A101SIM
--(-)-
-
WALL SECTION
WINDOW/ STOREFRONT TYPE
KEYNOTE
WALL, FLOOR, ROOF/ PARTITION TYPE
X
XXXX
X
XXX DETAIL
ELEV.
1
A101SIM
BUILDING SECTIONX
XXXX
FURNITURE: FN-##EQUIPMENT: EQ-##SPECIALTIES: SP-##TOILET ACCESSORIES: TA-##
X
X
ELEVATION
?
?X
X
X
X
INTERIOR ELEVATION
X
X
X
X
DOOR NUMBERXXX
DEMOLITION KEYNOTE
ANNOTATION LEGEND
D 1' - 0"Model Number
W 1' - 0"LOCK
ASI, RFI, CO, PR OR CCD REVISIONS
CASEWORK DEPTHAWI MODEL NUMBER OR CUSTOM CASEWORKCASEWORK WIDTHCASEWORK LOCKS AS INDICATED
ROOM NAME
101ROOM NAME AND NUMBER Revision Description
XADDENDUM, OWNER OR JURISDICTION REVISIONS / CHANGES
X
X
INTERIOR FINISH ELEVATION
X
X
X
X.XX
X.XX
NEW GRID LINE
EXISTING GRID LINE
EQ-##
XX
SYSTEM DESCRIPTIONFRAME MATERIAL
GLAZING TYPE
WINDOW/ STOREFRONT INFORMATION
VICINITY MAP
SITE
LOCATION MAP
BUILDING
1.9
G3
G1
F5
F2
F
E9
E
D
3 4 5
2.6 3.2 5.4 6.3
G2
7
7.1
1
6.1
119 SF
HUDDLE
302B
104 SF
HUDDLE
302A
OCCUPANCY 1:15119/15= 7.933
8 OCCUPANTS
OCCUPANCY 1:15104/15= 6.933
7 OCCUPANTS
1.54
1.54
1.54
BUSINESS USE OCCUPANCY 1:1002224 SF/15= 22.2423 OCCUPANTS
22
2
E9
E
D
4 5
3.2
EXIT#1
E9
E
D
4 5
3.2
CODE PLAN LEGEND
TRAVEL DISTANCE TO EXIT
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
EGRESS WIDTH
EXIT SIGN
X' - X"
2 HR FIRE BARRIER
1 HOUR FIRE BARRIER
1 HR SHAFT ENCLOSURE
RATED WALL LEGEND
CODE DATA
This report contains a code analysis of the fire protection and life safety features for the renovation of a 2534 SF office on the UCCS Central Campus, Main Hall, in Colorado Springs, Colorado.
New Construction Code DataOffice of the State Architect of Colorado
2015 International Building Code 2009 International Fire Code 2015 International Mechanical Code 2015 International Plumbing Code NFPA 70 2017 Edition – National Electrical Code NFPA 72 2016 Edition – National Fire Alarm Code NFPA 101 2018 Edition – Life Safety Code Jurisdictional Utility Company Requirements State Department of Labor Requirements State Department of Health Requirements State and Federal Safety and Health Laws ASHRAE Standards including but not limited to 55, 62.1 and 90.1, applicable versions Requirements of Owner’s Insurance Carrier ICC A117.1-2009
Use and Occupancy Classification (Chapter 3)Occupancy: Business: Group B
Fire-Resistance Rating Requirements for Building Elements (IBC Table 601)Type: IIIAStructural Frame 1 HRBearing Walls
Exterior: 2 HRInterior: 1 HR
Non-Bearing PartitionsExterior: 1 HRInterior: 0 HR
Floor Construction 1 HRRoof Construction 1 HR
Fire and Smoke Protection Features (Chapter 7)704.2 Column protection
Means of Egress (Chapter 10)Table 1004.1.1 – Occupant LoadFunction of Space Ratio Gross/Net OccupantsBusiness 1:100 (G) 23Assembly 1:15 (N) 15
Total 38(Occupant load of existing area = 39 Occupants)
Means of Egress Sizing (Section 1005.3 - Egress Width)(With sprinkler system)
Doors: Minimum = 0.15” per occupant * (25) occupants = 3.75" , 32". 32" min per IBC 1010.1.1Provided = 33.5" clear
Stairways and Corridors:Minimum = 0.2” per occupant * (25) occupants = 5” < 44". 44" min per IBC 1011.2. Provided = 48" min. clear
Dead End Corridors:Shall not exceed 50' per 1020.4 Exception 2 for B occupancy sprinklered buildings.
2
2
SHEET NO.
ISSUED FOR:
DATE
RTA PROJECT NUMBER
SHEET TITLE
© COPYRIGHT RTA, INC.
19 SOUTH TEJON ST., SUITE 300COLORADO SPRINGS, CO. 80903
TELE. 719−471−7566 FAX: 719−471−1174
www.rtaarchitects.com
DRAWN BY:
CHECKED BY:
QA/QC APPROVAL:
REVISIONS
c:\
Use
rs\h
eath
er\
Do
cu
men
ts\1
80
66
.00 U
CC
S U
niv
ers
ity
De
velo
pm
en
t O
ffic
e R
em
od
el_
v18
_h
eath
er@
rtaarc
hite
cts
.co
m.r
vt
11/2
6/2
018
1:5
6:1
9 P
M
G001
CONSTRUCTION DOCUMENTS
18066.00
11/07/2018
COVER SHEET
UC
CS
DE
VE
LO
PM
EN
T O
FFIC
E R
EM
OD
EL
UC
CS
142
0 A
ustin B
luffs P
ark
way,
MA
IN 3
04
CC
olo
rad
o S
pri
ng
s,
CO
80
91
8
HWSC
DM
UCCS DEVELOPMENT OFFICE REMODEL
CONSTRUCTION DOCUMENTS
COLORADO SPRINGS, CO
UCCS RTA ARCHITECTS ME ENGINEERS
VERT VERTICAL
VIF VERIFY IN FIELD
VP VINYL PLANKS
VRFY VERIFY
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WB WOOD BASE
WD WOOD
WFT WALL FINISH TYPE
WG WOOD GRAIN
WO WHERE OCCURS
WOM WALK OFF MAT
WP WALL PROTECTION
WS WOOD STAIN
WT WINDOW TREATMENT
PTN PARTITION
QT QUARRY TILE
QTY QUANTITY
QUAL QUALITY
RAD RADIUS
RB RESILIENT BASE
RCP REFLECTED CEILINGPLAN
RD ROOF DRAIN
REBAR REFORCING BAR
REF REFERENCE
REINF REINFORCEMENT
REM REMOVE
REQD REQUIRED
REV REVISION
RFG ROOFING
RO ROUGH OPENING
RS RESILIENT SHEET
RT RESILIENT TILE
SAG SUSPENDEDACOUSTICAL GRID
SC SOLID CORE/ SEALEDCONCRETE
SCHED SCHEDULE
SEC SECTION
SF SPORTS FLOORING
SHTG SHEATHING
SIM SIMILAR
SPEC SPECIFICATION
SS STAINLESS STEEL
SSC SOLID SURFACECOUNTERTOP
ST STAIN
STCN STAINED CONCRETE
STD STANDARD
STL STEEL
STN STONE
STRUCT STRUCTURAL
SURF SURFACE
SYS SYSTEM
TB TACKBOARD
TEMP TEMPORARY/ TEMPERED
THK THICK
TO__ TOP OF __
TP TOILET PARTITIONS
TR TRIM
TS TRANSITION STRIP
TYP TYPICAL
UNF UNFINISHED
UON UNLESS OTHERWISENOTED
UTIL UTILITY
VAR VARIES
VB VINYL BASE
JT JOINT
KD KNOCK DOWN
KO KNOCKOUT
LAD LADDER
LAM LAMINATE
LBL LABEL
LDR LEADER
LKR LOCKER
LNTL LINTEL
LOC LOCATE
LTG LIGHTING
LVR LOUVER
MAINT MAINTENANCE
MAN MANUAL
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIUMUM
MISC MISCELLANEOUS
ML METAL LAMINATE
MO MASONRY OPENING
MOD MODIFY
MTD MOUNTED
MTL METAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OPG OPENING
OPP OPPOSITE
OPP HD OPPOSITE HAND
P/PT PAINT
PA POURED ACRYLIC
PBD PARTICLE BOARD
PC PRECAST CONCRETE
PE POURED EPOXY
PL PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLWD PLYWOOD
PNL PANEL
PR PAIR
PRELIM PRELIMINARY
PREP PREPARED
PTD PAINTED
FA FIRE ALARM
FCP FIBER CEMENT PANEL
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHERCABINET
FF FACTORYFINISH/FINISHED FLOOR
FIN FINISH
FIX FIXTURE
FLASH FLASHING
FLR FLOOR
FLUOR FLUORESCENT
FND FOUNDATION
FO FINISHED OPENING
FO__ FACE OF __
FP FIREPROOFING
FRG FURRING
FRL FIBER REINFORCEDLAMINTE
FRMG FRAMING
FRP FIBER REINFORCEDPANEL
FRT ORFRTW
FIRE RETARDANTTREATED (WOOD)
FT FEET
FTG FOOTING
FURN FURNISH
FUT FUTURE
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERAL/ GENERATOR
GL GLAZING
GND GROUND
GR GRADE
GRAN GRANITE
GYP GYPSUM
GYP BD GYPSUM BOARD
HC HANDICAPPED
HDBD HARDBOARD
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HOR HORIZONTAL
HR HANDRAIL
ID INSIDE DIAMETER
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
JST JOIST
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DIV DIVISION
DN DOWN
DR DOOR
DS DOWNSPOUT
DTL DETAIL
DWG DRAWING
EA EACH
EB EDGE BANDING
EJ EXPANSION JOINT
EL ELEVATION
ELECT ELECTRIC
ELEV ELEVATOR
ENCL ENCLOSURE
ENTR ENTRANCE
EP EPOXY PAINT
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ESC ESCALATOR
EST ESTIMATE
EWC ELECTRIC WATERCOOLER
EXC EXCAVATE
EXH EXHAUST
EXISTOR (E)
EXISTING
EXP EXPANSION/ EXPOSED
EXT EXTERIOR
ACR ACRYLIC PANEL
ACT ACOUSTIC CEILING TILE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
APP APPROVED
APPROX APPROXIMATE
ARCH ARCHITECT/ARCHITECTURAL
AWC ACOUSTICAL WALLCOVERING
BD BOARD
BFG BELOW FINISHED GRADE
BG BUMPER GUARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BO__ BOTTOM OF __
BOT BOTTOM
BRG BEARING
CAB CABINET
CC CUBICLE CURTAIN
CER CERAMIC
CF CORK FLOORING
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLKG CAULKING
CLR CLEAR
CMU CONCRETE MASONRYUNIT
CNTR COUNTER
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
COND CONDITION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CPT CARPET
CT CERAMIC TILE
CTR CENTER
DBL DOUBLE
DRAWING INDEX
ABBREVIATIONS
19 SOUTH TEJON STREET, SUITE 300COLORADO SPRINGS, CO 80903(P) 719-471-7566(F) 719-471-1174CONTACT: STUART COPPEDGE, HEATHER WALLSTEN
1420 AUSTIN BLUFFS PKWYCOLORADO SPRINGS, CO 80903(P) 719-255-3588, CAROLYN FOX, UNIVERSITY ARCHITECT(F) 719-255-3222CONTACT: MARINESS FALCON
3425 AUSTIN BLUFFS PKWY, #201COLORADO SPRINGS, CO 80918(P) 719.536.0036CONTACT: JEREMY O'BRIEN
OWNER ARCHITECT/ INTERIOR DESIGNER MEP ENGINEER
GENERAL
G001 COVER SHEET
G002 ASSEMBLY TYPES AND PROJECT GENERAL NOTES
ARCHITECTURAL DEMOLITION
AD310 THIRD FLOOR DEMOLITION PLANS
ARCHITECTURAL
A310 THIRD FLOOR PLANS
A420 INTERIOR ELEVATIONS
A500 DETAILS AND SCHEDULES
INTERIOR FINISHES
I001 INTERIOR FINISH SCHEDULES, FINISH PLAN, AND FURNITURE PLAN
MECHANICAL
M001 MECHANICAL LEGEND
M002 MECHANICAL SPECIFICATIONS
M310 THIRD FLOOR MECHANICAL PLANS
M320 THIRD FLOOR MECHANICAL PIPING & CONTROLS PLANS
PLUMBING
P001 PLUMBING LEGEND
P310 THIRD FLOOR NEW WORK PLUMBING PLANS
ELECTRICAL
E001 ELECTRICAL LEGEND
E002 ELECTRICAL SPECIFICATIONS
ED310 THIRD FLOOR ELECTRICAL DEMOLITION PLANS
E310 THIRD FLOOR NEW WORK ELECTRICAL PLANS
E601 ELECTRICAL ONE-LINE AND SCHEDULES
1/8" = 1'-0"G001
1 3RD FLOOR CODE PLAN
1/8" = 1'-0"G001
2 2ND FLOOR CODE PLAN @ STAIRS1/8" = 1'-0"G001
3 1ST FLOOR CODE PLAN @ STAIRS
NORTH
CODE PLAN EGRESS PATH LENGTH
PATH NAME LENGTH
COMMON 01 95' - 6"
EXIT 01 108' - 6"
COMMON PATH OF TRAVEL (COMMON 01) SHALL BE CALCULATED AS PART OF THE OVERALL EXIT ACCESS TRAVEL DISTANCE, NOT TO EXCEED 300'.EXIT ACCESS TRAVEL DISTANCE = 204'
PROJECTNORTH
NTS
KEY PLAN
REVISIONS
# DATE DESCRIPTION
2 11/26/2018 ADD 02
KEYNOTE LEGEND
1.54 (E) 1 HR RATED WALL TO REMAIN. ANY MODIFICATIONS TO WALL MUST MAINTAIN RATING OF 1 HRCONSTRUCTION.
ASSEMBLY CONSTRUCTION/ RATING
ASSEMBLY HEIGHT USED ONLY FOR PARTITIONS)
ASSEMBLY MODIFIER
ASSEMBLY TYPE
ASSEMBLY SIZE
ASSEMBLY TYPE A(X)Z1 A
A(X)Z
A(X)Z
ASSEMBLY TYPE AND WALL TAG LEGEND
1 A
1 AA(X)Z1 A
A(X)Z1 A
A(X)Z1 A
FLOOR, SEE DETAILS INDICATED FORCONNECTION
STRUCTURE, SEE DETAILS INDICATED FORCONNECTION
PARTITION WIDTH - SEE SCHEDULE
METAL STUDS- SEE SCHEDULE, ACOUSTICINSULATION (SAFB) WHERE NOTED
5/8" GYPSUM BOARD- 1 LAYER EACH SIDE
CEILING, WHERE APPLICABLE
G002
7
G002
6
INTR-PTN-HEAD-05
GYPSUM BOARD PERPARTITION TYPEGYPSUM BOARD PERPARTITION TYPE
WALL TYPE
REF.PLAN
WIDTH VARIES
PARTITION
6" M
IN.
THIN-FACED GRIDSYSTEM WALL ANGLE
3 5/8" LIGHT GAUGE MTLTRACK
MTL STUD BRACE @ 4'-0"O.C. STAGGERED EACHSIDE, EXTEND TOSTRUCTURE, BEGIN 4'-0"FROM CORNERS
MTL STUD BRACE @ 4'-0"O.C. STAGGERED EACHSIDE, EXTEND TOSTRUCTURE, BEGIN 4'-0"FROM CORNERS
BATT INSULATION, OVERWALL AND EXTEND AMINIMUM OF 4' ON BOTHSIDES OF WALL. DO NOTCOVER LIGHT FIXTURES
CEILING TYPE
REF.RCP
WIDTH VARIES
PARTITION
INTR-PTN-BASE-01
CONTINUOUS STUDTRACK; SET IN SEALANTBED
LIGHT GAUGE METALSTUD, SIZE VARIES
BATT INSULATION, AS OCCURS
GYPSUM BOARD PERPARTITION TYPE
WALL BASED, AS SCHEDULED
POWDER ACTUATED FASTENER
(E) FLOOR ASSEMBLY
INTR-FLR-BASE-01
DEMOLISHED WALL
5/8" TYPE "X" GYP BOARD, PATCH WHEREWALLS ARE BEING REMOVED TO CREATECONTINUOS SEPERATION FROM WOODSTRUCTURE
(E) 1 HR RATED FLOOR ASSEMBLY (LISTED AS BOISE CASCADE ICBO 4665)
RETURN AIR PLENUM
NEW BLOCKING AS REQUIRED
(E) 1 HR RATED FLOOR ASSEMBLY (LISTED AS BOISE CASCADE ICBO 4665)
RETURN AIR PLENUM
NEW PIPING, RE: PLUMBING
FIRE STOPPING SYSTEM AROUND ALLFLOOR PENETRATIONS, RE: SPEC SECTION07 8400
WHERE WALLS ARE REMOVEDAT NEW FLOOR PENETRATIONS
2
FLOOR, SEE DETAILS INDICATED FORCONNECTION
CEILING/STRUCTURE, SEE DETAILSINDICATED FOR CONNECTION
PARTITION WIDTH-SEE SCHEDULE
METAL STUDS- SEE SCHEDULE, ACOUSTICINSULATION (SAFB) WHERE NOTED
5/8" GYPSUM BOARD- 1 LAYER EACH SIDE
G002
12
G002
11
INTR-PTN-HEAD-06
5/8" TYPE "X" GYP BOARD5/8" TYPE "X" GYP BOARD
WALL TYPE
REF.PLAN
POWDER ACTUATED FASTENER
DRYWALL SCREW, EA. SIDE
FIRE RESISTIVE JOINT SPRAY, TYP.
SLOTTED DEFLECTION TRACK, 1"DEFLECTION
FRAME AROUND BEAM / JOIST, ASOCCURS; FIRE SEAL AROUND ALL WALLPENETRATIONS
MINERAL WOOL
(E) 1 HR RATED FLOOR ASSEMBLY (LISTEDAS BOISE CASCADE ICBO 4665)
1/2"
MIN
, 1 3
/4"
MA
XN
OM
INA
L JO
INT
WID
TH4"
INTR-PTN-BASE-05
SEE SCHEDULE
PARTITION WIDTH
METAL STUDS- SEE SCHEDULE, ACOUSTICINSULATION (SAFB) WHERE NOTED
5/8" GYP BOARD, PER PARTITION TYPE
SCREW FASTENER
APPLIED BASE - SEEFINISH PLAN
3 5/8" LIGHT GAUGE MTL RUNNER TRACK.ATTACH TO DECK WITH POWDER-DRIVENFASTENERS AT 24" O.C. AND 2" FROM ENDS
FLEXIBLE FIRESTOP SEALANT FULL DEPTHOF GYPSUM BOARD, BOTH SIDES
(E) FLOOR ASSEMBLY
SHEET NO.
ISSUED FOR:
DATE
RTA PROJECT NUMBER
SHEET TITLE
© COPYRIGHT RTA, INC.
19 SOUTH TEJON ST., SUITE 300COLORADO SPRINGS, CO. 80903
TELE. 719−471−7566 FAX: 719−471−1174
www.rtaarchitects.com
DRAWN BY:
CHECKED BY:
QA/QC APPROVAL:
REVISIONS
c:\
Use
rs\h
eath
er\
Do
cu
men
ts\1
80
66
.00 U
CC
S U
niv
ers
ity
De
velo
pm
en
t O
ffic
e R
em
od
el_
v18
_h
eath
er@
rtaarc
hite
cts
.co
m.r
vt
11/2
6/2
018
1:5
6:1
9 P
M
G002
CONSTRUCTION DOCUMENTS
18066.00
11/07/2018
ASSEMBLY
TYPES AND
PROJECT
GENERAL NOTES
UC
CS
DE
VE
LO
PM
EN
T O
FFIC
E R
EM
OD
EL
UC
CS
142
0 A
ustin B
luffs P
ark
way,
MA
IN 3
04
CC
olo
rad
o S
pri
ng
s,
CO
80
91
8
HWSC
DM
1" = 1'-0"
PARTITION TYPE MF(X)A - NON-RATED PARTITION
ASSEMBLY TYPE
MARK ASSEMBLY
A
B BRICK
C CONCRETE
CM CONCRETE MASONRYUNITS
D
E
F FURRING
FR FLOOR
G
H
J
K
L LANDSCAPE
MF METAL FRAMING
P PLUMBING CHASE/CAVITY
PC PRECAST
Q
RF ROOF
S SHAFT
T
U
V
W EXTERIOR WALL
WF WOOD FRAMING
X
Y
Z
ASSEMBLY CONST. / RATING
MARK DESCRIPTION
A 1 LAYER GYPSUM BOARD PERASSEMBLY TYPE
B 2 LAYERS GYPSUM BOARDPER ASSEMBLY TYPE
C 1 LAYER/ 2 LAYERS GYPSUMBOARD PER ASSEMBLY TYPE
D STUCCO
E EIFS
F SIDING
G MASONRY VENEER
H
I
J
K
L
M METAL PANELS
N
O
P
Q
R 1 LAYER GYP. BD. @CORRIDOR SIDE
S FIRE WALL (2,3 OR 4 HOUR -IBC 705)
T 2 HOUR FIRE BARRIER (IBC706)
U 1 HOUR FIRE BARRIER (IBC706)
V 2 HOUR SHAFT ENCLOSURE(IBC 707)
W 1 HOUR SHAFT ENCLOSURE(IBC 707)
X 1 HOUR FIRE PARTITION (IBC708)
Y 1 HOUR SMOKE BARRIER (IBC709)
Z SMOKE PARTITION (IBC 710)
ASSEMBLY HEIGHT (USED ONLY FOR WALLS)
MARK HEIGHT
A BOTTOM OF DECK ABOVE
B 6" ABOVE CEILING
C BOTTOM OF CEILING
D PARTIAL HEIGHT WALL - SEE FLOOR PLAN
E EXTERIOR WALLS, SEE ELEVATIONS
F STUD TO BOTTOM OF DECK: GYP BD 6" ABOVECILING ONE SIDE, 6" BELOW DECK ONE SIDE
ASSEMBLY MODIFIER
MARK MODIFIER
1 BATT INSULATION
2 SECURITY SCREEN (CORRIDOR SIDE OFWALL)
3 LEAD SHIELDING
4 RADIO FREQUENCY SHIELDING
5 HIGH IMPACT GYP. BD.-SEE PLANS FORHEIGHT ABOVE FINISHED FLOOR
6 SPRAY FOAM AND BATT INSULATION
7 SOUND ATTENUATING FIRE BATTINSULATION
8-69 WALL / PARTITION MODIFIER
70-85 FLOOR MODIFIER
86-99 ROOF MODIFIER
ASSEMBLY SIZE
MARK MATERIAL SIZE
CM-CMU
4 4" CONCRETE MASONRYUNIT
6 6" CONCRETE MASONRYUNIT
8 8" CONCRETE MASONRYUNIT
F-FURRING
0 7/8" METAL FURRINGCHANNEL
1 1 1/2" METAL Z FURRING
1.1 1 5/8" METAL FURRINGCHANNEL
1.5 1 5/8" METAL FURRINGCHANNEL
2 2 1/2" METAL FRAMING
2.1 2" METAL Z FURRING
2.5 2 1/2" METAL Z FURRING
3 3 5/8" METAL FRAMING
4 4" METAL FRAMING
6 6" METAL FRAMING
MF-METAL FRAMING
0 5/8" METAL FRAMING
1 1 5/8" METAL FRAMING
2 2 1/2" METAL FRAMING
3 3 5/8" METAL FRAMING
4 4" METAL FRAMING
6 6" METAL FRAMING
S-SHAFT WALL
2 2 1/2" C-H METAL FRAMING
4 4" C-H METAL FRAMING
6 6" C-H METAL FRAMING
WF-WOOD FRAMING
4 2x4 WOOD FRAMING
6 2x6 WOOD FRAMING
8 2x8 WOOD FRAMING
PARTITION TYPE ASSEMBLY MF(X)A
ASSEMBLY SIZE (X) ASSEMBLY RATING U.L. LISTING PARTITION WIDTH
3 A
3" = 1'-0"G002
7 HEAD OF WALL - "B" HEIGHT
3" = 1'-0"G002
6 BASE OF WALL- NON-RATED WALL1" = 1'-0"G002
16 MODIFICATIONS TO FLOOR ASSEMBLY ABOVE
PARTITION TYPE ASSEMBLY MF(X)U
ASSEMBLY SIZE (X) ASSEMBLY RATING U.L. LISTING PARTITION WIDTH
6 U U419 7 1/4"
1" = 1'-0"
PARTITION TYPE MF(X)U - 1 HOUR FIRE BARRIER3" = 1'-0"G002
12 HEAD OF WALL- 1 HR FIRE BARRIER
3" = 1'-0"G002
11 BASE OF WALL - 1 HR FIRE BARRIER
4 7/8"
PROJECT GENERAL NOTES
1. GENERAL NOTES APPLY TO ALL DRAWINGS
2. GENERAL CONTRACTOR SHALL FURNISH AND INSTALL 2" X 10" CONTINUOUS FIRE TREATED WOOD BLOCKING IN STUD PARTITIONS FOR ANCHORAGE OF WALL ATTACHED ITEMS, INCLUDING BUT NOT LIMITED TO, THE FOLLOWING: GRAB BARS, VANITY UNITS, TOILET ACCESSORIES, WALL CABINETS, AND WALL MOUNTED FIXTURES, MARKER BOARDS, TACK BOARDS
3. GENERAL CONTRACTOR SHALL COORDINATE ALL MECHANICAL CHASE SIZES WITH MECHANICAL SUBCONTRACTOR.
4. WALL OPENINGS FOR FIRE DAMPERS SHALL BE FRAMED PER THE FIRE DAMPER MANUFACTURER'S RECOMMENDATIONS.
5. ELECTRICAL PLANS INDICATE THE GENERAL DESIGN AND ARRANGEMENT OF PIPES, CONDUIT, WIRING, EQUIPMENT, SYSTEMS, ETC. INFORMATION SHOWN IS DIAGRAMMATIC IN CHARACTER AND DOES NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING AND EXISTING CONDITION. LOCATION OF THESE ITEMS MAY BE ADJUSTED CONDITIONAL UPON THE SATISFACTORY COMPLIANCE WITH ALL OTHER REQUIREMENTS.
6. SEE PLANS FOR FIRE EXTINGUISHER (FE) AND FIRE EXTINGUISHER CABINET (FEC) LOCATIONS.
7. SEE SHEET G001 FOR LOCATIONS OF FIRE RATED WALLS WHERE APPLICABLE.
8. ALL WALL PENETRATIONS AT RATED WALL LOCATIONS REQUIRED FOR PIPES, CONDUIT, DUCTING ETC. SHALL BE SEALED TO STOP PASSAGE OF FIRE AND / OR SMOKE WITHFIRE SAFING AND APPROVED FIRESTOPPING SEALANT.
9. THE GENERAL CONTRACTOR SHALL COORDINATE CUT-OUTS FOR CASEWORK, MILLWORK, OR OTHER EQUIPMENT AS REQUIRED.
10. ALL ASPECTS OF THE WORK AND ITEMS NOT SPECIFICALLY MENTIONED, BUT WHICH ARE NECESSARY TO MAKE A COMPLETE WORKING INSTALLATION, SHALL BE INCLUDED, AND INDICATED IN THE CONTRACTORS BID.
11. NO ASBESTOS OR PCB CONTAINING MATERIALS SHALL BE USED ON THIS PROJECT.
12. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS ARE RESPONSIBLE FOR PROPER REMOVAL AND DISPOSAL OF ALL DEBRIS GENERATED BY CONSTRUCTION OF THIS PROJECT. THE REMOVAL AND DISPOSAL OF ALL CONSTRUCTION DEBRIS SHALL BE IN FULL COMPLIANCE WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS. THE PREMISES SHALL BE KEPT CLEAN AND FREE FROM ALL WASTE MATERIALS.
13. GENERAL CONTRACTOR SHALL PROTECT NEW CONSTRUCTION FROM DAMAGE BY ALL TRADES. ALL SUCH DAMAGE CAUSED BY THE CONTRACTOR DURING THE COURSE OF HIS WORK SHALL BE REPAIRED OR REPLACED AT THE CONTRACTORS EXPENSE.
14. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL DIMENSIONS AND FIELD CONDITIONS PRIOR TO ORDERING OR INSTALLING MATERIALS OR EQUIPMENT.
15. ALL PIPING AND CONDUITS SHALL BE CONCEALED WITHIN WALLS, UNDERGROUND, ABOVE CEILINGS OR IN ARCHITECT APPROVED UTILITY SPACES IN ALL CASES UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. EXPOSED ITEMS MUST BE LOCATED IN AREAS APPROVED BY THE ARCHITECT. EXPOSED ITEMS SHALL BE INSTALLED AND FINISHED TO PROVIDE MINIMAL VISUAL IMPACT. ALL EXPOSED ITEMS ARE TO BE PAINTED TO MATCH THE ADJACENT SURFACES UNLESS SCHEDULED FOR AN ACCENT COLOR.
16. FLOOR SPOT ELEVATIONS ARE SHOWN THUS: X'-X"
17. ARCHITECTURAL FINISH FLOOR ELEVATIONS X'-X" EQUALS ACTUAL SITE REFERENCE OF FINISH FLOOR:
18. SCRIBE GYPSUM BOARD OF WALLS AND PARTITIONS TO IRREGULARITIES OF STRUCTURE AND ROOF DECK ABOVE.
19. PROVISIONS SHALL BE MADE AT FULL HEIGHT NON-BEARING WALLS FOR 2- INCH VERTICAL MOVEMENT OF THE BUILDING STRUCTURE WITHOUT TRANSFER OF COMPRESSIVE LOADS TO WALL. FILL IRREGULARITIES BETWEEN TOP OF WALL AND DECK ABOVE WITH FIRE SAFING INSULATION OR FIRE STOPPING MATERIALS AS REQUIRED TO MEET FIRE RATING OF RESPECTIVE WALLS. FILL AT SMOKE PARTITIONS WITH MATERIALS CAPABLE OF RESISTING THE PASSAGE OF SMOKE. SEE DETAILS ON CODE RATING DETAIL SHEETS.
20. ALL MATERIALS, FIXTURES, AND/OR EQUIPMENT THAT CAN BE REUSED AND ARE NOT REQUIRED FOR THE PROJECT SHALL BE RETURNED TO OWNER.
21. SALVAGE ALL CEILING TILES AND RELOCATE PER NEW PLAN. RETURN UNUSED TILES TO OWNER.
22. SALVAGE DOORS, FRAMES, AND LIGHTING FOR RELOCATION OR REINSTALLATION. STORE SALVAGEABLE MATERIALS IN A LOCATION DIRECTED BY OWNER. ALL OTHER MATERIAL AND DEBRIS SHALL BE DISPOSED OF BY CONTRACTOR.
23. PROVIDE BLOCKING AT ALL WALL-MOUNTED ACCESSORIES (DOOR STOPS, MARKER BOARDS, TV DISPLAYS, ETC) AS REQUIRED.
24. MOUNT THERMOSTATS AT 48" AFF MAX.
25. RUN RESILIENT TILE IN BREAK AREA CONTINUOUS FROM WALL TO WALL AND UNDER ALL CASEWORK.
GENERAL CONTRACTOR'S GENERAL RESPONSIBILITIES
1. GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MATERIALS, CONSTRUCTION METHODS AND CRAFTSMANSHIP.
2. DO NOT SCALE DRAWINGS.
3. ALL NEW WORK IS TO BE PLUMB, LEVEL AND SQUARE.
4. ALL NEW WORK IS TO COMPLY WITH UCCS DESIGN AND CONSTRUCTION STANDARDS.
5. UNLESS NOTED OTHERWISE ALL INTERIOR DIMENSIONS ARE TO FINISH FACE OF EXISTING WALL.
6. THE CONTRACTOR IS RESPONSIBLE TO BRING DISCREPANCIES OR CONFLICTS BETWEEN VARIOUS CONSTRUCTION DOCUMENTS, INCLUDING DRAWINGS AND SPECIFICATIONS, TO THE IMMEDIATE ATTENTION OF THE ARCHITECT BEFORE BID OPENING FOR RESOLUTION.
7. CONTRACTORS ARE RESPONSIBLE FOR COORDINATING WORK WITH OTHER TRADES AND OWNER'S SELF-PERFORMED WORK WHEREVER AND WHENEVER THEY OVERLAP.
8. CONTRACTORS ARE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF FIRE RATED ASSEMBLIES WHEREVER AND WHENEVER THEIR WORK PENETRATES OR BREAKS THE INTEGRITY. FURNISH AND INSTALL FIRE STOPPING AT ALL OPENINGS AROUND PIPES, CONDUIT, STRUCTURAL MEMBERS, ETC. IN FIRE RATED ASSEMBLIES.
9. EXISTING FURNITURE TO BE REMOVED, STORED, AND REINSTALLED BY SEPARATE MOVING CONTRACTOR. NEW FURNITURE TO BE INSTALLED BY A SEPARATE VENDOR, BOTH UNDER CONTRACT WITH OWNER. GENERAL CONTRACTOR TO COORDINATE WORK.
10. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE INSPECTION SERVICES PROVIDED BY STATE INSPECTOR. FEES FOR MEP, FIRE DEPT. FEES, INSPECTIONS AND REQUIRED PERMITS TO BE BY GENERAL CONTRACTOR. FEES FOR STATE ARCHITECT INSPECTIONS BY OWNER.
11. ALL ELECTRICAL WORK WILL NEED TO BE PERFORMED BY A MASTER ELECTRICIAN WHO SHALL VERIFY THE LOAD CAPACITY OF ALL CIRCUITS AND PANELS BEING ADJUSTED. THE MASTER ELECTRICIAN SHALL SUBMIT A STATEMENT TO THE STATE INSPECTOR CERTIFYING THAT ALL AFFECTED LOAD CAPACITIES HAVE BEEN VERIFIED PRIOR TO FINAL INSPECTION.
12. GENERAL CONTRACTOR IS RESPONSIBLE FOR MODIFICATIONS TO EXISTING SPRINKLER SYSTEM. COORDINATE WORK WITH WESTERN STATES FIRE PROTECTION OR SIMPLEX.
13. GENERAL CONTRACTOR IS RESPONSIBLE FOR MODIFICATIONS TO EXISTING FIRE ALARM SYSTEM. COORDINATE WORK WITH SIMPLEX.
PARKING, TRASH REMOVAL, TEMPORARY FACILITIES, DELIVERIES, SCHEDULE, WORK HOURS & BUILDING ACCESS
1. FREE PARKING IS AVAILABLE DURING WINTER BREAK - DECEMBER 15, 2018- JANUARY 21, 2019. CONTRACTOR WILL BE RESPONSIBLE FOR PARKING FEES DURING OTHER TIMES.
2. PEDESTRIAN SPINE IN FRONT OF MAIN HALL CAN BE USED FOR TEMPORARY UNLOADING OF MATERIALS ONLY. NO PERMANENT PARKING ALLOWED.
3. GENERAL CONTRACTOR IS RESPONSIBLE FOR TRASH AND RECYCLING REMOVAL. COORDINATE DUMPSTER LOCATIONS WITH UCCS PROJECT MANAGER.
4. COORDINATE CONSTRUCTION ACTIVITIES WITH UCCS PRO MANAGER TO MEET OWNER'S SCHEDULE.
5. ACTIVITIES CAUSING NOISE, VIBRATION, ODORS, DUST, ETC. AND ACTIVITIES WHICH REQUIRES CLOSURE OF PART OF THE BUILDING OR INTERRUPTION OF UTILITY SERVICES MUST BE COORDINATED WITH OWNER'S SCHEDULE.
6. ARRANGE BUILDING ACCESS WITH UCCS PROJECT MANAGER.
7. ALL MEANS OF EGRESS SHALL BE OPEN AND OPERATIONAL DURING CONSTRUCTION. CONTRACTOR SHALL NOT BLOCK OR OBSTRUCT HALLWAYS, STAIRS, DOORS, ETC. FOR THE DURATION OF THE PROJECT.
8. CONTRACTOR TO PROVIDE DUST PARTITION OF ADJACENT SPACES DURING CONSTRUCTION AND IS RESPONSIBLE FOR MAINTAINING THE CLEANLINESS OF THE SITE INCLUDING STAGING AREAS.
REVISIONS
# DATE DESCRIPTION
1 11/20/2018 ADD 01
2 11/26/2018 ADD 02
ADD ALTERNATE #1
ALL ACOUSTIC PANELS (ACR-3) IN OPEN OFFICE 308. RE: I001
ADD ALTERNATE #2
CONVERT AREA OF WORK FROM PNEUMATIC TO DDC CONTROLS. RE: M320
1. EQUIPMENT LIST:A. (8) VARIABLE AIR VOLUME BOXES (VAV-1 THROUGH VAV-8) (EXISTING WITH HW REHEAT)B. (2) VARIABLE AIR VOLUME BOXES (NEW WITH HW REHEAT)
2. PROVIDINGA. REMOVE EXISTING PNEUMATIC CONTROLS AND ASSOCIATED ACTUATOR AND REPLACE WITH NEW DELTA
DVC-322 VAV CONTROLLER WITH INTEGRAL DIRECT COUPLED FLOATING CONTROL ACTUATOR; DEMO CUT AND CAP PNEUMATIC PIPE AND PNEUMATIC CONTROLS BACK TO MAIN
B. REMOVE EXISTING PNEUMATIC TSTAT, REPLACE WITH NEW DESIGNER SPACE TEMPERATURE SENSOR TO MATCH SITE STANDARD AT SAME LOCATION. USE EXISTING PNEUMATIC POLY PIPE AS PULL STRING FOR NEW SPACE SENSOR WIRE
C. REMOVE EXISTING PNEUMATIC VALVE ACTUATOR, REPLACE WITH NEW BELIMO ELECTRIC MODULATING FAIL LAST PROTECTION ACTUATOR
D. (2) PROVIDE AND INSTALL NEW DVC-322 VAV CONTROLLER , TIE INTO NEW MSTP AND POWER NETWORKE. (2) PROVIDE AND INSTALL NEW SPACE TEMPERATURE SENSOR TO MATCH SITE STANDARDF. (2) PROVIDE NEW CONTROL VALVE TO MATCH SITE STANDARD; INSTALLATION BY OTHERSG. NEW PSH500 POWER PANEL FOR 24V VAV POWERH. NEW 24VAC POWER TO NEW AND EXISTING VAVSI. NEW MSTP COMMUNICATION NETWORK TO NEW AND EXISTING VAVSJ. (1) DZNR-768 BACNET MSTP REPEATER FOR NETWORK MANAGEMENT AND TROUBLE SHOOTING
1
1
1
11/26/18
11/26/18
11/26/18
11/26/18