unit 5, block 503, greenogue business park, rathcoole, co ... - safe4 access door manual -...
TRANSCRIPT
ACS Group Unit 5, Block 503, Greenogue Business Park, Rathcoole, Co. DublinE: [email protected] W: www.acsgroup.ie Ph: 01 9011624
INTRODUCING THE SAFE4® RANGE OF ACCESS DOORS
© 2017 Air Force H&V Ltd. Introducting the range of SAFE4® Access Doors. Rev 1.2.2 2
Round Ductwork with SAFE4® saddle
(Smoke Extract & Passive Ducts):
EI 120 (Ve- Ho) o ↔ i
Square Ductwork
(Smoke Extract & Passive Ducts):
EI 120 (Ve- Ho) o → i
Tests conducted:
BS EN 1366-1; BS EN 1366-8;
Kitchen Rating (E):
Ve Ho i ↔ o 90 Tested 1500PA Multi S
Kitchen Rating (EI):
Ve Ho i ↔ o 90 Tested 1500PA Multi S
SAFE4® FIRE RATED ACCESS DOORS FOR KITCHEN AND SMOKE EXTRACT
TYPES AND FEATURES
CLEAN DOOR (I3PO)■■ i3PO, is a 30mm deep tabbed access door.■■ Suitable for uninsulated applications.■■ Designed to minimise any intrusion inside the ductwork, and prevent contaminants gathering at the door.
■■ Comes with fitted hygiene plate, safety chains and handles as standard for easy cleaning.
■■ Suitable for square and round ductwork.
DEEP CLEAN DOOR (I76)■■ i76, is a 76mm deep tabbed access door.■■ Suitable for insulated applications.■■ Suitable for multi-compartment insulated kitchen extract.
■■ Comes with fitted hygiene plate and safety chains as standard.
■■ Suitable for square and round ductwork.
■■ The hygiene plate is designed to minimise the intrusion of contaminants, increasing the life span of the door seals and making it easier to keep clean.
■■ The safety chain is designed to ensure that the door is not misplaced, giving total hands free access.
AVAILABLE SIZESSizes (mm) Ope necessary to suit (mm)
200 × 100 170 × 70
200 × 300 170 × 270
200 × 400 170 × 370
250 × 250 220 ×220
300 × 300 270 × 270
300 × 450 270 × 420
350 × 350 320 × 320
400 × 400 370 × 370
450 × 450 420 ×420
Safe4 FireDoor Label 1 - 150x150 - FA.pdf 1 07/04/2016 3:22 p.m.
Safe4 FireDoor Label 2 - 150x150 - FA.pdf 1 07/04/2016 3:21 p.m.
CE marked as part of the SAFE4® fire
rated ductwork system to harmonised
standard BS EN 12101-7. Suitable for square ductwork and round ductwork when
accompanied with the SAFE4® saddle.
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group
INTRODUCING THE SAFE4® RANGE OF ACCESS DOORS
© 2017 Air Force H&V Ltd. Introducting the range of SAFE4® Access Doors. Rev 1.2.2 3
FITTING INSTRUCTIONS
HANDLE
BENDABLE TEETH TO HOLD IN
ACCESS PANELS
76
30
HANDLE
FIRE SEAL
BENDABLE TEETH TO HOLD IN
ACCESS PANELS
FIRE SEAL
HANDLE
HANDLE
LOCKINGSYSTEM
LOCKINGSYSTEM
HANDLE
BENDABLE TEETH TO HOLD IN
ACCESS PANELS
76
30
HANDLE
FIRE SEAL
BENDABLE TEETH TO HOLD IN
ACCESS PANELS
FIRE SEAL
HANDLE
HANDLE
LOCKINGSYSTEM
LOCKINGSYSTEM
MAINTENANCE
1 For recommended cleaning procedures, please refer to the HVCA publication TR/19 “Guide to Good Practice – Cleanliness of Ventilation Systems”.
2 Inspect the locking mechanism to ensure it is performing correctly. Replace if necessary.
3 Inspect the seal to ensure it is intact and clean of contaminants. Replace if necessary with SAFE4® fire rated gasket.
4 Ensure the tabs in the door frame are securely connected to the ductwork. Re-secure if necessary.
COMPLIANCESAFE4® Access Doors comply with the following regulations:
1 The performance characteristics of the fire rated duct must be continued through ancillary equipment to ensure the fire resistance of the system is maintained [ASFP Blue Book B.3 pg 43]. The SAFE4® Access Doors will maintain a system tested to EN 1366-1/8/9, to the performance criteria of the door as outlined on page 2.
2 SAFE4® Access Doors have been tested in a Horizontal and a Vertical orientation, in keeping
with the requirements of the test standards EN 1366-1/8/9, and are approved for all orientations.
3 SAFE4® Access Doors have been tested where combustible linings have been measured, in keeping with the requirements of the test standards EN 1366-1/8/9, and are suitable for use in kitchen extract systems.
4 SAFE4® Access Doors have been tested to have a leakage of less than 10m3/h per 1m2. SAFE4® Access Doors have achieved a leakage of less than 5m3/h per 1m2 and thus carry a classification of "S" low leakage.
Clean Door i3PO Deep Clean Door i76
1 Select location of access door (top or sides only).
2 Never fit to underside of ductwork.
3 Fit giving consideration for clearance and ease of use.
4 Size of ope is calculated as door size -30mm, e.g. 450×450 door, ope size cut 420×420.
5 Mark ductwork and cut access.
6 Fit the tabbed frame, hammering tabs securely to the ductwork, on the top or sides, subject to access.
7 For kitchen extract ductwork to be compliant to the specification DW172 that access doors are installed at 3 meter centres.
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group
ACS Group Unit 5, Block 503, Greenogue Business Park, Rathcoole, Co. DublinE: [email protected] W: www.acsgroup.ie Ph: 01 9011624