type ca-16 percentage differential relay for bus protection class … · 2018-05-09 · 41-337.31 c...

16

Upload: others

Post on 25-Jan-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics
Page 2: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

2

Figu

re 1

.C

A-1

6 Fr

ont V

iew

Figu

re 2

.C

A-1

6 R

ear V

iew

Page 3: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

3

2.1. Restraint Elements

Each restraint element consists of an “E” laminatedelectromagnet with two primary coils and a second-ary coil on its center leg. Two identical coils on theouter legs of the laminated structure are connectedto the secondary winding in a manner so that thecombination of all fluxes produced by the electro-magnet results in out-of-phase fluxes in the air gap.The out-of-phase fluxes cause a contact openingtorque.

2.2. Operating Circuit

The operating circuit consists of an autotransformerand an operating element. The primary of the auto-transformer, which is the whole winding, is connectedto receive the differential or unbalanced current fromthe various transformers connected to the bus. Thesecondary winding of the autotransformer, which is atapped section of the winding, is connected to theoperating element of the relay.

The operating element consists of an “E” type lami-nated electromagnet with an autotransformer wind-ing on its center leg. Two identical coils on the outerlegs of the laminated structure are connected to thesecondary (tapped section) of the autotransformerwinding in a manner so that the combination of allfluxes produced by the electromagnet results in out-of-phase fluxes in the air gap. The out-of-phase airgap fluxes cause a contact closing torque.

2.3. Sensitive Fault Detector Circuit

The sensitive fault detector circuit consists of anautotransformer and a contactor switch. The contac-tor switch is connected across the secondary (tappedsection) of the auto-transformer winding.

The contactor switch is a small solenoid type ele-ment. A cylindrical plunger rides up and down on avertical guide rod in the center of the solenoid coil.The guide rod is fastened to the stationary core,which in turn screws into the unit frame. A silver discis fastened to the moving plunger through a helicalspring. When the coil is energized, the plungermoves upward carrying the silver disc which bridgesthree conical-shaped stationary contacts. In this posi-tion, the helical spring is compressed and the plungeris free to move while the contact remains stationary.Thus, ac vibrations of the plunger are prevented fromcausing contact bouncing. A micarta disc is fastenedto the bottom of the guide rod by two small nuts. Itsposition determines the pick-up current of the ele-ment.

The auto-transformer is designed to saturate at highvalues of current to limit the amount of current to thecontactor switch.

2.3.1. Indicating Contactor Switch Unit (ICS)

The dc indicating contactor switch is a small clappertype device. A magnetic armature, to which leaf-spring mounted contacts are attached, is attracted tothe magnetic core upon energization of the switch.

When the switch closes, the moving contacts bridgetwo stationary contacts, completing the trip circuit.Also during this operation two fingers on the arma-ture deflect a spring located on the front of theswitch, which allows the operation indicator target todrop. The target is reset from the outside of the caseby a push rod located at the bottom of the cover.

The front spring, in addition to holding the target pro-vides a restraint for the armature and thus controlsthe pick-up value of the switch.

3.0 OPERATION

The type CA-16 relay is an induction disc relay withfour electromagnets mounted on two discs that arefastened on a common shaft. One of the electromag-nets is the operating element while the other threeare restraint elements. The restraint elements areenergized from the secondaries of current transform-ers connected to the bus, and the operating circuit isenergized in accordance with the current flowing inthe differential connection of the current transform-ers.

A current of 5 amperes in at terminal 18 and out ofterminal 19 will produce a definite amount of restrain-ing torque (see Figure 3.) Similarly, a current of 5amperes flowing in at terminal 16 and out of terminal17 will produce an equal amount of torque. If both ofthese currents flow at the same time with the polarityas indicated above, their effect will be additive andthey will produce the same torque as though 10amperes are flowing in terminal 16 and out of termi-nal 17. Conversely, if equal currents flow in these twocoils, but in opposite directions, their ampere turnswill cancel and no torque will be produced. The samerelationship applies for the paired coils of the othertwo restraining units of the relay. The restraint effectwill always be additive if currents flow in the coilswhich belong to different restraint elements.

Page 4: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

4

4.0 CHARACTERISTICS

4.1. CA-16 Bus RelayThis relay has variable percentage characteristicswhich means that the operating coil currentrequired to close the relay contacts, expressed inpercent of the total restraint current, varies with themagnitude of the restraint current. The relay sensi-tivity is high, corresponding to a low percentageratio, at light currents, and its sensitivity is low, cor-responding to high percentage unbalance, at highcurrents. The relay is made sensitive at low cur-rents in order to detect light internal faults on thebus being protected. At the same time, however, itsreduced sensitivity at the higher currents allows thevarious current transformers involved to departfrom their true ratio to a large extent without caus-ing false tripping of the relay for external faults.

The variable percentage characteristics are particu-larly advantageous when severe saturation of cur-rent transformers is caused by the dc component ofasymmetrical short circuits. In the case of buseslocated close to generating stations where the dccomponents decay slowly, the breakdown in ratio ofthe current transformers will be much greater thanwould ever be expected from a consideration of theusual ratio curves of the current transformersinvolved.

The time of operation of the relay is shown in Fig-ure 4.

The main contacts will safely close 30 amperes at250 volts dc and the seal-in contacts of the indicat-ing contactor switch will safely carry this currentlong enough to trip a circuit breaker.

The indicating contactor switch has two taps thatprovide a pick-up setting of 0.2 or 2 amperes. Tochange taps requires connecting the lead located infront of the tap block to the desired setting bymeans of a screw connection.

4.2. Trip Circuit Constants

Indicating Contactor Switch (ICS)

0.2 amp rating 8.5 ohms dc1.0 amp rating 0.37 ohms dc2.0 amp rating 0.10 ohms dc

ENERGY REQUIREMENTSBurden of each restraint coil at 5 amperes

VOLT AMPERES POWER FACTOR

.75 .7Continuous Rating 14 amperes1 second rating 460 amperes

Burden of operating CircuitVOLT AMPERES

VARIABLE (See Figure 5)

Continuous rating 8 amperes1 second rating 280 amperes

4.3. Connections

4.3.1. CA-16To determine the ac connections, identify each pri-mary circuit as either a “source” or “feeder”. Asdefined here, a feeder contributes only a small por-tion of the total fault-current contribution for a busfault. Otherwise, the circuit is a source. Next lump anumber of feeders into a “feeder group” by parallelingfeeder ct’s, taking the precaution that each feedergroup has less than 14 amperes load current(restraint coil continuous rating). Also each feedergroup should not contribute more than 10% of thetotal phase or ground-fault current for a bus fault ifFigure 7 is to be used.

Connect per Figure 6 with three or four bus “circuit.”The term “circuit” refers to a source or to a feedergroup. For example, assume a bus consisting of 2sources and 6 feeders. Further, assume that thefeeders are lumped into 2 feeder groups. The busnow reduces to four circuits

If the bus reduces to more than four circuits, parallelsource-circuit ct’s or source-and feeder circuit ct’suntil only four circuits remain. Then connect thesefour sets of ct’s to the relays per Figure 6. The excep-tion to this rule occurs when the application consistsof three feeder groups. Then Figure 7 applies.

With 3 feeder groups and more than 3 sources, par-allel source ct’s until the application reduces to 6 cir-cuits; then, connect to the relays per Figure 7.

Page 5: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

5

4.4. Setting CalculationsNo calculations are required to set the CA-16.

4.5. Setting The RelayNo settings are required on the CA-16 relay.

5.0 INSTALLATIONThe relays should be mounted on switchboard panelsor their equivalent in a location free from dirt, moisture,excessive vibration and heat. Mount the relay verti-cally by means of the four mounting holes on theflange for the semi-flush type FT case. The mountingscrews may be utilized for grounding the relay. Exter-nal toothed washers are provided for use in the loca-tions shown on the outline and drilling plan to facilitatemaking a good electrical connection between the relaycase, its mounting screws and the relay panel. GroundWires are affixed to the mounting screws as requiredfor poorly grounded or insulating panels. Other electri-cal connections may be made directly to the terminalsby means of screws for steel panel mounting.

For detail information on the FT case refer to IL 41-076 for semi-flush mounting.

6.0 ADJUSTMENTS AND MAINTENANCEThe proper adjustments to insure correct operation ofthis relay have been made at the factory. Uponreceipt of the relay, no customer adjustments shouldbe required.

6.1. Acceptance CheckThe following check is recommended to insure thatthe relay is in proper working order. The relay shouldbe connected per Figure 8.

A. Minimum Trip Current

Apply current to terminals 12 and 13 of the relay. Therelay should operate as follows:

CA-16 0.15 amperes ±5%

B. Percentage Differential Characteristic

Apply 16 amperes to terminals 9 and 19 of the CA-16relay. The contacts should close when the followingoperating current is applied to the relay with connec-tions of Figure 8.

CA-16 17.0 amperes ±7%

Check each individual restraint winding by applying50 amperes to each winding. Apply sufficient operat-

ing current to the operating circuit until the contactsjust close. The operating current should be:

CA-16 3.9 to 5.1 amperes

C. Time Curve

Apply 20 amperes to terminals 12 and 13 of therelays. The contacts should close in the followingtimes:

CA-16 58 to 68 Milliseconds

D. Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient dccurrent through the trip circuit to close the contacts ofthe ICS. This value of current should not be greaterthan the particular ICS nameplate rating. The indica-tor target should drop freely.

Repeat above except pass 85% of ICS nameplaterating current. Contacts should not pickup and targetshould not drop.

E. Sensitive Fault Detector

Apply current to terminals 14 and 15 of the relay. Thefault detector should operate between the limits of0.142 to 0.158 amperes.

6.2. Routine MaintenanceAll contacts should be periodically cleaned. A contactburnisher is recommended for this purpose.(S#182A836H01). The use of abrasive material forcleaning contacts is not recommended, because ofthe danger of embedding small particles in the faceof the soft silver and thus impairing the contact.

7.0 CALIBRATIONUse the following procedure for calibrating the relay ifthe relay has been taken apart for repairs or theadjustments disturbed. This procedure should not beused until it is apparent that the relay is not in properworking order. (See “Acceptance Check”.)

7.1. ContactsAdjust the adjustable stop screw on the upper disc ofthe relay so that a contact separation of 0.050 inch isobtained between the moving contact and the sta-tionary contact. Lock the screw with the nut providedfor the purpose.

7.2. Minimum TripThe relay should be level for this test. Minimum trip

Page 6: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

6

current can best be determined with the permanentmagnet removed.

Adjust the spring tension until t he relay just closes itscontacts with the following current applied to termi-nals 12 and 13 of the relay.

CA-16 0.15 amperes

7.3. Percentage Slope CharacteristicConnect the relay per the test circuit of Figure 8.

Pass 20 amperes for the CA-16 relay into terminals 9and 19 of the relay. Adjust the plug (when used) inthe operating electromagnet until the contacts justclose with the following currents into the operatingcircuit of the relays.

CA-16 29.4 to 34 amperes

7.4. Time CurvePlace the permanent magnet on the relay and apply 20amperes to terminals 12 and 13 of the relay. Adjust thekeeper of the permanent magnet until the contacts justclose in the following times:

CA-16 58 to 68 Milliseconds

These times should be the average of 5 readings.

7.5. Indicating Contactor Switch (ICS)Initially adjust unit on the pedestal so that armature fin-gers do not touch the yoke in the reset position.(Viewed from top of switch between cover and frame).This can be done by loosening the mounting screw inthe molded pedestal and moving the ICS in the down-ward position.

a. Contact Wipe – Adjust the stationary contact sothat both stationary contacts make with the movingcontacts simultaneously and wipe 1/64” to 3/64”when the armature is against the core.

b. Target – Manually raise the moving contacts andcheck to see that the target drops at the sametime as the contacts make or 1/16” ahead. Thecover may be removed and the tab holding thetarget reformed slightly if necessary. However,care should be exercised so that the target will

not drop with a slight jar.

If the pickup is low, the front cover must be removedand the leaf springs on each side bent outwardequally.

7.6. Sensitive Fault Detector

Loosen the lock nut at the top of the element and runthe core screw down until it is flush with the top of thelock nut. Back off the Micarta disc by loosening thetwo lock nuts. Apply 0.15 amperes to terminals 14and 15. Operate the moving element by hand andallow the current to hold the moving contact discagainst the stationary contacts. Now, screw up thecore screw slowly. This causes the plunger to moveup, compressing the spring until a point of maximumdeflection is reached. Further upward motion willcause the plunger to drop part way out of the coil,thus diminishing the spring pressure on the contacts.By thus adjusting the core screw up or down themaximum spring deflection for this value of currentmay be found.

Then lock the core screw in place. Next, adjust thede-energized position of the plunger by raising theMicarta disc until the plunger just picks up electricallyat the 0.15 ampere value.

7.7. Electrical Checkpoints

Figures 9 and 10 will aid in trouble shooting theCA-16. These curves show the operating current totrip the relay for different restraint current for onerestraint element as well as for six restraint elementsconnected in series.

8.0 RENEWAL PARTS

Repair work can be done most satisfactorily at thefactory. However, interchangeable parts can be fur-nished to customers who are equipped for doingrepair work. When ordering parts, always give thecomplete nameplate data.

Page 7: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

7

Figure 3. Internal Schematic of the Type CA-16 Bus Relay

Sub 13532A95

Page 8: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

8

Figu

re 4

.Ty

pica

l Tim

e C

urve

s of

the

CA

-16

Diff

eren

tial R

elay

Su

b 1

5379

56

Page 9: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

9

Figu

re 5

.Ty

pica

l Bur

den

Cha

ract

eris

tics

of th

e Ty

pes

CA

-16

and

CA

-26

Rel

ays

Cur

ve 5

3795

7

Page 10: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

10

Figure 6. External Schematic of One Set of Type CA-16 Relays for the Protection of a Three and Four Circuit Bus

Sub 5187A424

Page 11: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

11

Figure 7. External Schematic of the Type CA-16 Relays for Protection of Six Circuit Bus with Three Feeder Groups

Sub 5187A425

Page 12: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

12

Figu

re 8

.D

iagr

am o

f Tes

t Con

nect

ions

for t

he C

A-16

Rel

ay

Sub

418

7A42

6

Page 13: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

13

Figure 9. Percentage Slope Curve of the CA-16 Relay with One Restraint Winding

Sub 1849A450

Page 14: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

41-337.31 C

14

Figure 10. Percentage Slope Curve of the CA-16 Relay with Six Restraint Windings in Series

Sub 2849A343

Page 15: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics
Page 16: Type CA-16 Percentage Differential Relay for Bus Protection Class … · 2018-05-09 · 41-337.31 C 4 4.0 CHARACTERISTICS 4.1. CA-16 Bus Relay This relay has variable percentage characteristics

ABB Inc.4300 Coral Ridge DriveCoral Springs, Florida 33065Telephone: +1 954-752-6700Fax: +1 954-345-5329www.abb.com/substation automation

IL 4

1-33

7.31

- R

evis

ion

C

ABB