Maple ArmorFounded in Montreal, Quebec, in 2011, Maple Armor Fire Alarm Device is adesigner and manufacturer of intelligent fire alarm systems for theinternational market. We work closely with them to develop a state-of-the-art, quality product line. We are proud that our work helps protect lives everyday and that our passion for our industry allows us to maintain the highestlevel of quality and reliability.
Doing fire alarm differently
ULC-S537Smoke & thermal detectors verification
Introduction
1 Introduction
2 ULC S537 regulation
3 Resume
4 Inspection report
5Alarm confirmationfor smoke detector
How a ULC-S537 audit is carried out and how to read an inspection report.
Many people limit themselves to thinking that a certificate certifies that all tests and installation were in perfect working order.
In fact; a certificate has no value and is not even required in the ULCS537 standard. Only the inspection report is the document that confirms and allows users (engineers, general contractor, electrical contractor, customer and owner) to have a complete assessment of the fire alarm system.
In this presentation, we will discuss about smoke detector
ULC-S537 smoke detector requirement
Resume1) Technician needs to check components (dirt, paint, obstruction, sampling tube,
installation as per ULC-S524. etc.)
2) Technician need to test the detector opération with smoke spray not with a magnet
3) Technician need to check detector sensitivity via a tool or via panel. When we test the duct smoke detector we need to test also the air velocity.
4) If we use panel sensitivity, we need to make sure we have the real sensitivity not a scale.
5) If a detector got replace; we need to indicate the replacement date.
6) When all tests are complete, we have to put all information in the report.
7) If technician is testing a multi-sensor each sensor needs to be tested individually and all information should indicate in the report individually.
8) Finally technician needs to indicate his name, signature and date on his report.
The detector sensitivity shall not be measured using any device that administers an unmeasured concentration of smoke or other aerosol into the detector”
CAN/ULC-S529
The Common Smoke Detector Testing Tool
Sprayed directly into detectors
Oily residue attracts dirt and dust
Contaminates detectors
Use the good tools / Smoke Detectors
“Acceptable methods of determining the smoke detector sensitivity are:
Manufacturer’s recommended test instrument, equipment, or method;
Installed control units or transponders designed to test the sensitivity of individual smoke detectors; or
Calibrated instruments that provide the operation as described in CAN/ULC-S529, Standard for Smoke Detectors for Fire Alarm Systems, for the purpose of testing smoke detector sensitivity.”
Section 5.7.4.1.6
YES OR NO ?
Fire protection is everywhere!
New type of fire alarm detector?
Following slide will indicate how a report shouldbe done and complete
1) ULCS-537 report could have different from.
2) report should include all elements fromULC-S537 requirement.
Typical report as per ULC-S537
Typical report as per ULC-S537
Typical report as per ULC-S537
OUR FIREWATCHER PANELS FW106, FW106S
Drift CompensationThe Drift Compensation is built into the detector FW511 for a sensitivity value of 1.6 to 2.4 and is not performed by the panel. Drift compensation automatically adjusts for gradually increasing effects of dust and other accumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detector going dirty according to the gradual change in the normal clean air value received. When it can no longer compensate for an increasingly dirty detector, a dirty detector trouble (contamination trouble) is indicated for that device. Our software 5.1.2 offer the sensitivity reading for customer with level 3 access.
Alarm confirmation for a smoke detector
CANADIAN MANUFACTURE YES! VERY SOON
• 10% invest in R&D
• Less than 1% in return
• 5-year warranty
• Flexibility
— Listen to customers
— Just to market needs
• Our service
— Technical assistance products and codes
— Large local inventory
— Training
— Personal training
— non-exclusive programmation
Innovation Reliability Expertise
Questions?