  • 8/10/2019 UCA Tech Tips BuckBoostTransformers

    1/4

    United CoolAirmanufactures units that

    can be applied with avariety of voltages. Some

    applications utilize an

    input or supply voltage of277-1-60. This power supply

    comes from a 460-3-60(4-wire) system (The Neutral

    Leg and the Line sideopposite the neutral leg).

    While some componentsare available for direct

    application of 277-1-60power, most manufacturers

    (including United CoolAir)

    nd that the use of abuck-boost transformer

    to lower the voltage ismore cost effective. The

    units are fabricated using

    components suitablefor 208/230-1-60 power

    supply. The control voltagetransformer is wired on the

    230-volt tap to provide the24-volt control voltage.

    Selecting a Buck-BoostTransformer

    The following information

    should be conrmed for

    the application:

    Line Voltage Conrmthat the supply / input

    voltage is 277.

    Frequency Input power

    supply frequency mustmatch the equipment

    either 50 or 60 Hertz (Hz).This TechTip is based on

    only applications of 60

    Hz.

    Phase The supply / input powerphasing must be the same as

    the equipment requirements.

    The TechTip is based on single-phase applications.

    Load KVA or Load Amps You

    only need to know one or theother. This information usually

    can be found on the unit

    nameplate(s). On United CoolAirequipment the Minimum Circuit

    Ampacity (MCA) should be used

    as the Load Amps.

    Selecting and ApplyingBuck-Boost Transformers

    BUCK-BOOST TRANSFORMERS

    The transformer is used to buck(decrease) the incoming power

    supply from 277 volts down to the

    230 volts required for the unit. Table1 lists the buck-boost transformers

    available from United CoolAir.

    Read down the column until yousee a KVA or Amp value that is just

    higher than the equipment to be

    operated.

    Table 1 Available Buck-Boost Transformers

    Single-Phase

    UCA

    Line Voltage 277

    Part Number Model

    (Available)

    Load Voltage

    (Output) 230

    KVA 1.44

    4CA1901 T-1-81064 Load

    Amps 6.25

    Max. Size of

    Fuse or Breaker10

    KVA 2.88

    4CA1902 T-1-81065 Load

    Amps 12.50

    Max. Size of

    Fuse or Breaker15

    KVA 4.31

    4CA1903 T-1-81066 Load

    Amps 18.75

    Max. Size of

    Fuse or Breaker20

    KVA 5.75

    4CA1904 T-1-37920 Load

    Amps 25.00

    Max. Size of Fuse or Breaker 30

    KVA 8.63

    4CA1905 T-1-37921 Load

    Amps 37.50

    Max. Size of

    Fuse or Breaker40

    KVA 11.5

    4CA1906 T-1-37922 Load

    Amps 50.00

    Max. Size of

    Fuse or Breaker60

    KVA 17.25

    4CA1907(1) T-1-37923 Load

    Amps 75.00

    Max. Size of

    Fuse or Breaker80

    (1) Model contains lifting ears.

  • 8/10/2019 UCA Tech Tips BuckBoostTransformers

    2/4

    BUCK-BOOST TRANSFORMERS

    Figure 1 Transformer Connection DiagramConnect the transformeraccording to the diagram to theright. Only one (1) transformer is

    required in the wiring diagramfor each power supply to theequipment.

    Notes:

    1. The symbol O used inthis connection diagram

    illustrates where to eldinstall an Overcurrent

    protective device (typicallya fuse or circuit breaker)

    when one input conductoris grounded and theother input conductor is

    ungrounded.

    2. When both input conductorsare ungrounded an

    Overcurrent protectiondevice is required to be

    installed in series with eachinput conductor.

    3. For additional informationrefer to the National

    Electrical Code, Article 450-4.

    General

    The installation, operationand maintenance of dry-type transformers should beperformed by an electrician or

    other qualied personnel whoare familiar with international,national or local electricalcodes. Familiarity with thepotential shock hazardsassociated with electricalequipment is also necessary.

    Encapsulated units are NEMA3R enclosures suitable for eitherindoor use in harsh environmentsor for outdoor use. CE markedunits have a protection index ofIP23.

    The transformer must beinstalled per the NationalElectrical Code (NEC) and localcode requirements. CE markedtransformers must be installed

    per EN 60742.

    Inspection and Handling

    The transformer should beinspected carefully upon receiptto check for any visible orconcealed damage that mayhave occurred during shipment.If damage is found, a claimshould be led immediately with

    the carrier.

    Transformers fty-ve (55)pounds or larger are providedwith lifting ears. Incorrecthandling can bend theenclosure, cause other damageor result in personal injury. (P/N4CA1907 contains lifting ears).

    Installation

    When installing a buck-boosttransformer, always follow allapplicable national and localcodes. Outside installation ofthe transformer should have thewiring in a conduit or as requiredby national and local codes.

    Encapsulated transformers canbe installed indoors or outdoors.When installed outdoors, theseunits should be installed withthe wiring compartment downto prevent the entrance ofmoisture. Some encapsulated

    units have a top-entry wiringcompartment and can beinstalled vertically (wiringcompartment up).

    For indoor oor mounting ofan encapsulated unit thathas a bottom-entry wiringcompartment, the unit can beinstalled horizontally (on its backside) for ease of making wire

    connections.

    CAUTION: Do not makeconnections other than thoseshown. The transformer must

    be as large (KVA) as the load itmust operate. Never exceed thenameplate rating as this could

    result in overheating, reduced lifeexpectancy or worst cases, re.

  • 8/10/2019 UCA Tech Tips BuckBoostTransformers

    3/4

    Electrical Connections

    Refer to the transformernameplate label or enclosedwiring diagram for primaryand secondary voltagecombinations, frequencyand number of phases. Tapconnections and voltagecombinations are also listed on

    the diagram or nameplate.

    Proper assembly of the eldwiring to the transformer leadsis extremely important. Makecertain that the connector orterminal is sized for the cable.Space and insulate connectionsor terminals per the NEC.

    Grounding

    All dry-type transformers havea ground stud in the enclosure.The transformer enclosureshould be solidly groundedto protect personnel. Thecustomer-supplied groundingconductor should have acurrent-carrying capacity tomeet international, national and/ or local requirements.

    BUCK-BOOST TRANSFORMERS

    Maintenance

    Non-ventilated encapsulated

    styles only require periodicwiping of dust and dirt from

    the outside of the caseunder normal conditions

    and environments. Adverseconditions may require morefrequent inspections.

    If a dry-type transformeraccidentally gets wet, it must

    be cleaned and thoroughlydried before energizing.

    Otherwise, complete failurecould result.

    Storage

    Encapsulated transformers

    should be stored in a clean,dry area. Care shoud be

    taken to prevent moisture orcondensation from entering

    the transformer. If storedoutside, the transformer mustbe covered and protected

    from water, dust and otherairborne contaminants.

    Hazardous Voltage.Will Cause SeverePersonal Injury or

    Death.

    Turn Power OffSupplying DeviceBefore Installing

    WARNING: Danger of electricshock! Do not remove partsor make connections while

    transformer is energized.

    CAUTION: Never perform internalmaintenance while the unit is

    energized!

    NOTICE: These instructions are

    general in nature and may notcover all variations in transformer

    design or conditions of installation,operation and maintenance in

    enough detail to meet customerneeds. Additional instructions maybe included with the transformer.If you need further information orshould a problem arise, please

    contact the manufacturer.

  • 8/10/2019 UCA Tech Tips BuckBoostTransformers

    4/4

    Notes

    BUCK-BOOST TRANSFORMERS

    Form TT002 (0513)

    BEA 1K (0513)

    491 East Princess Street, York, PA 17403 Toll Free 1-877-905-1111 Phone (717) 843-4311 Fax (717) 854-4462e-mail: [email protected] www.unitedcoolair.com

    2008 United CoolAir Corporation Manufacturer reserves the right to make changes without notice.