Differential Pressure Control Valve TYL-Series Valve body material: Brass Caliber:DN25~DN50 Differential pressure setting range:5-30Kpa or 25-70Kpa Temperature range:-10~120The max. working DP: P V ≤250kPa 1 Datasheet No. : TYL-01 Characteristics Differential pressure control valve(DPCV) can keep the differential pressure at two sides of load constant,that can improve the stability and accuracy,reduce the noise,and easy to balance and commission. 1.Pressure hole of low pressure cavity is built-in, reduce an external connecting pipe, which avoids damage during installation. 2.Target differential pressure value can be setted by hand wheel,it is more convenient. Every number on the hand wheel is corresponding to one setted value. Pre-setting function can be realized easily on site. 3.This valve has manual closing function, plug allen wrench into the center of hand wheel, rotate it to open and close the valve. 4.Balancing diaphragm and spring are built-in, it is nice and reliable. 5.External high pressure testing point, there is locking function, one allen wrench can lock external connecting pipe. Tiger Controls Equipment Co., Ltd Http:// www.tiger-control.com

Upload: buicong

Post on 29-Apr-2018

218 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: TYL-Series Differential Pressure Control Valve · Differential pressure control valve ... and accuracy,reduce the noise,and easy to balance and ... Debugging Instrument TPS is a debugging

Differential Pressure Control Valve

TYL-Series

Valve body material: BrassCaliber:DN25~DN50Differential pressure setting range:5-30Kpa or 25-70KpaTemperature range:-10~120℃The max. working DP: △PV≤250kPa

1

Datasheet No. : TYL-01

Characteristics

Differential pressure control valve(DPCV) can keep the differential pressure at two sides of load constant,that can improve the stability and accuracy,reduce the noise,and easy to balance and commission.

1.Pressure hole of low pressure cavity is built-in, reduce an external connectingpipe, which avoids damage during installation.

2.Target differential pressure value can be setted by hand wheel,it is moreconvenient. Every number on the hand wheel is corresponding to one settedvalue. Pre-setting function can be realized easily on site.

3.This valve has manual closing function, plug allen wrench into the center of handwheel, rotate it to open and close the valve.

4.Balancing diaphragm and spring are built-in, it is nice and reliable.

5.External high pressure testing point, there is locking function, one allen wrenchcan lock external connecting pipe.

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Page 2: TYL-Series Differential Pressure Control Valve · Differential pressure control valve ... and accuracy,reduce the noise,and easy to balance and ... Debugging Instrument TPS is a debugging

DN(mm)

Caliber(in.) Type PN

Max.permissibletemperature

(℃)

Setting range (Kpa)

25 1" TYL25-2VTC-30 16 120 5-30

32 1-1/4" TYL32-2VTC-30 16 120 5-30

40 1-1/2" TYL40-2VTC-30 16 120 5-30

50 2" TYL50-2VTC-30 16 120 5-30

2

Specification

Operating Instruction

1.Connect capillary pipe①, As shown in the installation diagram,one end of capillary pipe connects DPCV,the other end connects with static balancing valve through 3-port testing point②.Now the system is in a state of low pressure.2.Open the plug of air hole③,then open the 3-port measuring points ②. Pour water into pipeline until it exhausts all the air in valve cavity,and lock the air hole plug ③.3.As shown in the installation diagram,use digital differential pressure meter(see page 5) to measure differential pressure of P2 and P3,that is △PL .4.Setting △PL, by rotating the hand wheel⑤. Accurately adjust the data according to data of digital pressure meter.

Cut off function: on the top of hand wheel⑤,close the valve by allen wrench.

Testing point④Remove the cover and then insert the probe into self-sealing testing point.

Capillary pipe①2m capillary pipe is optional if longer one is needed.Attention!Must use matched capillary pipe.

Note:DN = CaliberPN = Pressure class. If PN25 is needed,change C to D in valve type. e.g.TYL25-2VTD-30Materials:Valve body:brass Hpb59-1, Valve Stem:Stainless Steel,Valve Core:Stainless Steel, Diaphragm:EPDM

△PL is 5-30Kpa

△PL is 25-70Kpa DN(mm)

Caliber(in.) Type PN

Max.permissibletemperature

(℃)

Setting range (Kpa)

25 1" TYL25-2VTC-70 16 120 25-7032 1-1/4" TYL32-2VTC-70 16 120 25-70

40 1-1/2" TYL40-2VTC-70 16 120 25-70

50 2" TYL50-2VTC-70 16 120 25-70

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Page 3: TYL-Series Differential Pressure Control Valve · Differential pressure control valve ... and accuracy,reduce the noise,and easy to balance and ... Debugging Instrument TPS is a debugging

3

Installation

USER

Inlet

Outlet

Pc

Note:The DPCV usually be placed in the return pipe and setted with correct water flow direction.

Working Range

A. Kvmin

B. Kvnom C. Kvmax

D. Working Range△PL±25%

1. Open the 3-port testing point

5

2. Open the plug of air hole and lock the air hole plug after it exhausts all the air in valve cavity.

3. Rotate hand wheel to set the DP 4. Close off function: rotate clockwise to tighten the valve

25

Debugging Instruction

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Page 4: TYL-Series Differential Pressure Control Valve · Differential pressure control valve ... and accuracy,reduce the noise,and easy to balance and ... Debugging Instrument TPS is a debugging

4

Dimension

DN D L H Weight(kg)25 1“ 98 177 2.432 1-1/4“ 110 185 2.840 1-1/2“ 120 192 3.650 2“ 150 205 4.8

25~70kPaqmin / qnom / qmax(m3/h)

DN

△pL(kPa)

25 30 40 50 60

qmin qnom qmax qmin qnom qmax qmin qnom qmax qmin qnom qmax qmin qnom qmax

25 0.25 1.83 2.61 0.32 2.62 3.68 0.38 3.46 5.58 0.52 4.52 6.42 0.61 5.33 7.52

32 0.34 2.81 3.86 0.42 3.58 5.23 0.61 4.62 6.41 0.71 5.47 7.65 0.76 6.21 8.82

40 0.39 4.51 6.62 0.44 5.07 7.12 0.51 5.61 8.14 0.58 6.23 10.5 0.67 7.21 12.5

50 0.66 7.61 11.2 0.75 9.12 13.3 0.88 10.7 15.5 0.96 12.1 17.2 1.15 13.2 19.1

DN

△pL(kPa)

70

qmin qnom qmax

25 0.72 7.23 9.18

32 0.83 8.21 11.2

40 0.78 7.41 13.6

50 1.28 14.5 20.7

Selection 1.Select the desired △PL in the tables.2.Select the same size of the valve as the pipe.3.Check that the desired flow is smaller than the specified qmax.If not,select the most similar large dimension,or a larger △PL.

The tables work in the following situation: △H≥2*△PL, the valve will work effectively from 2*△PL to 250kpa+△PL.

5~30kPaqmin / qnom / qmax(m3/h)

DN

△pL(kPa)

5 10 20 30

qmin qnom qmax qmin qnom qmax qmin qnom qmax qmin qnom qmax

25 0.15 0.96 1.33 0.28 1.24 1.68 0.36 1.82 2.66 0.47 2.12 3.21

32 0.26 1.74 2.63 0.33 2.06 2.65 0.45 2.51 3.84 0.59 3.15 4.57

40 0.32 2.71 3.71 0.46 2.93 4.08 0.55 3.87 5.52 0.68 4.58 7.12

50 0.47 3.52 5.12 0.57 5.07 9.11 0.63 7.44 10.4 0.88 9.14 13.3

Valve Inherent FlowCaliber DN25 DN32 DN40 DN50

Kvs 6.7 13 15 19

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Page 5: TYL-Series Differential Pressure Control Valve · Differential pressure control valve ... and accuracy,reduce the noise,and easy to balance and ... Debugging Instrument TPS is a debugging

5

Accessory

41

G1/4

Capillary pipe

The standard length is 100mm,200mm is optional if longer pipe is needed.

L[mm] Article No.

100 PIPE-100

200 PIPE-200

3-port testing point with cut-off function

Two testing port and cut-off function Article No.

CY-002

Seal-capping

Specifications Article No.

Red CY-003-R

Blue CY-003-B

Plug

For air hole G D[mm] Article No.

G1/16 12 TYL-001

G1/8 14 TYF-001

Testing point

High voltage end is in red,low voltage end is in blue.

Specifications Article No.

Red CY-001-R

Blue CY-001-B

Allen wrench

Use for closing the valve

Hand wheel

Supplied with the valve Specifications Article No.

DN15~DN50 SL-001

DN65~DN150 SL-002

DN200~DN500 SL-003

Specifications Article No.

3mm TPS-006-3

5mm TPS-006-5

8mm TPS-006-8

Joint

use for connecting the pipe and testing point

If there is no Static Balancing Valve in front of the DPCV, the testing point could be screwed with the threads end of Joint. Then dig a hole at the pressure-sampling position on pipe and weld the joint onto the pipe.

Article No.

TYF-002

G 1/4

Φ20

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Page 6: TYL-Series Differential Pressure Control Valve · Differential pressure control valve ... and accuracy,reduce the noise,and easy to balance and ... Debugging Instrument TPS is a debugging

6

Debugging Instrument TPS is a debugging instrument for measuring and documenting of differential pressure, flow, temperature and power consumption in hydronic systems. It connects to the specialized APP sofeware in an Android phone via bluetooth which could debug faster and more economical.

Max. Permissible Pressure 1000kPa

DP Measurement RangeTPS-200KPA.BOX: 0~200kPa

TPS-1000KPA.BOX: 0~1000kPa

Pressure Range during Flow measurement (Recommended Value)

TPS-200KPA.BOX: 3~200kPa

TPS-1000KPA.BOX: 3~1000kPa

Medium Temperature -20~120°C

Measurement Deviation

DP Sensor: ≤0.25%

Flow: DP Deviation+ Valve Deviation

Temperature: ≤1°C

Battery Capacity 3000mA

Operating Time >20 h

Charge Time 6 h

Ambient Temperature

During Operating and Charging:0~40°C

During Storage: -20~60°C(Do not leave water in the sensor when there is a risk of freezing)

Ambient Humidity Max. 90%RH

ChargerOutput Voltage: 12.6V DC

Output Current: 500mA

Technical Parameters

Hydraulic Balancing Debugging Instrument

TPS-200KPA.BOXTPS-1000KPA.BOX

TPS-200-1000KPA.BOX

Interface Introuduction The TPS.app can be installed in Android phone.During the debugging, it could easily figure out the flow value and it is more intuitive than the table lookup and easer to operate!

①Status Bar: The battery status is on the left. Time is in the middle. On the right, it

shows the connecting status of device, Bluetooth connection status and device battery

status. When the connection works, t h is icon will flicker.

②Title Bar: the software title is in the middle, right is setting button. Its functions

include equipment search, help, update and so on.

Search: search for Bluetooth devices, paired and so on.

Help: provide operating instructions.

Update: interconnection state, update software if there is a new version.

About: check the version number of the program.

③Display Bar: show current status of DP, Flow and temperature, connection status,

current cycles, current KV value and Distortion Ratio.

④Formula Bar: Input basic testing parameters, including valve number, caliber choice,

cycles setting, design flow, remark info. and so on.

⑤Operation Bar: Include calibrate, connect, data storage, view records and generate

reports.

Calibrate: calibrate the zero drift of the instrument.

Connect: connect to the default paired device.

Data Storage: store the current measuring value.

View records: View the current records in the database.

Generate reports: generate xls spreadsheet and store in the SD card.

⑥Menu Bar: include measure, data, settings and about.

Measure: turn to measuring interface

Data: view xls spreadsheet management.

Settings: set the normal operation information, such as project name, company

selection and so on.Tiger Controls Equipment Co., Ltd