understanding power production students’ laboratory manual
TRANSCRIPT
EEN-E1010 – Power Plants and Processes Course
Edition Author Date
V.01 Mohamed Magdeldin 11.10.2016
V.02 Mohamed Magdeldin 12.09.2017
V.03 Mohamed Magdeldin 12.10.2018
Understanding Power Production Students’ Laboratory Manual
Steam Turbine Electrical Generation
Course Instructors: Professor Mika Järvinen, M.Sc. Mohamed Magdeldin
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
1
Contents 1: INTRODUCTION ................................................................................................. 4
1.1 Rankine Cycle ................................................................................................... 5
1.2 The Laboratory Setup ....................................................................................... 7
1.2.1 Burner ......................................................................................................... 7
1.2.2 Boiler .......................................................................................................... 8
1.2.3 Sight glass ................................................................................................... 9
1.2.4 Boiler pressure gauge ................................................................................. 9
1.2.5 Steam admission valve ............................................................................... 9
1.2.6 Steam turbine ............................................................................................10
1.2.7 Generator ..................................................................................................11
1.2.8 Cooling tower ...........................................................................................11
1.2.9 Data acquisition system ............................................................................11
1.2.10 Operator panel ........................................................................................12
1.2.11 Liquid propane cylinder ..........................................................................13
1.2.12 Flue gas temperature thermocouple ........................................................13
1.3 General Operational limitations ......................................................................14
1.3.1 BOILER ....................................................................................................14
1.3.2 BURNER ..................................................................................................14
1.3.3 GENERATOR ..........................................................................................14
1.3.4 ABNORMAL SHUTDOWN “OFF-OPEN-OFF” ...................................14
1.4 General Guidelines .........................................................................................15
2: Pre-operation Preparation (For Demo run purposes only). .................................16
3: System Operation .................................................................................................17
3.1 Prestart check ..............................................................................................17
3.2 Start operation .............................................................................................20
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
2
3.3 Steady state operation (Experimental run) ..................................................23
3.4 Shutdown .....................................................................................................24
4: Practical Guidelines for Reporting ......................................................................27
4.1 Technical Report Guidelines ..........................................................................27
4.2 Oral presentation .............................................................................................28
4.3 RankineCyclerTM Data Run Plots ...................................................................29
4.4 System Analysis ..............................................................................................30
4.3.1 Boiler ........................................................................................................30
4.3.2 Turbine ......................................................................................................30
4.3.3 Cooling Tower ..........................................................................................31
4.3.4 Overall System ..........................................................................................31
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
3
List of Figures Figure 1. Schematic of an ideal Rankine cycle.. ...................................................................................................... 5
Figure 2. PV and TS property diagram for the ideal Rankine cycle. ................................................................... 5
Figure 3. Temperature- Entropy diagram representation of the four processes within the Rankine cycle.. . 6
Figure 4. Image of the RankineCyclerTM laboratory setup. ................................................................................... 7
Figure 5. Boiler assembly. .......................................................................................................................................... 8
Figure 6. Steam admission valve. ............................................................................................................................. 9
Figure 7. CAD cutaway of the steam turbine........................................................................................................ 10
Figure 8. Steam turbine. ........................................................................................................................................... 10
Figure 9. Electrical generator................................................................................................................................... 11
Figure 10. Cooling tower. ........................................................................................................................................ 11
Figure 11. Screenshot of the data acquisition system of the RankineCycler..................................................... 12
Figure 12. Flue gas temperature measurement. ................................................................................................... 13
Figure 13. Schematic of the boiler tubing. ............................................................................................................. 16
Figure 14. Caster wheels closed position. .............................................................................................................. 17
Figure 15. Snapshot of Load switch and rheostat position during the prestart checkup. .............................. 18
Figure 16. Snapshot of cooling tower draining step. ........................................................................................... 18
Figure 17. Snapshot of boiler front door during prestart check. ........................................................................ 18
Figure 18. Snapshot of boiler drain check during prestart check. ...................................................................... 19
Figure 19. Snapshot of proposed beaker position for boiler fill during prestart check. .................................. 19
Figure 20. Snapshot of the location for the aluminum coupler attachment to the boiler. .............................. 20
Figure 21. Location for observation of burner operation. ................................................................................... 21
Figure 22. Steam admission valve rotation counter-clockwise and clockwise to preheat the system. ......... 22
Figure 23. Snapshot of the target operating conditions for the generator after preheating is completed. ... 22
Figure 24. Snapshot of turning off the BURNER SWITCH during Shutdown. ............................................... 24
Figure 25.Snapshot of turning off the OPERATOR PANEL GAS VALVE during Shutdown. ...................... 25
Figure 26. Snapshot of turning off the LOAD RHEOSTAT during Shutdown. ............................................... 25
Figure 27. Snapshot of turning off the LOAD SWITCH during Shutdown. .................................................... 25
Figure 28. Snapshot of turning off the MASTER SWITCH during Shutdown. ................................................ 26
Figure 29. Snapshot of turning off the FUEL SOURCE during Shutdown. ...................................................... 26
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
4
1: INTRODUCTION
One of the most significant contributions to the development and growth of our modern technological way
of life has been the ability to extract vast amounts of energy from available natural resources. These energy
sources allowed us to generate and control work, power and heat to meet the functional demands of
societies around the world. Typical natural resources that are currently in use for energy purposes include
petroleum oil, natural gas, coal, biomass, water, wind, solar, and nuclear.
The production of heat and power is derived from man-designed thermodynamic cycles that manipulate
the existing conditions of a working fluid to extract naturally stored energy into a usable form. Several
cycles have been developed through history, however the Rankine cycle remains to be the most dominant
application in terms of market share (almost 90%), as it could be applied efficiently with a wide range of
fuels. The cycle is named after the Scottish civil engineer William Rankine (pronounced “Rang-Keene”),
who is considered one of the founding fathers in the field of thermodynamics.
In a power cycle, chemical energy of the fuel is transformed (through an intermediate step of heat
generation) into mechanical work. In a Rankine based power plant, the working fluid, which is water,
undergoes phase transformation into steam at elevated thermodynamic conditions and is used to drive a
turbine, where mechanical energy is finally transformed into the desirable or target product of electricity.
The real Rankine cycle found in existing power plants is much more complex and includes variations from
the idealized cycle, however the conceptual thermodynamic steps remain the same.
Upon completion of this laboratory assignment, as part of the course EEN-E1010 – Power Plants and
Process at Aalto University School of Engineering, a solid and fundamental understanding of the core
driving units in commercial power production is obtained. The RankineCyclerTM setup will offer an
opportunity for a hands-on experience on the operation and control of a lab-scale steam power plant. The
operational parameters of the cycle sub-processes are measured and analyzed to better understand their
performance characteristics. This knowledge will hopefully transfer very well into full-scale systems within
the power production industry.
Disclaimer: Some of the content in this laboratory students’ manual is based on the instruction and
operation manual documents provided by Turbine Technologies LTD for educational purposes of
operating the RankineCyclerTM steam turbine power system, model: RC-101.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
5
1.1 Rankine Cycle
Figure 1. Schematic of an ideal Rankine cycle. Q stands for heat and W for work. (Blue lines represent water in liquid state, Red
lines represent water in elevated steam conditions, Black lines are energy streams)
The ideal Rankine cycle consists of four subsequent processes for the working fluid, for e.g. water, to
undergo for the production of electricity, as shown and numbered in Figure 1. The theoretical starting point
of the cycle, state 1 is the water in its liquid form near ambient conditions. The first process is the isentropic
compression (1-2) of the working fluid by the mechanical work from the pump to elevated pressures. The
introduction of heat is the following step in an isobaric manner (2-3), for e.g. in a boiler, where liquid water
undergoes phase change into saturated and then finally superheated steam at state 3. Then the work
production step takes place, where the pressurized steam is expanded isentropically (3-4) within the
turbine to extract mechanical work. Finally, to close the cycle, remaining heat is removed in an isobaric
manner within the condenser (4-1) for the working fluid to return to the initial state of saturated liquid. The
thermodynamic cycle is further shown on the property diagrams in Figure 2, where the phase change or
cross from liquid to vapor and vice versa along with intermediate two-phase state are illustrated.
Figure 2. PV and TS property diagram for the ideal Rankine cycle.
BoilerTurbine
Pump
2
1 4
3
Condenser
qin
qout
WtWp
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
6
The four main steps of the real Rankine cycle are further demonstrated in Figure 3; where (1-2) is liquid
compression, (2-3) is the isobaric heat addition, (3-4) steam expansion and finally (4-1) water condensation.
In practice, the ideal cycle is not achievable and a deviation is present due to irreversibility in the
mechanical operation of the components, such as friction or heat transfer losses. The clear variation of the
real cycle (shown in Figure 3) to the ideal cycle (shown in Figure 2) is the presence of the irreversible steam
expansion step (3-4). As the introduction of the superheated steam through the nozzles of the turbine and
the process of vapor hitting the turbine blades and moving the shaft is irrecoverable in nature. As such,
step (3-4) is not isentropic and entropy is generated in that step which leads to less work extracted and then
additional heat is needed to be removed within the condenser step.
Figure 3. Temperature- Entropy TS diagram representation of the four processes within the Rankine cycle. Note: this is not an
ideal cycle.
As such, the energy analysis for the four processes/components could be defined by the enthalpy profile
at each stage, as following:
Water pump (1-2): 𝑊𝑝 = ℎ2 − ℎ1
Boiler (2-3): 𝑄𝑖𝑛 = ℎ3 − ℎ2
Turbine/Expander (3-4): 𝑊𝑝 = ℎ3 − ℎ4
Condenser (4-1): 𝑄𝑜𝑢𝑡 = ℎ4 − ℎ1
In addition, the overall thermal efficiency of the cycle is a combination of all four equations. Where, the
cycle input is the amount of heat added and product would be the net generated work.
Rankine cycle efficiency, 𝜂𝑇 =𝑊𝑛𝑒𝑡
Q𝑖𝑛 × 100% =
(ℎ3− ℎ4) −(ℎ2− ℎ1)
ℎ3− ℎ2 × 100%
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
7
1.2 The Laboratory Setup
Figure 4. Image of the RankineCyclerTM laboratory setup.
The RankineCyclerTM setup, shown in Figure 4, is a lab-scale power generation system specifically designed
for educational purposes. The setup resembles the operation and control of an industrial scale steam cycle,
where each component models the full size components in purpose and function. In this section, the
RankineCyclerTM components will be thoroughly introduced, including all components that make up the
actual system, its integrated data acquisition system and virtual instrument panel. From there, operating
the system allows the study of the important performance parameters such as; fuel energy density, boiler
heat flow, energy conversion efficiency, system mass flow rate, turbine work rate, generator
output/efficiency, condenser efficiency, total system efficiency.
1.2.1 Burner A forced air gas burner provides the necessary energy to vaporize the liquid working fluid as it passes
through the boiler, illustrated in Figure 5. An electrically driven centrifugal blower provides combustion
air to the burner through a blower duct. A fuel line is routed through this duct, delivering fuel to a gas
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
8
mixing nozzle. The fuel and air are further mixed by a vortex disk that introduces turbulence to the flow.
A “hot surface" igniter located in the fixed rear boiler door and at the end of the primary flame tube
provides the ignition source. The igniter is a resistance element that glows when current is applied to it.
The fuel and air mixture combusts when it comes in contact with this glowing element producing a flame
confined within the primary flame tube. Once combustion commences, the flame is self-sustaining and the
igniter will shut off.
Figure 5. Boiler assembly: 1- burner, 2- boiler 3- sight glass and 4- boiler pressure gauge.
1.2.2 Boiler
The boiler facilitates the vaporization of the system working fluid, making it available to the turbine for
power extraction. All boilers provide for some manner of heat transfer between the heat source and the
system working fluid. The RankineCyclerTM utilizes a fire tube and shell boiler arrangement, which is
representative of over 80% of all boiler systems in use today. The shell of the boiler is an 8 in (20.3 cm)
diameter by 11.5 in (29.2 cm) long stainless steel cylinder. The cylinder holds both the working fluid of the
system as well as the high-pressure vapor prior to it exiting to the turbine.
To allow heat transfer, 17 tubes of 0.5 in diameter (1.3 cm) pass through the cylinder allowing hot
combustion gasses from the burner to “flow through" the boiler. Five of these boiler tubes lie above the full
water line. A primary flame tube 2 in (5.1 cm) in diameter also passes through the boiler and holds the
flame produced by the burner. The walls of the 17 tubes and the primary flame tube provide nearly 380 in2
(2,451.6 cm2) of surface area for heat transfer.
1
2
3
4
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
9
Positive pressure provided by both the blower and the expansion of the combustion gasses moves the hot
air through and out of the primary flame tube. The rear boiler door then ducts this air to the 17 through
tubes. The combined volume of the 17 through tubes is just under that of the primary flame tube, insuring
an even air flow with maximum surface area contact. The hot air exits the through tubes and is ducted by
the front boiler door through a vertical stack, exhausting the combustion gasses up and away from the
boiler.
The front boiler door is hinged, while the rear is fixed. A latch secures the front door in the closed position
while the system is operating. When the system is not operating and sufficiently cool, the front door may
be unlatched and opened for viewing. The general arrangement of the through tubes and the primary flame
tube can be seen. The rear door holds the hot surface gas igniter while the front door holds the blower unit
and the exhaust stack.
1.2.3 Sight glass
The sight glass provides an indication of the relative level of working fluid within the boiler. An upper and
lower adjustable bezel allow the extents of working fluid to be marked. These markings make it easy to
measure the amount of working fluid consumed during operation of the system. Attached to the bottom
of the sight glass is the fill fitting, connecting the sight glass to the boiler and permitting the boiler working
fluid level to show in the sight glass. At the top of the sight glass is a vent fitting that also connects back to
the boiler to equalize pressure. The sight glass is not calibrated and only provides an indication of the boiler
fluid level. Because of the curvature of the boiler cylinder and the presence of the through tubes, the level
in the sight glass is non-linear over the volume of the boiler.
1.2.4 Boiler pressure gauge
An analog pressure gauge is installed providing a direct read out of available boiler pressure. The gauge
indicates the normal range of operation with a white background. The red area of the gauge indicates
pressure conditions that exceed normal operating limitations.
1.2.5 Steam admission valve
The steam admission valve is a needle type valve that regulates steam vapor flow to the turbine. In fully
clockwise position, it is CLOSED, preventing flow. In fully counter-clockwise position, the valve is OPEN
and the full flow of steam is available to the turbine. Intermediary positions regulate accordingly. In
addition to the steam admission valve setting, steam flow is dependent on boiler pressure and temperature.
Figure 6. Steam admission valve.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
10
1.2.6 Steam turbine
The steam turbine provides useful work through the extraction of energy from the vaporized working fluid
provided by the boiler. High pressure steam is directed through a nozzle, forcing the steam to impinge
directly on the blades of the turbine wheel causing it to rotate. This rotation is then used to derive useful
work. The single stage turbine unit is made up of a front and rear housing, each precision machined and
fitted with a carbon bearing requiring no additional oil or lubrication.
Figure 7. CAD cutaway of the steam turbine.
The three main functional steps within the turbine are shown in Figure 7 and could be summarized as:
1. Steam enters inlet port at the bottom left.
2. Steam flow forced through slits in stator ring (purple), impinging on turbine blades, spinning
turbine wheel (red).
3. Steam exits turbine to condenser.
In addition to the inlet and outlet fittings in the front and rear housing, respectively, two other fittings
provide transducer access to turbine inlet temperature and pressure as well as turbine outlet temperature
and pressure. These values are measured by the data acquisition system and available on the computer.
Figure 8. Steam turbine.
1
2
3
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
11
1.2.7 Generator
The generator utilizes the rotational motion of the turbine to produce electrical energy. A four-pole,
permanent magnet, brushless design, the generator is directly coupled to the output shaft of the turbine
and supported on its own set of preloaded ball bearings. Both alternating current (AC) and direct current
(DC) are available at the generator outputs.
Figure 9. Electrical generator.
1.2.8 Cooling tower
The cooling tower facilitates heat transfer between the hot vapor exiting the turbine and the relatively cool
ambient air surrounding the tower. The tower mantle, manufactured from aluminum, provides the heat
transfer interface and a condensation surface. Steam enters the cooling tower through a distribution
manifold that disperses the steam within the tower to maximize contact with the mantle. Four internal
stainless steel baffles further direct the steam along the mantle, while allowing condensate to run back to a
catchment basin at the bottom of the tower. This basin can be drained, using the attached hose and pinch-
clamp, to accurately measure the amount of condensate collected.
Figure 10. Cooling tower.
1.2.9 Data acquisition system
The RankineCyclerTM is equipped with a National Instruments 6218 precision data acquisition system,
which provides full range of system parameter measurement. This system, consists of a suite of sensors,
excitation power sources, signal conditioners, data acquisition hardware and user interface software, when
used in conjunction with an appropriate computer, allows actual run-time data to be displayed and
recorded for later analysis.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
12
Figure 11. Screenshot of the data acquisition system of the RankineCyclerTM.
1.2.10 Operator panel
The panel is shown in Figure 12 and consists of the following control switches:
Keyed Master Switch: The key lockable master switch controls the supply of electrical power to the
main bus that powers the indicator lights, boiler combustion boiler and the gas control module.
GREEN indicator light will illuminate when this switch is selected ON and power is available.
Burner Switch: The burner switch enables the gas control module and powers the burner blower. A
RED indicator light above the switch will illuminate when this switch is selected ON and power is
available to the burner circuits.
Low Water Indicator Light: RED indicator that shows a warning by the low water level in boiler.
Load Switch: The load switch enables the load bank. The load bank presents a true load to the
generator, allowing the operator to simulate conditions at a full scale power station when consumer
demand fluctuates.
Load Rheostat Control: The full counter-clockwise position of the control represents NO LOAD, full
clockwise position of the control represents FULL LOAD.
Operator Panel Gas Valve: Rotating the black gas valve knob counter-clockwise to the 3 o'clock
position OPENS the valve. Rotating the valve knob clockwise to the 6 o'clock position CLOSES
the valve and prevents any flow of gas through the regulator.
Amp Meter: The amp meter indicates the amount of current the load is drawing based upon the
load (as set by the Load Rheostat Control) and the available voltage (as provided by the generator;
a function of generator speed/RPM).
Volt Meter: The volt meter indicates the amount of voltage the generator is providing (a function of
generator speed/RPM).
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
13
Figure 12. RankineCyclerTM operator panel with illustrations of the main components.
1.2.11 Liquid propane cylinder
The cylinder contains the fuel necessary to operate the system. The fuel regulator is completely closed
during startup and then completely open when operation takes place. The Operator Panel Gas Valve in the
operator panel controls the flow of fuel to the burner, and is set to a constant value throughout the
experiments.
1.2.12 Flue gas temperature thermocouple The temperature thermocouple is inserted into the flue gas exhaust to record the outlet temperature. A
measurement device will be provided during the experiment to take sample readings, shown in Figure 13.
Figure 13. Flue gas temperature measurement.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
14
1.3 General Operational limitations The RankineCyclerTM is designed to be operated within the following limitations. Under no circumstances
should these limitations be exceeded by any margin. Operator safety and efficient operation of the R
RankineCyclerTM is contingent upon these limitations being followed.
1.3.1 BOILER
MAXIMUM OPERATIONAL BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . 120 psi (827 kPa)
MAXIMUM OPERATIONAL BOILER STEAM TEMPERATURE . . . . . . . . . . . 608 ±F (320 ±C)
MAXIMUM OPERATIONAL BOILER VOLUME . . . . . . . . . . . . . . . . . . . . . . 203 oz (6,000 ml)
OPERATING FLUID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WATER
1.3.2 BURNER
FUEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LIQUID PROPANE (LP) ONLY
1.3.3 GENERATOR MAXIMUM GENERATOR OUTPUT, Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15.0 Volts
MAXIMUM GENERATOR OUTPUT, Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0 Amps
MAXIMUM GENERATOR OUTPUT, Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Watts
MAXIMUM GENERATOR SPEED, RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4500 RPM
1.3.4 ABNORMAL SHUTDOWN “OFF-OPEN-OFF”
The RankineCyclerTM is designed with the necessary safety alarms and switch offs that minimize hazardous
operation and ensures operator safety. In the unlikeliness of abnormal events or accidents (Fire or electrical
malfunction) taking place during the operation, familiarize with the following ABNORMAL
SHUTDOWN procedure. CAUTION that this procedure is for the worst case scenario and will be
performed by the TEACHING ASSISTANT.
The “OFF-OPEN-OFF” procedure includes
1. OFF – Shut OFF the MASTER SWITCH, to cut off all electrical system operation.
2. OPEN – Fully OPEN the STEAM ADMISSION VALVE, to relieve system pressure.
3. OFF – Shut OFF the supply of gas to the burner.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
15
1.4 General Guidelines The following General Guidelines are offered as reminders of items requiring particular attention, further
details on each are mentioned throughout the manual.
Mandate the appropriate personal safety equipment for all operators and observers.
Know the facility safety policies, emergency contact numbers and location of fire extinguishers.
Read and become familiar with the RankineCyclerTM Student's Manual.
DO NOT operate RankineCyclerTM without first becoming familiar with the Student's Manual.
DO NOT operate the system unattended.
Use the provided checklists during every operation.
Lock all four caster wheels during operation.
Use only in a well ventilated area.
Continually monitor all system parameters and be attentive for out of limit readings. Immediately
consult with the teaching assistant if anything is questionable.
DO NOT exceed scale readings/limitations on any instrument or gauge.
Remember, the working fluid is high temperature, pressurized steam.
Consider all surfaces to be HOT during and for a significant time after operation. DO NOT touch
any surface during operation.
DO NOT move the system while operating or when the boiler is pressurized.
DO NOT allow the boiler water level to become less than 1.0 in (2.5 cm) as indicated on the sight
glass.
DO NOT attempt to fill the boiler while the system is pressurized.
DO NOT open the boiler doors while hot, doing so may cause permanent warp-age of the boiler
cradle.
DO NOT tighten or adjust fittings while system is under pressure.
DO NOT tap on or scratch boiler sight glass.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
16
2: Pre-operation Preparation (For Demo run purposes only). In preparation for the system operation and data analysis, students are advised to read the complete
laboratory manual, familiarize themselves with the setup and perform some background reading on the
Rankine cycle as well as the different operational components.
Each student present for the demo lab run is expected to present a personal data sheet answering the
following questions before taking part in the experiment.
1. Liquid propane (LP) is the current used fuel, where it is vaporized and introduced into the burner.
What is the energy content per unit volume and mass of gaseous LP? Identify both the lower and higher
heating value of LP? If we assume a flow of 6 L/min at steady state, what is the energy consumption
per hour of the system? What are the expected products in the flue gas, (assume 100% content of C3H8)
in the cases of excess, stoichiometric and deficit oxygen supplied?
2. Sketch a process flow diagram (use blocks to show components, do not need to draw each component)
of the laboratory setup, and illustrate the major input and output material and energy streams. (Hint:
Microsoft Visio® is a good tool to assist you. However, hand sketched diagrams are perfectly accepted).
3. The boiler is shell and tube style construction. Calculate the available volume for water in the boiler
given the basic construction dimensions shown in Table 1. If the boiler is filled with 5500 ml of water,
what is the fill percentage and estimate the number of flame tubes that would not be submerged within
the working fluid.
Table 1. Boiler basic dimensions.
Main Shell External Length 29.85 cm
Main Shell Wall Thickness 0.198 cm
End Plate Outside Diameter 20.32 cm
End Plate wall thickness 0.318 cm
Main Flame Tube Outside Diameter 5.08 cm
16 Return Pass Flame Tubes Outside Diameter 1.9 cm
Figure 14. Schematic of the boiler tubing.
4. What are the operating limitations for the BOILER pressure, generator voltage and ampere output.
5. State the three main steps in the ABNORMAL SHUTDOWN procedure.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
17
3: System Operation This section includes the standard procedural steps for Prestart check, Startup operation, Steady state
operation and Shutdown, which allows for an efficient and safe operation of the system. Familiarity with
these procedures must be made prior to operating the RankineCyclerTM for the first time. Even experienced
operators should continue to use the checklist for each operational run to eliminate the possibility of
overlooking or inadvertently eliminating a necessary step. All steps are expected to be conducted by the
student group members, under the supervision of the teaching assistant, and should be followed exactly in
the same sequence presented here in the manual. The data acquisition system is used to capture all
operational values from startup to shutdown, however some data are required to be obtained manually:
Steady state start time.
Steady state stop time.
Initial, intermediate and final Boiler fill estimate on the sight glass.
Amount of condensate collected during experiment.
Flue gas temperature readings.
3.1 Prestart check The PRE-START checklist must be completed prior to operating the RankineCyclerTM. The checklist ensures
that all system components are ready for operation and that heat can be safely applied to the boiler.
1. THE AREA CHECK and SAFETY MEASURES- assessment to VERIFY SUITABILITY OF
THE OPERATION and the SAFETY of the operators (Each group member should present a
personal data sheet similar to that shown in Section 2). This step is to ensure all members of
the group are familiar with laboratory safety procedures, any additional equipment
requirements and an opportunity for consultation with the teaching assistant on any questions
or concerns before operation. All operators and personnel in the immediate area should know
the location of fire extinguisher equipment, circuit breakers and fuel supply valves, as well as
being familiar with existing safety policies and procedures, emergency escape routes, and
emergency services telephone numbers/points of contact.
2. CASTER WHEELS must be in the LOCKED position prior to operation, preventing movement
that may either pose a safety hazard or disrupt critical operations such as boiler filling.
Figure 15. Caster wheels closed position.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
18
3. Ensure the following switch positions:
a. MASTER SWITCH - OFF position: GREEN light OFF
b. BURNER SWITCH - OFF position: DOWN position
c. LOAD SWITCH - OFF position
d. LOAD RHEOSTAT – Minimum load – FULL COUNTER-CLOCKWISE POSITION
Figure 16. Snapshot of Load switch and rheostat position during the prestart checkup.
e. OPERATOR PANEL GAS VALVE – OFF positon
4. Perform a thorough VISUAL INSPECTION of each major component and the system. Verify
that no components are damaged, tampered with or missing from previous runs.
5. Drain the COOLING TOWER using the attached clear tubing and pinch-clamp. Discard any
condensate collected, and empty in drain after measurement, DO NOT RE-USE.
Figure 17. Snapshot of cooling tower draining step.
6. The FRONT BOILER DOOR must be CLOSED and LATCHED (REAR DOOR is stationary).
Figure 18. Snapshot of boiler front door during prestart check.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
19
7. The STEAM ADMISSION VALVE must be OPEN to allow air to vent out of the boiler
during the fill operation. Water will not enter the boiler with the valve closed.
8. The BOILER should be DRAINED completely using the fill/drain valve and beaker assembly.
Figure 19. Snapshot of boiler drain check during prestart check.
9. Fill the BOILER with 5,500 ml of clean, distilled water for the most efficient operation. Any
quantity over this recommended amount will likely degrade boiler performance and may
prevent the boiler from producing any pressure. During fill, scale the boiler level on the sight
glass, in order to be able to estimate the water consumption during steady state. With the
beaker ball valve closed, fill the beaker to the desired boiler level.
a. Place the beaker on a firm support higher than the boiler fill/drain valve at the rear of
the boiler. If this is the first run of the day or adequate time has passed that the cooling
tower is sufficiently cold, beaker can be placed on the tower.
Figure 20. Snapshot of proposed beaker position for boiler fill during prestart check.
b. Insert the aluminum coupler at the end of the beaker hose assembly into the fill/drain
valve coupling hole.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
20
Figure 21. Snapshot of the location for the aluminum coupler attachment to the boiler.
c. Open the beaker ball valve to allow water to fill the boiler. At the meantime SCALE
(calibrate) the SIGHT GLASS at equal intervals. (recommended every 500 ml)
d. When all the water has emptied from the beaker, close the beaker ball valve and
remove the aluminum coupler from the fill/drain valve. If the beaker assembly was
placed into the top opening of the cooling tower while filling the boiler, remove it
before proceeding to the next step.
10. Now, put the STEAM ADMISSION VALVE back to the CLOSED position which was opened
before filling the boiler. Starting with a closed valve lets boiler pressure properly build up.
11. Now, connect the COMPUTER DAQ SYSTEM USB cable to the USB system on the left side
panel of the RankineCyclerTM. Make sure the computer is OFF prior to connecting the cable or
the DAQ Module hardware/software may not properly initialize.
12. Connect the RANKINECYCLER ELECTRICAL SERVICE to the electrical outlet.
13. Check the FUEL SOURCE line connection to the LP FUEL SUPPLY TANK.
3.2 Start operation The Start operation procedure is necessary to take the RankineCyclerTM from cold shutdown conditions
through preheating and to run-time data collection at steady state.
1. THE COMPUTER DAQ SYSTEM should be turned on. Note: ensure that the computer USB
connection is attached to RankineCyclerTM before the computer is turned on, to avoid improper
DAQ module hardware/software initialization. TURN DATA LOG ON.
2. FUEL SOURCE regulator is opened, and initial FUEL LEAK CHECK must be completed
before any further steps take place. (NOTE: LOOK OUT FOR A “HISSING” SOUND OR
FUEL ODOR)
3. OPERATOR PANEL GAS VALVE is turned to ON position.
4. MASTER SWITCH key is turned to ON position. GREEN light is illuminated, which indicates
that electrical power is now available to the system components.
5. Check if the FLUE GAS TEMPERATURE MEASUREMENT and GAS ANALYZER devices
are working.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
21
6. Select the BURNER SWITCH to the ON position. RED light is illuminated. Observe the
COMBUSTION BLOWER and verify if it is on. The blower motor should be heard as it begins
to rotate, drawing air into the burner and forcing it through the boiler.
NOTE: To PURGE FUEL LINES, you could allow the blower to operate for 45 seconds then
turn the BURNER SWITCH off and immediately back on (CONSULT WITH THE
TEACHING ASSISTING BEFORE PURGING).
7. VERIFY that the BURNER has LIT within 45 SECONDS of selecting the BURNER switch on.
It should be noted that the burner may occasionally burp" - producing an audible popping
noise with a small blue flame present at the blower inlet. This behavior is normal and should
NOT be considered a fire requiring the execution of the abnormal procedures.
Figure 22. Location for observation of burner operation, Blue flame is considered the first sign, in addition to a distinguishable
gas burning noise.
8. Monitor BOILER PRESSURE on the pressure gauge as well as through the DAQ system.
VERIFY POSITIVE PRESSURE within 3 MINUTES from start. If not, turn off the BURNER
SWITCH and investigate. Verify that the proper amount of water is in the boiler and the
STEAM ADMISSION VALVE is fully CLOSED.
9. Allow the indicated BOILER PRESSURE to rise to approximately 120 psi (827 kPa).
10. The system should now be PREHEATED. This allows the steam lines, valves and turbine to
come up to the proper operating temperature. The turbine bearings are also lubricated at this
time. During the preheating period, small vapor leaks and condensation droplets may be seen
around the turbine and related fittings. This is normal and should subside once the turbine
bearing clearances close due to thermal expansion. The preheating process outlined below
should take approximately 7 to 10 MINUTES to complete. This preheating process is essential
to supplying the highest quality steam available to the turbine. If preheating is omitted,
condensation will form in the steam lines degrading system performance overall. The
preheating steps are:
a. The STEAM ADMISSION VALVE should be turned counter-clockwise to OPEN.
This will allow steam to flow throughout the system. The turbine/generator may or
may not rotate at this point.
b. Monitor BOILER PRESSURE until it falls to approximately 50 psi (345 kPa). During
which the load switch (Turn ON) and rheostat knob will have to be used so the
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
22
turbine/generator does not over speed (RPM should be below 2500) and not exceed 9
volts. (GROUP WORK IS ESSENTIAL AT THIS POINT TO SYNCHRONIZE THE
RHEOSTAT ADJUSTMENT WITH THE RESULTING GENERATOR READING
ON THE DAQ SYSTEM)
c. The STEAM ADMISSION VALVE should be turned clockwise to CLOSE. This will
stop the steam flow and allow for boiler pressure to build up again.
Figure 23. Steam admission valve rotation counter-clockwise and clockwise to preheat the system.
d. Turn the RHEOSTAT knob back to original position and shut the LOAD SWITCH off.
e. Allow BOILER PRESSURE to rise back to approximately 120 psi (827 kPa).
11. Open the STEAM ADMISSION VALVE slowly, while maintaining approximately 120 psi
(827 kPa) of BOILER PRESSURE. Once the turbine begins to rotate, the generator will produce
electricity. Monitor the turbine RPM, it should not exceed the safe limit of 2500. Generator
output will be directly indicated on the VOLT METER.
12. Turn ON the LOAD SWITCH again. Continue opening the STEAM ADMISSION VALVE
and simultaneously ADJUST the LOAD RHEOSTAT.
Figure 24. Snapshot of the target operating conditions for the generator after preheating is completed.
13. In preparation of an experimental data run, the STEAM ADMISSION VALVE and the LOAD
RHEOSTAT may continue to be adjusted to achieve a STEADY STATE CONDITION.
Satisfactory run-time results can be achieved with the following values:
a. An AMP METER indication of approximately 0.23-0.35 Amps.
b. A VOLT METER indication of approximately 8.0-9.0 Volts.
c. A BOILER PRESSURE indication according to experimental conditions (generally
120 psi (827 kPa)).
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
23
3.3 Steady state operation (Experimental run) This section illustrates the experimental procedure for operation, as well as the necessary data acquisition
after steady state conditions are achieved. The system will be operated at two different boiler pressure
steady conditions, the first is the design (or optimal) setting of 120 psi and the second pressure level is at
the lower conditions of 85 psi. A data set will be collected for each pressure condition and a system level
analysis should be conducted for each.
1. To begin the experimental run, TIME and BOILER FILL LEVEL from the sight glass should
be noted. This is essential as data log in the DAQ is not in real time (only cumulative time) so
a comparison between the real time at which the log started and the experimental start is
needed to establish the time interval for usable data in the steady state analysis.
2. CHECK with the teaching assistant that the data log for the flue gas analyzer is also turned on.
3. SET the SIGHT GLASS UPPER BEZEL to the current, indicated WATER LEVEL. This value
will be compared to the end of the experiment level to validate your calculation for steam flow
rate through the system.
4. For the operation of the first pressure level, set the group starting TIME and continue to use
the STEAM ADMISSION VALVE to make PERIODIC ADJUSTMENTS maintaining the
STEADY STATE established in the experiment (120 psi) for a total period of 5 MINUTES.
5. The FLUE GAS TEMPERATURE reading should be periodically taken and noted every 30
seconds for the duration of the 4 minutes.
6. At the END of the 5-minute interval, NOTE the time for the 120 psi run and NOTE down the
new level of water in the BOILER from the CALIBRATED SIGHT GLASS, this data will be
used to assume the steam flow exiting the steam admission valve during the run.
7. After completion of data collection for the first run, use the STEAM ADMISSION VALVE to
make PERIODIC ADJUSTMENTS to bring the BOILER PRESSURE down to the second
pressure level and maintain steady state conditions for a total period of 3 MINUTES. The
RHEOSTAT KNOB should be adjusted accordingly to maintain the recommended operation
conditions for the generator similar to the steady state.
8. Note the TIME of start and BOILER FILL LEVEL. Then REPEAT STEPS 5 to 8 for the new
pressure level.
9. After finishing the experimental runs, the COOLING TOWER should be drained to measure
the amount of CONDENSATE collected during the whole experiment (preheating and steady
state operation). As the condensate will contain suspended turbine oil, it is suggested that a
disposable or condensate specific vessel be used. NOTE that the CONDENSATE is HOT, so
should be collected with care.
IMPORTANT NOTE: For the second run, make sure that the boiler water level does not drop too
low. If you observe that this is the case, consult with the teaching assistant immediately.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
24
A number of responsibilities could be delegated or shared among the group members during
the two pressure level runs. It is advised to be set and agreed upon as part of the preparation
before starting the experiment: (The arrangement below is only a suggestion).
a. Responsible for the checklist and ensure procedural sequence of the experimental run.
b. Monitor recommended operation conditions on the DAQ and liaison with other
member handling the rheostat knob.
c. Handle the steam admission valve and the rheostat knob (generator load) along with
monitoring the voltage and ampere readings of the generator from the operator panel.
d. Water level measurement in the boiler.
e. Data logging and time keeping for the two runs.
f. Flue gas measurement (temperature) recording, the analyzer data will be provided by
the teaching assistant.
g. Condensate collection and data recording.
3.4 Shutdown The SHUTDOWN checklist ceases RankineCyclerTM operation and places the system into a known, safe
condition.
1. Turn the STEAM ADMISSION VALVE to the CLOSED position.
2. SET the SIGHT GLASS LOWER BEZEL to the current, indicated WATER LEVEL. This allows
measurement of the boiler water consumed during the whole experimental run.
3. Select the BURNER SWITCH to OFF. Verify that the RED light is extinguished indicating
that no electrical power is available at the burner or the blower. The blower should
immediately stop rotating.
Figure 25. Snapshot of turning off the BURNER SWITCH during Shutdown.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
25
4. The OPERATOR PANEL GAS VALVE should be selected OFF.
Figure 26.Snapshot of turning off the OPERATOR PANEL GAS VALVE during Shutdown.
5. The LOAD RHEOSTAT should be turned FULL COUNTER-CLOCKWISE, resulting in
MINIMAL LOAD.
Figure 27. Snapshot of turning off the LOAD RHEOSTAT during Shutdown.
6. The LOAD SWITCH should be selected OFF.
Figure 28. Snapshot of turning off the LOAD SWITCH during Shutdown.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
26
7. Turn DATA LOG OFF in the computer DAQ system and the gas analyzer systems to stop
recording system measurements.
8. The MASTER SWITCH should be selected OFF. Verify that the GREEN light is extinguished.
Figure 29. Snapshot of turning off the MASTER SWITCH during Shutdown.
9. The STEAM ADMISSION VALVE should be turned to the fully OPEN position SLOWLY
as to not exceed 9 volts. This relieves all remaining boiler pressure.
10. The FUEL SOURCE valve should now be turned OFF.
Figure 30. Snapshot of turning off the FUEL SOURCE during Shutdown.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
27
4: Practical Guidelines for Reporting This section shows the guidelines for the final technical report and presentation for each student group, as
well as for laboratory run data acquisition and system analysis.
4.1 Technical Report Guidelines The technical report is expected to showcase the accumulated knowledge by the group members of the
fundamentals of a Rankine cycle-steam power plant for design, operation and analysis purposes. Logically
the language of the report should be in English only. All members of the group are expected to participate
actively in the laboratory run as well as in reporting. Thus, the report is expected to include a sub-section
as part of the introduction which specifies the delegated tasks and the contributions of each member. The
expected outline of the report (chapters) includes:
(Groups are free to restructure the report, this is merely a guideline for what should be included)
Cover page.
The cover page represents the title of the work, each group is free to choose the report name, which
should reflect the topic of report as well as purpose of laboratory run or the main findings from the
run. The page should include group number, list of members, and their respective information.
Abstract.
The abstract is a short summary of the report, maximum 200 words, with emphasis on the highlights
in the report. A list of 4 key words should be included at the end also.
Table of content, list of Figures and list of Tables.
Introduction.
Clearly indicate the context/background of the technical report. The objective of the laboratory run.
Group members’ contribution and designated tasks. Outline the reporting approach and content.
Theoretical background.
Use an appropriate title based on the content that is included. The chapter should include all the
necessary theory and background knowledge for the following chapters. In addition to a literature
review that lists all the sources for equations used in the calculations part.
Laboratory Setup and Procedure
Refer to the RankineCyclerTM schematic and explain the overall operation. Point out and explain the
similarities and differences between the laboratory setup and the industrial scale systems. Identify
what are the processing parameters measured and why. Provide a brief description of the experimental
procedure (Do not simply copy the Laboratory’ manual). List sets of experiments done and the range
of parameters that have been tested.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
28
Results.
List down and organize the laboratory run data in a coherent structure that would support the
following discussion. Select which data are relevant here and which could be rather included in the
Appendices. Present the data in a meaningful way, that major findings could be extracted from them,
thus graphs are always preferable to tables. (Note: tables are still recommended to use when listing
data such as specifications)
Discussion and Findings
Describe how the results alter along the variation of certain process parameters and how such change
would influence overall system and component performances. Identify sensitive (most impactful)
parameters and validate through comparison with what is reported in literature.
Note: This part should also include an analytical comparison between the two steady state operation
conditions.
Conclusions.
Brief summary of the main findings in the report.
References.
Nomenclature and Appendices if needed.
In general, each report should have enough detail so that the reader can comprehensively follow and
reproduce your main findings. The report is expected to list in detail the procedure and results of your
laboratory run, in addition to the discussion and analysis of the system performance. The latter two will
distinguish reports from each other and will significantly influence the final grading. The writing style is
expected to be in a technical and direct manner.
4.2 Oral presentation The schedule for the presentation is announced during the course lectures. The presentation is a group
effort where all members are expected to take part. The maximum duration of the presentation per group
is 20 minutes, with an additional 5 minutes allocated for a Q&A session. The content of the presentation
should be based around the technical report. However, complete freedom is given to the group in the
presentation design or for addition of elements to the presentation technical content deemed by the group
beneficial. The use of any support materials or tools during the presentation will be considered a bonus.
The overall grading for the presentation will be based on organization, time management, technical
content, presentation skills (language proficiency, demeanor & body language) and creativity.
The peer review process will take place after the oral presentation at which names of the group members
would be drawn anonymously, every member will be given two other member names to evaluate. The
results would be collected by the teaching instructors (only individuals to have access to that information)
and would be combined along the pre-assignment, technical report and oral presentation grading for the
overall grade.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
29
4.3 RankineCyclerTM Data Run Plots Graphically plot the RankineCyclerTM run data extracted from the DAQ system as a first step for the
following system analysis and performance calculations to be conducted in the following sections. Plot the
following operation parameters vs. TIME, utilizing MS-Excel, where the different operational states (the
two steady state operations and transitional states) are clearly defined and distinguished):
Fuel Flow.
Boiler Temperature.
Boiler Pressure.
Turbine Inlet/Outlet Temperature.
Turbine Inlet/Outlet pressure.
Generator DC Amps output.
Generator DC Voltage Output.
Turbine RPM.
Power produced.
From the gas analyzer data, plot the flue gas concentration of Oxygen, Carbon dioxide and Carbon
Monoxide, Propane vs. TIME, while showing the steady state conditions.
Note that steady state conditions will be the basis for your system level analysis. From the plots and the
data collected from the system run, record the following for each steady state pressure condition:
Average Fuel Flow.
Average Boiler Temperature.
Average Boiler Pressure.
Average Turbine Inlet/Outlet Temperature.
Average Turbine Inlet/Outlet pressure.
Average Power produced.
Water consumption from the Boiler.
Condensate amount collected (total operational time).
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
30
4.4 System Analysis The objective is to conduct performance calculations using controlled volume thermodynamic
conservation laws to develop the mass and energy balance of the system and its components.
Any thermal (steam) power plant performance is mainly characterized by
Mechanical power output, 𝑊𝑡 (kW)
Electrical power output, 𝑊𝑒𝑙 (kW)
Cycle thermal efficiency, 𝜂𝑡ℎ (%)
Heat rate, 𝐻𝑅 (kJ/kWh)
Steam rate, 𝑚𝑠 (g/s)
Fuel rate, 𝑚𝑓 (g/s)
Electrical (overall) efficiency, 𝜂𝑒𝑙 (%)
Capacity factor, reliability and operating flexibility. (not included in calculation but should be
discussed in the report)
In your calculations, refer to the lecture and exercise materials along with the reference book Advanced
Energy Systems by Khartchenko for detailed formulation of the equations. Assume kinetic and potential
energy as negligible throughout the calculation for the two pressure level cases. The data needed for these
calculations come from the information plotted and recorded in the previous section. Note that steam tables
should be also used for each of the points of interest within the system.
NOTE: that although the accuracy of measurement data is an important operational consideration for
industrial application, in this laboratory assignment, the emphasis is on showing the ability to interpret the
data collected from the laboratory run and utilize it for thermal analysis of the overall plant as well as the
sub-processes.
4.3.1 Boiler
Perform the mass and energy balance for the boiler, show an illustration of the material and energy streams
on a diagram and specify the following:
Heat flow into the Boiler. (kW)
Determine the real Air to Fuel ratio, as well as Lambda.
Heat losses with the Flue gas. (kW)
Heat production from the Boiler in the product steam. (kW)
Boiler thermal efficiency. (%)
4.3.2 Turbine Calculate and specify the following:
Isentropic efficiency of the turbine. (%)
Generator efficiency. (%)
Heat losses within the steam admission valve (losses due to throttling effect). (kW)
Note: if the calculated average values are below saturation temperature, assume saturated steam
properties.
EEN-E1010 – Power Plants and Processes
Laboratory Assignment Student Manual V.03
31
4.3.3 Cooling Tower
Perform the mass balance only for the cooler tower, show an illustration of the water streams on a diagram
and specify the following:
Overall tower extraction efficiency. (%) Hint: (𝑚𝑐𝑜𝑛𝑑𝑒𝑛𝑠𝑎𝑡𝑒
𝑚𝑖𝑛𝑙𝑒𝑡⁄ )
Heat rejected in the condenser for each steady state. (kW)
The current cooler is air-cooled, calculate the theoretical amount of cooling medium needed if it
was water cooled. (kg/s) Hint: assume a temperature rise of 10 °C for the coolant water.
4.3.4 Overall System
Perform the overall steady state mass and energy balance, show an illustration of all material and energy
streams (with computed values) on a process flow diagram, and specify the following:
The cycle thermal efficiency. (%)
The plant electrical efficiency. (%)
Also show the T-S and H-S diagrams of the plant for the three steady state cases.