uk_m09-1150b

Upload: kalyana-sundaram

Post on 04-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 uk_M09-1150B

    1/32

    NC

    8400 steel cooling towerINSTALLATION - OPERATION - MAINTENANCE

    uk_M09-1150B ISSUE D 8/2012 READ AND U NDERSTAND THIS MANUAL PRIOR TO OPERAT ING OR SERVICING THIS PRODUCT.

    USER MANUAL

  • 7/29/2019 uk_M09-1150B

    2/32

    2

    contents

    Tower Location ............................................................................................................5

    Tower Shipment...........................................................................................................5

    Receiving Tower ..........................................................................................................5

    Hoisting Tower .............................................................................................................5

    Tower Installation.........................................................................................................6Tower Start-Up .........................................................................................................13

    Tower Operation .......................................................................................................15

    Wintertime Operation..............................................................................................17

    Water Treatment and Blowdown ..........................................................................19

    Cooling Tower Cleaning .........................................................................................21

    Schedule o Tower Maintenance ..........................................................................24

    Motor Relubrication Instructions ..........................................................................26

    Seasonal Shutdown Instructions .........................................................................27

    Prolonged Shutdown ..............................................................................................28

    Maintenance Schedule ...........................................................................................29

    Troubleshooting ........................................................................................................30

    Additional Inormation .............................................................................................32

    NoteThis manual contains vital inormation or the proper installation and

    operation o your cooling tower. Careully read the manual beore

    installation or operation o the tower and ollow all instructions.

    Save this manual or uture reerence.

    Indicates presence o a hazard which can cause severe personal

    injury, death or substantial property damage i ignored.

    Indicates presence o a hazard which will or can cause personal

    injury or property damage i ignored.

    Indicates special instructions on installation, operation or main-

    tenance which are important but not related to personal injury

    hazards.

    Warning

    Caution

    Note

    The ollowing dened terms are used throughout this manual to bring attention

    to the presence o hazards o various risk levels, or to important inormation

    concerning the lie o the product.

  • 7/29/2019 uk_M09-1150B

    3/32

    3

    preparation

    The Marley NC cooling tower purchased or this installation represents the cur-

    rent state o the art in crossfow, induced drat cooling tower design. Thermally

    and operationally, it is the most ecient cooling tower o its class.

    These instructionsas well as those oered separately on motors, ans, Geare-

    ducers, couplings, drive shats, foat valves, etc.are intended to assure that

    the tower serves you properly or the maximum possible time. Since product

    warrantability may well depend upon your actions, please read these instruc-

    tions thoroughly prior to operation.

    I you have questions about the operation and/or maintenance o this tower,

    and you dont nd the answers in this manual, please contact your Marleysales representative. When writing or inormation, or when ordering parts,

    please mention tower serial number shown on the nameplate located on the

    access door.

    Saety First

    The location and orientation o the cooling tower can aect the saety o those

    responsible or installing, operating or maintaining the tower. However, since

    SPX Cooling Technologies does not determine the location or orientation o

    the tower, we cannot be responsible or addressing those saety issues thatare aected by the towers location or orientation.

    WARNING

    The ollowing saety issues should be considered by those respon-

    sible or designing the tower installation.

    accesstoandfromthefandeck

    accesstoandfrommaintenanceaccessdoors

    thepossibleneedforladders(eitherportableorpermanent)to

    gainaccesstothefandeckormaintenanceaccessdoors

    thepossibleneedforhandrailsaroundthefandeck

    thepossibleneedforexternalaccessplatforms

    potentialaccessproblemsduetoobstructionssurroundingthe

    tower

    lockoutofmechanicalequipment

    thepossibleneedforsafetycagesaroundladders

    theneedtoavoidexposingmaintenancepersonneltothepoten-

    tially unsae environment inside the tower.

    Warning

  • 7/29/2019 uk_M09-1150B

    4/32

    4

    preparation

    Those are only some o the saety issues that may arise in the design

    process. SPX strongly recommends that you consult a saety engineer

    to be sure that all saety considerations have been addressed.

    Several options are available that may assist you in addressing some o these

    personnel saety concerns, including:

    a handrail system around the perimeter o the an deck with either one or

    two ladders or access to the deck

    ladder extensions (used where the base o the tower is elevated)

    saety cages or an deck ladders

    external lube lines

    an cylinder extensions

    fow control/balancing valves

    an barrier

    access door platorm

    motor located outside the tower

    external motor access platorm

    Tower Location

    Space available around the tower should be as generous as possible to pro-

    mote ease o maintenanceand to permit reedom o airfow into and through

    the tower. I you have questions about the adequacy o the available space

    and the intended conguration o the tower, please contact your Marley sales

    representative or guidance.

    Prepare a stable, level support oundation or the tower, utilizing weight, wind

    load, and dimensional inormation appearing on appropriate Marley submittal

    drawings. Supports must be level to insure proper operation o the tower.

    The cooling tower must be located at such distance and direction

    to avoid the possibility o contaminated tower discharge air being

    drawnintobuildingfreshairintakeducts.Thepurchasershouldob-

    tain the services o a Licensed Proessional Engineer or Registered

    Architect to certiy that the location o the tower is in compliance

    with applicable air pollution, re, and clean air codes.

    Warning

  • 7/29/2019 uk_M09-1150B

    5/32

    5

    Tower Shipment

    Unless otherwise specied, NC towers ship by truck (on fat bed trailers),

    which lets you receive, hoist, and install the tower in one continuous operation.

    Single-cell towers ship on one truck. Multicell towers, depending on their size,

    may require more than one truck.

    Responsibility or the condition o the tower upon its arrival belongs to the

    truckeras does the coordination o multiple shipments, i required.

    Receiving TowerPrior to unloading the tower rom the delivering carrier, inspect the shipment

    or evidence o damage in transit. I damage is apparent, note the reight bill

    accordingly. This will support your uture recovery claim.

    Find and remove the installation instruction drawings and bills o material

    located in a plastic tote in the cold water basin. This inormation should be

    kept or uture reerence and maintenance purposes.

    Hoisting Tower

    NC8411 through NC8414 models consist o two modules per cell. The uppermodule includes hoisting clips at the top o the module. The hoisting clips on

    the lower module are located near the bottom on the sides o the cold water

    basin. All other models ship in a single module.

    NC upper and lower modules must be hoisted and set separately.

    Do not preassemble modules prior to hoisting.

    The hoisting clips or NC8409 are located near the bottom o the tower on

    the cold water basin sides. The hoisting clips or all other models are located

    at the top o the tower. A Hoisting-Installation label which has hoistingdimensional inormation is located on the side casing near the tower cen-

    terline. Remove tower rom the carrier and hoist into place according to the

    instructions on the label.

    Hoisting clips are provided or ease o unloading and positioning

    tower.Foroverheadlifts orwhereadditional safety is required,

    saety slings should also be placed under the tower. Under no

    circumstances should you combine the top and bottom modules

    o modular models and attempt to hoist them at the same time by

    utilizing the hoisting clips alone!

    Warning

    receiving and hoisting

    Caution

  • 7/29/2019 uk_M09-1150B

    6/32

    6

    Tower Installation

    These installation instructions are intended to help you prepare

    before your towerarrives. If discrepanciesexist between these

    instructions and those shipped with the tower, the instructions

    shipped with the tower will govern.

    1. Prior to placement o the tower, conrm that the supporting platorm is

    level, and that the anchor bolt holes are correctly located in accordance

    with Marley drawings.

    2. Place tower (or bottom module o NC8411 through NC8414 models)

    on your prepared supports, aligning anchor bolt holes with those in your

    supporting steel. Make sure that the orientation agrees with your intended

    piping arrangement. Attach tower to supporting steel with our 34"diameter

    bolts and fat washers (by others). Position fat washers between the bolt

    head and the tower basin fange.

    3. NC8411 through NC8414 models only.Beore setting top module in place

    on bottom module, clean any debris rom the underside o the top module ll,

    skid and beams and rom the top o the bottom module and remove shipping

    cover rom bottom o top modulereplace asteners at side o module toprevent leaks. Place top module on the top peripheral bearing surace (actory-

    installed gasket) o bottom module, aligning mating holes as it is set in place.

    (Make sure that the orientation o the top module agrees with your intended

    piping arrangement. Sections are 180 reversible with respect to each other.)

    Attach top module to bottom module with asteners providedaccording to

    NC Field Installation Manual Assembly Instructions.

    I tower purchased is one an cell only, ignore steps 4 through 8.

    4. I collection basins are to be equalized by the use o Marley standard

    fumes, unbolt the coverplate rom the basin o the cell just installed. The

    coverplate is located in the center o the basin side.

    5. Unbolt temporary coverplate rom the basin o the 2nd cell and set 2nd

    cell (or bottom module o 2nd cell) in place. Align anchor bolt holes and

    fume openings in basin sides.

    6. Install fume according to Field Installation Manual instructions.

    It is important that the cells be rmly anchored beore the fume is

    attached to the 2nd cell.Note

    Note

    installation

  • 7/29/2019 uk_M09-1150B

    7/32

    7

    7. Repeat steps 2 and 3 or 2nd top section on NC8411 through NC8414

    models.

    8. Repeat steps 4 through 7 or any remaining cells.

    9. Attach your cold water supply piping to the cold water basin outlet connec-

    tion in accordance with drawing instructions, utilizing gaskets provided.

    Do not support your pipe rom the tower or outlet connection

    supportitexternally.

    Normally, one o the ollowing three outlet arrangements is provided:

    Case ace connection:This is a actory-installed, galvanized pipe nipple,

    extending horizontally rom the side o the cold water basin. It is both

    beveled or weldingand grooved or a mechanical coupling. I a weld

    connection is used, it is recommended that the weld area be protected

    against corrosion. Cold galvanizing is suggested, applied according to

    the manuacturers instructions.

    Bottom outlet connection: This is a actory-installed, circular opening

    in the cold water basin foor o one or more cells. An appropriately-sized

    circular opening has been provided to accept a 125# ANSI B16.1 fat-

    ace fange connection.

    Side outlet sump connection: Unless otherwise specied, sumps are

    manuactured o heavy duty FRP (ber-reinorced polyester) construc-

    tion. Because o their size, they are attached upside down in the basin

    to prevent damage in shipment. They must be inserted into the square

    opening prepared in the foor o the cold water basin o one or more cells

    sealed against leakage, and attached by machine bolts, according to the

    installation drawing included. An appropriately-sized circular opening in

    the vertical ace o the sump has been provided to accept a 125# ANSI

    B16.1 fat-ace fange connection.

    10. Attach makeup water supply piping to appropriately-sized foat valve con-

    nection located in cold water basin side wall. Install the drain and overfow

    according to theNC Field Installation ManualAssembly Instructions.

    I you wish to pipe overfow and drain water to a remote discharge point,

    make those connections at this time also.

    11. Attach your warm water return piping to the inlet connections o the

    tower.

    Caution

    installation

  • 7/29/2019 uk_M09-1150B

    8/32

    8

    Fasteners and components provided by others that are to be at-

    tached to the tower must be compatible with the cooling tower

    materialsi.e. asteners in a stainless steel cold water basin must

    be stainless steel.

    Exceptforthehorizontalcomponentsoftop-mountedpiping,and

    as prescribed on Marley drawings, do not support your pipe rom

    thetowerorinletconnectionsupportitexternally.

    Normally, one o the ollowing our inlet arrangements is provided:

    Standard distribution basin connections:These are circular openings

    two per cellin the top deck o the tower near the air inlet ace, provided

    to accept standard 125# fat-ace fanges. Remove the center section o

    the inlet fume assembly to gain access to attach inlet asteners. (Reer

    to NC Field Installation Manual shipped with tower.)

    Marley ow-control valve connections (option): Marley fow-control

    valvestwo per cellare designed to 1take the place o the standard

    elbows normally required or inlet connection, and 2provide means o

    regulating fow to both sides o the tower. Remove the center inlet fumeassembly to gain access or attachment o valves. (Reer to NC Field

    Installation ManualAssembly Instructions shipped with tower.) Valves

    provide a vertical ace or attachment o your standard 125# fange.

    Side inlet connection (option): A pipe stub is provided in the casing

    wall above the access door or connection to the external piping by means

    o the rubber coupling provided.

    Bottom inlet connection (option): An appropriately sized hole and

    bolt circleone per cellis provided in the foor o the cold water basin.

    Bolt circle is designed to accept a standard 125# fat-ace fange.

    12. Wire motor in accordance with wiring diagram.

    For maintenance/safety purposes, SPX recommends a lockout

    typedisconnectswitchforallmechanicalequipment.Inaddition

    to a disconnect switch, the motor should be wired to main power

    supply through short circuit protection, and a magnetic starter with

    overload protection.

    Warning

    Note

    installation

    Caution

  • 7/29/2019 uk_M09-1150B

    9/32

    9

    installation

    Motor Wiring

    Wire motor leads as shown on the motor nameplate matching the supply

    voltage. Do not deviate rom the motor nameplate wiring.

    Either o ollowing symbols may be shown on the motor nameplate

    , , Y, or YY. These symbols represent how the motor is constructed on

    the inside and in no way have anything to do with a Delta or Wye electrical

    distribution system serving the motor.

    When using a starter: Setmotoroverloadprotection to110%ofmotornameplateamps.

    This setting allows the an motor to operate during cooler weather.

    Duringcoolerweatheritiscommonforthemotortodraw6to10%

    higher than nameplate amps. High amps are common during tower

    commissioning when the tower is dry and the ambient air temperature

    is cool.

    Donotstartthemotormorethansixtimesperhour.Shortcycling

    thetowerwillcausefuses,breakersorO.L.stooperateandwill

    decrease motor lie.

    When using a two-speedstarter:

    Motorrotationmustbethesameatslowspeedandhighspeed.

    Singlewindingmotorrequiresastarterwithashortingcontactor.

    Two-windingmotorrequiresastarterwithoutashortingcontactor.

    Alltwo-speedstartersmusthavea20secondtimedelayrelaywhen

    switching rom high speed to low speed.

    Donotstartthemotormorethanfourtovetimesperhour(each

    lowspeedstartandeachhighspeedstartcountasonestart).

    When using a VFD:

    Beore beginning, ensure that the motor is rated or Inverter Duty

    per NEMA MG-1, part 31.

    SettheVFDsolidstateoverloadprotectionto119%ofmotorname-

    plate amps and set maximum current parameter in the VFD to motor

    nameplate amps. Maximum current parameter will reduce an speed

    and limit amp draw to nameplate amps during cold weather opera-

    tion.IffurnishedwithamechanicalO.L.setthisat110%overmotor

    nameplate amps.

    Note

    Note

    Note

  • 7/29/2019 uk_M09-1150B

    10/32

    10

    installation

    Motor rotationmustbethe sameinbothVFDmodeandBy-pass

    mode.

    IfcabledistancebetweentheVFDandmotorisgreaterthan31meters

    a DV/DT output lter is recommended to avoid damage to the motor. 31

    meters distance is based on our eld experience, the VFD manuacture

    may state dierent distances and distance does vary depending on

    the VFD manuacture.

    ProgramtheVFDforvariabletorqueoutput.Fluxvectorandconstant

    torque modes may damage the gearbox.

    Donotstartandstopthemotorusingthesafetyswitchatthemotor.

    I the drive is being commanded to run and the load side is cycled ON

    and OFF with the saety switch this may damage the VFD.

    Using a VFD in cooling applications has advantages over traditional single

    or two speed motor control. A VFD can reduce the cost o electrical energy

    being used and provide better temperature control. In addition, it reduces the

    mechanical and electrical stress on the motor and mechanical equipment.

    Electrical savings can be large during periods o low ambient temperature

    when the cooling requirement can be satised at reduced speeds. To benet

    rom these advantages, it is important that the drive be installed correctly.Marley supplies VFD and VFD controls specically designed or our cool-

    ing products. I you have purchased a Marley VFD and/or controls package,

    please ollow the instructions in the User Manualor that system. Most VFD

    problems can be avoided by purchasing the Marley drive system. I you are

    installing a VFD other than the Marley drive, please reer to that drives instal-

    lation manual.

    ImproperuseofaVFDmaycausedamagetoequipmentorpersonal

    injury. Failure to correctly install the VFD drive will automatically

    voidallwarrantiesassociatedwiththemotorandanyequipment

    thatiseitherelectricallyormechanically(directly)attachedtothe

    VFD drive system. The length o this warranty avoidance will be

    contingent on properly installing the VFD system and repairing any

    damage that may have occurred during its operation. SPX Cool-

    ing Technologies does not assume responsibility or any technical

    support or damages or problems associate with non-Marley brand

    VFD systems.

    Changing the operational an speed rom the actory settings could

    cause the an to operate in an unstable region which may result in

    damagetotheequipmentandpossibleinjury.

    Warning

    Warning

  • 7/29/2019 uk_M09-1150B

    11/32

    11

    Mechanical Equipment:

    Always shut o electrical power to the tower an motor prior to

    perorming any maintenance on the tower. Any electrical switches

    shouldbelockedoutandtaggedouttopreventothersfromturning

    thepowerbackon.

    1. I equipped, check oil level in accordance with the Geareducer User

    Manualor the Geareducer. (Although the Geareducer was lled to the

    proper level at the actory, tipping during shipment and hoisting may havecaused some loss o oil.) I oil is required, ll Geareducer to the proper

    level with approved lubricant. (See Geareducer User Manual) Check oil

    level at the Geareducer or dipstick (standpipe located on an deck, i so

    equipped) to conrm that the proper level is indicated.

    2. Install an guard according to the installation drawing shipped with the

    tower. NC8401 through NC8403 models include a single-piece an guard.

    NC8405 through NC8414 models include a two-piece an guard. Models

    with extended velocity-recovery cylinders do not have an guards.

    Improper installation o the an guard will destroy the structural

    integrity o the an guard. Failure o the an guard could allow op-

    erating or maintenance personnel to all into the rotating an.

    3. Spin the an manually to assure that all an blades properly clear the

    inside o the an cylinder. Observe the action o the coupling (or drive

    shat couplings) to be sure that the motor and Geareducer are properly

    aligned. I necessary, correct the alignment in accordance with the included

    manual.

    For Power Belt Drive equipped models observe the action o the sheavesand belts to be sure that the motor is properly aligned with the an sheave.

    See the Belt Tensioning and Sheave Alignment section o this manual.

    It is essential that the an guard be installed in accordance with the

    Field Installation Manual shipped with the tower.

    Warning

    installation

    Warning

    Caution

  • 7/29/2019 uk_M09-1150B

    12/32

    12

    4. Momentarily bump (energize) the motor and observe rotation o the an.

    The an should rotate in a counterclockwise direction when viewed rom

    below. I rotation is backwards, shut o the an and reverse two o the

    three primary leads supplying power to the motor.

    Iftowerisequippedwithatwo-speedmotor,checkforproperrota-

    tionatbothspeeds.Checkalsotoseethatstarterisequippedwitha

    20 second time delay which prevents direct switching rom high

    speed to low speed. I the an is intended to be reversed or deicing

    purposes,makesurethatthestarterisequippedwitha2minutetime delay between changes o direction. These delays will prevent

    abnormalstressfrombeingappliedtothemechanicalequipment

    and the electrical circuit components.

    5. Run the motor and observe the operation o the mechanical equipment. Opera-

    tion should be stable, and there should be no evidence o oil leakage.

    6. I equipped with belt drive check the torque on the an and motor sheave

    ater 10 to 60 hours o operation. See Bushing Fastener Torque Values

    o the Belt Tensioning and Sheave Alignment section o this manual.

    I the water supply system is not being operatedor i there is no

    heat load on the systemmotor amps read at this time may indicate

    an apparent overload o as much as 1020%. This is because o the

    increased density o unheated air fowing through the an. Deter-

    mination o an accurate motor load should await the application o

    the design heat load.

    installation

    Caution

    Note

  • 7/29/2019 uk_M09-1150B

    13/32

    13

    Warning

    Tower Start-Up

    Amongother sources,outbreaksof LegionnairesDiseasehave

    reportedly been traced to cooling towers. Maintenance and water

    treatment procedures that prevent amplication and dissemination

    o Legionella and other airborne bacteria should be ormulated and

    implementedBEFOREsystemsareoperatedandcontinuedregularly

    thereaftertoavoidtheriskofsicknessordeath.

    Water System:1. New installations should be cleaned and treated with biocides by a water

    treatment expert beore startup.

    2. Remove any and all accumulated debris rom tower. Pay particular atten-

    tion to inside areas o cold water basin, hot water basins, louvers and

    drit eliminators. Make sure that cold water outlet screens are clear and

    properly installed.

    3. Fill the water system to an approximate depth o 180mm in the depressed

    area o the cold water basin at the center o the tower. For models NC8407

    through NC8414 ll the water system to an approximate depth o 200mm.

    This is the recommended operating water level. Adjust the foat valve so

    thatitis75%openatthatlevel.Continuellingthesystemuntilthewater

    reaches a level approximately 3mm below the lip o the overfow.

    Iftowerisequippedwithastandardcasefaceoutletconnection,

    vent accumulated air rom the top o the suction hood by removing

    one or both tap screws provided at that location. Replace these

    tapscrewswhenventingiscomplete.(Oncertainmodels,thetop

    o the suction hood or 14" diameter side suctions is 32mm above

    thetopoftheoverow.Inthosesituations,itisnecessarytoblockthe overfow and continue lling the basin to the level where the

    aforementionedtapscrewsaresubmergedbeforeventing.)

    4. Completely open all hot water fow control valves. Start your pump(s) and

    observe system operation. Since the water system external to the tower

    will have been lled only to the level achieved in the cold water basin, a

    certain amount o pump-down o the basin water level will occur beore

    water completes the circuit and begins to all rom the ll. The amount

    o initial pump-down may be insucient to cause the foat valve to open.

    Note

    installation

  • 7/29/2019 uk_M09-1150B

    14/32

    14

    However, you can check its operation by pressing down on the operating

    lever to which the stem o the foat valve is attached.

    Some trial and error adjustment o the foat valve may be required to

    balance the makeup water with tower operation. Ideally, the foat valve

    setting will be such that no water is wasted through the overfow at pump

    shutdown. However, the water level ater pump start-up must be deep

    enough to assure positive pump suction.

    5. I the tower is equipped with fow-control valves, adjust them to

    equalize hot water depth in the distribution basins ater reaching de-

    sign water fow rate. Each basin should have rom 75mm to 140mmwater depth, with uniorm depth rom basin to basin. Fix valves in this

    position with the locking bar when depth is correct. Failue to tighten the

    locking bar ater valve adjustment may result in damage to the valve. I

    the tower is equipped with the Marley internal piping option, the basins

    are sel-balancing and this step is not necessary.

    Uniorm distribution depth o 75mm to 140mm is essential to ecient

    tower operation. Contact your Marley sales representative i you are

    considering a permanent change in circulating water fow rate that would

    prevent operation within these limits.

    6. Continue pump operation or about 15 minutes, ater which it is recom-

    mended that the water system be drained, fushed, and relled.

    7. While operating the condensing water pump(s) and prior to operating the

    cooling tower an, execute one o the two alternative biocidal treatment

    programs described in the ollowing:

    Resumetreatmentwiththebiocidewhichhadbeenusedpriortoshut-

    down. Utilize the services o the water treatment supplier. Maintain the

    maximum recommended biocide residual (or the specic biocide) or

    a sucient period o time (residual and time will vary with the biocide)

    to bring the system under good biological control or

    Treatthesystemwithsodiumhypochloritetoa levelof4to5mg/L

    ree chlorine residual at a pH o 7.0 to 7.6. The chlorine residual must

    be held at 4 to 5 mg/L or six hours, measurable with standard com-

    mercial water test kits.

    installation

  • 7/29/2019 uk_M09-1150B

    15/32

    15

    I the cooling tower has been in operation and then shut down or a du-

    ration o time and not drained, perorm one o the two previous biocidal

    treatment programs directly to the cooling water storage vessel (cooling

    tower sump, drain down tank, etc.) without circulating stagnant water

    over the cooling tower ll or operating the cooling tower an.

    Ater biocidal pretreatment has been successully completed, cooling

    water may be circulated over the tower ll with the an o.

    When biocidal treatment has been maintained at a satisactory level or

    at least six hours, the an may be turned on and the system returned to

    service. Resume the standard water treatment program, including biocidaltreatment.

    Tower Operation

    General:

    The cold water temperature obtained rom an operating cooling tower will vary

    with the ollowing infuences:

    1. Heat load: With the an in ull operation, i the heat load increases, the

    cold water temperature will rise. I the heat load reduces, the cold water

    temperature will reduce.

    Note that the number o degrees (range) through which the tower cools

    the water is established by the system heat load and the amount o water

    being circulated, in accordance with the ollowing ormula:

    The cooling tower establishes only the cold water temperature attainable

    under any operating circumstance.

    2. Air wet-bulb temperature:Cold water temperature will also vary with the

    wet-bulb temperature o the air entering the louvered aces o the tower.

    Reduced wet-bulb temperatures will result in colder water temperatures.

    However, the cold water temperature will not vary to the same extent as

    the wet-bulb. For example, a 11C reduction in wet-bulb may result in only

    a 8C reduction in cold water temperature.

    3. Water ow rate: Increasing the water fow rate (m3/hr) will cause a slight

    elevation in cold water temperature, while reducing the water fow rate

    will cause the cold water temperature to decrease slightly. However, at

    a given heat load (see ormula above), water fow reductions also cause

    an increase in the incoming hot water temperature. Use care to prevent

    Range C =Heat Load (kW)

    Water Flow (m3/hr) x 1.162

    operation

  • 7/29/2019 uk_M09-1150B

    16/32

    16

    the hot water rom exceeding 52C, in order to prevent damage to the

    tower components.

    4. Air ow rate: Reducing air fow through the tower causes the cold wa-

    ter temperature to rise. This is the approved method by which to control

    leaving water temperature.

    I your tower is equipped with a single-speed motor, the motor may be

    shut o when the water temperature becomes too cold. This will cause

    the water temperature to rise. When the water temperature then becomes

    too warm or your process, the motor can be restarted.

    5. Fan cycling limits:

    Considering the normal an and motor sizes utilized on NC towers,

    anticipatethatapproximately4to5startsperhourareallowable.

    I your tower is equipped with a two-speed motor, you will enjoy greater

    opportunity or temperature control. When the water temperature becomes

    too cold, switching the an to hal-speed will cause the cold water tem-

    perature to risestabilizing at a temperature a ew degrees higher than

    beore. With a urther reduction in water temperature, the an may becycled alternately rom hal-speed to o.

    Donotstartthemotormorethanfourtovetimesperhour(each

    lowspeedstartandeachhighspeedstartcountasonestart).

    I your tower consists o two or more cells, cycling o motors may be

    shared between cells, increasing your steps o operation accordingly.

    Multicell towers equipped with two-speed motors will maximize energy

    savings and minimize sound levels i ans are staged so that all ans are

    brought up to low speed beore any an goes to high speed.

    For greater insight on cold water temperature control, please read

    Cooling Tower Energy and its Management, Technical Report

    #H-001-A, available on our website.

    operation

    Note

    Note

  • 7/29/2019 uk_M09-1150B

    17/32

    17

    Caution

    Wintertime Operation:

    The Marley ll system used in NC cooling towers has air entrance louvers that

    are molded as an integral part o the ll. This eature makes these towers very

    orgiving o cold weather operation, even at the low temperature and reduced

    load conditions encountered in ree cooling and other low temperature applica-

    tions. Nevertheless, during operation in subreezing weather the opportunity

    exists or ice to orm in the colder regions o the tower.

    Slushy, transitory ice orms routinely in the colder regions o the llo low temperature towers, and is visible through the tower louvers.

    Such ice normally has no adverse eect on tower operation, but

    itsappearanceshouldbeasignaltotheoperatortoundertakeice

    control procedures.

    It is the operator's responsibility to prevent the ormation o destruc-

    tive(hard)iceonthecoolingtowerll.Certainguidelinesshould

    be ollowed:

    1. Do not allow the towers leaving water temperature to drop below a mini-

    mum allowable levelsay 2C to 5C. I such low temperature operation is

    necessary or benecial to your process, establish the minimum allowable

    level as ollows:

    During the coldest days o the rst winter o operation, observe whether

    any ice is orming on the louver ace, particularly near the bottom part o

    the louver ace. I hard ice is present on the louvers, you must increase

    the allowable cold water temperature. I the coldest possible water is

    benecial to your process, ice o a mushy consistency can be tolerated

    but routine periodic observation is advisable.

    If the minimum allowable cold water temperature is established at

    or near minimum heat load, it should be safe for all operating condi-

    tions.

    Having established the minimum allowable cold water temperature,

    maintaining that temperature can be accomplished by an manipulation,

    as outlined in Item 4 under Tower Operation. However, in towers o

    more than one cell, where ans are manipulated sequentially, please realize

    that the water temperature will be signicantly lower in the cell or cells

    operating at the highest an speed than the net cold water temperature

    Note

    operation

  • 7/29/2019 uk_M09-1150B

    18/32

    18

    produced by the entire tower would indicate. Wintertime operation o

    multicell towers at low cold water temperature levels requires that the

    operator be especially watchul.

    2. As cold air enters the louvers, it causes the water fowing over the ll to

    be drawn inward toward the center o the tower. Thus, under an opera-

    tion, the louvers and lower periphery o the tower structure remain partly

    dry, seeing only random splashing rom within the towerplus normal

    atmospheric moisture rom the entering air. Such lightly wetted areas are

    most subject to reezing.

    Thereore, i excessive ice orms on the louvers, stop the an or a ewminutes. With the an o, the water fow will increase in the vicinity o the

    louvers and reduce the ice buildup.

    3. Under extended extreme cold conditions, it may be necessary to operate

    the an in reverse. This orces warm air out through the louvers, melting

    any accumulated iceadequate heat load must be available. Reversal

    o an should only be done at hal speed or less. Reverse operation o

    the an should be used sparingly and should only be used to control ice,

    not to prevent it. Reverse an operation should not need to exceed 1 or

    2 minutes. Monitoring is required to determine the time required to melt

    accumulated ice.

    Operatingthefaninreverseathalfspeedforprolongedperiods

    during subreezing weather can cause severe damage to ans and

    an cylinders. Ice can accumulate inside fan cylinders at fan blade

    planeofrotationandfanbladetipswilleventually strikethis ringof

    ice, damaging the fan blades or cylinder. Ice can also accumulate on

    fan blades and be thrown off, damaging fan cylinder or blades. Allow

    a minimum of 10 minute delay between reverse operation and forward

    operation during subfreezing weather to permit ice to dissipate from fanblades and fan cylinders. See Fan Drive Caution note in the Mechanical

    EquipmentInstallationsectionofthismanual.

    4. With no heat load on the circulating water, icing cannot be controlled

    eectively by air control during reezing weather. Towers must not be

    operated with reduced water rate and/or no heat load during

    reezing weather. I the circulating water system cannot be shut down,

    water returning rom the process should be made to bypass the tower. I

    a bypass is used, all water must be bypassed without modulation. I the

    water bypass is directly into the tower's cold water basin, its design must

    be approved by SPX Cooling Technologies.

    Warning

    operation

  • 7/29/2019 uk_M09-1150B

    19/32

    19

    Intermittent Wintertime Operation:

    Ifperiodsofshutdown(nights,weekends,etc.)occurduringfreezing

    weather,measuresmustbetakentopreventthewaterinthecold

    waterbasinandallexposedpiping,bothinternallyandexternally

    from freezing.

    Several methods are used to combat this, including:

    automatic water basin heater systems available rom Marley.

    eld installation o heat tracing o piping, both internally and externally.

    eld modication to provide a weep hole by drilling a 316" hole in PVC pip-

    ing, 180mm up rom the base o the fange o the internal riser. The hole

    should be plugged with a " tap screw with sealing washer. For steel pip-

    ing, drill a 1364" diameter hole 50mm up rom the base o the fange o the

    internal riser and tap or a -20 bolt with sealing washer that will be used

    as a plug. See fgures below or drilling details. Normally weep holes

    are plugged during tower operation and plugs removed during downtime in

    reezing temperatures. To leave the hole unplugged during operation, drill a316" hole at an upward angle that will allow the water fow to drain downward

    into the basin.

    Unless some means o reeze prevention is incorporated into your

    system,thetowerbasinandexposedpipeworkshouldbedrained

    at the beginning o each wintertime shutdown period.

    I tower basin is drained, veriy that all basin heaters have been shut

    o either by automatic cuto or disconnect switch.

    It is recommended that you discuss your reeze prevention options with yourlocal Marley sales representative.

    Caution

    operation

    Warning

    DRILL FOR PLUGGING HOLES

    DRILL FOR NO PLUG

    TAP SCREW

    OR BOLT

    Warning

  • 7/29/2019 uk_M09-1150B

    20/32

    20

    Water Treatment and Blowdown

    Maintaining Water Quality:

    The steel used in NC towers has been galvanized with a heavy zinc coating

    averaging 2.0 mils in thickness. The NC stainless steel option is even more

    corrosion resistant than galvanized steel in certain environments. Other ma-

    terials used (PVC ll, drit eliminators, and louvers, aluminum ans, cast iron

    Geareducer, etc.) are selected to oer maximum service lie in a normal

    cooling tower environment, dened as ollows:

    Circulating water with a pH between 6.5 and 8; a chloride content (as NaCl)below 500 mg/L; a sulate content (SO4) below 250 mg/L; total alkalinity

    (as CaCO3) below 500 mg/L; calcium hardness (as CaCO3) above 50

    mg/L; a maximum inlet water temperature not to exceed 52C; no signicant

    contamination with unusual chemicals or oreign substances; and adequate

    water treatment to minimize scaling.

    StartupConditions:Thewaterconditionsduringtheinitialtoweroperation

    are crucial in preventing premature corrosion o galvanized steel (white

    rust). For at least the rst eight weeks o operation, pH should be controlled

    between 6.5 and 8.0 with hardness and alkalinity levels between 100 and

    300 mg/L (expressed as CaCO3).

    Chlorine(ifused)shallbeaddedintermittently,withafreeresidualnotto

    exceed 1 mg/Lmaintained or short periods. Excessive chlorine levels may

    deteriorate sealants and other materials o construction.

    Anatmospheresurroundingthetowernoworsethanmoderateindustrial,

    where rainall and og are no more than slightly acid, and they do not contain

    signicant chlorides or hydrogen sulde (H2S).

    Manyproprietarychemicalsexistforcontrolofscale,corrosion,andbiologi-

    cal growth and should be used prudently. Also, combinations o chemicals

    may cause reactions which reduce treatment eectiveness, and certainchemicals such as suractants, biodispersants and antioams may increase

    drit rate.

    Unless you purchased a stainless steel NC, the structure o your NC

    tower consists primarily o galvanized steel, thereore your water

    treatmentprogrammustbecompatiblewithzinc.Inworkingwith

    your water treatment supplier, it is important that you recognize

    the potential eects on zinc o the specic treatment program you

    choose.

    operation

    Note

  • 7/29/2019 uk_M09-1150B

    21/32

    21

    Cooling Tower Cleaning:

    Any evaporative-type cooling tower must be thoroughly cleaned on

    a regular basis to minimize the growth o bacteria, including Legio-

    nellaPneumophila,toavoidtheriskofsicknessordeath.Service

    personnelmustwearproperpersonalprotectiveequipmentduring

    decontamination.DoNOTattemptanyserviceunlessthefanmotor

    islockedout.

    Operators o evaporative cooling equipment, such as water cooling towers,

    should ollow maintenance programs which will reduce to an absolute minimum

    the opportunity or bacteriological contamination. Public Health Service ocials

    have recommended that good housekeeping procedures be ollowed, such

    as: regular inspections or concentrations o dirt, scale, and algae; periodic

    fushing and cleaning; and the ollowing o a complete water treatment program

    including biocidal treatment.

    The visual inspection should take place at least once a week during the operat-

    ing season. The periodic fushing and cleaning should be done beore and ater

    each cooling season, but in any event at least twice a year. The louvers, drit

    eliminators, and easily accessible ll suraces should be fushed by use o a

    moderate-pressure water nozzle, being careul not to cause physical damage.

    A reliable water treatment program should be installed and maintained. Filtra-

    tion devices may be employed to reduce the suspended solids concentrations,

    thus increasing the eectiveness o the water treatment program. See Tower

    Startup section o this manual.

    Blowdown:

    A cooling tower cools water by continuously causing a portion o it to evaporate.

    Although the water lost by evaporation is replenished by the makeup system, it

    exits the tower as pure waterleaving behind its burden o dissolved solids to

    concentrate in the remaining water. Given no means o control, this increasing

    concentration o contaminants can reach a very high level.

    In order to achieve water quality which is acceptable to the cooling tower (as

    well as the remainder o your circulating water system), the selected water

    treatment company must work rom a relatively constant level o concentra-

    tions. This stabilization o contaminant concentrations is usually accomplished

    by blowdown, which is the constant discharge o a portion o the circulating

    water to waste. As a rule, acceptable levels on which to base a treatment

    schedule will be in the range o 2-4 concentrations. The ollowing table shows

    maintenance

    Warning

  • 7/29/2019 uk_M09-1150B

    22/32

    22

    the minimum amount o blowdown (percent o fow) required to maintain dierent

    concentrations with various cooling ranges*:

    * Range = Dierence between hot water temperature coming to tower and cold water tem-

    perature leaving tower.

    EXAMPLE: 159 m3/hr circulating rate, 10C cooling range. To maintain

    4concentrations,therequiredblowdownis0.458%or.00458times

    159 m3/hr, which is .73 m3/hr.

    I tower is operated at 4 concentrations, circulating water will contain our

    times as much dissolved solid as the makeup water, assuming none o the

    solids orm scale or are otherwise removed rom the system.

    When water treatment chemicals are added, they should not be in-

    troduced into the circulating water system via the cold water basin

    o the cooling tower. Water velocities are lowest at that point, which

    resultsininadequatemixing.

    Belt Tensioning

    The belt tension is adjusted by loosening the 8 bolts that secure the motor

    mount rame to the belt drive rame, then loosen the retaining nuts on the twothreaded rods and turn the threaded rods to apply proper tension. Apply the

    same quantity o turns to each threaded rod to insure that the tensioning rame

    remains parallel to the mechanical support beams. Retighten hardware. Ideal

    tension is the lowest tension at which the belt will not slip under peak load

    conditions. Check tension requently during the rst 24-48 hours o run-in

    operation. Overtensioning shortens belt and bearing lie. Keep belts ree rom

    oreign material which may cause slipping. Never apply belt dressing as this will

    damage the belt and cause early ailure. A Dodge V-Belt Tension Tester is an

    alternate method or tensioning V-belts. Check with you local belt supplier.

    maintenance

    Note

    Cooling RangeNumber o Concentrations

    1.5X 2.0X 2.5X 3.0X 4.0X 5.0X 6.0X

    3C .78 .38 .25 .18 .11 .08 .06

    6C 1.58 .78 .51 .38 .25 .18 .14

    8C 2.38 1.18 .78 .58 .38 .28 .22

    11C 3.18 1.58 1.05 .78 .51 .38 .30

    14C 3.98 1.98 1.32 .98 .64 .48 .38

    Multipliers are based on drit o 0.02% o the circulating water rate.

  • 7/29/2019 uk_M09-1150B

    23/32

    23

    SHEAVE

    STRAIGHT EDGE

    SHEAVETHREADED ROD

    FAN SHAFT

    Sheave Alignment

    Themotorsheaveistobepositionedascloseaspossibletothemotor

    in order to minimize torque on the motor bushings.

    Themotorandfansheavesmayhavegroovesthatarenotused.Thebot-

    tom surace o the motor and an sheaves must be aligned within 3mm o

    each other and level within 12 (3mm in 30cm) in order to not adversely

    aect belt and sheave lie.

    Alignmentcanbeachievedbyplacingastraightedgeacrossthesheaves

    making sure that it is level and measuring down to the bottom surace o

    both sheaves at our points.

    Thebeltistobelocatedinthelowestset

    o grooves.

    maintenance

    gnihsuB eziSrenetsaFeuqroT

    bltf mN

    HS 02- 6 8

    SDS 02- 6 8

    DS 02- 6 8

    KS 81- 31 81

    FS 61- 22 03

    E 31- 53 84

    F 21- 56 88

    Bushing Fastener

    Torque Values

  • 7/29/2019 uk_M09-1150B

    24/32

    24

    maintenance

    Schedule o Tower Maintenance

    Some maintenance procedures may require maintenance personnel to enter

    the tower. Each cased ace o the tower has a door or access to the interior

    o the tower. The NC8401 and NC8402 have a 760mm wide by 840mm high

    door. All other models have a 760mm wide by 1220mm high door.

    The optional an deck ladder is designed and intended solely or personnel to

    gain access to the an deck. The an deck ladder should not be used to enter

    or exit the access doors located on the cased ace o the tower unless the

    optional access door platorm is provided.

    The purchaser or owner is responsible or providing a sae method

    forenteringorexitingtheaccessdoor.Useofthefandeckladder

    toenterorexittheaccessdoorsmayresultinafall.

    Included with this instruction packet are separate Service Manuals on each

    major operating component o the tower, and it is recommended that you

    read them thoroughly. Where discrepancies may exist, the separate Service

    Manuals will take precedence.

    The ollowing is recommended as a minimum routine o scheduled mainte-

    nance:

    Always shut o electrical power to the tower an motor prior to

    perorming any inspections that may involve physical contact with

    themechanicalorelectricalequipmentinoronthetower.Lockout

    and tag out any electrical switches to prevent others rom turning

    thepowerbackon.Servicepersonnelmustwearproperpersonal

    protectiveclothingandequipment.

    Weekly: Inspect or bacterial growth and general operation conditions. Bacte-

    rial growth should be reported to your water treatment expert or immediate

    attention.

    Monthly (Weekly at start up): Observe, touch, and listen to the tower.

    Become accustomed to its normal appearance, sound, and level o vibration.

    Abnormal aspects relating to the rotating equipment should be considered

    reason to shut down the tower until the problem can be located and corrected.

    Observe operation o the motor, coupling (or drive shat), Geareducer and

    an. Become amiliar with the normal operating temperature o the motor, as

    well as the sight and sound o all components as a whole.

    Warning

    Warning

  • 7/29/2019 uk_M09-1150B

    25/32

    25

    maintenance

    I equipped, check or Geareducer oil leaks. Check the Geareducer as well

    as any optional oil lines to external oil dipstick/sight glass.

    Inspect louvers, drit eliminators and basin trash screens and remove any

    debris or scale which may have accumulated. Replace any damaged or worn

    out components. Use o high-pressure water may damage the eliminator and

    louver material.

    Observe operation o the foat valve. Depress the operating lever to make

    sure that the valve is operating reely. Inspect the suction screen or plugging.

    Remove any debris that may have accumulated.

    Check or any buildup o silt on the foor o the cold water basin. Mentally make

    note o the amount, i any, so uture inspections will enable you to determine

    the rate at which it is orming.

    Every 3 months: I equipped, lubricate an shat bearings. While rotating

    equipment by hand, grease the bearings until a bead orms around the seals.

    Mobil SHC 460 grease is recommended.

    Semi-Annually: I equipped, check the belt tension and condition.

    I equipped, check Geareducer oil level. Shut down the unit and allow 5 min-

    utes or the oil level to stabilize. Add oil i required.

    Clean and disinect cooling tower with biocides. Systems with bioouling, high

    general bacterial counts, or positive cultures o legionella may require addi-

    tional cleaning. Reer to Cooling Tower Cleaning section o this manual.

    Consult your water treatment expert as to prudent biological evaluation testing.

    Geareducer models used on NC cooling towers are designed or

    5-yearoilchangeintervals.Tomaintainve-yearchangeintervals,

    use only oil designed specically or these Geareducers. I, ater

    ve years, turbine-type mineral oil is used, the oil must be changed

    semiannually. Reer to the Geareducer Manual or oil recommenda-tions and urther instructions.

    Annually: Inspect the tower thoroughly, making maximum use o instructions

    given in the separate service manuals. Check structural bolted connections

    and tighten as required. Make preventive maintenance repairs as necessary.

    Note

  • 7/29/2019 uk_M09-1150B

    26/32

    26

    Relubricate motor according to the manuacturers instructions. Reer to the

    Motor Re-lubrication Instructions o this manual or towers equipped with the

    motor outside the plenum area.

    Check to see that all bolts are tight in the an and mechanical equipment

    region, including the an cylinder and an guard. Reer to Component User

    Manuals or torque values.

    Every 5 Years: I equipped, change Geareducer oil. Reer to the Geareducer

    User Manualor instructions.

    Motor Relubrication Instructions

    Motor located outside plenum option

    Openandlockoutdisconnectswitchtomakecertainmotorcannot

    be started.

    1. Remove guard as shown. Opposite end motor bearing is accessible rom

    outside the tower.

    2. Remove grease ll and relie plugs at both shat extension end and op-

    posite end bearings and remove hardened grease, using clean wire.

    maintenance

    MOTOR STEEL SIDE CASING

    ATTACHMENT SCREW

    GUARD

    GREASE FILL PLUG

    GREASE RELIEF PLUG

    3. Insert grease ttings in grease ll openings and add grease until grease

    is orced out through relie openings.

    4. Replace ll plugs and operate mechanical equipment 30 minutes to one

    hour to purge excess grease at grease relie opening.

    Warning

  • 7/29/2019 uk_M09-1150B

    27/32

    27

    5. Reinstall grease relie plugs and reinstall guard.

    6. Resume normal tower operation.

    Seasonal Shutdown Instructions

    When the system is to be shut down or an extended period o time, it is

    recommended that the entire system (cooling tower, system piping, heat

    exchangers, etc.) be drained. Leave the basin drains open.

    During shutdown, clean the tower (see Warning on cooling tower cleaning

    in the Maintenance section o this manual) and make any necessary repairs.

    Pay particular attention to mechanical equipment supports and coupling (or

    drive shats).

    Following each years shutdown and cleaning, inspect the towers metal suraces

    or evidence o the need to apply a protective coating. Do not misinterpret

    grimeand transient rust rom the piping systemas a need to have the tower

    painted. I relatively bright metal can be exposed by cleaning, consider that the

    galvanizing has remained eective. Unless there is evidence o a generalized

    ailure o the galvanizing, localized touch-up should be all that is required.

    Totheextentthatthegalvanizing(zinccoating)stillexists,paint

    will not adhere to it readily. Contact the manuacturer o the coating

    you intend to use or instructions.

    Tower ramework: Check structural bolted connections and tighten as

    required.

    Fans: Check an assembly bolting and tighten as required. Use torque values

    prescribed in the Fan User Manual.

    Fans shat bearings: I equipped, lubricate an shat bearings at close o each

    operating season, as described in the Maintenance section o this manual.

    Electric motors:Clean and lubricate motor at close o each operating season

    (reer to motor manuacturers recommendations.) Check motor anchor bolts

    and tighten as required.

    maintenance

    Note

  • 7/29/2019 uk_M09-1150B

    28/32

    28

    Do not start motor beore determining that there will be no interer-

    ence with ree rotation o the an drive.

    The motor should be operated or three hours at least once a month. This

    serves to dry out windings and re-lubricate bearing suraces (reer to Marley

    Electric Motor User ManualManual 92-1475 ).

    At start o new operating season, make sure bearings are adequately lubricated

    beore returning motor to service.

    Prolonged Shutdown

    I shutdown period is longer than seasonal, contact your Marley sales repre-

    sentative or additional inormation.

    SPX Cooling Technologies Services

    Our interest in your NC cooling tower does not end with the sale. Having

    conceived, designed, and manuactured the most reliable and longest-lasting

    cooling tower on the market, we want to make sure that you gain the maximum

    possible benet rom its purchase.

    Thereore, the ollowing services are available which are intended to: assure

    the maximum possible service lie under your operating conditions; tailor the

    operating characteristics to your specic needs; and maintain consistently

    optimum thermal perormance capability. They are available by contacting

    your Marley sales representative.

    Replacement parts: A complete stock o parts and components is

    maintained at one or more o the various Marley plants. In cases o emergency,

    they can normally be shipped within 24 hoursby air reight i necessary.

    However, you would obviously benet rom anticipating your need in advance,

    thus avoiding the cost o special handling.

    Be sure to mention your tower serial number (rom the tower nameplate) when

    ordering parts.Periodic maintenance: You may wish to contract with SPX or regularly

    scheduled visitsor the purpose o inspecting and reporting your towers

    conditionto make recommendations intended to prevent emergencies and

    to perorm maintenance considered outside the norm.

    This service is not intended to replace the important unction perormed by

    your maintenance sta. Their attention assures the towers routine operating

    perormance, and is invaluable. However, we recognize the unusual manner

    in which a cooling tower perorms its unctionas well as the unique orces

    which act upon itmay be considerations which occasionally require the

    services o an expert technician.

    maintenance

    Caution

  • 7/29/2019 uk_M09-1150B

    29/32

    29

    maintenance schedule

    Maintenance Service Monthly Semi-annually Seasonal Startup or Annually

    Inspect General Condition and Operation x x

    Observe Operation o:

    Mechanicalmotor, an and drive mechanism x x

    Makeup valve (i equipped) x x

    Inspect or unusual noise or vibration x x

    Inspect and Clean:

    Air inlet x x

    PVC drit eliminators x x

    Distribution basin, nozzles and collection basin x x

    Fan motor exterior x x

    Check:

    Collection water basin level x x

    Blowdownadjust as required x x

    Geareducer Drive (i equipped):

    Check or loose asteners including oil drain plug x

    Check or / repair oil leaks x x

    Check oil level x x

    Change oil R

    Make sure vent is open x x

    Check driveshat or coupling alignment x

    Check or loose driveshat or coupling asteners x

    Check driveshat or coupling bushings or ex element or unusual wear x x

    Lube lines (i equipped):

    Check or oil leaks in hoses or fttings x R x

    Belt drive (i equipped):

    Fan shat bearing lubrication (every 3 mo.) every 3 months every 3 months

    Check and tighten support asteners x

    Check shat, sheave and belt alignment x

    Check belt tension and condition x x

    Check sheave bushing astener torque x

    Fan:

    Check and tighten blade and hub asteners R x

    Check an blade pitch and tip clearance x

    Check an cylinder or loose astenersR x

    Motor:

    Lubricate (grease as required) R

    Check mounting bolts or tightness x

    Operate at least 3 hours a month 3 hours a month 3 hours a month

    Basin Heater (i equipped):

    Check or proper operation o temp/low water level sensor x

    Inspect/clean buildup o contaminant rom sensor x x

    Structure:

    Inspect/tighten all asteners x x

    Inspect and touch up all metal suraces x

    R Reer to Component User Manual

    Note: It is recommended at least weekly, that the general operation and condition be observed. Pay attention to

    any changes in sound or vibration that may signiy a need or closer inspection.

  • 7/29/2019 uk_M09-1150B

    30/32

    30

    elbuorT esuaC ydemeR

    tratStoNlliWrotoM

    slanimretrotomtaelbaliavatonrewoP

    snoitcennocdabynatcerroC.retratstarewopkcehC.rotomehtdnasutarappalortnocehtneewteb

    ,sdaolrevoteseR.tiucriclortnocdnastcatnocretratskcehClortnocdeliafecalperrosehctiwsdeppirtteser,stcatnocesolc

    .sehctiws

    daolrevoerusekam,retratstasdaelllanotonsirewopfI.noitidnocreporpnierasecivedtiucrictrohsdna

    snoitcennocgnorW .smargaidgniriwtsniagasnoitcennoclortnocdnarotomkcehC

    egatlovwoLkcehC.ylppusrewoptsniagaegatlovetalpemankcehC

    .slanimretrotomtaegatlov

    gnidniwrotomnitiucricnepO .stiucricneporofsgnidniwrotatskcehC

    kcutsevirdnafrorotoMrecuderaeGdnarotomkcehcdnadaolmorfrotomtcennocsiD

    .melborpfoesuacrof

    evtcefedrotoR .sgnirrosrabnekorbrofkooL

    esioNrotoMlausunU

    esahp-elgnisgninnurrotoM-elgnisfitratstonlliwrotoM.titratsottpmettadnarotompotS

    .rotomdna,slortnoc,gniriwkcehC.desahp

    yltcerrocnidetcennocsdaelrotoM .rotomnomargaidgniriwtsniagasnoitcennocrotomkcehC

    sgniraebdaB .sgniraebdabecalpeR.noitacirbulkcehC

    ecnalabnulacirtcelEfitcerroC.senileerhtllafostnerrucdnasegatlovkcehC

    .deriuqer

    mrofinutonpagriA .gniraebrostiftekcarbtcerrocdnakcehC

    ecnalabnurotoR .ecnalabeR

    draugllebdnegnittihnafgnilooC .nafecalperrollatsnieR

    toHsnuRrotoM

    egatlovdecnalabnuroegatlovgnorWetalpemantsniagasenileerhtllafotnerrucdnaegatlovkcehC

    .seulav

    daolrevOrofkcehC.launaMecivreSnaFeeS.hctipedalbnafkcehC

    .sgniraebdegamadmorfsaniartevirdnafnigard

    MPRrotomgnorWrotomfoMPRkcehC.ylppusrewoptsniagaetalpemankcehC

    .oitarraegdna

    desaergrevosgniraeBegrupotdeepsotpurotomnuR.sfeileresaergevomeR

    .esaergevissecxe

    sgniraebnitnacirbulgnorWs'rerutcafunamrotomeeS.tnacirbulreporpotegnahC

    .snoitcurtsni

    nepoesahpenO-elgnisfitratstonlliwrotoM.titratsottpmettadnarotompotS

    .rotomdna,slortnoc,gniriwkcehC.desahp

    noitalitnevrooPelpmawollA.sgnineponoitalitnevkcehcdnarotomnaelC

    .rotomdnuoranoitalitnev

    tluafgnidniW .retemmhOhtiwkcehC

    tfahsrotomtneB .tfahsecalperronethgiartS

    esaergtneiciffusnI .sgniraebesaergerdnasgulpevomeR

    segnahcdeepsrognitratstneuqerfooT.rh/sdnoces03folatotaotemitnoitareleccaevitalumuctimiLredisnoC.traparehtrafstnioptesegnahcdeepsroffo/noteS

    .lortnocerutarepmetenifrofevirdDFVyelraMagnillatsni

    ngierofro,esaergfonoitaroireteD

    esaergnilairetam.etacirbulerdnasgniraebhsulF

    degamadsgniraeB .sgniraebecalpeR

    pUemoCtoNseoDrotoM

    deepSoT

    slanimretrotomtawolootegatloV

    pordenilfoesuaceb

    noegatlovrehgihesU.spatfognittesdnaremrofsnartkcehCroeziseriwesaercnI.sdaolecuderroslanimretremrofsnart

    .aitreniecuder

    srabrotoRnekorB.deriuqerebyamrotorwenA.sgnirehtraenskcarcrofkooL

    .rotomkcehcnosrepecivresrotomevaH

    )rotoM(noitatoRgnorW sesahpfoecneuqesgnorW .sdaelrotomeerhtehtfoowtynahctiwS

    troubleshooting

  • 7/29/2019 uk_M09-1150B

    31/32

    31

    troubleshooting

    elbuorT esuaC ydemeR

    esioNrecuderaeG

    sgniraebrecuderaeG

    .noitarepofokeewenoretfasraeppasidesionfiees,wenfI

    ecivreSrecuderaeGeeS.recuderaeGlliferdna,hsulf,niarD.ecalper,ysionllitsfI.launaM

    sraeG.sraegnrowyldabecalpeR.tnemegagnehtoottcerroC

    .hteetdegamadronekorbhtiwsraegecalpeR

    evirDnaFlausunU

    noitarbiV

    swercspacdnastlobesooLtnempiuqelacinahcemllanoswercspacdnastlobllanethgiT

    .stroppusdna

    nrowrotfahsevirddecnalabnU

    sgnilpuoc

    reporpnierastfahsrecuderaeGdnarotomerusekaM

    roriapeR.dehctamylreporp"skramhctam"dnatnemngilarogniddaybtfahsevirdecnalabeR.sgnilpuocnrowecalper

    evirDeeS.swercspacgnicnalabmorfsthgiewgnivomer.launaMecivreStfahS

    naFytefassanafforetnecmorfrafsaerasedalbllaniatrecekaM

    eeS.emasehtdehctipebtsumsedalbllA.timrepsecived

    .sedalbnopu-dliubtisopedffonaelC.launaMecivreSnaF

    sgniraebrecuderaeGnroWsasgniraebecalpeR.yalpdnetfahsnoinipdnanafkcehC

    .yrassecen

    rotomdecnalabnU,setarbivllitsrotomfI.rotometarepodnadaoltcennocsiD

    .rotorecnalaber

    tfahsrecuderaeGtneBfiecalpeR.rotacidnilaidhtiwtfahsnoinipdnanafkcehC

    .yrassecen

    esioNnaFrednilycnaffoedisnignibburedalB .ecnaraelcpitedalbedivorpotrednilyctsujdA

    spmalcedalbnistlobesooL .yrassecenfinethgitdnakcehC

    ecnatsbusngierofroelacS

    metsysretawgnitalucricni

    nwodwolbtneiciffusnI launamsihtfonoitces"tnemtaerTretaW"eeS

    ycneicifedtnemtaertretaWretaW"eeS.tsilaicepsgnitaertretawtnetepmoctlusnoC

    launamsihtfonoitces"tnemtaerT

    erutarepmeTretaWdloCmraWooT

    )"noitarepOrewoT"eeS(

    ngisedevobasi.pmetblubtewgniretnE

    fieeS.rewotgnitceffaerasecruostaehlacolfieesotkcehC

    rewotfonoitalucricergnisuaceraserutcurtsgnidnuorrus.evitatneserperyelraMhtiwydemerssucsiD.riaegrahcsid

    wolootsaw.pmetblubtewngiseDyelraMhtiwydemerssucsiD.ezisrewotesaercniotevahyaM

    .evitatneserper

    ngisednahtretaergdaolssecorplautcAyelraMhtiwydemerssucsiD.ezisrewotesaercniotevahyaM

    .evitatneserper

    gnipmuprevO .snoitidnocngisedotrewotrevoetarwolfretawecudeR

    riarofdevratsrewoT

    tcartnoctcerrocfoerusebotegatlovdnatnerrucrotomkcehC,srevuolnaelC.yrassecenfisedalbnafhctip-eR.rewopesroh

    roserutcurtsybraenfieesotkcehC.srotanimilednallif

    .rewototwolfrialamrongnitcurtsboerasllawgnisolcne.evitatneserperyelraMhtiwydemerssucsiD

    gnitixEtfirDevissecxErewoT

    gniwolfrevosnisabnoitubirtsiDeB.snoitidnocngisedotrewotrevoetarwolfretawecudeR

    .deggulptondnaecalpnieraselzzonnisabretawtoherus

    noitanimiletfirdytluaF

    erasrotanimiledna,srevuol,lliflargetnitahteesotkcehC

    srotanimiletfirdfI.yltcerrocdellatsnidna,sirbedfoeerf,naelcnidellatsniyltcerrocerayehterusekam,llifmorfetarapesera

    tuonrowrodegamadecalpeR.yrassecenfinaelC.ecalp

    .stnenopmoc

  • 7/29/2019 uk_M09-1150B

    32/32

    Increased load requirements: NC towers are

    designed so that cells o either equal or unequal

    capacity can be added in the uture. This allows

    you to compensate or the load increases that

    normally occur with the replacement or addition o

    production equipmentand still retain continuity

    with respect to your cooling tower system.

    Tower rebuilding: SPX Cooling Technologies

    routinely rebuilds and upgrades cooling towers o

    all materials and manuacture. I your tower ever

    reaches the limit o its service lie, we recommend

    that you investigate the cost o rebuilding beoreyou routinely order a new replacement tower.

    Each NC tower includes a document package

    containing general orientation drawings, NC

    Field Installation Manual Assembly Instruc-

    tions, and tower component manuals. These

    documents contain important inormation

    relating to sae installation and operation

    o the cooling tower. Field installation is al-

    ways required or an guards, piping inlets and

    piping outlets. Some optional accessories, such

    as valves, handrails, ladders and saety cages

    may also require eld installation. I installation

    details are not covered in the NC Field Installa-

    tion Manual a separate installation drawing or

    manual or each purchased option is included in

    the document package along with bills o material.

    I you have purchased an option and cant nd the

    appropriate installation drawing, contact your local

    Marley sales representative beore proceeding.

    In addition to these specic documents, SPX pub-

    lishes numerous technical reports including moredetailed inormation on a variety o cooling tower

    operation and service topics. Your Marley sales

    representative will be happy to give you copies o

    these reports at no charge.

    For complete parts and service assistance, con-

    tact the Marley sales representative in your area.

    I you need help locating the oce nearest you,

    please phone 44 1905 750 270 or check the

    internet at spxcooling.com.

    additional information

    SPX COOLING TECHNOLOGIES UK LTD

    3 KNIGHTBRIDGE PARK

    WAINWRIGHT ROAD

    WORCESTR WR4 9FA, UK

    P: 44 1905 750 270

    F: 913 664 7439

    [email protected]

    I th i t t t h l i l ll d t bj t t d i