typical duct takeoff

Upload: farshan296015

Post on 24-Feb-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Typical Duct Takeoff

    1/1

    Visit us on the World Wide Web at: http://www.buckleyonline.com 98312A

    To maintain Buckley's policy of continuous improvement, we reserve the right to change prices, specifications,ratings or dimensions without notice or obligation. Manufactured by Sheet Metal Union Local 17.

    PREFERRED ALTERNATE

    BELLMOUTHCONNECTION

    MODEL BMD

    MINI-BELLMOUTHCONNECTION

    MODEL M-BMD

    AIR FLOW

    DUCT

    SIZE

    HOLE

    SIZE

    MINIMUM

    DUCT

    HEIGHT

    5" 8" 9"

    6" 9" 10"

    7" 10" 11"

    8" 11" 12"

    9" 12" 13"

    10" 13" 14"

    12" 15" 16"

    14" 17" 18"

    16" 19" 20"

    DUCT

    SIZE

    HOLE

    SIZE

    MINIMUM

    DUCT

    HEIGHT

    5"

    6" 7" 8"

    7"

    8" 9" 10"

    9"

    10" 11" 12"

    12"

    14"

    16"

    OVAL-BELLMOUTHCONNECTION

    MODEL FOBMD

    STANDARD 45RECTANGULAR TO ROUND

    MODEL 3300D

    AIR FLOW

    ALTERNATE

    TAKE-OFF DETAIL

    ALTERNATE

    TAKE-OFF DETAIL

    DUCT

    SIZE

    HOLE

    SIZE

    MINIMUM

    DUCT

    HEIGHT

    5"

    6"

    7" 9" x 10-9/16" 10"

    8" 9" x 12" 10"

    9" 9" x 13-11/16" 10"

    10" 9" x 15" 10"

    12" 9" x 18" 10"

    14" 9" x 21" 10"

    16" 9" x 24" 10"

    DUCT

    SIZE

    HOLE

    SIZE

    MINIMUM

    DUCT

    HEIGHT

    5" 5" x 10" 7"

    6" 6" x 12" 8"

    7" 6" x 12" 8"

    8" 6" x 12" 8"

    9" 6" x 14" 8"

    10" 6" x 16" 8"

    12" 7" x 18" 9"

    14" 9" x 20" 11"

    16" 10" x 20" 12"

    VD

    VD VD

    VD

    Note:Alternate fittings to be used when duct height does not permit the use of the full size Bellmouth.

    Boot connection

    *98312A

    INFORM TION L D T

    TYPICAL DUCT TAKE-OFF

    MANUFACTURED BY: Buckley Associates, Inc. HANOVER, MA