university of south carolina re-bid: coliseum ...purchasing.sc.edu/solicitations/coliseum...

12
UP UP UP UP UP ANGLE AT ABOVE FINISH FLOOR ALUMINUM ARCHITECTURAL BLOCKING BUILT- UP ROOF CENTERLINE CONTROL JOINT CEILING CENTER CONCRETE CONCRETE MASONRY UNIT CONTINUOUS DIAMETER DOWN SPOUT DRAWING EXTERIOR EXISTING EACH EXPANSION JOINT ELECTRICAL ELEVATION ELEVATOR EQUIPMENT ELECTRIC WATER COOLER FINISH FLOOR DRAIN FACE OF FINISH FACE OF STUD FIRE RETARDENT FIELD VERIFY GAUGE GYPSUM BOARD HOLLOW METAL HORIZONTAL HEIGHT HEATING VENTILATION AIR-CONDITIONING INSIDE DIAMETER INSULATION JOINT LAVATORY MAXIMUM MECHANICAL MANUFACTURER MINIMUM MASONRY OPENING NOT IN CONTRACT NOMINAL NOT TO SCALE ON CENTER OUTSIDE DIAMETER OPENING OPPOSITE PAINT PAIR PLATE, PROPERTY LINE PRESSURE TREATED RADIUS REQUIRED ROOF DRAIN ROUGH OPENING SQUARE FEET SIMILAR SPECIFICATIONS STAINLESS STEEL STANDARD STRUCTURAL SUSPENDED TOP OF STEEL TOP OF WALL TYPICAL UNLESS NOTED OTHERIWSE VERTICAL VINYL COMPOSITION TILE WITH WATER CLOSET WATER RESISTANT WELDED WIRE FABRIC WOOD @ AFF ALUM ARCH BLKG BU CJ CLG CTR CONC CMU CONT DIA DS DWG EXT EXIST EA EJ ELEC EL ELEV EQUIP EWC FIN FD FOF FOS FR FV GA GYP BD HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG OPP P PR PL PT R, RAD REQD RD RO SF SIM SPEC SS STD STR SUSP TOS TOW TYP UNO VERT VCT W/ WC WR WWF WD C L PLAN DETAIL REFERENCE ROOM TAG SYMBOL WALL SECTION / DETAIL SECTION REFERENCE DOOR SYMBOL ALTERNATE WALL SECTION REFERENCE BUILDING SECTION REFERENCE FIRE RATED WALL SYMBOLS REVISION SYMBOL DETAIL NUMBER WHERE DETAIL IS SHOWN DETAIL NUMBER WHERE DETAIL IS SHOWN WALL SECTION / DETAIL NUMBER WHERE WALL SECTION / DETAIL IS SHOWN ROOM NAME ROOM NUMBER DOOR NUMBER FRAME TYPE DOOR TYPE DIMENSION TO FACE OR EDGE DIMENSION TO CENTERLINE ELEVATION ABOVE SEA LEVEL ITEM IDENTIFIED WINDOW / STOREFRONT / CURTAIN WALL / LOUVER TYPE PARTITION TYPE FIRE EXTINGUISHER RECESSED IN WALL CABINET FIRE EXTINGUISHER MOUNTED ON WALL BRACKETS FD - FLOOR DRAIN BUILDING SECTION NUMBER WHERE BUILDING SECTION IS SHOWN WALL SECTION / DETAIL NUMBER WHERE WALL SECTION / DETAIL IS SHOWN TOP = TOP HALF OF WALL FOR PARTICULAR LEVEL BOT = BOTTOM HALF OF WALL FOR PARTICULAR LEVEL WALL SECTION / DETAIL NUMBER WHERE WALL SECTION / DETAIL IS SHOWN SIM = SIMILAR CONDITION OH = OPPOSITE HAND CONDITION OPP = OPPOSITE HAND CONDITION ROT = ROTATED CONDITION ONE-HOUR FIRE-RATED WALL ASSEMBLY TWO-HOUR FIRE-RATED WALL ASSEMBLY FOUR-HOUR FIRE-RATED WALL ASSEMBLY SEE PARTITION TYPES FOR UL DESIGN NO'S. BRICK VENEER / CMU CONTROL JOINT TOILET / LOCKER ROOM ACCESSORY SYMBOL GYPSUM BOARD CONTROL JOINT INDICATES A CHANGE IN ORIENTATION OF CUT PLANE (INTERIOR ELEVATION ONLY) CLOUD AROUND REVISION EXTERIOR WALL / ROOF CONSTRUCTION TYPE TITLE SCALE: 1'-0" = 1'-0" REF: 1/A1.1 1 A1.1 LOCATION OF DETAIL CUT (AS SHOWN) 1 A1.1 1 A1.1 1 BOT TOP SIM 001A DX FX S1 1A FE-C FE-C 100 RECEPTION 1 A1.1 1 A1.1 1 A1.1 1 A1.1 EXPANSION JOINT TYPE A 26 26 95 26 20 85 385 77 20 95 26 CAROLINA GEORGIA NORTH ATLANTIC OCEAN COLUMBIA STATE OF SOUTH CAROLINA MAP NORTH CLEARANCES TO COMPLY WITH LATEST VERSION OF ANSI A117.1 ADOPTED BY GOVERNING BODY NOTE: DIMENSIONS AND CLEARANCES SHOWN MUST BE PROVIDED AT ALL DOORS. CONTRACTOR SHALL REVIEW FIELD LAYOUT AND CONFIRM THAT ALL OF THE APPROPRIATE CLEARANCES ARE PROVIDED. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION. ANY REMEDIAL WORK THAT SHOULD HAVE BEEN AVOIDED BY BRINGING DISCREPANCIES TO THE ARCHITECT'S ATTENTION SHALL BE AT THE CONTRACTOR'S EXPENSE. TWO HINGED DOORS IN A SERIES HINGE SIDE APPROACHES FRONT APPROACHES LATCH SIDE APPROACHES PULL SIDE 36" MIN. 42" MIN. 60" MIN. PULL SIDE PUSH SIDE PUSH SIDE PUSH SIDE PULL SIDE 60" MIN. 18" MIN. 48" MIN. 24" MIN. 54" MIN. IF DOOR HAS CLOSER 24" MIN. 42" MIN. 48" MIN. IF DOOR HAS CLOSER 12" MIN. IF DOOR HAS BOTH CLOSER AND LATCH 52" MIN. 12" MIN. 42" MIN. 48" MIN. IF DOOR HAS IF BOTH CLOSER AND LATCH 48" MIN. 60" MIN. 48" MIN. 60" MIN. PUSH / PUSH PUSH / PULL 60" MIN. PULL / PUSH 64" MIN. (W/ 54" CLEAR) (W/ 60" CLEAR) IF BOTH CLOSER AND LATCH 22" MIN. 54" MIN. COMPACTED EARTH POROUS FILL (STONE OR GRAVEL) CONCRETE CONCRETE MASONRY UNIT (CMU) BRICK SAND, PLASTER, CEMENT, GROUT STEEL WOOD (ROUGH) WOOD (FINISHED) PLYWOOD BATT INSULATION GYPSUM BOARD RIGID INSULATION ARCHITECTURAL MECHANICAL FIRE PROTECTION ELECTRICAL T1.1 TITLE SHEET, INDEX TO DRAWINGS, CODE INFORMATION & LIFE SAFETY PLAN A1.1 GROUND FLOOR AND DEMOLITION PLANS A2.1 GROUND FLOOR REFLECTED CEILING PLAN AND CEILING DEMOLITION PLAN A3.1 ELEVATIONS, SECTIONS, PARTITION TYPES, DOOR SCHEDULE AND DETAILS A4.1 FINISHES MD1.1 HVAC DEMOLITION FLOOR PLAN M1.1 HVAC RENOVATION FLOOR PLAN, NOTES, SCHEDULE AND LEGEND FP1.1 FLOOR PLAN AND NOTES E0.1 ELECTRICAL NOTES & LEGENDS E0.2 ELECTRICAL ONE-LINE DIAGRAM & PANELBOARD SCHEDULE E1.1 LIGHTING PLANS E2.1 POWER/SYSTEMS PLANS PROJECT DESIGNED IN ACCORDANCE WITH: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2015 EDITION INTERNATIONAL FIRE CODE (IFC), 2015 EDITION INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2009 Edition INTERNATIONAL FUEL GAS CODE (IFGC), 2015 EDITION INTERNATIONAL MECHANICAL CODE (IMC), 2015 EDITION INTERNATIONAL PLUMBING CODE (IPC), 2015 EDITION with the following insertions: 1. Section 305.4.1, insert “18” and insert “18” 2. Section 903.1, insert “8” INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE (IPSDC), 2015 EDITION INTERNATIONAL PROPERTY MAINTENANCE CODE (IPMC), 2015 EDITION NATIONAL ELECTRICAL CODE (NEC) [NFPA-70], 2014 EDITION NATIONAL ELECTRICAL SAFETY CODE, IEEE-C2-2012 EDITION AMERICAN NATIONAL STANDARDS INSTITUTE, INC. (ANSI) - A117.1 - 2017, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES STATE FIRE MARSHAL RULES, REGULATIONS, AND POLICIES - LATEST EDITION STATE OF SC TELEPHONE EQUIPMENT ROOM AND COMMUNICATIONS/DATA SYSTEMS POLICY AS FORMULATED BY THE DSIT EXISTING BUILDING GENERAL CODE INFORMATION: DESIGNED c. 1966 UNDER CURRENT CODE AT THE TIME EXISTING BUILDING OCCUPANCY: ASSUMED MIXED USE - ASSEMBLY (A-1) AND BUSINESS (B) EXISTING CONSTRUCTION CLASSIFICATION: ASSUMED TYPE IIB, NON-SPRINKLERED, WITH FIRE ALARM (RECENT RENOVATIONS IN 2009, 2017 AND 2018 ON GROUND FLOOR ARE SPRINKLERED PER NFPA-13) PROJECT SCOPE RELEVANT CODE INFORMATION: GROUND FLOOR (ATHLETIC LEVEL) NEW USE - RENOVATION AREA AREA PER PERSON OCCUPANT LOAD BUSINESS (B) 850 SF 100 GROSS 9 TOTAL: 850 SF 9 - DISTANCE BETWEEN EXITS = MIN. ONE-THIRD LENGTH OF MAX. OVERALL DIAGONAL (SPRINKLERED) (PER TABLE 1007.1.1) - MAX. COMMON PATH OF EGRESS TRAVEL DISTANCE = 100' (SPRINKLERED) (PER TABLE 1006.2.1) - MAX. EXIT ACCESS TRAVEL DISTANCE = 300' (SPRINKLERED) (PER TABLE 1017.2) NOTES A. TRAVEL DISTANCES ARE BEING CONSIDERED FOR SPRINKLERED BUILDING SINCE ALL RENOVATED SPACE IS SPRINKLERED PER NFPA-13. OTHER EXISTING/NON-RENOVATED SPACES IN ORIGINAL BUILDING (COLISEUM) ARE NON-SPRINKLERED. B. CURRENT FIRE RATINGS ARE BEING MAINTAINED/NOT CHANGING. C. INCIDENTAL USE SEPARATION IS REQUIRED PER 2015 IBC 509.1 FOR LAUNDRY ROOMS OVER 100 SF. SINCE AREA IS BEING SPRINKLERED, 1-HOUR FIRE RATED SEPARATION NOT REQUIRED (TABLE 509). TRASH 203 LAUNDRY ACCESS 203A LAUNDRY 203B FOOD SERVICE 201D STAIR ST02 FOOD STORAGE 201C KITCHEN 201 STAIR ST01 ELECTRICAL 202 HALLWAY H107 RAMP H213 2 40 73' TO DOOR ALONG MAIN EGRESS PATH BUSINESS (100 GROSS) [825 SF = 9 P] 2 42 25+2=27 272 9P 9P FIRE ALARM 204 JANITOR 205 ST03 FE-B FE-B 164P+9P=173 (8 EXIT DOORS) TO EXIT ONE EXIT REQUIRED BUT SIGNING STAIR FOR SECONDARY EGRESS PATH FIRE EXTINGUISHER, BRACKET MOUNTED. SEE SPECS. FE-B EXIT LIGHTS - ALSO SEE ELECTRICAL DRAWINGS REQUIRED EGRESS WIDTH AT DOOR, IN INCHES EGRESS WIDTH PROVIDED AT DOOR, IN INCHES EGRESS WIDTH SYMBOLS 5 34 4' - 0" (3'-8") REQUIRED EGRESS WIDTH AT PASSAGE EGRESS WIDTH PROVIDED AT PASSAGE 23 # OF PEOPLE/DIRECTION OF TRAVEL [9,960 SF = 50 P] NET (OR GROSS) SQ. FT./# OF PEOPLE (OCCUPANCY OF SPACE) TRAVEL DISTANCE LEGEND 45' TRAVEL DIST. 300' TO EXIT FROM REMOTE CORNER 1. EXIT SIGNS ALSO SHOWN ON ELECTRICAL DRAWINGS PROJECT NO. DATE DRAWING NO. DRAWN BY: CHECKED BY: THIS DRAWING AND THE DESIGN THEREON ARE THE PROPERTY OF THE GARVIN DESIGN GROUP, INC. THE REPRODUCTION, COPYING, OR USE OF THIS DRAWING WITHOUT THE WRITTEN CONSENT OF THE GARVIN DESIGN GROUP IS PROHIBITED AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION. @2003 GARVIN DESIGN GROUP, INC. PROJECT TITLE A/E SEAL A/E SEAL DRAWING TITLE 1/28/2020 10:12:27 AM T1.1 U501.18 01.28.20 TITLE SHEET, INDEX TO DRAWINGS, CODE INFORMATION & LIFE SAFETY PLAN Author Checker RE-BID: COLISEUM LAUNDRY ROOM FOR BASKETBALL FP00000296 Carolina Coliseum 701 Assembly St. Columbia, SC 29208 RE-BID: COLISEUM LAUNDRY ROOM FOR BASKETBALL UNIVERSITY OF SOUTH CAROLINA 28 JANUARY 2020 CONSTRUCTION DOCUMENTS ABBREVIATIONS ARCHITECTURAL SYMBOLS LOCATION MAP MANEUVERING CLEARANCES MATERIAL DESIGNATIONS INDEX TO DRAWINGS CAROLINA COLISEUM 701 ASSEMBLY STREET COLUMBIA, SOUTH CAROLINA 29208 USC Project Number: FP00000296 Architect's Project Number: U501.18 CODE INFORMATION - GENERAL CODE INFORMATION - LAUNDRY REVISIONS NO. NAME DATE REFERENCED ON: 3/16" = 1'-0" T1.1 A3.1 1 LIFE SAFETY PLAN LEGEND - LIFE SAFETY GENERAL NOTES - LIFE SAFETY

Upload: others

Post on 11-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UP

UP

UP UP

UP

ANGLEATABOVE FINISH FLOORALUMINUMARCHITECTURALBLOCKINGBUILT- UP ROOFCENTERLINECONTROL JOINTCEILINGCENTERCONCRETECONCRETE MASONRY UNITCONTINUOUSDIAMETERDOWN SPOUTDRAWINGEXTERIOREXISTINGEACHEXPANSION JOINTELECTRICALELEVATIONELEVATOREQUIPMENTELECTRIC WATER COOLERFINISHFLOOR DRAINFACE OF FINISHFACE OF STUDFIRE RETARDENTFIELD VERIFYGAUGEGYPSUM BOARDHOLLOW METALHORIZONTALHEIGHTHEATING VENTILATION AIR-CONDITIONINGINSIDE DIAMETERINSULATIONJOINTLAVATORYMAXIMUMMECHANICALMANUFACTURERMINIMUMMASONRY OPENINGNOT IN CONTRACTNOMINALNOT TO SCALEON CENTEROUTSIDE DIAMETEROPENINGOPPOSITEPAINTPAIRPLATE, PROPERTY LINEPRESSURE TREATEDRADIUSREQUIREDROOF DRAINROUGH OPENING SQUARE FEETSIMILARSPECIFICATIONSSTAINLESS STEELSTANDARDSTRUCTURALSUSPENDEDTOP OF STEELTOP OF WALLTYPICALUNLESS NOTED OTHERIWSEVERTICALVINYL COMPOSITION TILEWITHWATER CLOSETWATER RESISTANTWELDED WIRE FABRICWOOD

@AFFALUMARCHBLKGBU

CJCLGCTRCONCCMUCONTDIADSDWGEXTEXISTEAEJELECELELEVEQUIPEWCFINFDFOFFOSFRFVGAGYP BDHMHORIZHTHVACIDINSULJTLAVMAXMECHMFRMINMONICNOMNTSOCODOPNGOPPPPRPLPTR, RADREQDRDRO SFSIMSPECSSSTDSTRSUSPTOSTOWTYPUNOVERTVCTW/WCWRWWFWD

CL

PLAN DETAIL REFERENCE

ROOM TAG SYMBOL

WALL SECTION / DETAIL SECTION REFERENCE

DOOR SYMBOL

ALTERNATE WALL SECTION REFERENCE

BUILDING SECTION REFERENCE

FIRE RATED WALL SYMBOLS

REVISION SYMBOL

DETAIL NUMBER

WHERE DETAIL IS SHOWN

DETAIL NUMBERWHERE DETAIL IS SHOWN

WALL SECTION / DETAIL NUMBERWHERE WALL SECTION / DETAIL IS SHOWN

ROOM NAME

ROOM NUMBER

DOOR NUMBER

FRAME TYPE

DOOR TYPE

DIMENSION TO FACE OR EDGE

DIMENSION TO CENTERLINE

ELEVATION ABOVE SEA LEVELITEM IDENTIFIED

WINDOW / STOREFRONT / CURTAIN WALL / LOUVER TYPE

PARTITION TYPE

FIRE EXTINGUISHER RECESSED IN WALL CABINET

FIRE EXTINGUISHER MOUNTED ON WALL BRACKETS

FD - FLOOR DRAIN

BUILDING SECTION NUMBERWHERE BUILDING SECTION IS SHOWN

WALL SECTION / DETAIL NUMBERWHERE WALL SECTION / DETAIL IS SHOWN

TOP = TOP HALF OF WALL FOR PARTICULAR LEVEL

BOT = BOTTOM HALF OF WALL FOR PARTICULAR LEVEL

WALL SECTION / DETAIL NUMBERWHERE WALL SECTION / DETAIL IS SHOWN

SIM = SIMILAR CONDITIONOH = OPPOSITE HAND CONDITIONOPP = OPPOSITE HAND CONDITIONROT = ROTATED CONDITION

ONE-HOUR FIRE-RATED WALL ASSEMBLY

TWO-HOUR FIRE-RATED WALL ASSEMBLY

FOUR-HOUR FIRE-RATED WALL ASSEMBLY

SEE PARTITION TYPES FOR UL DESIGN NO'S.

BRICK VENEER / CMU CONTROL JOINT

TOILET / LOCKER ROOM ACCESSORY SYMBOL

GYPSUM BOARD CONTROL JOINT

INDICATES A CHANGE IN ORIENTATION OF CUT PLANE(INTERIOR ELEVATION ONLY)

CLOUD AROUND REVISION

EXTERIOR WALL / ROOF CONSTRUCTION TYPE

TITLESCALE: 1'-0" = 1'-0" REF: 1/A1.1

1A1.1

LOCATION OF DETAIL CUT (AS SHOWN)

1A1.1

1A1.1

1

BOT

TOP

SIM

001ADX FX

S1

1A

FE-C FE-C

100RECEPTION

1A1.1

1A1.1

1A1.1

1A1.1

EXPANSION JOINT TYPEA

26

26

95

2620

85 38577

20

95

26 CAROLINA

GEORGIA

NORTH

ATLANTIC OCEAN

COLUMBIA

STATE OFSOUTH CAROLINA

MAPNORTH

CLEARANCES TO COMPLY WITH LATEST VERSION OF ANSI A117.1 ADOPTED BY GOVERNING BODY

NOTE: DIMENSIONS AND CLEARANCES SHOWN MUST BE PROVIDED AT ALL DOORS. CONTRACTOR SHALL REVIEW FIELD LAYOUT AND CONFIRM THAT ALL OF THE APPROPRIATE CLEARANCES ARE PROVIDED. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION. ANY REMEDIAL WORK THAT SHOULD HAVE BEEN AVOIDED BY BRINGING DISCREPANCIES TO THE ARCHITECT'S ATTENTION SHALL BE AT THE CONTRACTOR'S EXPENSE.

TWO HINGED DOORS IN A SERIES

HINGE SIDE APPROACHES

FRONT APPROACHES

LATCH SIDE APPROACHES

PULL SIDE

36" MIN.

42" MIN.

60" M

IN.

PULL SIDE

PUSH SIDE

PUSH SIDE

PUSH SIDE

PULL SIDE

60" M

IN.

18" MIN.

48" M

IN.

24" MIN.54" M

IN.

IF D

OOR

HAS

CLOS

ER

24" MIN.

42" M

IN.

48" M

IN.

IF D

OOR

HAS

CLOS

ER

12" MIN.IF DOOR HAS BOTHCLOSER AND LATCH

52" M

IN.

12" MIN.

42" M

IN.

48" M

IN. IF

DOO

R HA

SIF

BOT

H CL

OSER

AND

LATC

H

48" M

IN.

60" MIN.

48" M

IN.

60" MIN.

PUSH / PUSH

PUSH / PULL

60" MIN.

PULL / PUSH

64" M

IN.

(W/ 54" CLEAR)

(W/ 60" CLEAR)

IF BOTH CLOSER AND LATCH

22" MIN.54" M

IN.

COMPACTED EARTH

POROUS FILL (STONE OR GRAVEL)

CONCRETE

CONCRETE MASONRY UNIT (CMU)

BRICK

SAND, PLASTER, CEMENT, GROUT

STEEL

WOOD (ROUGH)

WOOD (FINISHED)

PLYWOOD

BATT INSULATION

GYPSUM BOARD

RIGID INSULATION

ARCHITECTURAL

MECHANICAL

FIRE PROTECTION

ELECTRICAL

T1.1 TITLE SHEET, INDEX TO DRAWINGS, CODE INFORMATION & LIFE SAFETY PLAN

A1.1 GROUND FLOOR AND DEMOLITION PLANSA2.1 GROUND FLOOR REFLECTED CEILING PLAN AND CEILING DEMOLITION PLANA3.1 ELEVATIONS, SECTIONS, PARTITION TYPES, DOOR SCHEDULE AND DETAILSA4.1 FINISHES

MD1.1 HVAC DEMOLITION FLOOR PLANM1.1 HVAC RENOVATION FLOOR PLAN, NOTES, SCHEDULE AND LEGEND

FP1.1 FLOOR PLAN AND NOTES

E0.1 ELECTRICAL NOTES & LEGENDSE0.2 ELECTRICAL ONE-LINE DIAGRAM & PANELBOARD SCHEDULEE1.1 LIGHTING PLANSE2.1 POWER/SYSTEMS PLANS

PROJECT DESIGNED IN ACCORDANCE WITH:

1.2.3.4.5.6.7.

8.9.10.11.12.

13.14.

INTERNATIONAL BUILDING CODE (IBC), 2015 EDITIONINTERNATIONAL EXISTING BUILDING CODE (IEBC), 2015 EDITIONINTERNATIONAL FIRE CODE (IFC), 2015 EDITIONINTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2009 EditionINTERNATIONAL FUEL GAS CODE (IFGC), 2015 EDITIONINTERNATIONAL MECHANICAL CODE (IMC), 2015 EDITIONINTERNATIONAL PLUMBING CODE (IPC), 2015 EDITION with the following insertions:

1. Section 305.4.1, insert “18” and insert “18”2. Section 903.1, insert “8”

INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE (IPSDC), 2015 EDITIONINTERNATIONAL PROPERTY MAINTENANCE CODE (IPMC), 2015 EDITIONNATIONAL ELECTRICAL CODE (NEC) [NFPA-70], 2014 EDITIONNATIONAL ELECTRICAL SAFETY CODE, IEEE-C2-2012 EDITIONAMERICAN NATIONAL STANDARDS INSTITUTE, INC. (ANSI) - A117.1 - 2017, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIESSTATE FIRE MARSHAL RULES, REGULATIONS, AND POLICIES - LATEST EDITIONSTATE OF SC TELEPHONE EQUIPMENT ROOM AND COMMUNICATIONS/DATA SYSTEMS POLICY AS FORMULATED BY THE DSIT

EXISTING BUILDING GENERAL CODE INFORMATION: DESIGNED c. 1966 UNDER CURRENT CODE AT THE TIME

EXISTING BUILDING OCCUPANCY: ASSUMED MIXED USE - ASSEMBLY (A-1) AND BUSINESS (B)

EXISTING CONSTRUCTION CLASSIFICATION: ASSUMED TYPE IIB, NON-SPRINKLERED, WITH FIRE ALARM (RECENT RENOVATIONS IN 2009, 2017 AND 2018 ON GROUND FLOOR ARE SPRINKLERED PER NFPA-13)

PROJECT SCOPE RELEVANT CODE INFORMATION: GROUND FLOOR (ATHLETIC LEVEL)

NEW USE - RENOVATION AREA AREA PER PERSON OCCUPANT LOAD

BUSINESS (B) 850 SF 100 GROSS 9

TOTAL: 850 SF 9

- DISTANCE BETWEEN EXITS = MIN. ONE-THIRD LENGTH OF MAX. OVERALL DIAGONAL (SPRINKLERED) (PER TABLE 1007.1.1)- MAX. COMMON PATH OF EGRESS TRAVEL DISTANCE = 100' (SPRINKLERED) (PER TABLE 1006.2.1)- MAX. EXIT ACCESS TRAVEL DISTANCE = 300' (SPRINKLERED) (PER TABLE 1017.2)

NOTESA. TRAVEL DISTANCES ARE BEING CONSIDERED FOR SPRINKLERED BUILDING SINCE ALL RENOVATED SPACE IS SPRINKLERED

PER NFPA-13. OTHER EXISTING/NON-RENOVATED SPACES IN ORIGINAL BUILDING (COLISEUM) ARE NON-SPRINKLERED.

B. CURRENT FIRE RATINGS ARE BEING MAINTAINED/NOT CHANGING.

C. INCIDENTAL USE SEPARATION IS REQUIRED PER 2015 IBC 509.1 FOR LAUNDRY ROOMS OVER 100 SF. SINCE AREA IS BEINGSPRINKLERED, 1-HOUR FIRE RATED SEPARATION NOT REQUIRED (TABLE 509).

TRASH203

LAUNDRY ACCESS203A

LAUNDRY203B

FOOD SERVICE201D

STAIRST02

FOOD STORAGE201C

KITCHEN201

STAIRST01

ELECTRICAL202

HALLWAYH107

RAMPH213

240

73' TO DOOR

ALONG MAIN

EGRESS PATH

BUSINESS (100 GROSS)[825 SF = 9 P]

242

25+2=27272

9P

9P

FIRE ALARM204 JANITOR 205

ST03

FE-B

FE-B

164P+9P=173

(8 EXIT DOORS)

TO EXIT

ONE EXIT REQUIRED BUT SIGNING STAIR FOR

SECONDARY EGRESS PATH

FIRE EXTINGUISHER, BRACKET MOUNTED. SEE SPECS.FE-B

EXIT LIGHTS - ALSO SEE ELECTRICAL DRAWINGS

REQUIRED EGRESS WIDTH AT DOOR, IN INCHESEGRESS WIDTH PROVIDED AT DOOR, IN INCHES

EGRESS WIDTH SYMBOLS534

4' - 0"(3'-8") REQUIRED EGRESS WIDTH AT PASSAGE

EGRESS WIDTH PROVIDED AT PASSAGE

23 # OF PEOPLE/DIRECTION OF TRAVEL

[9,960 SF = 50 P] NET (OR GROSS) SQ. FT./# OF PEOPLE (OCCUPANCY OF SPACE)

TRAVEL DISTANCE LEGEND45'

TRAVEL DIST.

300' TO EXIT FROM REMOTE CORNER

1. EXIT SIGNS ALSO SHOWN ON ELECTRICAL DRAWINGS

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

1/28

/202

0 10

:12:

27 A

M

T1.1U501

.18

01.2

8.20

TITL

E SH

EET,

INDE

X TO

DRA

WIN

GS,

CODE

INFO

RMAT

ION

& LI

FE S

AFET

YPL

AN

Auth

or

Chec

ker

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

00000296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

RE-BID: COLISEUM LAUNDRY ROOM FOR BASKETBALLUNIVERSITY OF SOUTH CAROLINA

28 JANUARY 2020CONSTRUCTION DOCUMENTS

ABBREVIATIONS ARCHITECTURAL SYMBOLS

LOCATION MAP MANEUVERING CLEARANCES

MATERIAL DESIGNATIONS

INDEX TO DRAWINGS

CAROLINA COLISEUM701 ASSEMBLY STREET COLUMBIA, SOUTH CAROLINA 29208USC Project Number: FP00000296 Architect's Project Number: U501.18

CODE INFORMATION - GENERAL

CODE INFORMATION - LAUNDRY

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

3/16" = 1'-0"T1.1 A3.11 LIFE SAFETY PLAN

LEGEND - LIFE SAFETY

GENERAL NOTES - LIFE SAFETY

Page 2: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UP

UPUP

UP

UP

UPUP

UP

4

3' - 8

"2'

- 8"

1

2

3

1' - 4

"4'

- 0"

EXISTING ROLL-UP DOOR TO REMAIN

6

5

TRASH203

LAUNDRY203B

FOOD SERVICE201D

STAIRST02

FOOD STORAGE201C

KITCHEN201

STAIRST01

ELECTRICAL202

HALLWAYH107

RAMPH213

CLOSET203C

REFERENCE ABATEMENT SPECIFICATIONS FOR KNOWN AREAS CONTAINING HAZARDOUS MATERIALS. CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED IN THE PROJECT SCOPE.

1 DEMO CMU WALL FOR NEW HOLLOW METAL FRAME. SAW CUT OPENING AS REQUIRED. SEE FRAME SCHEDULE FOR SIZE.

DEMO CMU WALL FOR NEW HOLLOW METAL DOOR AND FRAME. SAW CUT OPENING AS REQUIRED. SEE DOOR AND FRAME SCHEDULE FOR SIZE.

DEMO EXISTING HM DOOR AND FRAME. INFILL OPENING WITH 8" CMU. PAINT/FINISH TO MATCH EXISTING.

DEMO EXISTING CHALKBOARD

EXISTING CARPET TO REMAIN ON STAIRS AND UPPER LANDING.

REMOVE EXISTING CARPET ON MAIN FLOOR LEVEL ONLY.

2

3

4

5

6

EXSITING WALL TO REMAIN

EXISTING WALL TO BE DEMOLISHED

EXISTING DOOR AND FRAME TO BE DEMOLISHED

EXISTING DOOR AND FRAME TO BE REMAIN

NOTE: SEE KEYNOTES AND PLUMBING, MECHANICAL AND ELECTRICAL DEMO DRAWINGS FOR ADDITIONAL DEMO WORK

1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OFDEMOLITION AND NEW WORK. EXISTING BUILDING INFORMATIONSHOWN IS BASED ON THE EXISTING DRAWINGS PROVIDED BY THEOWNER AND SELECTIVE FIELD MEASUREMENTS. GENERALCONTRACTOR AND SUB-CONTRACTORS ARE TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID AND PRIOR TO CONSTRUCTION.

2. PROVIDE AND INSTALL ALL SHORING AND SUPPORT SYSTEMSNECESSARY TO ENSURE EXISTING STRUCTURE TO REMAIN STABLETHROUGHOUT DEMOLITION AND NEW CONSTRUCTION.

3. WHERE APPLICABLE, REFERENCE ABATEMENT SPECIFICATIONS FORKNOWN AREAS CONTAINING HAZARDOUS MATERIALS. CONTACTOWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUSMATERIALS NOT SHOWN TO BE REMOVED IN THE PROJECT SCOPE.

4. CONTRACTOR SHALL PHOTOGRAPH ALL EXISTING CONDITIONS PRIORTO COMMENCEMENT OF DEMOLITION OR NEW WORK TO DOCUMENTPRE-CONSTRUCTION CONDITIONS. PROVIDE ARCHITECT AND OWNERWITH ELECTRONIC COPY OF PHOTOGRAPHS.

5. ITEMS TO SALVAGED AND REMOVED BY THE OWNER PRIOR TODEMOLITION ARE IDENTIFIED WITHIN THE SPECIFICATIONS.

6. CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH EXISTINGCONDITIONS FOR SIZES, QUANTITIES AND LOCATIONS.

7. PROTECT ALL EXISTING PIPING & INSULATION, CONDUIT/BOXES,WIRING, LIGHTING, DUCTWORK, SPRINKLER PIPING, AND ALL OTHERUTILITIES TO REMAIN IN USE. REMOVE ALL ABANDONED ORDISCONNECTED ITEMS FROM ABOVE CEILINGS.

8. ALL FURNITURE, FIXTURES AND LOOSE ITEMS TO BE REMOVED BY OWNER BEFORE COMMENCEMENT OF WORK.

9. PATCH, CLEAN, SCRAPE AND OTHERWISE PREP ALL AFFECTED WALLS,CEILINGS AND FLOORS WHERE ITEMS ARE REMOVED OR WEREREMOVED BY OWNER TO PREPARE AREAS FOR FINAL WORK ANDFINISHES AS SPECIFIED. SEE PROJECT SPECIFICATIONS FORADDITIONAL REQUIREMENTS.

SEE T1.1 FOR MINIMUM REQUIRED ADA MANEUVERING CLEARANCES. VERIFY EXACT FE-B AND FE-C LOCATIONS WITH ARCHITECT..

SEE T1.1 FOR REQUIRED UL ASSEMBLIES OF ALL BUILDING SYSTEMS. ALL PENETRATIONS THROUGH RATED WALL AND FLOOR ASSEMBLIES MUST COMPLY WITH UL DESIGN FOR PENETRATIONS.

DIMENSIONS INDICATED ON THESE DRAWINGS ARE TO FACE OF CMU WALL, FACE OF EXTERIOR VENEER, FACE OF STUD WALL, OR CENTERLINE OF COLUMN UNLESS OTHERWISE INDICATED. COORDINATE ALL DIMENSIONS WITH STRUCTURAL DIMENSION PLANS, ENLARGED PLANS, SECTION AND DETAIL DRAWINGS, AND STRUCTURAL DRAWINGS AND VERIFY EXACT LOCATIONS. COORDINATE ALL FLOOR SLAB PENETRATIONS WITH SYSTEM DRAWINGS (S'S, M'S, P'S, FP'S, AND E'S) AND ACTUAL PRODUCT TO BE INSTALLED AND VERIFY LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION.

EXISTING AND MASONRY OPENINGS TO RECEIVE CURTAIN WALL, DOORS, WINDOWS, LOUVERS, OR OTHER ELEMENTS SHALL BE FIELD VERIFIED PRIOR TO MANUFACTURE OF SYSTEM.

INTERIOR METAL STUD OPENINGS TO RECEIVE STOREFRONT, DOORS, GRILLES, LOUVERS, OR OTHER ELEMENTS SHALL BE FIELD VERIFIED PRIOR TO MANUFACTURE OF SYSTEM. LOCATION OF ALL RECESSED CABINETS AND EQUIPMENT WALL PENETRATIONS MUST BE VERIFIED PRIOR TO INSTALLATION OF CMU WALLS TO ENSURE INDICATED LOCATION AND EVEN COURSING. ANY CONFLICTS WITH INDICATED DIMENSIONS OR LOCATIONS SHALL BE COORDINATED WITH ARCHITECT PRIOR TO INSTALLATION..

CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED WITHIN THE PROJECT SCOPE.

PATCH, CLEAN, SCRAPE AND OTHERWISE PREP ALL AFFECTED WALLS, CEILINGS AND FLOORS WHERE ITEMS ARE REMOVED OR WERE REMOVED BY OWNER TO PREPARE AREAS FOR FINAL WORK AND FINISHES AS SPECIFIED. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

1.

2.

3.

4.

5.

6

7.

FIRE EXTINGUISHER, BRACKET MOUNTED. SEE SPECS.FE-B

6' - 8

1/2

"

SLOPE DN 12"

DUMPSTER

DUMPSTER

CARD

BOAR

D

COMPACTOR

STORAGE BARRELS

TRASH203

LAUNDRY ACCESS203A

12" CONC. PAD AND RAMP

RAMP SLOPE UP

LAUNDRY203B

FOOD SERVICE201D

NEW HOLLOW METAL DOOR AND FRAME

NEW 3-5/8" METAL STUD AND GWB WALL AND FRAMED CEILING AT 9'-0" AFF

HOLLOW METAL FRAME (NO DOOR)

3' - 0"

4' - 0" 9' - 0"

ROOF DRAIN TO REMAIN

NEW ELEC. PANEL, SEE ELEC. DWGS.

FD

1' - 4

"4'

- 0"

A3.1 1

3

A3.1

2

A3.1

NEW SLOPED CONC. TRANSITION FROM DOOR THRESHOLD TO RAMP. CHIP OUT EXISTING CONCRETE AS REQ'D. TO ACCEPT NEW CONC. RAMP

A3.14

NEW 8" CMU INFILL WALL AT PREVIOUS DOOR OPENING. MATCH CMU COURSING AND PAINT FOOD SERVICE SIDE TO MATCH EXISTING

STAIRST02

203AAD1 F1

FOOD STORAGE201C

KITCHEN201

STAIRST01

ELECTRICAL202

HALLWAYH107

RAMPH213

CLOSET203C

5

3' - 8

"2'

- 8"

8

A3.1

FE-B

FE-B

6

7

M3A

TRASH ROOM EQUIP. TO BE RELOCATED BY OWNER

DRYER EXHAUST, SEE MECH. DWGS.

DRYERDRYER

A3.114

203AB-- F2

TWO DRYERS PROVIDED BY OWNER

NEW RELIEF DAMPER, SEE MECH. DWGS. CUT OPENING IN EXISTING WALL AS REQUIRED. COORDINATE FINAL LOCATION WITH A/E BEFORE CUTTING. COORDINATE REMOVAL OF HAZARDOUS EXTERIOR COATING WITH OWNER PRIOR TO CUTTING OPENING IN WALL. REPAINT WALL AND SEAL LOUVER AS REQUIRED TO MATCH EXISTING.

1' - 0" 0' - 0"

4' - 0" CLEARFUTURE DRYER

FUTURE DRYER

FUTURE DRYER

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

1/28

/202

0 9:

48:3

8 AM

A1.1U501

.18

01.2

8.20

GROU

ND F

LOOR

AND

DEM

OLIT

ION

PLAN

S

Auth

or

Chec

ker

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

REFERENCED ON:

1/4" = 1'-0"A1.1 A3.11 DEMOLITION PLAN

KEYNOTES - DEMO PLAN

LEGEND - DEMOLITION PLAN

GENERAL NOTES - DEMO PLAN

GENERAL NOTES - FLOOR PLAN

LEGEND - FLOOR PLAN

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/4" = 1'-0"A1.1 A3.12 FLOOR PLAN

Page 3: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

3

A3.1

2

A3.18

A3.1

LAUNDRY203B

TRASH203

LAUNDRY ACCESS203A

FOOD SERVICE201D

STAIRST02

FOOD STORAGE201C

KITCHEN201

STAIRST01

ELECTRICAL202

HALLWAYH107

RAMPH213

CLOSET203C

9' - 0"

EQEQ

EQ EQ

SLOPES UP

NOT ALL MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL PIPING SHOWN FOR CLARITY. SEE M, P, FP AND E DWGS.

EXISTING PLASTER CEILING TO REMAIN

NEW RELIEF DAMPER, SEE MECH. DWGS. CUT OPENING IN EXISTING WALL AS REQUIRED. COORDINATE FINAL LOCATION WITH A/E BEFORE CUTTING. COORDINATE REMOVAL OF HAZARDOUS EXTERIOR COATING WITH OWNER PRIOR TO CUTTING OPENING IN WALL.

NOT ALL MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL PIPING SHOWN FOR CLARITY. SEE M, P, FP AND E DWGS.

SEE ELEC. DWGS. FOR FULL SCOPE OF WORK RELATED TO ELECTRICAL LIGHTING AND DEVICES IN HALLWAY

EXISTING LIGHT FIXTURES TO REMAIN, TYP.

14' - 4"EXPOSED CONCRETE STRUCTURE

DRYER EXHAUST, SEE MECH. DWGS. SEAL AROUND ALL DUCT PENETRATIONS

9' - 0"

EXISTING CEILING GRID TO REMAIN. ACOUSTICAL TILE TO BE REMOVED AND REPLACED WITH NEW TILE

NEW TRANSFER DUCT AND LOUVER IN GYP. BD. CEILING, SEE MECH. DWGS.

1

2

3 3

4

SLOPES UP

EXISTING PLASTER CEILING TO REMAIN.

TRASH203

STAIRST02

LAUNDRY203B REFERENCE ABATEMENT SPECIFICATIONS FOR KNOWN AREAS CONTAINING

HAZARDOUS MATERIALS. CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED IN THE PROJECT SCOPE.

REFERENCE MECH. AND ELEC. DEMOLITION DRAWINGS FOR FULL EXTENT OF DEMOLITION REQUIREMENTS.

5

REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND SPECIFIC FIXTURE DESIGNATIONS, AND FOR ELECTRICAL CEILING AND WALL MOUNTED DEVICES.

ALL SUSPENDED ACOUSTICAL GRIDS ARE TO BE LOCATED AS SHOWN, UNLESS NOTED OTHERWISE. REFERENCE NOTES FOR GRID START POINTS AND FULL-TILE LOCATIONS. REVIEW ALL GRID LAYOUTS WITH ARCHITECT PRIOR TO INSTALLATION TO ASSURE NO "SLIVERS" OF TILE, OVERLAPPING WALL MOLDS, OR OUT-OF-SQUARE CONDITIONS OCCUR. GRIDS NOT COMPLYING WITH THIS PROCESS OR THESE STIPULATIONS WILL BE REMOVED AND RE-INSTALLED AT CONTRACTOR'S EXPENSE.

CEILING MOUNTED EQUIPMENT, DEVICES, FIXTURES & GRILLES MUST BE COORDINATED ON REFLECTED CEILING PLANS. CEILING MOUNTED SPRINKLERS TO BE LOCATED IN CENTER OF CEILING TILE IN APC CEILINGS AND ALIGNED WITH DOWNLIGHTS IN GWB CEILINGS/SOFFITS.

SEE FP DRAWINGS FOR FIRE PROTECTION SYSTEM LAYOUT. COORDINATE ROUTING OF PIPING W/ ARCHITECTURAL DWGS AND DETAILS AS WELL AS ALL OTHER SYSTEM DRAWINGS (S's, M's, P's, & E'S). SUBMIT LAYOUT/COORDINATION DRAWING FOR REVIEW & APPROVAL PRIOR TO INSTALLATION.

PAINT EXPOSED STRUCTURE/CEILING AREA AND UTILITIES ONLY AS NOTED ON FINISH SCHEDULES AND INTERIOR ELEVATIONS.

ACCESS PANELS BY GENERAL CONTRACTOR. QUANTITY OF ACCESS PANELS SHOWN ON ARCHITECTURAL DRAWINGS NOT INTENDED TO BE ALL INCLUSIVE; SEE MECHANICAL DRAWINGS, PLUMBING DRAWINGS, ELECTRICAL DRAWINGS, AND FIRE PROTECTION SHOP DRAWINGS FOR ADDITIONAL ACCESS PANELS NOT SHOWN. COORDINATE EXACT LOCATION OF ACCESS PANELS NOT SHOWN WITH ARCHITECT. BRING ALL MECHANICAL, PLUMBING AND ELECTRICAL ITEMS WHICH NEED ACCESS TO THE ACCESS PANEL LOCATIONS SHOWN - BRING THE NEED FOR ADDITIONAL ACCESS PANELS TO THE ARCHITECT'S ATTENTION BEFORE PROCEEDING.

1.

2.

3.

4.

5.

6.

SUPPLY & RETURN MECHANICAL DIFFUSERS, SEE MECH. DWGS.

GYPSUM BOARD CEILING / SOFFIT AS SPECIFIED

LIGHT FIXTURES, SEE ELEC. DWGS.

EXIT LIGHTS - SEE ELEC. DWGS. AND LIFE SAFETY PLAN FOR LOCATIONS

9' - 8" SHOWS CEILING HEIGHTS RELATIVE TO MAIN 0'-0" FINISHED FLOOR ELEVATION

APC-1 - SEE FINISH SCHEDULE

1 EXISTING CEILING GRID TO REMAIN. DEMOLISH AND DISPOSE OF ALL EXISTING ACOUSTICAL CEILING TILE. CONTRACTOR TO REMOVE GRID AS REQUIRED FOR NEW SPRINKLER AND EXHAUST DUCT INSTALLATION. GRID TO BE REPAIRED AND/OR REPLACED TO EXISTING CONFIGURATION WITH NEW ACOUSTICAL TILE TO BE INSTALLED IN EXISTING GRID AT COMPLETION OF WORK.

EXISTING LIGHT FIXTURES TO REMAIN

EXISTING HVAC UNITS AND DUCTWORK TO REMAIN

DEMO EXISTING PROJECTION SCREEN AND HOUSING

ALL CEILING MOUNTED DEVICES INCLUDING HVAC GRILLES, FIRE ALARM AND SMOKE DETECTION DEVICES, ETC. TO REMAIN. IF TEMPORARILY REMOVED FOR ACOUSTICAL CEILING TILE REPLACEMENT, SPRINKLER OR EXHAUST DUCT INSTALLATION, RE-INSTALL ALL GRILLES AND DEVICES IN SAME LOCATION WHEN NEW CEILING TILE IS INSTALLED.

2

3

4

5

1. FIELD VERIRY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITION AND NEW WORK. EXISTINGBUILDING INFORMATION SHOWN IS BASED ON THE EXISTING DRAWINGS PROVIDED BY THE OWNER ANDSELECTIVE FIELD MEASUREMENTS. GENERAL CONTRACTOR AND SUB-CONTRACTORS ARE TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID AND PRIOR TO CONSTRUCTION.

2. WHERE APPLICABLE, REFERENCE ABATEMENT SPECIFICATIONS FOR KNOWN AREAS CONTAININGHAZARDOUS MATERIALS. CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAININGMATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED IN THE PROJECTSCOPE.

3. CONTRACTOR SHALL PHOTOGRAPH ALL EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITIONOR NEW WORK TO DOCUMENT PRE-CONSTRUCTION CONDITIONS. PROVIDE ARCHITECT AND OWNER WITHELECTRONIC COPY OF PHOTOGRAPHS.

4. ITEMS TO SALVAGED AND REMOVED BY THE OWNER PRIOR TO DEMOLITION ARE IDENTIFIED WITHIN THESPECIFICATIONS.

5. CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH EXISTING CONDITIONS FOR SIZES, QUANTITIES ANDLOCATIONS.

6. PROTECT ALL EXITING PIPING & INSULATION, CONDUIT/BOXES, WIRING, LIGHTING, DUCTWORK, SPRINKLERPIPING, AND ALL OTHER UTILITIES TO REMAIN IN USE. REMOVE ALL ABANDONED OR DISCONNECTED ITEMSFROM ABOVE CEILINGS.

7. ALL FURNITURE, FIXTURES AND LOOSE ITEMS TO BE REMOVED BY OWNER BEFORE COMMENCEMENT OFWORK.

8. PATCH WALLS, CEILINGS AND FLOORS WHERE ITEMS ARE REMOVED OR WERE REMOVED BY OWNER TOPREPARE AREAS FOR FINAL WORK AND FINISHES AS SPECIFIED.

9. SEE MECHANICAL, PLUMBING AND ELECTRICAL DEMOLITION PLANS AND NOTES FOR DEMOLITION OF LIGHTS,DEVICES, DUCTWORK, PIPING, ETC. ABOVE CEILINGS. PREPARE ALL AREAS FOR NEW CEILNGS ANDUTILITIES INCLUDING RAISING AND/OR REMOVAL OF CONDUIT, PIPING, DUCTWORK, ETC. NECESSARY TOACHIEVE NOTED CEILING HEIGHTS. CONSULT WITH ARCHITECT SHOULD ANY UTILITY CONFLICTS ARISE.

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

1/28

/202

0 10

:34:

12 A

M

A2.1U501

.18

01.2

8.20

GROU

ND F

LOOR

REF

LECT

EDCE

ILIN

G PL

AN A

ND C

EILI

NGDE

MOL

ITIO

N PL

AN

Auth

or

Chec

ker

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

REFERENCED ON:

1/4" = 1'-0"A2.1 A3.11 REFLECTED CEILING PLAN

REFERENCED ON:

1/4" = 1'-0"A2.1 A3.12 DEMOLITION REFLECTED CEILING PLAN

GENERAL NOTES - REFLECTED CEILING PLAN

LEGEND - REFLECTED CEILING PLAN

KEYNOTES - DEMO RCP

GENERAL NOTES - DEMO RCP

REVI

SIO

N S

NO.

NAM

EDA

TE

Page 4: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

1 LAYER 5/8" GYPSUM WALL BOARD EACH SIDE

20 GAGE METAL STUDS @ 16" O.C. MAX.(SEE SPECIFIC PARTITIONTYPE FOR SIZE)

WALL FINISH, SEE FINISH SCHEDULE

STEEL RUNNER ATTACHED TO CONCRETE SLAB AT 12" O.C. MAX.@ TOP AND BOTTOM OF WALL

CONCRETE SLAB FINISH FLOOR MATERIAL, SEE FINISH SCHEDULE

BASE, SEE FINISH SCHEDULE

6" - 18 GAGE METAL STUD CEILING JOISTS AT 16" O.C. MAX.

1 LAYER 5/8" GYPSUM WALL BOARD CEILING

BASE, SEE FINISH SCHEDULE

3/4" WOOD TRIM FULL LENGTH OF WALL, PTD. WALL COLOR

5/8" PLYWOOD SHEATHING

3 1/

2"

M1M2M3M4M6M8

M2A*

MATERIAL FINISH CONSTRUCTION

SIZE

SEE CHART BELOW

SEE CHART BELOW

SEE PARTITION SECTION

1-1/2" METAL STUD2-1/2" METAL STUD3-5/8" METAL STUD4" METAL STUD6" METAL STUD8" METAL STUD

C4C8C12

4" CMU (3-5/8" NOM.)8" CMU (7-5/8" NOM.)12" CMU (11-5/8" NOM.)

INSULATION DESIGNATION

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

1' - 0

"7'

- 4"

4' - 0" 1' - 4"

NEW H.M. DOOR AND FRAME(FRAME 4'-0" X 7'-4") CUT INTO CMU WALL

EXISTING HM DOOR AND FRAME

EXISTING SPRINKLER VALVE TO REMAIN

EXISTING LIGHT SWITCH TO REMAIN

NEW SLOPED CONC. TRANSITION FROM DOOR THRESHOLD TO RAMP

EXISTING ROLL-UP DOOR

HVAC DUCTWORK, SEE MECH. DWGS.

NEW TRANSFER DUCT AND LOUVERCUT INTO CMU WALL, SEE MECH. DWGS.

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

3

A3.1

LAUNDRY ACCESS203A

7' - 4

"1'

- 0"

EXISTING CONC. SLAB AND RAMP

9' - 0"4' - 0"

WALL PROTECTION, SEE FINISH SCHED. AND SPECS

LAUNDRY203B

NEW H.M. DOOR AND FRAME

HOLLOW METAL CASED OPENING FRAME, F2

STAINLESS STEEL CORNER GUARDS ON H.M. FRAME, SEE SPECS

STAINLESS STEEL CORNER GUARDS ON H.M. FRAME, SEE SPECS.

A3.19

4' - 0

"

1' - 0

"3'

- 0"

RESILIENT BASE, RB-1

CONC. LANDING AND RAMP -3000 PSI CONCRETE WITH WWF 6 X 6 - W1.4 X W1.4 OVER EXISTING SLAB

1 1/

2"

A3.112

A3.115

PAINTED GWB, SEE FINISH SCHED.

OPEN TO TRASH ROOM BEYOND

6" METAL STUDS @ 16" O.C. WITH 5/8" GWB CEILING ON BOTTOM AND 5/8" PLYWOOD SHEATHING ON TOP. SEE PARTITION TYPE FOR DETAILS

HVAC DUCTWORK BEYONDLIGHT FIXTURE, SEE ELEC. DWGS.

NEW HVAC TRANSFER DUCT THROUGH CMU WALL AND GYP. BD. CEILING, SEE MECH. DWGS.

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

9' - 0

"

LAUNDRY ACCESS203A

OPEN

2

A3.1

3-5/8" METAL STUDS @ 16" O.C. WITH5/8" GWB BOTH SIDES. SEE PARTITIONTYPE FOR DETAILS

CONC. RAMP IN FOREGROUND

EXISTING CONC. COLUMN BEYOND

TRASH203

COMPACTOR

ROOF DRAIN BEYOND

H.M. CASED OPENING FRAME BEYOND

STAINLESS STEEL CORNER GUARDS, SEE SPECS.

6" METAL STUDS @ 16" O.C. WITH 5/8" GWB CEILING ON BOTTOM AND 5/8" PLYWOOD SHEATHING ON TOP. SEE PARTITION TYPE FOR DETAILS

6' - 8 1/2"

CONC. FLOOR ABOVE

4' - 0

"DUMPSTER

HVAC EXHAUST DUCTWORK, SEE MECH. DWGS.

CARDBOARD

F1

INTERIORHOLLOW METAL

(RABBETED FRAME WITH DOOR)

2" DOOR WIDTH 2"

4"DO

OR H

EIGH

T

D1

INTERIOR1-3/4" HOLLOW METAL DOOR W/

PAINTED FINISH

DOOR WIDTH

DOOR

HEI

GHT

F2

INTERIORHOLLOW METAL

(NON-RABBETED FRAME WITHOUT DOOR)

2" DOOR WIDTH 2"

4"DO

OR H

EIGH

T

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

2

A3.1

OPEN

ELEC.PANEL

DRYER

7' - 8

"

2' - 8" 3' - 8"

FE-B

HOLLOW METAL FRAME (NO DOOR), P-3STAINLESS STEEL CORNER GUARDS ON H.M. FRAME, SEE SPECS

3' - 1

0"

LAUNDRY203B

EXISTING LIGHT FIXTURES TO REMAIN

4' - 0

"

FE-B

EXISTING FAN COIL UNIT TO REMAIN, SEE MECH. DWGS.

DRYER EXHAUST DUCT WORK, SEE MECH. DWGS.

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

DRYER DRYERLAUNDRY

203B

EXISTING LIGHT FIXTURES TO REMAIN

EXISTING WATER FOUNTAIN TO REMAIN

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

FE-B

3' - 1

0"

LAUNDRY203B

EXISTING LIGHT FIXTURES TO REMAIN

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

3

A3.1

LAUNDRY203B

STAIRST02

EXISTING SUSPENDED PLASTER CEILING TO REMAIN

CLOSET203C

NEW ELEC. PANEL BEYOND, SEE ELEC. DWGS.

LAUNDRY ACCESS203A

WALL PROTECTION WP-1, SEE FINISH SCHED. AND SPECS

HOLLOW METAL FRAME

STAINLESS STEEL CORNER GUARDS ON H.M. FRAME, SEE SPECS

RESILIENT BASE, RB-1

4' - 0

"

SEE 2/A3.1 FOR ADDITIONAL / TYPICAL NOTES FOR THIS AREA, O.H.

EXISTING CONC. COLUMN

3' - 0

"

4' - 0

"

EXISTING LIGHT FIXTURES TO REMAIN

NEW TRANSFER DUCT BEYOND, SEE MECH. DWGS.

EXISTING FAN COIL UNIT TO REMAIN

01_ATHLETIC LEVEL0' - 0"

03_ACADEMIC LEVEL15' - 4"

STAIRST02

EXISTING SUSPENDED PLASTER CEILING TO REMAIN

CLOSET203C

LAUNDRY203B

SPRINKLER LINE WALL MOUNTED BELOW EXISTING CEILING, SEE FP DWGS.COORD. FINAL LOCATION AND MOUNTING WITH A/E

EXISTING CEILING GRID WITH NEW ACOUSTICAL TILE CEILING

01_ATHLETIC LEVEL0' - 0"

1/2"

2' - 0"

CHIP OUT 1/2" OF CONCRETE AT BASE OF RAMP TO ELIMINATE FEATHER EDGE

NEW CONCRETE RAMP

EXISTING CONCRETE SLAB

1 1/

2"

WWF 6 X 6 - W1.4 X W1.4 OVER EXISTING SLAB

EXISTING 8" CMU WALL

CONT. SEALANT & BACKER ROD ALL SIDES

HOLLOW METAL DOOR FRAME

8 3/4"

3/8" THICK X 7" WIDE STEEL PLATE LINTEL, MIN. 6" BEARING EACH SIDE

4"

EXISTING 8" CMU WALL

CONT. SEALANT & BACKER ROD ALL SIDES

HOLLOW METAL DOOR FRAME

3/8" THICK X 7" WIDE STEEL PLATE LINTEL, MIN. 6" BEARING EACH SIDE

4"

8 3/4"

EXISTING 8" CMU WALL

CONT. SEALANT & BACKER ROD ALL SIDES

HOLLOW METAL DOOR FRAME, WRAP CMU AT JAMB

8 3/4"

2"

EXISTING 8" CMU WALL

CONT. SEALANT & BACKER ROD ALL SIDES

NON-RABBETED HOLLOW METAL DOOR FRAME, WRAP CMU AT JAMB

8 3/4"

2"

HOLLOW METAL DOOR AND FRAME

RESILIENT BASE

NEW CONCRETE LANDING AND RAMP

EXISTING CMU WALL, CUT DOWN BELOW LANDING LEVEL TO MATCH SLOPE OF RAMP IN CORRIDOR AND CONTINUE CONCRETE FROM LANDING ACROSS CMU AT SILL TO CREATE SMOOTH TRANSITION AT THRESHOLD

SLOPED CONCRETE AT SILL TO TRANSITION TO SLOPED RAMP IN CORRIDOR (HEIGHT VARIES). CHIP OUT 1/2" OF CONCRETE AT BASE OF RAMP TO ELIMINATE FEATHER EDGE

EXISTING RAMP SLAB

VARI

ES A

LONG

SLO

PE4"

AT

HIGH

POI

NT

SAW CUT JOINT AT FACE OF CMU WALL TO CONTROL CRACKING

LAUNDRY ACCESS203A

1/2"

RECESS MIN. 2X DEPTH OF RESINOUS FLOORING COATING AT TERMINATION (WIDTH OF HM FRAME TO SAWCUT)

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

1/28

/202

0 9:

48:4

7 AM

A3.1U501

.18

01.2

8.20

ELEV

ATIO

NS, S

ECTI

ONS,

PART

ITIO

N TY

PES,

DOO

RSC

HEDU

LE A

ND D

ETAI

LS

Auth

or

Chec

ker

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

INTERIOR PARTITION1 1/2" = 1'-0"M#A

LEGEND - PARTITION TYPES

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.11 HALLWAY ELEVATION - EAST

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.12 SECTION AT LAUNDRY ACCESS - E/W

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.13 SECTION AT TRASH AND LAUNDRY ACCESS - N/S

DOOR & FRAME TYPES

DOOR SCHEDULE

Mark

DOORFRAMETYPE HEAD JAMB SILL RATING REMARKSWIDTH HEIGHT

DOORTYPE

01_ATHLETIC LEVEL203AA 3' - 8" 7' - 0" D1 F1 11/A3.1 13/A3.1 15/A3.1 N/A203AB 3' - 4" 7' - 4" -- F2 12/A3.1 14/A3.1 -- N/A NO DOOR01_ATHLETIC LEVEL: 2

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.14 WEST ELEVATION - LAUNDRY

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.15 NORTH ELEVATION - LAUNDRY

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.16 EAST ELEVATION - LAUNDRY

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.17 SOUTH ELEVATION - LAUNDRY

REFERENCED ON:

1/4" = 1'-0"A3.1 A1.18 SECTION AT STAIR

REFERENCED ON:

1 1/2" = 1'-0"A3.1 A3.19 DETAIL AT BASE OF RAMP

REFERENCED ON:

1 1/2" = 1'-0"A3.111 HEAD DETAIL 1

REFERENCED ON:

1 1/2" = 1'-0"A3.1 A3.112 HEAD DETAIL 2

REFERENCED ON:

1 1/2" = 1'-0"A3.113 JAMB DETAIL 1

REFERENCED ON:

1 1/2" = 1'-0"A3.1 A1.114 JAMB DETAIL 2

REFERENCED ON:

1 1/2" = 1'-0"A3.1 A3.115 SILL DETAIL 1

Page 5: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UP

UPUP

UP

ABBREVIATION DESCRIPTION BASIS OF DESIGN

BASERB

FLOOR

WALLSP-1

CEILINGS

4" RUBBER COVE

PAINT--GENERAL WALL COLOR

JOHNSONITE RECESS WALL BASE, COLOR: #63 BURNT UMBER

SEMI-GLOSS, TO MATCH SW#7632 MODERN GRAY

MISC.

P-3 PAINT-HM FRAMES, 'MED TONE,' SEMI-GLOSSP-2 PAINT-CEILINGS, 'WHITE TONE,' FLAT FLAT--TO MATCH SW # 7005 PURE WHITE

P-5 PAINT- DOORS ACCENT-'DARK GREY' SEMI-GLOSS TO MATCH 'DARK GREY' EXISTING DOORS--SW #7068 GRIZZLE GRAY OR EQ.

SEMI-GLOSS--'TAUPE' TO MATCH EXISTING ADJACENT FRAMES, SW#7507 STONE LION OR EQ.

CONCRETECONC BROOM FINISH, SEE SPECS.

WP WALL PROTECTION PANEL, 4'-0 WIDTH X 8 OR 10' LENGTHS, COLOR: CHARCOAL--SEE SPEC.WALL PROTECTION

CG CORNER GUARD, STAINLESS STEEL 4' H X 2" RETURN, STAINLESS STEEL CORNER GUARDS, SEE FINISH PLAN FOR LOCATION

EX EXISTING BASE

P-4 NOT USED

REFERENCE SPEC. SECTION

096513

099123099123099123

099123102650

102650

GB/P-* GYPSUM WALL BOARD - PAINTED SEE COLOR DESIGNATIONS ABOVE 092900

EXISTINGEX

APC-1 ACOUSTICAL PANEL CEILING TILE ARMSTRONG - GEORGIAN #764, WHITE, LAY-IN 095113

LAUNDRY203B

LAUNDRY ACCESS203A

STAIRST02

1

2

2

1

DRYER DRYER

FOOD SERVICE201D

KITCHEN201

CLOSET203C

TRASH203

4

5

3

WHERE SPECIFIC PRODUCTS ARE INDICATED, ITEM DESIGNATION INCORPORATES QUALITY AND AESTHETIC APPEARANCE FOR 'BASIS OF DESIGN.' SEE SPECIFICATIONS FOR EQUAL MANUFACTURER'S PER PRODUCT TYPE INDICATED. DEPENDING ON LOCATION OF ITEM, ALTERNATES SHALL MATCH IN COLOR/ TEXTURE, AS WELL AS PERFORMANCE CRITERIA, PER ARCHITECT'S APPROVAL.

ALL PAINT COLOR SELECTIONS SHALL BE FIELD VERIFIED WITH ARCHITECT IN LIGHTED CONDITIONS PRIOR TO FINAL INSTALLATION, SEE SPEC. RE: MOCK-UPS

REFERENCE REFLECTED CEILING PLANS FOR EXTENT/LOCATION OF CEILING FINISH DESIGNATIONS AND HEIGHTS.

SEE FINISH PLANS AND/OR ENLARGED INTERIOR PLANS & ELEVATIONS FOR EXTENT OF SPECIFIC FINISH DESIGNATIONS.

FINISH COLUMNS IN OPEN AREAS TO MATCH ADJACENT WALLS, UNLESS NOTED OTHERWISE.

SEE SPECS FOR FLOOR AND WALL PREP FOR ALL NEW FINISHES.

A.

B.

C.

D.

E.

F.

1 CORNER GUARD LOCATION, SEE SPECS.

EXTENT OF WALL PROTECTION (WP) INSTALLED FROM LAUNDRY LEVEL FINISH FLOOR TO 4'-0" A.F.F., SEE ELEV. 7/A3.1

EXISTING CARPET TO REMAIN ON STAIRS AND UPPER LANDING.

RESILIENT BASE @ NEW WALL

PAINT FOOD SERVICE SIDE OF NEW CMU INFILL TO MATCH EXISTING PAINT COLOR AND INFILL BASE TO MATCH EXISTING.

2

3

4

5

NEW CONCRETE

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

1/28

/202

0 10

:34:

47 A

M

A4.1U501

.18

01.2

8.20

FINI

SHES

Auth

or

Chec

ker

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

SCHEDULED INTERIOR FINISHESREFERENCED

ON:1/4" = 1'-0"A4.1 A3.1

1 FINISH PLAN

ROOM FINISH SCHEDULE (FINISH ORIENTATION IS PLAN NORTH)

Number NameBaseFinish Floor Finish NORTH EAST SOUTH WEST Ceiling Finish

201 KITCHEN EX EX EX EX EX EX EX203 TRASH RB EX EX EX P-1 EX EX203A LAUNDRY ACCESS RB CONC WP,P-1 P-1 WP,P-1 WP,P-1 GB/P-2203B LAUNDRY EX EX EX EX EX EX EX203C CLOSET EX EX EX EX EX EX EXST02 STAIR EX EX EX EX EX EX EX

REVI

SIO

N S

NO.

NAM

EDA

TE

GENERAL NOTES - INTERIOR FINISHES KEYNOTES - FINISHES

LEGEND - FLOOR FINISHES

Page 6: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UPUP

UP1

1

1

1

1

EXISTING EXHAUST LOUVER TO REMAIN

EXISTING INTAKE LOUVER ABOVE DOOR TO REMAIN

EXISTING EXHAUST DUCTWORK TO REMAIN

EXISTING EXHAUST DUCTWORK TO REMAIN T

EXISTING THERMOSTAT TO REMAIN

DEMOLITION NOTES

REMOVE ABANDONED SUPPLY DUCT AND ASSOCIATED DIFFUSERS AS SHOWN.1

REGISTERED

PROFES

SI O

N A L E N G I N E E R

B R A D L E YJ.

JASINSKI

SOUTHCA

R OL I N A

No. 2

3877

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] MD1.1U5

01.1

8

01.2

4.20

HVAC

DEM

OLIT

ION

FLOO

R PL

ANBJ

J

BJJ

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

1−24−20

1/4" = 1'-0"MD1.11 DEMOLITION FLOOR PLAN

REVI

SIO

N S

NO.

NAM

EDA

TE

EXISTING SUSPENDED FAN COIL UNIT TO REMAIN

Page 7: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UPUP

UP

TRASH203

LAUNDRYACCESS

203A

LAUNDRY203B

FOODSERVICE

201D

2M1.1

EXISTING EXHAUST LOUVER TO REMAIN

EXISTING INTAKE LOUVER ABOVE DOOR TO REMAIN

20ø

MIN

. 10'-

0"

SLOPE DUCTS 1/8" PER FOOT AWAY FROM FAN IN EACH DIRECTION

DUCT OFFSETS UP

20ø

DBF-1

DBF-1 FAN CONTROL PANEL

LINT FILTER

A

A

36x24

8'-8" AFF

2 2

8ø12ø LINT CLEANOUT; PROVIDE CAP AND QUICK RELEASE CLAMP

8ø8ø 8ø

15ø18ø

8ø 8ø

211

20ø

20ø

PROVIDE 20"x20" COUNTER BALANCED RELIEF DAMPER WITH FLANGE FRAME AND CONCRETE GRAY HI-PRO POLYESTER COATING

T

20ø 20ø

LAUNDRY203B

TRASH203

PROVIDE VERTICALLY MOUNTED INLINE LINT FILTER EQUAL TO CLEAN CYCLE SYSTEMS MODEL LLB-18

DBF-1PROVIDE 14"ø METAL HOODED WALL CAP WITH FLAPPER DAMPER AND WHITE PAINTED FINISH EQUAL TO FAMCO MODEL DWV14WH

DBF-1 FAN CONTROL PANEL

PRESSURE TIP

TUBING TO FAN CONTROL PANEL

18ø 15ø 12ø 8ø

20ø

SEISMIC RESTRAINT CABLE AT 45 DEGREE ANGLESSECURED TO STRUCTURE TYPICAL FOR 4 CORNERS

SUSPENDED FAN FROMSTRUCTURE

MOTOR COVER

RENOVATION NOTES

CONNECT HARD METAL DRYER EXHAUST DUCT TO APPLIANCE WITH CLAMP EQUAL TO FANTECH MODEL FC8.

PROVIDE DUCT CAP AND CLAMP EQUAL TO FANTECH MODEL FC8 FOR CONNECTION TO FUTURE APPLIANCE.

1

2

GENERAL NOTES

VISIT SITE PRIOR TO BIDDING. THIS CONTRACTOR SHALL DETERMINE DIFFICULTY OF INSTALLATION AND REFLECT THIS IN HIS BIDDING.

DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF DOORS, WINDOWS, AIR DISTRIBUTION, ETC.

THIS CONTRACTOR SHALL VERIFY ALL EXISTING ITEMS AND LOCATIONS IN THE FIELD.

ALL PIPING AND DUCTWORK LOCATIONS SHALL BE COORDINATED WITH WORK UNDER OTHER DIVISIONS OF THE SPECIFICATIONS TO AVOID INTERFERENCE.

EXISTING PIPE, DUCTWORK, CONDUIT, ETC. THAT INTERFERES WITH THE ROUTING OF NEW SYSTEMS SHALL BE RELOCATED. THIS CONTRACTOR SHALL INCLUDE THE COST OF SUCH IN HIS BID UNLESS NOTED OTHERWISE.

WATER SYSTEMS SHALL BE DRAINED AS REQUIRED FOR INSTALLATION OF WORK. UPON COMPLETION, SYSTEM SHALL BE FILLED WITH WATER AND VENTED OF ALL AIR.

ALL PIPING AND DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH PARTITIONS.

ALL PIPING IS SHOWN DIAGRAMMATIC. HOWEVER, THIS CONTRACTOR SHALL PROVIDE ALL REQUIRED FITTINGS, PIPING AND INSULATION FOR ALL OFFSETS AND/OR CHANGES IN ELEVATION.

EXTEND ALL DRAIN LINES TO NEAREST FLOOR DRAIN OR AS INDICATED – SO ROUTED AS TO AVOID INTERFERENCE WITH PASSAGEWAYS AND MAINTENANCE. DRAINS FROM AIR HANDLING UNITS SHALL BE TRAPPED PER STATIC PRESSURE REQUIREMENTS.

ALL WATER PIPING SHALL PITCH DOWN IN DIRECTION OF FLOW ONE-INCH PER FIFTY FEET WITH MANUAL AIR VENTS AT ALL HIGH POINTS AND 3/4-INCH DRAIN VALVES WITH STANDARD HOSE CONNECTION AT ALL LOW POINTS.

ALL VALVES AND SPECIALTIES SHALL BE LINE SIZE UNLESS NOTED OTHERWISE, USING ECCENTRIC REDUCERS ON AUTOMATIC VALVES AS REQUIRED.

MINIMUM PIPE SIZE SHALL BE 3/4-INCH UNLESS INDICATED OTHERWISE.

ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATIONS AND FURTHER SUPPORTS OR HANGERS SHALL BE PROVIDED TO PREVENT WEIGHT OF PIPING BEING PLACED ON EQUIPMENT.

ALL DUCTWORK SPECIFIED TO BE LINED SHALL BE INCREASED IN SIZE TO ALLOW FOR LINER.

PROVIDE FOR ACCESS TO ALL EQUIPMENT REQUIRING CLEANING OR ADJUSTMENT PER MANUFACTURER’S INSTRUCTIONS. PROVIDE FULL SPACE FOR COIL REMOVAL AND REPLACEMENT FOR ALL CHILLED WATER AIR HANDLING UNITS.

THIS CONTRACTOR SHALL PROVIDE ALL ITEMS OF MISCELLANEOUS STEEL AS REQUIRED FOR INSTALLATION OF ALL MECHANICAL ITEMS.

THIS CONTRACTOR SHALL DO ALL CONTROL WIRING. DIVISION 26 WILL DO ALL POWER WIRING. ALL WIRING SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE. CONTROL WIRING SHALL BE CONCEALED WITHIN WALL AND ALL CONTROL WIRING SHALL BE ROUTED IN EMT CONDUIT. DUCT DETECTORS PROVIDED BY DIVISION 26 SHALL BE INSTALLED BY DIVISION 23. POWER WIRING AND FIRE ALARM CONNECTIONS SHALL BE BY DIVISION 26. CONTROL WIRING FOR UNIT SHUTDOWN SHALL BE BY DIVISION 23.

LOCATE ALL SPACE CONTROL INSTRUMENTS 4'-0" ABOVE FINISHED FLOOR TO TOP OF DEVICE IN ACCORDANCE WITH ADA. COORDINATE LOCATIONS WITH ARCHITECTURAL ELEVATIONS TO AVOID ITEMS INCLUDING BUT NOT LIMITED TO CUSTOM FINISHES, FIXED CASEWORK, FURNITURE, AND DOOR SWINGS. IN THE EVENT OF CONFLICTS IN THE FIELD, THE CONTRACTOR SHALL BRING THIS TO THE ATTENTION OF THE A/E FOR FINAL APPROVAL OF LOCATION.

INSTRUMENT TEST HOLES SHALL BE LOCATED IN EACH SUPPLY DUCT OR ZONE DUCT, IN EACH RETURN AIR DUCT AND EACH OUTSIDE AIR DUCT.

CORRECT SETTINGS ON ALL BALANCING FITTINGS SHALL BE PERMANENTLY MARKED. PROVIDE ORANGE FLAGGING RIBBON ON EACH DAMPER HANDLE FOR EASY IDENTIFICATION.

THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY NECESSARY DISMANTLING OF EQUIPMENT TO BE REMOVED.

ITEMS REMOVED UNDER THIS CONTRACT SHALL BECOME THE PROPERTY OF THE CONTRACTOR, UNLESS NOTED OTHERWISE, AND SHALL BE DISPOSED OF PROPERLY.

THE HVAC SYSTEMS SHALL NOT BE OPERATED DURING HEAVY CONSTRUCTION OPERATIONS INCLUDING MASONRY, GYPSUM BOARD SANDING, HEAVY CLEANUP ACTIVITIES, OR OTHER ACTIVITIES THAT CREATE AIRBORNE PARTICLES OR DEBRIS. ALL SYSTEMS SHALL BE CLEAN OF CONSTRUCTION DEBRIS, DUST AND DIRT AT FINAL COMPLETION. DUCT CLEANING AND UNIT/COIL CLEANING SHALL BE PERFORMED AS REQUIRED.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

100A

LEGEND

T ZONE TEMPERATURE SENSOR

TYPE "A" DIFFUSER, 100 CFM

SYMBOL DESCRIPTION

MBD MANUAL OPPOSED BLADE BALANCING DAMPER

48"x24" RECTANGULAR DUCT

RETURN AND FRESH AIR DUCTWORK

RECTANGULAR SUPPLY DUCTWORK

48x24

CONNECTION POINT OF NEW TO EXISTING

ABOVE FINISHED FLOORAFF

EXHAUST DUCTWORK

DBF-1

TAG

EQB-15-15

GREENHECKMODEL NO.

INLINE

TYPE

3,750

CFM

1-1/2

MOTORH.P./W.

1.0

ESP

19

SONES(MAX.)

1,2

REMARKS

DRYER BOOSTER FAN SCHEDULE

1. PROVIDE BELT DRIVEN MIXED FLOW INLINE FAN WITH DISCONNECT SWITCH, CONCRETE GRAYPERMATECTOR COATING, DUCT COLLARS, MOTOR COVER, BELT GUARD, AND BOLTED ACCESSDOOR.

2. PROVIDE CLEAN CYCLE SYSTEMS EQUALIZER VFD FAN CONTROL PANEL WIRED TO CONTROLFAN SPEED BASED ON DUCT MOUNTED PRESSURE PROBE.

TAG

A

NECK SIZEDESCRIPTION MANUFACTURER MODEL FRAME CFM MAX NCFACE SIZE REMARKS

AIR DISTRIBUTION SCHEDULE

1. PROVIDE WITH STANDARD WHITE FINISH.2. PROVIDE ALUMINUM CONSTRUCTION.

LOUVERED TRANSFER PRICE 630 SURFACE - - - 36"x24" 3538"x26" 1,2

REGISTERED

PROFES

SI O

N A L E N G I N E E R

B R A D L E YJ.

JASINSKI

SOUTHCA

R OL I N A

No. 2

3877

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] M1.1U5

01.1

8

01.2

4.20

HVAC

REN

OVAT

ION

FLOO

R PL

AN,

NOTE

S, S

CHED

ULE,

AND

LEG

END

BJJ

BJJ

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

1−24−20

1/4" = 1'-0"M1.11 RENOVATION FLOOR PLAN

1/4" = 1'-0"M1.12 DRYER VENTING SECTION

REVI

SIO

N S

NO.

NAM

EDA

TE

Page 8: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UPUP

UP

TRASH203

LAUNDRYACCESS

203A

LAUNDRY203B

FOODSERVICE

201D

FOODSTORAGE

201C

KITCHEN201

ELECTRICAL202

STAIRST01

STAIRST02

CLOSET203C

1

2

F F

33

SCOPE OFWORK

F

5

4

GENERAL NOTESSUBMIT DRAWINGS INDICATING EXACT LOCATION OF ALL SPRINKLER HEADS FOR OWNER'S REVIEW AND BRING ALL FIELD CONFLICTS AND REQUIRED ADJUSTMENTS TO THE OWNER'S ATTENTION FOR VERIFICATION OF FINAL LOCATION OF ALL SPRINKLER HEADS.

SPRINKLER DRAWINGS PROVIDED ARE TO ASSIST THE CONTRACTOR. SUCCESSFUL CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF A COMPLETE SYSTEM PER THESE PLANS AND SPECIFICATIONS AND IN COMPLIANCE WITH ALL APPLICABLE CODES. CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMISSION TO THE OFFICE OF THE STATE FIRE MARSHAL.

THE DESIGN TEAM, TO INSURE COMPATIBILITY WITH THE BUILDING DESIGN INTENT, WILL CAREFULLY REVIEW SPRINKLER PLANS. CORRECTIONS WILL BE MADE BY THE CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER.

ALL NEW SPRINKLER HEADS SHALL BE CENTERED IN ALL ACOUSTICAL CEILING TILES OR CENTERED IN GYPSUM BOARD SOFFITS AS REQUIRED.

SPRINKLER PIPING SHALL BE INSTALLED TO MEET SEISMIC REQUIREMENTS WITH LATERAL SWAY BRACING, LONGITUDINAL SWAY BRACING, AND FOUR-WAY BRACING AS REQUIRED BY NFPA AND THE INTERNATIONAL BUILDING CODES.

ALL PIPING 2-1/2" AND LARGER SHALL BE SCHEDULE 10 STEEL PIPING AND ALL PIPING SMALLER THAN 2-1/2" SHALL BE SCHEDULE 40 STEEL PIPING.

1.

2.

3.

4.

5.

6.

SPECIAL NOTES

EXISTING SPRINKLER SYSTEM SHALL BE EXTENDED OVER TO UNPROTECTED AREA INSIDE "SCOPE OF WORK" LINE AND PROVIDE COVERAGE AT NEW CEILINGS TO PROVIDE A FULLY PROTECTED AREA. PROTECTION ABOVE CEILING NOT REQUIRED.

AREA OF LAUNDRY ACCESS 203A HAS SPRINKLERS INSTALLED AT STRUCTURE LEVEL. FIRE SPRINKLER CONTRACTOR TO EXTEND HEADS DOWN TO NEW CEILING. EXISTING SPRINKLERS TO REMAIN IN PLACE.

EXISTING SPRINKLER SYSTEM TO BE EXTENDED INTO NEW LAUNDRY. VERIFY HYDRAULIC SIZES.

DROP NEW SPRINKLER LINE BELOW CEILING FOR PROTECTION OF STAIRS.

NEW FIRE SPRINKLER LINE AT STAIR TO BE ROUTED EXPOSED AND MOUNTED TO WALL NEAR CEILING. REFERENCE ARCHITECTURAL DRAWINGS AND ELEVATIONS FOR ADDITIONAL INFORMATION AND ROUTING LOCATION.

1

2

3

4

5

NOTE:ALL WORK SHALL COMPLY WITHNFPA 13 - 2013 EDITION FOR AWET PIPE SYSTEM.

ORDINARY HAZARD - GROUP I-

LIGHT HAZARD

LEGEND

-

WATER FLOW INFORMATION

INFORMATION PROVIDED BY JASON A.SHAW, P.E. WITH THE CITY OF COLUMBIA (803-545-3400).

STATIC: 102 PSIRESIDUAL: 67 PSIFLOW: 1520 GPMDATE: 12/17/2019

REGISTERED

PROFES

SI O

N A L E N G I N E E R

T O D DF .

SWYGERT

SOUTHCA

R OL I N A

No. 1

5574

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] FP1.1U5

01.1

8

01.2

4.20

FLOO

R PL

AN A

ND N

OTES

DEM

TFS

RE-B

ID:

COLI

SEUM

LAU

NDRY

RO

OM F

OR B

ASKE

TBAL

LFP

0000

0296

Caro

lina

Colis

eum

701

Asse

mbly

St.

Colum

bia, S

C 29

208

1−24−20

1/4" = 1'-0"FP1.11 FLOOR PLAN

REVI

SIO

N S

NO.

NAM

EDA

TE

All work this sheet to be priced as Alternate # 1.

Page 9: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UP

UP

UP UP

UP

UP

ELECTRICAL SYMBOL LEGEND

DESCRIPTIONSYMBOL SYMBOL

SINGLE RECEPTACLE (WALL MOUNTED @ 18"AFF)

DUPLEX RECEPTACLE (WALL MOUNTED @ 18"AFF)

PHONE OR DATA OUTLET (WALL MOUNTED @ 18"AFF)

MOTOR CONNECTION (AS NOTED)

J JUNCTION BOX (WALL MTD)

J JUNCTION BOX (FLOOR MOUNTED)

DUPLEX RECEPTACLE (FLOOR MOUNTED)

QUADPLEX RECEPTACLE (FLOOR MOUNTED)

DISCONNECT SWITCH, (REFER TO EQUIPMENT

CONNECTION SCHEDULE)

DISCONNECT SWITCH, (NON PROTECTED)

SP SPEAKER (CEILING MOUNTED)

SP SPEAKER (WALL MOUNTED)

DUPLEX RECEPTACLE (CEILING MOUNTED)

QUADPLEX RECEPTACLE (CEILING MOUNTED)

TV TELEVISION / CATV OUTLET (WALL MOUNTED @ 18"

AFF)

R SECURITY CARD READER

S SMOKE DETECTOR (WALL MOUNTED)

D SMOKE DETECTOR (DUCT MOUNTED)

A FIRE ALARM AUDIBLE DEVICE (WALL MOUNTED @

7'-6" AFF)

WF Wi-Fi ACCESS POINT (CEILING MOUNTED)

AIUADDRESSABLE INTERFACE UNIT (MONITOR OR

CONTROL TYPE)

HANDHOLEHH

DESCRIPTION

FSD FIRE / SMOKE DAMPER

W CCTV CAMERA (WALL MOUNTED)

C CCTV CAMERA (CEILING MOUNTED)

PUSH BUTTON CONTROL

H HEAT DETECTOR (CEILING MOUNTED)

SPD SURGE PROTECTION DEVICE

CABLE TRAY

KITCHEN EQUIPMENT CALLOUT (REFER TO SCHEDULE)#

DUPLEX RECEPTACLE (@ 6" ABOVE COUNTER)

DUPLEX RECEPTACLE (GFI TYPE @ 18"AFF)

DUPLEX RECEPTACLE (USB TYPE @ 18"AFF)

QUAD RECEPTACLE (WALL MOUNTED @ 18"AFF)

QUAD RECEPTACLE (GFI TYPE @ 18"AFF)

QUAD RECEPTACLE (USB TYPE @ 18"AFF)

QUAD RECEPTACLE (@ 6" ABOVE COUNTER)

J JUNCTION BOX (CEILING)

PHONE OR DATA OUTLET (MTD ABOVE COUNTER)

PHONE OR DATA OUTLET (FLOOR MOUNTED)

V FIRE ALARM VISUAL DEVICE (WALL MOUNTED @ 7'-6"

AFF)

A/V FIRE ALARM AUDIBLE/VISUAL DEVICE (WALL MOUNTED @

7'-6" AFF)

FIRE ALARM AUDIBLE DEVICE (CEILING MOUNTED)

FIRE ALARM VISUAL DEVICE (CEILING MOUNTED)

FIRE ALARM AUDIBLE/VISUAL DEVICE (CEILING MOUNTED)

A

V

A/V

S SMOKE DETECTOR (CEILING MOUNTED)

FIRE ALARM PULL STATION (WALL MOUNTED @ 48"

AFF TOP OF BOX)F

T FIRE ALARM TAMPER SWITCH

P FIRE ALARM PRESSURE SWITCH

H HEAT DETECTOR (WALL MOUNTED)

F FIRE ALARM FLOW SWITCH

TV TELEVISION / CATV OUTLET (CEILING MOUNTED)

MULTI-PHASE RECEPTACLE (AS NOTED ON PLAN)

CONDUIT CALLOUT (# INDICATES DIAMETER)#" C.

LIGHTING CONTROL CALLOUT (REFER TO SCHEDULE)#

K SECURITY KEY PAD

PANELBOARD (SURFACE MOUNTED)

PANELBOARD (RECESS MOUNTED)

PIV PRESSURE INDICATING VALVE

#

LIGHT SWITCH, SINGLE POLE

LIGHT SWITCH, 3 WAY TYPE

LIGHT SWITCH, 4 WAY TYPE

LIGHT SWITCH, AUTOMATIC (CONNECT TO LCS)

LIGHT SWITCH, DIGITALLY TIMED (0-30 MINUTES)

LIGHT SWITCH, DIMMER TYPE

LOWER CASE SUBSCRIPT INDICATES SWITCH-LEGa

T

D

A

4

3

OS OCCUPANCY SENSOR (CEILING MOUNTED)

OS OCCUPANCY SENSOR (WALL MOUNTED)

PC PHOTOCELL LIGHTING CONTROL

KEY NOTE CALLOUT (REFER TO KEY NOTES ON SHEET)#

CONTROL PANEL (SURFACE MOUNTED)

CONTROL PANEL (RECESS MOUNTED)

REMOTE TEST STATION FOR DUCT MOUNTED DETECTORS

(WALL MOUNTED)

REMOTE TEST STATION FOR DUCT MOUNTED DETECTORS

(CEILING MOUNTED)

T

T

MMOTOR RATED SNAP SWITCH IN NEMA 1 ENCLOSURE

ELECTRICAL METERING DEVICE

ELECTRICAL UTILITY METER & C/T CABINET

M

M

DUPLEX REC/DATA COMBINATION (FLOOR MOUNTED)

QUADPLEX REC/DATA COMBINATION (FLOOR

MOUNTED)

MULTI-LEVEL SWITCHING CONFIGURATION

DUPLEX RECEPTACLE (GFI TYPE @ 6" ABOVE

COUNTER)

DUPLEX RECEPTACLE (USB TYPE @ 6" ABOVE

COUNTER)

QUAD RECEPTACLE (GFI TYPE @ 6" ABOVE

COUNTER)

QUAD RECEPTACLE (USB TYPE @ 6" ABOVE

COUNTER)

REMOTE FEED-THRU GFCI DEVICE WITH

INDICATOR LIGHT. (NO RECEPTACLE)G

FIRE

12"

DOOR, OPENING

OR END OF

WALL

NOTE:

DEVICES SHOWN WITHIN 48" OF EACH OTHER ON ALL ELECTRICAL PLANS SHALL BE ALIGNED

PER THIS DETAIL. IF DEVICES ARE SHOWN IN MIDDLE OF WALL, THEN CENTER DEVICES ON

WALL.

18"

48"

SEE LEGEND

TELEVISION

DEVICE

RECEPTACLE

VOICE/DATA OUTLET

LIGHT

SWITCH

HVAC THERMOSTAT,

HUMIDISAT, CO

SENSOR, ETC.

FIRE ALARM ANNUNCIATION DEVICE

6"

CL

PHONE OUTLET

CARD

READER

6"

6"

6"

APPROXIMATE LOCATION

OF SWITCHBOARD "MDP-A"

EXISTING TELEPHONE/DATA

EQUIPMENT ROOM

SEE DETAIL 1/E0.2 FOR SIZING

PANEL "LP"

EXISTING PANEL "HB"

EXISTING PANEL "LB"

EXISTING PANEL "EB"

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21815US21815US21815

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

PR

OJE

CT

NO

.

DA

TE

DRAWING NO.

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

TH

IS D

RA

WIN

G A

ND

TH

E D

ES

IGN

T

HE

RE

ON

AR

E T

HE

PR

OP

ER

TY

OF

B

ELK

A E

NG

INE

ER

ING

AS

SO

CIA

TE

S,

INC

. T

HE

RE

PR

OD

UC

TIO

N,

CO

PY

ING

, O

R U

SE

OF

TH

IS

DR

AW

ING

WIT

HO

UT

TH

E W

RIT

TE

N

CO

NS

EN

T O

F B

ELK

A E

NG

INE

ER

ING

A

SS

OC

IAT

ES

, IN

C.

IS P

RO

HIB

ITE

D

AN

D A

NY

IN

FR

ING

EM

EN

T W

ILL B

E

SU

BJE

CT

TO

LE

GA

L A

CT

ION

.

PR

OJE

CT

TIT

LE

A/E

SE

AL

A/E

SE

AL

DR

AW

ING

TIT

LE

01-27-20

1/2

7/2

020 1

0:1

7:3

8 A

M

E0.1

U5

01.1

8

01.2

7.2

0

EL

EC

TR

ICA

L N

OT

ES

& L

EG

EN

DS

JJS

CE

S

RE-B

ID:

CO

LIS

EU

M L

AU

ND

RY

ROOM

FOR

BAS

KETB

ALL

FP00

0002

96C

aro

lina C

olis

eum

701 A

ssem

bly

St.

Colu

mbia

, S

C 2

9208

GENERAL EXISTING CONDITION NOTES1 AREAS OF WORK EXIST FOR THIS PROJECT WHICH ARE NOT ACCESSIBLE OR HAVE LIMITED ACCESS DURING

DESIGN. AS SUCH CONTRACTOR SHALL VERIFY ALL UTILITIES IN AREA OF WORK BEFORE DEMOLITION OF ANY

SERVICE. ANY ELECTRICAL COMPONENTS NOT SHOWN SHALL BE IDENTIFIED AND THE ARCHITECT AND

ENGINEER SHALL BE NOTIFIED AS SOON AS POSSIBLE. NO ELECTRICAL REWORK SHALL BE COMMENCEDWITHOUT COORDINATION OF BOTH ARCHITECT AND ENGINEER.

2 IN AREAS WHERE THE EXISTING CEILINGS ARE NOT SLATED TO BE REMOVED, THE CONTRACTOR SHALL WORKTHRU THE EXISTING CEILINGS (SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR AREA OF WORK). THE

CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY DAMAGED TILE OR GRID THAT IS A RESULT OF

THEIR WORK.

3 REFER TO ARCHITECTURAL PLANS FOR PHASING OF CONSTRUCTION.

4 WHERE INSTALLATION REQUIRES CUTTING OR DRILLING OF THE EXISTING FLOOR SLAB, THE CONTRACTORSHALL X-RAY THE EXISTING SLAB PRIOR TO WORK TO ENSURE THAT NO EXISTING UTILITIES OR STRUCTURAL

ELEMENTS IN THE SLAB WILL BE COMPROMISED BY THE WORK. NOTIFY THE ARCHITECT/ENGINEER OF ANY

CONFLICTS THAT WILL REQUIRE RELOCATING THE PROPOSED SLAB WORK. THE CONTRACTOR SHALL BERESPONSIBLE FOR THE REPAIR OF ANY DAMAGED UTILITIES OR STRUCTURAL ELEMENTS CAUSED BY THE SLAB

DEMOLITION.

5 SUPPORT ALL EXISTING CONDUITS AND JUNCTION BOXES ABOVE THE CEILING PER NEC IN THECONSTRUCTION AREA.

6 REMOVE ALL ABANDONED CONDUIT, WIRE, AND COMMUNICATION CABLES ABOVE THE CEILING IN THECONSTRUCTION AREA.

7 PROVIDE JUNCTION BOX COVER PLATES ON ALL EXISTING JUNCTION BOXES ABOVE THE CEILING IN THECONSTRUCTION AREA.

8 SUPPORT ALL EXISTING COMMUNICATION CABLES ABOVE THE CEILING IN THE CONSTRUCTION AREA

9 WHERE INFORMATION SHOWN ON THESE DRAWINGS CONFLICTS WITH VERIFIED FIELD CONDITIONS, IT SHALL BEBROUGHT TO THE ATTENTION OF THE ENGINEER

GENERAL "ELECTRICAL" NOTES1 BRANCH CIRCUIT WIRING SHALL BE NO. 12 AWG UNLESS NOTED OTHERWISE. WHERE CONDUCTOR AND

RACEWAY SIZE ARE SHOWN AT HOMERUN, SUCH SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.

EXCEPTION: FINAL CONNECTION TO DEVICES, IN OUTLET BOXES, IS NOT REQUIRED TO BE LARGER THAN NO.

12 AWG.

2 20A/120V BRANCH CIRCUITS EXCEEDING 100' IN LENGTH FROM PANEL TO FARTHEST DEVICE OR FIXTURESHALL USE NO. 10 CONDUCTORS AND 3/4"C.

3 PRIOR TO ROUGH-IN, COORDINATE THE LOCATION AND MOUNTING HEIGHT OF ALL WALL AND CEILINGMOUNTED DEVICES WITH THE ARCHITECTURAL ELEVATIONS, MILLWORK SHOP DRAWINGS, AND EXISTING

CONDITIONS. IN THE EVENT OF A CONFLICT, NOTIFY THE ARCHITECT. MINOR ADJUSTMENTS IN DEVICE

LOCATION, I.E. 5'-0" IN ANY DIRECTION SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER.

4 RACEWAYS SHALL BE INSTALLED CONCEALED IN NEW WALL CONSTRUCTION ABOVE CEILINGS, BELOW FLOOR,AND IN OTHER CAVITIES TO THE GREATEST EXTENT POSSIBLE. WHERE EXPOSED RACEWAYS MUST BE USED,

LAYOUT RACEWAYS TO MINIMIZE THE NUMBER OF VERTICAL RUNS.

5 THE ARRANGEMENT, GROUPING, AND ROUTING OF BRANCH CIRCUITS SHALL BE PROVIDED AT THECONTRACTOR'S DISCRETION IN ACCORDANCE WITH GENERALLY ACCEPTED PRACTICE FOR ELECTRICAL WORK,

THE NATIONAL ELECTRICAL CODE REQUIREMENTS, LOCAL ORDINANCES, AND THE FOLLOWING:

5.1 A COMMON NEUTRAL SHALL NOT BE INSTALLED IN A HOMERUN FOR 2 OR 3 BRANCH CIRCUITS UNLESSDIRECTION IS PROVIDED BY THE ENGINEER IN WRITTING FOR A SPECIFIC APPLICATION.

5.2 MULTIPLE SINGLE-POLE BRANCH CIRCUITS (UP TO 3 HOTS, 3 NEUTRALS, 1 GROUND) RATED FOR 30-AMPSOR LESS MAY BE PULLED INTO A SINGLE RACEWAY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING

THE RACEWAYS AND DERATING CONDUCTORS PER NEC ARTICLE 310.15.

5.3 BRANCH CIRCUIT, FEEDER & COMMUNICATION CIRCUITS SHALL BE ROUTED OVERHEAD UNLESS PRIORAPPROVAL HAS BEEN GRANTED BY THE ARCHITECT AND ENGINEER.

5.4 A GROUND CONDUCTOR SHALL BE PROVIDED IN ALL RACEWAYS UNLESS NOTED OTHERWISE.

6 PROVIDE EXPANSION JOINT COUPLINGS ANYWHERE A CONDUIT PASSES THROUGH A BUILDING EXPANSIONJOINT.

7 THE USE OF MC CABLE IS NOT ALLOWED.

8 SEAL ALL EXISTING AND NEW FIRE RATED WALL AND FLOOR PENETRATIONS IN THE CONSTRUCTION AREA

9 SEE THE ARCHITECTURAL DRAWINGS FOR ALL LOCATIONS OF FIRE RATED WALLS.

10 WHEREVER ON THE ELECTRICAL DRAWINGS THE WORD "PROVIDE" IS USED, IT SHALL BE INFERRED TO MEAN"FURNISH AND INSTALL".

11 WHERE CARD READERS AND / OR DOOR CONTACTS ARE SHOWN ON DRAWINGS, COORDINATE WITH ACCESSCONTROL AND DOOR HARDWARE SUPPLIER TO ENSURE THAT ALL RACEWAYS AND BOXES FOR POWER,

SIGNALING, AND DATA ARE PROVIDED TO CARD READER LOCATIONS, DOOR FRAME, POWER SUPPLIES, AND

CABLE-TRAY.

GENERAL "POWER" NOTES1 ALL BRANCH CIRCUITS INDICATED ON THESE PLANS TO BE LARGER THAN NO. 12 AWG SHALL BE SIZED AS

INDICATED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

2 PROVIDE AND INSTALL AN ENGRAVED LAMINATED PLASTIC NAMEPLATE ON EACH ITEM OF ELECTRICALEQUIPMENT SERVING MECHANICAL EQUIPMENT WHICH MATCH MECHANICAL DESCIPTIONS, TO INDICATE THE

DESIGNATION OF THE UNIT ON THE PLANS & THE BRANCH CIRCUIT SERVING THE EQUIPMENT.

3 PROVIDE NEMA CONFIGURATION RECEPTACLES TO MATCH PLUGS ON EQUIPMENT FURNISHED.

4 WHERE SPEED CONTROLLER IS INDICATED TO BE PROVIDED WITH FANS, IT SHALL BE PROVIDED BYMECHANICAL CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR.

5 PROVIDE LABEL ON INSIDE FACE OF COVER PLATE OF ALL RECEPTACLES, SWITCHES & WALL MOUNTEDDEVICES INDICATING PANEL AND BRANCH CIRCUIT TO WHICH EACH DEVICE IS CONNECTED.

GENERAL "LIGHTING" NOTES1 SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE EXACT LOCATION OF ALL CEILING MOUNTED LIGHTING

FIXTURES.

2 EXACT LOCATIONS OF LIGHTING FIXTURES IN MECHANICAL SPACES SHALL BE DETERMINED IN THE FIELD. DONOT SUPPORT FIXTURES FROM DUCT OR PIPING. PROVIDE CHAIN OR TRAPEZE-TYPE HANGERS WHERE

FIXTURES CAN NOT BE MOUNTED DIRECTLY TO CEILING.

3 LIGHTING FIXTURE CATALOG NUMBERS ARE INDICATIVE OF THE STYLE OF FIXTURE REQUIRED. CONTRACTORSHALL PROVIDE FIXTURES WITH THE PROPER TRIM, VOLTAGE AND OPTIONS NECESSARY FOR INSTALLATION.

4 DOUBLE-FACED EXIT FIXTURES SHALL BE OF THE SAME MANUFACTURER & SERIES AS THE SINGLE TYPESPECIFIED.

5 REGARDLESS OF CATALOG NUMBER INDICATED IN SCHEDULE, PROVIDE BATTERY PACKS FOR ALL FIXTURESINDICATED ON THE DRAWINGS TO BE EMERGENCY TYPE.

6 ALL EXIT SIGNS SHALL BE CONNECTED TO LOCAL LIGHTING CIRCUIT AHEAD OF ALL SWITCHING.

7 REGARDLESS OF CATALOG NUMBER INDICATED IN SCHEDULE, ALL EXIT SIGNS SHALL BE PROVIDED WITH ABATTERY PACK, SHALL BE WIRED AHEAD OF LOCAL SWITCH AND SHALL NOT BE SWITCHED.

8 REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING DETAILS OF LIGHT FIXTURE TO ACOUSTICAL CEILINGSYSTEM AND STRUCTURE.

GENERAL "DEMOLITION" NOTES1 ALL ELECTRICAL EQUIPMENT TO BE REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER. THE

CONTRACTOR SHALL NOT DISPOSE OF ANY MATERIALS UNTIL RELEASED BY OWNER'S PROJECT MANAGER.

MATERIALS THAT OWNER'S PROJECT MANAGER CHOOSES TO RETAIN SHALL BE DELIVERED BY THE

CONTRACTOR TO A LOCATION DESIGNATED BY THE PROJECT MANAGER. ALL OTHER MATERIALS SHALL BEPROPERLY DISPOSED OF BY THE CONTRACTOR.

2 REMOVE ALL EXPOSED ABANDONED COMMUNICATION CABLE FOUND DURING THE CONSTRUCTION PROCESS.SUPPORT ALL EXISTING REMAINING CABLE PER THE NEC.

3 ELECTRICAL DEVICES NOT SHOWN ON WALLS TO BE DEMOLISHED SHALL BE DEMOLISHED AT NO ADDITIONALCOST TO OWNER.

4 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS OR WALLS TO REMAIN SHALL REMAIN IN PLACE. PROTECTFROM DAMAGE DURING CONSTRUCTION

5 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS TO BE REMOVED SHALL BE TEMPORARILY DISCONNECTED ANDREMOVED DURING DEMOLITION AND RE-INSTALLED ON NEW CEILING IN SAME LOCATION.

ABBREVIATIONS

ABR DESCRIPTION(E) EXISTING

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

BAS BUILDING AUTOMATION SYSTEM

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BOD BOTTOM OF DEVICE

CBB COMMUNICATIONS BACK BOARD

cd CANDELA

CLG CEILING

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FDS FUSED DISCONNECT SWITCH

FSD FIRE/SMOKE DAMPER

GBB GROUND BUSS BAR

GFCI GROUND-FAULT CIRCUIT-INTERRUPTING

GFI GROUND-FAULT INTERRUPTING

GP GENERAL PURPOSE

HP HEAT PUMP

ICP IRRIGATION CONTROL PANEL

IG ISOLATED GROUND

J-BOX JUNCTION BOX

LCS LIGHTING CONTROL SYSTEM

NEC NATIONAL ELECTRIC CODE

NFDS NON-FUSED DISCONNECT SWITCH

OC ON CENTER

RFAP REMOTE FIRE ALARM ANNUNCIATOR PANEL

RTU ROOF TOP UNIT

SD SMOKE DETECTOR

SPD SURGE PROTECTION DEVICE

TGB TELEPHONE GROUNDING BUSS BAR

UNO UNLESS OTHERWISE NOTED

UTP UNSHIELDED TWISTED PAIR

VFD VARIABLE FREQUENCY DRIVE

W/ WITH

WH WATER HEATER

WP WEATHERPROOF

XFMR TRANSFORMER

ELECTRICAL DRAWING INDEX

# SHEET NAMEE0.1 ELECTRICAL NOTES & LEGENDS

E0.2 ELECTRICAL ONE-LINE DIAGRAM & PANELBOARD SCHEDULE

E1.1 LIGHTING PLANS

E2.1 POWER & SYSTEMS PLANS

DEMOLITION/RENOVATION NOTATIONIF NO ANNOTATION IS SHOWN ASSUME EXISTING TO REMAIN INPLACE FOR SOLID LINES AND DEMOLISH FOR DASHED LINES.

DEVICES AND EQUIPMENT NOT SHOWN SHALL BE ASSUMED TOBE EXISTING TO REMAIN IN PLACE.

E EXISTING FIXTURE OR DEVICE TO REMAIN IN PLACE. REPLACEANY BROKEN DEVICES OR PLATES; COLOR TO MATCH EXISTING.

R EXISTING FIXTURE OR DEVICE TO BE REMOVED BY THEELECTRICAL CONTRACTOR. MAINTAIN CONTINUITY OF REMAINING

PORTIONS OF BRANCH CIRCUIT.

RE EXISTING DEVICE TO BE REMOVED BY THE ELECTRICALCONTRACTOR. EXISTING CIRCUIT SHALL BE RETAINED. PROVIDE

NEW DEVICE AS SHOWN ON RENOVATION PLANS.

RN RELOCATED FIXTURE (NEW LOCATION).

RR EXISTING FIXTURE TO BE RELOCATED BY THE ELECTRICALCONTRACTOR TO NEW LOCATION SHOWN ON RENOVATION PLAN.

SCALE: 12" = 1'-0"E0.1

1 DEVICE ALIGNMENT DETAILSCALE: 1/16" = 1'-0"E0.1

2 ELECTRICAL OVERALL PLAN

EQUIPMENT CONNECTION SCHEDULE NOTES1 ALL SWITCHES SHALL BE GENERAL DUTY TYPE, FUSIBLE UNLESS NOTED WITH "NF" (NON-FUSIBLE).

2 "M" DENOTES DISCONNECT SWITCH INTEGRAL WITH MECHANICAL EQUIPMENT.

3 PROVIDE FUSING PER EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

4 EXISTING WASHER 1 SHALL BE CORD CONNECTED TO 20 AMP, 120V DUPLEX RECEPTACLE. 480V SWITCH SHALL BE FUTURE REPLACEMENT WASHER.

EQUIPMENT CONNECTION SCHEDULE

UNIT I.D. CONNECTION DESCRIPTION

ELECTRICAL SUMMARY DISCONNECT SUMMARY

NOTESVOLTAGE

# OFPOLES

LOAD(VA)

FURN.BY

DISC.RATING

TRIP /FUSE

NEMARATING

DBF-1 DRYER BOOSTER FAN 208 V 2 2496 EC 30 A M 1 2

DRYER 1 RELOCATED EQUIPMENT (UNI-MAC) 480 V 3 31500 EC 60 A - 4 3

DRYER 2 RELOCATED EQUIPMENT (UNI-MAC) 480 V 3 31500 EC 60 A - 4 3

LIGHT FIXTURE SCHEDULE NOTES1 LUMENS LISTED IN SCHEDULE REPRESENT DELIVERED LUMENS OF FIXTURES.

2 SEE ARCHITECTURAL RCP AND ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHTS.

3 CONFIRM QUANTITIES OF FIXTURES SHOWN IN RCP MATCH QUANTITIES SHOWN ON ELECTRICAL PLANS PRIOR TO BID. IF NO DISCREPANCIES ARE NOTED PRIOR TO BID THE HIGHESTQUANTITY OF EACH FIXTURE TYPE SHOWN SHALL BE PROVIDED.

LIGHT FIXTURE SCHEDULE

SYMBOL

FIXTURE SPECIFICATIONS LAMPING ELECTRICAL

MOUNTING REMARKS NOTESTYPE FIXTURE DESCRIPTION MANUFACTURER CAT. # NO. LAMP TYPEFIXT.LOAD VOLTS

AE 4' LINEAR LED VAPORTIGHTFIXTURE WITH BATTERY PACK

HUBBELL LXEM4-40ML-RFA-EU-ELL14

- LED, 4343L,4000K

39 120 V SURFACE 1,2,3

E SEE DEMOLITION/RENOVATIONNOTATION ON SHEET E0.1

59 120 V

E or R SEE DEMOLITION/RENOVATIONNOTATION ON SHEET E0.1

X EXIT SIGN WITH BATTERY ANDRED LETTERING

COMPASS CER - LED 4 120 V AS SHOWN ON PLAN 1,2,3

RE

VIS

ION

S

NO

.N

AM

ED

AT

E

All work on electricalsheets to be pricedas Alternate # 2.

Page 10: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

EXISTING

SWITCHBOARD

"SWBD"PANEL

"LP"

MAIN ELECTRICAL ROOM

FIRST FLOOR

2E0.2

LAUNDRY H120F

PROVIDE 400A,

3POLE BREAKER

PROVIDE 4-#600KCMIL,

1#2G. IN 4"C.

EXISTING

TYPICAL

SECONDARY

PANELSERVICE ENTRANCE

RATED EQUIPMENT

NEUTRAL GROUND

PROVIDE BUILDING GROUND ROD

CLUSTER. PROVIDE A #4/0

MINIMUM BARE COPPER WIRE

WELDED TO RODS.

20' MINIMUM INTERIOR METAL COLD-WATER PIPE(S)

SERVICE NEUTRAL FROM

UTILITY TRANSFORMER.

SIZE TO MATCH PHASE

CONDUCTORS.

EGC

NEUTRAL GROUND

GEC

METAL OUTLET BOX

GREEN HEX HEAD

GROUNDING SCREW

[250.126]

BOND BOX USING GROUNDING

SCREW, DO NOT USE SHEET

METAL SCREW [250.8]

[250.146]

EGC

SIZE NEUTRALS TO

MATCH PHASE.

GEC [250.66(B)]

PIGTAIL AND

SPLICE.

CONCRETE ENCASED

REINFORCING STEEL OR COPPER

CONDUCTOR.

[250.52(A)(3)] - WHERE

EXISTING

GEC

PIPE GROUNDING CLAMPS. CONNECTION

MADE AT NOT GREATER THAN 5'-0"

FROM POINT OF ENTRANCE [250.52(A)

(1)].

GAS PIPING

EGC PIPE GROUNDING CLAMPS. BOND ONLY

IF LIKELY TO BECOME ENERGIZED BY

FAULTED CONDUCTOR [250.104(B)].

EGCSIZE

NEUTRALS TO

MATCH

PHASE.

GEC

MBJ

GROUNDING LEGEND

ABBR. DESCRIPTION SIZE

MBJ MAIN BONDING JUMPER

SBJ SYSTEM BONDING JUMPER *

GEC GROUNDING ELECTRODE CONDUCTOR 3/0

EGC EQUIPMENT GROUNDING CONDUCTOR **

GROUNDING NOTES:

1. NUMBERS IN BRACKETS REFER TO SPECIFIC SECTIONS OF THE NATIONAL ELECTRICAL CODE.

2. ALL UNDERGROUND OR OTHERWISE INACCESSIBLE GROUND CONNECTIONS AND SPLICES SHALL BE

EXOTHERMICALLY WELDED [250.68].

3. GROUND ELECTRODE FOR SEPARATELY DERIVED SYSTEMS SHALL BE THE NEAREST METAL WATER PIPE ORSTRUCTURAL METAL. IF EITHER IS NOT AVAILABLE, PROVIDE GROUNDING CONDUCTOR BACK TO MAIN

GROUND BUS AT SERVICE ENTRANCE.

4. PROVIDE A GROUND WIRE IN ALL CONDUITS.

5. EARTH SHALL NOT BE USED AS THE SOLE GROUND RETURN PATH FOR ANY EQUIPMENT POWERED UNDER

THIS PROJECT.

6. NO ALUMINUM SHALL BE USED FOR GROUNDING WORK WITHOUT THE SPECIFIC WRITTEN PERMISSION OF THE

ENGINEER. EXCEPTION: ALUMINUM BUILDING STRUCTURAL MATERIALS SHALL BE BONDED WITH LISTED

ALUMINUM EQUIPMENT WITH ALUMINUM TO COPPER CONNECTORS FOR ROUTING COPPER EGC'S.

7. PROVIDE GROUNDING BUSHING ON BOTH ENDS OF ALL SERVICE ENTRANCE RACEWAYS, SIZE AS A GEC

[250.80]. THIS INCLUDES RIGID STEEL ELBOWS ON PVC CONDUIT.

8. ALL METAL ENCLOSURES AND RACEWAYS SHALL BE BONDED TO GROUND [250.86]. FOR CIRCUITS OVER250V PROVIDE BOND PER [250.97], STANDARD LOCKNUTS ARE NOT ACCEPTABLE.

9. PROVIDE EGC CONNECTED TO ANY JUNCTION BOX WHERE SPLICE IS MADE [250.148] OR WHERE A DEVICE

IS INSTALLED.

10. PROVIDE BOND TO EXPOSED METAL ON ALL MOTORS, PUMPS, AND LIGHTING FIXTURES PER [250.112].

* SIZE PER TABLE 250.66 OF THE NEC OR

12.5% OF CONDUCTOR SIZE [250.28].

** SIZE PER TABLE 250.122.

DIAGRAM PROVIDES OVERALL VIEW OF BUILDING GROUNDING SYSTEM. EQUIPMENT SHALL BE GROUNDED BASED ON ITS PORTION OF THIS DIAGRAM.

3/0

SSBJ SUPPLY SIDE BONDING JUMPER 2/0

TIE SSJB TO A

GROUNDING BUSHING ON

EACH SERVICE ENTRANCE

CONDUIT.

SSBJ

NOTE 3

GEC

EGC

TYPICAL

SUB-PANEL

NEUTRAL GROUND EGC

EGC

SBJ

TRANSF.

NEUTRAL

LUG

TYPICAL

TRANSFORMER

GROUND

SIZE NEUTRALS TO

MATCH PHASE.

BUILDING STEEL

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21815US21815US21815

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

PR

OJE

CT

NO

.

DA

TE

DRAWING NO.

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

TH

IS D

RA

WIN

G A

ND

TH

E D

ES

IGN

T

HE

RE

ON

AR

E T

HE

PR

OP

ER

TY

OF

B

ELK

A E

NG

INE

ER

ING

AS

SO

CIA

TE

S,

INC

. T

HE

RE

PR

OD

UC

TIO

N,

CO

PY

ING

, O

R U

SE

OF

TH

IS

DR

AW

ING

WIT

HO

UT

TH

E W

RIT

TE

N

CO

NS

EN

T O

F B

ELK

A E

NG

INE

ER

ING

A

SS

OC

IAT

ES

, IN

C.

IS P

RO

HIB

ITE

D

AN

D A

NY

IN

FR

ING

EM

EN

T W

ILL B

E

SU

BJE

CT

TO

LE

GA

L A

CT

ION

.

PR

OJE

CT

TIT

LE

A/E

SE

AL

A/E

SE

AL

DR

AW

ING

TIT

LE

01-27-20

1/2

7/2

020 1

0:1

8:1

2 A

M

E0.2

U5

01.1

8

01.2

7.2

0

EL

EC

TR

ICA

L O

NE

-LIN

E D

IAG

RA

M &

PA

NE

LB

OA

RD

SC

HE

DU

LE

JJS

CE

S

RE-B

ID:

CO

LIS

EU

M L

AU

ND

RY

ROOM

FOR

BAS

KETB

ALL

FP00

0002

96C

aro

lina C

olis

eum

701 A

ssem

bly

St.

Colu

mbia

, S

C 2

9208

NOT TO SCALEE0.2

1 POWER ONE-LINE DIAGRAM

NOT TO SCALEE0.2

2 GROUNDING DETAIL

ELECTRICAL DISTRIBUTION SYSTEM

PANEL DISTRIBUTION PHASE# OFWIRES

MAINSTYPE MCB

FEDFROM REMARKS

SWBD 480 V/3-0 3 4 5000 A EXISTING, MANUFACTURER: WESTINGHOUSE

LP 480 V/3-0 3 4 MCB 400 A SWBD

NOTES:

TOTAL PER PHASE AMPACITY: 76 76 76 CONNECTED AMPACITY: 76

TOTAL PER PHASE KVA: 21.0 21.0 21.0 CONNECTED KVA: 63.0

41 0.0 0.0 -- -- PREPARED SPACE 42 --

39 0.0 0.0 -- -- PREPARED SPACE 40 ----

37

DRYER #4 (ADC) (FUTURE) 60 3

0.0 0.0 -- -- PREPARED SPACE 38 --

35 0.0 0.0 -- -- PREPARED SPACE 36 --

33 0.0 0.0 -- -- PREPARED SPACE 34 ----

31

DRYER #3 (ADC) (FUTURE) 60 3

0.0 0.0 -- -- PREPARED SPACE 32 --

29 10.5 0.0 -- -- PREPARED SPACE 30 --

27 10.5 0.0 -- -- PREPARED SPACE 28 --3-#6, 1-#6, 1-#10

25

DRYER #2 (UNI-MAC) 60 3

10.5 0.0 -- -- PREPARED SPACE 26 --

23 10.5 0.0 -- -- PREPARED SPACE 24 --

21 10.5 0.0 -- -- PREPARED SPACE 22 --3-#3, 1-#3, 1-#8

19

DRYER #1 (UNI-MAC) 100 3

10.5 0.0 -- -- PREPARED SPACE 20 --

-- 17 PREPARED SPACE -- -- 0.0 0.0 18

-- 15 PREPARED SPACE -- -- 0.0 0.0 16

-- 13 PREPARED SPACE -- -- 0.0 0.0

3 30 WASHER #2 (UNI-MAT 35) (FUTURE)

14

--

-- 11 PREPARED SPACE -- -- 0.0 0.0 12

-- 9 PREPARED SPACE -- -- 0.0 0.0 10

-- 7 PREPARED SPACE -- -- 0.0 0.0

3 30 WASHER #1 (FUTURE)

8

--

-- 5 PREPARED SPACE -- -- 0.0 0.0 6

-- 3 PREPARED SPACE -- -- 0.0 0.0 4

-- 1 PREPARED SPACE -- -- 0.0 0.0

3 100 DRYER #5 (CISSEL, CKT 1: HEAT) (FUTURE)

2

--

WIRE SIZE CKT DESCRIPTION BKR P A B C P BKR DESCRIPTION CKT WIRE SIZE

MOUNTING: SURFACE ENCLOSURE: Type 1

SUPPLIED FROM: SWBD WIRES: 4 MCB RATING: 400 A

PHASES: 3 MAINS RATING: 400 A

PANELBOARD:

LPDISTRIBUTION: 480/277 Wye A.I.C. RATING: 28,860

1"C.

1"C.

RE

VIS

ION

S

NO

.N

AM

ED

AT

E

All work on electricalsheets to be pricedas Alternate # 2.

Page 11: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UP

UPUP

UP

UP

UPUP

UP

RR

E

E

E E

E E

E E E E

EE

E E E

E

E

RR

RR

E

E

E

RR

203TRASH

203A

LAUNDRY

ACCESS

203B

LAUNDRY

201D

FOOD

SERVICE

E

E

RN

1

X

X

X X

3

3

E

E

RN

AE

E E

E E

EE

E E E E E

E

EEE

E E

E

2

SHADING INDICATES EMERGENCY FIXTURE SUPPLIED WITH EMERGENCY BATTERY PACK

CE = UPPERCASE LETTER / LETTERS INDICATE FIXTURE TYPEd = LOWERCASE LETTER INDICATES SWITCH IDENTIFICATION NL or EM = INDICATES NON SWITCHED "NIGHT LIGHT" / "EMERGENCY"A-2 = DESIGNATES PANEL NAME - CIRCUIT NUMBER

NOTE:

ALL "EM" FIXTURES INDICATED IN PLAN CONTAIN EMERGENCY BALLASTS. ALL EMERGENCY BALLAST FIXTURES REQUIRE AN EXTRA CONSTANT POWER CONDUCTOR TO BE CONNECTED TO THE EMERGENCY BALLAST FOR CHARGING. CONDUCTOR MUST NOT BE CONTROLLED BY ANY LIGHTING SYSTEM OR HAVE POWER INTERUPTED AT ANY TIME. "NL" FIXTURES SHALL HAVE ABSOLUTELY NO LIGHTING CONTROL & SHALL BE OPERATIONAL AT ALL TIMES.

IN BOTH CASES "EM" & "NL" , WHERE UTILITY POWER SHOULD FAIL, FIXTURES SHALL REMAIN OPERATIONAL FOR A MINIMUM 90 MINUTES @ 1400 LUMENS.

NL A-2

CE

LIGHT FIXTURE PLAN KEY

d

N

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21815US21815US21815

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

PR

OJE

CT

NO

.

DA

TE

DRAWING NO.

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

TH

IS D

RA

WIN

G A

ND

TH

E D

ES

IGN

T

HE

RE

ON

AR

E T

HE

PR

OP

ER

TY

OF

B

ELK

A E

NG

INE

ER

ING

AS

SO

CIA

TE

S,

INC

. T

HE

RE

PR

OD

UC

TIO

N,

CO

PY

ING

, O

R U

SE

OF

TH

IS

DR

AW

ING

WIT

HO

UT

TH

E W

RIT

TE

N

CO

NS

EN

T O

F B

ELK

A E

NG

INE

ER

ING

A

SS

OC

IAT

ES

, IN

C.

IS P

RO

HIB

ITE

D

AN

D A

NY

IN

FR

ING

EM

EN

T W

ILL B

E

SU

BJE

CT

TO

LE

GA

L A

CT

ION

.

PR

OJE

CT

TIT

LE

A/E

SE

AL

A/E

SE

AL

DR

AW

ING

TIT

LE

01-27-20

1/2

7/2

020 1

0:1

8:3

3 A

M

E1.1

U5

01.1

8

01.2

7.2

0

LIG

HT

ING

PL

AN

S

JJS

CE

S

RE-B

ID:

CO

LIS

EU

M L

AU

ND

RY

ROOM

FOR

BAS

KETB

ALL

FP00

0002

96C

aro

lina C

olis

eum

701 A

ssem

bly

St.

Colu

mbia

, S

C 2

9208

KEY NOTES

1 EXISTING EXIT SIGN SHALL BE REMOVED AND REINSTALLED IN THE SAMELOCATION, PENDANT MOUNTED AT APPROXIMATELY 3'0" BELOW CEILING.

2 EXISTING LAUNDRY ROOM LIGHTING FIXTURES SHALL REMAIN. IF LIGHTINGCONFLICTS WITH NEW DRYER DUCTS REMOVE OR RELOCATE FIXTURES AS

REQUIRED AND DIRECTED BY ARCHITECT.

GENERAL NOTES1 ELECTRICAL CONTRACTOR SHALL RE-USE OR EXTEND EXISTING LIGHTING

CIRCUIT(S) THAT SERVED AREA FOR RENOVATION PHASE LIGHTING

FIXTURES.

SCALE: 1/4" = 1'-0"E1.1

1 LIGHTING DEMOLITION PLAN

SCALE: 1/4" = 1'-0"E1.1

2 LIGHTING RENOVATION PLAN

0 8' - 0" 12' - 0" 16' - 04' - 0"

SCALE: 1/4" = 1'-0"

RE

VIS

ION

S

NO

.N

AM

ED

AT

E

All work on electricalsheets to be pricedas Alternate # 2.

Page 12: UNIVERSITY OF SOUTH CAROLINA RE-BID: COLISEUM ...purchasing.sc.edu/solicitations/Coliseum Laundry_FINAL...HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG

UP

UPUP

UP

J J J

J

J

A/V S

A/V

JJ

UP

UPUP

UP J

J

A/V SJ

A/V

E

R R R E

E

E

EERR

COMPACTOR

E

E

MOTION

MOTION

RR RR

SECURITY PAD

HVAC CTRLS

R

SECURITY

ENCLOUSRE

E

R

E E1

RR

2

44

2

203TRASH

203A

LAUNDRY

ACCESS

203BLAUNDRY

201D

FOOD

SERVICE

E

PANEL "LP"

COMPACTOR

RN

DRYER

1

DRYER

2

RN

RN

60cd

E

E

19,21,23 25,27,29

RN

21

UNI-MAC

UNI-MAC

3

DBF-1 FAN CONTROL PANEL

2

3

5

6 6

E E

E

E

E

E

N

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21815US21815US21815

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. 26181

R

A

NILORACHTU

O

S

J EE

NI

GN

E

LANOISSEF

OR

PD

ES

NE

CILA

S

ON E

AR

T

L.HERA

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

No. C00953

ASSOC. INC.

BELKA

ENGINEERING

A

NILORACHTU

O

S

CE

RT

I FI CATE OF AUTHOR

I ZA

TI O

N

PR

OJE

CT

NO

.

DA

TE

DRAWING NO.

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

TH

IS D

RA

WIN

G A

ND

TH

E D

ES

IGN

T

HE

RE

ON

AR

E T

HE

PR

OP

ER

TY

OF

B

ELK

A E

NG

INE

ER

ING

AS

SO

CIA

TE

S,

INC

. T

HE

RE

PR

OD

UC

TIO

N,

CO

PY

ING

, O

R U

SE

OF

TH

IS

DR

AW

ING

WIT

HO

UT

TH

E W

RIT

TE

N

CO

NS

EN

T O

F B

ELK

A E

NG

INE

ER

ING

A

SS

OC

IAT

ES

, IN

C.

IS P

RO

HIB

ITE

D

AN

D A

NY

IN

FR

ING

EM

EN

T W

ILL B

E

SU

BJE

CT

TO

LE

GA

L A

CT

ION

.

PR

OJE

CT

TIT

LE

A/E

SE

AL

A/E

SE

AL

DR

AW

ING

TIT

LE

01-27-20

1/2

7/2

020 1

1:3

2:4

6 A

M

E2.1

U5

01.1

8

01.2

7.2

0

PO

WE

R &

SY

ST

EM

S P

LA

NS

JJS

CE

S

RE-B

ID:

CO

LIS

EU

M L

AU

ND

RY

ROOM

FOR

BAS

KETB

ALL

FP00

0002

96C

aro

lina C

olis

eum

701 A

ssem

bly

St.

Colu

mbia

, S

C 2

9208

KEY NOTES

1 COORDINATE RELOCATION OF EXISTING TRASH COMPACTOR WITH OWNERAND ARCHITECT BEFORE ROUGH-IN. MODIFY AND EXTEND EXISTING

BRANCH CIRCUIT AS REQUIRED.

2 ELECTRICAL CONTRACTOR SHALL RELOCATE INDICATING DEVICE SUCH THATIT IS NOT COVERED/CONCEALED BY DUCT WORK.

3 ELETRICAL CONTRACTOR SHALL PROVIDE A 25 AMP, 208 VOLT, SINGLEPHASE CIRCUIT BREAKER IN EXISTING PANEL "LB" TO SERVE THIS UNIT

(SEE ELECTRICAL OVERALL PLAN ON SHEET E0.1 FOR LOCATION OF

PANEL). ELECTRICAL CONTRACTOR SHALL COORDINATE AVAILABLE SPACEAND CIRCUITS WITH OWNER'S RESIDENT ELECTRICIAN IN EXISTING PANEL

"LB". ELECTRICAL CONTRACTOR SHALL FEED THIS UNIT WITH 2-#10,

1-#10 GROUND IN 3/4" CONDUIT. ELECTRICAL CONTRACTOR SHALL TURN

OVER ANY BREAKERS REMOVED FROM PANEL "LB" TO MAKE ROOM FOR25 AMP BREAKER. ELECTRICAL CONTRACTOR SHALL FEED CONTROL PANEL

AND PROVIDE INTERCONNECTING WIRING FROM CONTROL PANEL TO

DBF-1.

4 EXISTING EQUIPMENT TO REMAIN IN PLACE.

5 PROVIDE BRANCH CIRCUITS FROM PANEL "LP" (SEE PANEL SCHEDULE ONDWG. E0.2 & EQUIPMENT CONNECTION SCHEDULE ON DWG E0.1.

6 PROVIDE DRYER DISCONNECT SWITCHES COORDINATING LOCATION &ACCESSIBILITY WITH DRYER EXHAUST DUCTWORK.

GENERAL NOTES1 ELECTRICAL DEVICES ON THIS SHEET SHALL BE CIRCUITED FROM PANEL

"LP" WITH CIRCUIT NUMBER SHOWN, UNLESS INDICATED OTHERWISE.

SCALE: 1/4" = 1'-0"E2.1

1 POWER/SYSTEMS DEMOLITION PLAN

SCALE: 1/4" = 1'-0"E2.1

2 POWER/SYSTEMS RENOVATION PLAN

0 8' - 0" 12' - 0" 16' - 04' - 0"

SCALE: 1/4" = 1'-0"

RE

VIS

ION

S

NO

.N

AM

ED

AT

E

All work on electricalsheets to be pricedas Alternate # 2.