABLE ONLY FOR BUTTERFLY VALVE ACTUATORS.

A PUSH BUTTON GEARBOX RELEASE SHALL BE PROVIDED FOR ALL NON-SPRING ACTUATORS.

MODULATING ACTUATORS SHALL BE 24VAC AND CONSUME 10VA POWER OR LESS.

CONDUIT CONNECTORS ARE REQUIRED WHEN SPECIFIED AND WHEN CODE REQUIRES IT.

CONTROL VALVES: THE BAS CONTRACTOR SHALL FURNISH AND SIZE ALL AUTOMATIC CONTROL VALVES

UNLESS PROVIDED WITH PACKAGED EQUIPMENT. THE PIPING CONTRACTOR SHALL INSTALL ALL VALVES

UNLESS PROVIDED WITH PACKAGED EQUIPMENT. VALVE BODIES SHALL BE 2-WAY MODULATING AND

3-WAY MODULATING. VALVE BODIES 2" AND SMALLER SHALL BE BRONZE, SCREWED TYPE AND SHALL BE

RATED AT 250 PSIG. VALVES SHALL BE SIZED BY THE CONTROL MANUFACTURER AND THE MAXIMUM

ALLOWABLE PRESSURE DROP SHALL BE 5 FT. WATER COLUMN. VALVES SHALL HAVE STAINLESS STEEL

STEMS AND ALLOW FOR SERVICING INCLUDING PACKING, STEM AND DISK REPLACEMENT. STEAM

CONTROL VALVES AND ACTUATORS SHALL BE FLOWRITE 599 SERIES OR EQUAL WITH BRONZE BODY,

ANSI CLASS 250 CONSTRUCTION, ANSI LEAKAGE CLASS IV (0.01% OF CV). ACTUATOR SHALL BE 24 VAC

FOR PROPORTIONAL CONTROL AND UL LISTED.

I. ENCLOSURES: ALL CONTROLLERS, POWER SUPPLIES AND RELAYS SHALL BE MOUNTED IN ENCLOSURES.

ENCLOSURES MAY BE NEMA 1 WHEN LOCATED IN A CLEAN, DRY, INDOOR ENVIRONMENT. INDOOR

ENCLOSURES SHALL BE NEMA 12 WHEN INSTALLED IN OTHER THAN A CLEAN ENVIRONMENT.

ENCLOSURES SHALL HAVE HINGED, LOCKING DOORS. PROVIDE LAMINATED PLASTIC NAMEPLATES FOR

ALL ENCLOSURES IN ANY MECHANICAL ROOM OR ELECTRICAL ROOM. INCLUDE LOCATION AND UNIT

SERVED ON NAMEPLATE. LAMINATED PLASTIC SHALL BE 1/8” THICK SIZED APPROPRIATELY TO MAKE

LABEL EASY TO READ.

J. EXECUTION

EXAMINATION: PRIOR TO STARTING WORK, CAREFULLY INSPECT INSTALLED WORK OF OTHER TRADES

AND VERIFY THAT SUCH WORK IS COMPLETE TO THE POINT WHERE WORK OF THIS SECTION MAY

PROPERLY COMMENCE. NOTIFY THE OWNERS' REPRESENTATIVE IN WRITING OF CONDITIONS

DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE WORK. DO NOT BEGIN WORK UNTIL ALL

UNSATISFACTORY CONDITIONS ARE RESOLVED.

INSTALLATION (GENERAL): INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. PROVIDE

ALL MISCELLANEOUS DEVICES, HARDWARE, SOFTWARE, INTERCONNECTIONS INSTALLATION AND

PROGRAMMING REQUIRED TO ENSURE A COMPLETE OPERATING SYSTEM IN ACCORDANCE WITH THE

SEQUENCES OF OPERATION AND POINT SCHEDULES.

LOCATION AND INSTALLATION OF COMPONENTS: LOCATE AND INSTALL COMPONENTS FOR EASY

ACCESSIBILITY; IN GENERAL, MOUNT 48 INCHES ABOVE FLOOR WITH MINIMUM 3'-0" CLEAR ACCESS SPACE

IN FRONT OF UNITS. OBTAIN APPROVAL ON LOCATIONS FROM OWNER'S REPRESENTATIVE PRIOR TO

INSTALLATION. ALL INSTRUMENTS, SWITCHES, TRANSMITTERS, ETC., SHALL BE SUITABLY WIRED AND

MOUNTED TO PROTECT THEM FROM VIBRATION, MOISTURE AND HIGH OR LOW TEMPERATURES. IDENTIFY

ALL EQUIPMENT AND PANELS. PROVIDE PERMANENTLY MOUNTED TAGS FOR ALL PANELS. PROVIDE

STAINLESS STEEL OR BRASS THERMOWELLS SUITABLE FOR RESPECTIVE APPLICATION AND FOR

INSTALLATION UNDER OTHER SECTIONS--SIZED TO SUIT PIPE DIAMETER WITHOUT RESTRICTING FLOW.

HVAC SPECIFICATIONS:

Page 18: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

MEH

INTERLOCKING AND CONTROL WIRING: PROVIDE ALL INTERLOCK AND CONTROL WIRING. ALL WIRING SHALL

BE INSTALLED NEATLY AND PROFESSIONALLY, IN ACCORDANCE WITH SPECIFICATION DIVISION 16 AND ALL

NATIONAL, STATE AND LOCAL ELECTRICAL CODES. PROVIDE WIRING AS REQUIRED BY FUNCTIONS AS

SPECIFIED AND AS RECOMMENDED BY EQUIPMENT MANUFACTURERS, TO SERVE SPECIFIED CONTROL

FUNCTIONS. PROVIDE SHIELDED LOW CAPACITANCE WIRE FOR ALL COMMUNICATIONS TRUNKS. CONTROL

WIRING SHALL NOT BE INSTALLED IN POWER CIRCUIT RACEWAYS. MAGNETIC STARTERS AND DISCONNECT

SWITCHES SHALL NOT BE USED AS JUNCTION BOXES. PROVIDE AUXILIARY JUNCTION BOXES AS REQUIRED.

COORDINATE LOCATION AND ARRANGEMENT OF ALL CONTROL EQUIPMENT WITH THE OWNER'S

REPRESENTATIVE PRIOR TO ROUGH-IN. PROVIDE AUXILIARY PILOT DUTY RELAYS ON MOTOR STARTERS AS

REQUIRED FOR CONTROL FUNCTION. PROVIDE POWER FOR ALL CONTROL COMPONENTS FROM NEAREST

ELECTRICAL CONTROL PANEL OR AS INDICATED ON THE ELECTRICAL DRAWINGS--COORDINATE WITH

ELECTRICAL CONTRACTOR. ALL CONTROL WIRING IN THE MECHANICAL, ELECTRICAL, TELEPHONE AND BOILER

ROOMS TO BE INSTALLED IN RACEWAYS. ALL OTHER WIRING TO BE INSTALLED NEATLY AND

INCONSPICUOUSLY PER LOCAL CODE REQUIREMENTS. IF LOCAL CODE ALLOWS, CONTROL WIRING ABOVE

ACCESSIBLE CEILING SPACES MAY BE RUN WITH PLENUM RATED CABLE (WITHOUT CONDUIT).

DDC OBJECT TYPE SUMMARY: PROVIDE ALL DATABASE GENERATION. SYSTEM DISPLAYS SHALL SHOW ALL

ANALOG AND BINARY OBJECT TYPES WITHIN THE SYSTEM. THEY SHALL BE LOGICALLY LAID OUT FOR EASY

USE BY THE OWNER. PROVIDE OUTSIDE AIR TEMPERATURE INDICATION ON ALL SYSTEM DISPLAYS

ASSOCIATED WITH ECONOMIZER CYCLES. AT A MINIMUM, RUN TIME TOTALIZATION SHALL BE INCORPORATED

FOR EACH MONITORED SUPPLY FAN, RETURN FAN, EXHAUST FAN. WARNING LIMITS FOR EACH POINT SHALL

BE ENTERED FOR ALARM AND OR MAINTENANCE PURPOSES. ALL BINARY AND ANALOG OBJECT TYPES

(INCLUDING ZONES) SHALL HAVE THE CAPABILITY TO BE AUTOMATICALLY TRENDED. ALL ANALOG INPUTS

(HIGH/LOW LIMITS) AND SELECTED BINARY INPUT ALARM POINTS SHALL BE PRIORITIZED AND ROUTED

(LOCALLY OR REMOTELY) WITH ALARM MESSAGE PER OWNER'S REQUIREMENTS. PROVIDE BACK-UP

DATABASE FOR ALL STAND-ALONE APPLICATION CONTROLLERS ON DISK.

K. FIELD SERVICES: PREPARE AND START LOGIC CONTROL SYSTEM UNDER PROVISIONS OF THIS SECTION.

START-UP AND COMMISSION SYSTEMS. ALLOW SUFFICIENT TIME FOR START-UP AND COMMISSIONING PRIOR

TO PLACING CONTROL SYSTEMS IN PERMANENT OPERATION. PROVIDE THE CAPABILITY FOR OFF-SITE

MONITORING AT CONTROL CONTRACTOR'S LOCAL OR MAIN OFFICE. AT A MINIMUM, OFF-SITE FACILITY SHALL

BE CAPABLE OF SYSTEM DIAGNOSTICS AND SOFTWARE DOWNLOAD. OWNER SHALL PROVIDE PHONE LINE

FOR THIS SERVICE FOR 1 YEAR OR AS SPECIFIED. PROVIDE OWNER'S REPRESENTATIVE WITH SPARE PARTS

LIST. IDENTIFY EQUIPMENT CRITICAL TO MAINTAINING THE INTEGRITY OF THE OPERATING SYSTEM.

L. TRAINING: PROVIDE APPLICATION ENGINEER TO INSTRUCT OWNER IN OPERATION OF SYSTEMS AND

EQUIPMENT. PROVIDE SYSTEM OPERATOR'S TRAINING TO INCLUDE (BUT NOT LIMITED TO) SUCH ITEMS AS

THE FOLLOWING: MODIFICATION OF DATA DISPLAYS, ALARM AND STATUS DESCRIPTORS, REQUESTING DATA,

EXECUTION OF COMMANDS AND REQUEST OF LOGS. PROVIDE THIS TRAINING TO A MINIMUM OF 3 PERSONS.

PROVIDE ON-SITE TRAINING ABOVE AS REQUIRED, UP TO 4 HOURS AS PART OF THIS CONTRACT.

M. DEMONSTRATION: PROVIDE SYSTEMS DEMONSTRATION. DEMONSTRATE COMPLETE OPERATING SYSTEM TO

OWNER'S REPRESENTATIVE. PROVIDE CERTIFICATE STATING THAT CONTROL SYSTEM HAS BEEN TESTED AND

ADJUSTED FOR PROPER OPERATION.

N. CONTROL SEQUENCES:

FAN COIL UNITS (FC):

OCCUPIED MODE: ON A CALL FOR COOLING FROM A WALL MOUNTED TEMPERATURE SENSOR THE BAS SHALL

CONTINUOUSLY RUN THE UNIT FAN AND MODULATE THE 2-WAY CHILLED WATER VALVE AS REQUIRED TO

MAINTAIN SETPOINT.

UNOCCUPIED MODE: THE UNIT SHALL OPERATE TO MAINTAIN THE NIGHT TEMPERATURE SETBACK.

MORNING WARM-UP/COOL-DOWN: THE BAS SHALL OPTIMALLY CYCLE THE UNIT AND MODULATE THE HEATING

OR COOLING TO REACH OCCUPIED SETPOINT BY SCHEDULED OCCUPIED TIME.

A CONDENSATE OVERFLOW SWITCH FOR EACH FAN COIL UNIT SHALL SHUT OFF THE FAN COIL UNIT FAN AND

ALARM THE BAS IF A HIGH CONDENSATE LEVEL TRIPS THE SWITCH.

HVAC SPECIFICATIONS (CONTINUED):

Page 19: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR NEW WORK PLAN - DUCTWORKSCALE: 1/8" = 1'-0"

LAB

5029

LAB

5029B

CORRIDOR

CR-5B

LAB

5005B

LAB

5005

LAB

5014

CORRIDOR

CR-5A

LAB

5034

LAB

5026

LAB

5016

OFFICE

5016B

1

1

FC-5

FC-5

1FC-6

1FC-6

250/1024

(TYP. FOR 2)

160/

0824

10" Ø

10" Ø

18x8

500/16x16

CR

8" Ø

12" Ø 12" Ø

12" Ø

12" Ø

365/1224

(TYP. FOR 2)

360/1224

(TYP. FOR 2)

800/20x12

TR

800/22x22

CR

15x18

825/20x12

TR

825/22x22

CR

375/1224

(TYP. FOR 4)

12" Ø

12" Ø

24x8

2

2

2

2

22

22

2

22x14

4

4

4

4

4

43x16 39x16 37x14 30x12

30x8

34x20 38x14

27x1

4

27x1

2

16x12

24x8

27x18

30x1833x1843x18

27x12

16x12

16x12

27x1

816

x18

18x8

34x20

27x1

2

27x1

1

27x1

415

x14

16x1

2

5

5

OFFICE

5014A

12" Ø 1

FC-66

22x14

6

4

CS135CS

139

CE

22

VS121

CE18

VS120VS118

7

7 12x6

24x7

4

18x8

22x11

8

9

10

32x12

VS123VS122

VE84VE86 VE88

VS126

VS124

VS130 VS133

CS140

VS127

LINE OF NEW

CEILING BULKHEAD

LINE OF NEW

CEILING BULKHEAD

3 2

2

2 600/18x12

CR

600/18x12

CR

18x10 18x10

42

2 2

300/1024

(TYP. FOR 2)

300/1024

(TYP. FOR 2)

10" Ø

(TYP. FOR 4)

3

32

4

4

5

FC-6

PARTIAL FIFTH FLOOR NEW WORK PLAN - PIPINGSCALE: 1/8" = 1'-0"

T T

T

T

TTO FC-5

TO FC-6TO FC-6

CO

CO

LAB

5029

LAB

5029B

CORRIDOR

CR-5B

LAB

5005B

LAB

5005

LAB

5010

LAB

5014

CORRIDOR

CR-5A

LAB

5034LAB

5026

LAB

5016

OFFICE

5016B

CO

EXISTING 1-1/2"

LP STEAM

1-1/2" LP

1-1/2" LP

1" LP

3/4" LP

TO FC-6

TO FC-5

FC-5

FC-5

FC-6

FC-6

2-1/2" CWS

FRM ABV.

2-1/2" CWR

TO ABV.

1 1/

4"C

WR

1 1/

4"C

WS

1 1/

4"C

WS

1 1/

4"C

WR

2-1/2" CWS2-1/2" CWR

2" CWS

2" CWR

1-1/2" CWS1-1/2" CWR

1-1/4"1-1/4"

1

2

3

3

3

5

5

1

1

2 23

4

2

3

3

1

3

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

MEH

PLAN NOTES:

1. FAN COIL UNIT MOUNTED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. COORDINATE LOCATION WITH CEILING GRID EXISTING

DUCTWORK, PIPING, CONDUIT, SPRINKLER PIPING, AND OTHER NEW AND EXISTING UTILITIES. PROVIDE MANUFACTURER RECOMMENDED SERVICE

CLEARANCES AND REFRIGERANT PIPING CONNECTION LENGTHS.

2. CONNECT NEW DUCT TO EXISTING. TRANSITION AS REQUIRED AND SEAL AIR-TIGHT.

3. NEW DUCT FULL SIZE OF EXISTING DUCT. PROVIDE CAPPED END AND SEAL CONNECTION AIR-TIGHT.

4. EXISTING EXHAUST DUCT, AIR DEVICES, AND ACCESSORIES ARE POTENTIALLY HAZARDOUS AND CHEMICAL LADEN. CONTRACTOR SHALL TAKE PROPER

SAFETY PRECAUTIONS IN ACCORDANCE WITH CURRENT OSHA AND ENVIRONMENTAL HEALTH AND SAFETY STANDARDS WHEN HANDLING DURING

DEMOLITION. COORDINATE CLOSELY WITH THE UNIVERSITY ENVIRONMENTAL HEALTH AND SAFETY DEPARTMENT.

5. CONNECT NEW DUCT TO EXISTING CHEMICAL/FUME EXHAUST HOOD TO BE RE-USED. EXTEND AND CONNECT TO EXISTING EXHAUST RISER.

6. TOP REGISTER IN NEW BULKHEAD.

7. CONNECT NEW EXHAUST DUCT TO HOOD BELOW AND TO EXISTING EXHAUST BOX.

8. 80"x42"x24" TYPE II EXHAUST HOOD ABOVE OVENS. SET MD FOR 550 CFM. INSTALL IN STRICT ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS.

9. 108"x57"x24" TYPE II EXHAUST HOOD ABOVE AUTOCLAVES. SET MD FOR 550 CFM. INSTALL IN STRICT ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS

10. 18x8 TRANSFER DUCT WITH 16X16 CG (TYP. FOR 2).

PLAN NOTES:

1. FAN COIL UNIT MOUNTED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. COORDINATE LOCATION WITH CEILING GRID

EXISTING DUCTWORK, PIPING, CONDUIT, AND OTHER NEW AND EXISTING UTILITIES. PROVIDE MANUFACTURER RECOMMENDED SUPPORTS,

SERVICE CLEARANCES AND PIPING CONNECTION LENGTHS.

2. 1-1/4" COLD WATER SUPPLY AND RETURN PIPING TO/FROM FAN COIL UNIT. ROUTE CLEAR OF UNIT SERVICE ACCESS AND COORDINATE

LOCATION WITH EXISTING UTILITIES. SEAL PIPE WALL PENETRATIONS WEATHER-TIGHT.

3. 1-1/4" CONDENSATE PIPING. PROVIDE CLEAN-OUT. ROUTE CLEAR OF UNIT SERVICE ACCESS.

4. 1-1/4" CONDENSATE PIPING DOWN. TERMINATE MINIMUM 4" ABOVE FLOOR DRAIN - MAXIMUM 6" COORDINATE LOCATION WITH PLUMBING

PLANS.

5. CONNECT NEW LP STEAM PIPING AND EXTEND AND CONNECT TO NEW AUTOCLAVES. SIZE AS RECOMMENDED BY THE MANUFACTURER.

COORDINATE LOCATION WITH EQUIPMENT. SECURE PIPING TO WALL.

0 16 24 328

1/8" = 1' - 0"

LEGEND:

1-HR FIRE WALL

2-HR FIRE WALL

Page 20: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL PENTHOUSE FLOOR NEW WORK PLAN - PIPINGSCALE: 1/8" = 1'-0"

EX 8" CWS

EX 8"CWR

EXIST.

HPU2-1/2" CWS DOWN

2-1/2" CWR FROM BELOW

4"LPR

1/4

" LP

R

PENTHOUSE

F-1

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

SSL

0 16 24 328

1/8" = 1' - 0"

Page 21: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR DEMOLITION PLAN - LIGHTINGSCALE: 1/8" = 1'-0"

ER

EMERGENCY LIGHTING

UNIT, TO BE REMOVED

EMERGENCY

LIGHTING UNIT,

TO BE REMOVED

ER

ER

ER

ER

ER

ER

ER ER

ER ER ER ER ERER

ER ER ER ER ERER

ER ER ER ER ERER

EM

EM

ERERER ER ER ER

ERERERERERER

ER ER ER ER ER

LAB

5005

LAB

5005B

LAB

5017

LAB

5029B

LAB

5029

LAB

5029A

OFFICE

5029C

ICE

E03

CORRIDOR

CR-5B

OFFICE

5014A

LAB

5014

LAB

5010 LAB

5000

LAB

5007LAB

5034

LAB

5026

LAB

5026

LAB

5016

JANITOR

E06

CORRIDOR

CR-5C

OFFICE

5016B

CORRIDOR

CR-5A

ER ER

ER ER

ER ER

ER ER

ER

ER

ER ER ER

ER

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

JTO

GENERAL NOTES:

1. THE EXISTING CIRCUITS SERVING LIGHT FIXTURES BEING REMOVED SHALL BE DISCONNECTED AND RETAINED FOR

RECONNECTION TO THE NEW LIGHT FIXTURES.

2. WHERE A SWITCH IS INDICATED TO BE REMOVED, THE EXISTING OUTLET BOX SHALL BE RETAINED FOR REUSE.

0 16 24 328

1/8" = 1' - 0"

Page 22: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR DEMOLITION PLAN - POWERSCALE: 1/8" = 1'-0"

1

4

1

4

1

4

4

4

4

3

1

4

PSPS

4

2

ER ERER

PNL-PC53PNL-LC51

PNL-ELEC

PSPS

6

6

6

6

6 66

EXISTING PANEL - PC-51

6

ERER

ER

ER

1

10

EXISTING CONDUIT

6

6

6

66 6 6

6

6

66

66

6 6

6

8 8 8

9

DISCONNECTEXISTING HOOD

5

5

5

5

EXISTING HOOD AND ALL ELECTRICALCONNECTIONS TO REMAIN

LAB

5005

LAB

5005B

LAB

5017

LAB

5029B

LAB

5029

LAB

5029A

OFFICE

5029C

ICE

E03

CORRIDOR

CR-5B

OFFICE

5014A

LAB

5014

LAB

5010LAB

5000

LAB

5007

LAB

5034

LAB

5026

LAB

5026

LAB

5016

JANITOR

E06

CORRIDOR

CR-5C

OFFICE

5016B

CORRIDOR

CR-5A

1-HR FIRE WALL (TYP.)

2-HR FIRE WALL (TYP.)

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

CAD

DEMOLITION NOTES:

1. REMOVE RECEPTACLES AND COVER PLATES IN FLUSH BOXES, UNO.RETAIN THE EXISTING WIRING AND OUTLET BOX FOR REUSE,RECEPTACLES SHALL BE REPLACED.

2. REMOVE PLUG STRIP FROM CASEWORK TO ALLOW INSTALLATION OFNEW COUNTERTOPS.

3. DISCONNECT ALL ELECTRICAL CONNECTIONS TO COLD ROOM TOALLOW REMOVAL OF COLD ROOM.

4. REMOVE ALL SURFACE MOUNTED CONDUIT AND SURFACE RACEWAY.

5. EXISTING FIRE ALARM DEVICE TO REMAIN. PROTECT DURINGCONSTRUCTION.

6. REMOVE RECEPTACLE, COVER PLATE AND WIRE BACK TO PANEL.PROVIDE BLANK COVER ON OUTLET BOX.

7. NOT USED.

8. EXISTING CIRCUITS IN THIS ROOM ARE FROM PANEL - PC53.DISCONNECT CIRCUITS 2,3,4,5,6,7,8,9,10,11,13, AND 28. REMOVECONDUCTORS FROM PANEL TO OUTLETS. REMOVE CONDUIT WHEREACCESSIBLE.

9. EXISTING CIRCUITS TO PLUG STRIP ON LAB TABLES. REMOVECONDUCTORS. CONDUIT WILL BE USED TO FEED NEW RECEPTACLESON TABLES. SEE SHEET E1.2.

10. EXISTING CIRCUITS IN THIS ROOM ARE FROM EXISTING PANEL PC-51.DISCONNECT CIRCUITS 8,10,11,12,13,14,16,23 AND 27. REMOVECONDUCTORS FROM DEVICES BACK TO PANEL. WHERE ACCESSIBLE.

208Y/120V

SURFACE

YES

PLUGMOLD 5014 (EXISTING)

RECEP IN FUME HOOD 5028 (EXIST ING)

RECEPTACLES 5022 (EXISTING)

RECEPTACLES ON TABLE 5016 ( NOTE2)

RECEPTACLES 5028A-5028B (EXIST)

RECEPTACLE B5028 (EXISTING)

LOAD SERVED

INTERRUPT RATING:

''

''

DISC SWITCH 5026 C (EXISTING)

''

208 VOLT RECE. 5014 $5022 (EXISTING)

''

208 VOLT RECEPTACLE 5016 (EXISTING)

''

RECEPTACLE IN FUME HOOD 5020 EXISTING)

SPARE (NOTE 1)

PLUGMOLD 5022 (EXISTING)

FUME HOOD RECEP. 5016 (EXISTING)

RECEPTACLES ON TABLE 5016 ( NOTE2)

RECEPTACLES 5016-5028 (EXISTING)

PLUGMOLD 5014 (EXISTING)

MOUNTING:

VOLTAGE:

SOLID NEUTRAL:

-

--

--

0

10,000 AIC

-

-

-

40/2

20/2

0 0

-

--

-

-

--

-

20/1

-

30/2

-

20/2

''

BECKMAN (EXISTING)

''

''

208 VOLT HOOD RECEP 5022 (EXISTING)

''CENTRIFUGE (EXISTING)

PLUGMOLD 5028 (EXISTING)

RECEPTACLES 5014-5022 (EXISTING)'

SPARE (NOTE 1)

SPARE (NOTE 1)

L3

--

-.72

--

--

--

-

20/1

-

20/2

20/2

20/1

20/1

20/1

20/1

-

--

--

- -

- -

.72

20/1

20/1

20/1

20/1

20/1

20/1

-

BKR

-

-.72

-

--

- -

L1

- -

L2

20/1

-

20/2

20/2

20/1

20/1

20/1

20/1

PLUGMOLD 5028B (EXISTING)

208 VOLT RECEP 5016 (EXISTING)

-

RECEPTACLE 5028 (EXISTING)

RECEPTACLES ON TABLE 5016 ( NOTE2)

RECEPTACLES 5014 (EXISTING)

UNKNOWN (EXISTING)

20/1

20/1

20/1

20/1

20/1

BKR

20/1

20/1

SPARE (NOTE 1)

SPARE (NOTE 1)

PLUGMOLD 5028 (EXISTING)

PLUGMOLD 5028 (EXISTING)

LOAD SERVED

BUS RATING:

MAIN:

SYSTEM: 3PH, 4W

EXISTING PANEL PC51

100A

GROUND BUS:

INTEGRAL SPD:

YES

LOADS ( )

LIGHTING

REC TO 10 KVA

REC REMAINING

LARGEST MOTOR

SPACE HEATING

KITCHEN EQUIPMENT

CONNECTED

0

0

0

0

0

0

0

0

DEMAND

1.25

1.0

0.5

1.0

0.25

0.0

1.0

1.25

0

0

0

0

0

0

0

0

FACTOR

TOTAL CONNECTED LOAD

MIN. FEEDER / PANEL CAPACITY

0 1.0 0

CONTINUOUS

NON-CONTINUOUS

DEMAND

00

0 0

AMPSKVA

KVA AMPS

33

9

25

29

31

27

17

23

19

21

13

15

11

1

5

7

3

CKT

34

10

26

30

32

28

18

22

24

20

14

16

12

2

6

8

4

CKT

KVA

DEMAND 0 1.0 0

OVERALL DEMAND FACTOR 1

100A MLO NO

--

3/4"

3/4"

3/4"

3/4"

-

-

3/4"

-

-

#8

#8

#12

#12

#12

#12

#12

#12

3/4"

3/4"

-

3/4"

3/4"

3/4"

3/4"

-

#12

#12

#12

#12

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

COND

#12

#12

#12

#12

PHASE NEUT GND

-

-

#8

-

#12

-

#12

-

-

-

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12 #12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

-

#12

-

#12

-

#12

-

#10

-

-

#12

#12

#12

-

-

-

-

#12

#12

#12

#12

#12

#12

-

#12

-

#12

-

#10

-

#12

NEUT

3/4"#12

-

3/4"

-

3/4"

#10

#10

#12

#12

-

3/4"

-

3/4"

#12

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

#12

#12

#12

#12

3/4"

-

-

#12

-

-

-

-

3/4"

3/4"

-

-

#12

#12

PHASE COND

3/4"#12

#12

-

#10

-

#12

-

#12

-

#12

#12

#12

#12

#12

#12

-

-

-

-

#12

#12

GND

#12

LOADS (KVA)

WATER HEATING

AIR CONDITIONING 0

0

CONNECTED

0

0

DEMANDFACTOR

1.0

1.0

DEMAND

NON-SEASONAL MOTORS

L1 L2 L3

PHASE LOAD TOTALS1. REMOVE CONDUCTORS AND CONDUIT WHERE ACCESSIBLE.

2. EXISTING BREAKER TO BE REUSED. PROVIDE NEW CONDUCTOR IN EXISTING CONDUIT.

0 16 24 328

1/8" = 1' - 0"

Page 23: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

TYPICAL WALL DEVICE LOCATION DETAILNO SCALE

LIGHT SWITCH(ES)

RECEPTACLE OR

TELECOMM OUTLET

FIRE ALARM

NOTIFICATION DEVICE

DOOR

2"

DEVICES SHOWN IN SAME

AREA ON PLANS SHALL ALIGN

VERTICALLY WITH DEVICES

ABOVE AND/OR BELOW

NOTE:

• NOT ALL DEVICES SHOWN ARE USED IN ALL LOCATIONS. REFER TO THE ELECTRICAL FLOOR PLANS

FOR DEVICE LOCATIONS.

• WHERE DEVICE HEIGHTS INDICATED ON FLOOR PLANS ARE DIFFERENT FROM WHAT IS SHOWN IN

THE DETAIL, THE HEIGHTS INDICATED ON FLOOR PLANS SHALL TAKE PRECEDENCE.

• DEVICES SHOWN SIDE-BY-SIDE ON THE PLANS THAT ARE NOT GANGED TOGETHER SHALL HAVE 2"

OF SEPARATION BETWEEN FACEPLATES UNLESS NOTED OTHERWISE OR UNLESS MORE

SEPARATION IS REQUIRED TO MAINTAIN FIRE RATING OF WALL.

• FOR WALL DEVICES MOUNTED ABOVE ARCHITECTURAL ITEMS (SUCH AS FIRE ALARM STROBES

MOUNTED ABOVE MARKERBOARDS OR TACKBOARDS), COORDINATE MOUNTING HEIGHTS OF WALL

DEVICES SUCH THAT THEY DO NOT INTERFERE WITH ARCHITECTURAL ITEMS. CONFIRM LOCATIONS

WITH ARCHITECT PRIOR TO INSTALLATION.

• THIS DETAIL DOES NOT APPLY TO LOCATIONS WHERE EXISTING SWITCH OUTLETS ARE USED.

• CONFIRM THE LOCATION OF ALL SURFACE MOUNTED RACEWAYS WITH THE ARCHITECT PRIOR TO

INSTALLATION.

3"

1'-4

" T

O

BO

TT

OM

4'-0

" T

O T

OP

7'-6

" T

O B

OT

TO

M M

INIM

UM

OR

8'-0

" T

O T

OP

MA

XIM

UM

FINISHED

FLOOR

DEVICE

SYMBOL

LIGHTING SENSOR AND CONTROL SWITCH LEGEND/SCHEDULE

DESCRIPTION OPERATIONMANUFACTURER / MODEL NUMBER

NOTES:

BASIS OF DESIGN

LD ACUITY nLIGHT nPP16 D SA/SA2

USE WITH VACANCY SENSORS AND MANUAL CONTROLS FOR

MANUAL-ON OPERATION. PROVIDES ON/OFF/RAISE/LOWER

CAPABILITY FOR ONE ZONE OF LIGHTING.

1. DEVICE FINISHES SHALL BE AS OUTLINED IN THE SPECIFICATIONS.

2. IF ONE OF THE "OTHER ACCEPTABLE PRODUCT" SENSORS ARE USED, CONTRACTOR SHALL PROVIDE ADDITIONAL SENSORS AS NEEDED TO COMPLETELY COVER THE SPACE SERVED. QUANTITIES ON DRAWINGS ARE BASED ON

THE COVERAGE OF THE BASIS-OF-DESIGN SENSORS. EXACT LOCATIONS OF ALL SENSORS SHALL BE AS RECOMMENDED BY MANUFACTURER.

3. ALL OCCUPANCY/VACANCY SENSOR TIME DELAYS SHALL BE 15 MINUTES, UNLESS NOTED OTHERWISE.

4. PROVIDE ALL LOW-VOLTAGE WIRING NEEDED FOR A FULLY OPERATIONAL SYSTEM (CAT 5E, 0-10V VIOLET-AND-GRAY, ANY OTHER MANUFACTURER-RECOMMENDED CABLING, PLENUM-RATED WHERE IN AIR HANDLING SPACES,

IN DEDICATED CONDUIT SYSTEM WHERE NOT ABOVE ACCESSIBLE CEILINGS, IN DEDICATED SLEEVES WHERE PENETRATING PARTITIONS).

5. FOR CAT5E "PLUG-AND-PLAY" SYSTEMS, AT LEAST ONE WALL SWITCH IN EACH ROOM SHALL HAVE AN OPEN CAT5E PORT (SO THAT THERE IS AN EASILY ACCESSIBLE OPEN PORT).

6. PROVIDE ALL PROGRAMMING NEEDED TO SET UP SENSORS, POWER PACKS AND LOW-VOLTAGE SWITCHES.

7. LOAD CONTROLLERS SHALL BE LOCATED ABOVE THE NEAREST ACCESSIBLE CEILING (PLENUM-RATED WHERE IN AIR HANDLING SPACES), EXCEPT WHERE LUTRON OR EATON GREENGATE PRODUCTS ARE USED SHALL BE

LOCATED ABOVE THE ACCESSIBLE CEILING IN THE CORRIDOR OUTSIDE THE ROOM SERVED.

8. PROVIDE LOAD CONTROLLERS IN QUANTITIES NEEDED TO SERVE THE NUMBER OF ZONES INDICATED ON THE DRAWINGS. ROOMS MAY SHARE LOAD CONTROLLERS IF THERE ARE SUFFICIENT OUTPUTS AND IF ROOMS CAN

STILL OPERATE INDEPENDENTLY OF ONE ANOTHER. LOAD CONTROLLERS SHALL BE THE DIMMING TYPE WITH 0-10V WIRING IN ROOMS WHERE SWITCHES ARE THE DIMMING TYPE.

9. SEE SPECIFICATIONS FOR MORE DETAILS.

OTHER ACCEPTABLE PRODUCTS

1 ACUITY nLIGHT nPODM DX

USE WITH VACANCY SENSOR(S) FOR MANUAL-ON OPERATION.

PROVIDES ON/OFF/RAISE/LOWER CAPABILITY FOR ONE ZONE ATLOW VOLTAGE SINGLE-ZONE

ON/OFF/RAISE/LOWER SWITCH

HUBBELL NX SYSTEM SWITCH;

WATTSTOPPER DLM SYSTEM SWITCH;

LUTRON seeTOUCH QS SWITCH;ONE OR MORE SWITCH LOCATIONS.

VACANCY SENSOR, 0-10V DIMMING WITH MANUAL-ON AUTO-OFF ACUITY SENSOR SWITCH WSX D SA

HUBBELL LHD SERIES;

WATTSTOPPER PW-311 SERIES;

LUTRON MS-Z101 SERIESD

WALL SWITCH 0-10V DIMMING

OCCUPANCY SENSOR

VACANCY SENSOR ACUITY nLIGHT nCM PDT 10 RJB1LOW VOLTAGE DUAL TECH CEILING

MOUNTED OCCUPANCY SENSOR

HUBBELL NX SYSTEM DUAL TECH CEILING SENSOR;

WATTSTOPPER DLM SYSTEM DUAL TECH CEILING SENSOR;

LUTRON LOS-CDT SERIES;

LOAD CONTROLLER, 0-10V DIMMING

(ON/OFF/RAISE/LOWER)

HUBBELL NX SYSTEM ROOM CONTROLLER;

WATTSTOPPER DLM SYSTEM ROOM CONTROLLER;

LUTRON ENERGI SAVR NODE;

EATON GREENGATE ROOM CONTROLLER DUAL TECH CEILING SENSOR

EATON GREENGATE ROOM CONTROLLER

EATON GREENGATE ROOM CONTROLLER SYSTEM SWITCH

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

JTO

MTG. HGT. SYMBOL DESCRIPTION

ELECTRICAL LEGEND

PLAN NOTE DESIGNATION.1

A1 LIGHTING FIXTURE TYPE DESIGNATION.

ASTERISK DENOTES BOTTOM OF OUTLET BOX MOUNTED 8 IN. ABOVE TOP OF COUNTER.DISTANCE INCLUDES HEIGHT OF BACKSPLASH.

LIGHTING FIXTURE, LED, CEILING MOUNTED.

LIGHTING FIXTURE, LED, CEILING MOUNTED WITH INTEGRAL EMERGENCY LED DRIVER(TYPICAL FOR ALL LIGHTING FIXTURES).

EXISTING EMERGENCY LIGHTING UNIT, SURFACE WALL MOUNTED.

EXISTING EMERGENCY LIGHTING UNIT, SURFACE WALL MOUNTED.

EXISTING GENERAL USE SWITCH, SINGLE POLE. 4'-0" S

RECEPTACLE, DUPLEX, WALL. ALPHA-NUMERIC OR NUMERIC SUBSCRIPT, WHERE SHOWN,INDICATES CIRCUIT. (TYPICAL FOR ALL RECEPTACLES)

1'-4" TO BOT

RECEPTACLE, DUPLEX GFCI, WALL.1'-4" TO BOT

RECEPTACLES, TWO DUPLEX (QUAD) IN A TWO GANG OUTLET BOX, WALL.1'-4" TO BOT

RECEPTACLE, SPECIAL PURPOSE, WALL.1'-4" AFF TOBOT, UNO

FIRE ALARM HORN OR SPEAKER WITH INTEGRAL VISUAL DEVICE, WALL. NUMBERINDICATES VISUAL DEVICE MINIMUM CANDELA RATING.30

F7'-6" TO TOP

FIRE ALARM VISUAL DEVICE, WALL. NUMBER INDICATES VISUAL DEVICE MINIMUMCANDELA RATING.

30F7'-6" TO TOP

208/120 VOLT PANELBOARD.6'-0"

NON-FUSIBLE SAFETY SWITCH, WALL OR EQUIPMENT MOUNTED. NUMBER INDICATESNON-FUSED/3-POLE/60 AMP RATING.N/3/60

5'-0"

CIRCUIT DESIGNATION. DESIGNATION SHOWN INDICATES PANEL 2HB1 AND CIRCUITNUMBER 24.

2HB1-24

CONDUIT CONCEALED IN WALL OR ABOVE CEILING.

EXISTING CONDUIT TO BE REMOVED.

SR1 SURFACE RACEWAY. NUMBER, WHERE SHOWN, INDICATES TYPE AS SCHEDULED ONDRAWINGS OR IN SPECIFICATIONS.

NOTES (ELECTRICAL LEGEND):

1. THESE ARE STANDARD ELECTRICAL SYMBOLS AND MAY NOT ALL APPEAR ON THE PROJECT DRAWINGS.

HOWEVER, WHEREVER AN ELECTRICAL SYMBOL APPEARS ON THE PROJECT DRAWINGS, THE ITEM SHALL BE

FURNISHED AND INSTALLED.

2. MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO TOP OF OUTLET OR EQUIPMENT, UNO. WHERE THE

MOUNTING HEIGHT INDICATED ON THE DRAWINGS IS DIFFERENT FROM THE LEGEND, THE DRAWING TAKES

PRECEDENT. SEE DRAWINGS FOR MOUNTING HEIGHTS NOT INDICATED IN THE LEGEND.

3. SEE ELECTRICAL ABBREVIATIONS FOR ALPHABETIC SUBSCRIPT WITH SYMBOL, UNO.

ELECTRIC WATER COOLEREWC

SCCR SHORT CIRCUIT CURRENT RATING

1. ALL ABBREVIATIONS LISTED MAY NOT APPLY TO THIS PROJECT. REFER TO OTHER ABBREVIATION LISTS

NOTE (ELECTRICAL ABBREVIATIONS):

ELSEWHERE IN THESE DOCUMENTS FOR ABBREVIATIONS NOT LISTED HERE.

IG

IMC INTERMEDIATE METAL CONDUITISOLATED GROUND

GF OR GFI

FLUORFLUOR

HPF

HZ

HW

HPS

HTR

HP

HID

HOA

HG

H OR HOR

GND

FC

GEN

FXTRFXTR

FSD

FSS

FACPFACP

FDR

FA

EXIST

EXT

HIGH INTENSITY DISCHARGE

HORSEPOWER OR HEAT PUMP

HIGH PRESSURE SODIUM

HIGH POWER FACTOR

HAND-OFF-AUTOMATIC

HOT WATER

HERTZ

HEATER

HORIZONTAL

HOSPITAL GRADE

GROUND

FIRE/SMOKE DAMPER

FUSIBLE SAFETY SWITCH

FIRE ALARM CONTROL PANELFIRE ALARM CONTROL PANEL

FOOTCANDLE

GENERATOR

FLUORESCENTFLUORESCENT

GROUND FAULT INTERRUPTER

FIXTURE

EXISTING

EXTERIORFIRE ALARM

FEEDER

WP WEATHERPROOF

TRANSFORMER

TRANSFER

XFMR

XFER

TC TIME CLOCK

VOLT-AMPERE

UNDERGROUND

WATT OR WIRE

VOLT-AMPERE REACTIVE

UNLESS NOTED OTHERWISE

VOLT

VOLTMETER

W

VM

V

VAR

VA

UNDERFLOOR

TYPICAL

TELEVISION

TELEPHONE

UG

UNO

UF

TYP

TV

TEL

MOTOR OPERATED SMOKE DAMPER

SURGE SUPPRESSOR

SYMMETRICAL

SWITCHBOARD

SURFACE RACEWAY

SOLID NEUTRAL

SURFACE METAL RACEWAY

STR STARTER

SWITCHGEAR

SWITCH

SYM

SN

SWGR

SWBD

SW

SECONDARY

SPEAKERSPKR

SSSR

SDR

SEC

SMR

COMB

E OR EMER

ENG

ER

EQUIP

EP

ENCL

EMT

EML

EM

EMN

ELEC

EL

CTRL

DC

DR

DISC

CW

CU

COND

CONT

CT

CONN

CND

CNTR

EXIST RELOCATED TO THIS LOCATION

EXIST REMOVED

EXIST REMOVED AND NEW INSTALLED

ELECTRICAL METALLIC TUBING

EXIST TO REMAIN

EQUIPMENT

ENCLOSURE

EXPLOSIONPROOF

ENGINE

EMERGENCY

ELECTRIC OR ELECTRICAL

DOOR RELEASE SERVICE

CURRENT TRANSFORMER

CONTROL

DISCONNECT

DIRECT CURRENT

COLD WATER

COPPER

CONTACTOR

CONNECTION

CONDUCTOR

COMBINATION

CENTERCONDUIT

BRKR

ASYM

AWG

CATV

CCTV

CF

CKT

CLG

CB

CAB

CA

BD

BEL

AM

ATS

AMPL

AIC

AL

AFF

ABV

AFD

ACACB

A OR AMP

AMERICAN WIRE GAGE

COMPACT FLUORESCENT

CLOSED CIRCUIT TELEVISION

CABLE TV

CIRCUIT BREAKER

CIRCUIT

CEILING

BUS DUCT

BREAKER

CABINET

CABLE

BELOW

ADJUSTABLE FREQUENCY DRIVE

ABOVE FINISHED FLOOR

ALTERNATING CURRENT

ABOVE COUNTER BACKSPLASH

AMPERES INTERRUPTING CAPACITY

AUTOMATIC TRANSFER SWITCH

AMMETER

ALUMINUM

AMPLIFIER

ASYMMETRICAL

ABOVE

AMPERE

MS

PBS PUSHBUTTON STATION

PANELBOARD

POLYVINYL CHLORIDE

RIGID GALVANIZED STEEL CONDUIT

POTENTIAL TRANSFORMER

RECEPTACLE

QUANTITY

REC

RGS

QTY

POWER

PANEL OR PANELBOARD

PHASE

PRIMARY

PTPVC

PWR

PRI

PNLBRD

PH

PNL

PULL BOX OR PUSHBUTTON

MOUNTED OR MOUNTING

MAGNETIC STARTER

MERCURY VAPOR

NON-FUSIBLE SAFETY SWITCH

NATIONAL ELECTRICAL CODE

NFSS

OVERHEAD

POLE

NUMBER

PB

P

OH

NO

NEUTRAL

METER

NEUT

NEC

MTG

MV

MTR

LTG LIGHTING

MAIN DISTRIBUTION FRAME

MAIN LUGS ONLY

THOUSAND CIRCULAR MILS

MOTOR CONTROL CENTER

METAL HALIDE OR MOUNTING HEIGHT

MOTOR OPERATED DAMPER

MASTER ANTENNA TELEVISION

MAIN CIRCUIT BREAKER

MOTOR

MOD

MOT

MLO

MCM

MDF

MH

LUMENS OR LUMINAIRE

MANUALMAGNETIC

MAN

MATV

MCC

MCB

MAGLUM

JUNCTION BOX

LIGHTNING ARRESTER

LOW PRESSURE SODIUM

KILOWATT-HOUR

KILOVOLT-AMPERE

KILOVOLT-AMPERE REACTIVE

KILOWATT

KWH

LPS

LA

KVAR

KW

KVA

KILOVOLT

THOUSAND CIRCULAR MILS

JB

KCMIL

KV

DB DOOR BELL

DS DOOR SWITCH

GD GARAGE DOOR

C COUNTERTOP

ERC ELEVATOR RECALL

ELEV ELEVATOR

UNDERWRITERS' LABORATORIESUL

HGT HEIGHT

REFRIGERATORREFRIG

BOT BOTTOM

DIM DIMENSION

MINIMUMMIN

DWG DRAWING

ARC FAULT INTERRUPTERAF OR AFI

FACU FIRE ALARM CONTROL UNITSURGE PROTECTIVE DEVICESPD

EXIST REMOVED AND RELOCATED

VERTICALVERT

ELECTRICAL ABBREVIATIONS

NIGHT LIGHTNL

SB SOUNDER BASE

RELAY BASERB

MASS NOTIFICATION SYSTEMMNS

KNOCKOUTKO

IC INTERCOM OR INTERRUPTING CAPACITY

TAMPER RESISTANTTR

LRP LIGHTING RELAY PANEL

CR CORROSION RESISTANTNORMALN OR NORM

SL SINGLE STATION

UNDERCOUNTERUC

S/O SPACE ONLY

LIGHT EMITTING DIODELED

SPECIAL PURPOSESP

MANUAL MOTOR STARTERMMS

ECNC EXIST CND AND NEW CONDS

ABD ABANDONED

AIP ABANDONED IN PLACE

INITIALINIT

GFP GROUND FAULT PROTECTION/PROTECTED

INCANDESCENTINC

BAS BUILDING AUTOMATION SYSTEM

MAXIMUM OVER CURRENT PROTECTIONMOCP

MINIMUM CIRCUIT AMPACITY MCA

IDF INTERMEDIATE DISTRIBUTION FRAME

MOTOR/GENERATORM/G

WIRE GUARDWG

GTD GENERATOR TRANSFER DEVICE

VARIABLE FREQUENCY DRIVEVFD

WIRELESS ACCESS POINTWAP

FIXTURE

TYPE

LIGHTING FIXTURE SCHEDULE

MOUNTINGLAMP

(NO.) TYPEREMARKS

LEDA2

MANUFACTURER AND CATALOG NO.

RECESSED

CEILING

2'X2' RECESSED MOUNTED LED ZERO PLENUM TROFFER,

LAY-IN WITH TELESCOPING HOUSING TO INSTALL FROM

BELOW THE CEILING, 3500 LUMENS, 82 CRI, 4000K,

60,000HR, (0-10 VOLT DIMMING), LINEAR PRISMATIC LENS.

COLUMBIA LIGHTING:

LZPT22-40MLG-LSRS-EDU

LIGHTING FIXTURE SCHEDULE NOTES:

1. PROVIDE THE "BASIS OF DESIGN" LIGHT FIXTURES AS SCHEDULED. THESE SCHEDULED LIGHT FIXTURES HAVE BEEN STANDARDIZED FOR THIS

BUILDING BY THE OWNER. ANY SUBSTITUTES FROM THE SCHEDULED LIGHT FIXTURES ABOVE WILL SPECIFICALLY REQUIRE A SAMPLE OF THE

SUBSTITUTED LIGHT FIXTURE(S) FOR THE OWNER AND ARCHITECT TO REVIEW ON-SITE AND FOR OWNER APPROVAL PRIOR TO ORDERING.

2. PROVIDE AN INTEGRAL 1400 LUMEN EMERGENCY BATTERY PACK FOR EACH FIXTURE INDICATED FOR EMERGENCY OPERATION ON THE DRAWINGS.

INPUT

WATTS

31

CONDUIT BELOW FLOOR.

PS

LEDA1RECESSED

CEILING

2'X2' RECESSED MOUNTED LED ZERO PLENUM TROFFER,

LAY-IN WITH TELESCOPING HOUSING TO INSTALL FROM

BELOW THE CEILING, 2800 LUMENS, 82 CRI, 4000K,

60,000HR, (0-10 VOLT DIMMING), LINEAR PRISMATIC LENS.

26COLUMBIA LIGHTING:

LZPT22-40LWG-LSRS-EDU

AVERAGE FOOT-CANDLE LEVELSPACE TYPE

LIGHTING FOOT-CANDLE LEVEL SUMMARY

LAB 5014 62

LAB 5016 63

LAB 5026 55

LAB 5029 60

LAB 5034 64

DEMAND SUMMARY:

THE EXISTING LIGHT FIXTURES, TOTALING

3.46 KVA, ARE BEING DISCONNECTED FROM

EXISTING CIRCUITS. THE NEW LIGHT

FIXTURES, TOTALING 2.06 KVA, ARE BEING

RECONNECTED TO THE EXISTING CIRCUITS,

RESULTING IN A NET REDUCTION OF 1.40 KVA

ON THE PANEL.

JUNCTION BOX, CEILING.J

CONDUIT TURNED DOWN.

LEDA3RECESSED

CEILING

2'X2' RECESSED MOUNTED LED ZERO PLENUM TROFFER,

LAY-IN WITH TELESCOPING HOUSING TO INSTALL FROM

BELOW THE CEILING, 3900 LUMENS, 82 CRI, 4000K,

60,000HR, (0-10 VOLT DIMMING), LINEAR PRISMATIC LENS.

COLUMBIA LIGHTING:

LZPT22-40HLG-LSRS-EDU35

COORDINATION NOTE:

DERRING HALL ELECTRICAL DISTRIBUTION SYSTEM REPAIRS PROJECT MAY BE UNDER

CONSTRUCTION AT THE SAME TIME THIS PROJECT IS UNDER CONSTRUCTION. CONTRACTOR

SHALL FULLY COORDINATE BEFORE STARTING CONSTRUCTION OF THIS PROJECT WITH THAT

OF THE DISTRIBUTION SYSTEM REPAIRS PROJECT NUMBER G707-16-19673.

1-HR FIRE WALL

2-HR FIRE WALL

Page 24: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

JTO

GENERAL NOTES:

1. LOAD SIDE CONDUCTOR AND CONDUIT SIZES FROM DISCONNECT SWITCHES TO EQUIPMENT

SHALL BE THE SAME AS LINE SIDE CONDUCTORS AND CONDUIT.

2. CAREFULLY COORDINATE ALL ELECTRICAL EQUIPMENT LOCATIONS WITH DUCTWORK, PIPING

AND MECHANICAL EQUIPMENT. MAINTAIN ALL CLEARANCES AND SPACES REQUIRED BY THE

NEC.

3. WHERE MULTIPLE CIRCUITS ARE COMBINED IN A SINGLE CONDUIT, INCREASE CONDUCTOR

AMPACITIES PER THE NEC.

4. ALL EMERGENCY LIGHTING FIXTURES SHALL BE MARKED SO AS TO BE IDENTIFIED BY VISUAL

INSPECTION FOR TESTING PURPOSES. IDENTIFICATION SHALL BE BY ONE 1/2" RED

SELF-STICK DOT ON THE VERTICAL PORTION OF LOUVER OR ON THE TOP OF THE LENS.

5. EXACT LOCATION AND ORIENTATION OF OCCUPANCY SENSORS SHALL BE AS RECOMMENDED

BY MANUFACTURER TO OBTAIN COMPLETE COVERAGE. IF THE CONTRACTOR USES A

SENSOR THAT HAS A COVERAGE PATTERN DIFFERENT FROM THAT WHICH IS SPECIFIED, AND

AS A RESULT ADDITIONAL SENSORS ARE REQUIRED TO COMPLETELY COVER A SPACE, THE

CONTRACTOR SHALL PROVIDE ADDITIONAL SENSORS AS REQUIRED (CONNECTED IN

PARALLEL WITH EACH OTHER) AT NO ADDITIONAL COST TO THE OWNER. ALL OCCUPANCY

SENSOR TIME DELAYS SHALL BE SET TO NO MORE THAN 30 MINUTES.

6. UNLESS INDICATED OTHERWISE, SWITCHES AND OCCUPANCY SENSORS IN A ROOM/SPACE

SHALL CONTROL ALL LIGHTING FIXTURES IN THAT ROOM/SPACE.

7. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ALL PANELBOARD FEEDER

ENTRANCE LOCATIONS (TOP, BOTTOM, SIDE).

8. CAREFULLY COORDINATE LOCATIONS OF ALL LIGHTING FIXTURES, OCCUPANCY SENSORS,

CEILING SPEAKERS, SMOKE AND HEAT DETECTORS, FIRE ALARM NOTIFICATION APPLIANCES

AND OTHER ELECTRICAL CEILING DEVICES WITH HVAC CEILING DEVICES.

9. WHERE RE-USE OF EXISTING CONDUIT, WIRING AND/OR OUTLET BOXES IS INDICATED, ALSO

PROVIDE NEW MATERIALS IF NECESSARY. IF NEW EXPOSED MATERIALS ARE NEEDED, USE

SURFACE RACEWAY (SINGLE-CHANNEL EXCEPT WHERE SPECIFICALLY INDICATED

OTHERWISE), EXCEPT EXPOSED CONDUIT AND BOXES MAY BE USED IN UNFINISHED AREAS

(MECHANICAL/ELECTRICAL/IT ROOMS, STORAGE AND HOUSEKEEPING CLOSETS, ETC.).

10. WHERE OUTLETS ARE SHOWN ABOVE A COUNTER OR SIMILAR SURFACE WITH A SPECIFIC

MOUNTING HEIGHT, COORDINATE MOUNTING HEIGHT WITH BOTH THE SURFACE BELOW AND

WITH ANY WALL MOUNTED ARCHITECTURAL ITEMS ABOVE (TACKBOARDS, ETC.) BEFORE

ROUGH-IN.

11. SEE DRAWINGS FOR RATED WALL, FLOOR AND CEILING CONSTRUCTION, AND PROVIDE

NECESSARY RATED DEVICES AND FIRE SEALANT FOR PENETRATIONS.

12. PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR EXISTING PANELS WHERE CIRCUITS HAVE

BEEN ADDED, DELETED OR CHANGED AS PART OF THIS CONTRACT. ALL NEW BREAKERS IN

EXISTING PANELS SHALL MATCH EXISTING BREAKER AIC RATING.

13. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING BID IN ORDER TO VERIFY ALL

EXISTING CONDITIONS, TO DETERMINE THE FULL EXTENT OF DEMOLITION WORK REQUIRED,

AND TO DETERMINE THE FULL EXTENT OF RELOCATION AND MODIFICATION WORK REQUIRED

FOR ELECTRICAL WORK (DUE TO OTHER DISCIPLINES INTERFERING OR ANY OTHER REASON).

EXISTING SPACE IS TIGHT IN MANY AREAS (PARTICULARLY ABOVE CEILINGS), AND THE

CONTRACTOR SHALL BE FULLY RESPONSIBLE TO COORDINATE ALL ELECTRICAL WORK WITH

BOTH NEW AND EXISTING PIPING, DUCTWORK, CONDUIT, ETC. NO CHANGE ORDERS WILL BE

APPROVED FOR ADDITIONAL WORK DUE TO THE CONTRACTOR NEGLECTING TO VISIT THE

SITE AND GATHERING ALL NECESSARY INFORMATION.

14. WHERE EXISTING RECEPTACLES ARE TO BE REPLACED, CONTRACTOR SHALL TRACE

EXISTING CIRCUIT AND PROVIDE LABEL WITH CIRCUIT NUMBER AND PANELBOARD WHERE

CIRCUIT ORIGINATES IN ACCORDANCE WITH SPECIFICATION SECTION 11.

15. WHERE CIRCUITS ARE INDICATED TO BE REMOVED, REMOVE CONDUCTORS BACK TO PANEL

AND CONDUIT BACK TO PANEL WHERE IT IS ACCESSIBLE.

16. MOUNT ALL RECEPTACLES IN ALL LABS AT THE SAME HEIGHT.

ELECTRICAL SPECIFICATIONS:

1. SCOPE OF WORK: PROVIDE SUPERVISION, LABOR, MATERIAL, EQUIPMENT, MACHINERY, PLANT AND OTHER ITEMS NECESSARY FOR A COMPLETE

AND OPERABLE ELECTRICAL SYSTEM.

2. STANDARDS AND CODES: THE MATERIALS AND EQUIPMENT SHALL BE NEW AND LISTED BY UNDERWRITERS LABORATORIES, INC. THE

INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2012 VIRGINIA UNIFORM STATEWIDE BUILDING CODE (USBC); THE 2012 INTERNATIONAL

BUILDING CODE (IBC) AS ADOPTED AND MODIFIED BY THE 2012 USBC; THE 2011 NFPA-70 (NATIONAL ELECTRICAL CODE, OR NEC); THE 2010 NFPA-72

(NATIONAL FIRE ALARM AND SIGNALING CODE);AND OTHER RELATED CODES AND STANDARDS. THE COMPLETED INSTALLATION SHALL COMPLY

WITH THE ADAAG "AMERICAN WITH DISABILITIES ACT GUIDELINES FOR BUILDINGS AND FACILITIES". WORKMANSHIP SHALL MEET THE "STANDARDS

OF INSTALLATION" AS PUBLISHED BY THE NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA).

3. PERMITS AND FEES: BONDS, LICENSES AND INSPECTION CERTIFICATES WILL BE OBTAINED BY VIRGINIA TECH. PAY INSPECTION FEES AND TAXES.

FILE PLANS AND PREPARE DOCUMENTS REQUIRED TO OBTAIN APPROVALS OF GOVERNMENTAL DEPARTMENTS HAVING JURISDICTION.

4. CONDUIT: PROVIDE ELECTRICAL METALLIC TUBING (EMT), MINIMUM 3/4", FOR EMPTY CONDUIT RUNS AND STUB-UPS, BRANCH CIRCUITS AND PANEL

FEEDERS; ALL CONDUIT STUBS SHALL HAVE BUSHINGS. PROVIDE GALVANIZED SINGLE STRIP FLEXIBLE CONDUIT, MINIMUM 18" LONG, FOR MOTOR

CONNECTIONS. USE PVC JACKETED FLEXIBLE LIQUID-TIGHT CONDUIT TYPE UA FOR MOTOR CONNECTIONS IN WET LOCATIONS. CONDUIT SHALL BE

MINIMUM ¾ INCH. FITTINGS SHALL NOT BE CAST POT METAL.

ALL CONDUITS PASSING THROUGH RATED WALLS OR CEILINGS SHALL BE SLEEVED AND PACKED WITH U.L. LISTED SEALANT TO MAINTAIN RATING.

TYPE AC, MC AND NMC CABLE ARE NOT ALLOWED.

5. JUNCTION, OUTLET AND PULL BOXES : PROVIDE JUNCTION, OUTLET AND PULL BOXES FOR WIRING DEVICES, FIXTURES, CONNECTIONS TO

EQUIPMENT AND AS REQUIRED BY THE NEC. BOXES SHALL BE STEEL UNLESS REQUIRED OTHERWISE BY ENVIRONMENT.

6. HANGERS AND SUPPORTS: PROVIDE ALL HANGERS, SUPPORTS, ANCHORS, SLEEVES AND SEALS AS REQUIRED BY THE NEC.

7. WIRING: PROVIDE COPPER CONDUCTORS, THHN OR THWN, 600 VOLT. WIRING SHALL BE COLOR-CODED TO IDENTIFY PHASES, NEUTRAL AND

GROUND. MATCH EXISTING BUILDING WIRING COLOR-CODING. NUMBER 12 AWG SHALL BE THE SMALLEST SIZE WIRE USED FOR POWER.

CONDUCTORS 8 AWG AND LARGER SHALL BE STRANDED; CONDUCTORS 10 AWG AND SMALLER SHALL BE SOLID. DO NOT INSTALL A SHARED

NEUTRAL ON ANY CIRCUIT.

8. GROUNDING: PROVIDE AN EQUIPMENT GROUNDING SYSTEM INSTALLED TO METALLIC STRUCTURES, ENCLOSURES, RACEWAYS, JUNCTION BOXES,

OUTLET BOXES, PULL BOXES, CABINETS, MACHINE FRAMES, PORTABLE EQUIPMENT AND OTHER CONDUCTIVE ITEMS IN CLOSE PROXIMITY TO

ELECTRICAL CIRCUITS. ALL BRANCH AND FEEDER CIRCUITS SHALL INCLUDE A GREEN GROUNDING CONDUCTOR. PROVIDE GROUND BUS IN ALL

PANELBOARDS.

9. IDENTIFICATION: WHEREVER REASONABLY REQUIRED FOR SAFETY, MAINTENANCE AND/OR OPERATIONAL PURPOSES, PROVIDE SELF-ADHESIVE

PLASTIC SIGNS FOR IDENTIFICATION, INSTRUCTION OR WARNING ON SWITCHES AND OUTLETS, AS WELL AS OTHER CONTROLS, DEVICES AND

ENCLOSURE COVERS. PROVIDE A DANGER SIGN WHEREVER IT IS POSSIBLE FOR PERSONS TO COME INTO CONTACT WITH A VOLTAGE HIGHER

THAN 120 VOLTS, AS WELL AS ON CRITICAL SWITCHES AND CONTROLS WHERE UNTIMELY OPERATION COULD BE A SAFETY HAZARD. PROVIDE AN

ENGRAVED PLASTIC-LAMINATE LABEL ON EACH MAJOR UNIT OF ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO: PANELBOARDS,

CONTROL PANELS, CABINETS, ENCLOSURES, AND DISCONNECT SWITCHES. EQUIPMENT LABELS SHALL INCLUDE WHAT IS REQUIRED IN NEC

408.4(B). ENCLOSURE TYPES SHALL BE MARKED PER NEC 110.28. WIRING COLOR-CODE KEY SHALL BE READILY AVAILABLE OR PERMANENTLY

POSTED PER NEC 200.6(D).

10. CONNECTIONS TO EQUIPMENT: MAKE FINAL ELECTRICAL POWER CONNECTIONS TO MECHANICAL EQUIPMENT. PROVIDE CONDUITS, OUTLET BOXES

AND POWER WIRING FROM THE POWER SOURCE TO THE MOTOR OR EQUIPMENT JUNCTION BOX, INCLUDING WIRING THROUGH STARTERS OR

SAFETY SWITCHES, IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

11. WIRING DEVICES (SHOP DRAWINGS REQUIRED) : WIRING DEVICES SHALL BE BLACK AND SHALL BE HEAVY-DUTY SPECIFICATION GRADE. EXCEPT

WHERE NOTED OTHERWISE ON THE DRAWINGS, RECEPTACLES SHALL BE NEMA 5-20R, GROUNDED. SPECIAL PURPOSE AND GROUND FAULT

RECEPTACLES SHALL BE BY SAME MANUFACTURER AS DUPLEX RECEPTACLES. GFCI TYPE DUPLEX RECEPTACLES SHALL BE RATED 5 MILLIAMPS,

AND SHALL BE READILY ACCESSIBLE WHERE REQUIRED BY NEC 210.8. WIRING DEVICE WALLPLATES SHALL BE STAINLESS STEEL AND SHALL BE BY

SAME MANUFACTURER AS WIRING DEVICES AND HAVE SAME PROFILE.

PROVIDE A LABEL ON ALL SWITCHES, RECEPTACLES AND DISCONNECTS INDICATING PANELBOARD AND CIRCUIT NUMBER THAT FEEDS THE DEVICE.

LABELS SHALL BE SELF-STICK MADE WITH A TAPE GUN WITH MINIMUM 3/16” HIGH LETTERS IN BLACK ON A WHITE BACKGROUND.

WIRING DEVICE MANUFACTURER SHALL BE BRYANT, EATON ARROW/HART, HUBBELL, LEVITON OR PASS & SEYMOUR.

SPECIAL PURPOSE RECEPTACLE TYPES SHALL BE AS FOLLOWS:

a. NEMA 15-20 R

b. NEMA 6-30 R

c. NEMA 6-15 R

d. NEMA 6-20 R

e. NEMA L5-20 R

f. NEMA L15-20

12. SAFETY SWITCHES (SHOP DRAWINGS REQUIRED) : PROVIDE SURFACE-MOUNTED, GENERAL-DUTY OR HEAVY-DUTY AS APPLICABLE,

HORSEPOWER-RATED, NON-FUSIBLE , SAFETY SWITCHES WITH LUGS SUITABLE FOR COPPER OR ALUMINUM CONDUCTORS AND ELECTRO-SILVER

PLATED CURRENT CARRYING PARTS, AND WITH EQUIPMENT GROUND BUS WITH APPROPRIATE LUGS. SWITCHES SHALL HAVE HINGED DOOR WITH

DEFEATABLE INTERLOCK TO PREVENT DOOR FROM BEING OPENED IN "ON" POSITION; OPERATING LEVER ARRANGED FOR PADLOCKING IN THE

"OFF" POSITION; ARC QUENCHERS; CAPACITY AND CHARACTERISTICS AS REQUIRED; NON-TEASABLE QUICK-MAKE AND QUICK-BREAK MECHANISM;

DEAD FRONT; LINE SIDE SHIELD.

MANUFACTURER SHALL BE SQUARE D, GENERAL ELECTRIC, EATON OR SIEMENS.

13. PANELBOARDS (SHOP DRAWINGS REQUIRED) : PANELBOARDS SHALL BE DEAD-FRONT, COPPER BUS, WITH THERMAL MAGNETIC MOLDED CASE

CIRCUIT BREAKERS IN ACCORDANCE WITH SCHEDULES SHOWN ON THE DRAWINGS. BREAKERS FOR APPLIANCE PANELBOARDS SHALL BE BOLT-ON.

SERIES RATING IS NOT ACCEPTABLE. PANELBOARDS SHALL HAVE TYPED, FRAMED CIRCUIT DIRECTORIES. THE CIRCUIT DIRECTORIES SHALL

INDICATE THE LOAD TYPE AND THE OWNER'S ROOM NAMES/NUMBERS (NOT THE CONSTRUCTION DOCUMENT ROOM NAMES/NUMBERS). DOORS

SHALL HAVE LOCKS, BE KEYED ALIKE AND BE PAINTABLE. EMPTY SPACES SHALL BE FULLY BUSSED WITH HARDWARE FOR FUTURE BREAKERS.

14. LIGHTING (SHOP DRAWINGS REQUIRED) : PROVIDE FIXTURES AS INDICATED ON THE DRAWINGS. MANUFACTURERS SHALL BE AS INDICATED ON THE

DRAWINGS. THE FIXTURES INDICATED ON THE FIXTURE SCHEDULE HAVE BEEN STANDARDIZED FOR THIS BUILDING BY THE OWNER. ANY

SUBSTITUTIONS FROM THE SPECIFIED LIGHT FIXTURES WILL REQUIRE A SAMPLE TO BE SUBMITTED TO THE OWNER AND ARCHITECT FOR REVIEW

AND APPROVAL PRIOR TO ORDERING. FIXTURES SHALL BE COMPLETE WITH REQUIRED SOCKETS, WIRING, GLASSWARE, REFLECTORS, HANGERS,

FITTINGS AND MOUNTING TRIM. FIXTURES SHALL BE CLEANED AFTER THEY HAVE BEEN INSTALLED. PROVIDE PROPER TRIM, FRAMES, MOUNTING

DEVICES, CONFIGURATION AND ACCESSORIES REQUIRED TO PROPERLY INSTALL FIXTURES IN THE BUILDING CONSTRUCTION.

CATALOG NUMBERS OF FIXTURES SCHEDULED ARE TO ESTABLISH A TYPE OF FIXTURE, NOT TO DETERMINE A METHOD OF MOUNTING. VERIFY

CEILING CONSTRUCTION BEFORE ORDERING FIXTURES, AND PROVIDE MOUNTING TRIM SUITABLE FOR THE CEILING FINISH IN WHICH FIXTURE IS

INSTALLED. INSTALL RECESSED LAY-IN TYPE LED FIXTURES SO THAT THE LENS HOUSING MAY BE EASILY OPENED AND SO THAT THE FIXTURES MAY

BE REMOVED AND RELOCATED WITHOUT FORCING THE FIXTURES. COORDINATE LIGHTING LAYOUT WITH CEILING LAYOUT AND FINISH BEFORE

CEILING GRID IS INSTALLED.

ALL DRIVERS SHALL COMPLY WITH NEMA 410-2011 FOR INRUSH CURRENT. 0-10V DIMMING DRIVERS SHALL COMPLY WITH IEC 60929. FOR 0-10V

DIMMING CONTROLS, THE PERFORMANCE CURVES FOR THE 0-10V CONTROL AND THE 0-10V DRIVERS SHALL NOT BOTH BE LOGARITHMIC. ALL

DRIVERS SHALL HAVE TOTAL HARMONIC DISTORTION OF LESS THAN 10% AT FULL OUTPUT.

15. LIGHTING CONTROL DEVICES (SHOP DRAWINGS REQUIRED): PROVIDE ALL LIGHTING CONTROL DEVICES AS INDICATED ON THE DRAWINGS AND AS

REQUIRED TO ACHIEVE A COMPLETE AND OPERABLE SYSTEM. REFER TO SHEET E0.1 FOR THE SCHEDULE OF LIGHTING CONTROL DEVICES. THE

LIGHTING CONTROL DEVICES SHALL BE BLACK WITH STAINLESS STEEL WALLPLATES. PROVIDE ALL 0-10V WIRING NECESSARY (600V RATED WHERE

SHARING RACEWAY WITH LINE VOLTAGE) FOR DIMMING CONTROL. PROVIDE ALL CATEGORY 5E CABLING NECESSARY FOR CONNECTION OF

LOW-VOLTAGE CONTROLS. SUBMIT SHOP DRAWINGS FOR ALL LIGHTING CONTROL DEVICES AND WIRING.

16. FIRE ALARM SYSTEM (SHOP DRAWINGS REQUIRED) : PROVIDE FIRE ALARM DEVICES AS AN EXTENSION OF THE EXISTING FIRE ALARM SYSTEM. NEW

DEVICES SHALL BE ADDRESSABLE. ADDITIONAL MODULES SHALL BE PROVIDED AS NECESSARY TO ACHIEVE A FULLY ADDRESSABLE AND COMPLETE

FIRE ALARM SYSTEM. ALL DEVICES SHALL BE BY THE SAME MANUFACTURER AND SHALL MATCH THE EXISTING FIRE ALARM SYSTEM DEVICES.

PROVIDE FIRE ALARM INDICATING APPLIANCES WITH CANDELA RATING MATCHING THE NUMBERS SHOWN ON THE DRAWINGS. PROVIDE A FULL

CONDUIT (EMT) SYSTEM DEDICATED FOR FIRE ALARM CABLING. ALL NEW FIRE ALARM WIRING SHALL MATCH EXISTING. PROVIDE ALL COMPONENTS,

RELAYS, POWER MODULES, EXTENDER PANELS, ETC. NECESSARY FOR A COMPLETE AND OPERABLE EXTENSION OF THE EXISTING FIRE ALARM

SYSTEM. REPROGRAM THE FIRE ALARM REMOTE ANNUNCIATOR PANEL AS REQUIRED AFTER INSTALLATION OF NEW DEVICES HAS BEEN

COMPLETED. PROVIDE ALL TESTING REQUIRED BY THE AUTHORITY HAVING JURISDICTION.

17. SURFACE METAL RACEWAYS (SHOP DRAWINGS REQUIRED): PROVIDE SURFACE METAL RACEWAY, TYPE 'SR', WHERE INDICATED ON THE DRAWINGS.

RACEWAY SHALL BE TWO-PIECE TYPE WITH SINGLE COMPARTMENT, LENGTH AS NECESSARY; PROVIDE NOMINAL 2-3/4" X 1-15/32" WITH FLUSH,

SNAP-ON COVER. MAKE CHANGES IN DIRECTION OF RACEWAY RUN WITH PROPER FITTINGS SUPPLIED BY THE RACEWAY MANUFACTURER. NO FIELD

BENDS OF RACEWAY SECTIONS WILL BE PERMITTED. PROPERLY ANCHOR RACEWAYS FOR THEIR ENTIRE LENGTH BY STRUCTURAL MATERIALS.

RACEWAYS SHALL NOT SPAN ANY SPACE UNSUPPORTED. USE BOXES AS SUPPLIED BY THE RACEWAY MANUFACTURER WHEREVER JUNCTION, PULL

OR DEVICE BOXES ARE REQUIRED. STANDARD ELECTRICAL 'HANDY' BOXES, ETC. SHALL NOT BE PERMITTED FOR USE WITH SURFACE RACEWAY

INSTALLATIONS. COORDINATE FINAL RACEWAY LOCATIONS, FEEDS, HEIGHTS, ETC. WITH THE ARCHITECT PRIOR TO INSTALLATION. ALL RACEWAY

FEEDS SHALL OCCUR AT THE INSIDE CORNERS OF EXISTING AND NEW WALLS (TYPICAL).

208Y/120V

SURFACE

YES

-80° C FREEZER IN LAB 5034

SPARE

SPARE

REFRIGERATOR IN LAB 5029

INCUBATORS LAB 5029

-80° C FREEZER IN LAB 5034

LOAD SERVED

INTERRUPT RATING:

''

''

GLASS WASHER IN LAB 5026

''

BECKMAN OPTIMA IN LAB 5034

''

3.9KW DRYING OVEN IN LAB 5026

SPACE ONLY

FRENCH PRESS

PURIFIER AND DISMEMBRANTOR

SPARE

INCUBATOR

REFRIGERATOR IN LAB 5029

RECEPTACLES LAB 5034

-80° C FREEZER IN LAB 5034

MOUNTING:

VOLTAGE:

SOLID NEUTRAL:

-

12.5

2.222.22

16.36

10,000 AIC

-

-

-

20/3

30/2

14.84 16.1

2.22

2.222.22

1

2.22

12.5

-

-

-

20/3

-

20/2

''

''

''

''

2 KW DRYING OVEN IN LAB 5926

GLASS WASHER IN LAB 5026

-80° C FREEZER IN LAB 5034

SPARE

AUTOCLAVE

PURIFIER AND PRESS IN LAB 5026

L3

1.441.44

.361.2

--

11.98

-1

.84

20/1

-

25/2

20/1

20/1

20/1

20/1

20/1

1.98

-1.2

--

- -

- -

1

20/1

20/1

20/1

20/1

20/1

20/1

20/1

BKR

.36

11.2

.78

1.81.64

1.44 1.44

L1

1.44 1.44

L2

-

-

20/2

-

20/1

20/1

20/1

20/1

SPACE ONLY

CENTRIFUGE IN LAB 5029

SPACE ONLY

SPACE ONLY

AUTOCLAVE

SPARE

SPARE

20/1

20/1

20/1

20/1

20/1

BKR

20/1

20/1

OVEN IN IN LAB 5026

RECEPTACLES IN LAB 5026

-80° C FREEZER IN LAB 5034

-80° C FREEZER IN LAB 5034

LOAD SERVED

BUS RATING:

MAIN:

SYSTEM: 3PH, 4W

NEW PANEL PC57

225A

GROUND BUS:

INTEGRAL SPD:

YES

LOADS ( )

LIGHTING

REC TO 10 KVA

REC REMAINING

LARGEST MOTOR

SPACE HEATING

KITCHEN EQUIPMENT

CONNECTED

0

1.72

0

0

0

0

0

10.64

DEMAND

1.25

1.0

0.5

1.0

0.25

0.0

1.0

1.25

0

1.72

0

0

0

0

0

13.3

FACTOR

TOTAL CONNECTED LOAD

MIN. FEEDER / PANEL CAPACITY

34.94 1.0 34.94

CONTINUOUS

NON-CONTINUOUS

DEMAND

138.850

47.3 131.4

AMPSKVA

KVA AMPS

41

9

25

33

39

37

35

27

29

31

17

23

19

21

13

15

11

1

5

7

3

CKT

42

10

26

34

38

40

36

30

32

28

18

22

24

20

14

16

12

2

6

8

4

CKT

KVA

DEMAND 0 1.0 0

OVERALL DEMAND FACTOR 1.06

225A MLO NO

-#10

3/4"

3/4"

-

3/4"

-

-

3/4"

-

-

#10

#10

#8

#8

#8

#8

-

#10

-

-

3/4"

-

3/4"

3/4"

3/4"

#10

-

-

-

#12

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

COND

#12

#12

#12

#12

PHASE NEUT GND

-

-

-

-

-

-

-

-

#10

#10

-

-

-

#12

#12

#12

#12

#12

#12

#12

#12 #12

#12

#12

#12

#12

#12

#12

#12

-

-

-

#12

#12

-

#10

-

#10

-

#12

-

-

#12

#12

#12

#8

#8

#12

#10

#10

-

-

-

-

-

-

#12

-

-

-

-

-

-

NEUT

-#10

-

3/4"

-

3/4"

#10

#10

#10

#10

-

3/4"

-

-

#12

#12

-

-

-

-

-

-

-

-

-

-

3/4"

3/4"

3/4"

#10

#10

#12

3/4"

3/4"

3/4"

3/4"

#8

#8

#12

#12

PHASE COND

3/4"#12

-

-

#12

-

#12

-

#12

-

-

-

-

-

-

#12

#12

#12

#12

#12

#12

#12

GND

#12

LOADS (KVA)

WATER HEATING

AIR CONDITIONING 0

0

CONNECTED

0

0

DEMANDFACTOR

1.0

1.0

DEMAND

NON-SEASONAL MOTORS

L1 L2 L3

PHASE LOAD TOTALS

ACT CEILING GRIDACT CEILING GRIDGLEASON CP-2

CABLE STOP

KEWAUNEE 2'x2' CEILING SERVICE PANEL

(3) #12, 3/4" FLEXIBLE METAL

CONDUIT TO EACH CORD REEL

4"X4"X2-11/16" JUNCTION BOX

WITH BLANK COVERPLATE

120V BRANCH CIRCUITS IN 3/4" CONDUITUNISTRUT ON STRUCTURE ABOVE

(4) 3/8" DIAMETER STAINLESS

STEEL DOUBLE ANCHOR BOLTS

AND LOCK WASHERS

EXISTING CONCRETE DOUBLE TEES

CORD REEL BASIS OF DESIGN: GLEASON REEL

CABLE MASTER MODEL CM14-C03-A1105

COMPLETE WITH 20' OF 12/3 SOOW CABLE.

12/3 S00W CABLE

STRAIN RELIEF

GLEASON RG14 CABLE GUIDE. ATTACH TO

CEILING SERVICE PANEL WITH 2 BOLTS

CONDUIT TO OTHER

CORD REEL

STANDARD 1 1/4" x 2"

DATA/COMM CUTOUT

NEMA 5-20 DUPLEX

RECEPTACLES PVC BOXES

PROVIDE TWO (2) QUAD RECEPTACLES IN BACK

TO BACK BOXES PER CORD REEL IN LABS 5010

AND 5029. COORDINATE THE COLOR OF BOXES,

RECEPTACLES, AND COVER PLATES WITH THE

ARCHITECT PRIOR TO ORDERING.

SYSTEM NO. W-L-1054

SECTION A-A

A

A

1A

3

2 1B

C

CLA

SS I F IEDClassified by

Underwriters Laboratories, Inc.to UL 1479 and CAN/ULC-S115

US

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F RATINGS —1 AND 2 HR (SEE ITEMS 1 AND 3) F RATINGS — 1 AND 2 HR (SEE ITEMS 1 AND 3)

T RATING — 0 HR FT RATING — 0 HR

L RATING AT AMBIENT — LESS THAN 1 CFM/SQ FT FH RATINGS —1 AND 2 HR (SEE ITEMS 1 AND 3)

L RATING AT 400 F — LESS THAN 1 CFM/SQ FT FTH RATING — 0 HR

FTH RATING — 0 HR

L RATING AT AMBIENT — LESS THAN 1 CFM/SQ FT

L RATING AT 400 F — LESS THAN 1 CFM/SQ FT

1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE

MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE

RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2

BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 2-1/2 IN. (64 MM) WIDE AND SPACED MAX 24 IN.

(610 MM) OC. WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH OF STUD CAVITY, THE OPENING

SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD INSTALLED BETWEEN THE VERTICAL STUDS AND

SCREW-ATTACHED TO THE STEEL STUDS AT EACH END. THE FRAMED OPENING IN THE WALL SHALL BE 4 TO 6 IN. (102 TO 152 MM)

WIDER AND 4 TO 6 IN. (102 TO 152 MM) HIGHER THAN THE DIAM OF THE PENETRATING ITEM SUCH THAT, WHEN THE PENETRATING

ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. (51 TO 76 MM) CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM AND

THE FRAMING ON ALL FOUR SIDES.

B. GYPSUM BOARD* - 5/8 IN. (16 MM) THICK, 4 FT (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE,

THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR

U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 32-1/4 IN. (819 MM) FOR STEEL STUD

WALLS. MAX DIAM OF OPENING IS 14-1/2 IN. (368 MM) FOR WOOD STUD WALLS. THE F AND FH RATINGS OF THE FIRESTOP SYSTEM

ARE EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.

2. THROUGH-PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY

WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 0 IN. TO MAX 2-1/4 IN. (57 MM). PIPE MAY BE INSTALLED WITH

CONTINUOUS POINT CONTACT. PIPE, CONDUIT OR TUBING MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEGREES FROM

PERPENDICULAR. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES

AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 6 IN. (152 MM) . DIAM STEEL CONDUIT.

D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH

WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PIPE AND WALL, A MIN 1/2 IN. (13 MM)

DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE WALL INTERFACE ON BOTH SURFACES OF WALL.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE SEALANT OR FS-ONE MAX INTUMESCENT SEALANT

* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL OR CUL

CERTIFICATION (SUCH AS CANADA), RESPECTIVELY.

1 & 2-HOUR GYPSUM/STUD PENETRATION FIRESTOPPING DETAILNO SCALE

NOTE:

VERIFY FINAL LOCATIONS AND CLEARANCE WITH ARCHITECT.

CORD REEL INSTALLATION DETAILNO SCALE

MOUNT CORD REEL IN

BAY BETWEEN RIBS

Page 25: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR NEW WORK PLAN - LIGHTINGSCALE: 1/8" = 1'-0"

LAB

5029

LAB

5029B

CORRIDOR

CR-5B

LAB

5005B

LAB

5005

ICE

E03

LAB

5014

CORRIDOR

CR-5A

LAB

5034

LAB

5026

LAB

5016

OFFICE

5016B

ER ER

ER

ER

ER

ER

ER

ER ER

ER ER ER ER ERER

ER ER ER ER ERER

ER ER ER ER ERER

TYPA1

TYPA3

TYPA3

TYPA1

1

1

1

1

1 1

1

1

1

1 1

1

LD

LD

LD

LD

1

11

1

2

2 2

2

3

3

ERERER ER ER ER

ERER

ER ERER

4

4

SR

4

1

2

1

1LD

TYPA2

4

44

1 1

4

ER ER

ER ER

ER ER

ER ER

ER

ER

ER ER ER

ER

OFFICE

5014A

2

2

2

2

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

JTO

PLAN NOTES:

1. THE NEW LIGHT FIXTURES SHALL BE CONNECTED TO THE EXISTING RETAINED LIGHTING CIRCUIT IN THIS SPACE. EXTEND THE

EXISTING CIRCUIT AS REQUIRED AND CONNECT TO THE NEW FIXTURES VIA THE LOAD CONTROLLER IN THE SPACE. NEW CONDUIT

AND WIRING SHALL MATCH EXISTING.

2. CONNECT ALL OF THE LOW-VOLTAGE SWITCHES, OCCUPANCY SENSORS AND LOAD CONTROLLERS TOGETHER WITH CATEGORY

5E CABLE SO THAT ALL OF THE LIGHT FIXTURES IN THE SPACE ARE CONTROLLED BY EACH LOW-VOLTAGE DEVICE. ALL

OCCUPANCY SENSORS SHALL BE SET TO 'VACANCY' MODE.

3. NO NEW LIGHTING WORK IS TO BE COMPLETED IN THIS SPACE UNDER THIS PROJECT.

4. CEILING SERVICE PANEL; REFER TO SHEET E1.2 FOR DETAILS.

GENERAL NOTE:

1. NEW SWITCHES SHALL BE INSTALLED IN THE EXISTING OUTLET BOXES UNLESS INDICATED OTHERWISE ON THE FLOOR PLAN.

PROVIDE BLANK PLATES MATCHING THE NEW DEVICE PLATES FOR ALL UNUSED OUTLET BOXES.

2. THE ORIENTATION OF THE 2'X2' LIGHT FIXTURES SHALL BE COORDINATED WITH THE ARCHITECT ON SITE.

3. ALL EXISTING TO REMAIN LIGHT FIXTURES SHALL BE COMPLETELY CLEANED AND RELAMPED. PROVIDE NEW LAMPS TO MATCH

EXISTING TYPE, WATTAGE, COLOR TEMPERATURE AND LUMEN OUTPUT. PROVIDE NEW BALLASTS AS REQUIRED FOR PROPER

FIXTURE OPERATION.

0 16 24 328

1/8" = 1' - 0"

Page 26: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

LAB

5034

LAB

5026

PC57-4

PC57-2

PC57-5

PC57-3

PC57-1

2

1

3

1

7

PC57-6

PC57-33

PC57-7

SR

14

SR

16

37

38PC57-12

PC57-12

f

f

36"

30"

SR

SR

b

FC-6

FC-6

TO FC-6 IN 5016

21

21

21

21

TO FC-5 IN 5029

EX. PANEL-PC56

SEE SHEET E 1.3

25

M.H.=36"

M.H.=36"

M.H.=36"

SR

SR

NEW PANEL-PC57

CONDUIT FROM SR

THROUGH WALL TO PANEL

6 ICE

E03

29

fSR c

SR

34

SR

SR

10

23

23

10

23

PC57-14,16,23,

25,29,34,37,389

25 25

SR

PC57-23

3

PC57-23

PC57-25

26

26

CORRIDOR

CR-5A

LAB

5016

OFFICE

5016B

SR

PC56-21

SR

PC56-21

SR

PC56-21

SR

SR

1718

16

PC51-13 PC51-13

PC51-16

SR

SR

PC53-27PC53-27SR

PC53-27

SR

PC53-29

SR

PC53-29

PC53-18

SR

PC56-8

SR

PC56-2

SR

PC56-4PC56-6

PC56-8

SR

PC56-11

SR

PC56-133/4" CONDUIT

DOWN TO SR

1" CONDUIT

DOWN TO SR

SRPC56-29

c SR

PC56-14

SRPC56-12

SRPC56-12

PC51-11

PC51-13,16

PC51-11,13

18 18

18

4-#12 AND 2-#12

GROUNDS TO

PANEL-PC56

8-#10 AND 4-#12

GROUNDS TO

PANEL-PC56

PC56-8,21

SR

SR

2 2

2

6-#12 AND 3-#12

GROUNDS TO

PANEL-PC56

SR DOWN TO SR

21

TO FC-8 IN 5026

FC-5

EXISTING HOOD 22

PC56-12,14,29

SRSR

10

10

SR

SR

SR

SR

SR

SR

15

14

2

PC56-12

23

SR DOWN FROM

CEILING SPACE

SR DOWN FROM

CEILING SPACE

25

26

27

26

2

LAB

5029

LAB

5029B

SR SR SR

SR

2

SR

2

SR

2

SR

4

SR

4

SR

4

SR

4

SR SR SR SRC

SR

SR

13

SR

SR

9

SR

SR

SR

SR

SR

SR

SR

SR

SR

PC56-20

PC56-18

PC56-16

PC56-16

PC56-16

PC56-19

PC56-22

PC56-17

PC56-15

PC56-22

8 8 10 10

6 66

PC57-30PC56-16,18,20

PC56-15,17,19,22

PC57-9,11,13PC53-8,10

PC53-6PC53-2,4

2

2

2

20

19

12

PC53-3,5

20

19

12

PC53-7,9

CONCRETE TEES AT

STRUCTURE ABOVE

21TO FC-7 IN 5034

FC-5

PC56-24

HP-2 IN

MECHANICAL

ROOM ABOVE

N/2/60

30

PC56-10

19

SR

SR

SR

SR

SR

23

14

2

23

SR

15

SR

11

4

PC57-30

15

SR SR

23

24

SR

15

25

23

23

FC-6 25

26

LAB

5014

PC56-9

PC56-7

12

20

20

12

CONCRETE TEES AT

STRUCTURE ABOVE

OFFICE

5014A

27

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

CAD

PARTIAL NEW WORK FLOOR PLAN - POWERSCALE: 1/4" = 1'-0"

PLAN NOTES:

1. ALL CIRCUITS IN THIS ROOM SHALL BE FED FROM PANEL-PC57 UNO.

2. THE SURFACE RACEWAY SHALL BE MOUNTED FLUSH WITH THE TOP OF THE BACKSPLASH.

COORDINATE FINAL HEIGHT WITH ARCHITECT.

3. MOUNT THE RECEPTACLES FOR THE WASHER BELOW THE COUNTER AT 18" ABOVE THE FLOOR

TO CENTER USING SURFACE MOUNTED BOXES AND 3/4" CONDUIT. ROUTE THE FEEDER

CONDUIT TO BEYOND THE EDGE OF THE CASEWORK, TURN UP AND CONNECT TO THE

SURFACE RACEWAY IN NOTE 2. PROVIDE A NEMA 15-20P PLUG AND INSTALL ON WASHER

CORD.

4. ELECTRICAL HOOK-UPS FOR HOOD SHALL BE RELOCATED FROM THE CORRIDOR WALL

LOCATION TO THE NEW LOCATION IN LAB 5029.

5. NOT USED.

6. ROUTE ONE (1) 1-1/2" CONDUIT FROM THE SURFACE RACEWAY TO PANEL-PC57 WITH 14 #8

PHASE CONDUCTORS AND 6 #12 GROUND CONDUCTORS.

7. 2" WIDE YELLOW PAINTED LINE ON FLOOR. STENCIL "NO STORAGE ELECTRICAL WORKING

SPACE" IN 2" HIGH YELLOW LETTERS CENTERED IN OUTLINED AREA.

8. 6 #8, 2 #12 AND 1 #10 GROUNDS IN 1" CONDUIT FROM THE SURFACE RACEWAY TO PANEL-PC57.

9. 2 #8, 16 #10 AND 8 #12 GROUNDS IN 1" CONDUIT.

10. 2 #12 AND 1 #12 GROUND IN 3/4" CONDUIT.

11. NOT USED.

12. 2'x2' CEILING SERVICE PANEL. SEE SHEET E1.1 FOR EXACT LOCATION. COORDINATE LOCATION

WITH CEILING GRID/ DUCTWORK ABOVE CEILING AND CONCRETE TEES AT STRUCTURE.

13. NOT USED.

14. 4 #12 AND 2 #12 GROUNDS IN 3/4" CONDUIT.

15. 6 #12 AND 3 #12 GROUNDS IN 3/4" CONDUIT.

16. EXISTING CONDUIT FROM PANEL-PC51 IN OR UNDER FLOOR. PULL NEW CIRCUITS IN EXISTING

CONDUIT.

17. EXISTING JUNCTION BOXES ON CONDUIT FROM PANEL-PC53 UNDER LAB TABLE. PROVIDE NEW

FLEXIBLE CONDUIT FROM JUNCTION BOX TO RECEPTACLES IN PEDESTAL FITTING.

18. RECEPTACLES INSTALLED IN WIREMOLD 525G OR EQUAL PEDESTAL FITTING WITH DUPLEX

OPENING EACH SIDE. MOUNTED ON TOP OF LAB TABLE.

19. FEEDER CONDUIT TO BE INSTALLED IN EXISTING CASEWORK BELOW BOTTOM OF LAB TOP.

TYPICAL FOR ALL CASEWORK TO REMAIN. CIRCUITS SHALL BE HARDWIRED TO CORD REEL

JUNCTION BOX.

20. PROVIDE CORD REEL MOUNTED ABOVE CEILING. LOCATE SO CORD EXITS THROUGH

INDICATED HOLE IN CEILING SERVICE PANEL. SEE CORD REEL DETAIL SHEET E0.2.

21. 2 #12 PHASE CONDUCTORS AND 1 #12 GROUND IN ONE (1) 3/4" EMT CONDUIT.

22. ALL EXISTING ELECTRICAL CONNECTIONS TO HOOD SHALL REMAIN.

23. SR DOWN FROM CEILING SPACE TO HORIZONTAL SR. CONVERT TO CONDUIT ABOVE CEILING.

24. 8 #12 PHASE CONDUCTORS AND 4 #12 GROUNDS IN ONE (1) 3/4" CONDUIT.

25. PROVIDE COOPER SCY BOX COVER UNIT WITH (2) 3 AMP TYPE W FUSES. MOUNT ABOVE

CEILING ADJACENT TO UNIT.

26. MOUNT SR AT SAME HEIGHT AS SR MOUNTED AT CASEWORK WITH BACKSPLASH.

COORDINATE FINAL HEIGHT WITH ARCHITECT.

27. REPLACE ALL EXISTING RECEPTACLES AND COVERPLATES IN THIS ROOM.

PARTIAL NEW WORK FLOOR PLAN - POWERSCALE: 1/4" = 1'-0"

PARTIAL NEW WORK FLOOR PLAN - POWERSCALE: 1/4" = 1'-0"

PARTIAL NEW WORK FLOOR PLAN - POWERSCALE: 1/4" = 1'-0"

0 8 12 164

1/4" = 1' - 0"

Page 27: TY I S R E V I N DERRING HALL S ASBESTOS AND LEAD …lionberger.com/files/2016/11/IFB_0047615-Bid-Drawings.pdfa1.2 new work - plans, partial plans, notes a1.3 new work - partial plans

PARTIAL FIFTH FLOOR PANELBOARD PLANSCALE: 1/8" = 1'-0"

LAB

5029

LAB

5029B

CORRIDOR

CR-5B

LAB

5005BLAB

5005

LAB

5010

LAB

5014

CORRIDOR

CR-5A

LAB

5034

LAB

5026

LAB

5016

OFFICE

5016B

EXISTING

PANEL-PC55

EXISTING

PANEL-PC54

EXISTING

PANEL-PC52EXISTING

PANEL-PC51

EXISTING PANEL-ELECCNS CABINET

EXISTING

PANEL-LC53EXISTING

PANEL-PC51

5026

ELEC.

E2

NEW PANEL-PC57

EXISTING

PANEL-PC56

EXISTING

PANEL-DC51

ELEC.

E2A

4-#1/0 AND 1-#6 GROUND

IN 2" CONDUIT

EXISTING

PANEL-DB51

ELEC.

E13A

PROVIDE A 150 AMP

3-POLE BREAKER IN

EXISTING PANEL-DB51

TO FEED PANEL-PC57

2-HOUR FIREWALL

(TYPICAL)

1-HOUR

FIREWALL

2-HOUR FIREWALL, TYP.

2

1

KEWAUNEE OR APPROVED EQUAL 2x2

PANEL. #SC10M022 CEILING SERVICE

PANEL. PROVIDE QUANTITY OF

KNOCKOUTS SHOWN ON DRAWINGS.

COORDINATE LOCATIONS WITH USER

AND FURNITURE BEFORE ORDERING.

3" TYP

3" TYP

STANDARD 1 1/4" x 2"

DATA PUNCH OUT

QUICK CONNECT 3/8" COLOR

CODED NATURAL GAS SERVICE

OUTLETS

CEILING SERVICE PANEL DETAILNO SCALE

SUITE 301 620 N. MAIN STREETBLACKSBURG, VA . 24060P. 540.953.ARCH (2724)F. 540.953.2725

DATE

SCALE

DRAWN

JOB

SHEET

AS NOTED

WORK ORDER

BLA

CK

SB

UR

G .

V

IRG

INIA

SEPTEMBER . 30 . 2016

G843-16-219956

1618

DE

RR

ING

HA

LL

FIF

TH

FL

OO

R L

AB

OR

AT

OR

IES

RE

NO

VA

TIO

NS

TO

REVISIONS DATE

CAD

208Y/120V

SURFACE

YES

EXISTING CIRCUIT (NOTE 3)

RECEPTACLES IN LAB 5016 (NOTE 2)

AIR LOCK IN LAB 5029B (NOTE 1)

SHAKER/INCUBATOR (NOTE 1)

CORD REEL LAB 5010 (NOTE 1)

EXISTING CIRCUIT (NOTE 3)

LOAD SERVED

INTERRUPT RATING:

''

''

HIGH SPEED CENTRIFUGE5016 (NOTE 2)

SPARE (NEW BREAKER)

SPARE (NEW BREAKER)

''

BECKMAN LAB 5016

''

FC-5, FC-6, FC-7 AND FC-8 (NOTE 2)

RECEPTACLES IN LAB 5016 (NOTE 2)

AIR LOCK IN LAB 5029B (NOTE 2)

COLD CABINET IN LAB 5029B (NOTE 1)

SHAKER/INCUBATOR (NOTE 1)

CORD REEL LAB 5010 (NOTE 1)

EXISTING CIRCUIT (NOTE 3)

MOUNTING:

VOLTAGE:

SOLID NEUTRAL:

-

--

-1.66

12.72

10,000 AIC

-

-

20/1

30/3

20/1

13.78 11.26

-

-1.66

-

1.66

--

20/1

20/1

20/1

20/1

-

20/1

SPARE (NEW BREAKER)

SPARE (NEW BREAKER)

SPACE

SPARE (NEW BREAKER)

SPARE (NEW BREAKER)

SPARE (NEW BREAKER)

-20/30 °C FREEZER LAB 5016 (NOTE 1)

FREEZER IN LAB 5029B (NOTE 1)

HPLC SYSTEM (NOTE 1)

CORD REEL LAB 5029 (NOTE 1)

L3

1.44-

.36.84

1.441.8

.361

3.46.36

1.92

20/1

-

20/2

20/2

20/1

20/1

20/1

20/1

1

3.46.14

3.46.14

1.8 1.44

.54 .36

.54

20/1

20/1

20/1

20/1

20/1

20/1

20/1

BKR

.72

1.2.8

.36

.72.72

- 1.2

L1

- 1.2

L2

60/3

-

20/1

-

20/1

20/1

20/1

20/1

HP-2 (NOTE 2)

THERMO REFRIGERATOR LAB 5016 (NOTE 2)

''

''

SURF. RACEWAY IN LAB 5029B (NOTE 1)

FREEZER IN LAB 5029B (NOTE 2 )

RECEPTACLES LAB 5029B (NOTE 2)

20/1

20/1

20/1

20/1

20/1

BKR

20/1

20/1

THERMO REFRIGERATOR LAB 5016 (NOTE 1)

RECEPTACLES LAB 5016 (NOTE 1)

REFRIGERATOR LAB 5016 (NOTE 1)

REFRIGERATOR LAB 5016 (NOTE 1)

LOAD SERVED

BUS RATING:

MAIN:

SYSTEM: 3PH, 4W

EXISTING PANEL PC56

225A

GROUND BUS:

INTEGRAL SPD:

YES

LOADS ( )

LIGHTING

REC TO 10 KVA

REC REMAINING

LARGEST MOTOR

SPACE HEATING

KITCHEN EQUIPMENT

CONNECTED

0

4.32

0

0

0

0

0

0

DEMAND

1.25

1.0

0.5

1.0

0.25

0.0

1.0

1.25

0

4.32

0

0

0

0

0

0

FACTOR

TOTAL CONNECTED LOAD

MIN. FEEDER / PANEL CAPACITY

22.78 1.0 22.78

CONTINUOUS

NON-CONTINUOUS

DEMAND

104.137.5

37.5 104.1

AMPSKVA

KVA AMPS

41

9

25

33

39

37

35

27

29

31

17

23

19

21

13

15

11

1

5

7

3

CKT

42

10

26

34

38

40

36

30

32

28

18

22

24

20

14

16

12

2

6

8

4

CKT

KVA

DEMAND 0 1.0 0

OVERALL DEMAND FACTOR 1.00

225A MLO NO

-#10

3/4"

3/4"

-

3/4"

-

-

3/4"

-

-

#10

#10

-

-

#12

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

#12

#12

#12

#12

#12

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

COND

#12

#12

#12

#12

PHASE NEUT GND

-

-

-

-

-

-

-

-

-

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12 #12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

-

#12

-

-

-

#10

-

-

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

-

-

-

#12

-

-

-

-

-

-

NEUT

--

-

-

-

-

-

-

-

-

-

3/4"

-

-

-

#12

#6

#6

1"

3/4"

3/4"

3/4"

#6

#12

#12

#12

3/4"

3/4"

3/4"

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

#12

#12

#12

#12

PHASE COND

3/4"#12

-

-

-

-

-

-

#12

-

-

#10

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

GND

#12

LOADS (KVA)

WATER HEATING

AIR CONDITIONING 10.38

0

CONNECTED

0

10.38

DEMANDFACTOR

1.0

1.0

DEMAND

NON-SEASONAL MOTORS

L1 L2 L3

PHASE LOAD TOTALS1. EXISTING BREAKER TO REMAIN. NEW CONDUIT AND WIRE PER ELECTRICAL PLANS.

2. BREAKER, CONDUIT AND WIRE ARE NEW.

3. EXISTING BREAKER CONDUIT AND WIRE TO REMAIN.

208Y/120V

SURFACE

YES

CORD REEL LAB 5029 ( NOTE 1)

''

UNKNOWN EXIST.

''

CORD REEL LAB 5029 ( NOTE 1)

RECEPTACLES B530 (EXIST)

LOAD SERVED

INTERRUPT RATING:

UNKNOWN EXIST.

''

UNKNOWN EXIST.

FREEZER IN HALL EXIST.

''

RECEPTACLE 5017 EXIST.

RECEPTACLES IN LAB 5016 (NOTE3)

RECEPTACLES IN LAB 5016 (NOTE3)

UNKNOWN EXIST.

UNKNOWN EXIST.

RECEPTACLE 5017B EXIST.

PLUGMOLD 5029B-5017 EXIST.

EXISTING CIRCUIRT (EXIST)

CORD REEL LAB 5029 ( NOTE 1)

CORD REEL LAB 5029 ( NOTE 1)

MOUNTING:

VOLTAGE:

SOLID NEUTRAL:

20/2

--

--

3.78

10,000 AIC

20/2

-

20/1

20/1

-

1.98 4.86

-

--

-

-

--

20/2

-

20/2

-

20/2

-

UNKNOWN EXIST

''

FREEZER EXIST.

UNKNOWN EXIST.

''

''

SURFACE RACEWAY LAB 5029 (NOTE 1)

FREEZER LAB 5016

PLUGMOLD 5022A EXIST.

SURFACE RACEWAY LAB 5029 (NOTE 1)

L3

.541.08

--

1.44-

-.72

--

-

20/1

20/1

20/1

20/1

20/2

-

20/1

20/1

-

--

-.9

- -

- -

-

-

20/2

20/1

20/1

20/1

20/1

20/1

BKR

1.08

--

.36

.361.08

- .54

L1

1.08 .72

L2

20/1

20/2

-

20/1

20/1

20/1

20/1

20/1

RECEPTACLES 5026B-5034 EXIST.

''

SPARE (NOTE 2)

UNKNOWN EXIST.

SPARE (NOTE 2)

RECEPTACLES 5017B EXIST.

RECEPTACLES 5026-5026B, 5034 EXIST.

20/1

20/1

20/1

20/1

20/1

BKR

20/1

20/1

SURFACE RACEWAY LAB 5029 ( NOTE 1)

PLUGMOLD 5022A EXIST.

SURFACE RACEWAY LAB 5029 (NOTE 1)

SURFACE RACEWAY LAB 5029 (NOTE 1)

LOAD SERVED

BUS RATING:

MAIN:

SYSTEM: 3PH, 4W

EXISTING PANEL PC53

225A

GROUND BUS:

INTEGRAL SPD:

YES

LOADS ( )

LIGHTING

REC TO 10 KVA

REC REMAINING

LARGEST MOTOR

SPACE HEATING

KITCHEN EQUIPMENT

CONNECTED0

9.18

0

0

0

0

0

0

DEMAND

1.25

1.0

0.5

1.0

0.25

0.0

1.0

1.25

0

9.18

0

0

0

0

0

0

FACTOR

TOTAL CONNECTED LOAD

MIN. FEEDER / PANEL CAPACITY

1.44 1.0 1.44

CONTINUOUS

NON-CONTINUOUS

DEMAND

29.510.6

10.6 29.5

AMPSKVA

KVA AMPS

41

9

25

33

39

37

35

27

29

31

17

23

19

21

13

15

11

1

5

7

3

CKT

42

10

26

34

38

40

36

30

32

28

18

22

24

20

14

16

12

2

6

8

4

CKT

KVA

DEMAND 0 1.0 0

OVERALL DEMAND FACTOR 1.00

225A MCB NO

-#12

3/4"

3/4"

-

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

#12

#12

#12

#12

#12

#12

#12

#12

3/4"

-

3/4"

3/4"

-

3/4"

3/4"

#12

#12

#12

#12

#12

#12

#12

#12

3/4"

3/4"

3/4"

3/4"

COND

#12

#12

#12

#12

PHASE NEUT GND

-

#12

#12

#12

-

#12

#12

#12

#12

#12

-

#12

#12

#12

-

-

#12

#12

#12

#12

#12 #12

#12

#12

#12

#12

#12

-

#12

#12

#12

-

#12

#12

#12

#12

#12

-

#12

#12

#12

-

#12

#12

#12

#12

#12

#12

#12

-

#12

#12

#12

#12

#12

-

-

#12

-

#12

-

#12

-

NEUT

-#12

3/4"

-

3/4"

-

#12

#12

#12

#12

3/4"

-

-

3/4"

#12

-

-

#12

3/4"

3/4"

3/4"

3/4"

#12

#12

#12

#12

3/4"

3/4"

3/4"

-

#12

#12

3/4"

3/4"

3/4"

3/4"

#12

#12

#12

#12

PHASE COND

3/4"#12

-

#12

-

#12

-

#12

-

-

#12

#12

#12

#12

#12

-

#12

#12

#12

#12

#12

#12

GND

#12

LOADS (KVA)

WATER HEATING

AIR CONDITIONING

0

0

CONNECTED

0

0

DEMANDFACTOR

1.0

1.0

DEMAND

NON-SEASONAL MOTORS

L1 L2 L3

PHASE LOAD TOTALSEXIST = EXISTING BREAKER, WIRE AND CONDUIT TO REMAIN.

1. EXISTING BREAKER TO REMAIN. NEW CONDUIT AND WIRE PER ELECTRICAL PLANS.

2. EXISTING BREAKER TO REMAIN. CONDUCTORS TO BE REMOVED.

3. REMOVE 2 POLE BREAKER AND INSTALL 2-1 POLE BREAKERS.

0 16 24 328

1/8" = 1' - 0"

PLAN NOTES:

1. FEEDER TO PANEL IS 4 #1 COPPER.

2. FEEDER TO PANEL IS 4 #1/0 COPPER.