Page 1: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Project Submittal Package 2018-10-25

Typical Operating Room

Sales Representative:Antec Controls by Price

MB

Consulting Engineer:Antec Controls by Price

MB

Page 2: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Nomenclature 2018-10-25

Acronym Description Acronym Description

108 8" diameter - Single body ADDL Coil access (upstream & downstream) fastened w/ snap latches

110 10" diameter - Single body ADDQ Coil access (upstream & downstream) fastened w/ quarter turn sash latch

112 12" diameter - Single body ADL Coil access (upstream) fastened w/ snap latches

114 14" diameter - Single body ADQ Coil access (upstream) fastened w/ quarter turn sash latch

210 10" diameter - Dual body AI Analog Input

212 12" diameter - Dual body AL Aluminum

214 14" diameter - Dual body AO Analog Output

312 12" diameter - Triple body BACnet Building automation and control network

314 14" diameter - Triple body BI Binary Input

412 12" diameter - Quadruple body BO Binary Output

414 14" diameter - Quadruple body BSC Biological safety cabinet

115-24V Transformer 115V supply BTN Pushbutton setpoint adjustment

120-1 120V single phase °C Degrees celcius

1L Left hand one row CC Cooling coil

1R Right hand one row CFL Companion flange

1RM Single room configuration CFM Cubic feet per minute

208-1 208V single phase CO2 Carbon dioxide sensor

208-3 208V three phase COM Common

240-1 240V single phase CRAF Cleanroom aluminum foil liner 5/8"

240-24V Transformer 240V supply CSL Heating coil shipped loose

24VAC 24VAC power connection CV Constant volume

277-1 277V single phase CVB Coil attached - Controls enclosure to bottom

277-24V Transformer 277V supply CVL Coil attached - Controls enclosure LH

2L Left hand two row CVR Coil attached - Controls enclosure RH

2P 2-Position actuator CVT Coil attached - Controls enclosure to top

2R Right hand two row DBC Drawband clamp

2RM Two room configuration DCS Door contact switch

300VA 120/24VAC 300VA transformer DCS-F Floor mount door contact switch

347-1 347V single phase DCS-S Surface mount door contact switch

3L Left hand three row DDC Direct digital control

3R Right hand three row DSF1 1 door switch - Flush mount

3RM Three room configuration DSF2 2 door switches - Flush mount

40VA 120/24VAC 40VA transformer DSF3 3 door switches - Flush mount

480-24V Transformer 480V supply DSS1 1 door switch - Surface mount

480-3 480V three phase DSS2 2 door switches - Surface mount

4L Left hand four row DSS3 3 door switches - Surface mount

4R Right hand four row DT Duct temperature sensor

4RM Four room configuration EARTH Earth ground

500VA 120/24VAC 500VA transformer EC Electric Coil

50VA 120/24VAC 50VA transformer EMCS Energy management and control system

600-3 600V three phase °F Degrees fahrenheit

6RM Six room configuration FAC Controls supplied by others - factory mounted

8RM Eight room configuration FACC Factory calibrated curve

96VA 120/24VAC 96VA transformer FCP Fail closed position

AD Coil access (upstream) fastened with screws FEV Fumehood exhaust valve

ADD Coil access (upstream & downstream) fastened w/ screws FF Fiber free foam 3/4"

Page 3: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Nomenclature 2018-10-25

Acronym Description Acronym Description

FHC Fume hood controller PTX Price pressure transducer

FHI Fume hood interface RAV Return air valve

FHN Fume hood network RDV Round duct terminal

FL Flange connection RH Relative humidity sensor

FLD Controls supplied by others - field mounted RIN Room information network

FLDC Field calibrated curve RM Room temperature sensor

FLP Fail last position RTR Bacnet MS/TP to IP router

FOP Fail open position S7 7" screen

FPI Fins per inch SAV Supply air valve

FPS Fume hood presense sensor SC Standard capacity hot water coil

FUS Main line fusing SCRV SCR control (0-10VDC)

ga Gauge SDV Square duct terminal

GEV General exhaust valve sec Seconds

GL Galvanized steel SIN Sensor information network

H Horizontal SIND Sensor information network device

HC High capacity hot water coil SL Slip connection

HSA High speed actuator SM Solid metal liner 3/4"

HWC Hot water reheat coil SPS1 One sash position sensor

HWV Modulating (0-10V) reheat valve SPS2 Two sash position sensors

I Imperial SPS3 Three sash position sensors

ID Inner diameter SRPS1 One SIN room pressure sensor

IDSW Door interlock disconnect SRPS2 Two SIN room pressure sensors

IN 3/4" external foam insulation SRPS3 Three SIN room pressure sensors

in. Inches SS316 316 stainless steel

in.w.c. Inches water column SSA Standard speed actuator

K Kynar coating SSO Standard shutoff valve

KP Keypad SWS1 1 sidewall face velocity sensor

KSW Isolation/setback keyswitch SWS2 2 sidewall face velocity sensors

LP Low pressure (0.3 to 3.0in.w.c) T# Thermistor input

M Metric TU Terminal unit

mm Millimeters VCT Valve connection companion type

MP Medium pressure (0.6 to 3.0in.w.c) VD Vertical down

MS/TP Master slave token passing VDC Modulating (0-10VDC) actuator

MVM Multi-variable monitor VFX Venturi FX damper blade

OD Outer diameter VIT Valve installation tape

OEV Other exhaust valve (eg. biosafety cabinets/ snorkels/ etc) VP Valve Pressure

OHC Oversized high capacity hot water coil VPS Valve pressure switch

OSC Oversized standard capacity hot water coil VPT Valve power transformer

P1 Phenolic coating (heresite class 1) VAV Variable air volume

P2 Phenolic coating (heresite class 2) VU Vertical up

Pa Pascals VV Venturi valve

PACE Pace™ controller VVEC Valve electric coil

PM Panel mount VVHWC Valve hot water coil

PMT Touchscreen room pressure monitor VVR Venturi valve retrofit

POT Potentiometer WEB Webserver

PT Pressure transducer (mounted on Pace™ controller)

Page 4: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

Valve and Controller Schedule

Val

ve M

od

el

Val

ve T

ag

Ro

om

Ap

plic

atio

n

Un

it S

ize

MA

X F

low

(CFM

)

MIN

Flo

w(C

FM)

MIN

Un

occ

up

ied

Flo

w(C

FM)

Ro

om

Off

set

(CFM

)

Bo

dy

Typ

e

Pre

ssu

re R

ang

e

Ori

enta

tio

n

Co

atin

g

Insu

lati

on

Co

nn

ecti

on

Typ

e

Co

ntr

ol T

ype

Co

ntr

ols

Act

uat

or

Co

ntr

ol

Act

uat

or

Res

po

nse

Act

uat

or

Fail

Po

siti

on

Acc

esso

ries

Cal

ibra

tio

n M

eth

od

VA

Req

uir

ed

No

tes

VFX SAV-OR Operating Room SAV 114 2000 2000 2000 - - - IN SL - PACE - SSA FLP - - 21 1VFX GEV-OR Operating Room GEV 114 1750 1750 1750 - - - SL - PACE - SSA FLP - - 21 1

Notes:1. Installation and wiring of equipment by Others

Page 5: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

VCT Schedule

Val

ve A

cces

sori

es M

od

el

Val

ve T

ag

Mat

ing

Val

ve S

ize

Co

nn

ecti

on

Typ

e

Mat

eria

l Typ

e

No

tes

VCT 114 DBC GL 1

Notes:1. Installation and wiring of equipment by Others

Page 6: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

ES Schedule

Ro

om

Co

ntr

ol

Acc

esso

ries

Mo

del

Val

ve T

ag

Ro

om

Nam

e

Sen

sor

Typ

e

Dis

pla

y T

ype

Dis

pla

y U

nit

s

Set

po

int

Ad

just

men

t

Rel

ativ

e H

um

idit

y

Car

bo

n D

ioxi

de

No

tes

ES SAV-OR Operating Room DT 1ES SAV-OR Operating Room RM LCD F BTN RH 1

Notes:1. Installation and wiring of equipment by Others

Page 7: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

PMT Schedule

Mo

nit

or

Mo

del

Loca

tio

n

Ro

om

Pre

ssu

re S

enso

r

Net

wo

rk In

terf

ace

Do

or

Sw

itch

Key

swit

ch

Ro

om

No

tes

PMT SRPS1 BAC Operating Room 1

Notes:1. Installation and wiring of equipment by Others

Page 8: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

MVM Schedule

Mo

nit

or

Mo

del

Ro

om

Nam

e

Scr

een

Siz

e(i

n.)

Ro

om

Co

nfi

gu

rati

on

Loca

tio

ns

No

tes

MVM Operating Room S7 1RM 1

Notes:1. Installation and wiring of equipment by Others

Page 9: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

VVHWC Schedule and Performance

Val

ve A

cces

sori

es M

od

el

Val

ve T

ag

Un

it S

ize

Hea

tin

g F

low

(CFM

)

Co

il C

apac

ity

Co

il T

ype

Flu

id T

ype

Gly

col

(%)

En

teri

ng

Air

Tem

per

atu

re(°

F)

En

teri

ng

Flu

id T

emp

erat

ure

(°F)

Leav

ing

Air

Tem

per

atu

re(°

F)

Leav

ing

Flu

id T

emp

erat

ure

(°F)

Flu

id F

low

(GP

M)

Flu

id P

ress

ure

Dro

p

(ft.

w.g

.)

Co

il C

apac

ity

(MB

H)

MA

X A

ir P

ress

ure

Dro

p

(in

. w.g

.)

Acc

ess

Do

or

Hea

tin

g C

oil

Mo

un

tin

g

No

tes

VVHWC SAV-OR 114 2000 SC 2R WTR 0.00 55.0 180.0 83.7 116.1 2.00 0.42 62.2 0.45 AD CSL 1

Notes:1. Installation and wiring of equipment by Others

Page 10: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Typical Operating Room

Schedule 2018-10-25

Sound Performance

Val

ve M

od

el

Val

ve T

ag

Un

it S

ize

MA

X F

low

(CFM

)

MIN

Flo

w(C

FM)

Pre

ssu

re R

ang

e

Sta

tic

Pre

ssu

re

(in

. w.g

.)

MIN

Dis

char

ge

So

un

d P

ow

er L

evel

s

MIN

Rad

iate

dS

ou

nd

Po

wer

Lev

els

MIN

Inle

tS

ou

nd

Po

wer

Lev

els

MA

X D

isch

arg

eS

ou

nd

Po

wer

Lev

els

MA

X R

adia

ted

So

un

d P

ow

er L

evel

s

MA

X In

let

So

un

d P

ow

er L

evel

s

No

tes

VFX SAV-OR 114 2000 2000 - 0.30 59 52 53 49 46 41 32 33 37 33 33 30 70 59 54 48 43 38 59 52 53 49 46 41 32 33 37 33 33 30 70 59 54 48 43 38 1VFX GEV-OR 114 1750 1750 - 0.30 57 51 52 48 45 40 36 32 36 32 32 23 68 57 53 46 42 37 57 51 52 48 45 40 36 32 36 32 32 23 68 57 53 46 42 37 1

Notes:1. Test obtained in accordance with AHRI Standard 880 and ASHRAE Standard 130

Page 11: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VFX-1-X

270128Rev. A

2018/11/23

© Copyright Antec Controls by PRICE 2018

Sol

id E

dge

Venturi FX Valve

Product Submittal

D -1/8" (3)

L

1.50 (38)

W L

SINGLE VALVE

DUAL VALVE

*WEIGHTS ARE ± 5lbs (2kg) DEPENDING ON OPTIONS

LOW PRESSURE TAP

HIGH PRESSURE TAP

D L WEIGHT*

in.(mm) in.(mm) lb.(kg)

8 8 (203) 23.50 (597) 19 (9)

10 10 (254) 21.75 (552) 20 (9)

12 12 (305) 27.00 (686) 22 (10)

14 14 (356) 30.00 (762) 24 (11)

UNIT SIZE

SINGLE VALVE

L H W WEIGHT*

in.(mm) in.(mm) in (mm) lb (kg)

212 27.00 (686) 13.250 (337) 26.250 (667) 40 (18)

214 30.00 (762) 15.250 (387) 30.250 (768) 45 (20)

UNIT SIZE

DUAL VALVE

H

MIN. AIRFLOW MAX AIRFLOW MIN. AIRFLOW MAX AIRFLOW

CFM (L/s) CFM (L/s) CFM (L/s) CFM (L/s)

8 80 (38) 800 (378) 212 360 (170) 3600 (1700)

10 120 (57) 1300 (614) 214 500 (236) 5000 (2360)

12 180 (85) 1800 (850)

14 250 (118) 2500 (1180)

UNIT SIZE

SINGLE VALVE DUAL VALVE

UNIT SIZE

VFX OPERATIONAL RANGE

Sheet 1 of 3

ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

VALVE BODY 14 Ga ALUMINUM

PRESSURE SENSOR 316 STAINLESS STEEL TUBES

VFX SPECIFICATIONS:

DAMPER BLADE

DAMPER SHAFTUNCOATED: ZINC PLATED STEELCOATED: 316 STAINLESS STEEL

UNCOATED: 24 Ga GALVANIZED STEEL WITH TEFLON GASKETCOATED: 22 Ga 316 STAINLESS STEEL WITH TEFLON GASKET

NOTE: SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 12: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VFX-1-X

270128Rev. A

2018/11/23

© Copyright Antec Controls by PRICE 2018

Sol

id E

dge

Venturi FX Valve

Product Submittal

FAIL IN PLACE (FLP)FAIL OPEN POSITION (FOP)FAIL CLOSED POSITION (FCP)

ACTUATOR FAIL SAFE OPTIONS

STANDARD SPEED (SSA)

ACTUATOR SPEED OPTIONS

3/4" EXTERNAL FIBER FREE FOAM INSULATION (IN)

INSULATION OPTION

PHENOLIC COATING - VALVE BODY (P1)

COATING OPTION

HIGH SPEED (HSA)

Sheet 2 of 3

GALVANIZED CONTROLS ENCLOSURE

6.26 (160)

6.15 (156)

16.00 (406)

NOTE: PLEASE REFER TO VFX MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

CONTROL ENCLOSURE

16.00 (406)

6.26 (160)

6.15 (156)

Page 13: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VFX-1-X

270128Rev. A

2018/11/23

© Copyright Antec Controls by PRICE 2018

Sol

id E

dge

Venturi FX Valve

Product Submittal

SLIP CONNECTION (SL) -VALVE SLIPPED INTO DUCT WITH 1" OVERLAP,SINGLE SIZES

SLIP END SPECIFICATIONS

O .438 (11)

FLANGED CONNECTION (FL), SINGLE SIZES

BC

OD

A

SINGLE DUCT

in. (mm)

8 Ø 8" (203)

10 Ø 10" (254)

12 Ø 12" (305)

14 Ø 14" (356)

UNIT SIZE

FLANGED END SPECIFICATIONS SINGLE VALVE

BC OD A

in. (mm) in. (mm) Degrees

8 6 Ø 9.25" (235) Ø 10" (254) 60

10 6 Ø 11.25" (286) Ø 12" (305) 60

12 6 Ø 13.25" (337) Ø 15" (381) 60

14 8 Ø 15.75" (400) Ø 17" (432) 45

UNIT SIZE

NUMBER OF BOLT HOLES

A/2

FLANGED CONNECTION (FL), DUAL SIZES FLANGED END SPECIFICATIONS, DUAL VALVES

.275 (7)

.275 (7)

FLANGE CORNER DETAIL A

X

A

A

B

Y

DUAL DUCT

in. (mm)

212 26"(660) x 13"(330)

214 30"(762) x 15"(381)

UNIT SIZE

X Y A B

in.(mm) in.(mm) in. (mm) in. (mm)

212 27.250 (692) 14.250 (362) 6.675(170) 6.850 (174)

214 31.250 (794) 16.250 (413) 7.675 (195) 7.850 (199)

UNIT SIZE

CONNECTION OPTIONS

Sheet 3 of 3

NOTE: PLEASE REFER TO VFX MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 14: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

PACE-1-X

270117Rev. E

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Pace™ - Critical Space Controller

Product Submittal

Sheet 1 of 5

VENTURI VALVE (VV)

DIMENSIONS:

AIRFLOW DEVICE TYPE:

PRESSURE SENSOR 0 to 4.0 in.w.c. (0 to 1000 Pa)

VENTURI FX (VFX) OR TERMINAL (TU)

PRESSURE SENSOR 0 to 2.0 in.w.c. (0 to 500 Pa)

PANEL MOUNTED (PM)

AIRFLOW DEVICE MOUNTED (DEFAULT)

MOUNT:

8.90 (226)

1.89 (48)

9.55 (243)

4.48 (114)

1.22 (31)

8.31 (211)

3.77 (114)

ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -22⁰F to 130⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)

INDICATORS STATUS LED

COMMUNICATION PROTOCOL BACNET MS/TP

HOUSING UL 94 V-0, PC-ABS PLASTIC

RATED IMPULSE VOLTAGE 330 V (AFTER TRANSFORMER)

OUTPUTS2 ACTIVE BINARY OUTPUTS (24 VAC, MAX: 500 mA),4 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA)

PACE SPECIFICATIONS:

INPUTS

2 BINARY INPUTS (CONTACT CLOSURE),4 ANALOG INPUTS (0 to 10 VDC), 2 10K TYPE 2 THERMISTORS INPUTS, ROOM INFORMATION NETWORK,SENSOR INFORMATION NETWORK,2 POT INPUTS2 RS485 NETWORK (FHN, BACNET)1 TRANSDUCER (VV: 0-4 in.w .c., VFX: 0-2 in.w .c.)

INPUT POWER24 VAC, 50/60 Hz SINGLE PHASE, 75 VA MAX (18 VA EXCLUDING EXTERNAL LOADS), CLASS 2 or LPS PELV

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 15: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

PACE-1-X

270117Rev. E

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Pace™ - Critical Space Controller

Product Submittal

Sheet 2 of 5

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Object Name Units Range Description Write Setting

AI#1 [Pace name] AI1 – [AI1 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the PACE manual for options

R

AI#2 [Pace name] AI2 – [AI2 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the PACE manual for options

R

AI#3 [Pace name] AI3 – [AI3 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the PACE manual for options

R

AI#4 [Pace name] AI4 – [AI4 Device name] Dynamic DynamicAnalog Input w ith multiple usesSee Input section of the PACE manual for options

R

AI#5 [Pace name] T1 – [T1 Device name] °F or °C 0 to 150 °F Thermistor reading R

AI#6 [Pace name] T2 – [T2 Device name] °F or °C 0 to 150 °F Thermistor reading R

BI#1 [Pace name] BI1 – [BI1 Device name] Open/Closed Open/ClosedBinary Input w ith multiple usesSee Input section of the PACE manual for options

R

BI#2 [Pace name] BI2 – [BI2 Device name] Open/Closed Open/ClosedBinary Input w ith multiple usesSee Input section of the PACE manual for options

R

AO#1 [Pace name] AO1 – [AO1 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the PACE manual for options

R/W

AO#2 [Pace name] AO2 – [AO2 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the PACE manual for options

R/W

AO#3 [Pace name] AO3 – [AO3 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the PACE manual for options

R/W

AO#4 [Pace name] AO4 – [AO4 Device name] VDC 0 to 10Analog Output w ith multiple usesSee Output section of the PACE manual for options

R/W

BO#1 [Pace name] BO1 – [BO1 Device name] Active/Inactive Active/InactiveBinary Output w ith multiple usesSee Output section of the PACE manual for options

R/W

BO#2 [Pace name] BO2 – [BO2 Device name] Active/Inactive Active/InactiveBinary Output w ith multiple usesSee Output section of the PACE manual for options

R/W

AV1 Room Pressure Setpoint in.w .c.; Pa-0.100 to

0.100 in.w .c.Current room pressure setpointHidden when pressure control not used

R/W

AV2 Room Pressure in.w .c.; Pa-0.100 to

0.100 in.w .c.Current room pressure R

AV3 Room Pressure Low Alarm in.w .c.; Pa-0.100 to

0.100 in.w .c.Low room pressure alarm setpoint (+/-) R/W

AV4 Room Pressure High Alarm in.w .c.; Pa-0.100 to

0.100 in.w .c.High room pressure alarm setpoint (+/-) R/W

AV5 Airf low Offset Setpoint CFM; L/s-10000 to

10000 CFMCurrent airf low offset setpointHidden when offset control not used

R/W

Note: Analog output AO1 will display as AO11 for Pace™ Controller 1, AO21 for Pace™ Controller 2, etc…

Note: Analog output BO1 will display as BO11 for Pace™ Controller 1, BO21 for Pace™ Controller 2, etc…

ANALOG VALUE

BINARY OUTPUTS

BACNET POINTS LIST v1.0.X

BINARY INPUTS

ANALOG OUTPUTS

ANALOG INPUTS

Note: Analog input AI1 will display as AI11 for Pace™ Controller 1, AI21 for Pace™ Controller 2, etc…

Note: Binary input BI1 will display as BI11 for Pace™ Controller 1, BI21 for Pace™ Controller 2, etc…

Page 16: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

PACE-1-X

270117Rev. E

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Pace™ - Critical Space Controller

Product Submittal

Name Units Range Description Write Setting

AV6 Airflow Offset Actual CFM; L/s -10000 to 10000 CFMCurrent airf low offset (+/-) R/W

AV7 Total Exhaust Airf low Target CFM; L/s 0 to 10000 CFM Total room exhaust airf low target R

AV8 Total Exhaust Airf low Actual CFM; L/s 0 to 10000 CFM Total room exhaust airf low R

AV9 Total Supply Airf low Target CFM; L/s 0 to 10000 CFM Total room supply airf low target R

AV10 Total Supply Airf low Actual CFM; L/s 0 to 10000 CFM Total room supply airf low R

AV11 Total Fume Hood Exhaust CFM; L/s 0 to 10000 CFMTotal fume hood exhaust airf lowHidden if no fume hoods connected

R

AV12 Room Volume ft3 0 to 32767 Room volume R/W

AV13 Current Air Change Rate # 0.0 to 100.0 Current air change rate R

AV14 Temperature Setpoint - Zone 1 °F;°C 0 to 150 °F Temperature setpoint in zone 1 R/W

AV15 Temperature Reading - Zone 1 °F;°C 0 to 150 °F Current temperature in zone 1 R

AV16 Temperature Setpoint - Zone 2 °F;°C 0 to 150 °FTemperature setpoint in zone 2Hidden if multiple zones have not been configured

R/W

AV17 Temperature Reading - Zone 2 °F;°C 0 to 150 °FCurrent temperature in zone 2Hidden if multiple zones have not been configured

R

AV18 Temperature Setpoint - Zone 3 °F;°C 0 to 150 °FTemperature setpoint in Zone 3Hidden if multiple zones have not been configured

R/W

AV19 Temperature Reading - Zone 3 °F;°C 0 to 150 °FCurrent Temperature in zone 3Hidden if multiple zones have not been configured

R

AV20 Room Temperature Setpoint - Low Limit °F;°C 0 to 150 °F Low est user-adjustable temperature setpoint on the Thermostat R/W

AV21 Room Temperature Setpoint - High Limit °F;°C 0 to 150 °F Highest user-adjustable temperature setpoint on the Thermostat R/W

AV22 DAT Low Limit °F;°C 0 to 200 °FDischarge air temperature low temperature limitHidden if DAT Limits are not enabled

R/W

AV23 DAT High Limit °F; °C 0 to 200 °FDischarge air temperature high temperature limit Hidden if DAT Limits are not enabled

R/W

AV24 Single Airf low Setpoint CFM; L/s 0 to 10000 CFMSingle airf low setpointHidden if single airflow control not used

R/W

AV25 Single Airf low Actual CFM; L/s 0 to 10000 CFMSingle airf low Hidden if single airflow control not used

R/W

AV#01 [Pace name] f low - [POT1 Device name] CFM; L/s 0 to 10000 CFMPOT1 airf low readingHidden when POT1 is not used

R

AV#02 [Pace name] f low - [POT2 Device name] CFM; L/s 0 to 10000 CFMPOT2 airf low readingHidden when POT2 is not used

R

BACNET POINTS LIST v1.0.X (CONTINUED)

Object

Note: Analog value AV#01 will display as AV101 for Pace™ Controller 1, AV201 for Pace™ Controller 2, etc…

ANALOG VALUE

Sheet 3 of 5

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 17: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

PACE-1-X

270117Rev. E

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Pace™ - Critical Space Controller

Product Submittal

Sheet 4 of 5

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Object Name Units Range Description Write Setting

AV#03 [Pace name] - Valve Pressure in.w .c.; Pa 0 to 5 in.w .c.Valve PressureHidden when device type is not VV

R

AV#04[Pace name] f low - [Transducer Device name]

CFM; L/s 0 to 10000 CFMTransducer airf low readingHidden when airflow source is not transducer

R

AV#11 Fume Hood # Airf low CFM; L/s 0 to 10000 CFMDisplays the current airf low being exhausted from the fume hood

R

AV#12 Fume Hood # Face Velocity FPM; m/s 0 to 250 FPMDisplays the current face velocity across the fume hood

R

AV#13 Fume Hood # Sash Position % 0 to 100Displays the current position of the sash on the fume hood

R

AV#14 Fume Hood # Valve Pressure in.w .c.; Pa 0 to 5 in.w .c.Displays the current pressure across the valve on the fume hood

R

MV1 Airf low Control Sequence Text 3 states

Displays the current airf low control sequence1 - Constant Flow Control2 - Pressure Control3 - Offset Control

R

MV2 Room Pressure Mode Text 2 statesDisplays the current room pressure mode1 - Positive2 - Negative

R

MV3 Room Alarm Status Text 13 states

Displays the current room alarm status1 - Diversity2 - Binary Input3 - Missing Room Pressure Sensor4 - Mode Alarm5 - Room Low Pressure6 - Room High Pressure 7 - Door Open8 - Low Airf low9 - Low Valve Pressure10 - High Airf low11 - High Valve Pressure12 - Controller Not Responding13 - No Alarm

R

MV4 Room Mode Text 6 states

Displays the current room mode1 - [Default Room Mode Name]2 - [Custom Room Mode 1 Name]3 - [Custom Room Mode 2 Name]4 - [Custom Room Mode 3 Name]5 - [Custom Room Mode 4 Name]6 - [Custom Room Mode 5 Name]

R/W

MV99 Firmw are Update Status Text 4 states

Displays the current f irmw are update status1 - Idle2 - Start Firmw are Update3 - Updating Firmw are4 - Firmw are Update Failed

R/W

MULTISTATE VALUE

BACNET POINTS LIST v1.0.X (CONTINUED)

Note: Analog value AV#11 will display as AV111 for Fume Hood Controller (FHC) 1, AV211 for Fume Hood Controller (FHC) 2, etc…

Note: Analog value AV#01 will display as AV101 for Pace™ Controller 1, AV201 for Pace™ Controller 2, etc…

Page 18: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

PACE-1-X

270117Rev. E

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Pace™ - Critical Space Controller

Product Submittal

Name Units Range Description Write Setting

MV#1 Fume Hood # Status Text 6 states

Displays the status of the fume hoods1 - Missing FHC2 - Normal3 - Caution4 - Alarm5 - Setback6 - Off

R

MV#2 Fume Hood # Error Type Text 21 states

Displays the cause of any alarms or cautions on the fume hoods1 - No Error2 - Emergency3 - Netw ork4 - Contact Input5 - No Primary Sensor6 - No Sec. Sensor7 - No Sash18 - No Sash29 - No Sash 310 - Low Velocity11 - High Velocity12 - Low Pressure13 - High Pressure14 - Venturi Out of Range15 - Sash Height16 - Low Airflow17 - High Airf low18 - Sash Broken19 - BI120 - BI221 - Setback Sash Height

R

FIL1 Firmw are - -The f ile object used for f irmw are upgrades - feature only available if supported by BAS

W

Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…

BACNET POINTS LIST v1.0.X (CONTINUED)

Object

MULTISTATE VALUE

FILE

Sheet 5 of 5

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 19: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VCT-1-X

270214Rev. A

2018/11/23

© Copyright Antec Controls by PRICE 2018

Sol

id E

dge

Venturi Companion Connection Type

Product Submittal

Sheet 1 of 1

BAND 3.5in. WIDTH, 24 Ga GALVANIZED STEEL

FOAM 0.25in., UL 94, ELASTOMERIC

HARDWARE BOLT AND LOCK NUTS

VALVE COMPANION SIZES 108, 110, 112, 114

VALVE COMPANION TYPE SLIP

DBC SPECIFICATIONS:

ALUMINUM (AL)

316 STAINLESS STEEL (SS)

COMPANION FLANGE MATERIAL OPTIONS:

DRAWBAND CLAMP (DBC)

MATERIAL SEE MATERIAL OPTIONS BELOW

HARDWARE NOT INCLUDED

VALVE COMPANION SIZES 108, 110, 112, 114

VALVE COMPANION TYPE SLIP

CFL SPECIFICATIONS:

COMPANION FLANGE (CFL)

DIMENSIONS:

O .438 (11)

BC

OD

A

A/2

IDBC OD A

ID(MAX DUCT OD)

in. (mm) in. (mm) Degrees in. (mm)

8 6 Ø 9.25" (235) Ø 10" (254) 60 Ø 8.25" (210)

10 6 Ø 11.25" (286) Ø 12" (305) 60 Ø 10.25" (260)

12 6 Ø 13.25" (337) Ø 15" (381) 60 Ø 12.25" (311)

14 8 Ø 15.75" (400) Ø 17" (432) 45 Ø 14.25" (362)

UNIT SIZE

NUMBER OF BOLT HOLES

NOTE: PLEASE REFER TO VV MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 20: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VVHWC-1-X

270129Rev. A

2018/12/27

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Valve Hot Water Coil

Product Submittal

Sheet 1 of 4

7. ALLOW 1 1/2 " (38) MINIMUM CLEARANCE FOR INSTALLATION AT THIS END.

6. HAND OF HOT WATER COIL CONNECTIONS IS DETERMINED WHEN VIEWED FROM AIR INLET SIDE.

1. FABRICATED FROM 22 GA. GALVANIZED STEEL, MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.NOTES:

4" x 6 3/4" (102 x 171)

BEAD-IN

2. HOT WATER COILS HAVE COPPER TUBES AND ALUMINUM FINS WITH O.D. SWEAT CONNECTIONS.

3. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE FOR AIR VOLUMES AND HOT WATER COIL CAPACITIES.

4. METHOD OF VENTING HOT WATER COIL IS TO BE PROVIDED BY INSTALLING CONTRACTOR.

5. ACCESS DOORS WITH GASKETED PERIMETER FOR INSPECTION AND MAINTENANCE OF COIL, TOP & BOTTOM.

8. CONFIGURATION OF COIL CONNECTION VARIES WITH SIZE & CIRCUITRY OF COIL.

9. PERFORMANCE RATED AND CERTIFIED IN ACCORDANCE WITH THE CURRENT EDITION OF ARI STANDARD 410.

10. IT IS NOT RECOMENDED TO REVERSE 3 & 4 ROW COILS. INDICATE HANDING WHILE ORDERING.

11. STANDARD COILS SUPPLIED WITH 10 FINS PER INCH / HIGH CAPACITY COILS SUPPLIED WITH 12 FINS PER INCH.

INLET, ØA

12. HIGH CAPACITY ONLY AVAILABLE FOR 1 AND 2 ROW COILS.

STANDARD HOT WATER COIL SPECIFICATIONS

NOTE: WEIGHTS ARE ±3lb (1.5kg)

8 7/8(225)

11 3/8(289)

13 7/8(352)

16 3/8(416)16 3/8(416)

13 3/4(349)

11 1/4(286)

8 3/4(222)

1 ROW HC,STD

1 ROW2,3,4 ROW

D

7/8(22)

7/8(22)

7/8(22)

10

12

8

16(406)

14(356)

12(305)

7/8(22)

15(381)

12 1/2(318)

10(254) 1/2(13)

2,3,4 ROW

COIL CONNECTIONS

IMPERIAL UNITS (SI UNITS), in(mm)NOMINAL

SIZE A B 1 ROWC

17 1/2(445)20(508)14

STD HC

1 ROW

23(10 1/2)19(8 1/2)

19(8 1/2)

9(4)

14(6 1/2)

11(5)

11(5)

14(6 1/2)

8 1/2(4)

27(12 1/2)

20(9)

17 (8)

4 ROW

23(10 1/2)

3 ROW

13(6)

16(7 1/2)10

12

8 6 1/2(3)

COIL WEIGHT lb(kg)NOMINAL

SIZE A1 ROW

14

2 ROW

3 ROW

19(8 1/2)

16(7 1/2)

2 ROW

19(8 1/2)

14(6 1/2)

11(5)

23(10 1/2)

COIL WEIGHT lb(kg)

NOTE: WEIGHTS ARE ±3lb (1.5kg)

23(10 1/2)

27(12 1/2)

20(9)

4 ROW

34(15 1/2)22(10) 31(14)

1 ROW

11(5)

8 1/2(4)

10

12

NOMINAL

SIZE A

8

14

14(6 1/2)

16(7 1/2)

D

1 ROW

13 3/4(349)

11 1/4(286)

STD1 ROW HC,2,3,4 ROW

1 ROW

COIL CONNECTIONS

1 ROW

HCSTDINLET ØAC

10(254)

8(203)

14(356)

12(305)

15(381)

12 1/2(318)

17 1/2(445)

18(457)

BCOIL SIZE

WATER

16(406)

14(356)

20(508)

24(610)

12

10

14

212

10

12

8

VENTURI

SIZE

14

2,3,4 ROW

IMPERIAL UNITS (SI UNITS), in(mm)

OVERSIZED HOT WATER COIL SPECIFICATIONS

FOR TOTAL LENGTH OF UNIT WITHADD 10 7/8"(276) LENGTH OF SECOND ADAPTERNOTE: CONFIGURATION WITH SINGLE ADAPTER SHOWN.

UPSTREAM AND DOWNSTREAM ADAPTERS.

LH WATER COILCONNECTIONS

CO

IL A

DA

PT

ER

SE

CT

ION

TOP & BOTTOM ACCESS DOOR

SLIP & DRIVECONNECTION

RH WATER COILCONNECTIONS

B

C D O A

5"(127) FOR 1, 2 ROW OR7 1/4"(184) FOR 3, 4 ROW

8"(203)

NOTE: PLEASE REFER TO VV MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

1/2(13)

1/2(13)

1/2(13)

1/2(13)

7/8(22)

7/8(22)

7/8(22)

7/8(22)

7/8(22)

7/8(22)

7/8(22)

1/2(13)

1/2(13)

1/2(13)

7/8(22)

7/8(22)

7/8(22)

7/8(22)

7/8(22)

11 3/8(289)

13 7/8(352)

16 3/8(416)

16 3/8(416)

16 3/8(416)

16 3/8(416)

WATER COILSECTION

VVHWC, B x C

10 7/8"(276)O1/2"(13) @ 3"(76)O7/8"(22) @ 4 1/4(108)

SEE NOTE #7

1"(25)

Page 21: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VVHWC-1-X

270129Rev. A

2018/12/27

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Valve Hot Water Coil

Product Submittal

Sheet 3 of 4

NOTE: PLEASE REFER TO VV MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

VENTURI VALVE WITH STANDARD CAPACITY (SC) HWC

VENTURI VALVE WITH OVERSIZED STANDARD CAPACITY (OSC) HWC

VENTURI VALVE WITH HIGH CAPACITY (HC) HWC. ONLY 1 & 2 ROW HC COILS AVAILABLE

VENTURI VALVE WITH OVERSIZED HIGH CAPACITY (OHC) HWC. ONLY 1 & 2 ROW HC COILS AVAILABLE

AIRFLOW

CONTROL ENCLOSURE ORIENTATION OPTIONS:

RIGHT HAND (R) HWC / CONTROL DOWN (CVB)

RIGHT HAND (R) HWC / CONTROL UP (CVT)

RIGHT HAND (R) HWC / CONTROL LH (CVL)

RIGHT HAND (R) HWC / CONTROL RH (CVR)

RH

WA

TE

R C

OIL

RH

WA

TE

R C

OIL

LEFT HAND (L) HWC / CONTROL RH (CVR)

LEFT HAND (L) HWC / CONTROL LH (CVL)

LEFT HAND (L) HWC / CONTROL UP (CVT)

LEFT HAND (L) HWC / CONTROL DOWN (CVB)

TOP VIEW

TOP VIEW

UNLESS OTHERWISE SPECIFIED.

NOTE: COIL SHIPPED LOOSE FROM VALVE (CSL)

TOP VIEW

RH

WA

TE

R C

OIL

TOP VIEW

CONTROL ENCLOSURE ORIENTATION OPTIONS:

RIGHT HAND (R) HWC / CONTROL DOWN (CVB)

RIGHT HAND (R) HWC / CONTROL UP (CVT)

RH

WA

TE

R C

OIL

LEFT HAND (L) HWC / CONTROL UP (CVT)

LEFT HAND (L) HWC / CONTROL DOWN (CVB)

AIRFLOW

NOTE: OVERSIZED WATER COIL OPTION UTILIZES AN ADAPTER ONE SIZE LARGER THAN STANDARD VENTURI UNIT.

SINGLE VALVE, CONTROLS & WC ADAPTOR CONFIGURATIONS

OPTIONS:

MULTIBODY VALVE, CONTROLS & WC ADAPTOR CONFIGURATIONS

AIRFLOW

OPTIONALCONTROLS ENCLOSURE

SLIP & DRIVECONNECTION

SLIP & DRIVECONNECTION

OPTIONALSILENCERCONTROL UP

SHOWN

UNLESS OTHERWISE SPECIFIED.

NOTE: COIL SHIPPED LOOSE FROM VALVE (CSL)

OPTIONALCONTROLS ENCLOSURE

AIRFLOW OPTIONALSILENCER

SLIP&DRIVECONNECTION

OPTIONALCONTROLS ENCLOSURE

CONTROL UP SHOWN

CONTROL UP SHOWN

CONTROL UP SHOWN

OPTIONALCONTROLS ENCLOSURE

Page 22: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

VVHWC-1-X

270129Rev. A

2018/12/27

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Valve Hot Water Coil

Product Submittal

4" x 6 3/4"

WATER COILCONNECTIONS

WATER COIL AND SINGLE VALVE ADAPTOR CONFIGURATION OPTIONS

WA

TE

R C

OIL

WA

TE

R C

OIL

ADDQ - COIL ACCESS DOORW/QUARTER TURN SASH LATCHES4"(102) x 6 3/4"(171)

ADD - COIL ACCESS DOORW/SCREWS4"(102) x 6 3/4"(171)

ADDL - COIL ACCESS DOORW/SNAP LATCHES4"(102) x 6 3/4"(171)

ADQ - COIL ACCESS DOORW/QUARTER TURN SASH LATCHES4"(102) x 6 3/4"(171)

AD - COIL ACCESS DOORW/SCREWS4"(102) x 6 3/4"(171)

ADL - COIL ACCESS DOORW/SNAP LATCHES4"(102) x 6 3/4"(171)

UPSTREAMADAPTOR

UPSTREAMADAPTOR DOWNSTREAM

ADAPTOR

WATER COIL AND MULTI- VALVE ADAPTOR CONFIGURATION OPTIONS

SLIP & DRIVECONNECTION

WA

TE

R C

OIL

CONNECTIONSLIP & DRIVEWATER COIL

CONNECTIONS

WATER COILCONNECTIONS

UPSTREAMTRANSITION

UPSTREAMTRANSITION

DOWNSTREAMTRANSITION

WA

TE

R C

OIL

Sheet 4 of 4

NOTE: PLEASE REFER TO VV MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

COIL ACCESS DOOR (102 x 171),TOP & BOTTOM,NOT INSULATED

4" x 6 3/4"COIL ACCESS DOOR (102 x 171), TOP & BOTTOM, NOT INSULATED

AIRFLOWAIRFLOW

ADDQ - COIL ACCESS DOORW/QUARTER TURN SASH LATCHES4"(102) x 6 3/4"(171)

ADD - COIL ACCESS DOORW/SCREWS4"(102) x 6 3/4"(171)

ADDL - COIL ACCESS DOORW/SNAP LATCHES4"(102) x 6 3/4"(171)

ADQ - COIL ACCESS DOORW/QUARTER TURN SASH LATCHES4"(102) x 6 3/4"(171)

AD - COIL ACCESS DOORW/SCREWS4"(102) x 6 3/4"(171)

ADL - COIL ACCESS DOORW/SNAP LATCHES4"(102) x 6 3/4"(171)

AIRFLOWAIRFLOW

4" x 6 3/4"COIL ACCESS DOOR (102 x 171),TOP & BOTTOM,NOT INSULATED 4" x 6 3/4"

COIL ACCESS DOOR (102 x 171),TOP & BOTTOM,NOT INSULATED

WATER COILCONNECTIONS

Page 23: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

ES-1-X

270215Rev. C

2019/01/11

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Environmental Sensor

Product Submittal

DIMENSIONS:

ROOM TEMPERATURE SENSOR (RM) WITH DISPLAY (LCD),PUSHBUTTON SETPOINT ADJUSTMENT (BTN) AND RELATIVE HUMIDITY SENSOR (RH)

3.38 (86)

5.0 (127) 3.28 (83) MAX

CLOSED CELL FOAM

COMMUNICATION PORT:

Sheet 5 of 9

RJ-45

CKJ-B - PUSHDOWN CONNECTIONTO PACE CONTROLLERWHERE APPLICABLE

WALLMOUNT PLATE

WALLMOUNT PLATEFACE PLATE

2.8 (71) MIN

TERMINATION:

5VDC24VDC/VAC

TEMP

COM

GNDV+

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

OUT2OUT2OUT1

OUT4OUT3

TEMP+--

V + INPUT POWER, HOT

GND INPUT POWER, GROUND

TEM P +

TEM P -

OUT 1 TEM PERATURE SETPOINT OUTPUT

OUT 2 RELATIVE HUM IDITY OUTPUT

THERM ISTOR RESISTANCE OUTPUT

ENVIRONMENTAL (OPERATING) 32⁰F to 122⁰F (0⁰C to 50⁰C), 0 to 95% R.H.(NON-CONDENSING)

DISPLAY LCD SCREEN

INPUT TYPE KEYPAD

TEMPERATURE READING 10K-2 THERMISTOR

HUMIDITY READING CAPACITIVE POLYMER, ±2% RH @ 77⁰F (25⁰C), 20 to 80% RH

HOUSING UL 94 V-0, ABS PLASTIC

COMMUNICATION PORT RJ-45

ES-RM-LCD-BTN-RH SPECIFICATIONS:

MOUNTSTANDARD 2in. x 4in. (51mm x 102mm) J-BOX orDRYWALL MOUNT

OUTPUTS2 ANALOG (0 to 10 VDC): TEMPERATURE SETPOINT - RANGE: 50⁰F to 90⁰F (10⁰C to 32⁰C) HUMIDITY OUTPUT - RANGE: 0 to 100% RH

INPUT POWER15 to 40 VDC or 15 to 28 VAC. (DO NOT RUN AC POWER IN THESAME CONDUIT AS SIGNAL WIRES)

°F/C

DISPLAY SWITCH (vF or vC)

Page 24: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

ES-1-X

270215Rev. C

2019/01/11

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Environmental Sensor

Product Submittal

DIMENSIONS:

DUCT MOUNTED SENSOR (DT)

ENVIRONMENTAL (OPERATING) -40⁰F to 185⁰F (-4⁰C to 85⁰C), 0 to 95% R.H.(NON-CONDENSING)

TEMPERATURE READING 10K TYPE 2 THERMISTOR

PROBE 304 STAINLESS STEEL PROBE, 0.25in. (7mm) DIAMETER, 8in. (203mm) LENGTH

HOUSING PC PLASTIC, UL 94 V-0, IP10, NEMA1

ES-DT SPECIFICATIONS:

2.1 (53)

3.0 (76)

9.5 (241)

8.0 (203)

Sheet 8 of 9

.25O (6)

2.67 (68)

1.78 (45)

TERMINATION:

YELLOW

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

YELLOW

YELLOWTHERM ISTOR RESISTANCE OUTPUT

YELLOW

Page 25: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

PMT-1-X

270120Rev. C

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Touchscreen Room Pressure Monitor

Product Submittal

ENVIRONMENTAL (OPERATING) 50⁰F to 95⁰F (10⁰C to 35⁰C), 0% to 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 34 VA (EXTERNAL LOADS NOT INCLUDED), CLASS 2

INPUTS 1 BINARY INPUT, 1 BINARY/ANALOG INPUT, 1 SENSOR INFORMATION NETWORK INPUT

OUTPUTS 2 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA), 1 DRY BINARY OUTPUT (MAX: 24 VAC/VDC, 100 mA)

DISPLAY TYPE CAPACITIVE TOUCH, 4.3in.(109mm) TFT/IPS, DIMMABLE

RESOLUTION WVGA RGB 480px x 800px

COMMUNICATION PROTOCOL BACNET MS/TP

MONITOR SPECIFICATIONS:

NOTE: PLEASE REFER TO PMT MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Sheet 1 of 5

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

PMT

DIMENSIONS:

3.65 (93)

5.0 (127)

1.34 (34)

.84 (21)

ROOM PRESSURE SENSORS:

ONE SIN ROOM PRESSURE SENSOR (SRPS1)

TWO SIN ROOM PRESSURE SENSORS (SRPS2)

THREE SIN ROOM PRESSURE SENSORS (SRPS3)

INPUT POWER POWERED FROM PMT

RANGE +/- 0.1 in.w .c. (+/- 25 Pa)

ACCURACY 3% OF READING

PRESSURE TUBING 24"(588mm) LONG, BLACK, FIRE-RATED

FACE PLATE ABS PLASTIC, WHITE

ROOM PRESSURE SENSOR (SRPS) SPECIFICATIONS:

ENVIRONMENTAL (OPERATING)50⁰F TO 95⁰F (10⁰C TO 35⁰C) 0% TO 95% R.H.(NON-CONDENSING)

ENVIRONMENTAL (STORAGE)-22⁰F TO 122⁰F (-30⁰C TO 50⁰C) 0% TO 95% R.H.(NON-CONDENSING)

2.8 (71) MIN3.58 (91) MAX

Page 26: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

PMT-1-X

270120Rev. C

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Touchscreen Room Pressure Monitor

Product Submittal

TERMINATION:

BO

CI

CI B

I

CO

M

AO

2

HO

T

CO

M

AO

1

Net

CO

M

+ -- Vbu

s

D D

+ --

Vco

m

BACNet S.I.N.

CONTACTCLOSURE

Sheet 2 of 5

HOT INPUT POWER, HOT

COM INPUT POWER, GROUND

AO1 ANALOG OUTPUT

AO2 ANALOG OUTPUT

BI

COM

CI +

CI -

Vbus S.I.N. POWER

Vcom S.I.N. GROUND

D + S.I.N. NET +

D - S.I.N. NET -

+ BACNet NET +

- BACNet NET -

Net COM BACNet NET COM

CONFIGURABLE INPUT

BINARY INPUT

DRY CONTACTBINARY OUTPUT

BO

NOTE: PLEASE REFER TO PMT MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

CONFIG.INPUT

BINARYINPUT

ANALOGOUTPUTS

24VAC

+ --

2.75 (70)

4.50 (114)

.25 (6)

2.10 (53)

3.56 (90)

2.36 (60)

SRPS FACEPLATE

3.91 (99)

.83 (21)

3.25 (83)

3.0 (76)DINRAIL

.7 (18)

DIMENSIONS (CONTINUED):

Page 27: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

PMT-1-X

270120Rev. C

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Touchscreen Room Pressure Monitor

Product Submittal

NOTE: UNITS IN TABLE ARE SHOWN IN IMPERIAL. THE UNITS WILL CONVERT TO METRIC WITH CORRESPONDING RANGES IF METRIC UNITS ARE SELECTED IN THE USER PREFERENCE MENU.

Sheet 3 of 5

Disabled Standard Open

Room Pressure 1 in.w .c. / Pa -0.1 to +0.1Pressure reading of the monitored room using SRPS1

R R R

Room Pressure 2 in.w .c. / Pa -0.1 to +0.1Pressure reading of the monitored room using SRPS2 (Only available w hen SRPS2 connected)

R R R

Room Pressure 3 in.w .c. / Pa -0.1 to +0.1Pressure reading of the monitored room using SRPS3 (Only available w hen SRPS3 connected)

R R R

BI1 Binary Input 1 - [usage] - Open / ClosedThe Binary Input can be configured to several types of input signals. See Input section of PMT manual for options

R R R

MI1Configurable Input 1 -

[usage]Based on

usage

2 or 3 Statesbased on

usage

The Configurable Input can be configured to several types of input signals. See Input section of PMT manual for options

R R R

Analog Output 1 VDC 0-10

Analog Output 1 can be configured to provide VDC output for several different values. See Output section of PMT manual for options

R W W

Analog Output 2 VDC 0-10

Analog Output 2 can be configured to provide VDC output for several different values. See Output section of PMT manual for options

R W W

Binary Output 1 - On / Off

Binary Output 1 can be configured to provide 24VAC output for several different values. See Output section of PMT manual for options

R W W

Room Low Pressure Alarm 1

in.w .c. / Pa0 to AV2 or

AV2 to 0

Alarm trip point of Low Pressure Alarm for the room using SRPS1(Value w ill change sign if the room isconfigured for a Negative or Positive mode)

R R W

Room High Pressure Alarm 1

in.w .c. / PaAV1 to 0.1or 0 to AV1

Alarm trip point of High Pressure Alarm for the room using SRPS1(Value w ill change sign if the room isconfigured for a Negative or Positive mode)

R R W

Room Low Pressure Alarm 2

in.w .c. / Pa0 to AV4 or

AV4 to 0

Alarm trip point of Low Pressure Alarm for the room using SRPS2(Value w ill change sign if the room isconfigured for a Negative or Positive mode)

R R W

AV1

AV2

AV3

MULTISTATE INPUTS

BO1

ANALOG VALUE

BINARY OUTPUTS

BACNET POINTS LIST v2.2.X

BINARY INPUTS

ANALOG OUTPUTS

AO1

AO2

ANALOG INPUTS

AI1

AI2

AI3

Object Name Units Range Description

Write Settings

Page 28: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

PMT-1-X

270120Rev. C

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Touchscreen Room Pressure Monitor

Product Submittal

NOTE: UNITS IN TABLE ARE SHOWN IN IMPERIAL. THE UNITS WILL CONVERT TO METRIC WITH CORRESPONDING RANGES IF METRIC UNITS ARE SELECTED IN THE USER PREFERENCE MENU.

Sheet 4 of 5

Disabled Standard Open

Room High Pressure Alarm 2

in.w .c. / PaAV3 to 0.1or 0 to AV3

Alarm trip point of High Pressure Alarm for the room using SRPS2(Value w ill change sign if the room isconfigured for a Negative or Positive mode)

R R W

Room Low Pressure Alarm 3

in.w .c. / Pa0 to AV6 or

AV6 to 0

Alarm trip point of Low Pressure Alarm for the room using SRPS3(Value w ill change sign if the room isconfigured for a Negative or Positive mode)

R R W

Room High Pressure Alarm 3

in.w .c. / PaAV5 to 0.1or 0 to AV5

Alarm trip point of High Pressure Alarm for the room using SRPS3(Value w ill change sign if the room isconfigured for a Negative or Positive mode)

R R W

Displays the current status of all rooms. (Value w ill change sign if any room changes status)1 - Normal2 - Caution3 - Alarm4 - Setback

Indicates w hether the PMT has beenoverride to a specif ic mode

1 – No Override2 – Force Isolation3 – Force Caution4 – Force Alarm5 – Force Setback

Indicates the isolation mode of roomusing SRPS1

1 - Positive2 - Negative

Object Name Units Range Description

Write Settings

Room 3 Air Change Rate readingfrom other BACnet device

R R RAV15 Room 3 Air Change Rate - BACnet A.C.H. 0 - 100

Room 3 Temperature readingfrom other BACnet device

R R R

AV14 Room 3 Relative Humidity - BACnet % R.H. 0 - 100Room 3 Relative Humidity readingfrom other BACnet device

R R R

AV13 Room 3 Temperature - BACnet ºF / ºC 0 - 200

Room 2 Relative Humidity readingfrom other BACnet device

R R R

AV12 Room 2 Air Change Rate - BACnet A.C.H. 0 - 100Room 2 Air Change Rate readingfrom other BACnet device

R R R

AV11 Room 2 Relative Humidity - BACnet % R.H. 0 - 100

AV10 Room 2 Temperature - BACnet ºF / ºC 0 - 200Room 2 Temperature readingfrom other BACnet device

R R R

AV7 Room 1 Temperature - BACnet ºF / ºC 0 - 200

Room 1 Air Change Rate readingfrom other BACnet device

R R RAV9 Room 1 Air Change Rate - BACnet A.C.H. 0 - 100

AV8 Room 1 Relative Humidity - BACnet % R.H. 0 - 100Room 1 Relative Humidity readingfrom other BACnet device

R R R

AV5

AV6

MULTISTATE VALUES

R R WMV2 Status Override Text 5 States

MV1 Status Text 4 States R R R

Room 1 Temperature readingfrom other BACnet device

R R

MV3 Room Isolation Mode 1 Text 2 states R R W

AV4

BACNET POINTS LIST v2.2.X (CONTINUED)

R

Page 29: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

PMT-1-X

270120Rev. C

2019/01/14

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Touchscreen Room Pressure Monitor

Product Submittal

Sheet 5 of 5

Disabled Standard Open

Indicates the isolation mode of roomusing SRPS2

1 - Positive2 - Negative

Indicates the isolation mode of roomusing SRPS3

1 - Positive2 - Negative

Indicates the reason for any alarm that may be present

1 - No Alarm2 - Netw ork Override3 - Contact Input4 - Missing Sensor5 - Room Low Pressure6 - Room High Pressure7 - Extended Door Open

Indicates the reason for any cautionthat may be present

1 - No Caution2 - Netw ork Override3 - Contact Input4 - Door Open5 - Room Low Pressure6 - Room High Pressure7 - Missing Sensor

BACNET POINTS LIST v2.2.X (CONTINUED)

Object Name Units Range Description

Write Settings

W

MV5 Room Isolation Mode 3 Text 2 states R R W

MV4 Room Isolation Mode 2 Text 2 states R R

R R

MV7 Caution Status Text 7 states R R R

MV6 Alarm Status Text 7 states R

NOTE: PLEASE REFER TO PMT MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

Page 30: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

MVM-1-X

270116Rev. C

2019/01/18

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Multi-Variable Monitor

Product Submittal

6.0 (152)

8.75 (222)

7.0 (178)

.11 (3)

2.11 (54)

3.75 (95)

6.25 (159)3.61 (92)

1.3 (33)

1.4 (36)

DIMENSIONS:

ENVIRONMENTAL (OPERATING) 50⁰F to 105⁰F (10⁰C to 40⁰C), 10% to 90% R.H.(NON-CONDENSING)

INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 14 VA, CLASS 2

DISPLAY TYPE CAPACITIVE TOUCH, 7in. (178mm), DIMMABLE

RESOLUTION 800px x 480px, 262144 COLORS

FACE GLASS, IP54

COMMUNICATION PROTOCOL BACNET MS/TP, BACNET IP

MVM SPECIFICATIONS:

Sheet 1 of 4

7in. (178mm) SCREEN SIZE (S7)

NOTE: PLEASE REFER TO MVM MANUAL FOR INSTALLATION, SETUP INSTRUCTIONS AND ADDITIONAL INFORMATION. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

TERMINATION:

ETHERNETPOWER24VAC

+-- GN

D

RS-485

+--

POWER + INPUT POWER, HOT

POWER - INPUT POWER, GROUND

GND NET COM

+ NET +

- NET -

ETHERNETIP CONNECTION FOR BACNET IP ORTO LAPTOP FOR CONFIGURATION

Page 31: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

MVM-1-X

270116Rev. C

2019/01/18

© Copyright Antec Controls by PRICE 2019

Sol

id E

dge

Multi-Variable Monitor

Product Submittal

CONFIGURATIONS:SINGLE ROOM CONFIGURATIONS (1RM)

CONFIGURATION TYPE: (1)DISPLAY POINTS: (RMP-RMT-RMRH)

Room Pressure

Temperature

Humidity

Room Status

Alarm/Caution Reason

Room Pressure Mode

Occupancy Override

CONFIGURATION TYPE: (2)DISPLAY POINTS: (RMP-RMT-ACH)

Room Pressure

Temperature

Air Changes per Hour

Room Status

Alarm/Caution Reason

Room Pressure Mode

Occupancy Override

CONFIGURATION TYPE: (3)DISPLAY POINTS: (RMT-RMRH-CO2)

Temperature

Humidity

CO2

Room Status

Alarm/Caution Reason

Room Pressure Mode

Occupancy Override

CONFIGURATION TYPE: (4)DISPLAY POINTS: (RMT-RMRH-ACH)

Temperature

Humidity

Air Changes per Hour

Room Status

Alarm/Caution Reason

Room Pressure Mode

Occupancy Override

Sheet 3 of 4

CONFIGURATION TYPE: (5)DISPLAY POINTS FOR EACH ROOM: (RMP-RMRH)

Room Pressure

Humidity

Room Status

Alarm/Caution Reason

Occupancy Override

CONFIGURATION TYPE: (6)DISPLAY POINTS FOR EACH ROOM: (RMP-ACH)

Room Pressure

Air Changes per Hour

Room Status

Alarm/Caution Reason

Occupancy Override

CONFIGURATION TYPE: (7)DISPLAY POINTS FOR EACH ROOM: (RMT-RMRH)

Temperature

Humidity

Room Status

Alarm/Caution Reason

Occupancy Override

CONFIGURATION TYPE: (8)DISPLAY POINTS FOR EACH ROOM: (RMT-ACH)

Temperature

Air Changes per Hour

Room Status

Alarm/Caution Reason

Occupancy Override

TWO ROOM CONFIGURATIONS (2RM)

THREE ROOM CONFIGURATIONS (3RM)

CONFIGURATION TYPE: (9)DISPLAY POINTS FOR EACH ROOM: (RMP-RMT)

Room Pressure

Temperature

Room Status

Alarm/Caution Reason

Occupancy Override

CONFIGURATION TYPE: (10)DISPLAY POINTS FOR EACH ROOM: (RMP-ACH)

Room Pressure

Air Changes per Hour

Room Status

Alarm/Caution Reason

Occupancy Override

CONFIGURATION TYPE: (11)DISPLAY POINTS FOR EACH ROOM: (RMT-RMRH)

Temperature

Humidity

Room Status

Alarm/Caution Reason

Occupancy Override

CONFIGURATION TYPE: (12)DISPLAY POINTS FOR EACH ROOM: (RMT-ACH)

Temperature

Air Changes per Hour

Room Status

Alarm/Caution Reason

Occupancy Override

NOTE: PLEASE REFER TO MVM MANUAL FOR INSTALLATION, SETUP INSTRUCTIONS AND ADDITIONAL INFORMATION. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

Page 32: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 33: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 34: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 35: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 36: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 37: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 38: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 39: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description
Page 40: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Sequence Number: 1

Sequence Type: Volumetric OffsetRoom(s): Operating Room

Volumetric Offset Control:

Temperature Control:

Modes of Operation:

Occupied Mode:

Unoccupied Mode:

Pressure Monitoring:

Humidity Monitoring:

The controller will measure the space temperature from a wall mounted room temperature sensor.

Occupied mode may be activated by a contact input or command by building management system.A local occupancy sensor shall be given priority over a building management system command allowing the user to override the occupancy mode and set the space to “Occupied” for a predetermined interval.While in occupied mode the controller will target the scheduled occupied airflows.

2018/10/25

Typical Operating Room

Sequence of Operations

The Airflow Control System (ACS) will modulate the supply and general exhaust to maintain the scheduled volumetric offset target. With no thermal demand, the supply and general exhaust will be maintained at their minimum scheduled values. As airflow demand increases (see section: Temperature Control) the supply and general exhaust will be increased simultaneously to maintain the scheduled volumetric offset.

If the space temperature falls below the adjustable room temperature setpoint, the airflow will initially be maintained at the minimum scheduled heating airflow (or the value dictated by other demands, e.g. fume hoods) and the reheat coil output will be increased. Once the discharge temperature reaches the adjustable maximum value, the reheat output will be maintained. If the room temperature does not rise to the room temperature setpoint, the airflow will then be increased (if scheduled) towards the maximum scheduled heating airflow, allowing the reheat output to increase while maintaining the maximum discharge temperature.

A humidity sensor will measure the room relative humidity. A humidity level can be displayed locally and integrated to the building management system.

If the space temperature rises above the adjustable room temperature setpoint, the reheat output will be decreased. Once the discharge temperature reaches the adjustable minimum value, the reheat output will be maintained. The airflow will initially be maintained at the minimum scheduled cooling airflow (or value dictated by other demands). If the room temperature does not decrease to the room temperature setpoint, the airflow will be increased towards the maximum scheduled cooling airflow.

A room pressure sensor will measure the differential pressure between the room and adjoining space. The differential pressure is displayed on the wall mounted interface. Low and high room pressure alarms and cautions can be enabled for local visual and audible alert. Room differential pressure and alarms are available to the building management system.

Unoccupied mode may be activated by a contact input or command by building management system.While in unoccupied mode the controller will target the scheduled unoccupied airflow.

Page 41: Typical Operating Room Project Submittal Package · 3/27/2019  · MB Consulting Engineer: Antec Controls by Price MB . Typical Operating Room Nomenclature 2018-10-25 Acronym Description

Display:

Local/Room Level Communication:

Building Network Communication

All valves and controllers as part of the Airflow Control System (ACS) within the room will communicate via an independent high-speed room level network. The ACS will route all room level data to a single connection for interface to the building level network. All room level control is self-contained with no communication or data required from sources outside of the room ACS.

The Airflow Control System (ACS) will communicate over a native BACnet MS/TP trunk to the building automation network. All points are available to the BMS with no network gateway required.

The display unit allows monitoring and control of system variables to be displayed on the user interface.The display unit will provide local audible and visual alerts for systems variables.The display unit will communicate directly with room level controllers and to display necessary system variables. It can be integrated with the building management system.

2018/10/25

Typical Operating Room

Sequence of Operations