Sensing and Control
UDC2300Universal Digital Controller
Limit Control ModelProduct Manual
Doc. No.: 51-52-25-74
Release: B
Last Revision Date: 10/00
ii UDC2300 Limit Controller Product Manual 10/00
Copyright, Notices, and Trademarks
Printed in U.S.A. – © Copyright 2000 by Honeywell
Revision B – October 2000
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective materials andfaulty workmanship. Contact your local sales office for warranty information. If warrantedgoods are returned to Honeywell during the period of coverage, Honeywell will repair orreplace without charge those items it finds defective. The foregoing is Buyer’s soleremedy and is in lieu of all other warranties, expressed or implied, including thoseof merchantability and fitness for a particular purpose. Specifications may changewithout notice. The information we supply is believed to be accurate and reliable as of thisprinting. However, we assume no responsibility for its use.
While we provide application assistance personally, through our literatureand the Honeywell web site, it is up to the customer to determine thesuitability of the product in the application.
Sensing and ControlHoneywell
11 West Spring StreetFreeport, Illinois 61032
UDC2300 is a trademark of Honeywell
10/00 UDC2300 Limit Controller Product Manual iii
About This Document
AbstractThis document provides descriptions and procedures for the installation, configuration, operation, andtroubleshooting of your UDC2300 Limit Controller.
Contacts
World Wide Web
The following lists Honeywell’s World Wide Web sites that will be of interest to our customers.
Honeywell Organization WWW Address (URL)
Corporate http://www.honeywell.com
Sensing and Control http://www.honeywell.com/sensing
International http://www.honeywell.com/Business/global.asp
Telephone
Contact us by telephone at the numbers listed below.
Organization Phone Number
United States andCanada
Honeywell 1-800-423-9883 Tech. Support1-888-423-9883 Q&A Faxback
(TACFACS)1-800-525-7439 Service
Asia Pacific Honeywell Asia PacificHong Kong
(852) 2829-8298
Europe Honeywell PACE, Brussels, Belgium [32-2] 728-2111
Latin America Honeywell, Sunrise, Florida U.S.A. (854) 845-2600
iv UDC2300 Limit Controller Product Manual 10/00
Symbol DefinitionsThe following table lists those symbols that may be used in this document to denote certain conditions.
Symbol Definition
This DANGER symbol indicates an imminently hazardous situation, which, if notavoided, will result in death or serious injury.
This WARNING symbol indicates a potentially hazardous situation, which, if notavoided, could result in death or serious injury.
This CAUTION symbol may be present on Control Product instrumentation andliterature. If present on a product, the user must consult the appropriate part of theaccompanying product literature for more information.
This CAUTION symbol indicates a potentially hazardous situation, which, if notavoided, may result in property damage.
WARNINGPERSONAL INJURY: Risk of electrical shock. This symbol warns the user of apotential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms,42.4 Vpeak, or 60 Vdc may be accessible. Failure to comply with theseinstructions could result in death or serious injury.
ATTENTION, Electrostatic Discharge (ESD) hazards. Observe precautions forhandling electrostatic sensitive devices
Protective Earth (PE) terminal. Provided for connection of the protective earth (greenor green/yellow) supply system conductor.
Functional earth terminal. Used for non-safety purposes such as noise immunityimprovement. NOTE: This connection shall be bonded to protective earth at thesource of supply in accordance with national local electrical code requirements.
Earth Ground. Functional earth connection. NOTE: This connection shall be bondedto Protective earth at the source of supply in accordance with national and localelectrical code requirements.
Chassis Ground. Identifies a connection to the chassis or frame of the equipmentshall be bonded to Protective Earth at the source of supply in accordance withnational and local electrical code requirements.
Earth Ground. Functional earth connection. NOTE: This connection shall be bondedto Protective earth at the source of supply in accordance with national and localelectrical code requirements.
Chassis Ground. Identifies a connection to the chassis or frame of the equipmentshall be bonded to Protective Earth at the source of supply in accordance withnational and local electrical code requirements.
10/00 UDC2300 Limit Controller Product Manual v
Contents
1 INTRODUCTION................................................................................................... 11.1 Overview........................................................................................................................................ 1
1.2 CE Conformity (Europe)................................................................................................................ 2
2 INSTALLATION .................................................................................................... 32.1 Overview........................................................................................................................................ 3
2.2 Model Number Interpretation ........................................................................................................ 5
2.3 Preliminary Checks ........................................................................................................................ 6
2.4 Limit Control and Alarm Relay Contact Information.................................................................... 8
2.5 Mounting........................................................................................................................................ 9
2.6 Wiring .......................................................................................................................................... 11
2.7 Wiring Diagrams.......................................................................................................................... 12
2.8 Limit Control Application Diagram............................................................................................. 17
3 INITIAL START-UP............................................................................................. 193.1 Overview...................................................................................................................................... 19
3.2 Powering Up the Controller ......................................................................................................... 19
3.3 Operator Interface and Key Functions......................................................................................... 20
3.4 Key Error Message....................................................................................................................... 20
4 CONFIGURATION .............................................................................................. 214.1 Overview...................................................................................................................................... 21
4.2 Configuration Prompt Hierarchy ................................................................................................. 22
4.3 Configuration Procedure.............................................................................................................. 23
4.4 Lock Set Up Group ...................................................................................................................... 24
4.5 Limit Set Up Group...................................................................................................................... 25
4.6 Input 1 Set Up Group ................................................................................................................... 26
4.7 Options Set Up Group.................................................................................................................. 28
4.8 Communications Set Up Group ................................................................................................... 29
4.9 Alarms Set Up Group................................................................................................................... 31
4.10 Configuration Record Sheet......................................................................................................... 33
vi UDC2300 Limit Controller Product Manual 10/00
5 OPERATING THE LIMIT CONTROLLER........................................................... 355.1 Overview...................................................................................................................................... 35
5.2 Operator Interface ........................................................................................................................ 36
5.3 Entering a Security Code ............................................................................................................. 36
5.4 Lockout Feature ........................................................................................................................... 37
5.5 Monitoring Your Limit Controller............................................................................................... 38
5.6 Operating Your Limit Controller ................................................................................................. 40
5.7 Alarm Setpoints............................................................................................................................ 42
6 INPUT CALIBRATION ........................................................................................ 436.1 Overview...................................................................................................................................... 43
6.2 Minimum and Maximum Range Values ...................................................................................... 44
6.3 Preliminary Information............................................................................................................... 45
6.4 Input 1 Set Up Wiring.................................................................................................................. 47
6.5 Input 1 Calibration Procedure...................................................................................................... 49
6.6 Restore Factory Calibration ......................................................................................................... 51
7 TROUBLESHOOTING/SERVICE ....................................................................... 537.1 Overview...................................................................................................................................... 53
7.2 Troubleshooting Aids................................................................................................................... 54
7.3 Power-up Tests............................................................................................................................. 56
7.4 Status Tests .................................................................................................................................. 56
7.5 Background Tests......................................................................................................................... 57
7.6 Controller Failure Symptoms....................................................................................................... 58
7.7 Troubleshooting Procedures ........................................................................................................ 59
8 PARTS LIST........................................................................................................ 638.1 Exploded View............................................................................................................................. 63
9 INDEX ................................................................................................................. 65
10/00 UDC2300 Limit Controller Product Manual vii
Tables
Table 2-1 Condensed Specifications _____________________________________________________ 4Table 2-2 Preliminary Checks __________________________________________________________ 6Table 2-3 Limit Control Relay Contact Information _________________________________________ 8Table 2-4 Alarm Relay Contact Information _______________________________________________ 8Table 2-5 Mounting Procedure_________________________________________________________ 10Table 2-6 Permissible Wiring Bundling__________________________________________________ 12Table 4-1 Configuration Prompt Hierarchy _______________________________________________ 22Table 4-2 Configuration Procedure _____________________________________________________ 23Table 4-3 LOCK Group Function Prompts _______________________________________________ 24Table 4-4 LIMIT Group Function Prompts _______________________________________________ 25Table 4-5 INPUT1 Group Function Prompts ______________________________________________ 26Table 4-6 Options Group Function Prompts ______________________________________________ 28Table 4-7 Communications Group ______________________________________________________ 29Table 4-8 ALARMS Group Function Prompts ____________________________________________ 31Table 5-1 Procedure to Enter a Security Code _____________________________________________ 37Table 5-2 Annunciators ______________________________________________________________ 38Table 5-3 Error Messages_____________________________________________________________ 39Table 5-4 Using Contact Input Option ___________________________________________________ 41Table 5-5 Procedure for Displaying Alarm Setpoints _______________________________________ 42Table 6-1 Voltage and Resistance Equivalents for 0% and 100% Range Values __________________ 44Table 6-2 Equipment Needed__________________________________________________________ 46Table 6-3 Set Up Wiring Procedure for Thermocouple Inputs Using an Ice Bath _________________ 47Table 6-4 Set Up Wiring Procedure for Thermocouple Inputs using Thermocouple Source _________ 47Table 6-5 Set Up Wiring Procedure for RTD Inputs ________________________________________ 48Table 6-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts, or Volts Inputs
(Except 0-10 Volts) _________________________________________________________ 48Table 6-7 Set Up Wiring Procedure for 0 to 10 Volts _______________________________________ 49Table 6-8 Input 1 Calibration Procedure _________________________________________________ 50Table 6-9 Restore Factory Calibration ___________________________________________________ 52Table 7-1 Procedure for Identifying the Software Version ___________________________________ 55Table 7-2 Procedure for Displaying the Status Test Results __________________________________ 56Table 7-3 Background Tests___________________________________________________________ 57Table 7-4 Controller Failure Symptoms__________________________________________________ 58Table 7-5 Troubleshooting Power Failure Symptoms _______________________________________ 60Table 7-6 Troubleshooting Latching Output Relay Failure ___________________________________ 60Table 7-7 Troubleshooting Alarm Relay Output Failure _____________________________________ 61Table 7-8 Troubleshooting a Keyboard Failure ____________________________________________ 61Table 8-1 Parts Identification __________________________________________________________ 63Table 8-2 Parts Not Shown____________________________________________________________ 64
viii UDC2300 Limit Controller Product Manual 10/00
Figures
Figure 1-1 UDC2300 Operator Interface __________________________________________________ 2Figure 2-1 Model Number Interpretation __________________________________________________ 5Figure 2-2 Jumper Placements __________________________________________________________ 7Figure 2-3 Mounting Dimensions (not to scale)_____________________________________________ 9Figure 2-4 Mounting Method __________________________________________________________ 10Figure 2-5 Composite Wiring Diagram __________________________________________________ 12Figure 2-6 Mains Power Supply________________________________________________________ 13Figure 2-7 Input 1 Connections ________________________________________________________ 13Figure 2-8 Electromechanical Relay Output ______________________________________________ 14Figure 2-9 Solid State Relay Output ____________________________________________________ 14Figure 2-10 Open Collector Relay Output ________________________________________________ 15Figure 2-11 Alarm Output Connections __________________________________________________ 15Figure 2-12 External Interface Option Connections ________________________________________ 16Figure 2-13 Limit Controller Application Diagram _________________________________________ 17Figure 3-1 Operator Interface and Key Functions __________________________________________ 20Figure 5-1 Operator Interface__________________________________________________________ 36Figure 6-1 Input 1 Wiring Terminals ____________________________________________________ 45Figure 6-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath _____________________ 47Figure 6-3 Wiring Connections for Thermocouple Inputs Using Thermocouple Source ____________ 47Figure 6-4 Wiring Connections for RTD (Resistance Thermometer Device) _____________________ 48Figure 6-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, or Volts (Except 0 to 10
Volts) ___________________________________________________________________ 49Figure 6-6 Wiring Connections for 0 to 10 Volts __________________________________________ 49Figure 8-1 UDC2300 Exploded View ___________________________________________________ 63
Introduction
10/00 UDC2300 Limit Controller Product Manual 1
1 Introduction
1.1 Overview
Introduction
UDC2300 Limit Controllers accept input signals from any of several types of externalsensors such as Thermocouples (T/Cs) and Resistance Temperature Detectors (RTDs). Itconditions these signals, as necessary, to derive the equivalent Process Variable (PV)value that drives various circuits in the controller.
The equivalent PV signal is compared with the Limit control set point and any errorsignal from the differential amplifier de-energizes the coil of an electromechanical,single-pole, single-throw (SPST) limit output relay.
When de-energized, the output relay “Locks Out” and remains that way until the PV inputsignal drops below the High Limit Set Point or goes above the Low Limit Set Point andthe controller is reset manually via the keyboard or from a remote location (Contact InputOption).
You can select normally open (N.O.) or normally closed (N.C.) Limit Relay Contactssimply by moving a jumper.
The contact of the output relay terminates at the rear terminal of the controller to whichyou make the appropriate field wiring connections.
A flashing “LIMIT” in the lower display indicates that the output relay is de-energized.
High Limit Controller
When the PV input signal is below the limit set point, the output relay energizes. If thePV signal exceeds the limit set point, the output relay de-energizes and the flashing“LIMIT” display is turned on.
When the PV signal returns to a value below the limit set point, the controller can be resetmanually using the MAN-AUTO RESET key or Contact Input Option.
Low Limit Controller
When the PV input signal is above the limit set point, the output relay energizes. If thePV signal falls below the limit set point, the output relay de-energizes and the flashing“LIMIT” display is turned on.
When the PV signal returns to a value above the limit set point, the controller can be resetmanually using the MAN-AUTO RESET key or Contact Input Option.
Introduction
2 UDC2300 Limit Controller Product Manual 10/00
Operator Interface
ALM PVF
FUNCTION
AUTOTUNE
MAN-AUTORESET
SET UP
RUNHOLD
C12
SP
2300
DISPLAY
Figure 1-1 UDC2300 Operator Interface
1.2 CE Conformity (Europe)This product is in conformity with the protection requirements of the following EuropeanCouncil Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMCDirective. Conformity of this product with any other “CE Mark” Directive(s) shall not beassumed.
Product Classification: Class I: Permanently connected, panel-mounted IndustrialControl Equipment with protective earthing (grounding). (EN61010-1).
Enclosure Rating: Panel-mounted equipment, IP 00. This controller must be panel-mounted. Terminals must be enclosed within the panel. Front panel IP 65 (IEC 529).
Installation Category (Overvoltage Category): Category II: Energy-consumingequipment supplied from the fixed installation, local level appliances, and IndustrialControl Equipment. (EN61010-1)
Pollution Degree: Pollution Degree 2: Normally non-conductive pollution withoccasional conductivity caused by condensation. (Ref. IEC 664-1)
EMC Classification: Group 1, Class A, ISM Equipment (EN55011, emissions), IndustrialEquipment (EN50082-2, immunity)
Method of EMC Assessment: Technical File (TF)
Declaration of Conformity: 51309602-000
Deviation from the installation conditions specified in this manual, and the specialconditions for CE conformity in Section 2.1, may invalidate this product’s conformitywith the Low Voltage and EMC Directives.
Installation
10/00 UDC2300 Limit Controller Product Manual 3
2 Installation
2.1 Overview
Introduction
Installation of the UDC2300 consists of mounting and wiring the controller according tothe instructions given in this section. Read the pre-installation information, check themodel number interpretation, and become familiar with your model selections, thenproceed with installation.
What’s in this section?
The following topics are covered in this section.
TOPIC See Page
2.1 Overview 3
2.2 Model Number Interpretation 5
2.3 Preliminary Checks 6
2.4 Limit Control and Alarm Relay Contact Information 8
2.5 Mounting 9
2.6 Wiring 11
2.7 Wiring DiagramsComposite Wiring DiagramAC Line VoltageInput 1 ConnectionsRelay Output
ElectromechanicalSolid StateOpen Collector
Alarm ConnectionsExternal Interface Connections
12121313
1414151516
2.8 Limit Controller Application Diagram 17
Installation
4 UDC2300 Limit Controller Product Manual 10/00
Pre-installation Information
If the controller has not been removed from its shipping carton, inspect the carton fordamage then remove the controller.
• Inspect the unit for any obvious shipping damage and report any damage due to transitto the carrier.
• Make sure a bag containing mounting hardware is included in the carton with thecontroller.
• Check that the model number shown on the inside of the case agrees with what youhave ordered.
Condensed Specifications
Honeywell recommends that you review and adhere to the operating limits listed in Table2-1 when you install your controller.
Table 2-1 Condensed Specifications
Operating Limits Ambient Temperature: 32 °F to 131 °F (0 °C to 55 °C)
Relative Humidity: 5 % to 90 % RH up to 104 °F (40 °C)
Vibration:Frequency: 0 Hz to 200 HzAcceleration: 0.6g
Mechanical Shock:Acceleration: 5 gDuration: 30 ms
Power:90 Vac to 264 Vac, 50/60 Hz(CSA models rated to 250 Vac maximum)
Power Consumption: 12 VA maximum
Accuracy ± 0.25 % of span typical± 1 digit for display15-bit resolution typical
CE Conformity SpecialConditions (Europe)
Shielded twisted-pair cables are required for all analog I/O,process variable, RTD, thermocouple, dc Millivolts, low levelsignal, 4-20 mA, digital I/O, and computer interface circuits.
Refer to 51-52-05-01, How to Apply Digital Instrumentation inSevere Electrical Noise Environments, for additionalinformation.
Installation
10/00 UDC2300 Limit Controller Product Manual 5
2.2 Model Number Interpretation
Introduction
Write the model number into the spaces provided in
Figure 2-1 and compare it to the model number interpretation. This information will alsobe useful when you wire your controller.
0D C 2 3 0
External Interface0 _ = None1 _ = RS422/485 ASCII / Modbus2 _ = Auxiliary Output or Digital Input
Software Options_ 0 = Single Display (includes Accutune II on DC230B)_ A = Dual Display, MA, + Accutune II_ B = Setpoint Programming (SPP), Dual Display,
MA, Accutune II
Manuals0 _ = EnglishF _ = French (Europe)G _ = German (Europe)T _ = Italian (Europe)S _ = Spanish (Europe)Certificate_ 0 = None_ C = Certificate of Conformance (F3391)
Options0 _ _ _ _ _ _ = 90 to 264 Vac Power1 _ _ _ _ _ _ = 24 Vac/dc Power
(requires Alarms plus IN 2)_ 0 _ _ _ _ _ = UL and CE_ A _ _ _ _ _ = UL, CE, CSA and (FM pending)_ _ 0 _ _ _ _ = None_ _ T _ _ _ _ = Customer ID Tag_ _ _ 0 _ _ _ = None_ _ _ F _ _ _ = Rear Terminal Cover_ _ _ _ 0 _ _ = Gray Elastomer Bezel_ _ _ _ B _ _ = Blue Elastomer Bezel_ _ _ _ T _ _ = Tan Elastomer Bezel_ _ _ _ _ 0 _ = Future_ _ _ _ _ _ 0 = Future
B = Basic Controller Model
L = Limit Controller ModelI = Digital Indicator Model
Output #1
C _ = CurrentE _ = Relay, E-MA _ = Relay, SS 1 ampS _ = Relay, SS 10 ampT _ = Open Collector Output
Output #2 or Alarm #2 and Alarm #1_ 0 = No additional outputs or alarms_ E = Relay, E-M and Alarm #1_ A = Relay, SS 1 amp and Alarm #1_ S = Relay, SS 10 amp and Alarm #1_ T = Open Collector Output and Alarm #1
PV Input1 _ = T/C, RTD, Radiamatic, mV, 0-5V, 0-20mA, 4-20mA2_ = T/C, RTD, Radiamatic, mV, Volts, milliamps, 0-10 Volts
Optional Input 2_ 0 = None_ 1 = 0-5V, 1-5V, 0-20mA, 4-20mA
None 0 _ =
Figure 2-1 Model Number Interpretation
Installation
6 UDC2300 Limit Controller Product Manual 10/00
2.3 Preliminary Checks
Introduction
Before you install the controller, remove the chassis and make any preliminary checksnecessary that are listed in Table 2-2. Figure 2-2 shows the locations for jumperplacements.
Table 2-2 Preliminary Checks
CheckNumber
Preliminary Check Description
1 Input I Jumper Placement Check the internal jumper for INPUT 1 to make sure itis set for the correct input type. The jumper is located atposition S101 on the printed wiring board. Figure 2-2shows the location of the jumper and positionselections.
2 Limit Control Relay 1 Check the internal jumper (W101) for CONTROL. Therelay is shipped as N.O. (Normally Open). Figure 2-2shows the location of the jumper and positionselections.
See Table 2-3 for Limit Control Relay contactinformation
3 Alarm Relay Action. The controller has been shipped with ALARM relaysconfigured for N.C. (Normally Closed). If you want tochange to N.O. refer to Figure 2-2, Jumper positionsW201 and W202:
W201 is the ALARM RELAY 1 jumper.
W202 is the jumper for ALARM RELAY 2.
See Table 2-3 for Limit Control Relay contactinformation, and Table 2-4 for Alarm Relay contactinformation.
See Alarm Relay Caution Note, Page 8.
Note: Solid State and Open Collector must have jumper set to N.O. (Normally Open).
Installation
10/00 UDC2300 Limit Controller Product Manual 7
Jumper Placements
W201
NO
NC
Alarm Relay #1
NC (default)
NO
NC
NO
W202
NO
NC
Alarm Relay #2
NC (default)
NO
NC
NO
W101
NO
NC
Output #1
NC
NO
NC
NO (Default)
S101
4 3 2
1
Input #1
Position 1: thermocouple (default)
Position 2: mV, Volt, RTD
Position 3: not used
Position 4: mA
No jumper: 0 -10 volts
Note: Jumpers enlarged for clarity
S201
W201
2 1
W202
NO
NC
NO
NC
S1014 3 2
1
W101NO
NC
MainBoard
1
Figure 2-2 Jumper Placements
Installation
8 UDC2300 Limit Controller Product Manual 10/00
2.4 Limit Control and Alarm Relay Contact Information
Limit Control Relays
Limit Control relays are designed to operate in a Failsafe mode. This results in momentary(5 seconds maximum) limit action when power is initially applied, until the unit completes self-diagnostics.If power is lost to the unit, the Limit Control Relay will still function.
Table 2-3 Limit Control Relay Contact Information
Variable NOT inLimit State
Variable INLimit State
UnitPower
Limit Control RelayJumper
RelayContact Indicator
RelayContact Indicator
N.O. Open OpenOff
N.C. ClosedOff
ClosedOff
N.O. Closed OpenOn
N.C. OpenOff
ClosedOn
Alarm Relays
Alarm relays are designed to operate in a Failsafe mode (that is, de-energized during alarm sate). Thisresults in alarm actuation when power is OFF or when initially applied, until the unit completes self-diagnostics. If power is lost to the unit, the alarms will function.
Table 2-4 Alarm Relay Contact Information
Variable NOT in Alarm State Variable in Alarm StateUnitPower
Alarm RelayWiring
RelayContact
Indicators RelayContact
Indicators
N.O. Open OpenOff
N.C. Closed
Off
Closed
Off
N.O. Closed OpenOn
N.C. Open
Off
Closed
On
Installation
10/00 UDC2300 Limit Controller Product Manual 9
2.5 Mounting
Physical Considerations
The controller can be mounted on either a vertical or tilted panel using the mounting kitsupplied. Adequate access space must be available at the back of the panel for installationand servicing activities.
• Overall dimensions and panel cutout requirements for mounting the controller areshown in Figure 2-3.
• The controller’s mounting enclosure must be grounded according to CSA standardC22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5.
• The front panel is moisture rated NEMA 3/IP65 (IEC) when properly installed withpanel gasket.
Overall Dimensions
96
3.780
96
3.780
Panel Cutout
90 =0.0+0.8
3.5906 +0.03
24
.945
Max PanelThickness
10
.394Max (2)
4.19105.4
.103
2.62 with optionalrear cover
90.73.57
21.0
.826
Dimensions:Millimeters
Inches
20751
3.622 +0.031-0.0
92 -0.0+0.008
3.622 +0.031-0.0
92 -0.0+0.008
Figure 2-3 Mounting Dimensions (not to scale)
Installation
10 UDC2300 Limit Controller Product Manual 10/00
Mounting Method
Before mounting the controller, refer to the nameplate on the outside of the case andmake a note of the model number. It will help later when selecting the proper wiringconfiguration.
Panel
20752
Figure 2-4 Mounting Method
Mounting Procedure
Table 2-5 Mounting ProcedureStep Action
1 Mark and cut out the controller hole in the panel according to the dimension informationin Figure 2-3.
2 Remove the screw cover and loosen the screw on the front of the controller. Pull thechassis out of the case.
3 Orient the case properly and slide it through the panel hole from the front.
4 Remove the mounting kit from the shipping container and install the kit as follows:
• Install the screws into the threaded holes of the clips.
• Insert the prongs of the clips into the two holes in the top and bottom of the case.
• Tighten both screws to secure the case against the panel.
• Carefully slide the chassis assembly into the case, press to close, and tighten thescrew. Replace the screw cover.
Installation
10/00 UDC2300 Limit Controller Product Manual 11
2.6 Wiring
Electrical Considerations
The controller is considered “rack and panel mounted equipment” per EN61010-1, SafetyRequirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive requiresthe user to provide adequate protection against a shock hazard. The user shall install thiscontroller in an enclosure that limits OPERATOR access to the rear terminals.
Mains Power Supply
This equipment is suitable for connection to 90 Vac to 264 Vac, 50/60 Hz, power supplymains. It is the user’s responsibility to provide a switch and non-time delay (NorthAmerica), quick-acting, high breaking capacity, Type F (Europe), 1/2A, 250V fuse(s), orcircuit-breaker, as part of the installation. The switch or circuit breaker shall be located inclose proximity to the controller, within easy reach of the OPERATOR. The switch orcircuit breaker shall be marked as the disconnecting device for the controller.
Controller Grounding
PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it isinstalled shall be in accordance with National and Local electrical codes. To minimizeelectrical noise and transients that may adversely affect the system, supplementarybonding of the controller enclosure to a local ground, using a No. 12 (4 mm2) copperconductor, is recommended.
Control/Alarm Circuit Wiring
The insulation of wires connected to the Control/Alarm terminals shall be rated for thehighest voltage involved. Extra Low Voltage (ELV) wiring (input, current output, andlow voltage Control/Alarm circuits) shall be separated from HAZARDOUS LIVE (>30Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling, Table 2-6.
Electrical Noise Precautions
Electrical noise is composed of unabated electrical signals, which produce undesirableeffects in measurements and control circuits.
Digital equipment is especially sensitive to the effects of electrical noise. Your controllerhas built-in circuits to reduce the effect of electrical noise from various sources. If there isa need to further reduce these effects:
• Separate External Wiring—Separate connecting wires into bundles(See Permissible Wiring Bundling - Table 2-6) and route the individual bundlesthrough separate conduit metal trays.Use Suppression Devices—For additional noise protection, you may want to addsuppression devices at the external source. Appropriate suppression devices arecommercially available.
For additional noise information, refer to Document #51-52-05-01, How to Apply Digital Instrumentation inSevere Electrical Noise Environments.
Installation
12 UDC2300 Limit Controller Product Manual 10/00
Permissible Wiring Bundling
Table 2-6 Permissible Wiring BundlingBundle No. Wire Functions
1 • Line power wiring• Earth ground wiring• Control relay output wiring• Line voltage alarm wiring
2 Analog signal wire, such as:• Input signal wire (thermocouple, 4 to 20 mA, etc.)Digital input signals
3 • Low voltage alarm relay output wiring• Low voltage wiring to solid state type control circuits
2.7 Wiring DiagramsIdentify Your Wiring Requirements
To determine the appropriate diagrams for wiring your controller, refer to the modelnumber interpretation in this section. The model number of the controller can be found onthe outside of the case.
Limit Control Application Diagram
Figure 2-13 shows the Right and Wrong way to wire your Limit Controller.
Wiring the Controller
Using the information contained in the model number, select the appropriate wiringdiagrams from the composite wiring diagram below. Refer to the individual diagramslisted to wire the controller according to your requirements.
910111213
141516
7654L2 / NL1
8Input TerminalSee Figure 2-7
Control OutputTerminalsSee Note 1
Mains Power Supply Terminals
See Figure 2-6
External InterfaceOptions TerminalsSee Figure 2-12
Alarm OutputConnections
See Figure 2-11
24855
Electromechanical Relay Output – See Figure 2-8Solid State Relay Output – See Figure 2-9Open Collector Output – See Figure 2-10
NOTE1:
Figure 2-5 Composite Wiring Diagram
Installation
10/00 UDC2300 Limit Controller Product Manual 13
L2 / NL1
Neutral
Mains power supply
Hot
Ground
1
2
24856
PROTECTIVE BONDING (grounding) of this controllerand the enclosure in which it is installed, shall be inaccordance with National and Local electrical codes. Tominimize electrical noise and transients that mayadversely affect the system, supplementary bonding ofthe controller enclosure to a local ground, using a No.12 (4 mm2) copper conductor, is recommended.Before powering the controller, see “PreliminaryChecks” in this section of the Product manual forswitch and jumper settings.
1
2 Provide a switch and non-time delay (North America),quick-acting, high breaking capacity, type F (Europe),1/2 A, 250 V fuse(s), or circuit-breaker as part of theinstallation.
Figure 2-6 Mains Power Supply
8
7
6 R
+
-
mV, Volts (except 0-10V),Milliamperes, or RadiamaticThermocouple
PlatinumRTD
24857
8
7
6 R
+
-mV, Volt,
orMilliampere
Source
8
7
6R
+
-
0 to 10 Volts
The voltage divider for 0 to 10Volts is supplied with thecontroller when the input isspecified. You must install itwhen you wire the controllerbefore start-up. 1
VoltSource
876
+_
R_
+ 1
2
3
1 These inputs are wired differently than the UDC2000
RTD1
UseThermocoupleextension wireonly
Figure 2-7 Input 1 Connections
Installation
14 UDC2300 Limit Controller Product Manual 10/00
1 Control relay is configured N.O. as shipped. Alarm relays1 and 2 are configured N.C. as shipped. N.O. or N.C. configurationsare selectable by jumpers on the Main printed wiring boards.See “Preliminary Checks” in this section of theProduct Manual for details. Each SPST relay is rated at 5A, 120Vac and 30 Vdc, 2.5 A 240 Vac. User-provided fuses should be sizedaccordingly. For solid state relay outputs, see Figure 2-13.
24859
1
5
4
LoadSupplyPower
5 amp Fast Blo
Limit Control RelayLoad
OUT
See Figure 2-11 for Alarm Output Connections.See Table 2-3 and Table 2-4 for Limit Control and Alarm Relay Contact
information.
Figure 2-8 Electromechanical Relay Output
If the load current is less than the minimum rated value of 20 mA,there may be a residual voltage across both ends of the load evenif the relay is turned off. Use a dummy resistor as shown tocounteract this. The total current through the resistor and the loadcurrent must exceed 20 mA.
2
1
Solid State relay is rated at 1 Amp at 25°C, linearly derated to 0.5Amp at 55°C. Customer should size fuse accordingly.
54
ACLoadPowerSupply
Dummy Resistor
2
1 24860
Limit Control RelayLoad
1 amp Fast Blo OUT
See Figure 2-11 for Alarm Output Connections.
See Table 2-3 and Table 2-4 for Limit Control and Alarm Relay Contactinformation.
Figure 2-9 Solid State Relay Output
Installation
10/00 UDC2300 Limit Controller Product Manual 15
CAUTION Open collector outputs are internally powered at 24 Vdc.Connecting an external supply will damage the controller.External relays should be fused between power and relay load.
1
24861L
Customer Supplied External Solid State Relay
5 –4++
–1
0-24 Vdc
Customer Supplied External Electromechanical Relay
5–4+
1
+
–
0-24 Vdc
See Figure 2-11 for Alarm Output Connections.
See Tables 2-3 and 2-4 for Limit Control and Alarm Relay Contact information.
OUT
OUT
Figure 2-10 Open Collector Relay Output
9
10
11
12
1LoadSupplyPower
AlarmRelay #2 Load
AlarmRelay #1 Load
LoadSupplyPower
5 amp fast Blo
5 amp Fast Blo
24867
Control relay is configured N.O. as shipped. Alarm relays 1
and 2 are configured N.C. as shipped. N.O. or N.C. configurations areselectable by jumpers on main printed wiring boards. See “PreliminaryChecks” in this section of the Product Manual for details.
Each SPST relay is rated at 5 A, 120 Vac and 30 Vdc, 2.5 A, 240 Vac.
1
1
Figure 2-11 Alarm Output Connections
Installation
16 UDC2300 Limit Controller Product Manual 10/00
1314
+_
AuxiliaryLoad
0 - 500 Ω
Connect shieldto ground at oneend only.
1
1 AuxOut , Digital Input and Communications are mutually exclusive.
Auxiliary Output
1314
+_
ContactInput
Switch
Connect shieldto ground at oneend only.
Digital Inputs 1
1
13
14
D–
D+
COMMUNICATION MASTER
(A) (RTN) (B)
D+ SHLD D–
120 OHMS
TO OTHER COMMUNICATION
CONTROLLERS
D+D–
120 OHMS ON LAST LEG
Connect shield wires together with Honeywell supplied crimp part number 30755381-001
1
2 Do not run these lines in the same conduit as AC power.
1
2
Communications
Figure 2-12 External Interface Option Connections
Installation
10/00 UDC2300 Limit Controller Product Manual 17
2.8 Limit Control Application Diagram
Limit Controller Wiring
Figure 2-13 shows the RIGHT and WRONG way to wire your Limit Controller.
PROCESSCONTROLLER
LIMITCONTROLLER
PROCESSCONTROLLER
LIMITCONTROLLER
CONTROLRELAY/SOLENOID
POWER
1 2
The Limit Controller CANNOT protectagainst a failure of the Control relay
LOAD
POWER
1 2
CONTROLRELAY/SOLENOID
LOAD
POWER
POWER
The Limit Controller CAN protectagainst a failure of the Control relay
WRONG RIGHT
Figure 2-13 Limit Controller Application Diagram
Installation
18 UDC2300 Limit Controller Product Manual 10/00
Initial Start-up
10/00 UDC2300 Limit Controller Product Manual 19
3 Initial Start-up
3.1 OverviewThis section gives you the information necessary to start up your controller prior toconfiguration. Review the Operator Interface portion to make sure you are familiar withthe indicator definitions and key functions.
3.2 Powering Up the Controller
Apply Power
When power is applied, the controller will run three diagnostic tests. After these tests arecompleted, “TEST DONE” is displayed.
Test Failures
If one or more of these tests fail, a message indicating which test failed will appear in thelower display. Then, “DONE” will appear in the lower display.
Initial Start-up
20 UDC2300 Limit Controller Product Manual 10/00
3.3 Operator Interface and Key Functions
ALMPV
F
FUNCTION
AUTOTUNE
MAN-AUTORESET
SET UP
RUNHOLD
ALM - Alarmconditions exist
Keys
C12
SP2300
DISPLAY
F - °Fahrenheit being usedC - °Centigrade being used
Upper Display - Four digits• Normal operation - Process Variable• Configuration mode - displays parameter value or selection
Lower Display - Six alphanumeric characters• Normal operation – display is blank unless configured For default prompt of PV or Setpoint• Configuration mode - displays functions and parameters
Resets the latching Limit Controller relay.In Set Up mode, used to restore original value orselection.
FUNCTION Selects functions within each configuration group.
DISPLAYReturns Controller to normal display from Set Upmode.
MAN-AUTORESET
SET UP Scrolls through the configuration Setup groups.
AUTOTUNE
HOLD
Decreases setpoint value. Decreases theconfiguration values or changes functions in Configurationmode groups.
Increases setpoint value. Increases theconfiguration values or changes functions in Configurationmode groups.
Not Applicable
24868
RUN Alarm Acknowledge
Figure 3-1 Operator Interface and Key Functions
3.4 Key Error MessageWhen a key is pressed and the prompt KEYERR appears in the lower display, it will befor one of the following reasons:
• parameter is not available,
• not in Set Up mode, press [SET UP] key first,
• key malfunction.
Configuration
10/00 UDC2300 Limit Controller Product Manual 21
4 Configuration
4.1 Overview
Introduction
Configuration is a dedicated operation where you use straightforward keystrokesequences to select and establish (configure) pertinent control data best suited for yourapplication.
To assist you in the configuration process, there are prompts that appear in the upper andlower displays. These prompts let you know what group of configuration data (Set Upprompts) you are working with and also, the specific parameters (Function prompts)associated with each group.
Figure 3-1 shows you an overview of the prompt hierarchy as they appear in thecontroller.
As you will see, the configuration data is divided into 5 main Set Up groups plus promptsfor calibration and prompts that show the status of the continuous background tests thatare being performed
What’s in this section?
The following topics are covered in this section.
TOPIC See Page
4.1 Overview 21
4.2 Configuration Prompt Hierarchy 22
4.3 Configuration Procedure 23
4.4 Lockout Group 24
4.5 Limit Group 25
4.6 Input 1 Set Up Group 26
4.7 Options Set Up Group 28
4.8 Communications Set Up Group 29
4.9 Alarms Set Up Group 31
4.10 Configuration Record Sheet 33
Configuration
22 UDC2300 Limit Controller Product Manual 10/00
4.2 Configuration Prompt Hierarchy
Table 4-1 Configuration Prompt Hierarchy
Set Up Group Function Prompts
LOCK SECUR LOCK
LIMIT LOorHI POWRUP SPMAX SPMIN DISPLY
INPUT1 DECMAL UNITS IN1TYP XMITR1 IN1 HI IN1 LO RATIO1 BIAS 1
FILTR1 BRNOUT EMISS FREQ
OPTIONS EXTRST AUXOUT
COM ComSTA ComADR SDENAB SHDTIM PARITY BAUD TX DLY WS FLT
UNITS LOOPBK
ALARMS A1S1VA A1S2VA A2S1VA A2S2VA A1S1TY A1S2TY A2S1TY A2S2TY
A1S1HL A1S1EV A1S2HL A1S2EV A2S1HL A2S1EV A2S2HL A2S2EV
ALHYST ALARM1 BLOCK
STATUS VERSON FAILSF TESTS
Configuration
10/00 UDC2300 Limit Controller Product Manual 23
4.3 Configuration Procedure
IntroductionEach of the Set Up groups and their functions are pre-configured at the factory.The factory settings are shown in Table 4-3 through Table 4-8 that follow this procedure.
If you want to change any of these selections or values, follow the procedure in Table 4-2.This procedure tells you the keys to press to get to any Set Up group and any associatedFunction parameter prompt.
Procedure
The prompting scrolls at a rate of 2/3 seconds when the [SET UP] or [FUNCTION] key is held in.Also, [] [] keys will move group prompts forward or backward at a rate twice as fast.
Table 4-2 Configuration ProcedureStep Operation Press Result
1 Enter Set UpMode
SET UP Upper Display = SET
Lower Display = LOCK (This is the first Set Up Group title)
2 Select any Set UpGroup
SET UP Sequentially displays the other Set Up group titles shown inthe prompt hierarchy in Table 4-1.You can also use the [] [] keys to scan the Set Up groupsin both directions. Stop at the Set Up group title thatdescribes the group of parameters you want to configure.Then proceed to the next step.
3 Select a FunctionParameter
FUNCTION Upper Display = the current value or selection for the firstfunction prompt of the selected Set Upgroup.
Lower Display = the first Function prompt within that Set Upgroup.
Sequentially displays the other function prompts of the SetUp group you have selected. Stop at the function prompt thatyou want to change, then proceed to the next step.
4 Change theValue orSelection
[] [] Increments or decrements the value or selection thatappears for the selected function prompt. If you change thevalue or selection of a parameter while in Set Up mode thendecide not to enter it, press [MAN-AUTO/RESET] once—theoriginal value or selection is recalled.
5 Enter the Valueor Selection
FUNCTION Enters value or selection made into memory after anotherkey is pressed.
6 Exit Configuration DISPLAY Exits configuration mode and returns controller to the samestate it was in immediately preceding entry into the Set Upmode. It stores any changes you have made.If you do not press any keys for 30 seconds, the controllertimes out and reverts to the mode and display used prior toentry into Set Up mode.
Configuration
24 UDC2300 Limit Controller Product Manual 10/00
4.4 Lock Set Up Group
Introduction
The Lock Set Up group contains the Function parameters that will allow your controllerto protect Configuration and Calibration data.
Because this group contains functions that have to do with Security and Lockout, it is bestto configure this group last, after all the other configuration data has been loaded.
Function Prompts
Table 4-3 LOCK Group Function Prompts
Prompt Description Selection or Range of Setting FactorySetting
SECUR Security Code 0 to 4095When “Lock” is none, this number isdisplayed and can be changed using theraise/lower keys
DIS
LOCK Configuration Lockout NONE – all parameters are read/write
CAL - all parameters are read/writeexcept Calibration
CONF – configuration parameters areRead Only; no writes permitted
+SP – Only the Lockout group isavailable for read/write. Setpoint value isRead Only.
CAL
Configuration
10/00 UDC2300 Limit Controller Product Manual 25
4.5 Limit Set Up Group
Introduction
This data deals with the type of Limit Control you want, power up Logic, setpoint highand low limits, and the default display function Prompts
Table 4-4 LIMIT Group Function Prompts
Prompt Description Selection or Range of Setting FactorySetting
LOorHI Type of LimitController
LOW - Limit Control - latching relay de-energizeswhen PV goes below configured setpoint; cannotbe reset until PV rises above configured setpointand [MAN-AUTO RESET] key is pressed.
HIGH - Limit Control - latching relay de-energizeswhen PV goes above configured setpoint; cannotbe reset until PV drops below configured setpointand [MAN-AUTO RESET] key is pressed.
Configuredaccording tothe modelnumber
POWRUP Power Up Logic RST - after power down, the controller latchingrelay will have to be reset.
NORM - after power down, the controller willoperate normally in the same mode as beforepower was removed unless a limit has beenexceeded. If the limit was latched at power down,the unit will be in “Limit” at power up and have tobe reset.
NORM
SP_MAX SP High Limit HIGH SETPOINT LIMIT - this selection preventsthe setpoint from going above the value selectedhere. The setting must be equal to or less thanthe upper range of the input.0 % to 100 % of input in engineering units
1000
SP_MIN SP Low Limit LOW SETPOINT LIMIT - this selection preventsthe setpoint from going below the value selectedhere. The setting must be equal to or greaterthan the lower range of the input.0 % to 100 % of input in engineering units
0
DISPLY Normal Display SP - Setpoint - if configured the setpoint will bedisplayed in the upper display. “SP” will appear inthe lower display.
PROC - Process Variable - PV will be displayedin the upper display.
PROC
Configuration
26 UDC2300 Limit Controller Product Manual 10/00
4.6 Input 1 Set Up Group
IntroductionThis data deals with various parameters required to configure Input 1.
Function Prompts
Table 4-5 INPUT1 Group Function Prompts
Prompt Description Selection or Range of Setting FactorySetting
DECMAL Decimal PointSelection
This selection determines where the decimalpoint appears in the display.8888 (none)888.888.88
8888
UNITS Temperature Units This selection will be indicated on theannunciator. (“What display of temperature doyou want?”)FCNONE
F
IN1TYP Input 1 ActuationType
BE HE LJ HJ LK HK LNNMHNNMLN90HN90LNICRST HT L
W HW L100H100L200500RADHRADI0-204-2010m50m0-51-50-10100m
K H
XMITR1 TransmitterCharacterization
Available onLinear actuationsonly.
Not available on FMModels
BE HE LJ HJ LK HK LNNMHNNMLN90HN90LNICR
ST HT LW HW L100H100L200500RADHRADILINSrT
LIN
Notavailableon FMModels
Configuration
10/00 UDC2300 Limit Controller Product Manual 27
Prompt Description Selection or Range of Setting FactorySetting
IN1 HI Input 1 High RangeValue
Range of Setting:−999 to 9999. floating in engineering unitsLinear Ranges Only
2400
IN1 LO Input 1 Low RangeValue
Range of Setting:−999 to 9999. floating in engineering unitsLinear Ranges Only
0
BIAS 1 Bias on Input 1 Range of Setting:-999 to 9999 (Non-FM)(Engineering Units)-10 to 10 (FM Models)
0.0
FILTR1 Filter for Input 1 A software digital filter is provided for input 1 tosmooth the input signal. You can configure thefirst order lag time constant from 1 to 120secondsRange of Setting:0 to 120 seconds0 = No Filter
1.0
BRNOUT Burnout Protection(Sensor Break)
UP - UPSCALE BURNOUT is provided for highlimit control.
DOWN - DOWNSCALE BURNOUT is providedfor low limit control.
UP
EMISS Emissivity Emissivity is a correction factor applied to theRadiamatic input signal that is the ratio of theactual energy emitted from the target to theenergy which would be emitted if the target werea perfect radiator.Range of Setting:0.01 to 1.00 (RADH and RADI only)
1.0
FREQ Power LineFrequency
Select whether your controller is operating at 60Hz or 50 Hz.6050
For units powered by +24 Vdc, this configurationshould be set to the AC Line frequency used toproduce the +24 Vdc Supply. Failure to set thisparameter properly can cause normal modenoise problems in the input readings.
60
Configuration
28 UDC2300 Limit Controller Product Manual 10/00
4.7 Options Set Up Group
Introduction
The Options group lets you configure the remote mode switch (Digital Inputs) to aspecific contact closure response, or configure the Auxiliary Output to be a specificselection with desired scaling. Auxiliary Output and External Reset are mutuallyexclusive.
Function Prompts
Table 4-6 Options Group Function Prompts
Prompt Description Selection or Range of Setting FactorySetting
AUXOUT Auxiliary Output This selection provides a current outputrepresenting the process variable. The display forauxiliary output viewing will be in engineeringunits.
Other prompts affected by these selections: "0PCT" and "100 PCT."
NONE DisabledPROC Represents the value of the Process
Variable.
DIS
0 PCT Auxiliary OutputLow Scaling Factor
Value in Engineering Units 0
100PCT Auxiliary OutputHigh Scaling Factor
Value in Engineering Units 100
EXTRST Digital Input EXTERNAL RESET (DIGITAL INPUT) — resetsthe latching relay on contact closure.
DIS – Disable
ENAB – Enable
DIS
Configuration
10/00 UDC2300 Limit Controller Product Manual 29
4.8 Communications Set Up Group
Introduction
The Communications group lets you configure the controller to be connected to a hostcomputer via RS422/485 or Modbus® protocol.
Function Prompts
Table 4-7 Communications Group
Prompt Description Selection or Range of Setting FactorySetting
COMSTA CommunicationsState
This prompt lets you select the type ofcommunications protocol.
DIS DisabledR422 RS-422/485MODB Modbus
DIS
ComADD Station Address This is a number that is assigned to a controllerthat is to be used with the communicationsoption. This number will be its address.
Range of Setting: 1 to 99
0
SDENAB Disable/EnableShed function
DIS DisableENAB Enable
ENAB
SHDTIM Shed Time This is the number that represents how manysample periods there will be before the controllersheds from communications. Each period equals1/3 seconds; 0 equals No shed.
Range of Setting: 0 to 255 Sample Periods
0
PARITY Parity PARITY pertains to the use of a self-checkingcode employing binary digits in which the totalnumber of ONE’s (or ZERO’s) in eachpermissible code expression is either ODD orEVEN.
ODD
BAUD Baud Rate BAUD RATE is the transmission speed in bitsper second
2400 Baud4800 Baud9600 Baud19200 Baud
2400
TX_DLY Response Delay Configurable response-delay timer allows you toforce the UDC to delay its response for a timeperiod of from 1 to 500 milliseconds compatiblewith the host system hardware/software.
Range of Setting: 1 to 500 milliseconds
1
Configuration
30 UDC2300 Limit Controller Product Manual 10/00
Prompt Description Selection or Range of Setting FactorySetting
WS FLT Word/Byte Orderfor floating pointcommunicationsdata
Byte Contents0 seeeeeee1 emmmmmmm2 mmmmmmmm3 mmmmmmmm
Choice Byte OrderFP_B 0123FPBB 1032FP_L 3210FPLB 2301
FP_B Floating point big endianFPBB Floating point big endian with byte-
swappedFP_L Floating point little endianFPLB Floating point little endian with byte-
swapped
FP_B
UNITS CommunicationsOverride Units
This selection determines how the controllervalues are expressed during communications.
PCT PercentEng Engineering Units
PCT
LOOPBK Local LoopbackTest
Allows loopback test. The UDC goes intoLoopback mode in which it sends and receives itsown message. The UDC displays PASS or FAILstatus in the upper display and LOOPBACK inthe lower display while the test is running. TheUDC will go into manual mode. The test will rununtil the operator disables it here, or until poweris turned off and on.
The UDC does not have to be connected to theRS-485 link to perform this test. If it is connected,only one UDC2300 should run the loopback testat a time. The computer should not betransmitting on the link while the loopback test isactive.
DIS DisableEnAB Enable
DIS
Configuration
10/00 UDC2300 Limit Controller Product Manual 31
4.9 Alarms Set Up Group
Introduction
An alarm is an indication that an event that you have configured (for example—ProcessVariable) has exceeded one or more alarm limits. There are two alarms available. Eachalarm has two setpoints. You can configure each of these two setpoints to alarm onvarious controller parameters.
There are two alarm output selections, High and Low. You can configure each setpoint toalarm either High or Low. These are called single alarms.
You can also configure the two setpoints to alarm on the same event and to alarm bothhigh and low. A single adjustable Hysteresis of 0 to 100% is configurable for the alarmsetpoint.
See Table 2-4 in the Installation section for Alarm relay contact information.The prompts for the Alarm Outputs appear whether or not the alarm relays are physicallypresent. This allows the Alarm status to be shown on the display and/or sent viacommunications to a host computer.
Function Prompts
Table 4-8 ALARMS Group Function Prompts
Prompt Description Selection or Range of Setting FactorySetting
AxSxVAA1S1A1S2A2S1A2S2
Alarm SetpointxValueX = 1 or 2
This is the value at which you want the alarm typechosen in Prompt "AxSxTY" to actuate. The valuedepends on what the alarm setpoint has beenconfigured to represent.
Range of Setting:within the range of the selected parameter or ofthe PV Span for Deviation configurations
90
AxSxTYA1S1A1S2A2S1A2S2
Alarmx SetpointxTypeX = 1 or 2
Select what you want Setpoint x of Alarm x torepresent; it can represent the Process Variable orDeviation.
NONE No AlarmPROC Process VariableDE DeviationSHED Shed Communications (Shed alarms do
not have setpoint values)PVRT PV Rate of ChangeDI Alarm on Digital Input
NONE
AxSxHLA1S1A1S2A2S1A2S2
Alarmx SetpointStateX = 1 or 2
Select whether you want the alarm type chosen inprompt "AxSxTY" to alarm High or Low.
LOW Low AlarmHIGH High Alarm
HIGH
Configuration
32 UDC2300 Limit Controller Product Manual 10/00
Prompt Description Selection or Range of Setting FactorySetting
ALHYST Alarm Hysteresis A single adjustable hysteresis is provided onalarms such that when the alarm is OFF itactivates at exactly the alarm setpoint; when thealarm is ON, it will not deactivate until the variableis 0.0 % to 100 % away from the alarm setpoint.
Configure the hysteresis of the alarms based onINPUT signals as a % of input range span.
Range of Setting:0.0 % to 100.0 % of span
0.0
ALARM1 Latching AlarmOutput
When configured for latching, the alarm will stayon, after the alarm condition ends, until the[RUN/HOLD] key is pressed.
NO L Non LatchingLACH Latching
NO L
BLOCK Alarm Blocking Alarm Blocking prevents nuisance alarms whenthe controller is first powered up. The alarm issuppressed until the parameter gets to the non-alarm limit or band. Alarm blocking affects bothalarm setpoints.
DIS Disable BlockingBK1 Block Alarm 1 onlyBK2 Block Alarm 2 onlyBK12 Blocks both Alarms
DIS
Configuration
10/00 UDC2300 Limit Controller Product Manual 33
4.10 Configuration Record SheetEnter the value or selection for each prompt on this sheet so you will have a record ofhow your controller was configured.
GroupPrompt
FunctionPrompt
Value orSelection
FactorySetting
GroupPrompt
FunctionPrompt
Value orSelection
FactorySetting
LOCK SECURLOCK
______________
DISCAL
LIMIT LOW or HIGHPOWRUPSP MAXSP MINDISPLY
___________________________________
HIGHNORM10000PROC
COM ComSTAComADRSDENABSHDTIMPARITYBAUDTX DLYWS FLTUNITSLOOPBK
______________________________________________________________________
DIS0ENAB0ODD24001FP_BPCTDIS
INPUT1 DECMALUNITSIN1TYPXMITR1IN1 HIIN1 LOBIAS 1FILTR1BRNOUTEMISFREQDISPLY
____________________________________________________________________________________
8888FKHLIN24001.000.01.0UP1.060SP
OPTIONS AUXOUT0 PCT100 PCTEXT RST
____________________________
DIS0100DIS
ALARMS A1S1VAA1S2VAA2S1VAA2S2VAA1S1TYA1S1TYA2S1TYA2S2TYA1S1HLA1S2HLA2S1HLA2S2HLALHYSTALARM1BLOCK
_________________________________________________________________________________________________________
90909090NONENONENONENONEHIGHHIGHHIGHHIGH 0.0NOLDIS
Configuration
34 UDC2300 Limit Controller Product Manual 10/00
Operation
10/00 UDC2300 Limit Controller Product Manual 35
5 Operating the Limit Controller
5.1 Overview
Introduction
This section gives you all the information necessary to help you monitor your controllerincluding an Operator Interface overview, how to lockout changes to the controller,entering a security code, and monitoring the displays.
What’s in this section?
The following topics are covered in this section.
TOPIC See Page
5.2 Operator Interface 36
5.3 Entering A Security Code 37
5.4 Lockout Feature 36
5.5 Monitoring The Limit Controller 38
5.6 How to Operate Your Limit Controller 40
5.7 Alarm Setpoints 42
Operation
36 UDC2300 Limit Controller Product Manual 10/00
5.2 Operator Interface
Introduction
Figure 5-1 is a view of the Operator Interface. A description of the displays and indicatorsis included.
ALM PVF
FUNCTION
AUTOTUNE
MAN-AUTORESET
SET UP
RUNHOLD
ALM - Alarmconditions exist C
12
SP2300
DISPLAY
F - °Fahrenheit being usedC - °Centigrade being used
Upper Display - Four digits• Normal operation - Process Variable• Configuration mode - displays parameter value or selection
Lower Display - Six alphanumeric characters• Normal operation - display is blank unless configured for default prompt of Setpoint)• Configuration mode - displays functions and parameters
24868
Figure 5-1 Operator Interface
5.3 Entering a Security Code
Introduction
The level of keyboard lockout may be changed in the Set Up mode. However, knowledgeof a security code number (0 to 4095) may be required to change from one level oflockout to another. When a controller leaves the factory, it has a security code of 0, whichpermits changing from one lockout level to another without entering any other codenumber.
Procedure
If you require the use of a security code, select a number from 0001 to 4095 and enter itwhen the lockout level is configured as NONE. Thereafter, that selected number must beused to change the lockout level from something other than NONE.
Write the number on the Configuration Record Sheet in the configuration section so you will have apermanent record.
Operation
10/00 UDC2300 Limit Controller Product Manual 37
Table 5-1 Procedure to Enter a Security Code
Step Operation Press Result
1 Enter Set UpMode
SET UP Upper Display = SET UP
Lower Display = LOCK
2 Select any Set UpGroup
FUNCTION Upper Display = 0
Lower Display = SECUR
3 Security CodeEntry
[] [] To enter a four digit number in the upper display(0001 to 4095)
This will be your security code.
5.4 Lockout Feature
Introduction
The lockout feature in the UDC2300 is used to inhibit changes (via keyboard) of certainfunctions or parameters by unauthorized personnel.
Lockout levels
There are different levels of Lockout depending on the level of security required. Theselevels are:
• NONE No Lockout. All groups Read/Write.
• CAL All groups Read/Write except Calibration
• CONF Configuration parameters are Read only. No writes permitted.Calibration Group is not available.
• +SP Only the Lockout group is available for Read/Write.Setpoint value is Read Only.
See Subsection 4.4- Lockout Parameters Set Up Group prompts to select one of theabove.
Key error
When a key is pressed and the prompt “Key Error” appears in the lower display, it will befor one of the following reasons:
• Parameter not available or locked out• Not in setup mode, press [SET UP] key first
Operation
38 UDC2300 Limit Controller Product Manual 10/00
5.5 Monitoring Your Limit Controller
Annunciators
The following annunciator functions have been provided to help monitor the controller:
Table 5-2 Annunciators
Annunciator Indication
ALM 1 2 A visual indication of each alarmBlinking 1 indicates alarm latched and needs to be acknowledgedbefore extinguishing when the alarm condition ends
F or C A visual indication of the temperature unitsF—Degrees FahrenheitC—Degrees Celsius
Display Mode
The displays and indicators on the operator interface, as shown in Figure 5-1, let you seewhat is happening to your process and how the Limit Controller is responding.
The Limit Controller is a single line display device except when in the SETUP mode orthe [DISPLAY] key is pressed or limit has been reached.
This display can be one of two types:
Display Mode 1
The PV is displayed in the upper display and the lower display is blank.
Display Mode 2
The setpoint is displayed in the upper display and “SP” is displayed inthe lower display.
Viewing the operating parameters
Press the [DISPLAY] key to scroll through the operating parameters:SP* Setpoint
PV Process Variable* You can press or to change the value of this parameter.
Timing out from lower display
The normal variable display will automatically return in the upper display if the[DISPLAY] key is not pressed for 30 seconds.
Operation
10/00 UDC2300 Limit Controller Product Manual 39
Diagnostic Error Messages
The UDC2300 performs background tests to verify data and memory integrity. If there is amalfunction, an error message will be displayed. In the case of more than onesimultaneous malfunction, the messages will be displayed sequentially on the lowerdisplay. If any of these error messages in Table 5-3 occur, refer to Section 7 -Troubleshooting for information to correct the failure.
Table 5-3 Error Messages
Prompt Description
EE FAIL Unable to write to nonvolatile memory.
IN1FL Two consecutive failures of input 1 integration.
CNFERR Configuration Errors—Low limit greater than high limit for PV or SP
IN1RNG Input 1 Out-of-RangeOut-of-range criteria:
Linear range: ±10% out-of-rangeCharacterized range: ±1% out-of-range
PV LIM PV Out-of-RangePV = PV + PV bias
FAILSF Failsafe — conditions for Failsafe are:… EEROM Test Failed… Scratch Pad RAM Test Failed… Configuration Test FailedCheck the “Status” group.
High and Low Limit Indication
When the high or low limit is exceeded, the lower display indicates the word “LIMIT”(blinking). The PV is indicated in the upper display. This will continue until the Out-of-Limit condition exists and you reset the latching relay using the [MAN-AUTO RESET] keyor through the Optional External Reset feature.
The Limit Relay cannot be reset while a Limit condition exists.
Operation
40 UDC2300 Limit Controller Product Manual 10/00
5.6 Operating Your Limit Controller
Operating Principles
The Limit Controller accepts signals from such sources as Thermocouples (T/Cs),Resistance Temperature Detectors (RTDs), and Radiamatics. The equivalent PV signal iscompared with the Limit set point. If above (Hi Limit) or below (Lo Limit), a limit outputrelay is de-energized. When de-energized, the output relay locks out and remains in thisstate until the PV input signal drops below the high limit setpoint or rises above the lowlimit setpoint, and the controller is reset manually from the front of the controller orthrough an optional external switch.
Check the configuration
Make sure the Limit Controller has been configured to handle your process needs. Referto Section 4 - Configuration for prompts and parameters.
• Input Parameters
• Alarm Set Points and type
• Limit Control Type - high or low
• External Reset (Contact Input) - enable or disable
• Power-up Logic - Reset (relay on) or Normal (same as before power down)
• Lockout selection
Power Up Logic
Configurable power-up logic lets you select the latching output relay to require “RESET”or to provide normal operation at power-up. If power to the limit controller fails andpower is reapplied, the controller goes through power up tests then starts in one of thefollowing configurable conditions:
• If you configured RST at setup group “LIMIT”, the lower display will blink “LIMIT”at power up. This will require reset via the [MAN-AUTO RESET] key or external switchto obtain normal operation.
• If you configured NORM at setup group “LIMIT”, the display and limit controllerwill function normally at power up, (that is, no reset of the latching relay is requiredunless a limit has been exceeded). If the limit was latched when power went down,the unit will be in limit at power-up.
Refer to Section 4 - Configuration, subsection 4.5 Limit Parameters Set Up Group underSET UP prompt “LIMIT” and make your selection at FUNCTION prompt “POWRUP.”
Operation
10/00 UDC2300 Limit Controller Product Manual 41
How to Reset the Latching Relay
The latching relay cannot be reset until the PV input signal drops below the high setpoint (High Limit) or rises above the low set point (Low Limit) value.
Press the [MAN-AUTO RESET] key or make contact closure of an external switch if theExternal Reset option is present.
Using the Digital Input Option (External Reset)
The Contact Input option detects the state of external contacts. On contact closure, thecontroller will reset the latching relay if the controller has External Reset enabled. Toallow External Reset (contact input) use the procedure in Table 5-4.
Table 5-4 Using Contact Input Option
Step Operation Press Result
1 Select OptionsSet-up Group
SET UP Until you see:Upper Display = SET
Lower Display = OPTIONS
2 Access theExternal Reset
Prompt
FUNCTION Until you see:Upper Display = ENAB
DIS
Lower Display = EXTRST
3 Change a value [] [] To select ENAB in the upper display
Operation
42 UDC2300 Limit Controller Product Manual 10/00
5.7 Alarm Setpoints
Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm relayis de-energized if setpoint 1 or setpoint 2 is exceeded.
The alarm relay is energized when the monitored value goes into the allowed region bymore than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or normally closed(NC) de-energized using internal jumper placement. See Table 2-4 in the Section 2 –Installation for alarm relay contact information.
There are four alarm setpoints, two for each alarm. The type and state (High or Low) isselected during configuration. See Subsection 4– Configuration for details.
Alarm Setpoints Display
Table 5-5 Procedure for Displaying Alarm Setpoints
Step Operation Press Result
1 Select AlarmSet-up Group
SET UP Until you see:Upper Display = SET
Lower Display = ALARMS
2 Access the AlarmSetpoint Values
FUNCTION To successively display the alarm setpoints and their values.Their order of appearance is shown below.Upper Display = (the alarm setpoint value)Range values are within the range of the selectedparameters:DE (Deviation) value = within Input 1 SpanPV (Process variable) value = Within Input 1 range
3 Change a value [] [] To change any alarm setpoint value in the upper display
4 Return to NormalDisplay
DISPLAY
Input Calibration
10/00 UDC2300 Limit Controller Product Manual 43
6 Input Calibration
6.1 Overview
Introduction
This section describes the field calibration procedures for Input 1.
• Every UDC2300 Limit controller contains all input actuation ranges, which are fullyfactory-calibrated and ready for configuration to range by the user.
• However, these procedures can be implemented if the factory calibration of thedesired range is not within specification.
FIELD CALIBRATION WILL BE LOSTThe field calibration will be lost if a change in input type configuration is implemented at a later time. Theoriginal factory calibration data remains available for later use after a field calibration is done. Seesubsection 6.6 if you want to restore factory calibration.
What’s in this section?
The following topics are covered in this section.
TOPIC See Page
6.1 Overview 43
6.2 Minimum and Maximum Range Values 44
6.3 Preliminary Information 45
6.4 Input #1 Set Up Wiring 47
6.5 Input #1 Calibration Procedure 49
6.6 Restore Factory Calibration 51
WARNING—SHOCK HAZARD !
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, ANDSHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THANONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.
Failure to comply with these instructions could result in death or serious injury.
Input Calibration
44 UDC2300 Limit Controller Product Manual 10/00
Calibration Steps
Use the following steps when calibrating an input.
Step Action
1 Find the minimum and maximum range values for your PV input range from Table 6-1.
2 Disconnect the field wiring and find out what equipment you will need to calibrate.
3 Wire the calibrating device to your controller according to the set up wiring instructionsfor your particular input (Subsection 6.4).
4 Follow the calibration procedure given for Input #1 (Subsection 6.5).
6.2 Minimum and Maximum Range Values
Select the Range Values
You should calibrate the controller for the minimum (0 %) and maximum (100 %) rangevalues of your particular controller. Select the Voltage or Resistance equivalent for 0 %and 100 % range values from Table 6-1. Use these values when calibrating yourcontroller.
Table 6-1 Voltage and Resistance Equivalents for 0 % and 100 % Range Values
PV Input Range Range ValuesSensor Type
°F °C 0 % 100 %
ThermocouplesB 0 to 3300 –18 to 1816 –0.100 mV 13.769 mV
E -454 to 1832 –270 to1000 –9.835 mV 76.373 mV
E (low) -200 to 1100 –129 to593 –6.472 mV 44.455 mV
J 0 to 1600 –18 to871 –0.886 mV 50.060 mV
J (low) 20 to 770 –7 to410 –0.334 mV 22.400 mV
K 0 to 2400 –18 to1816 –0.692 mV 52.952 mV
K (low) –20 to 1000 –29 to538 –1.114 mV 22.255 mV
NiNiMoly (NNM68) 32 to 2500 0 to1371 0.000 mV 71.330 mV
NiNiMoly (low) 32 to 1260 0 to682 0.000 mV 31.820 mV
NiMo-NiCo (NM90) 32 to 2500 0 to1371 0.000 mV 71.773 mV
NiMo-NiCo (low) 32 to 1260 0 to682 0.000 mV 31.825 mV
Nicrosil Nisil (Nic) 0 to 2372 –18 to1300 –0.461 mV 47.513 mV
R 0 to 3100 –18 to1704 –0.090 mV 20.281 mV
S 0 to 3100 –18 to1704 –0.092 mV 17.998 mV
T -300 to 700 –184 to371 –5.341 mV 19.097 mV
Input Calibration
10/00 UDC2300 Limit Controller Product Manual 45
PV Input Range Range ValuesSensor Type
°F °C 0 % 100 %
T (low) -200 to 500 –129 to260 –4.149 mV 12.574 mV
W5W26 0 to 4200 –18 to2315 –0.234 mV 37.075 mV
W5W26 (low) 0 to 2240 –18 to1227 –0.234 mV 22.283 mV
Honeywell Radiamatic
Type RHType RI*
0 to 34000 to 3200
–18 to1871–18 to1760
0.00 mV0.00 mV
57.12 mV60.08 mV
RTD(IEC Alpha=0.00385)
100 ohms100 ohms (low)
200 ohms500 ohms
-300 to 1200-300 to 300-300 to 900-300 to 900
–184 to649–184 to149–184 to482–184 to482
25.18 ohms25.18 ohms50.36 ohms125.90 ohms
274.96 ohms156.90 ohms549.92 ohms1374.80 ohms
Linear
Milliamps(impedance – 249 Ω)
4 to 20 mA0 to 20 mA
4.00 mA0.00 mA
20.00 mA20.00 mA
Millivolts 0 to 10 mV0 to 50 mV0 to 100 mV
0.00 mV0.00 mV0.00 mV
10.00 mV50.00 mV100.00 mV
Volts 1 to 5 Volts0 to 2 Volts0 to 5 Volts
0 to 10 Volts*
1.00 Volts0.00 Volts0.00 Volts0.00 Volts
5.00 Volts2.00 Volts5.00 Volts10.00 Volts
6.3 Preliminary Information
Disconnect the Field Wiring
Tag and disconnect any field wiring connected to the input 1 terminals on the rear of thecontroller.
+_
R
Input 1Connections
876
Figure 6-1 Input 1 Wiring Terminals
Input Calibration
46 UDC2300 Limit Controller Product Manual 10/00
Check the Jumper for Input 1
Before you calibrate Input #1, check the internal jumper for Input 1 to make sure it is setfor the correct input type. The jumper is located at position S101 on the printed wiringboard. Figure 2-2 shows the location of the jumper and position selections.
Equipment Needed
Table 6-2 lists the equipment you will need to calibrate the specific types of inputs thatare listed in the table. You will need a screwdriver to connect these devices to yourcontroller.
Table 6-2 Equipment Needed
Type of Input Equipment Needed
ThermocoupleInputs (Ice Bath)
• A calibrating device with ± 0.02 % accuracy for use as a signalsource such as a Millivolts source.
• Thermocouple extension wire that corresponds with the type ofthermocouple that will be used with the controller input.
• Two insulated copper leads for connecting the thermocoupleextension wire from the ice baths to the mV source.
• Two containers of crushed ice.
ThermocoupleInputs (T/C Source)
• A calibrating device with ± 0.02 % accuracy for use as a signalsource such as a millivolt source.
• Thermocouple extension wire that corresponds with the type ofthermocouple that will be used with controller input.
RTD (ResistanceThermometerDevice)
• A decade box, with ± 0.02 % accuracy, capable of providing steppedresistance values over a minimum range of 0 ohms to 1400 ohmswith a resolution of 0.1 ohm.
• Three insulated copper leads of equal length for connecting thedecade box to the controller.
Milliamperes,Millivolts, Volts, andRadiamatic
• A calibrating device with ± 0.02 % accuracy for use as a signalsource.
• Two insulated copper leads for connecting the calibrator to thecontroller.
• Place current source at zero before switching ON.
• Do not switch current sources OFF/ON while connected to theUDC2300 input.
For Radiamatic inputs only, set Emissivity value to 1.0. See Section 4.6 –Configuration Set Up prompt INPUT1, function prompt EMISS.
Input Calibration
10/00 UDC2300 Limit Controller Product Manual 47
6.4 Input 1 Set Up Wiring
Thermocouple Inputs Using an Ice Bath
Refer to Figure 6-2 and wire the controller according to the procedure given in Table 6-3.Make sure the jumper at S101 is in the #1 position (Figure 2-2).
Table 6-3 Set Up Wiring Procedure for Thermocouple InputsUsing an Ice Bath
Step Action
1 Connect the copper leads to the calibrator.
2 Connect a length of thermocouple extension wire to the end of each copper lead andinsert the junction points into the ice bath.
3 Connect the thermocouple extension wires to the terminals for Input #1.See Figure 6-2.
24872
+_Millivolt
Source87
+
Ice Bath
Copper LeadsThermocoupleExtension Wire
_
Figure 6-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath
Thermocouple Inputs Using a Thermocouple Source
Refer to Figure 6-3 and wire the controller according to the procedure given in Table 6-4.Make sure the jumper at S101 is in the #1 position (Figure 2-2).
Table 6-4 Set Up Wiring Procedure for Thermocouple Inputs usingThermocouple Source
Step Action
1 Connect the thermocouple extension wires to the terminals for Input #1 as shown inFigure 6-3.
24873
ThermocoupleSource
87
+_
ThermocoupleExtension Wire
+_
Figure 6-3 Wiring Connections for Thermocouple Inputs UsingThermocouple Source
Input Calibration
48 UDC2300 Limit Controller Product Manual 10/00
RTD Inputs
Refer to Figure 6-4 and wire the controller according to the procedure given in Table 6-5.Make sure the jumper at S101 is in the #2 position (Figure 2-2).
Table 6-5 Set Up Wiring Procedure for RTD Inputs
Step Action
1 Connect the copper leads from the calibrator to the Input #1 terminals as shown inFigure 6-4.
2 Place current source at zero before switching on.
3 Do not switch current sources ON/OFF while connected to the UDC2300 input.
24875
DecadeResistance
Box
876
+_
R
Copper LeadsEqual Length
Figure 6-4 Wiring Connections for RTD (Resistance Thermometer Device)
Radiamatic, Millivolts, Milliamperes, or Volts
Refer to Figure 6-5 and wire the controller according to the procedure given in Table 6-6.Make sure the jumper at S101 is in the #2 position for, mV, Volts, or the #4 position formA (Figure 2-2).
Table 6-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts,or Volts Inputs (Except 0-10 Volts)
Step Action
1 Connect the copper leads from the calibrator to the Input #1 terminals as shown inFigure 6-5.
2 Place current source at zero before switching on.
3 Do not switch current sources ON/OFF while connected to the UDC2300 input.
For Radiamatic inputs only, set Emissivity value to 1.0. See Section 4.6 – Configuration Set Up promptINPUT1, function prompt EMISS.
Input Calibration
10/00 UDC2300 Limit Controller Product Manual 49
24876
Milliampere,Millivolt, Volt
Source
87
+_
+_
Figure 6-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, orVolts (Except 0 to 10 Volts)
0 to 10 Volts
Refer to Figure 6-6 and wire the controller according to the procedure given in Table 6-7.Make sure the jumper at S101 is in parked position (Figure 2-2).
Table 6-7 Set Up Wiring Procedure for 0 to 10 Volts
Step Action
1 Connect the copper leads from the calibrator to the Input #1 terminals as shown inFigure 6-6.
2 Place current source at zero before switching on.
3 Do not switch current sources ON/OFF while connected to the UDC2300 input.
24877
VoltSource
876
+_
R_
+ 12
3
Figure 6-6 Wiring Connections for 0 to 10 Volts
6.5 Input 1 Calibration Procedure
Preliminary Steps• Apply power and allow the controller to warm up for 30 minutes before you calibrate.
• Please read Section 6.4 – Input 1 Set Up Wiring before beginning the procedure.
• Make sure you have LOCK set to NONE. See Section 4.5 - Limit Set Up Group.
• See Table 6-1 for Voltage vs. Resistance equivalents or 0 % and 100 % range values.
For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100 % value.
Input Calibration
50 UDC2300 Limit Controller Product Manual 10/00
Procedure
The calibration procedure for Input #1 is listed in Table 6-8.
Table 6-8 Input 1 Calibration Procedure
Step Operation Press Result
1 Enter CalibrationMode
SET UP
until you see
Upper Display = CALLower Display = INPUT1
FUNCTION You will see:
Upper Display = DISLower Display = CALIN1
The calibration sequence is enabled and you will see:
Upper Display = BEGNLower Display = CALIN1
At the completion of the sequence, the selectionautomatically reverts to disable.
2 Calibrate 0 % FUNCTION You will see:
Upper Display = APLYLower Display = IN1ZRO
• Adjust your calibration device to an output signal equal tothe 0 % range value for your particular input sensor. SeeTable 6-1 for Voltage, Degrees, or Resistanceequivalents for 0 % range values.
• Wait 15 seconds, and then go to the next step.
3 Calibrate 100 % FUNCTION You will see:
Upper Display = APLYLower Display = IN1SPN
• Adjust your calibration device to an output signal equal tothe 100 % range value for your particular input sensor.See Table 6-1 for Voltage, Degrees, or Resistanceequivalents for 100 % range values.
• Wait 15 seconds, and
If … Then …
you are calibrating a Thermocouple input go to step 4
you are calibrating other than a go to step 5Thermocouple input
Input Calibration
10/00 UDC2300 Limit Controller Product Manual 51
Step Operation Press Result
4 Check the ColdJunctionTemperature
FUNCTION The calculations for zero and span are now stored and youwill see:
Upper Display = The cold junction temperature at the rearterminalsLower Display = CJTEMP
The value in the upper display is in tenths of a degree. It isthe current reading of the temperature as measured at thethermocouple terminals and recognized by the controller.You can change this value, if it is in error, using the [] []keys.
The accuracy of the controller is directly affected by theaccuracy of this value. Change this value only if the zero andspan calibration procedures did not bring the controller withinthe specified accuracy requirements.
5 Exit theCalibration Mode
FUNCTION
then
The controller stores the calibration constants and exits thecalibration mode.
DISPLAY
6.6 Restore Factory Calibration
Introduction
The factory calibration constants for all the input actuation types that can be used with thecontroller are stored in its nonvolatile memory. Thus, you can quickly restore the“Factory Calibration” for a given input actuation type by simply changing the actuationtype to another type and then changing it back to the original type.
Refer to Table 6-9 Restore Factory Calibration for procedure.
A restored factory calibration overwrites any previous field calibration done for the input and may changethe High and Low Range Limits. Be sure to protect any field calibration from accidental overwrites byconfiguring the appropriate LOCKOUT selection after calibration. See the Section 4 - Configuration forspecific instructions to set the lockout.
Input Calibration
52 UDC2300 Limit Controller Product Manual 10/00
Table 6-9 Restore Factory Calibration
Step Operation Press Result
1 Set LOCKOUT toNONE
SET UP until you see:Upper Display = SET UPLower Display = LOCK
FUNCTION Until you see:
Upper Display = one of the following:NONE – all parameters are read/writeCAL - all parameters are read/write except CalibrationCONF – configuration parameters are Read Only; nowrites permitted+SP – Only the Lockout group is available for read/write.Setpoint value is Read Only.
Lower Display = LOCK
[] [] Until NONE is in the upper display
2 Enter INPUT 1Setup Group
SET UP until you see:Upper Display = SET UPLower Display = INPUT 1
FUNCTION until you see:Upper Display = the current selectionLower Display = IN1TYP
[] [] to change the current selection to another selection
3 Scroll throughFunctions
FUNCTION until the lower display rolls through the rest of the functionsand returns to
Upper Display = the new selectionLower Display = IN1TYP
[] [] until you change the input selection in the upper display backto the proper selection. You will see:
Upper Display = Original Input Selection that matches yourtype of sensor.Lower Display = IN1TYP
4 Return to NormalOperation
DISPLAY to return to Normal operating mode.
The factory calibration will be restored. If the problem is notcorrected, contact the Honeywell Technical AssistanceCenter.
1-800-423-9883 USA and Canada
Troubleshooting/Service
10/00 UDC2300 Limit Controller Product Manual 53
7 Troubleshooting/Service
7.1 Overview
Introduction
Instrument performance can be adversely affected by installation and applicationproblems as well as by hardware problems. We recommend that you investigate theproblems in the following order:
• installation related problems
• application related problems
• hardware and software related problems
and use the information presented in this section to solve them. If a replacement of anypart is required, follow the procedures listed under “Parts Replacement Procedures.”
What’s in this section?
The following topics are covered in this section.
TOPIC See Page
7.1 Overview 53
7.2 Troubleshooting Aids• Overall Error Messages• Controller Failure Symptoms• Customer Support• Determining the Software Version Number
54
7.3 Power-up Tests 56
7.4 Status Tests 56
7.5 Background Tests 57
7.6 Controller Failure Symptoms 58
7.7 Troubleshooting Procedures• Power Failure• Alarm Relay Output Failure• Keyboard Failure
59
Troubleshooting/Service
54 UDC2300 Limit Controller Product Manual 10/00
Installation related problems
Read the Installation section in this manual to make sure the UDC2300 has been properlyinstalled. The installation section provides information on protection against electricalnoise, connecting external equipment to the controller, and shielding and routing externalwiring.
System noise induced into the controller will result in diagnostic error messages recurring. If the diagnosticerror messages can be cleared, it indicates a “soft” failure and is probably noise related.
If system noise is suspected, completely isolate the controller from all field wiring. Use calibration sourcesto simulate PV and check all controller functions.
Application related problems
Review the application of the controller; then, if necessary, direct your questions to thelocal sales office.
Hardware and software related problems
Use the troubleshooting error message prompts and controller failure symptoms toidentify typical failures which may occur in the controller. Follow the troubleshootingprocedures to correct them.
7.2 Troubleshooting Aids
Overall error messages
An error message can occur:
• at power-up, see Subsection 7.3
• when the Status Tests are requested. See Subsection 7.4
• during continuous background tests while in normal operation. See Subsection 7.5
Controller failure symptoms
Other failures may occur that deal with the Power, Output, or Alarms. Refer to thecontroller failure symptom in Table 7-4 to determine what is wrong and thetroubleshooting procedures to use to correct the problem.
Check installation
If a set of symptoms still persists, refer to Section 2 - Installation and ensure properinstallation and proper use of the controller in the system.
Troubleshooting/Service
10/00 UDC2300 Limit Controller Product Manual 55
Customer support
If you cannot solve the problem using the troubleshooting procedures listed in thissection, you can get technical assistance by dialing 1-800-423-9883 USA and Canada.
An engineer will discuss your problem with you. Please have your complete modelnumber, serial number, and Software version available. The model and serialnumbers can be found on the chassis nameplate. The software version can be viewedunder Setup Group “Status.” See Table 7-1.
If it is determined that a hardware problem exists, a replacement controller or part will beshipped with instructions for returning the defective unit.
Do not return your controller without authorization from Honeywell’s TechnicalAssistance Center or until the replacement has been received.
For a list of frequently asked questions and their answers, dial Honeywell’s Faxback 24hour Service:
1-888-423-9883 USA
Or check out Honeywell’s web site at http://www.honeywell.com/sensing.
Determining the software version
Table 7-1 lists the procedure for identifying the software version number.
Table 7-1 Procedure for Identifying the Software Version
Step Operation Press Result
1 SelectSTATUSSet Up Group
SET UP Upper Display = READLower Display = STATUS
2 Read the softwareversion
FUNCTION You will see:
Upper Display = Software version numberLower Display = A2xx Limit Controller
Please give this number to the Customer Support person. Itwill indicate which version of UDC2300 you have and helpthem determine a solution to your problem.
Troubleshooting/Service
56 UDC2300 Limit Controller Product Manual 10/00
7.3 Power-up Tests
What happens at power-up
When the controller is powered-up, the UDC2300 software to ensure memory integrityruns three tests.
Test failures
If any of these three tests fail, TEST will appear momentarily in the upper display, and amessage indicating which test failed will appear in the lower display. (see 7.4). Then“DONE” will appear in the lower display.
7.4 Status Tests
Introduction
When required, the results of these tests can be checked to determine the reason thecontroller has gone to Failsafe.
How to check the status tests
The procedure in Table 7-2 tells you how to display the results of the status tests.
Table 7-2 Procedure for Displaying the Status Test Results
Step Operation Press Result
1 SelectSTATUSSet Up Group
SET UP Upper Display = READLower Display = STATUS
2 Read the testresults
FUNCTION You will see:
Upper Display = NO or YES YES indicates a failureLower Display = FAILSF
FUNCTION Upper Display = PASS or FAILLower Display = TEST
Troubleshooting/Service
10/00 UDC2300 Limit Controller Product Manual 57
7.5 Background Tests
Introduction
The UDC2300 performs ongoing background tests to verify data and memory integrity.If there is a malfunction, an error message will be displayed (blinking) in the lowerdisplay.
In the case of simultaneously malfunctions, the messages will appear in sequence in thelower display. Table 7-3 lists these background tests, the reason for their failure, and howto correct the problem.
Table 7-3 Background Tests
LowerDisplay
Reason for Failure How to Correct the Problem
EEFAIL Unable to write to non-volatilememory. Anytime you change aparameter and it is not accepted, youwill see EE FAIL.
1. Check the accuracy of the parameter and re-enter.
2. Try to change something in configuration.
3. Run through STATUS tests to re-write toEEPROM.
FAILSF This error message shows wheneverthe controller goes into a Failsafemode of operation. This will happen if:
• RAM test failed
• Configuration test failed
• Calibration test failed
• Burnout configured for noneand the input failed.
1. Run through STATUS check to determine thereason for the failure.
2. Press the [SET UP] key until STATUSappears in the lower display.
3. Press the FUNCTION] key to see whetherthe tests pass or fail, then run through theSTATUS codes a second time to see if theerror cleared.
IN1FL Two consecutive failures of input 1integration; i.e., cannot make analog todigital conversion. This will happen if:
• Upscale or Downscale burnoutis selected
• Input not configured correctly
1. Make sure the actuation is configuredcorrectly. See Section 4 - Configuration.
2. Make sure the input is correct.
3. Check for gross over-ranging. Check S101jumper position. See Figure 2-2 JumperPlacements
4. Replace factory calibration. See Section 6.6.
CNFERR • PV low limit is > PV high limit• SP low limit is > SP high limit• Output low limit > Output high limit
1. Check the configuration for each item andreconfigure if necessary.
Troubleshooting/Service
58 UDC2300 Limit Controller Product Manual 10/00
LowerDisplay
Reason for Failure How to Correct the Problem
IN1RNG Input 1 out of range. The process inputis outside the range limits.
1. Make sure the range and actuation areconfigured properly.
2. Check the input source.
3. Restore the factory calibration.(See Subsection 6.6.)
4. Field calibrate.See Section 6- Input Calibration.
PV LIM PV out of range.PV = INP1 + INP1 BIAS
1. Make sure the input signal is correct.
2. Make sure the Bias settings are correct.
3. Recheck the calibration. Use Bias of 0.0
7.6 Controller Failure Symptoms
Introduction
In addition to the error message prompts, there are failure symptoms that can be identifiedby noting how the controller displays and indicators are reacting.
Symptoms
Compare your symptoms with those shown in Table 7-4.
Table 7-4 Controller Failure Symptoms
UpperDisplay
LowerDisplay
Indicators ControllerOutput
ProbableCause
Trouble-shooting
Procedure
Blank Blank Off None Power Failure 1
OK DisplayedOutput
disagrees withcontroller
output
OK ControllerOutput
disagrees withdisplayed
output
Relay Output 2
OK OK OK External Alarmfunction doesnot operate
properly
Malfunction inalarm output
3
Display does not function when a key is pressed KeyboardMalfunction
4
Troubleshooting/Service
10/00 UDC2300 Limit Controller Product Manual 59
Other symptoms
If a set of symptoms or prompts other than the one you started with appears whiletroubleshooting, re-evaluate the symptoms. This may lead to a different troubleshootingprocedure.
If the symptom still persists, refer to the installation section in this manual to ensureproper installation and proper use of the controller in your system.
7.7 Troubleshooting Procedures
Introduction
The troubleshooting procedures are listed in numerical order as they appear in Table 7-4.Each procedure lists what to do if you have that particular failure and how to do it orwhere to find the data needed to accomplish the task.
WARNING—SHOCK HAZARD !
TROUBLESHOOTING MAY REQUIRE ACCESS TO HAZARDOUSLIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BYQUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCHMAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE SERVICING.
Failure to comply with these instructions could result in death or serious injury.
Equipment needed
You will need the following equipment in order to troubleshoot the symptoms listed inthe tables that follow:
• Calibration sources – T/C, mV, Volt, etc.
• Voltmeter
Troubleshooting/Service
60 UDC2300 Limit Controller Product Manual 10/00
Procedure #1
Table 7-5 explains how to troubleshoot power failure symptoms.
Table 7-5 Troubleshooting Power Failure Symptoms
Step What to do How to do it
1 Check the AC line voltage. Use a voltmeter to measure the AC voltage acrossterminals L1 and L2 on the rear terminal panel of thecontroller.
Check the earth ground connection.
2 Make sure the chassis plugs intothe rear of the case properly.
Withdraw the chassis and visually inspect thecontroller board and the inside of the case.
3 Check the system for Brown-outs, heavy load switching, etc.,and conformance to installationinstructions.
Refer to Section 2 - Installation.
4 Change Main board. Installation instructions supplied with new board.
Procedure #2
Table 7-6 explains how to troubleshoot Latching Output Relay failure.
Table 7-6 Troubleshooting Latching Output Relay Failure
Step What to do How to do it
1 Make sure all the configurabledata stored in the controller iscorrect. Reconfigure, ifnecessary.
Refer to Section 4 - Configuration to check all thisdata and how to reconfigure.
2 Check that the Latching Relayactuates properly.
Move the setpoint above or below the PV value,depending on the type of Limit Control configured.Listen for the click of the relay as the setpoint ismoved above or below the PV.
3 Check the Latching Relayjumper position (NO or NC).
Refer to subsection 2.4 Limit Control and AlarmRelay Contact Information for Relay Contactinformation.
Troubleshooting/Service
10/00 UDC2300 Limit Controller Product Manual 61
Procedure #3
Table 7-7 explains how to troubleshoot Alarm Relay Output failure.
Table 7-7 Troubleshooting Alarm Relay Output Failure
Step What to do How to do it
1 Check the alarm configurationdata. If it is correct, check thefield wiring.
Reconfigure if necessary.Refer to Section 4 - Configuration for details.
2 Check that the applicable alarmrelay actuates properlydepending on what you have setat prompt AxSxTYPE.
If it does, check the field wiring.
If the alarm type is set for PV, place the controller inmanual mode. Vary the input to raise and lower thePV around the setpoint. Listen for a click from therelay as the PV moves in either direction and notethat the proper ALM1 or ALM2 is lit.
EXAMPLE: If the alarm is set for MAN, put thecontroller into manual mode. The alarm light is ON.Put the controller into automatic mode and the alarmlight is OFF.
3 Check the contacts. Make sure the NO or NC contact wiring is correct.
Refer to Section 2 - Installation for relay jumperplacement and relay contact information.
4 Change Main board. Installation instructions supplied with new board.
Procedure #4
Table 7-8 explains how to troubleshoot a Keyboard failure.
Table 7-8 Troubleshooting a Keyboard Failure
Step What to do How to do it
1 Make sure the keyboard isconnected properly.
Withdraw the chassis from the case and visuallyinspect the connection.
2 Controller Keyboard or specifickeys may be LOCKED OUT viathe security code.
Use your four-digit security code number to changethe lockout level. Refer to Section 4 – Configuration.
Using “1000” as a security code number will overridethe 4-digit code previously entered.
3 Replace the display/keyboard ifany keys are not functioning.
Installation instructions supplied with newdisplay/keyboard.
Troubleshooting/Service
62 UDC2300 Limit Controller Product Manual 10/00
Parts List
10/00 UDC2300 Limit Controller Product Manual 63
8 Parts List
8.1 Exploded View
Introduction
Figure 8-1 is an exploded view of the UDC2300 Limit Controller. Each part is labeledwith a key number. The part numbers are listed by key number in Table 8-1. Parts notshown are listed in Table 8-2.
Figure 8-1 UDC2300 Exploded View
Table 8-1 Parts Identification
KeyNumber
Part Number Description
1 30756667-503 Bezel Assembly (Gray)
2 51309766-501 Display/Keyboard
3 51309782-501
51309831-501
Auxiliary Output/Digital Input PWA
RS-422/485 Communications PWA
4 51404896-501 Case Assembly (includes 30755050-001 Mounting Kit)
1
2
3
4
Parts List
64 UDC2300 Limit Controller Product Manual 10/00
Table 8-2 Parts Not Shown
Part Number Description
30755223-003 DIN Adapter (Gray)
30756683-001 NEMA 3 Gasket (Panel to Case)
30755050-001 Mounting Kit
30757215-001 NEMA 4 Adapter Kit
30756679-501 Open Collector Output
30756764-002 Rear Terminal Cover Kit
30756018-001 SS Relay 10 Amp (external)
30756725-501 SS Relay 1 Amp (internal)
30754465-501 0-10 Volt Input resistor assembly (100K pair)
30754142-003 Terminal Strip Assembly
30755306-501 Electro-mechanical Relay (5 Amp)
Index
10/00 UDC2300 Limit Controller Product Manual 65
9 Index
AAccuracy, 4Alarm 2Relay Action, 6Alarm Blocking, 32Alarm Hysteresis, 32Alarm Output Connections, 15Alarm Relay Contact Information, 8Alarm Relay Output failure, 61alarm setpoints, 42Alarm Setpoints, 42Alarms Set Up Group, 31Alarmx Setpoint x State, 31Alarmx Setpointx Type, 31Alarmx Setpointx Value, 31Annunciators, 38Application related problems, 54Auxiliary Output, 28Auxiliary Output High Scaling Factor, 28Auxiliary Output Low Scaling Factor, 28
Bbackground tests, 57Baud Rate, 29Bias on Input 1, 27Burnout Protection, 27
CCalibration Mode, 50, 52Calibration Steps, 44CE Conformity, 4CE Conformity (Europe), 2Cold Junction Temperature, 51Communications Override Units, 30Communications Set Up Group, 29Communications State, 29Composite Wiring Diagram, 12Configuration, 21Configuration Lockout, 24Configuration Procedure, 23Configuration Prompt Hierarchy, 22Configuration Record Sheet, 33Contact Input, 41Control/Alarm Circuit Wiring, 11Controller Failure Symptoms, 58Controller Grounding, 11Customer support, 55
DDecimal Point Selection, 26Digital Input, 28Digital Input Option, 41Dimensions, 9Display Mode, 38displays and indicators, 36DOWNSCALE BURNOUT, 27
EElectrical Considerations, 11Electrical Noise Precautions, 11Electromechanical Relay Output, 14Emissivity, 27EMISSIVITY, 27equipment you will need to calibrate, 46Error Messages, 39Exploded View, 63External Interface Option Connections, 16External Reset, 41External Wiring, 11
F, GFactory calibration, 51Field Wiring, 45Filter for Input 1, 27Function Prompts, 22
HHigh and Low Limit Indication, 39High Limit Controller, 1HIGH SETPOINT LIMIT, 25
IInitial Start-up, 19Input 1 Actuation Type, 26Input 1 Calibration Procedure, 49, 50Input 1 Connections, 13Input 1 High Range Value, 27Input 1 Low Range Value, 27Input 1 Set Up Group, 26Input 1 Set Up Wiring, 47Input 1 Wiring Terminals, 45Input Calibration, 43Input I Jumper Placement, 6Installation, 3
Index
66 UDC2300 Limit Controller Product Manual 10/00
Installation related problems, 54internal jumper (W101) for CONTROL, 6
JJumper for Input 1, 46Jumper Placement, 7
KKey error, 37Key Error Message, 20Key Functions, 20Keyboard failure, 61
LLatching Alarm for Output, 32Limit Control and Alarm Relay Contact Information,
8Limit Control Application Diagram, 17Limit Control Relay Contact Information, 8Limit Control relays, 8Limit Controller Wiring, 17Limit Set Up Group, 25Local Loopback Test, 30Lock Set Up Group, 24lockout feature, 37Lockout levels, 37Low Limit Controller, 1LOW SETPOINT LIMIT, 25
MMains Power Supply, 11, 13Milliampere, Millivolt, Volts, and Radiamatic, 46Minimum and Maximum Range Values, 44Model Number Interpretation, 5Monitoring Your Limit Controller, 38Mounting, 9Mounting Method, 10Mounting Procedure, 10
NNormal Display, 25
OOpen Collector Relay Output, 15Operating Limits, 4Operating Principles, 40Operating the Limit Controller, 35Operating Your Limit Controller, 40Operator Interface, 2, 20, 36Options Set Up Group, 28
P, QParity, 29Parts Identification, 63Parts List, 63Permissible Wiring Bundling, 12Physical Considerations, 9power failure symptoms, 60Power Line Frequency, 27Power Up Logic, 25, 40Powering Up, 19Power-up Tests, 56Pre-installation Information, 4Preliminary Checks, 6
RRange Values, 44relay contacts, 42Reset the Latching Relay, 41Response Delay, 29RTD (Resistance Thermometer Device), 46RTD Inputs, 48
SSECURITY CODE, 24, 36Security Code Entry, 37Set Up Group, 22Shed Time, 29Shock hazard warning, 59software version number, 55Solid State Relay Output, 14SP High Limit, 25SP Low Limit, 25Specifications, 4start up, 19Station Address, 29Status Tests, 56Suppression Devices, 11
Index
10/00 UDC2300 Limit Controller Product Manual 67
TTemperature Units, 26Test failures, 56Test Failures, 19Thermocouple Inputs (Ice Bath), 46Thermocouple Inputs (T/C Source), 46Thermocouple Inputs Using a Thermocouple Source,
47Thermocouple Inputs Using an Ice Bath, 47Time Proportional Output failure, 60Timing out from lower display, 38Transmitter Characterization, 26Troubleshooting Aids, 54troubleshooting procedures, 59Troubleshooting/Service, 53Type of Limit Controller, 25
UUDC2300 Limit Controllers, 1UPSCALE BURNOUT, 27
VViewing the operating parameters, 38Voltage and Resistance Equivalents for 0% and 100%
Range Values, 44
W, X, Y, ZWARNING—SHOCK HAZARD, 59Wiring, 11Wiring Bundling, 12Wiring Connections for 0 to 10 Volts, 49Wiring Connections for Radiamatic, Milliampere,
Millivolts, or Volts (Except 0 to 10 Volts), 49Wiring Connections for RTD (Resistance
Thermometer Device), 48Wiring Diagrams, 12
Index
68 UDC2300 Limit Controller Product Manual 10/00
.
HSM8 HONEYWELL SERVICE CENTERS
ARGENTINA BULGARIA GERMANY
HONEYWELL S.A.I.C.BELGRANO 1156BUENOS AIRESARGENTINATel. : 54 1 383 9290
HONEYWELL EOOD14, Iskarsko ChaussePOB 79BG- 1592 SofiaBULGARIATel : 359-791512/ 794027/ 792198
HONEYWELL AGKaiserleistrasse 39D-63067 OFFENBACHGERMANYTel. : 49 69 80 640
ASIA PACIFIC CANADA HUNGARY
HONEYWELL ASIA PACIFIC Inc.Room 3213-3225Sun Kung Kai CentreN° 30 Harbour RoadWANCHAIHONG KONGTel. : 852 829 82 98
HONEYWELL LIMITEDTHE HONEYWELL CENTRE529 Mc Nicoll AvenueM2H 2C9 NORTH YORK,ONTARIOCANADATel. : 416 502 5200
HONEYWELL KftGogol u 13H-1133 BUDAPESTHUNGARYTel. : 36 1 451 43 00
AUSTRALIA CZECH REPUBLIC ICELAND
HONEYWELL LIMITED5 Thomas Holt DriveNorth Ryde SydneyNSW AUSTRALIA 2113Tel. : 61 2 353 7000
HONEYWELL, Spol.s.r.o.Budejovicka 1140 21 Prague 4Czech RepublicTel. : 42 2 6112 3434
HONEYWELLHataekni .hfArmuli 26PO Box 8336128 reykjavikIcelandTel : 354 588 5000
AUSTRIA DENMARK ITALY
HONEYWELL AUSTRIA G.m.b.H.Handelskai 388A1020 VIENNAAUSTRIATel. : 43 1 727 800
HONEYWELL A/SAutomatikvej 1DK 2860 SoeborgDENMARKTel. : 45 39 55 56 58
HONEYWELL S.p.A.Via P. Gobetti, 2/b20063 Cernusco Sul NaviglioITALYTel. : 39 02 92146 1
BELGIUM FINLAND MEXICO
HONEYWELL S.A.3 Avenue de BourgetB-1140 BRUSSELSBELGIUMTel. : 32 2 728 27 11
HONEYWELL OYRuukintie 8FIN-02320 ESPOO 32FINLANDTel. : 358 0 3480101
HONEYWELL S.A. DE CVAV. CONSTITUYENTES 900COL. LOMAS ALTAS11950 MEXICO CITYMEXICOTel : 52 5 259 1966
BRAZIL FRANCE THE NETHERLANDS
HONEYWELL DO BRAZIL AND CIARua Jose Alves Da ChunhaLima 172BUTANTA05360.050 SAO PAULO SPBRAZILTel. : 55 11 819 3755
HONEYWELL S.A.Bâtiment « le Mercury »Parc Technologique de St AubinRoute de l’Orme (CD 128)91190 SAINT-AUBINFRANCETel. from France: 01 60 19 80 00From other countries: 33 1 60 19 80 00
HONEYWELL BVLaaderhoogtweg 181101 EA AMSTERDAM ZOTHE NETHERLANDSTel : 31 20 56 56 911
HSM8 HONEYWELL SERVICE CENTERS
NORWAY REPUBLIC OF SOUTHAFRICA
SWEDEN
HONEYWELL A/SAskerveien 61PO Box 263N-1371 ASKERNORWAYTel. : 47 66 76 20 00
HONEYWELLSouthern AfricaPO BOX 138Milnerton 7435REPUBLIC OF SOUTH AFRICATel. : 27 11 805 12 01
HONEYWELL A.B.S-127 86 SkarholmenSTOCKHOLMSWEDEN
Tel. : 46 8 775 55 00
POLAND ROMANIA SWITZERLAND
HONEYWELL Sp.z.o.oUI Domainewksa 4102-672 WARSAWPOLANDTel. : 48 22 606 09 00
HONEYWELL OfficeBucharest147 Aurel Vlaicu Str., Sc.Z.,Apt 61/62R-72921 BucharestROMANIATel : 40-1 211 00 76/ 211 79 43
HONEYWELL A.G.Hertistrasse 28304 WALLISELLENSWITZERLANDTel. : 41 1 831 02 71
PORTUGAL RUSSIA TURKEY
HONEYWELL PORTUGAL LDAEdificio Suecia IIAv. do Forte nr 3 - Piso 32795 CARNAXIDEPORTUGALTel. : 351 1 424 50 00
HONEYWELL INC4th Floor AdministrativeBuiliding of AO "Luzhniki"Management24 Luzhniki119048 MoscowRUSSIATel : 7 095 796 98 00/01
HONEYWELL Otomasyon veKontrolSistemlen San ve Tic A.S.(Honeywell Turkey A.S.)Emirhan Cad No 144Barbaros Plaza C. Blok Kat 18Dikilitas 80700 IstanbulTURKEYTel : 90-212 258 18 30
REPUBLIC OF IRELAND SLOVAKIA UNITED KINGDOM
HONEYWELLUnit 1Robinhood Business ParkRobinhood RoadDUBLIN 22Republic of IrelandTel. : 353 1 4565944
HONEYWELL LtdMlynske nivy 73PO Box 75820 07 BRATISLAVA 27SLOVAKIATel. : 421 7 52 47 400/425
HONEYWELLUnit 1,2 &4 Zodiac HouseCalleva ParkAldermastonBerkshire RG7 8HWUNITED KINGDOMTel : 44 11 89 81 95 11
REP. OF SINGAPORE SPAIN U.S.A.
HONEYWELL PTE LTDBLOCK 750E CHAI CHEE ROAD06-01 CHAI CHEE IND. PARK1646 SINGAPOREREP. OF SINGAPORETel. : 65 2490 100
HONEYWELL S.AFactoryJosefa Valcarcel, 2428027 MADRIDSPAINTel. : 34 91 31 3 61 00