uniflair brex1612a-2812a technical data
DESCRIPTION
Schneider Electric chiller manualTRANSCRIPT
Release 1.0 – July 2011 – for internal use only 3
Release 1.0 – July 2011 – for internal use only 4
Release 1.0 – July 2011 – for internal use only 5
MAIN TECHNICAL DATA
BREC – F 1612A 1812A 2212A 2512A 2812A
Power supply V/ph/Hz 400 / 3 / 50
Refrigerant R134a
Fans Nr 6 6 8 8 8
Standard model Type Axial with asynchronous motor
poles 6 6 6 6 6
EC model Nr Axial with electronically commutated motor
Condensation control
Type Modulating condensation control based on condensing temperature
Cooling circuits Nr 2 2 2 2 2
Expansion Valve Type Electronic Expansion Valve
Compressors Nr 2 2 2 2 2
Type Double Screw
Capacity control Mode Step
Steps 8
Evaporator Type Single passage Shell & Tube
Partial heat recovery heat exchanger
Type Plate
Release 1.0 – July 2011 – for internal use only 6
TECHNICAL DATA
NOMINAL CONDITIONS
The technical data shown in the following pages refer to nominal conditions and tolerances which are as follows:
Nominal conditions BREC BREF
Operation mode Cooling Cooling Free-cooling
Inlet / outlet water temperature °C 12 / 7 15 / 10 15
External air temperature °C 35 35 5
Ethylene glycol % 0 20 20
Nominal power supply tolerance R0 400V +/- 10%
Storage conditions C0 tra / between – 20°C e + 45°C per tutti i modelli / for all models
CORRECTION FACTORS
If antifreeze mixtures are being used, some of the unit’s specifications given in the table (capacity, water delivery, load loss) will change. Correction factors are given below for calculating the data based on different percentages of ethylene glycol.
Minimum fluid temperature with unit operating
5,0 °C 3,0 °C -5,0 °C -10,0 °C -18,0 °C -28,0°C
Freezing temperature 0 °C -4,4 °C -9,6 °C -16,1 °C -24,5 °C -35,5 °C
Percentage of ethylene glycol by weight 0% 10% 20% 30% 40% 50%
Correction factors % 0% 10% 20% 30% 40% 50%
Cooling capacity R0 1 0,985 0,98 0,97 0,96 0,95
Compressor power consumption P0 1 0,995 0,99 0,98 0,98 0,97
Volumetric flow rate L0 1 1,02 1,05 1,08 1,10 1,14
Evaporator / condenser pressure drop C0 1 1,10 1,25 1,40 1,60 1,7
Corrected cooling capacity (**) = Nominal cooling capacity x R0. Corrected compressor power consumption (**): Nominal absorbed power x P0. Corrected volumetric flow rate (**):Nominal volumetric flow rate x L0. Corrected evaporator pressure drop, water side (**): Evaporator pressure drop x Co. (**) with the same evaporator inlet and outlet temperatures 12/7
Release 1.0 – July 2011 – for internal use only 7
BREC
BREC
NOMINAL TECHNICAL DATA
BREC
Cooling only unit 1612A 1812A 2212A 2512A 2812A
Cooling capacity (1) kW 365 420 517 557 661
Absorbed power (2) kW 104,7 119,1 151,9 168,4 189,3
E.E.R. (2) 3,48 3,52 3,40 3,32 3,49
E.S.E.E.R. (3) 4,41 4,28 4,53 4,30 4,52
I.P.L.V. (4) 5,00 4,80 5,18 4,86 5,11
Water flow (1) l/h 62640 72360 88920 95922 113760
Evaporator pressure drop (1) kPa 29 41 50 57 55
Air flow (1) m3/h 121875 116813 162500 162500 155750
BREC
Cooling only unit with economizer
1612A 1812A 2212A 2512A 2812A
Cooling capacity (1) kW 394 469 562 598 728
Absorbed power (2) kW 116 140 172 186 222
E.E.R. (2) 3,38 3,34 3,26 3,21 3,28
E.S.E.E.R. (3) 4,46 4,32 4,50 4,29 4,49
I.P.L.V. (4) 5,18 4,95 5,35 4,95 5,18
Water flow (1) l/h 67944 80761 96903 102960 125363
Evaporator pressure drop (1) kPa 33,7 50 59 65,5 65
Air flow (1) m3/h 121875 116813 162500 162500 155750
(1) Data refer to nominal conditions: Inlet / outlet water temperature: 12 / 7 °C; External air temperature 35 °C; glycol 0% (2) Data refer to total input power.(compressors and fans) (3) European Seasonal Energy Efficiency Ratio (4) Integrated Partial Load Value
Release 1.0 – July 2011 – for internal use only 8
BREF
BREF
NOMINAL TECHNICAL DATA
BREF
Free-cooling unit 1612A 1812A 2212A 2512A 2812A
Cooling capacity (1) kW 396 446 553 598 702
Absorbed power (2) kW 110 126 158,5 178,7 203
E.E.R. (2) 3,60 3,54 3,49 3,35 3,46
Water flow (1) l/h 72720 82080 101520 109909 128880
Evaporator pressure drop (1) kPa 43 58 72 83 78
Airflow (1) m3/h 112500 105000 150000 150000 140000
Free-cooling capacity (3) kW 295 345 399 405 477
Absorbed power in free-cooling (3-4)
kW 16,7 17,3 23,8 24,1 25,
E.E.R. in free-cooling (3-4) 17,7 19,9 16,7 16,8 19
BREF
Free-cooling unit with economizer
1612A 1812A 2212A 2512A 812A
Cooling capacity (1) kW 423 497 599 635 772
Absorbed power (2) kW 122 148 179 197 239
E.E.R. (2) 3,46 3,34 3,35 3,22 3,23
Water flow (1) l/h 77774 91440 110038 116652 141840
Evaporator pressure drop (1) kPa 48,6 70 83 92,6 92,4
Airflow (1) m3/h 112500 105000 150000 150000 140000
Free-cooling capacity (3) kW 295 345 399 405 477
Absorbed power in free-cooling (3-4)
kW 16,7 17,3 23,8 24,1 25,
E.E.R. in free-cooling (3-4) 17,7 19,9 16,7 16,8 19
(1) Data refer to nominal conditions: Inlet / outlet water temperature: 15 / 10 °C; External air temperature 35 °C; glycol 20% (2) Data refer to total input power.(compressors and fans) (3) Data refer to nominal conditions: Inlet water temperature: 15 °C; External air temperature 5 °C; glycol 20% (4) Data refer to (fans and free-cooling pump) input power
Release 1.0 – July 2011 – for internal use only 9
DIMENSIONS and WEIGHTS
Models 1612A 1812A 2212A 2512A 2812A
Height (**) mm 2510 2510 2510 2510 2510
Depth mm 4985 4985 6415 6415 6415
Width mm 2200 2200 2200 2200 2200
Weights (BREC)
Weight (basic version, without hydraulic kit) (*)
Kg 3961 4317 4803 4803 5095
Weight (basic version with 1 pump) (*) Kg 4111 4467 4968 4968 5260
Weight (version with 2 pumps) (*) Kg 4271 4627 5151 5151 5441
Weights (BREF)
Weight (basic version, without hydraulic kit) (*)
Kg 4677 5121 5762 5762 5936
Weight (basic version with 1 pump) (*) Kg 4827 5271 5927 5927 6101
Weight (version with 2 pumps) (*) Kg 4989 5433 6112 6112 6286
Options
Partial heat recovery Kg 80 80 110 110 110
Ultra low noise version Kg 200 200 200 200 200
Economizer Kg 35 35 45 45 45
(*) with empty hydraulic circuit (**) without vibration supports
REFRIGERANT CONTENT
The table below shows the refrigerant content for the basic version. These values are indicative and the quantities may vary slightly due to adjustments made during end of line testing. The above data refer to the basic version of each unit, i.e. it goes without saying that the amount may vary depending on the configuration of the unit itself.
BREC - F 1612A 1812A 2212A 2512A 2812A
Circuit 1 Kg 47 48 63 64 65
Circuit 2 Kg 47 48 63 64 65
Release 1.0 – July 2011 – for internal use only 10
WATER CIRCUIT
HYDRAULIC CONNECTIONS
BREC - F 1612A 1812A 2212A 2512A 2812A
Main hydraulic connections 4” - OD 114.3
Type Victaulic
Main hydraulic connections (optional)
DN 100 DN 100 DN 100 DN 100 DN 100
Type Flanged
Partial heat recovery hydraulic connections
2”M 2”M 2”M 2”M 2”M
Type BSP
Intelligent free-cooling connections DN100 DN100 DN100 DN100 DN100
Type Flanged
WATER CIRCUIT CAPACITY
BREC 1612A 1812A 2212A 2512A 2812A
Evaporator litres 140 140 160 160 256
BREF 1612A 1812A 2212A 2512A 2812A
Evaporator litres 140 140 160 160 256
Free-cooling coils litres 150 186 200 200 250
RECOMMENDED MINIMUM PLANT CAPACITY
BREC/BREF 1612A 1812A 2212A 2512A 2812A
Recommended minimum plant capacity
litres 1000 1150 1300 1400 1600
MAXIMUM WORKING PRESSURE OF HYDRAULIC CIRCUIT
BREC/BREF 1612A 1812A 2212A 2512A 2812A
Maximum working pressure of hydraulic circuit
Barg 10
Release 1.0 – July 2011 – for internal use only 11
EVAPORATOR PRESSURE DROPS
Data refer to 0% glycol.
Release 1.0 – July 2011 – for internal use only 12
PUMP HEAD PRESSURE AND UNIT PRESSURE DROPS
The available head pressure is the difference between the “pump head pressure” curve and the curve for load losses. Data refer to 0% glycol
Release 1.0 – July 2011 – for internal use only 13
PARTIAL HEAT RECOVERY
PARTIAL CONDENSATION HEAT RECOVERY
1612A 1812A 2212A 2512A 2812A
Cooling capacity kW 365 410 509 557 641
Absorbed power kW 105 120 151 168 188
Heat recovery heating capacity kW 66 79 99 108 121,5
Heat recovery water flow l/h 11350 13590 17028 18576 20900
Heat recovery pressure drop kPa 13 18 11 13 16
Data refer to nominal conditions for both heat recovery: inlet / outlet water temperature 12 / 7 °C; external temperature: 35 °C; Heat recovery water temperature: 40/45°C; glycol 0%
Release 1.0 – July 2011 – for internal use only 14
OPERATING LIMITS
BREC The BREC units are equipped with modulation control and oil heaters for the mass produced compressors, still, depending on requirements, it is necessary to select the different options. The available options are: • Low ambient temperature: the unit will be equipped with anti-condensation resistance for the circuit board. • High ambient temperature: the unit will be equipped with compressors provided with motors capable of
operating with high condensation temperatures. • Low water temperature production: the units are predisposed for the production of glycoled water at low
temperature.
Glycol water mixtures can be cooled down to -10°C as long as the water in the circuit contains sufficient antifreeze to prevent freezing inside the evaporator
Minimum fluid temperature with unit operating
5,0 °C 3,0 °C -5,0 °C -10,0 °C -18,0 °C -28,0°C
Freezing temperature 0 °C -4,4 °C -9,6 °C -16,1 °C -24,5 °C -35,5 °C
Percentage of ethylene glycol by weight 0% 10% 20% 30% 40% 50%
Release 1.0 – July 2011 – for internal use only 15
OPERATING LIMITS
BREF The BREF units are equipped with modulation control and oil heaters for the mass produced compressors and anti-condensation resistance for the circuit board, still, depending on requirements, it is necessary to select the different options. The available options are: • High ambient temperature: the unit will be equipped with compressors provided with motors capable of
operating with high condensation temperatures.
Release 1.0 – July 2011 – for internal use only 16
NOISE PRESSURE LEVELS
The NOISE PRESSURE levels (measured with BRÜEL & KJǼR class 1 sound-level meter model 2260) are measured with units working at full load, in free-field conditions with direction factor Q=2, 10m away from the unit on the condensing coil. The data are taken according to ISO3744 - ISO3746
NOISE POWER level for each octave band frequency supplied in compliance with standard ISO3744-ISO3746. The tolerance on the data is equivalent to +/- 2 dB. Note: the data supplied refers to units working based on factory settings without onboard pumps.
NOISE PRESSURE LEVEL TAKEN AT DIFFERENT POSITIONS AND DISTANCES
The attenuation of the noise pressure level is calculated according to the following:
( ) ( ) ( ) ( )
++⋅
⋅−
++⋅=
+⋅+⋅+⋅+⋅
rifD
HD
LrifD
HD
L
DHLD
DDHLA
13131313
log10log10
Where A: Noise attenuation [dB(A)] L: Length of the unit [m] H: Height of the unit [m] D: Distance [m]
Distance m 1 2 3 4 5 6 7 8 9 10
Variation dBA +14 +11 +9 +7 +6 +5 +3 +2 +1 0
It is possible to calculate the noise pressure level at the desired distance or unit side: electrical board side or on the sides. The delta which need to be added to the data contained in the following pages are indicated in the following table.
Low noise unit
Position Electrical board side Rear side
Attenuation dBA -2 -4
Ultra-low noise unit
Position Electrical board side Rear side
Attenuation dBA -3 -4
Release 1.0 – July 2011 – for internal use only 17
NOISE LEVELS
LOW NOISE VERSION The NOISE PRESSURE levels (measured with BRÜEL & KJǼR class 1 sound-level meter mod. 2260) for each octave band frequency, measured with units working at full load, free-field conditions with Q=2, 10m away from the unit condensing coil according to ISO3744-3746 NOISE POWER level for each octave band frequency supplied in compliance with standard ISO3744-ISO3746. The tolerance on the data is equivalent to +/- 1.5 dB. Note: the data supplied refers to units working based on factory settings and units without onboard pumps.
NOISE PRESSURE LEVEL
Model 63Hz [dB]
125Hz [dB]
250Hz [dB]
500Hz [dB]
1000Hz [dB]
2000Hz [dB]
4000Hz [dB]
8000Hz [dB]
Lp [dB(A)]
1612A 26,0 26,0 28,3 45,4 52,4 56,4 51,6 45,6 59,2
1812A 26,0 33,1 45,8 52,0 56,0 53,0 44,5 31,1 59,2
2212A 27,2 28,7 46,8 60,2 61,0 54,3 45,0 37,6 64,2
2512A 27,2 29,4 45,4 55,6 60,4 56,9 44,4 37,5 63,1
2812A 26,9 30,8 44,6 57,2 60,0 55,7 44,3 37,1 62,9
NOISE POWER LEVEL
Model 63Hz [dB]
125Hz [dB]
250Hz [dB]
500Hz [dB]
1000Hz [dB]
2000Hz [dB]
4000Hz [dB]
8000Hz [dB]
Lw [dB(A)]
1612A 57,1 57,1 59,4 76,5 83,5 87,5 82,7 76,7 90,3
1812A 57,1 64,2 76,9 83,1 87,1 84,1 75,6 62,8 90,3
2212A 58,3 59,8 77,9 91,3 92,1 85,4 76,1 68,7 95,3
2512A 58,3 60,4 76,5 86,7 91,5 88,0 75,5 68,6 94,2
2812A 58,6 62,4 76,3 88,9 91,6 87,4 76,0 68,8 94,6
Release 1.0 – July 2011 – for internal use only 18
NOISE LEVELS
ULTRA LOW NOISE VERSION The NOISE PRESSURE levels (measured with BRÜEL & KJǼR class 1 sound-level meter mod. 2260) for each octave band frequency, measured with units working at full load, free-field conditions with Q=2, 10m away from the unit condensing coil according to ISO3744-3746 NOISE POWER level for each octave band frequency supplied in compliance with standard ISO3744-ISO3746. The tolerance on the data is equivalent to +/- 1.5 dB. Note: the data supplied refers to units working based on factory settings and units without onboard pumps.
Ultra-low noise version - Equipment Ultra-low noise units are equipped with sound-proofing and mufflers for compressors
NOISE PRESSURE LEVEL
Model 63Hz [dB]
125Hz [dB]
250Hz [dB]
500Hz [dB]
1000Hz [dB]
2000Hz [dB]
4000Hz [dB]
8000Hz [dB]
Lp [dB(A)]
1612A 25,9 25,9 27,6 41,5 47,9 51,9 47,8 42,8 54,9
1812A 25,9 30,5 41,7 47,7 51,7 48,4 42,5 29,1 54,9
2212A 27,1 28,4 42,8 53,9 55,3 49,6 43,5 37,3 58,6
2512A 27,1 28,7 42,1 50,4 54,9 51,1 43,4 37,2 57,7
2812A 26,7 29,2 41,4 51,4 54,4 50,1 42,9 36,7 57,4
NOISE POWER LEVEL
Model 63Hz [dB]
125Hz [dB]
250Hz [dB]
500Hz [dB]
1000Hz [dB]
2000Hz [dB]
4000Hz [dB]
8000Hz [dB]
Lw [dB(A)]
1612A 57,0 57,0 58,7 72,5 79,0 83,0 78,9 73,9 86,0
1812A 57,0 61,6 72,8 78,8 82,8 79,5 73,5 60,8 86,0
2212A 58,2 59,5 73,9 85,0 86,4 80,7 74,6 68,3 89,7
2512A 58,2 59,8 73,2 81,5 86,0 82,1 74,5 68,3 88,8
2812A 58,4 60,8 73,1 83,0 86,1 81,8 74,6 68,4 89,1
Release 1.0 – July 2011 – for internal use only 19
ELECTRICAL DATA
BREC - Cooling only series
Compressors circuit 2 Compressors circuit 2
OP OA FLI FLA LRA ST OP OA FLI FLA LRA ST
1612A 47,5 84,0 70,2 144 350 PW 47,5 84,0 70,2 144 350 PW
1812A 54,7 93,3 82,1 162 423 PW 54,7 93,3 82,1 162 423 PW
2212A 69,3 120,5 100,7 182 520 PW 69,3 120,5 100,7 182 520 PW
2512A 77,9 136,6 111,6 196 612 PW 77,9 136,6 111,6 196 612 PW
2812A 87,2 152,3 127,3 214 665 PW 87,2 152,3 127,3 214 665 PW
Standard fans EC fans
OP FLA OP FLA
1612A 12 25,8 13,2 20,4
1812A 12 25,8 13,2 20,4
2212A 16 34,4 17,6 27,2
2512A 16 34,4 17,6 27,2
2812A 16 34,4 17,6 27,2
Main pumps
OP OA LRA
1612A 10,88 18,5 153,55
1812A 10,88 18,5 153,55
2212A 12,55 21,5 180,6
2512A 12,55 21,5 180,6
2812A 12,55 21,5 180,6
Release 1.0 – July 2011 – for internal use only 20
ELECTRICAL DATA
BREC - Cooling only series without pumps
Units without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 107,0 193,7 401,7 154,2 313,8 519,8 0,80
1812A 121,4 212,4 477,9 173,8 349,8 610,8 0,83
2212A 154,6 275,4 590,1 223,8 398,4 736,4 0,81
2512A 171,8 307,7 689,9 240,6 426,4 842,4 0,81
2812A 190,4 339,1 746,1 271,6 462,4 913,4 0,81
Units with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 107,0 170,3 401,7 154,2 313,8 519,8 0,91
1812A 121,4 193,4 477,9 173,8 349,8 610,8 0,91
2212A 154,6 248,6 590,1 223,8 398,4 736,4 0,90
2512A 171,8 274,1 689,9 240,6 426,4 842,4 0,90
2812A 190,4 305,0 746,1 271,6 462,4 913,4 0,90
Units with high external temperature option without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 107,0 193,7 401,7 184 349,8 610,8 0,80
1812A 121,4 215,1 477,9 204 365,8 674,8 0,81
2212A 154,6 275,4 590,1 239 526,4 945,4 0,81
2512A 171,8 307,7 689,9 278 512,4 938,4 0,81
2812A 190,4 339,1 746,1 316 576,4 1034,4 0,81
Units with high external temperature option with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 107,0 170,3 401,7 154,2 313,8 610,8 0,91
1812A 121,4 193,4 477,9 173,8 349,8 674,8 0,91
2212A 154,6 248,6 590,1 223,8 398,4 945,4 0,90
2512A 171,8 274,1 689,9 240,6 426,4 938,4 0,90
2812A 190,4 305,0 746,1 271,6 462,4 1034,4 0,90
Release 1.0 – July 2011 – for internal use only 21
ELECTRICAL DATA
BREC - Cooling only series with pumps
Units without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 117,8 212,2 420,2 165,08 332,3 538,3 0,80
1812A 132,3 230,9 496,4 184,68 368,3 629,3 0,83
2212A 167,1 296,9 611,6 236,35 419,9 757,9 0,81
2512A 184,3 329,2 711,4 253,15 447,9 863,9 0,81
2812A 202,9 360,6 767,6 284,15 483,9 934,9 0,81
Units with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 117,8 186,9 420,2 165,08 332,3 538,3 0,91
1812A 132,3 210,0 496,4 184,68 368,3 629,3 0,91
2212A 167,1 268,1 611,6 236,35 419,9 757,9 0,90
2512A 184,3 293,7 711,4 253,15 447,9 863,9 0,91
2812A 202,9 324,6 767,6 284,15 483,9 934,9 0,90
Units with high external temperature option without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 117,8 212,2 420,2 194,88 368,3 629,3 0,80
1812A 132,3 233,6 496,4 214,88 384,3 693,3 0,82
2212A 167,1 296,9 611,6 251,55 547,9 966,9 0,81
2512A 184,3 329,2 711,4 290,55 533,9 959,9 0,81
2812A 202,9 360,6 767,6 328,55 597,9 1055,9 0,81
Units with high external temperature option with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 117,8 186,9 420,2 165,08 332,3 629,3 0,91
1812A 132,3 210,0 496,4 184,68 368,3 693,3 0,91
2212A 167,1 268,1 611,6 236,35 419,9 966,9 0,90
2512A 184,3 293,7 711,4 253,15 447,9 959,9 0,91
2812A 202,9 324,6 767,6 284,15 483,9 1055,9 0,90
Release 1.0 – July 2011 – for internal use only 22
ELECTRICAL DATA
BREF - Free-Cooling series
Compressors circuit 1 Compressors circuit 2
OP OA FLI FLA LRA ST OP OA FLI FLA LRA ST
1612A 49,9 87,5 70,2 144 350 PW 49,9 87,5 70,2 144 350 PW
1812A 60,395 101,67 82,1 162 423 PW 60,395 101,67 82,1 162 423 PW
2212A 72,708 125,73 100,7 182 520 PW 72,708 125,73 100,7 182 520 PW
2512A 82,549 143,71 111,6 196 612 PW 82,549 143,71 111,6 196 612 PW
2812A 93,628 161,97 127,3 214 665 PW 93,628 161,97 127,3 214 665 PW
Standard fans / EC fans
OP FLA OP FLA
1612A 12 25,8 13,2 20,4
1812A 12 25,8 13,2 20,4
2212A 16 34,4 17,6 27,2
2512A 16 34,4 17,6 27,2
2812A 16 34,4 17,6 27,2
main pump Free-cooling pump
OP OA LRA OP OA LRA
1612A 10,88 18,5 153,55 8,45 16 140,8
1812A 10,88 18,5 153,55 8,45 16 140,8
2212A 12,55 21,5 180,6 10,88 18,5 153,55
2512A 12,55 21,5 180,6 10,88 18,5 153,55
2812A 12,55 21,5 180,6 10,88 18,5 153,55
Release 1.0 – July 2011 – for internal use only 23
ELECTRICAL DATA
BREF - Free-cooling series without pumps
Unit without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 120,2 216,8 417,7 162,65 329,8 535,8 0,80
1812A 141,2 245,1 493,9 182,25 365,8 626,8 0,83
2212A 172,3 304,4 608,6 234,68 416,9 754,9 0,82
2512A 192,0 340,3 708,4 251,48 444,9 860,9 0,81
2812A 214,1 376,8 764,6 282,48 480,9 931,9 0,82
Unit with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 120,2 183,3 417,7 162,65 329,8 535,8 0,95
1812A 141,2 206,4 493,9 182,25 365,8 626,8 0,99
2212A 172,3 265,2 608,6 234,68 416,9 754,9 0,94
2512A 192,0 290,8 708,4 251,48 444,9 860,9 0,95
2812A 214,1 321,7 764,6 282,48 480,9 931,9 0,96
Units with high external temperature option without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 120,2 216,8 417,7 192,45 365,8 626,8 0,80
1812A 141,2 245,1 493,9 212,45 381,8 690,8 0,83
2212A 172,3 304,4 608,6 249,88 544,9 963,9 0,82
2512A 192,0 340,3 708,4 288,88 530,9 956,9 0,81
2812A 214,1 376,8 764,6 326,88 594,9 1052,9 0,82
Units with high external temperature option with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 120,2 183,3 417,7 162,65 329,8 626,8 0,95
1812A 141,2 206,4 493,9 182,25 365,8 690,8 0,99
2212A 172,3 265,2 608,6 234,68 416,9 963,9 0,94
2512A 192,0 290,8 708,4 251,48 444,9 956,9 0,95
2812A 214,1 321,7 764,6 282,48 480,9 1052,9 0,96
Release 1.0 – July 2011 – for internal use only 24
ELECTRICAL DATA
BREF - Free-cooling series with pumps
Unit without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 131,1 235,3 436,2 173,53 348,3 554,3 0,80
1812A 152,1 263,6 512,4 193,13 384,3 645,3 0,83
2212A 184,8 325,9 630,1 247,23 438,4 776,4 0,82
2512A 204,5 361,8 729,9 264,03 466,4 882,4 0,82
2812A 226,7 398,3 786,1 295,03 502,4 953,4 0,82
Unit with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 131,1 199,9 436,2 173,53 348,3 554,3 0,95
1812A 152,1 223,0 512,4 193,13 384,3 645,3 0,98
2212A 184,8 284,7 630,1 247,23 438,4 776,4 0,94
2512A 204,5 310,3 729,9 264,03 466,4 882,4 0,95
2812A 226,7 341,2 786,1 295,03 502,4 953,4 0,96
Unit for high external temperatures without power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 131,1 235,3 436,2 203,33 384,3 645,3 0,80
1812A 152,1 263,6 512,4 223,33 400,3 709,3 0,83
2212A 184,8 325,9 630,1 262,43 566,4 985,4 0,82
2512A 204,5 361,8 729,9 301,43 552,4 978,4 0,82
2812A 226,7 398,3 786,1 339,43 616,4 1074,4 0,82
Units with high external temperature option with power phase capacitors
OP OA SC FLI FLA LRA Cosphi
1612A 131,1 199,9 436,2 173,5 348,3 645,3 0,95
1812A 152,1 223,0 512,4 193,1 384,3 709,3 0,98
2212A 184,8 284,7 630,1 247,2 438,4 985,4 0,94
2512A 204,5 310,3 729,9 264,0 466,4 978,4 0,95
2812A 226,7 341,2 786,1 295,0 502,4 1074,4 0,96
Release 1.0 – July 2011 – for internal use only 25
Release 1.0 – July 2011 – for internal use only 26
Manual code @ digit: 06ME06400B0100
July 2011
Sede legale ed amministrativa /
Registered office & Administrative
Headquarters: Viale della Tecnica
2, 35026 Conselve (PD) Italy
P.IVA 02160760282 C.C.I.A.A. di
PD R.E.A. 212586 del 21/04/1988
R.I.N. 02160760282 M. PD004505
Cap. Soc. € 19.550.000 i.v.
Owned and directed by Schneider
Electric SA - Diretta e coordinata
da Schneider Electric SA