Types of Light fittings to be adopted for various locations in an power plant
The indoor and outdoor lighting for the various areas of the power plant will be designed based on the illumination level, reflectance, and maintenance factors etc as per industrial standards.
Location Type of fitting Qty
TG machines building- high bay 400W HPSV high bay400W HPSV flood lighting
TG machine building - 00 level 70W HPSV well glass fitting
Pump house 70WHPSV well glass fitting
DM plant 70WHPSV well glass fitting
Fuel handling system 70WHPSV well glass fitting
Building 70WHPSV well glass fitting
conveyor 70WHPSV well glass fitting
Outdoor switchyard 70 /150W road light fitting or 250W HPSV flood light fitting
Outdoor fuel storage yard 1 X 400W or 2 x 400W flood light fitting mounted on flood light tower/ lighting protection tower ( 30 m high)
Control room 2 x 40W fluorescent light fitting with mirror optic type reflectors
PCC, MCC room /Switchgear room
2 x 40W trough / rail type fluorescent light fitting
Other room & miscellaneous buildings
2 x 40W trough / rail type fluorescent light fitting
Expected lighting load for plant building and outdoor /road lighting will be 50KW approximately.