type ka-4 carrier auxiliary relay instruction leaflet · 41-923.4m 3 figure 2.internal schematic of...

16

Upload: vuongque

Post on 26-Apr-2018

242 views

Category:

Documents


10 download

TRANSCRIPT

Page 1: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type
Page 2: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

2

Figure 1. Type KA-4 Relay without case. (Front View)

Page 3: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

Sub 3629A389

Sub 9629A476

Figure 2. Internal Schematic of the Type KA-4 Relay for KRCarrier Set.

Sub 13491A17

Figure 3. Internal Schematic of the Type KA-4 Relay for TCCarrier Set.

Sub 1349A16

Figure 4. Internal Schematic of the Type KA-4 Relay withModified Carrier Stop to Terminal 11 for TC CarrierSet.

Figure 5. Internal Schematic of the Type KA-4 Relay for theTA-3 tones.

3

Page 4: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

shaft. The shaft has removable top and bottom jewelbearings. The shaft rides between the bottom pinbearing and the upper pin bearing with the cylinderrotating in an air gap formed by the electromagnetand the magnetic core.

The bridge is secured to the electromagnet andframe by two mounting screws. In addition to holdingthe upper pin bearing, the bridge is used for mount-ing the adjustable stationary contact housing. Thestationary contact housing is held in position by aspring type clamp. The spring adjuster is located onthe underside of the bridge and is attached to themoving contact arm by a spiral spring. The springadjuster is also held in place by a spring type clamp.

With the contacts closed, the electrical connection ismade through the stationary contact housing clamp,to the moving contact, through the spiral spring out tothe spring adjuster clamp.

When the current in the overcurrent unit exceeds thepick-up value the contacts open, allowing positivepotential to be applied to the carrier transmitter.

A transformer and current limiting reactor is used inconjunction with the cylinder unit. The transformersupplies one set of coils on the cylinder unit with volt-age shifted by approximately 90° from the residualcurrent supplied directly to another set of coils. Thetransformer and reactor are of the saturating typewhich limits energy to the cylinder unit and reducesthe burden on the transmission line CT.

2.2. AUXILIARY UNITS

These are two solenoid-type contactor switches des-ignated as CSP and CSG. The plunger of the contac-tor switch has a circular conducting disc mounted onits lower end and as the plunger travels upward, thedisc bridges three silver stationary contacts. TheCSP switch is energized by the operation of the sec-ond zone or KD-10 distance relay, and the CSGswitch, by the operation of the directional and over-current units of the KRD-4 ground relay. The contactsof the two switches are connected in parallel asshown in the internal schematic. The operation ofeither of these switches connects the carrier controlcircuit to negative to stop carrier, and energizes theRRT operating coil of the receiver relay unit.

2.3. RECEIVER UNIT

The receiver unit consists of an armature and con-tacts mounted on a leaf spring supported symmetri-cally within a magnet frame. The armature rides inthe front air-gap of the frame with the contacts pro-jecting outside. The poles of a permanent magnetclamp directly to each side of the frame. Two adjust-able shunts are located across the rear air-gaps.These change the reluctance of the magnetic path asshown in Figure 7 so as to force some of the flux thruthe moving armature which is fastened to the framemidway between the two rear air gaps. Flux in thearmature polarizes it and creates a magnetic bias,causing it to move towards either the left or right,depending upon the adjustment.

Two stationary contact screws are mounted to the left(front view) of the moving contact assembly andadjusted for normally open contacts. These contactsare designated, RRP and RRG, and are connected inthe phase and ground trip circuit respectively. Thesecontacts are operated by two concentric coils, RRTand RRH, which are placed around the armature andwithin the magnetic frame. RRT is the operating coiland receives its energy from the local battery wheneither CSP or CSG is closed. RRH is the holding coiland receives its energy from the carrier transmittedeither from the local transmitter or the one at the endof the line section. These two coils are connected inoppose each other with the operating coil, RRT oper-

Figure 6.Typical Time Characteristics of carrier start over-current unit of the type KA-4 Relay.

4

Page 5: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

ating to close the RRP and RRG contacts and trip;and the holding coil, RRH to hold the RRP and RRGcontacts open and block tripping. The restrainingtorque of the RRH coil is sufficient to overcome theoperating torque of the RRT coil. Consequently, RRPand RRG contacts cannot close as long as RRH isenergized.

2.4. ALARM UNIT

The alarm unit is similar in construction to thereceiver unit except that it is energized by a singlecoil and operates a single set of contacts. The coil isenergized by the received carrier to close its contactsand give an alarm. This unit has a higher pick-upthan that of the receiver unit in order to obtain adirect check on the sensitivity of the carrier transmit-ter-receiver. The failure of the alarm unit to pick-upwhen carrier is started indicates insufficient outputfrom the transmitter receivers.

2.5. SQUELCH UNIT

The function of the squelch unit is to hold of the car-rier for a period of 150 milliseconds after the Breaker“a” contact opens. This is to insure that all other ter-minals of the line are tripped before allowing carrierto be transmitted for any functions.

The squelch unit is a telephone type unit of slowrelease type.

In these relays, an electromagnet attracts a rightangle iron bracket which in turn operates one nor-mally open contact. The slow release is obtained bya copper slug located at the end opposite from thearmature. When the coil becomes deenergized, thechange in flux through the slug results in an electro-motive force and associated current in it. This currentproduces a flux which aids the main flux and delaysthe release of the armature. When the coil is ener-gized, the operation of the relay is not appreciablydelayed because the armature is operated by flux notlinking the slug.

2.6. OPERATION INDICATOR

The operation indicator gives a visual indication of acarrier tripping operation for phase faults by the dis-tance relay through the RRP contacts. For a groundfault carrier relaying operation, the indicating contac-tor switch (ICS) located in the ground relay will drop atarget.

3.0 CHARACTERISTICS

The characteristics of the various elements of therelays are as follows:

The pick-up and operating values of these units aregiven under “Adjustments and Maintenance”.

The time characteristic of the overcurrent unit is

183A062

N

N

S

S

N

N

S

S

Moving Contact

Armature

PermanentMagnet

BALANCED AIR GAPS UNBALANCED AIR GAPSN

AdditionalFlux Path

Shunt

Figure 7. Permanent Magnet Flux Paths of Receiver and Alarm Units

5

Page 6: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

shown in figure 6.

The pick-up value of the overcurrent unit can bechanged from the factory adjusted value of 0.5amperes to any value up to 1 amp. by increasingspring restraint.

4.0 SETTINGS

There are not settings to be made

5.0 INSTALLATION

The relays should be mounted on switchboard pan-els or their equivalent in a location free from dirt,moisture, excessive vibration, and heat. Mount therelay vertically by means of the four mounting holeson the flange for semi-flush mounting or by means of

the rear mounting stud or studs for projection mount-ing. Either a mounting stud or the mounting screwsmay be utilized for grounding the relay. The electricalconnections may be made directly to the terminals bymeans of screws for steel panel mounting or to theterminal studs furnished with the relay for thick panelmounting. The terminal studs may be easily removedor inserted by locking two nuts on the stud and thenturning the proper nut with a wrench.

The carrier relaying schematic (supplied with the car-rier order) should be consulted for details of theexternal connections of these relays.

6.0 ADJUSTMENTS & MAINTENANCE

The proper adjustments to insure correct operation ofthis relay have been made at the factory. Uponreceipt of the relay, no customer adjustments, otherthan those covered under “SETTINGS”, should berequired.

6.1. ACCEPTANCE CHECK

The following check is recommended to insure thatthe relay is in proper working order.

6.1.1. Overcurrent Unit

Pass 0.5 amperes of altered current through relayterminals 16 and 17, the contact should pickup within.475 and .525 amp.

6.1.2. Auxiliary Units (CSP and CGS)

Each contactor switch has a section of a tappedresistor in series with it, and will pick up positivelywhen rated control voltage is applied across the coiland its section of the resistor.

These units should operate at 24 volts for the 48-voltrelay, 60 volts for the 125-volt relay, and 120 volts for250-volt relay. These units have an intermittent rat-ing, and should not be energized for more than a fewseconds.

6.1.3. Operation Indicator (OI)

With the polar unit contacts closed, apply direct cur-rent to the operation indicator relay terminals. Theoperation indicator should pick-up and drop the indi-cator target between 1 ampere and 1.2 amperes dc.

For Use With KR-Set48VAvg.

Ohms

125Avg.

Ohms

250Avg.

Ohms

CSP or CSG CoilCSP & CSG Tapped ResistorCarrier ResistorRRT Operating CoilRRT Coil ResistorRRH Holding CoilAL-Alarm CoilOperation Indicator (1 amp.)Squelch Unit CoilSquelch Unit Adj. Resistor

27200

2000110013201700

5000.1

3300-

27600

3750110050001700

5000.1

33008500

4356000

190001100

112001700

5000.1

33001500

For Use With TC-Set

CSP or CSG CoilCSP & CSG Tapped ResistorCarrier ResistorRRT Operating CoilRRT Coil ResistorRRH Holding CoilAL-Alarm CoilOperation Indicator (1 amp.)Squelch Unit CoilSquelch Unit Adj. Resistor

27200

100011001320

204

0.13300

-

27600

375011005000

204

0.133008500

456000

-1100

1120020

40.1

330015000

For Use With TA-3 Tones

CSP or CSG CoilCSP & CSG Tapped ResistorCarrier ResistorRRT Operating CoilRRT Coil ResistorRRH Holding CoilAL-Alarm CoilOperation Indicator (1 amp.)Squelch Unit CoilSquelch Unit Adj. Resistor

27200200

110013201700

5000.1

3300-

27600

4000110050001700

5000.1

33008500

4356000

106001100

112001700

5000.1

330015000

6

Page 7: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

6.1.4. Squelch Unit (SQ)

Apply rated dc voltage to relay terminals that willenergize the squelch unit and note contact operation.

6.1.5. Blocking Zener Diode

Apply rated dc voltage in series with 10,000 ohmresistors across terminals 8 and 9 with positive on 9,the current leakage flow should not exceed .25 mA.Reserve polarity of the applied voltage; the currentflow should be equal to the applied voltage dividedby the series resistance.

6.2. FOR RELAYS TO BE USED WITHTC-TYPE CARRIER

6.2.1. Receiver Unit

Connect a jumper between the middle and left-handcontact connection of the CSG or CSP switch. TheCSG switch is located on the left-hand pedestal andCSP is located on the right-hand pedestal on therelay (front view). Apply rated voltage across theRRT coil and the RRT coil resistor, observing polarityas shown in the internal schematic. The armatureshould move to the left.

To the holding coil (RRH) relay terminals, apply directcurrent observing polarity. Increase the current untilthe armature moves to the right.

The armature should move to the right at approxi-mately 60 mA. Now reduce the current and the arma-ture should move to the left at approximately 40 mA.

6.2.2. Alarm Unit (AL)

Connect direct current to the alarm unit relay termi-nals. Increase the current until the contacts pick-up.The contacts should pick up at approximately 80 mA.Now reduce the current and the contacts shouldopen at 40 to 60 mA.

6.3. FOR RELAYS TO BE USED WITHTYPE KR CARRIER OR TA-3 TONES

6.3.1. Receiver Unit

Connect a jumper between the middle and left-handcontact connection of the CSG or CSP switch.

CSG switch is located on the left-hand pedestal andCSP is located on the right-hand pedestal on the

relay (front view). Apply rated voltage across theRRT coil and the RRT coil resistor, observing polarityas shown in the internal schematic. The armatureshould move to the left.

To the holding coil (RRH) relay terminals, apply directcurrent observing correct polarity. Increase the cur-rent until the armature moves to the right. The arma-ture should move to the right at approximately 6 mA.Now reduce the current and the armature shouldmove to the left at approximately 4 mA.

6.3.2. Alarm Unit (AL)

Connect direct current to the alarm unit relay termi-nals. Increase the current until the contacts pickup.The contacts should pickup at approximately 8 mA.Now reduce the current and the contacts shouldopen at 4 to 6 mA.

7.0 ROUTINE MAINTENANCE

All relays should be inspected periodically and theoperation should be checked at least once everyyear or at such other time intervals as may be dic-tated by experience to be suitable to the particularapplication.

All contacts should be periodically cleaned. A contactburnisher Style # 182A836H01 is recommended forthis purpose. The use of abrasive material for clean-ing contacts is not recommended, because of thedanger of embedding small particles in the face ofthe soft silver and thus impairing the contact.

7.1. CALIBRATION

Use the following procedure for calibrating the relay ifthe relay has been taken apart for repairs or theadjustments have been disturbed. This procedureshould not be used unless it is apparent that the relayis not in proper working order. (See “AcceptanceCheck”).

7.1.1. Overcurrent Unit

The upper bearing screw should be screwed downuntil there is approximately 1/64” clearance betweenit and the top of the shaft bearing. Securely lock inposition with the lock nut. The lower bearing positionis fixed and cannot be adjusted.

7

Page 8: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

With the moving contact in the normally closed posi-tion, i.e., against the right side of the bridge, screw inthe stationary contact until both contacts just close.Then screw in the stationary contact approximatelyone-quarter turn farther to provide the correctamount of follow for KR & TC type carrier, one-halfturn for TA-3 tones.

The clamp holding the stationary contact housingneed not be loosened for the adjustment since theclamp utilizes a spring-type action in holding the sta-tionary contact in position.

The sensitivity adjustment is made by varying thetension of the spiral spring attached to the movingelement assembly. The spring is adjusted by placinga screwdriver or similar tool into one of the notcheslocated on the periphery of the spring adjuster androtating it. The spring adjuster is located on theunderside of the bridge and is held in place by aspring type clamp that does not have to be loosenedprior to making the necessary adjustments.

Pass 0.5 amp of ac through relay terminals 16 and17. Adjust the spring until the contact just opens. In asimilar manner the pick-up value can be adjusted forany value between .5 and 1.0 amp.

7.1.2. Auxiliary Units (CSP and CSG)

The two contactor switches, CSP and CSG, haveadjustable plunger travel. Adjust the stationary coreand the moving core of 1/64” when the switch ispicked up. This can be done by turning the relayupside-down and screwing up the core screw of theswitch until the contacts just separate. Then back offthe core screw approximately one turn and lock inplace. This prevents the moving core from strikingand sticking to the stationary core because of resid-ual magnetism. Adjust the contact clearance forapproximately 1/32” by means of the two small nutson either side of the Micarta disc.

Each contactor switch has a section of a tappedresistor in series with it, and will pick up positivelywhen rated trip circuit voltages is applied across thecoil and its section of the resistor.

The units should operate at 24 volts for the 48-voltrelay, 60 volts for the 125-volt relay and 120 volts for

250-volt relay. These units have an intermittent rat-ing, and should not be energized for more than a fewseconds.

7.1.3. Squelch Unit

Check operation with timer. Adjust series resistor tomeasure approximately 5000 ohms for 125 Vdcrelays and for 13000 ohms for 250 Vdc relay. Witharmature closed, adjust the residual air gap to be.002” – .003”. Contact gap should measure from.020” to .035”. Check for dropout time between .140and .160 seconds. If necessary dropout time can beadjusted by changing the residual air gap. After finaladjustment the gap should be at lease .002”. Thepickup time should be below 16 milliseconds at -20%rated dc voltage. If necessary readjust series resis-tor.

7.1.4. Operation Indicator

The operation indicator should pickup and drop theindicator target when the current is between 1 and1.2 amperes dc.

Make sure that the target drops freely when the unitoperates.

7.2. ZENER DIODE TEST

7.2.1. Forward Characteristics

Pass 200 mA of dc current through terminals 8 and 9with positive on terminal 8. Measure voltage dropacross terminals 8 and 9 with positive on 9. The volt-age drop should not exceed 3.5 volts.

7.2.2. Reverse Characteristics – Breakdown Voltage

The breakdown Voltage is determined by increasingvoltage across terminals 8 and 9 with positive on 9.Place 10,000 ohm resistor in series with ammeter.Increase voltage until current reads .25 mA. Measuredc voltage across terminals 8 and 9. The voltageshould be between 160 and 240 volts for 48 and 125Vdc rated relays; and 320 to 480 volts for 250 Vdcrated relays. DO NOT exceed 3.0 mA current in thecircuit.

8

Page 9: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

7.3. FOR RELAY TO BE USED WITHTC-TYPE CARRIER

7.3.1. Receiver Unit

Back off contact screws so that they do not makecontact. Screw magnetic shunts into the all-out posi-tion (5 or 6 screw threads showing.) The armatureshould remain against whichever side it is pushedwith this adjustment.

Adjust the stationary contacts for a contact gap ofapproximately .020”. This can be done by inserting a.010” steel thickness gage between the large rivethead on the moving armature and the right-hand poleface (a .010” travel of the rivet head is equal to .020”travel of the moving contacts). Using an indicatinglight in each contact circuit, adjust the upper andlower stationary contacts to touch the moving contactat the same time. With the feeler gauge removed thecontact gap is 0.20” and the moving contacts closesimultaneously.

Connect a jumper between the middle and left-handcontact connection of the CSG or CSP switch. TheCSG switch is located on the right-hand pedestal andCSP is located on the right-hand pedestal of therelay (front view). Apply rated voltage across theRRT coil and the RRT coil resistor observing polarityas shown in the internal schematic diagram. Thearmature should move to the left.

To the holding coil, RRH, apply 100 to 200 milliam-peres dc current observing correct polarity. Thearmature should now move to the right. Deenergizeboth coils and see that the armature stays up againstthe right-hand side.

Run both shunt screws all the way in, and then backout the left-hand shunt screw approximately 6 turns.Back out the right-hand shunt screw approximately 9turns.

Re-energize the operating coil with rated voltage andthe holding coil with 40 milliamperes dc. Adjust theright-hand shunt screw until the armature moves tothe left. If the armature moves to the left, at a value ofholding coil current greater than 40 milliamperes, theright-hand shunt screw should be turned out to lowerthis value to the correct 40 milliampere point.

Increase the holding coil current to 60 milliamperesand adjust the left-hand shunt screw until the arma-ture resets, or moves to the right. If the armatureresets at a value of current less than 60 milliam-peres, the left-hand shunt screw should be turnedout. This will increase the reset value of the armatureand provide for the correct 60 milliampere resetvalue.

Minor adjustments of both shunt screws must bemade several times until the desired operating pointsare obtained, since the adjustments of one shuntscrew affect the adjustment on the other shunt screw.

7.3.2. Alarm Unit

The contacts should close with 80 milliamperes dc±5% applied to the alarm coil. Adjust the contactscrews to obtain an .050” contact gap such that thearmature motion between the left and right-hand con-tacts is in the central part of the air gap between thepole faces. Tighten the contact locking nuts. Approxi-mate adjustments of the two magnetic shunt screwsare as follows:

Turn both shunt screws all the way in. Then back outboth shunt screws approximately seven turns. Apply80 milliamperes dc to the coil, observing correctpolarity, and screw in the left-hand shunt screw untilthe armature moves to the right. If the armaturemoves to the right at a value of current less than 80milliamperes, screw the left-hand shunt out until thearmature moves to the right at 80 milliamperes.Check the dropout point by reducing the dc current.The armature should move to the left between thelimits of 40 and 60 milliamperes. If it fails to do so,adjust the right-hand shunt screw until it does. It willthen be necessary to recheck the pickup and dropoutpoints again and make any minor adjustments to theshunt screws that may be necessary until correct cal-ibration is obtained.

In general, screwing in the left-hand shunt screwreduces the pickup current of the relay. Screwing inthe right-hand shunt screw increases the dropoutcurrent. This will in turn cause a change in the pickupcurrent, making necessary several slight readjust-ments of both shunt screws to obtain the desired cal-ibration. The armature as finally calibrated shouldpickup and dropout with a snappy action.

9

Page 10: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

7.4. FOR RELAYS TO BE USED WITHKR-TYPE CARRIER OR TA-3 TONES

7.4.1. Receiver Unit

Calibrate as outlined under TC Type Carrier. Apply15 mA dc current for polarity check. The pickup valueshould be 4 milliamperes dc (armature moves to left)instead of 40 mA. The calibration of reset (armaturemoves to the right) should be done at 6 milliamperesinstead of 60 mA.

7.4.2. Alarm Unit

Calibrate as outlined under TC-type Carrier. Checkpick-up at 8 mA ±5% instead of 80 mA. Dropoutshould be between 4 and 6 mA instead of 40 and 60mA.

8.0 RENEWAL PARTS

Repair work can be done most satisfactorily at thefactory. However, interchangeable parts can be fur-nished to the customers who are equipped for doingrepair work. When ordering parts, always give thecomplete nameplate data.

9.0 ENERGY REQUIREMENTS9.1. CURRENT BURDEN AT 60 CYCLES

9.2. RATING OF OVERCURRENT UNIT

Continuous rating 5 amperes. One second rating 100amps.

Current Amperes

VoltAmperes

PowerFactorAngle

0.55

204060

2.243

39412402760

33° †

70° †

49° ††

39.2° ††

32.5° ††

† Current lagging voltage.†† Current leading voltage.

10

Page 11: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

11

THIS PAGE LEFT BLANK

Page 12: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

12

Figure 8. Typical External Schematic of a KA-4 Relay in a KD-4/TC Blocking System

Sub 45307D96

Page 13: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

13

Figure 8. Typical External Schematic of a KA-4 Relay in a KD-4/TC Blocking System

Sub 45307D96

Page 14: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

14

Figure 9A. Typical External Schematic of a KA-4 Relay in a KD-10/TC Blocking System

Page 15: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type

41-923.4M

15

Figure 9B. Typical External Schematic of a KA-4 Relay in a KD-10/TC Blocking System

Page 16: Type KA-4 Carrier Auxiliary Relay Instruction Leaflet · 41-923.4M 3 Figure 2.Internal Schematic of the Type KA-4 Relay for KR Carrier Set. Figure 3.Internal Schematic of the Type