IM 05P02C41-15EN page 1/14
Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams
IntroductionThankyouforpurchasingtheUP55AProgramController.Thisoperationguidedescribesthebasicoperationsrelatedtothesingle-loopcontrolfunctionoftheUP55A.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrect operation.Fordetailsofeachfunction,refertoUser’sManual.Beforeusingtheproduct,referto thetableofModelandSuffixCodestomakesurethat thedeliveredproduct isconsistentwith themodelandsuffixcodesyouordered.Alsomakesure that thefollowingitemsareincludedinthepackage.
•ProgramController(themodelyouordered) ..........................................x1• Set of Brackets ........................................................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE) ..............................................................................x1(Onlywhenordered.)•TerminalCover(L4502XP) .....................................................................x1
lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injuryto theuserordamageto the instrument,andsignifies that theusermustrefer totheuser’smanual forspecial instructions.Thesamesymbol isused in theuser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).
NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.
Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin
theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto
anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.
Safety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,
andtoensuresafeoperation,observethesafetyprecautionsdescribed in theuser’smanual.Useof the instrument inamannernotprescribedhereinmaycompromise the product's functions and the protection features inherent in the device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.
(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproduct itself; foolproofor failsafedesignofaprocessor lineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomer deems necessary.
(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.
(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.
(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.(7)This product isULRecognizedComponent. In order to complywithUL
standards,end-productsarenecessary tobedesignedby thosewhohaveknowledgeoftherequirements.
WARNING
lPower Supply Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.
l Damage to the Protective Construction Operation of the instrument in a manner not specified in the
user’s manual may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.
2. ModelandSuffixCodes UP55A
Model SuffixcodeOptionalsuffixcode
Description
UP55A
ProgramController(Powersupply:100-240VAC)(providedwith3DIs,and3DOs)30programpatterns/300programsegments(Max.99segmentsperpattern)
Fixedcode -NNN Always"-NNN”(fordetailedcodemodel)
Displaylanguage(*1)
-1 English(Default.Canbeswitchedtootherlanguagebythesetting.)-2 German(Default.Canbeswitchedtootherlanguagebythesetting.)-3 French(Default.Canbeswitchedtootherlanguagebythesetting.)-4 Spanish(Default.Canbeswitchedtootherlanguagebythesetting.)
Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)
Output1(*2)(*3)
-A Analogoutput(current/voltagepulse)-R Relayoutput(c-contact)-U Universaloutput(current/voltagepulse/relay)-T Triac output-P Position proportional output
Output2(*2)(*3)
A Analogoutput(current/voltagepulse)R Relayoutput(c-contact)U Universaloutput(current/voltagepulse/relay)T Triac outputN None
Retransmissionoutput /RT Retransmissionoutputor15VDCpowersupplyHeaterbreakalarm(*3) /HA Heaterbreakalarm
E1terminalarea(*4)
/R1 Remote(1additionalaux.analog)inputand1additionalDI/U1 1additionaluniversalinput(TC/RTD/DCV/mA)/X1 5additionalDIs/Y1 5additionalDOs/W1 2additionalDIsand2additionalDOs
E2terminalarea(*4)
/A2 1additionalaux.analoginputand1additionalDI/X2 5additionalDIs/Y2 5additionalDOs/W2 2additionalDIsand2additionalDOs
E3terminalarea(*4)(*5)
/CH3 RS485communication(Max.38.4kbps,2-wire/4-wire)/CC3 CC-Linkcommunication(withModbusmasterfunction)/PD3 PROFIBUS-DPcommunication(withModbusmasterfunction)/DN3 DeviceNetcommunication(withModbusmasterfunction)/ET3 Ethernetcommunication(withserialgatewayfunction)/X3 5additionalDIs/Y3 5additionalDOs/W3 2additionalDIsand2additionalDOs
E4terminalarea(*4)(*5)
/A4 1additionalaux.analoginputand1additionalDI/C4 RS485communication(Max.19.2kbps,2-wire/4-wire)/L4 24VDClooppowersupply
/AC4 1additionalaux.analoginput,1additionalDI,andRS485communication(Max.19.2kbps,2-wire)
/LC4 24VDClooppowersupplyandRS485communication(Max.19.2kbps,2-wire)
/X4 5additionalDIs/Y4 5additionalDOs/W4 2additionalDIsand2additionalDOs
Power supply /DC Powersupply24VAC/DCAdditionaltreatment(*6) /CT Coating
*1: English,German,French,andSpanishareavailablefortheguidedisplay.*2: Forheating/coolingoutput,bothOutput1andOutput2shouldbespecified.Notavailable
whenOutput2is“N”.Forpositionproportionaloutput,specify“-P”forOutput1and“N”forOutput2.*3: The/HAoptioncanbespecifiedonlywhenthecodeforOutput1and2is“-AN”,“-RN”,“-UN”or“-TN.”*4: OnlyoneoptionisavailableforeachterminalareaofE1toE4.*5: The/L4and/LC4optionsforE4terminalareacanbespecifiedonlywhentheE3terminal
areaoptionisnotspecifiedorspecifiedanyof/CH3,/X3,/Y3or/W3.*6: Whenthe/CToptionisspecified,theUT55Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).
Accessories (sold separately)Thefollowingisanaccessorysoldseparately.• LL50AParameterSettingSoftware
Model Suffixcode DescriptionLL50A -00 ParameterSettingSoftware
• ExternalPrecisionResistorModel Suffixcode Description
X010 SeetheGeneralSpecifications(*) ResistanceModule
*:Necessarytoinputthecurrentsignaltothevoltageinputterminal.• TerminalCover:ModelUTAP001• Brackets(Partnumber:L4502TP) 2 pcs for upper and lower sides•User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.• OperationGuideforSingle-loopControl(thisdocument)x7(A3size) (InstallationandWiring,InitialSettings,Programmings,Operations,andParameters)
3. How to Install
Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.
• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.
However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tiple indicatingcontrollers,seetheexternaldimensions/panelcutoutdimensionswhichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywiththesepanelcutoutdimensionstoprovidesufficientclearancebetweentheinstru-ments.
• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.
Front panelof controller
Keep this anglewithin 30°
Rear ofcontroller
30°
NoteIf the instrument ismoved froma locationwith low temperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if the temperaturechangesrapidly, condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases
Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.
• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.
• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.
• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the controller before in-stalling it on the panel to avoid an electric shock.
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA
Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation
150 mm150 mm
150 mm
150 mm
OperationGuideIM 05P02C41-15EN
UP55AProgram Controller (Detailed code model)
Operation Guide for Single-loop Control
This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation.
3rd Edition : Apr. 2015
Installation and Wiring
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
• AuthorisedRepresentativeintheEEA YokogawaEuropeBV. (Address: Euroweg 2 , 3825HDAmersfoort, TheNetherlands) is theAuthorisedRepresentativeofYokogawaElectricCorporationforthisProductintheEEA.
• Printed ManualsModel Description
UP55AProgramControllerOperationGuide(Standardcodemodel) IM05P02C41-11ENUP55AProgramControllerOperationGuide(Detailedcodemodel) IM05P02C41-15ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
• ElectronicManuals Youcandownloadthelatestmanualsfromthefollowingwebsite: URL:http://www.yokogawa.com/ns/ut/im/
Model DescriptionUP55AProgramControllerOperationGuide(Standardcodemodel) IM05P02C41-11ENUP55AProgramControllerOperationGuide(Detailedcodemodel) IM05P02C41-15ENUP55AProgramControllerUser’sManual IM05P02C41-01ENUTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01ENUTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02ENLL50AParameterSettingSoftwareInstallationManual IM05P05A01-01ENLL50AParameterSettingSoftwareUser’sManual IM05P05A01-02ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
• GeneralSpecificationModel Description
UP55AProgramController GS05P02C41-01ENLL50AParameterSettingSoftware GS05P05A01-01EN
* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethelanguageinwhichthemanualiswritten.
IM 05P02C41-15EN page 2/14
Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstallthecontroller:1) Insert thecontroller into theopening from the frontof thepanelso that the
terminalboardontherearisatthefarside.2) Setthebracketsinplaceonthetopandbottomofthecontrollerasshowninthe
figurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.
Bracket(top mounting hardware)
Terminal board
Bracket(bottom mounting hardware)
Panel
Insert a screwdriver into thebrackets to tighten the screws.
Direction to insert thecontroller
Appropriatetightening torque:0.25 N•m
Insert the controllerinto the opening atthe front of the panel.
CAUTION
• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.
• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.
External Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]117 (4.61) min.
145 (5.71)min.
+0.80
+0.8092
“N” stands for the number of controllers to beinstalled.However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11(0.43)
UP55A
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)Bracket
Bracket
94.6
(3.7
2)
91.6
(3.6
1)
105.
2 (4
.14)
Unit: mm (approx. inch)96 (3.78)
96 (3
.78)
• General mounting • Side-by-side close mounting
Terminal cover
Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8092
+0.030(3.62 )
(0.98)+0.030(3.62 )
+0.8092
+0.030(3.62 )
([(N-1)×3.78+3.62] )+0.030
4. HardwareSpecifications
WARNING
This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance IVCable
III TO( I )
II
Category IEC/EN/CSA・UL 61010-1: 2001 EN 61010-2-030 Remarks
No.1 Measurement CategoryI O(Other) For measurements performed on circuits not direct-
lyconnectedtoMAINS.
No.2 Measurement CategoryII
Measurement CategoryII
For measurements performed on circuits directly connectedtothelow-voltageinstallation.
No.3 Measurement CategoryIII
Measurement CategoryIII
Formeasurementsperformedinthebuildinginstal-lation.
No.4 Measurement CategoryIV
Measurement CategoryIV
For measurements performed at the source of the low-voltageinstallation.
InputSpecifications
UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type Instrument Range
AccuracyºC ºF
Thermo-couple
K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to1200.0ºC -300.0to2300.0ºF
T-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C
S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.
W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V4.00to20.00mA
DCvoltage/current
0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:Selectfrom100and200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω
•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC,thepowerfrequencycanbesetmanually. Automaticdetectionisalsoavailable. For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
AuxiliaryAnalogInput• Use:Remotesetpointsetting,externalcompensatinginput,auxiliaryinputforcom-
putation, etc.• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type Instrument Range Accuracy
Standardsignal0.400to2.000V ±0.2%ofinstrumentrange±1digit1.000to5.000V ±0.1%ofinstrumentrange±1digit
DCvoltage0.000to2.000V ±0.2%ofinstrumentrange±1digit0.00to10.00V ±0.1%ofinstrumentrange±1digit
DCvoltageforhigh-inputimpedance
0.000to1.250V ±0.1%ofinstrumentrange±1digit
• Inputsampling(control)period:Sameasuniversalinput• Inputresistance:About1MΩ However,10MΩormoreforDCvoltageforhigh-inputimpedancerange•Burnoutdetection:Functionsatstandardsignal Burnoutisdeterminedtohaveoccurredifitis0.1Vorless.
UniversalInput(Optionalsuffixcode:/U1)• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype,instrumentrange,andmeasurementaccuracy:Sameasthestandard-equippeduniversalinputexceptthetablebelow.
Input Type Instrument Range
Accuracy°C °F
4-wireRTD
JPt100-200.0to500.0°C -300.0to1000.0°F ±0.5°Cofinstrumentrange±1digit-150.00to150.00°C -200.0to300.0°F ±0.2°Cofinstrumentrange±1digit
Pt100-200.0to850.0°C -300.0to1560.0°F ±0.1%ofinstrumentrange±1digit
(Note1)-200.0to500.0°C -300.0to1000.0°F ±0.5°Cofinstrumentrange±1digit-150.00to150.00°C -200.0to300.0°F ±0.2°Cofinstrumentrange±1digit
Note1:±0.5°C±1digitintherangebetween-200.0and500.0°C/-300.0and1000.0°F.
• Inputsampling(control)period:Sameasthestandard-equippeduniversalinput.• Burnoutdetection:Sameasthestandard-equippeduniversalinput.
ContactInputSpecifications• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAormore.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Controlperiod+50ms• Use:PTNO.switch,operationmodeswitch,andeventinput
AnalogOutputSpecifications• Numberofoutputs: Controloutput:1 Cooling-sidecontroloutputofHeating/coolingtype:1• Outputtype:Currentoutputorvoltagepulseoutput• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless) Theaccuracy isthat inthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz.
• Voltagepulseoutput: Use:Timeproportionaloutput On-voltage:12Vormore/loadresistanceof600Ωormore Off-voltage:0.1VDCorless Timeresolution:10msor0.1%ofoutput,whicheverislarger
RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC looppower
supply• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof
transmission output itself.
15VDCLoopPowerSupplySpecifications(Sharedwithretransmissionoutput)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
StepResponseTimeSpecificationsWithin500ms(whenthecontrolperiodis100ms)Within1s(whenthecontrolperiodis200ms)(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)
RelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Controloutput:contactpoint1c;1point Cooling-sidecontroloutputofHeating/coolingtype:contactpoint1c;1point Eventoutput:contactpoint1a;3points(commonisindependent)• Contactrating: Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(eventoutput):240VAC,1Aor30VDC,1A(resistanceload)• Use:Timeproportionaloutput,eventoutput,alarmoutput,FAILoutput,etc.• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislargerNote:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore. Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
TransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.100ms
TriacOutputSpecifications•Contacttypeandnumberofoutput:zerocross;1pointLoadvoltage:75to250VACAllowableloadcurrent:0.8Awhentheambienttemperatureis20°C,0.3Awhentheambienttemperatureis50°C.•Minimumloadcurrent:20mA(*)*: If there isa riskofsurgecurrent,connectacurrent-limiting reactor,acurrent-
limitingfuseorabreakerinseriestotheloadpowersupply.•Use:Timeproportionaloutput,Alarmoutput•Timeresolutionofcontroloutput:1/commercial frequency(s)or0.1%ofoutput,whicheverislarger.
PositionProportionalOutputSpecifications• Positionsignalinput: Slideresistance:100Ωto2.5kΩoftotalresistance 100%sideandslideline:withdisconnectiondetection 0%side:withoutdisconnectiondetection Currentinput:4to20mA(withdisconnectiondetection)• Samplingperiod:50ms• Measurementresolution:0.1%ofinputspan• Positionproportionalrelayoutput: Contactpoint1a;2points,250VAC,3Aor30VDC,3A(resistanceload)Note:Thisshouldalwaysbeusedwithaloadof10mAormore.
HeaterBreakAlarmSpecifications• Numberofinputs:2• Numberofoutputs:2(transistorcontactoutput)• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)andgeneratesaheaterbreakalarmwhenthemeasuredvalueis lessthanthebreakdetectionvalue.
• Currenttransformerinputresistance:About9.4Ω• Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeap-plied.)
• Heatercurrentsettingrange:OFF,0.1to300.0Arms Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms Note:TheCTratiocanbeset.CTratiosettingrange:1to3300• RecommendedCT:CTfromU.R.D.,Ltd. CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms• Heatercurrentmeasurementperiod:200ms• Heatercurrentmeasurementaccuracy:±5%ofcurrent transformer input rangespan±1digit(CTerrorisnotincluded.)
• Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)
IM 05P02C41-15EN page 3/14
24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
SafetyandEMCStandards• Safety: Compliantwith IEC/EN61010-1 (CE), IEC/EN61010-2-030 (CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.
Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofIEC/EN/CSA/
UL61010-1.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations), EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave
protection standard compliance
Construction,Installation,andWiring• Dust-proofanddrip-proof: IP66(for frontpanel) (Notavailable forside-by-sideclosemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm):96(W)×96(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeach forupperandlowermounting
• Panelcutoutdimensions(mm):92+0.8/0(W)×92+0.8/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:18VA(DC:9VA,AC:14VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC
• IsolationspecificationsPV (universal ) input terminals
Remote (universal) input terminals with direct input / Remote input terminals
Aux. analog (AIN2) input terminals
Control relay (contact point c)/Triac output terminals
PV event-1 relay (contact point a) output terminals
PV event-2 relay (contact point a) output terminals
PV event-3 relay (contact point a) output terminals
Position proportional relay output terminals
Contact input terminals (all)RS-485 communication terminals (2 ports)
Contact output (transistor) terminals
Ethernet communication terminal
PROFIBUS-DP/DeviceNet/CC-Link communication terminals
Current transformer input terminals
Control, retransmission (analog) output terminals(not isolated between the analog output terminals)Valve position (feedback) input terminals
Internalcircuits
Powersupply
The circuits divided by lines are insulated mutually.
Aux. analog (AIN4) input terminals
EnvironmentalConditions
NormalOperatingConditions:• Ambienttemperature:-10to50ºC(side-by-sideclosemounting:-10to40ºC) 0to50°CiftheCC-Linkoptionisspecified.(side-bysidemounting:0to40°C)• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections
• Short-periodvibration:14.7m/s2, 15 seconds or less• Shock:98m/s2 or less, 11 ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds
*:TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelowtemperature.However,thecontrol fuction is not affected.
TransportationandStorageConditions:• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.
• Be sure to turn OFF the power supply to the controller before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.
• As a safety measure, always install a circuit breaker (an IEC 60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm from other signal wires.
• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical Code:ANSI/NFPA-70)or thewiringconstructionstandards incountries or regions where wiring will be installed.
• For control relay output, alarm relay output, and power terminal connections, use heat-resistant cables.
• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)
This product
Functional insulation
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
CAUTION
• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.
• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.
CAUTION
• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.
• If there is a risk of external lightning surges, use a lightning arrester etc.• For TC input, use shielded compensating lead wires for wiring.
For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.
• Since the control output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended to use for the instrument.
RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
E4-terminal area
E3-terminal area E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101-112
501-512
401-412
301-312
201-212
ALM (Equipped as standard)Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)
PV event-2 output
PV event-3 output
PV event-1 output
Common
Common
Common
UP104
105
106
107
108
109
PVPV inputTC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equippedas standard)
202
203
201
202
203
202
203
203
204
Factory default: PV input type is undefined.
OUTCurrent/voltage pulse output
0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,4-20 mA DC
Control output (Suffix code: Output 1; -A or -U)
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
207
208
207
- 208
207
208
Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output.Current output range can be changed.In Position proportional type, can be used for retransmission output or 15 V DC loop power supply.
RETRetransmission output
4-20 mA DC or0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
Retransmission output (Optional suffix code /RT)
205
206
205
206
Can be used for 15 V DC loop power supply when not used for retransmission output.
VALV(Suffix code: Output 1=-P)
Position proportional control output
Resistance: 100 Ω to 2.5 kΩ
Feedback input100%
0%
Relay contact output
HIGH(direct)
LOW(reverse)
COM
Contact rating: 250 V AC, 3A 30 V DC, 3 A (resistance load)
507
508
509
510
511
512
-
Feedback inputCurrent (mA)input
When feedback input is current
510
511
512
+
HBA(Optional suffix code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1output
Heater break alarm-2output
Common
510
511
512
HAL1
HAL2
COM
UP507
508
509
112
(24 V AC/DC power supply: Optional suffix code /DC)
Power supply100-240 V AC power supply
N
L
Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
112 112
N
L
OUT(Suffix code: Output 1; -T)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
101
102
Triac output
103
NO
COM
Contact rating: 75 - 250 V ACAllowable load current: 0.8 A
OUT
(Suffix code:Output 1; -R or -U)
OUT2
Current/voltage pulse output
0-20 mA DC,4-20 mA DC,Voltage pulse (12V)
+
-
Retransmission output
+
-Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,4-20 mA DC
Cooling-side control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
511
512
507
508
509
511
512
511
512
507
508
Triac output
509
NO
COM
Contact rating: 75 - 250 V ACAllowable load current: 0.8 A
Triac
(Suffix code: Output 2; A or U)
(Suffix code: Output 2; R or U) (Suffix code: Output 2; T)
DI (Equipped as standard)Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COMCommon
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltagecontact
Transistor contactUP UP
209
210
211
212
209
210
211
212
Function can be changed.
Start of program operation when DI1 changes from OFF to ON.
Stop of program operation when DI2 changes from OFF to ON.
Start of local-mode operation when DI3 changes from OFF to ON.
Wiring direction
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal.• Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
UP55A
Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2
CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer
Power supply, relay contact outputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2isrecommended.Ifthecross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.
RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresEthernetcommunication 100BASE-TX(CAT-5)/10BASE-TPROFIBUS-DPcommunication DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)DeviceNetcommunication DedicatedcableforDeviceNet(Shieldedfive-wires)CC-Linkcommunication DedicatedcableforCC-Link(Shieldedthree-wires)
PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)DeviceNetConnector(wiringside)(Partnumber:L4502BW)Recommendedtighteningtorque:0.5to0.6N·m
External DC power supplyRelay
UP’s contactDiode(Mount it directlyto the relay coilterminal (socket).)
Relay(Use one with a relay coil rating
less than the UP’s contact rating.)
R
UP55A
DC Relay Wiring AC Relay Wiring
UP55A
R
UP’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)
External AC power supply
Relay(Use one with a relay coilrating less than the UP’s
contact rating.)
IM 05P02C41-15EN page 4/14
E1-Terminal Area301-306 E2-Terminal Area307-312
(Optional suffix code /X1)Contact inputExternal contact input
DI11
DI12
DI13
DI14
DI15
COMCommon
DI11
DI12
COM+5V
+5V
No-voltage contactTransistor contact
Contact rating: 12 V DC, 10 mA or more
DI13+5V
DI14+5V
DI15+5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP UP
301
302
303
304
305
306
301
302
303
304
305
306
Function can be assigned to the terminals with no function.
DI
Contact outputExternal contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
DO13
DO14
DO15
COMCommon
UP
(Optional suffix code /Y1)
PV event-4 output
PV event-5 output
PV event-6 output
PV event-7 output
PV event-8 output 301
302
303
304
305
306
Function can be assigned to the terminal with no function.
DO (Optional suffix code /U1)Universal input
TC input RTD input
Voltage (mV, V) input
+
-
+
-
Current (mA) input
+
-
4-wire
302
303
302
303
303
304
RSP
a
B
b
A 301
302
303
305
(Optional suffix code /R1)Remote input / Contact inputExternal contact input
DI16
COMCommon
DI16
COM+5V
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
UP UP
Start of remote-modeoperation when DI16switches from OFF to ON.
303
304
303
304
RSPRemote input
Default: 1-5 V DC
+
-
305
306
Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC
Contact outputExternal contact output
Transistor contact rating: 24 V DC, 50 mA
DO22
DO21
DO23
DO24
DO25
COMCommon
UP
(Optional suffix code /Y2)
307
308
309
310
311
312
Function can be changed.
DO
Time event-5 output
Time event-4 output
Time event-3 output
Time event-2 output
Time event-1 output
(Optional suffix code /W1)External contact output
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
COMCommon
UP
Contact input / Contact outputExternal contact input
DI11
DI12
COMCommon
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP
301
302
303
304
305
306
DI/DO
Function can be assigned to the terminals with no function.
DI11
DI12
COM+5V
+5V
UP
301
302
303
(Optional suffix code /X2)Contact inputExternal contact input
DI21
DI22
DI23
DI24
DI25
COMCommon
DI21
DI22
COM+5V
+5V
No-voltage contactTransistor contact
Contact rating: 12 V DC, 10 mA or more
DI23+5V
DI24+5V
DI25+5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP UP
307
308
309
310
311
312
307
308
309
310
311
312
Function can be assigned to the terminals with no function.
DI
(Optional suffix code /W2)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO22
DO21
COMCommon
UP
Contact input / Contact output
External contact input
DI21
DI22
COMCommon
DI21
DI22
COM+5V
+5V
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP UP
307
308
309
307
308
309
310
311
312
DI/DO
Function can be assigned to the terminals with no function.
(Optional suffix code /A2)Aux. analog input
Default: 1-5 V DC
+
-
Aux. analog input / Contact inputExternal contact input
DI26
COMCommon
DI26
COM+5V
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
UP UP
309
310
309
310
311
312
Function can be assigned to the terminals with no function.
AIN2
Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC
PV event-4 output
PV event-5 output
Time event-1 output
Time event-2 output
E3-Terminal Area401-412 E4-Terminal Area501-506
(Optional suffix code /ET3)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TXRJ45 connector
ColorLitUnlit
Amber100M bps10M bps
GreenLinkedActiveLink failure
ColorLitBlinkUnlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHR
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
(Optional suffix code /CH3)407
408
409
410
411
RS485
Contact inputExternal contact input
DI41
DI42
DI43
DI44
DI45
COMDI41
DI42
COM+5V
+5V
DI43+5V
DI44+5V
DI45+5V
UP UP
(Optional suffix code /X4)
CommonNo-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Bit-0 of program pattern number
Bit-1 of program pattern number
Bit-2 of program pattern number
Bit-3 of program pattern number
Bit-4 of program pattern number
501
502
503
504
505
506
501
502
503
504
505
506
Function can be changed.
DI
(Optional suffix code /X3)Contact inputExternal contact input
DI31
DI32
DI33
DI34
DI35
COMCommon
DI31
DI32
COM+5V
+5V
No-voltage contactTransistor contact
Contact rating: 12 V DC, 10 mA or more
DI33+5V
DI34+5V
DI35+5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP UP
407
408
409
410
411
412
407
408
409
410
411
412
DI
Function can be assigned to the terminals with no function.
Contact output (Optional suffix code /Y3)DOExternal contact output
DO32
DO31
DO33
DO34
DO35
COM
Time event-6 output
Time event-7 output
Time event-8 output
Time event-9 output
Time event-10 output
Common
UP407
408
409
410
411
412
Transistor contact rating: 24 V DC, 50 mA Function can be changed.
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
501
502
503
504
505
RS485(Optional suffix code /C4)
RS-485
RSB(+)
RSA(-)
SG
RS-485 communication/24 V DC loop power supply
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
-
501
502
503
505
506
RS485/LPS24(Optional suffix code /LC4)
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
-
24 V DC loop power supply
505
506
LPS24(Optional suffix code /L4)
Aux. analog input/Contact input(Optional suffix code /A4)
AIN4
Aux. analog input
Default: 1-5 V DC
+
-
External contact input
DI46
COMDI46
COM+5V
UP UPCommon
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
503
504
503
504
505
506
Function can be assigned to the terminals with no function.
Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC
(Optional suffix code /PD3)
PROFIBUS-DP communication (with Modbus master)
Pin1
2
Signal name DescriptionVP
RxD/TxD-P
3 RxD/TxD-N
4 DGND5 SHIELD
+5V bus powerData signal (positive data receive/transmit)Data signal (negative data recive/transmit)Signal groundShield ground
RS-485
RSB(+)
RSA(-)
SG
407
408
409
PROF
If the UP is located at the end of a segment for the PROFIBUS communication wiring, terminating resistors are separately needed.These are to be prepared by users. (390 Ω: 2 pcs. 220 Ω: 1 pc., or an active terminator.)
VP
RxD/TxD-PData line
Data line
390Ω
220Ω
390ΩRxD/TxD-N
DGND
LEDCHK(red)
RDY(green)
Lit Unlit
ERR(red)
User profile error
CHKRDYERR
12345
Normal
NormalNot connected, or communication failure (flashing)
Normal.Communicating successfully
No electricity, or communication failure
Contact outputExternal contact output
DO42
DO41
DO43
DO44
DO45
COM
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Common
UP
(Optional suffix code /Y4)
501
502
503
504
505
506
DO
Transistor contact rating: 24 V DC, 50 mA Function can be assigned to the terminals with no function.
(Optional suffix code /W4)
Contact input / Contact output DI/DO
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO42
DO41
COMCommon
UP
External contact input
DI41
DI42
COMCommon
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP
501
502
503
504
505
506
Function can be assigned to the terminals with no function.
DI41
DI42
COM+5V
+5V
UP
501
502
503
RS-485 communication / Aux. analog input / Contact input
(Optional suffix code /AC4)
External contact input
DI46
COMCommon
DI46
COM+5V
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
UP UP
Factory default: No function
503
504
503
504
AIN4/RS485 Aux. analog input
Default: 1-5 V DC
+
-
505
506
Specify within a range of 1-5 V DC, 0-2 V DC,0-10 V DC
RS-485
RSB(+)
RSA(-)
SG
501
502
503
Program pattern number 1 2 3 4 5 6 7 8 9 10 11 12DI41 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFFDI42 OFF ON ON OFF OFF ON ON OFF OFF ON ON OFFDI43 OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ONDI44 OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ONDI45 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
(Suffix code: Type 3=5, except Type 2=3)
DeviceNet communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
DNET
If the UP is located at the end of a segment for the DeviceNetcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (121 Ω: 1 pc.)
CAN_H
CAN_L
121Ω
LEDCHK(red)
RDY(green/
red)
Lit/flashing Unlit
User profile error Normal
Pin12
Signal name Description
CAN_H
CAN_L3
V+
4
V-5
DRAINRX/TX + signal
RX/TX - signalShield/Drain wire
DeviceNet power supply 24V
DeviceNet power supply common
Normal. Communicating successfully (green, lit).Not connected (green, flashing).Critical link failure (red, lit).Communication timeout (red, flashing)At power-on/Communication faulted (green/red, flashing)
No electricity
CHK
MNS
12345
(Suffix code: Type 3=3, except Type 2=3)
CC-Link communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
CC-L
If the UP is located at the end of a segment for the CC-Linkcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)
DA
DB
110Ω
LEDCHK(red)
L ERR(red)
L RUN(green)
Lit Unlit
User profile error Normal
Normal
Pin12
Signal name Description
DA
DB
3 DG4
SLD
5
FG
RX/TX - signal
RX/TX + signal
Frame ground
TX/RX signal groundShield
Normal Communicating successfully
Communication failure (CRC error)
No carrier detected/Connection timeout
CHK
L RUNL ERR
12345
Function can be assigned to the terminals with no function.
(Optional suffix code /W3)Contact input / Contact output
External contact input
DI31
DI32
COMCommon
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP
407
408
409
DI/DO
DI31
DI32
COM+5V
+5V
UP
407
408
409
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO32
DO31
COMCommon
UP410
411
412
Time event-6 output
Time event-7 output
A program pattern is selected with the combination of ON and OFF of a contact input.In the case of a pattern 5, ON (1) of "DI45 to DI41" and OFF (0) is represented as a binary number "00101": it is "5" decimally.The pattern 13 or later can be selected similarly.
Bit-0 of program pattern number
Bit-1 of program pattern number
E4-terminal area
E3-terminal area
E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101-112
501-512
401-412
301-312
201-212
112
UP55A(Continuedfrompage3) [ Operations 13. Troubleshooting ] n Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.
PV display (Operation
Display)
Setpoint display(Operation Display)
Status indicator(Operation Display)
Parameter that displays error details Error description Cause and diagnosis Remedy
Indication off Indication off — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty. Contactusforrepair.
ERR
SYS-----
—
— System data error System data is corrupted. Faulty. Contactusforrepair.
PAR0004 (foruserdefaultvalueerroronly)
Setupparameter(PA.ER)
User(parameter)defaultvalueerror
Userparameteriscorrupted.Initializedtofactorydefaultvalue.
Checkandreconfiguretheinitializedsettingparameters.Errorindicationiserased when the power is turned on again.
PAR0010(forsetupparametererroronly) Setup parameter error Setup parameter data is corrupted.
Initializedtouserdefaultvalue.
PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.
Initializedtouserdefaultvalue.
PAR0040(forprogrampatternerroronly) Programpatternerror Programpatterndataiscorrupted.
Allprogrampatternsaredeleted.
SLOT0017(0017:ErroroccurstoallhardwareofE1toE4-terminalareas.)
Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E1toE4-terminalareas)
Inconsistence of system data and hardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1toE4-terminalareas).
Faulty.Contactusforrepair.
Normalindication Normalindication
RightmostdecimalpointonPVdisplayblinks.
Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause
ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint
onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.
Normalindication Normalindication LADDERlampblinks Setupparameter(LA.ER) Corruptedladderprogram Ladderprogramiscorrupted.
Operateswithoutladderprogram. Downloadtheladderprogramagain.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.
[ Operations 13. Troubleshooting ] n Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.
PV display (Operation
Display)
Setpoint display(Operation Display)
Status indicator(Operation Display)
Parameter that displayserror details Error description Cause and diagnosis Remedy
AD.ERR Normalindication(Note) — Setupparameter(AD1.E)
AnaloginputterminalADCerror•PVinput•RSPinput(E1-terminalarea)•AIN2input(E2-terminalarea)•AIN4input(E4-terminalarea)
AnaloginputterminalADvalueerror Faulty.Contactusforrepair.
RJC.E(DisplaysRJC.EandPValternately.)
Normalindication(Note) — Setupparameter(AD1.E)UniversalinputterminalRJCerror•PVinput•RSPinput(E1-terminalarea)
UniversalinputterminalRJCerror
Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.
B.OUT Normalindication(Note) —
Setupparameter(AD1.E)
Analoginputterminalburnouterror•PVinput•RSPinput(E1-terminalarea)•AIN2input(E2-terminalarea)•AIN4input(E4-terminalarea)
AnaloginputterminalsensorburnoutCheckwiringandsensor.Errorindicationiserasedinnormaloperation.
Setupparameter(PV1.E/PV2.E) PVinputburnouterror(Loop1,Loop2) BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.
OVER-OVER
Normalindication — Setupparameter(PV1.E/PV2.E)
PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)(Loop1,Loop2)
PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.
Checkanaloginputvalueorladderprogram.
Normalindication Normalindication — Setupparameter(PV1.E) RSPinputburnouterror(Loop1) BurnoutofanaloginputconnectedtoRSP Checkwiringandsensor.Error
indication is erased in normal operation.Normalindication RSPB.OUT — Setupparameter(PV1.E) BurnouterrorwhenRSPinputis
usedforcontrol(Loop1)BurnoutofanaloginputconnectedtoRSPwhenRSPisusedforcontrolcomputation
Checkwiringandsensor.Errorindication is erased in normal operation.
Normalindication OUT----- — Setupparameter(AD2.E) Feedbackinputresistor/current
burnout FeedbackinputburnoutCheckwiringoffeedbackinputresistor/current.Errorindicationiserasedinnormal operation.
Normalindication
Normalindication LADDERlampblinks Setupparameter(LA.ER)
Laddercalculationoverflow Floatingpointcomputationforladdercalculationisinfinite. Checktheladderprogram.
Loadfactorover100%
Computationdoesnotendwithinthecontrolperiod.(Whentheloadfactoris100%ormore,andthecomputationdoesnotendwithinthecontrolperiod.)
Changethecontrolperiodorreducethenumberofstepsfortheladderprogram.
Loadfactorover200%(Forcedend)
Computationdoesnotendwithinthecontrolperiod(loadfactoris200%ormore).
Changethecontrolperiodorreducethenumberofstepsfortheladderprogram.
Ladderprogramerror Ladderprogramiscorrupted.Downloadtheladderprogramagain.Ifthe error indication is still not erased, thereisafault.Contactusforrepair.
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Peer-to-peercommunicationerror Peer-to-peercommunicationerrorCheckthatthetargetdevicesareconnected correctly.Recoveryatnormalreceipt.
AT.E Normalindication — Setupparameter(PV1.E/PV2.E) Auto-tuningtime-out(Loop1,Loop2)
Auto-tuningdoesnotendevenwhen24hourshaveelapsedafterthestartoftuning.
Checktheprocess.Holddownanykeytoerase the error indication
VAT.E Normalindication — Setupparameter(AD2.E) Valvepositionautomaticadjustmenterror
Fully-closedvalvepositionisequaltoorlargerthanthefully-openvalvepositionafterautomaticvalvepositionadjustmentisperformed.
Checkwiringandvalve.Holddownanykey to erase the error indication.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Communicationerror(RS-485communication)
FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.
Normalindication Normalindication Rightmostdecimalpointon
Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.
Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.
Note:WhenanerroroccursininputshowninAnaloginputdisplay(Operationdisplay),SetpointdisplayshowsthesamesymbolasthePVdisplay.
IM 05P02C41-15EN page 5/14
Contents1. NamesandFunctionsofDisplayParts2. Setup Procedure3. QuickSettingFunction(SettingofInputandOutput)4. AdjustingValvePositionAutomatically(foraPositionProportionalTypeControllerOnly)5. SettingAlarmType6. SettingAlarmSetpoint
1. Names and Functions of Display Parts
(2) + (3) + (4) : Setpoint display
(1)(9)
(2)
(10)
(11)
(12)
(13)
(4)(3)
(5)
(6)
(7)
(8)
No.infigure Name Description
(1) PVdisplay (whiteorred)
DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.
(2)Groupdisplay(patternnumber) (green)
1to30representpatternnumbersintheOperationDisplay.Displaysagroupnumber(1to8orR)andterminalarea(E1toE4)intheParameterSettingDisplay.
(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.
(5)Bar-graphdisplay(event,alarm) (orange)
DisplaystheeventstatusandthesegmentpositionintheOperationDisplay.(Defaultvalues:Timeeventstatus,Alarmstatus)Displayscontroloutputvalue(OUT)andmeasuredinputvalue(PV).Thedatatobedisplayedcanbesetbytheparameter.
(6) Eventindicator (orange)
LitwhenthePVeventsoccur.Eventdisplayscanbesetbytheparameter.
(7) Keynavigationindica-tor(green)
LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.
(8) Parameterdisplaylevelindicator(green)
Displaysthesettingconditionsoftheparameterdisplaylevelfunction.
Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit
(9) Programmonitor(green)
Displaysthestatusofincrement,constancy,anddecrementoftheprogramsetpoint.
:Litwhenaprogramsetpointisincreasing.:Litwhenaprogramsetpointisconstant.
:Litwhenaprogramsetpointisdecreasing.
(10) Status indicator (greenandred)
Displaystheoperatingconditionsandcontrolstatus.
Indicator Description HLD Litwheninholdmode(HLD).CAS Litwhenincascademode(CAS).
PRGLitwheninprogramoperationmode(PRG).LitwhiletheStartingtimeofprogramoperation(S.TM)isavailable.
RST Litwheninresetmode(RST).
MAN Litwheninmanualmode(MAN).Blinksduringauto-tuning.
(11) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.
(12) Ladderoperationindicator(green)
Litwhiletheladderprogramoperationisexecuted.
(13)Loop2indicator (LP2lamp)(green)
LitwhenthecontrolmodeisCascadecontrol.IntheOperationDisplay,theLP2lampislitwhiletheLoop-2datais displayed on Setpoint display.IntheParameterSettingDisplay,theLP2lampindicatestheloopofdisplayedmenusymbolorparametersymbol.TheLP2lampislitwhiletheLoop-2menusymbolorparametersymbolisdisplayed.
(4)
(5)
(1)(2)
(3)
No.infigure Name Description
(1) DISPLAYkey
UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedOperationDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.
(2) PARAMETERkey
Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).
(3)SET/ENTERkeyUp/Down/Left/Rightarrow keys
SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthe setpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/Down/Left/RightarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode (setpointisblinking)tomovebetweendigitsaccordingtotheparameter.
(4) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.
(5)
RUNkeyRSTkeyMODEkeyPTNkey
RUNkey:PresstheRUNkeyfor1secondwhileanoperationdisplayisshownstartstheprogrampatternoperation.
RSTkey:PresstheRSTkeyfor1secondwhileanoperationdisplayisshownstopstheprogrampatternoperation.
MODEkey:PresentsadisplayforswitchingbetweentheHOLD,ADVANCE,PROG,RESET,LOCAL,REMOTEandAUTO/MAN.Inordertochangetheoperationmode,presstheSET/ENTERkeywhilethesetpointisblinking.
PTNkey:Aprogrampatternnumbercanbeselectedduringtheoperationexcepttheprogrampatternoperation.(TheprogrampatternnumberdisplayedontheGroupdisplayblinks.)WhenthePTNkeyispressedwhiletheprogrampatternnumberisblinking,theblinkingstops.
Userscanassignfunctionstothekeyusingparameters.
Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareison the top of the unit.
2. Setup ProcedureThefollowingflowchartshowsthesetupprocedureforUP55A.
Install and wire a controller.
Monitoring and control of regular operations
Adjust PID using auto-tuning or manually for PID control.
Other setup
Operation
NO
NO NO
YES
YES YES
Control mode: Single-loop control only
Set the other parameters as needed.
Programming Set the program pattern.
PID tuning
Input setup
Output setup
Installationand wiring
Power ON
Control mode setup
Control type setup
Control type setupInput/output setup
Valve positionadjustment
UseQuick setting
function?
Positionproportional
type?
Positionproportional
type?
For Position proportional type
3. Quick Setting Function (Setting of Input and Output)TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionofthecontrol-ler.TurnonthecontrollertostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysetthecontroltype,input,andoutput,andquicklystart the control action.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Controltype(PIDcontrol,Heating/coolingcontrol,etc.)(2)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)(3)Outputfunction(controloutputtypeandcycletime)
Afterturningonthecontroller,firstdecidewhetherornottousetheQuicksettingfunc-tion.TheQuicksettingfunctioncanbeusedonlywhenthecontrolmodeisSingle-loopcontrol.Forothercontrolmodes,set thefunctionswithoutusingtheQuicksettingfunction.
Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.
OperationGuide
Initial Settings
This operation guide describes basic settings and operations of the UP55A.For details of each function, see User’s Manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the MODE key.
UP55AProgram Controller (Detailed code model)
Operation Guide for Single-loop Control
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-TERkeytoregisterthesetting.
Making Settings Using Quick Setting FunctionExample: Setting toPIDcontrol, thermocouple typeK (rangeof 0.0 to
500.00C), and current control outputFor thedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextpage.
(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)Setthecontroltypeparameter(CNT)toPID(PIDcontrol).(3)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.00C).(4)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).(5)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(6)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(7)Settheoutputtypeselectionparameter(OT)toOUTterminals(current).(8)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto
completethesetup.OperationDisplayappears.
FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeMODEkey.
First, the control type parameter (CNT) is displayed.Initial value: PID (PID control)H/C (Heating/cooling control) for Heating/cooling type unit.
The PV input type parameter (IN) is displayed.Initial value: OFF
OFF blinks.Blinking allows you to change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)
Press the SET/ENTER key while YES is displayed to start the Quick setting. Select NO with the Down
arrow key and press the SET/ENTER key.
Select NO to return to the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
Displays the measured input value (PV).Displays the starting target setpoint (SSP).
Follow the same procedure to set RL to 0.0 and OT to 00.02.Set other parameters as needed.
Quick setting starts
Power-on
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
12.
7.
[YES]
Operation Display
[NO]
First, the control type parameter (CNT) is displayed.Initial value: PID (PID control)H/C (Heating/cooling control) for Heating/cooling type unit.
The PV input type parameter (IN) is displayed.Initial value: OFF
OFF blinks.Blinking allows you to change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)
Press the SET/ENTER key while YES is displayed to start the Quick setting. Select NO with the Down
arrow key and press the SET/ENTER key.
Select NO to return to the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
Displays the measured input value (PV).Displays the starting target setpoint (SSP).
Follow the same procedure to set RL to 0.0 and OT to 00.02.Set other parameters as needed.
Quick setting starts
Power-on
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
12.
7.
[YES]
Operation Display
[NO]
IM 05P02C41-15EN page 6/14
Parameterstobeset
Control TypeParameter Symbol Name of Parameter Setting Range
CNT Controltype
PID:PIDcontrolONOF:ON/OFFcontrol(1pointofhysteresis)ONOF2:ON/OFFcontrol(2pointsofhysteresis)H/C:Heating/coolingcontrol
Note: Somesetpointsmaynotbedisplayeddependingonthemodelandsuffixcodes.
Input FunctionParameter Symbol Name of Parameter Setting Range
IN PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.00to150.000C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
RH MaximumvalueofPVinputrange
Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
RL MinimumvalueofPVinputrange
SDPPVinputscaledecimal point position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces
3:Threedecimalplaces4:Fourdecimalplaces
SH MaximumvalueofPVinputscale
-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof
PVinputscale
Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988
Output FunctionParameter Symbol Name of Parameter Setting Range
OT
Outputtypeselection
Upper two digitsLower two digits
ControloutputorHeating-sidecontroloutput(Lowertwodigits)00:OFF01:OUTterminals(voltage
pulse)02:OUTterminals(current)03:OUTterminals(relay/
triac)04:OUT2terminals(voltage
pulse)05:OUT2terminals(current)06:OUT2terminals(relay/triac)
Cooling-sidecontroloutput(Uppertwodigits)
00:OFF01:OUTterminals(voltage
pulse)02:OUTterminals(current)03:OUTterminals(relay/
triac)04:OUT2terminals(voltage
pulse)05:OUT2terminals(current)06:OUT2terminals(relay/triac)
CT
ControloutputcycletimeHeating-sidecontroloutput cycle time (inHeating/coolingcontrol)
0.5to1000.0s
CTc Cooling-sidecontroloutput cycle time
4. Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)Thefollowingoperatingproceduredescribeshowtoinputfeedbacksignalsfromthecontrolvalveandadjustthefully-openandfully-closedpositionsofthecontrolvalveautomatically.Thefully-openandfully-closedpositionsofthevalvecanbeadjustedautomaticallybyinputtingfeedbacksignalsfromthevalve.Toadjustthevalveposi-tion,youneedtocarryouttheconnectionandbringthecontrollerintomanualmode.Fortheconnection,see“6.TerminalWiringDiagrams” in"InstallationandWiring",andfor themanualmode,see“5.SwitchingbetweenAUTOandMAN” in"Opera-tions."Theautomaticadjustmentcanbedone inprogrampatternoperation, localoperation, and remote operation.
CTL menu is displayed.
+
OUT menu is displayed.
OFF blinks.
1.
2.
3.
4.
5.
6.
7.
Show the Operation Display.
MAN is lit
* When a password is set, PASS is displayed. If the correct password is not entered, setup parameters cannot be changed.
Hold down the keys for 3 seconds.
Press the Right arrow key until OUT menu appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter V.AT (automatic valve position adjustment) is displayed.
Press the Up arrow key.
ON is displayed.Blinks during the change.
ON has been registered and the automatic adjustment of the valve position starts.V.AT blinks during the automatic adjustment. After the adjustment is completed, press the DISPLAY key or DISP key once to return to the Operation Display.
When the adjustment is completed normally, the indication automatically returns to OFF. When VAT.E appears on PV display, it indicates an error. Check the wiring for feedback input and perform the automatic
adjustment again. To perform a valve adjustment manually, see User’s Manual.
5. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhigh limitalarm) toPV low limitalarm(setpoint:02). (Thesealarmsworkirrespectiveoftheoperationmode.)
MODE menu is displayed.
ALRM menu is displayed.
1.
2.
3.
4.
5.
6.
Symbol
Show the Operation Display.
Hold down the key for 3 seconds.
Press the Right arrow key until ALRM menu appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter AL1 (alarm-1 type) is displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The alarm-1 type setpoint 02 (PV low limit) is registered.After the setup is completed, press the DISPLAY key once to return to the Operation Display.Stand-by actionEnergized/De-energizedLatch action
To change the alarm type, change the last 2 digits of the 5-digit value.
Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”)
For the latch action, see User ’s Manual.
Press the Up/Down arrow keys to display the parameter needs to be changed.
MODE menu is displayed.
ALRM menu is displayed.
1.
2.
3.
4.
5.
6.
Symbol
Show the Operation Display.
Hold down the key for 3 seconds.
Press the Right arrow key until ALRM menu appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter AL1 (alarm-1 type) is displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The alarm-1 type setpoint 02 (PV low limit) is registered.After the setup is completed, press the DISPLAY key once to return to the Operation Display.Stand-by actionEnergized/De-energizedLatch action
To change the alarm type, change the last 2 digits of the 5-digit value.
Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”)
For the latch action, see User ’s Manual.
Press the Up/Down arrow keys to display the parameter needs to be changed.
フィード バック入 力 上 限
フィード バック入 力 下 限
P V 変 化 率 警 報
自 己 診 断 警 報
Hysteresis
Alarm setpoint PV, RSP, AIN2 or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation setpoint
PV
Hysteresis Hysteresis
Open (unlit)
Closed (lit)
SP or Target SPPVDeviation setpoint
Hysteresis
- -
SP or Target SP
PV
Hysteresis Hysteresis
Deviation setpoint
Open (unlit)
SP or Target SP
Alarm setpoint
Hysteresis
SP or Target SP
Hysteresis
Alarm setpoint
Alarm setpointOutput
Hysteresis
Closed(lit)
Hysteresis
Alarm setpoint Output
Alarm setpoint
Hysteresis
PV, RSP, AIN2 or AIN4
Hysteresis
Alarm setpoint PV, RSP, AIN2 or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation setpoint
PV
Hysteresis Hysteresis
SP or Target SPPVDeviation setpoint
Hysteresis
SP or Target SP
PV
Hysteresis Hysteresis
Deviation setpoint
Closed (unlit)
SP or Target SP
Alarm setpoint
Hysteresis
SP or Target SP
Hysteresis
Alarm setpoint
Alarm setpoint
Hysteresis
PV, RSP, AIN2 or AIN4
Alarm setpointOutput
Hysteresis
Hysteresis
Alarm setpoint Output
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm typeWithout (0) or With (1) Stand-by action
Latch action (0/1/2/3/4)See User’s Manual.
PV low limit alarm setpoint
Treatedas normal
ºC
Power-on Time
The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.
Normal Abnormal
The alarm outputturns on.
No alarm (00)
Alarm Action (De-energized)
PV high limit (01)Analog input PV high limit (19)Analog input RSP high limit (21)Analog input AIN2 high limit (23)Analog input AIN4 high limit (25)
PV low limit (02)Analog input PV low limit (20)Analog input RSP low limit (22)Analog input AIN2 low limit (24)Analog input AIN4 low limit (26)
SP high limit (03)Target SP high limit (09)
SP low limit (04)Target SP low limit (10)
Deviation high limit (05)Target SP deviation high limit (11)
Deviation low limit (06)Target SP deviation low limit (12)
Deviation high and low limits (07)Target SP deviation high and low limits (13)
Deviation within high and low limits (08) Target SP deviation within high and low limits (14)
Control output high limit (15)Cooling-side control output high limit (17)
Control output low limit (16)Cooling-side control output low limit (18)
Feedback input high limit (27)
Feedback input low limit (28)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Open (unlit)
Open (unlit)
Open (lit)
Closed (lit)
Open (unlit)
Open (lit)
Closed (unlit)
Closed (unlit)
Open (lit)
Closed (unlit)
Closed (unlit)
Open (lit)
Open (lit)Closed
(lit)Closed
(lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Burnout of PV input, RSP remote input, or AIN2/AIN4 auxiliary analog input. ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.Note 2: Positive setpoint, Negative setpoint
フィード バック入 力 上 限
フィード バック入 力 下 限
P V 変 化 率 警 報
自 己 診 断 警 報
Hysteresis
Alarm setpoint PV, RSP, AIN2 or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation setpoint
PV
Hysteresis Hysteresis
Open (unlit)
Closed (lit)
SP or Target SPPVDeviation setpoint
Hysteresis
- -
SP or Target SP
PV
Hysteresis Hysteresis
Deviation setpoint
Open (unlit)
SP or Target SP
Alarm setpoint
Hysteresis
SP or Target SP
Hysteresis
Alarm setpoint
Alarm setpointOutput
Hysteresis
Closed(lit)
Hysteresis
Alarm setpoint Output
Alarm setpoint
Hysteresis
PV, RSP, AIN2 or AIN4
Hysteresis
Alarm setpoint PV, RSP, AIN2 or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation setpoint
PV
Hysteresis Hysteresis
SP or Target SPPVDeviation setpoint
Hysteresis
SP or Target SP
PV
Hysteresis Hysteresis
Deviation setpoint
Closed (unlit)
SP or Target SP
Alarm setpoint
Hysteresis
SP or Target SP
Hysteresis
Alarm setpoint
Alarm setpoint
Hysteresis
PV, RSP, AIN2 or AIN4
Alarm setpointOutput
Hysteresis
Hysteresis
Alarm setpoint Output
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm typeWithout (0) or With (1) Stand-by action
Latch action (0/1/2/3/4)See User’s Manual.
PV low limit alarm setpoint
Treatedas normal
ºC
Power-on Time
The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.
Normal Abnormal
The alarm outputturns on.
No alarm (00)
Alarm Action (De-energized)
PV high limit (01)Analog input PV high limit (19)Analog input RSP high limit (21)Analog input AIN2 high limit (23)Analog input AIN4 high limit (25)
PV low limit (02)Analog input PV low limit (20)Analog input RSP low limit (22)Analog input AIN2 low limit (24)Analog input AIN4 low limit (26)
SP high limit (03)Target SP high limit (09)
SP low limit (04)Target SP low limit (10)
Deviation high limit (05)Target SP deviation high limit (11)
Deviation low limit (06)Target SP deviation low limit (12)
Deviation high and low limits (07)Target SP deviation high and low limits (13)
Deviation within high and low limits (08) Target SP deviation within high and low limits (14)
Control output high limit (15)Cooling-side control output high limit (17)
Control output low limit (16)Cooling-side control output low limit (18)
Feedback input high limit (27)
Feedback input low limit (28)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Open (unlit)
Open (unlit)
Open (lit)
Closed (lit)
Open (unlit)
Open (lit)
Closed (unlit)
Closed (unlit)
Open (lit)
Closed (unlit)
Closed (unlit)
Open (lit)
Open (lit)Closed
(lit)Closed
(lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Closed (lit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (unlit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Open (lit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Closed (unlit)
Burnout of PV input, RSP remote input, or AIN2/AIN4 auxiliary analog input. ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.Note 2: Positive setpoint, Negative setpoint
NotethattheSPinreset-modeisSSP(Startingtargetsetpoint).
6. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointto180.0.(Thesealarmsworkirrespectiveoftheoperationmode.)Beforesettingthealarmsetpoint,checkthealarmtype.Tochangethealarmtype,see“5.SettingAlarmType.”
Display the parameter that need to be changed.
Blinks during the change.
1.2.
3.
4.
5.
6.
Show the Operation Display.
Display MODE menu with the same procedure as described in Setting Alarm Type.
Press the Right arrow key.
AL menu is displayed.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.
Each parameter can be changed in the Parameter Setting Displays of alarms using arrow keys.Up/Down arrow keys: changing parameters
The setpoint has been registered.After the setup is completed, press the DISPLAY key once to return to the Operation Display.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Initializing parameter valuesParametersthatyouhavechangedcanbeinitializedtofactorydefaultvaluesoruserdefaultvalues.Fordetails,see“ParameterInitialization”intheUser’sManual.
Changing the parameter display levelsThisoperationguidedoesnotexplainalltheparameters.Todisplayalltheparam-eters,youneedtochangetheparameterdisplayleveltoprofessionalsettingmode.Fordetails,see“SettingSecurityFunctions”intheUser’sManual.
IM 05P02C41-15EN page 7/14
Contents1. OverviewofProgramPatterns2. CreatingProgramPatterns3. ProgramPatternSetupCharts
1. Overview of Program PatternsTheprogrammingexamplegivenheredemonstrateshowtodothetasksoutlinedbelow.1) Program the controller to start program operation at 50.0°C and raise the
temperature up to 100.0°C in 50 minutes.2) When the temperature reaches 100.0°C, keep it at this level for 30 minutes.3) Raise the temperature up to 200.0°C in 60 minutes.4) When the temperature reaches 200.0°C, keep it at this level for 30 minutes.5) Lower the temperature to 50.0°C in 50 minutes.6) When the temperature reaches 50.0°C, keep it at this level for 30 minutes.
PVinputrangesarefollowing:MaximumvalueofPVinputrange:250.0°CMinimumvalueofPVinputrange:0.0°CPVinputunit:C
ZonePIDselection(ZON):SegmentPIDselection(0)Segmentsettingmethod(SEG.T):Segmenttimesetting(TIME)Programtimeunit(TMU):hour.minute(HH.MM)
Seg.1 Seg.2 Seg.3 Seg.4 Seg.5 Seg.6
321
PV event 1
Segment timeTIME
Segment PID numberS.PIDN
100.0ºC
50.0ºC
200.0ºC
Time event 1
Time event 2
4 5 6
60 min.30 min.50 min. 30 min. 50 min. 30 min. Time
Setpoint
TSP
TSP
TSP
The display symbols of the parameters, TSP (Final target setpoint), TIME (Segment time setting), and S.PID (Segmet PID number selection) are the same in each segment. However, the segment can be recognized by the number displayed on the Symbol display.
TSP
SSP
TSP
Dev. high (5ºC) PV high (110ºC)
On
On On On
OnOff
Off Off Off
Off Off Off Off OffOn
Dev. high (5ºC) PV high (210ºC) Dev. low (5ºC) PV low (10ºC)
SeeUser'sManual for theWaitandRepeatactions,ZonePID,Startofprogramoperation(Startcode),Changingoperationmodeatsegmentswitching(Junctioncode),Localmode,andRemotemode.
OperationGuide
Programming
UP55AProgram Controller (Detailed code model)
Operation Guide for Single-loop Control
This operation guide describes basic program settings of the UP55A.For details of each function, see User’s Manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the MODE key. (The scrolling guide is OFF when displaying the Program parameter setting display first.)For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
2. Creating Program PatternsThefollowingoperatingproceduredescribesanexampleofcreating theprogramdiscussedin“1.OverviewofProgramPatterns.”
CAUTION
Note that the program patterns are all deleted if the settings change after creating program patterns.Be sure to check the PV input range, Program time unit (TMU), and Segment setting method (SEG.T) before creating.
PTNO.=1
SEGNO.=0
1.
2.
3.
4.
5.
Set the common parameter of the specified pattern.
When SEGNO.=0, set the common parameter for the pattern specified.When SEGNO.=1 to 99, set the parameter for the segment specified.
6.
7.
Starting target setpoint=50.0°C
STC=SSP (Starting target setpoint)8.
Segment 1
Set the final target setpoint.9.
10.
11.
Final target setpoint=100.0°C
Set the segment time.
Keep the initial value.
Pattern number
RST lamp is lit.
Hold down the keys for 3 seconds.
Show the Operation Display.
MODE menu is displayed.
PROG menu is displayed.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Press the Down arrow key.
Set the final target setpoint.Continues the TSP of segment 1.
12.
Set the segment PID number.Keep the initial value.
Keep the initial value.Set the junction code.
Segment time=50 minutes
13.
14.
15.
16.
Time event-2 starts from the Off state.
There is no the Off time.
Set the On time.
PV event-1 type=Deviation high limit
Set the PV event-1 type.
Set the PV event-1 setpoint.17.
18.
PV event-1 setpoint=5.0°C
25. Set the segment time.
19.
20.
21.
On time=25 minutes
22.
23.
24.
Segment 2
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the Up/Down arrow keys to move the parameters for segment-1 and the Left/Right arrow keys to move between each segmets.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TIM1 appears.)
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Time event-1 starts from the Off state.
Settings for the segment 3 to 6 can be done similarly. For programming and the settings for Wait and Repeat actions,
see User's Manual.
Set the junction code.In this case, the former segment is left unchanged.
PV event-1 type=PV high limit
Set the PV event-1 type.
26.
Segment time=30 minutes
Segment PID number=2
27.
29.
30.
Set the segment PID number.
Set the PV event-1 setpoint.32.
31.
28.
Start condition of time event 2=ON start
33.
PV event-1 setpoint=110.0°C
35. Set the time event 2.
34.
36.
37. Press the DISPLAY key once to return to the Operation Display.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key. (until TIM2 appears.)
Press the Down arrow key (until TIM1 appears.)
Change the Up/Down arrow keys to move the parameters for segment-1 and the Left/Right arrow keys to move between each segmets.
Press the Down arrow key.
Time event-1 starts from the Off state.
PTNO.=1
SEGNO.=0
1.
2.
3.
4.
5.
Set the common parameter of the specified pattern.
When SEGNO.=0, set the common parameter for the pattern specified.When SEGNO.=1 to 99, set the parameter for the segment specified.
6.
7.
Starting target setpoint=50.0°C
STC=SSP (Starting target setpoint)8.
Segment 1
Set the final target setpoint.9.
10.
11.
Final target setpoint=100.0°C
Set the segment time.
Keep the initial value.
Pattern number
RST lamp is lit.
Hold down the keys for 3 seconds.
Show the Operation Display.
MODE menu is displayed.
PROG menu is displayed.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Press the Down arrow key.
Set the final target setpoint.Continues the TSP of segment 1.
12.
Set the segment PID number.Keep the initial value.
Keep the initial value.Set the junction code.
Segment time=50 minutes
13.
14.
15.
16.
Time event-2 starts from the Off state.
There is no the Off time.
Set the On time.
PV event-1 type=Deviation high limit
Set the PV event-1 type.
Set the PV event-1 setpoint.17.
18.
PV event-1 setpoint=5.0°C
25. Set the segment time.
19.
20.
21.
On time=25 minutes
22.
23.
24.
Segment 2
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the Up/Down arrow keys to move the parameters for segment-1 and the Left/Right arrow keys to move between each segmets.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TIM1 appears.)
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Time event-1 starts from the Off state.
Settings for the segment 3 to 6 can be done similarly. For programming and the settings for Wait and Repeat actions,
see User's Manual.
Set the junction code.In this case, the former segment is left unchanged.
PV event-1 type=PV high limit
Set the PV event-1 type.
26.
Segment time=30 minutes
Segment PID number=2
27.
29.
30.
Set the segment PID number.
Set the PV event-1 setpoint.32.
31.
28.
Start condition of time event 2=ON start
33.
PV event-1 setpoint=110.0°C
35. Set the time event 2.
34.
36.
37. Press the DISPLAY key once to return to the Operation Display.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key. (until TIM2 appears.)
Press the Down arrow key (until TIM1 appears.)
Change the Up/Down arrow keys to move the parameters for segment-1 and the Left/Right arrow keys to move between each segmets.
Press the Down arrow key.
Time event-1 starts from the Off state.
PTNO.=1
SEGNO.=0
1.
2.
3.
4.
5.
Set the common parameter of the specified pattern.
When SEGNO.=0, set the common parameter for the pattern specified.When SEGNO.=1 to 99, set the parameter for the segment specified.
6.
7.
Starting target setpoint=50.0°C
STC=SSP (Starting target setpoint)8.
Segment 1
Set the final target setpoint.9.
10.
11.
Final target setpoint=100.0°C
Set the segment time.
Keep the initial value.
Pattern number
RST lamp is lit.
Hold down the keys for 3 seconds.
Show the Operation Display.
MODE menu is displayed.
PROG menu is displayed.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Press the Down arrow key.
Set the final target setpoint.Continues the TSP of segment 1.
12.
Set the segment PID number.Keep the initial value.
Keep the initial value.Set the junction code.
Segment time=50 minutes
13.
14.
15.
16.
Time event-2 starts from the Off state.
There is no the Off time.
Set the On time.
PV event-1 type=Deviation high limit
Set the PV event-1 type.
Set the PV event-1 setpoint.17.
18.
PV event-1 setpoint=5.0°C
25. Set the segment time.
19.
20.
21.
On time=25 minutes
22.
23.
24.
Segment 2
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the Up/Down arrow keys to move the parameters for segment-1 and the Left/Right arrow keys to move between each segmets.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TIM1 appears.)
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Time event-1 starts from the Off state.
Settings for the segment 3 to 6 can be done similarly. For programming and the settings for Wait and Repeat actions,
see User's Manual.
Set the junction code.In this case, the former segment is left unchanged.
PV event-1 type=PV high limit
Set the PV event-1 type.
26.
Segment time=30 minutes
Segment PID number=2
27.
29.
30.
Set the segment PID number.
Set the PV event-1 setpoint.32.
31.
28.
Start condition of time event 2=ON start
33.
PV event-1 setpoint=110.0°C
35. Set the time event 2.
34.
36.
37. Press the DISPLAY key once to return to the Operation Display.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key. (until TIM2 appears.)
Press the Down arrow key (until TIM1 appears.)
Change the Up/Down arrow keys to move the parameters for segment-1 and the Left/Right arrow keys to move between each segmets.
Press the Down arrow key.
Time event-1 starts from the Off state.
IM 05P02C41-15EN page 8/14
3. Program Pattern Setup ChartsYoucanregistermax.99programsegmentswiththeUP55Acontroller.Createasmany copies of the chart as necessary.
System name
ProgramNo.
Programname
Model
SerialNo.
Thefollowingparametersarenecessarytobesetbeforeprogrammings.Note that theprogram isdeleted ifTMUorSEG.T ischangedaftercreatingpro-grams.Forthesettingrange,see"Parameters."
< Setup Parameters >Parametersymbol Parameter name Usersettings
TMU Programtimeunit
SEG.T Segmentsettingmethod
ZON ZonePIDselection
PT2.G Programpattern-2retransmission
Thefollowingparametersarecommonparametersfortheprogrampatternspecified.Forthesettingrange,see"Parameters."
< Program Pattern Data (common parameter) >Parametersymbol Parameter name Usersettings
SSP Startingtargetsetpoint
SSP Startingtargetsetpoint(forprogrampattern-2retransmission)
STC Start code
WT.SW1 WaitfunctionON/OFF1
WZ.UP1 Upper-sidewaitzone1
WZ.LO1 Lower-sidewaitzone1
WT.TM1 Waittime1
WT.SW2 WaitfunctionON/OFF2
WZ.UP2 Upper-sidewaitzone2
WZ.LO2 Lower-sidewaitzone2
WT.TM2 Waittime2
WT.SW3 WaitfunctionON/OFF3
WZ.UP3 Upper-sidewaitzone3
WZ.LO3 Lower-sidewaitzone3
WT.TM3 Waittime3
WT.SW4 WaitfunctionON/OFF4
WZ.UP4 Upper-sidewaitzone4
WZ.LO4 Lower-sidewaitzone4
WT.TM4 Waittime4
WT.SW5 WaitfunctionON/OFF5
WZ.UP5 Upper-sidewaitzone5
WZ.LO5 Lower-sidewaitzone5
WT.TM5 Waittime5
R.CYCL Numberofrepeatcycles
R.STRT Repeatcyclestartsegmentnumber
R.END Repeatcycleendsegmentnumber
Error Indication at Program Pattern Creation and EditingErrorcode Errorinformation Causeoferror
ERR01Patterncreationoreditingisdisableduringprogramoperation.
Deletingorcopyingoftheprogrampattern,orinsertingordeletingofthesegmentwasexecutedduringprogramoperation.
ERR22 Segmentwriteerror Thetotalnumberofsegmentsexceeded300.
ERR23 Segmentinserterror Newsegmentcannotbeinsertedbecausethenumberofsegmentsinapatternexceeded99.
ERR32 Pattern source specificationerror Nopatternexistsinthesource.
ERR33 Pattern destination specificationerror Patternsalreadyexistinthedestination.
ERR41 Pattern delete error Thepatterntobedeleteddoesnotexist.
Excepttheaboveerrors,therearesomeerrorcodesincommunication.Fordetails,seeUser'sManual.
< Program Pattern Data (parameters for segments) >MaximumvalueofPVinputrange/MaximumvalueofPVinputscale ()
Unit()
Aprogrampatterncanbedrawnintherighttable.
MinimumvalueofPVinputrange/MinimumvalueofPVinputscale ()
Parameter symbol Parameter name
Segments1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TSP Finaltargetsetpoint
TSP FinaltargetsetpointforProgrampattern-2retransmission
TIME Segmenttimesetting
TM.RT Segmentramp-ratesetting
S.PID SegmentPIDnumberselection
JC Junction code
PV.TY1 PVevent-1type
PV.EV1 PVevent-1setpoint
PV.TY2 PVevent-2type
PV.EV2 PVevent-2setpoint
PV.TY3 PVevent-3type
PV.EV3 PVevent-3setpoint
PV.TY4 PVevent-4type
PV.EV4 PVevent-4setpoint
PV.TY5 PVevent-5type
PV.EV5 PVevent-5setpoint
PV.TY6 PVevent-6type
PV.EV6 PVevent-6setpoint
PV.TY7 PVevent-7type
PV.EV7 PVevent-7setpoint
PV.TY8 PVevent-8type
PV.EV8 PVevent-8setpoint
TME1 Startconditionoftimeevent1
T.ON1 Ontimeoftimeevent1
T.OF1 Offtimeoftimeevent1
TME2 Startconditionoftimeevent2
T.ON2 Ontimeoftimeevent2
T.OF2 Offtimeoftimeevent2
TME3 Startconditionoftimeevent3
T.ON3 Ontimeoftimeevent3
T.OF3 Offtimeoftimeevent3
TME4 Startconditionoftimeevent4
T.ON4 Ontimeoftimeevent4
T.OF4 Offtimeoftimeevent4
TME5 Startconditionoftimeevent5
T.ON5 Ontimeoftimeevent5
T.OF5 Offtimeoftimeevent5
TME6 Startconditionoftimeevent6
T.ON6 Ontimeoftimeevent6
T.OF6 Offtimeoftimeevent6
TME7 Startconditionoftimeevent7
T.ON7 Ontimeoftimeevent7
T.OF7 Offtimeoftimeevent7
TME8 Startconditionoftimeevent8
T.ON8 Ontimeoftimeevent8
T.OF8 Offtimeoftimeevent8
TME9 Startconditionoftimeevent9
T.ON9 Ontimeoftimeevent9
T.OF9 Offtimeoftimeevent9
TME10 Startconditionoftimeevent10
T.ON10 Ontimeoftimeevent10
T.OF10 Offtimeoftimeevent10
TME11 Startconditionoftimeevent11
T.ON11 Ontimeoftimeevent11
T.OF11 Offtimeoftimeevent11
TME12 Startconditionoftimeevent12
T.ON12 Ontimeoftimeevent12
T.OF12 Offtimeoftimeevent12
TME13 Startconditionoftimeevent13
T.ON13 Ontimeoftimeevent13
T.OF13 Offtimeoftimeevent13
TME14 Startconditionoftimeevent14
T.ON14 Ontimeoftimeevent14
T.OF14 Offtimeoftimeevent14
TME15 Startconditionoftimeevent15
T.ON15 Ontimeoftimeevent15
T.OF15 Offtimeoftimeevent15
TME16 Startconditionoftimeevent16
T.ON16 Ontimeoftimeevent16
T.OF16 Offtimeoftimeevent16
IM 05P02C41-15EN page 9/14
Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. Performing/CancelingAuto-tuning3. SelectingProgramPatternNumber(PT.No)4. SwitchingbetweenRUNandRESET5. SwitchingbetweenAUTOandMAN6. ManipulatingControlOutputinManualMode7. Enabling/DisablingHold-mode(HOLD)ofProgramOperation8. ChangingProgramSetpointswheninHold-mode(HOLD)9. Executing“Advance”(ADV)Function10.SwitchingtoLocal-mode(LOCAL)Operation11.ChangingSetpointsduringLocal-mode(LOCAL)Operation12.SwitchingtoRemote-mode(REMOTE)Operation13.Troubleshooting
1. Monitoring-purpose Operation Displays Available during Operation
Operation Display Switching Diagram
SP Display
TSP Display
Remaining Segment-time Display
Segment Number Display
Remaining Repetition Display
Program Pattern Display
OUT Display / Heating/cooling OUT Display
Displays the target setpoint (SP) on Setpoint display.Displays "SSP" during reset-mode.Displays "L.SP" during local-mode operation.Displays "R.SP" during remote-mode operation.
Displays the final target setpoint (TSP) on Setpoint display only during program operation.
Displays the remaining segment time (R.TIM) on Setpoint display during program operation.
Displays the segment number (SEG.N) for which operation is in progress, the number of segments included in the selected program pattern.
Displays the number of remaining repetitions (R.CYC) on Setpoint display. This display is displayed only when the repeat function is set and the operation mode is PROG.
Displays the program pattern (overview) on Setpoint display.Program pattern display can be scrolled using Up/Down/Left/Right arrow keys.Soak and ramp can be displayed.
Displays the measured input value on PV display.
Displays the control output value (OUT) on Setpoint display. Displays the control output values (C.H.) of heating and cooling sides on Setpoint display (C.H. can be changed in manual mode).
AftershowingtheProgramPatternDisplay,presstheDISPLAYkeytoshowthefol-lowingdisplaysconditionally.Fordetails,seeUser’sManual.
Standard, Position Proportional, and Heating/Cooling Types• SELECTDisplays1to5(whichappearwhenregistered)• AnalogInputDisplay(displayonly)(factorydefault:non-display)• PositionProportionalComputationOutputDisplay(displayonly)(factorydefault:non-display)
• PIDNumberDisplay(displayonly)(factorydefault:non-display)• Alarm-5to-8StatusDisplay(whichappearwhenregistered)• HeaterBreakAlarm-1CurrentDisplay(displayonly)(forheaterbreakalarmoptiononly)• HeaterBreakAlarm-2CurrentDisplay(displayonly)(forheaterbreakalarmoptiononly)
Event DisplayTimeevent(TME),PVevent(PVE)andalarm(AL)aredisplayedontheBar-graphdisplayandtheEventIndicator.(factorydefaultsetting)
PV event 1 to 8
Time event 1 to 16
Alarm 1 to 4
Operation Display Switching Diagram
*1: For another operation, when select ADV=ON and starts program operation. In this case, the segment is advanced.
(1) Press RUN key for 1 s.(2) Press RST key for 1 s.(3) Press MODE key, select HOLD=ON and press SET/ENT key.(4) Press MODE key, select HOLD=OFF and SET/ENT key.(5) Press MODE key, select LOC=ON and press SET/ENT key.(6) Press MODE key, select REM=ON and press SET/ENT key.
Reset Remote-mode operation
Local-mode operation
Program operation
Hold-mode operation
(*1)
(1)(1)
(2)
(2)
(2)
(2)
(3)
(1) (4)
(5)
(5)(5)
(5)
(6)
(6)(6)
(6)
(1)
2. Performing/Canceling Auto-tuningAuto-tuningshouldbeperformedaftersettingaprogrampattern.Makesurethatthecontrollerisinautomaticmode(AUTO)andinrunmode(RUN)beforeauto-tuning.Forsetting toAUTO,see “5.SwitchingbetweenAUTOandMAN,”andforsettingtoRUN,see“4.SwitchingbetweenRUNandRESET.”Ifthesetpointisknowninadvanceorauto-tuningdoesnotfindanyappropriatePIDconstants,setthePIDmanually.ForsettingthePIDmanually,seeUser’sManual.
CAUTION
Do not perform auto-tuning for the following processes.Tune PID manually.• Processes with fast response such as flow rate control and pres-
sure control.• Processes which do not allow the output to be turned on and off
even temporarily.• Processes which prohibit severe output changes at control
valves (or other actuators).• Processes in which product quality can be adversely affected if
PV values fluctuate beyond their allowable ranges.
1.2.
3.
4.
OFF blinks.
Blinks during the change.
The MAN lamp goes off, which means that the auto-tuning completed normally.
5.
6.
7.
8.
Show the Operation Display.
Hold down the PARAMETER key for 3 seconds to display MODE menu.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release of program operation) is displayed (during program operation.)
Press the Down arrow key until the parameter AT appears.
The parameter AT (auto-tuning switch) is displayed.
Press the Up/Down arrow keys to display the required setpoint.
The setting range is 1 to 8 (represent group numbers) or R.To perform auto-tuning for the PID of group 1, set the parameter AT to 1.To quit the auto-tuning, set the parameter to OFF.
The setpoint has been registered. This starts auto-tuning.The limiter can be set to the output during auto-tuning. For details, see User’s Manual.
During auto-tuning,• The MAN lamp blinks.• The OUT symbol appears.• The output values at 100.0% and 0%
appear alternately.
1.2.
3.
4.
OFF blinks.
Blinks during the change.
The MAN lamp goes off, which means that the auto-tuning completed normally.
5.
6.
7.
8.
Show the Operation Display.
Hold down the PARAMETER key for 3 seconds to display MODE menu.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release of program operation) is displayed (during program operation.)
Press the Down arrow key until the parameter AT appears.
The parameter AT (auto-tuning switch) is displayed.
Press the Up/Down arrow keys to display the required setpoint.
The setting range is 1 to 8 (represent group numbers) or R.To perform auto-tuning for the PID of group 1, set the parameter AT to 1.To quit the auto-tuning, set the parameter to OFF.
The setpoint has been registered. This starts auto-tuning.The limiter can be set to the output during auto-tuning. For details, see User’s Manual.
During auto-tuning,• The MAN lamp blinks.• The OUT symbol appears.• The output values at 100.0% and 0%
appear alternately.
3. Selecting Program Pattern Number (PT.No)Programpatternnumberselectioncanbeperformedusinganyofthefollowing:(1)key,(2)Parameter,(3)Contactinput,and(4)Communication.Thefollowingshowsanexampleofchangingtheprogrampatternnumber(PTNO.)to1usingthekey.ProgrampatternnumbercanbeselectedwhenthecontrollerisinaRESETmode.
1.2.
3.
4.
RST lamp is lit.
PTNO. has been changed to 1.
Blinks during the change.
Show the Operation Display.
Press the SET/ENTER key.
Press the PTN key.
Press the Up/Down arrow keys to display the required setpoint.
OperationGuide
This operation guide describes key entries for operating the UP55A.For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.”If you cannot remember how to carry out an operation during setting, press the DISPLAY key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the MODE key.
UP55AProgram Controller (Detailed code model)
Operation Guide for Single-loop ControlOperations
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
4. Switching between RUN and RESETRUNandRESETswitchingcanbeperformedusinganyofthefollowing:(1)key,(2)Contactinput,(3)Parameter,and(4)Communication.Thefollowingshowsanexampleofswitchingusingthekey.Fordetailsofotherswitchingmethodsandthedisplayappearingwhentheoperationisstarted,seeUser’sManual.Display in RUN mode
Starting target setpoint
RST lamp is lit.
Display in RESET mode
Current segment number and symbol (SP)
PRG lamp is lit.
Program setpoint
Press RUN key for 1 s.
Symbol SSP
The number of segments included in the selected program pattern.The segment number for which operation is in progress.
The figure below is displayed while the right arrow key is held down.
Press RST key for 1 s.
Whenthecontrollerisstopped,inputandoutputsareasfollows:PVinput DisplaysthePVvalue.Controloutput WhenthezonePIDselectionparameter(ZON)issettosegment
PIDselection,thepresetoutputvalueforthePIDgroupnumber1isoutput.WhenthezonePIDselectionparameter(ZON)issettootherthansegmentPIDselection,thepresetoutputvalueforthePIDgroupnumberforwhichzonecontrolisperformedisoutput.
Eventoutput Turnstheoutputoffincaseofanevent.Alarmoutput Turns the output on in case of an alarm.
5. Switching between AUTO and MANAUTOandMANswitchingcanbeperformedusinganyofthefollowing:(1)MODEkey,(2)Contactinput,(3)Contactinput,and(4)Communication.ThefollowingshowsanexampleofswitchingusingtheMODEkey.WhenAUTOandMANswitchingfunction isassignedtothecontact input,andthecontactinputisON,theswitchingbykeyoperationcannotbeperformed.Fordetails,seeUser’sManual.
Displays ”MODE MAN” in AUTO mode. Displays ”MODE AUTO” in MAN mode.
1.2.
3.
Press MODE key several times.
Show the Operation Display.
4.
MAN lamp is lit in MAN mode.
Press the SET/ENTER key.
WhenAUTOisswitchedintoMAN,thecontroloutputvalueinAUTOmodeisheld.Thecontrollercanbeoperatedmanuallyfromtheholdvalue.If themanualpresetoutput isset(MPONparameter≠OFF), thecontrollercanbeoperatedmanuallyfromthearbitraryoutputvalue(MPO1toMPO5parameters).
IM 05P02C41-15EN page 10/14
6. Manipulating Control Output in Manual Mode
NOTEInmanualmode,controloutput ismanipulatedbyoperatingthekeys(thevalue ischangedusingtheUp/Downarrowkeys,thenoutputtedasitis).Even if theSET/ENTERkey isnotpressed, thecontroloutputvaluechangesac-cordingtothedisplayedvalue.Instopmode(whentheRSTlampislit),controloutputcannotbemanipulated.
MAN lamp is lit.
Up arrow key: increases control output.Down arrow key: decreases control output.
In Position proportional control:Up arrow key; opens the valve.Down arrow key; closes the valve.Output; only while pressing a key. OUT; valve opening (0-100%)
Output manipulation in Position proportional control is not restricted from output limiters (OH, OL).
Manual operation in Heating/cooling control
Symbol of cooling side
Program pattern (PTNO.) number
Symbol of heating side
Heating-side control output
Cooling-side control output
Uparrowkey:concurrentlydecreasescooling-sidecontroloutputand increasesheating-sidecontroloutput.
Downarrowkey:concurrently increasescooling-sidecontroloutputanddecreasesheating-sidecontroloutput.
(Eithernoneof theheating-sideandcooling-sideoutputsarepresented,orbothofthemarepresentedaccordingtothedeadbandsetting.)
Actual output (%)
DB=24.8 Dead band: Operation parameter DB
Control computation output Control computation output
12.40-12.4
Manipulated output changewhen a dead band is positive (+)
Actual output (%)100
DB= -24.8
12.40-12.4
Manipulated output changewhen a dead band is negative (-)
100
Cooling-sidemanipulated output
Heating-sidemanipulated output
Heating-sidemanipulated output
Cooling-sidemanipulated output
7. Enabling/Disabling Hold Mode of Program OperationEnabling/disablingholdmodeofprogramoperationcanbeperformedduringpro-gramoperationusinganyofthefollowing:(1)MODEkey,(2)Parameter,(3)Contactinput,and(4)Communication.ThefollowingshowsanexampleofswitchingusingtheMODEkey.
1.2.
3.
4.
Show the Operation Display.
Press the MODE key.
The number of segments included in the selected program pattern.The segment number for which operation is in progress.
The figure below is displayed while the right arrow key hold down.
Displays ”HOLD ON” in PROG mode. Displays ”HOLD OFF” in HOLD mode.
HLD lamp is lit in HOLD mode.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release of program operation) is displayed (during program operation.)
1.2.
3.
4.
Show the Operation Display.
Press the MODE key.
The number of segments included in the selected program pattern.The segment number for which operation is in progress.
The figure below is displayed while the right arrow key hold down.
Displays ”HOLD ON” in PROG mode. Displays ”HOLD OFF” in HOLD mode.
HLD lamp is lit in HOLD mode.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release of program operation) is displayed (during program operation.)
Otheroperatingproceduresfordisablingtheholdmode:(1)PresstheRUNkeyfor1secondduringhold-modeoperation. In thiscase, the
controllerresumesprogramoperation.(2)Execute the“Advance“ functionduringhold-modeoperation. In thiscase, the
segmentisadvanced.
8. Changing Program Setpoints when in Hold ModeThefollowingoperatingprocedureschangesaprogramsetpointofsoaksegmentduringHold-modeoperation.Theprogramoperation isstartedwhenreleasing theHoldafterchangingthepro-gramsetpoint.
1.
2.
Set program operation in hold mode.
3.
4.
Blinks during the change.
Blinks during the change.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up/Down arrow keys to display the required setpoint.
9. Executing “Advance” Function“Advance”canbeperformedduringprogramoperationusinganyofthefollowing:(1)MODEkey,(2)Parameter,(3)Contactinput,and(4)Communication.ThefollowingshowsanexampleofswitchingusingtheMODEkey.Whenexecutingthe“Advance”functionduringhold-modeoperation,theholdmodeisdisabled.
1.2.
3.
4.
The segment is advanced.
Press the SET/ENTER key.
Show the Operation Display.
Press the MODE key.
The ADV (Advance of segment) is displayed (during program operation.)
10. Switching to Local-mode (LOCAL) OperationSwitchingtolocal-modecanbeperformedusinganyofthefollowing:(1)MODEkey(userfunctionkey),(2)Parameter,(3)Contactinput,and(4)Commu-nication.ThefollowingshowsanexampleofswitchingusingtheMODEkey.
1.2.
3.
4.
“LSP” is displayed when in local-mode operation.
Press the SET/ENTER key.
Show the Operation Display.
Press the MODE key several times.
The LOC (local operation) is displayed.
11. Changing Setpoints during Local-mode OperationThefollowingoperatingprocedureschangessetpointsduringlocal-modeoperation.
1.
2.
3.
4.
“LSP” is displayed when in local-mode operation.
Press the SET/ENTER key.
Press the SET/ENTER key.
Blinks during the change.
Blinks during the change.
Press the Up/Down arrow keys to display the required setpoint.
13. TroubleshootingRemedies if Power Failure Occurs
during Operations• Instantaneouspowerfailurewithin20ms. Apower failure isnotdetected.Normal
operation continues.• Powerfailureforlessthanabout5seconds,orforabout5secondsormore.
Affectsthe"settings"and"operationsta-tus."
Fordetails,seeUser'sManual.
NOTEWritedownthesettingsofparameters forarepairrequest.
FortheErrorsatPowerOnand the Errors during Op-eration, see “Installation” in this manual.
12. Switching to Remote-mode (REM) OperationSwitchingtoremote-modecanbeperformedusinganyofthefollowing:(1)MODEkey(userfunctionkey),(2)Parameter,(3)Contactinput,and(4)Commu-nication.ThefollowingshowsanexampleofswitchingusingtheMODEkey.
1.2.
3.
4.
“R.SP” is displayed when in remote-mode operation.
Press the SET/ENTER key.
Show the Operation Display.
Press the MODE key several times.
The REM (remote operation) is displayed.
TroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningonthecontroller’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
Is the controllerdefective?
Contact us for repair. Problem solved.
No communicationcapability
Completelyinactive?
Yes
Yes
Yes
No
No
No
Keyoperationfailure?
Yes
No
Yes
Check wiring of thepower terminals.
Check the key locksetting.
Displayfailure?
*Yes
No
Turn off power, andthen turn it on again.
I/O signalfailure?
Yes
No
Check the supply voltage.
Check the specifications and polarity
of connected devices .
Check the communication-related parameters.
Check the specificationsof communication
devices.
Check thecommunication wiring.
Communicationfailure?
No Withcommuni-
cation?
Yes
Yes
Normal?Is the
key locked?
Check the specificationsof the controller.
Yes
NoCorrect?
Correct the error(s).
Cancel the setting.
Check the I/O specificationsof the controller.
* The LCD (a liquid crystal display) is used for a display portion of this product. The LCD has a characteristic that the display action becomes late at the low temperature. Additionally, the luminance and contrast degradation are caused due to aged deterioration. However, the control function is not affected.
IM 05P02C41-15EN page 11/14
Operation Parameters / Program ParametersHolddownthePARAMETERkeyfor3secondstomovefromtheOperationDisplaytotheOperationParameterSettingDisplay.PresstheDISPLAYkeyoncetoreturntotheOperationDisplay.
Menu
DISPLAY
key key key
key key
The parameter groups can be switched using , keys.
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
PROG
PTNO.
SEGNO.
END
Menu END
END
Menu D isp lay and Parameter Setting Display are changed in a circular pattern.
Hold down PARAMETER key for 3 sec.
SET/ENTER key1 to 30
SET/ENTER key
SET/ENTER key
PARAMETER keyPARAMETER
key
PARAMETER key
0, 1 to 99
Parameter
ParameterEND
Move to the Setup Parameter Setting Display: Hold down the PARAMETER key and the Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodelandsuffixcodes,controlmode(CTLM),controltype(CNT),etc.The parameters for pro-fessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
Operation ModeMenusymbol: (MODE)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(HOLD)Pause/cancelreleaseofprogramoperation
Displayduringprogramoperation.ON:PauseOFF:Cancelrelease(Programopera-tionrestart)
OFF
EASY
(ADV)Advanceofsegment
Displayduringprogramoperation.Setas“ADV=ON”toadvancefromthecurrentsegmenttothenextsegment.
OFF
(MODE)Operationmode
RESET:StopofprogramoperationPROG:StartofprogramoperationLOCAL:Startoflocal-modeoperationREM:Startofremote-modeoperation
RESET
(A.M)AUTO/MANswitch AUTO:Automaticmode
MAN:Manualmode MAN
(PTNO.)Programpatternnumberselection
0:Notselectprogrampattern1to30 0
(SST)Start-of-programseg-mentnumber
1to99Thesettingvaluereturnsto“1”whentheprogramoperation(PROG)chang-esintoRESET,LOCAL,orREM.
1
(P.FWD)Fast-forwardingofprogramoperation
1:Normal,2:Twice,5:Fivetimes, 10:Tentimes*Usethisfunctionwhencheckingtheprogrampatternsetting.OnlySegmenttimeandTimeeventcanbefaster.
*Theoperationreturnstothenormalspeedafterfast-forwarding.
1
(AT)AUTO-tuningswitch
OFF:Disable1to8:Performauto-tuning.TuningresultisstoredinthespecifiednumberedPID.
R:TuningresultisstoredinthePIDforreferencedeviation.
OFF
(PID)PIDnumber
ThePIDgroupnumberbeingselectedis displayed.1to8,R:PIDgroupforreferencedeviation
1
SELECT ParameterMenusymbol: (CS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
Registeredpa-rametersymbol
SELECTparameter10to19
Settingrangeofaregisteredparameter.Fordetails,seeUser'sManual. — Table
below EASY
Parameter n=10 n=11 n=12 n=13 n=14 n=15 n=16 n=17 n=18 n=19
CSn
FortheregistrationofSELECTparameters,seeUser'sManual.
Program Setting ParameterMenusymbol:( PROG> PTNO.(=01to30)> SEGNO.(=00))
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(SSP)Startingtargetsetpoint
0.0to100.0%ofPVinputrange(EU)(Settingrange:P.RLtoP.RH) P.RL
EASY
(STC)Start code
SSP:Programoperationbeginswiththestartingtargetsetpoint.
RAMP:Ramp-prioritizedPVstartTIME:Time-prioritizedPVstartLSP:Local-modestartRSP:Remote-modestart*STC=TIMEcannotbeselectedwhentheparameterSEG.TisTM.RT.
SSP
to
(WT.SW1toWT.SW5)
WaitfunctionON/OFF1to5
OFF:DisableON:Enable OFF
STD
to
(WZ.UP1toWZ.UP5)
Upper-sidewaitzone1to5
0.0to10.0%ofPVinputrange(EU)
0.5%ofPVinput range
to
(WZ.LO1toWZ.LO5)
Lower-sidewaitzone1to5
0.5%ofPVinput range
to
(WT.TM1toWT.TM5)
Waittime1to5
OFF:Nofunction0.00to999.59(“hour.minute”or“minute.second”)*Availableonlyforthewaittimeatthesegment
switching.*UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
OFF
(R.CYCL)Numberofrepeat cycles
0to999,CONT(limitlessnumberoftimes) 0
(R.STRT)
Repeatcyclestartsegmentnumber 1to99
1≤R.STRT≤R.END≤99
1
(R.END)
Repeatcycleendsegmentnumber
1
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedfortheparameterSSP.(LP2lampislit.)Wait-function-relatedparametersaredisplayedinorderofthe1stgroup(WT.SW1,WT.TM1,WZ.UP1,Z.LO1),the2ndgroup,the3rdgroup,andsoon.
Program Setting ParameterMenusymbol:( PROG> PTNO.(=01to30)> SEGNO.(=01to99))
Parameter symbol
Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(TSP)Finaltargetsetpoint
0.0to100.0%ofPVinputrange(EU)(Settingrange:P.RLtoP.RH) P.RL
See "Pro-gram-ming"in this
manual.
EASY
(TIME)Segmenttimesetting
-:Unregistered0.00to999.59(“hour.minute”or“minute.second”) *SettingavailablefortheparameterSEG.T=TIME. *UsetheparameterTMUtosetthetimeunit.(Commonintheinstrument.) *Ifthesettingis0.00,TSPchangesinstepwiseafter one control period.
-
(TM.RT)
Segmentramp-ratesetting
-:UnregisteredRamp:0.0to100.0%ofPVinputrangespan(EUS)/1houror1minute
Soak:0.00to999.59(“hour.minute”or“minute.second”)*SettingavailablefortheparameterSEG.T=TM.RT*UsetheparameterTMUtosetthetimeunit.(Commonintheinstrument.)
Per1hour:TMU=HH.MM,Per1minute:TMU=MM.SS*Ifitissetto0.0%oftheinputrangespan,orthesegmenttime0.00,theprogrammovestothenextsegmentafteronecontrolperiod.
-
(S.PID)SegmentPIDnumberselection
1to8*PIDnumbercanbesetwhentheparameter“ZON=0.” 1
(JC)Junction code
CONT:SwitchingforcontinuationHOLD:Hold-onswitching(thecontrollerholdstheend-of-
segmentsetpointwhenthesegmentiscompleted,toperformcontrol).
LOCAL:Local-modeswitching(thecontrollerswitchestoalocalsetpointwhenthesegmentiscompleted).
REM:Remote-modeswitching(thecontrollerswitchestoaremotesetpointwhenthesegmentiscompleted).
W.SW1toW.SW5:Waitduringswitchingbetweensegments.W.IV1toW.IV5:Waitwithinasegmentinterval.W.SL1toW.SL5:Segmentswitching(thecontrollerswitches
toalocalsetpointwhenthesegmentiscompletedafterrelease.)(5groups)
W.SR1toW.SR5:Segmentswitching(thecontrollerswitchestoaremotesetpointwhenthesegmentiscompletedafterrelease.)(5groups)
PLK.1toPLK.30:Linkedtopatterns1to30.INS.:Allowsasegmenttobeaddedtotheendofaspecified
segment.DEL.:Allowsaspecifiedsegmenttobedeleted.
CONT
See "Pro-gram-ming"in this
manual.
STD
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedfortheparameterSSP.(LP2lampislit.)
Program Setting ParameterMenusymbol:( PROG> PTNO.(=1to30)> SEGNO.(=1to99))
Parameter symbol
Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(PV.TY1toPV.TY8)
PVevent-1to-8type
OFF:Disable(Energized)1:PVhighlimit,2:PVlowlimit,3:SPhighlimit,4:SPlowlimit,5:Deviationhighlimit,6:Deviationlowlimit,7:Deviationhighandlowlimits,8:Deviationwithinhighandlowlimits,9:TargetSPhighlimit,10:TargetSPlowlimit,11:TargetSPdeviationhighlimit,12:TargetSPdeviationlowlimit,13:TargetSPdeviationhighandlowlimits,14:TargetSPdeviationwithinhighandlowlimits,15:OUThighlimit,16:OUTlowlimit,17:Cooling-sideOUThighlimit,18:Cooling-sideOUTlowlimit*Add100for"de-energized".Forexample,whenthePVhighlimitisde-energized,thesettingis101.
OFF
See "Pro-gram-ming"in this
manual.
STD to
(PV.EV1toPV.EV8)
PVevent-1to-8setpoint
SetadisplayvalueofsetpointofPValarm,SPalarm,deviationalarm,oroutputalarm.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.
0
to
(TME1toTME16)
Start condition of timeevent1to16
ON:StartONstateOFF:StartOFFstate OFF
to
(T.ON1toT.ON16)
Ontimeoftimeevent1to16
-:Unregistered0.01to999.59(“hour.minute”or“minute.second”)*Availableonlywithinthesegmenttime.*OFFwhentheoperationmodeischangedtothemodeexcepttheprogramoperation.
*UsetheparameterTMUtosetthetimeunit.(Commonintheinstrument.)
-
to
(T.OF1toT.OF16)
Offtimeoftimeevent1to16 -
PVeventandTimeeventareavailableonlyduringtheprogramoperation.PVeventparametersaredisplayedinorderofPVevent1(PV.TY1,PV.EV1),PVevent2,PVevent3,andsoon.TimeeventparametersaredisplayedinorderofTimeevent1(TME1,T.ON1,T.OF1),Timeevent2,Timeevent3,and so on.
Local Setting ParameterMenusymbol: (LOC)
Parameter symbol
Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(LSP)Localtargetsetpoint
0.0to100.0%ofPVinputrange(EU)(Settingrange:P.RLtoP.RH) P.RL
EASY
(L.PID)
PIDnumberse-lectionforlocal-mode operation
SetaPIDgroupnumbertouse.1to8*AvailableonlyfortheL.PIDwhenZON=0or5.*Ifsetto“LocalPIDselection,”localPIDisse-lectedirrespectiveoftheoperationmodes.
1
to
(L.TY1toL.TY8)
Localevent-1to-8type
OFF:Disable(Energized)1:PVhighlimit,2:PVlowlimit,3:SPhighlimit,4:SPlowlimit,5:Deviationhighlimit,6:Deviationlowlimit,7:Deviationhighandlowlimits,8:Deviationwithinhighandlowlimits,9:TargetSPhighlimit,10:TargetSPlowlimit,11:TargetSPdeviationhighlimit,12:TargetSPdeviationlowlimit,13:TargetSPdeviationhighandlowlimits,14:TargetSPdeviationwithinhighandlowlimits,15:OUThighlimit,16:OUTlowlimit,17:Cooling-sideOUThighlimit,18:Cooling-sideOUTlowlimit*Add100for"de-energized".Forexample,
whenthePVhighlimitisde-energized,thesettingis101.
OFF
STD
to
(L.EV1toL.EV8)
Localevent-1to-8setpoint
SetadisplayvalueofsetpointofPValarm,SPalarm,deviationalarm,oroutputalarm.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype
0
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedfortheparameterLSP.(LP2lampislit.)LocaleventparametersaredisplayedinorderofLocalevent1(L.TY1,L.EV1),Localevent2,Localevent3,and so on.
Alarm Setpoint Setting ParameterMenusymbol: (AL)
Parameter symbol
Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to (A1toA8)
Alarm-1to-8setpoint
Thesealarmsworkirrespectiveoftheoperationmode.SetadisplayvalueofsetpointofPValarm,SPalarm,deviationalarm,outputalarm,orvelocityalarm.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype
0 Tablebelow EASY
UsethefollowingtabletorecordSPandalarmsetpoints.
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
An
SP-related Setting ParameterMenusymbol: (SPS)
Parameter symbol Name of Parameter Setting Range Initial value User
settingDisplay
level
(RMS)Remoteinputmethod RSP:Viaremote(auxiliaryanalog)input
COM:Viacommunication RSP
STD
(RFL)Remoteinputfilter OFF,1to120s OFF
(RT)Remoteinputratio
SP=RemoteinputxRT+Re-moteinputbias
0.001to9.9991.000
(RBS)Remoteinputbias -100.0to100.0%ofPVinput
rangespan(EUS)
0.0%ofPVinputrange
span
(SPT)SPtrackingselection
TrackingisperformedwhenthemodechangesfromProgramorRemotetoLocal.(Thelocalset-pointkeepstrackoftheprogramorremotesetpoint.)OFF,ON
OFF
(S.TM)Startingtimeofprogramoperation
0.00to999.59(“hour.minute”or“minute.second”(commonuseofinstrument)*UsetheparameterTMUtosetthe time unit.
0.00
(PNC)Programpatternnumberclearance
OFF:Notcleared.ON:Cleared. (SettheprogramNo.beforerestartprogramoperation)*Thecontrollerresets(clears)theprogrampatternnumberontheoperatingdisplayto“0”attheendofprogramoperation.
OFF
Alarm Function Setting ParameterMenusymbol: (ALRM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(EHY1toEHY8)
Event-1to-8hysteresis
ThehysteresissetpointofPVeventorLocaleventissettotheparcentageof0.0to100.0%.Thesettingvalue(%)isforthePVinputrangespanoroutputspan.
0.5 STD
to
(AL1toAL8)
Alarm-1to-8typeExample:Alarm-1
Stand-by action
Latch actionEnergized/De-energize
Alarm type
Thesealarmsworkirrespectiveoftheoperation mode.Seta5-digitvalueinthefollowingorder.[Latchaction(0/1/2/3/4)]+[Energized(0)orDe-energized(1)]+[Without(0)orWith(1)Stand-byaction]+[Alarmtype:2digits(seebelow)]Forlatchaction,seeUser'sManual. AL1,
AL3: Latchaction (0)
Ener-gized(0)
WithoutStand-by
action (0)
PVhighlimit(01)
AL2,AL4:Latchaction (0)
Ener-gized(0)
WithoutStand-by
action (0)
PVlowlimit(02)
AL5toAL8:notdisplayed for facto-ry default
Tablebelow EASY
Alarmtype:2digits 00:Disable01:PVhighlimit02:PVlowlimit03:SPhighlimit04:SPlowlimit05:Deviationhighlimit06:Deviationlowlimit07:Deviationhighandlowlimits08:Deviationwithinhighandlowlimits09:TargetSPhighlimit10:TargetSPlowlimit11:TargetSPdeviationhighlimit12:TargetSPdeviationlowlimit13:TargetSPdeviationhighandlowlimits14:TargetSPdeviationwithinhigh
and low limits15:OUThighlimit16:OUTlowlimit17:Cooling-sideOUThighlimit18:Cooling-sideOUTlowlimit19:AnaloginputPVhighlimit20:AnaloginputPVlowlimit21:AnaloginputRSPhighlimit22:AnaloginputRSPlowlimit23:AnaloginputAIN2highlimit24:AnaloginputAIN2lowlimit25:AnaloginputAIN4highlimit26:AnaloginputAIN4lowlimit27:Feedbackinputhighlimit28:Feedbackinputlowlimit29:PVvelocity30:Faultdiagnosis31:FAIL32:Deviation(%)highlimit33:Deviation(%)lowlimit34:Deviation(%)highandlowlimits35:Deviation(%)withinhighandlowlimits36:TargetSPdeviation(%)highlimit37:TargetSPdeviation(%)lowlimit38:TargetSPdeviation(%)highand
low limits39:TargetSPdeviation(%)withinhigh
and low limits
to
(VT1toVT8)
PVvelocityalarmtimesetpoint1to8 0.01to99.59(minute.second) 1.00
to
(HY1toHY8)
Alarm-1to-8hysteresis
Setadisplayvalueofsetpointofhysteresis.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.Whenthedecimalpointposi-tionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".
10
OperationGuide
Yokogawa Electric Corporation
Parameters
UP55AProgram Controller (Detailed code model)
Operation Guide for Single-loop Control
This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the controller. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the MODE key.For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
IM 05P02C41-15EN page 12/14
to
(DYN1toDYN8)
Alarm-1to-8On-delaytimer
AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpointis reached. 0.00to99.59(minute.second)
0.00Tablebelow STD
(AMD)Alarmmode
0:Alwaysactive1:NotactiveinRESETmode2:NotactiveinRESETorMANmode
0
Forthealarmfunctionsettingparameter,4alarmsaredisplayedforthefactorydefault.ThenumberofalarmscanbechangedbythesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,seeUser'sManual.
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
EHYn
ALn
VTn
HYn
DYNn
n:alarmnumber
PV-related Setting ParameterMenusymbol: (PVS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BS)PVinputbias -100.0to100.0%ofPVinputrange
span(EUS)
0.0%ofPVinput
rangespan EASY
(FL)PVinputfilter OFF,1to120s OFF
PID Setting ParameterMenusymbol: (PID)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(P)
ProportionalbandHeating-sideproportion-alband(inHeating/cool-ingcontrol)
0.0to999.9%When0.0%isset,itoperatesas0.1%.Heating-sideON/OFFcontrolapplieswhen0.0%inHeating/coolingcontrol
5.0%
EASY
(I)
IntegraltimeHeating-sideintegraltime(inHeating/coolingcontrol)
OFF:Disable1to6000s 240s
(D)
DerivativetimeHeating-sidederivativetime(inHeating/coolingcontrol)
OFF:Disable1to6000s 60s
(OH)
ControloutputhighlimitHeating-sidecontroloutputhighlimit(inHeating/coolingcontrol)
-4.9to105.0%,(OL<OH)InHeating/coolingcontrol:0.1to105.0%(OL<OH)
100.0%
(OL)
ControloutputlowlimitHeating-sidecontroloutputlowlimit(inHeat-ing/coolingcontrol)
-5.0to104.9%,(OL<OH),SD:TightshutInHeating/coolingcontrol:0.0to104.9%(OL<OH)
0.0%
(MR)Manual reset
EnabledwhenintegraltimeisOFF.ThemanualresetvalueequalstheoutputvaluewhenPV=SP.-5.0to105.0%
50.0%
(HYS)
Hysteresis(inON/OFFcontrol or Position proportionalcontrol)Heating-sideON/OFFcontrolhysteresis(inHeating/coolingcontrol)
InON/OFFcontrol:0.0to100.0%ofPVinputrangespan(EUS)
InHeating/coolingcontrolorPositionproportionalcontrol:0.0to100.0%
In ON/OFFcontrol:0.5%ofPVinputrangespan
In Heating/cooling
control or Position-proportional control:0.5%
(HY.UP)Upper-sidehysteresis(inON/OFFcontrol)
0.0to100.0%ofPVinputrangespan(EUS)
0.5%ofPVinput rangespan
(HY.LO)Lower-sidehysteresis(inON/OFFcontrol)
0.5%ofPVinput rangespan
(DR)Direct/reverseactionswitch
RVS:ReverseactionDIR:Directaction RVS STD
(Pc)Cooling-sidepropor-tionalband
0.0to999.9% (Cooling-sideON/OFFcontrolapplieswhen0.0%inHeating/coolingcontrol)
5.0%
EASY
(Ic)Cooling-sideintegraltime
OFF:Disable1to6000s 240s
(Dc)Cooling-sidederivativetime
OFF:Disable1to6000s 60s
(OHc)Cooling-sidecontroloutputhighlimit 0.1to105.0%,(OLc<OHc) 100.0%
(OLc)Cooling-sidecontroloutput low limit 0.0to104.9%,(OLc<OHc) 0.0%
(HYSc)Cooling-sideON/OFFcontrol hysteresis 0.0to100.0% 0.5%
(DB)
Outputdeadband(inHeating/coolingcontrolorPositionproportionalcontrol)
InHeating/coolingcontrol:-100.0to50.0%InPositionproportionalcontrol:1.0to10.0% 3.0%
(PO)
Preset outputHeating-sidepresetoutput(inHeating/cool-ingcontrol)
InRESETmode,fixedcontroloutputcanbegenerated.InPositionpropor-tionalcontrol,Valveopeningcanbeset;-5.0to105.0%
0.0% EASY
(POc)Cooling-sidepresetoutput
InRESETmode,cooling-sidefixedcontroloutputcanbegenerated.-5.0to105.0%
0.0% EASY
IfyouareusingtwoormoregroupsofPIDparameters,usethefollowingtabletorecordtheirsettingvalues.
Parameter n=2 n=3 n=4 n=5 n=6 n=7 n=8 R
P
I
D
OH
OL
MR
HYS
HY.UP
HY.LO
DR
Pc
Ic
Dc
OHc
OLc
HYSc
DB
PO
POc
n:groupnumber
Tuning ParameterMenusymbol: (TUNE)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(SC)Super function
OFF:Disable1:Overshootsuppressingfunction
(normalmode)2:Huntingsuppressingfunction
(stablemode) Enablestoanswerthewidercharacteristicchangescomparedwith response mode.
3:Huntingsuppressingfunction(responsemode) Enablesquickfollow-upandshortconvergingtimeofPVforthechangedSP.
4:Overshootsuppressingfunction(strongsuppressingmode) Note:Setpoints2and3mustbeusedinPIDcontrolorPIcontrol.Disabledinthefollowingcontrols: 1)ON/OFFcontrol,2)PDcontrol,3)Pcontrol,4)Heating/coolingcontrol. Donotusethefunctionforthecontrol processes with response suchasfloworpressurecontrol.
OFF EASY
(AT.TY)Auto-tuningtype 0:Normal
1:Stability 0 STD
(AR)
Anti-resetwindup(excessintegrationprevention)
AUTO,50.0to200.0% AUTO
STD
(OPR)Outputvelocitylimiter OFF:Disable
0.1to100.0%/s OFF
(MPON)Manual preset output numberselection
SelecttheoutputusedinMANmodewhenswitchedfromAUTOtoMANmode.OFF:HoldthecontroloutputinAUTO
mode(bumpless)1:Usemanualpresetoutput1(outputbump)2:Usemanualpresetoutput2(outputbump)3:Usemanualpresetoutput3(outputbump)4:Usemanualpresetoutput4(outputbump)5:Usemanualpresetoutput5(outputbump)
OFF
to
(MPO1toMPO5)
Manual preset output 1 to 5
-5.0to105.0%However,outputislimitedtotheoutputhighlimitandlowlimit.
0.0% Tablebelow
Usethefollowingtabletorecordthemanualpresetoutputsettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5
MPOn
Zone Control ParameterMenusymbol: (ZONE)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(RP1toRP7)
Referencepoint1to7
Set reference points at which switch-ingiscarriedoutbetweengroupsofPIDconstantsaccordingtothegiventemperaturezone.0.0to100.0%ofPVinputrange(EU)(RP1≤RP2≤RP3≤RP4≤RP5≤RP6≤RP7)
100.0%ofPVinput range
Tablebelow STD
(RHY)ZonePIDswitchinghysteresis
Hysteresiscanbesetforswitchingata reference point.0.0to10.0%ofPVinputrangespan(EUS)
0.5%ofPVinput rangespan
STD
(RDV)Referencedeviation
SetadeviationfromSP.ThePIDforreferencedeviationisusedifthereisalargerdeviationthanthepresetreferencedeviation.OFF:Disable0.0+1digitto100.0%ofPVinputrangespan(EUS)
OFF STD
ForZonecontrol,setthesetupparameterZON(zonePIDselection)toZonePIDselection.Usethefollowingtabletorecordthereferencepointsettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7
RPn
P Parameter (for Ladder Program)Menusymbol: (PPAR)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(P01toP10)
P01toP10parameter-19999to30000(SetadecimalpointpositionusingLL50AParameterSet-tingSoftware.)
0 Tablebelow STD
Parameter n=01 n=02 n=03 n=04 n=05 n=06 n=07 n=08 n=09 n=10
Pn
10-segment Linearizer-1, -2 Setting ParameterMenusymbol: (PYS1) (PYS2)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PYS)10-segmentlinearizerselection
OFF:DisablePV:PVanaloginputRSP:RSPanaloginputAIN2:AIN2analoginputAIN4:AIN4analoginputPVIN:PVinputOUT:OUTanalogoutputOUT2:OUT2analogoutputRET:RETanalogoutput
PV(CTLM:SGL)
STD
(A1)10-segmentlinearizerinput 1
-66.7to105.0%ofinputrange(EU)Outputlinearizer:-5.0to105.0% 0.0%
(B1)10-segmentlinearizeroutput 1
10-segmentlinearizerbias:-66.7to105.0%ofinputrangespan(EUS)
10-segmentlinearizerapproximation:-66.7to105.0%ofinputrange(EU)
Outputlinearizer:-5.0to105.0%
0.0%
to , to
(A2toA11,B2toB11)
10-segmentlinearizerinput 2 to 1110-segmentlinearizeroutput 2 to 11
SameasA1andB1
Same asA1and B1
(PMD)10-segmentlinearizermode
0:10-segmentlinearizerbias1:10-segmentlinearizerapproximation 0
Usethefollowingtabletorecordthe10-segmentlinearizerinputandoutputsettingvalues.
Parameter n=2 n=3 n=4 n=5 n=6 n=7 n=8 n=9 n=10 n=11
An
Bn
Setup ParametersHolddownthePARAMETERkeyandLeftarrowkeysimultaneouslyfor3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplaytotheSetupParameterSettingDisplay.PresstheDISPLAYkeyoncetoreturntotheOperationDisplay.
Menu
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu Display and P a r a m e t e r Sett ing Display are changed in a circular pattern.
Hold down PARAMETER key and Left arrow key simultaneously for 3 sec.
DISPLAY key
PARAMETER keySET/ENTER key
Move to the Operation Parameter Setting Display: Hold down the PARAMETER key for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
NotethattherearesomeparameterswhicharenotdisplayeddependingontheModelandSuffixcodes,controlmode(CTLM),control type(CNT),etc.Theparameters forprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
Control Function Setting ParameterMenusymbol: (CTL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(CTLM)Controlmode
WhenusingthecontrolsotherthanSingle-loopcontrol,seeUser'sManual.
SGL STDSGL:Single-loopcontrolCAS1:Cascadeprimary-loopcontrolCAS:CascadecontrolPVSW:LoopcontrolwithPVswitchingPVSEL:LoopcontrolwithPVauto-selector
(CNT)Controltype
PID:PIDcontrolONOF:ON/OFFcontrol(1pointofhysteresis)
ONOF2:ON/OFFcontrol(2pointsofhysteresis)
H/C:Heating/coolingcontrol
PID or H/C (for
Heating/Coolingtype)
EASY
(ZON)ZonePIDselection
0:SegmentPIDselection1:ZonePIDselection(selectionbyPV)2:ZonePIDselection(selectionby
targetSP)4:ZonePIDselection(selectionbySP)5:LocalPIDselection*Ifsetto“SegmentPIDselection,”allowsPIDconstantstobeselectedforeachsegments.
*Ifsetto“ZonePIDselection,”automaticallyselectsPIDconstantsaccordingtotherangesetintheReferencepoint.
*Ifsetto“LocalPIDselection,”localPIDisselectedirrespectiveoftheoperation modes.
1 STD
(SEG.T)Segmentsettingmethod
TIME:SegmenttimesettingTM.RT:Segmentramp-ratesetting*Note:Achangeofsettingdeletesaprogrampattern.
TIME
EASY
(TMU)Programtimeunit HH.MM:hour.minute
MM.SS:minute.second HH.MM
(PT2.G)Programpattern-2retransmission
OFF:Notused.ON:used.*Thecontrollercanserveasaprogrampatterngenerator.
*Retransmissionoutputtypes(RTS,O1RS,orO2RS)needtobesettoSP2.
OFF
STD
(SMP)Inputsamplingperiod(controlperiod) 100:100ms,200:200ms 200
PV Input Setting ParameterMenusymbol: (PV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(IN)
PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.0to150.00C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
OFF
EASY
(UNIT)PVinputunit
-:Nounit,C:DegreeCelsius, -:Nounit,--:Nounit,---:Nounit, F:DegreeFahrenheit
C
(RH)MaximumvalueofPVinputrange
Dependsontheinputtype.-Fortemperatureinput-
Setthetemperaturerangethatisactuallycontrolled.(RL<RH)
-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.
Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumval-ueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
Dependson the
input type
(RL)MinimumvalueofPVinputrange
Dependson the
input type
(SDP)PVinputscaledecimalpoint position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
Dependson the
input type
IM 05P02C41-15EN page 13/14
(SH)MaximumvalueofPVinput scale
-19999to30000,(SL<SH),|SH-SL|≤30000
Dependson the
input typeEASY
(SL)MinimumvalueofPVinput scale
Dependson the
input type
(BSL)PVinputburnoutaction
OFF:DisableUP:UpscaleDOWN:Downscale
Dependson the
input type
STD(A.BS)
PVanaloginputbias -100.0to100.0%ofPVinputrangespan(EUS)
0.0%ofPVinputrangespan
(A.FL)PVanaloginputfilter OFF,1to120s OFF
W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988,WRE:W97Re3-W75Re25
RSP Input Setting Parameter (E1-terminal Area)Menusymbol: (RSP)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(IN)RSPremoteinputtype
0.4-2V:0.400to2.000V1-5V:1.000to5.000V0-2V:0.000to2.000V0-10V:0.00to10.00V0-125:0.000to1.250VForoption/DR,RSPremoteinputtypeissameasPVinputtype
1-5V
EASY
(UNIT)RSPremoteinputunit
-:Nounit,C:DegreeCelsius, -:Nounit,--:Nounit,---:Nounit, F:DegreeFahrenheit
C
(RH)MaximumvalueofRSPremoteinputrange
Dependsontheinputtype.-Fortemperature(/DRoption)input-Setthetemperaturerangethatisactuallycontrolled.(RL<RH)
-Forvoltage/current(/DRoption)input-Settherangeofavoltage/currentsignalthatisapplied.
Thescaleacrosswhichthevoltage/currentsignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andmini-mumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
Dependson the
input type
(RL)MinimumvalueofRSPremoteinputrange
Dependson the
input type
(SDP)RSPremoteinputscaledecimal point position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
Dependson the
input type
(SH)MaximumvalueofRSPremote input scale
-19999to30000,(SL<SH), |SH-SL|≤30000
Dependson the
input type
(SL)MinimumvalueofRSPremote input scale
Dependson the
input type
(BSL)RSPremoteinputbum-out action
OFF:DisableUP:UpscaleDOWN:Downscale
Dependson the
input type
STD
(RTD.S)RTDwiringsystem
3-W:3-wiresystem4-W:4-wiresystem(TheLL50AParameterSettingSoft-wareisrequiredtouseRSPterminalsinputasPV.)
3-W
AIN2/AIN4 Aux. Analog Input Setting Parameter (E2/E4-terminal Area)
Menusymbol: (AIN2) (AIN4)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(IN)AIN2/AIN4aux.analoginput type
0.4-2V:0.400to2.000V1-5V:1.000to5.000V0-2V:0.000to2.000V0-10V:0.00to10.00V0-125:0.000to1.250V
1-5V
EASY
(UNIT)AIN2/AIN4aux.analoginput unit
-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit
C
(RH)
MaximumvalueofAIN2/AIN4aux.analoginputrange
Dependsontheinputtype.Settherangeofavoltagesignalthatis applied.Thescaleacrosswhichthevoltagesignalisactuallycontrolledshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
Dependson the
input type
(RL)
MinimumvalueofAIN2/AIN4aux.analoginputrange
Dependson the
input type
(SDP)
AIN2/AIN4aux.analoginput scale decimal point position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
Dependson the
input type
(SH)
MaximumvalueofAIN2/AIN4aux.analoginputscale -19999to30000,(SL<SH),
|SH-SL|≤30000
Dependson the
input type
(SL)
MinimumvalueofAIN2/AIN4aux.analoginputscale
Dependson the
input type
(BSL)AIN2/AIN4aux.analoginputburnoutaction
OFF:DisableUP:UpscaleDOWN:Downscale
Dependson the
input typeSTD
Input Range, SP Limiter Setting ParameterMenusymbol: (MPV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(P.UNI)ControlPVinputunit
-:NounitC:DegreeCelsius-:Nounit,--:Nounit,---:NounitF:DegreeFahrenheit
Same asPVinput unit
STD
(P.DP)ControlPVinputdecimalpoint position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
Dependson the
input type
(P.RH)MaximumvalueofcontrolPVinputrange
-19999to30000,(P.RL<P.RH),|P.RH-P.RL|≤30000
Dependson the
input type
(P.RL)MinimumvalueofcontrolPVinputrange
Dependson the
input type
(SPH)SPhighlimit
0.0to100.0%ofPVinputrange(EU),(SPL<SPH)Placelimitsontheprogramsetpointsor the local setpoints when the con-trollerisinprogramoperation.*Placesthelimitontheprogram
setpoint, local setpoint, or remote setpointduringprogramoperation.
*WhenLP2lampison,SPHandSPLlimittheprogramsetpointforprogrampattern2retransmission.
100.0%ofPVinput range
(SPL)SP low limit
0.0%ofPVinput range
Output Setting ParameterMenusymbol: (OUT)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(OT)
Outputtypeselection
Upper two digits
Lower two digits
ControloutputorHeating-sidecontroloutput(Lowertwodigits)00:OFF01:OUTterminals(voltagepulse)02:OUTterminals(current)03:OUTterminals(relay/triac)04:OUT2terminals(voltagepulse)05:OUT2terminals(current)06:OUT2terminals(relay/triac)
Cooling-sidecontroloutput(Uppertwodigits)00:OFF01:OUTterminals(voltagepulse)02:OUTterminals(current)03:OUTterminals(relay/triac)04:OUT2terminals(voltagepulse)05:OUT2terminals(current)06:OUT2terminals(relay/triac)
Standard type:00.03
Heating/coolingtype:06.03
EASY(CT)
Controloutputcycletime Heating-sidecontroloutputcycletime(inHeating/coolingcontrol) 0.5to1000.0s
30.0s
(CTc)Cooling-sidecontroloutput cycle time 30.0s
(V.AT)Automaticvalvepositionadjustment
OFF:StopautomaticadjustmentON:Startautomaticadjustment OFF
(V.RS)Valvepositionsettingreset
SettingV.RStoONresetsthevalveadjustmentsettingsandcausestheindication“V.RS”toblink.
OFF
(V.L)Fully-closedvalveposi-tionsetting
PressingtheSET/ENTERkeywithvalvepositionsettothefully-closedpositionbyDownarrowkeycausestheadjustedvaluetobestored.WhenV.Ladjustmentiscompleted,V.Lstopsblinking.
-
(V.H)Fully-openedvalveposi-tionsetting
PressingtheSET/ENTERkeywithvalvepositionsettothefully-openedpositionbyUparrowkeycausestheadjustedvaluetobestored.WhenV.Hadjustmentiscompleted,V.Hstopsblinking
-
(TR.T)Valvetravelingtime 5to300s 60s
STD
(V.MOD)Valveadjustingmode
0:Valvepositionfeedbacktype1:Valvepositionfeedbacktype(movestotheestimatingtypeifafeedbackinputerrororbreakoccurs.)
2:Valvepositionestimatingtype
0
(RTS)RetransmissionoutputtypeofRET
OFF:DisablePV1:PVSP1:SPOUT1:OUT(Valveopening:0to100%inPositionproportionalcontrol)
LPS:15VDClooppowersupplyPV2:Loop-2PVSP2:Loop-2SPOUT2:Loop-2OUTTSP1:TargetSPHOUT1:Heating-sideOUTCOUT1:Cooling-sideOUTMV1:Positionproportionaloutput(internalcomputedvalue)
TSP2:Loop-2targetSPHOUT2:Loop-2heating-sideOUTCOUT2:Loop-2cooling-sideOUTMV2:Loop-2positionproportionaloutput(internalcomputedvalue)
PV:PVterminalsanaloginputRSP:RSPterminalsanaloginputAIN2:AIN2terminalsanaloginputAIN4:AIN4terminalsanaloginput*Loop-2settingvaluesareunavailable inSingle-loopcontrol.
PV1 EASY
(RTH)
Maximumvalueofretransmission output scaleofRET
WhenRTS=PV1,SP1,PV2,SP2,TSP1,TSP2,PV,RSP,AIN2,orAIN4,RTL+1digitto30000-19999toRTH-1digitDecimalpointposition:WhenRTS=PV1,SP1,orTSP1,
decimal point position is same as thatofPVinput.
WhenRTS=PV2,SP2,orTSP2,decimal point position is same as thatofRSPinput.
WhenRTS=PV,decimalpointpositionissameasthatofPVinputscale.
WhenRTS=RSP,decimalpointpositionissameasthatofRSPinputscale.
WhenRTS=AIN2,decimalpointposi-tionissameasthatofAIN2scale.
WhenRTS=AIN4,decimalpointposi-tionissameasthatofAIN4scale.
100%ofPVinput range
STD
(RTL)
Minimumvalueofretransmission output scaleofRET
0%ofPVinput range
(O1RS)
RetransmissionoutputtypeofOUTcurrentoutput
SameasRTS OFF
STD
(O1RH)
Maximumvalueofretransmission output scaleofOUTcurrentoutput
WhenO1RS=PV1,SP1,PV2,SP2,TSP1,TSP2,PV,RSP,AIN2,orAIN4,O1RL+1digitto30000-19999toO1RH-1digitDecimalpointposition:WhenO1RS=PV1,SP1,orTSP1,
decimal point position is same as thatofPVinput.
WhenO1RS=PV2,SP2,orTSP2,decimal point position is same as thatofRSPinput.
WhenO1RS=PV,decimalpointposi-tionissameasthatofPVinputscale.
WhenO1RS=RSP,decimalpointpositionissameasthatofRSPinput scale.
WhenO1RS=AIN2,decimalpointpositionissameasthatofAIN2scale.
WhenO1RS=AIN4,decimalpointpositionissameasthatofAIN4scale
-
(O1RL)
Minimumvalueofretransmission output scaleofOUTcurrentoutput
-
(O2RS)
RetransmissionoutputtypeofOUT2currentoutput
SameasRTS OFF
STD
(O2RH)
Maximumvalueofretransmission output scaleofOUT2currentoutput
WhenO2RS=PV1,SP1,PV2,SP2,TSP1,TSP2,PV,RSP,AIN2,orAIN4,O2RL+1digitto30000-19999toO2RH-1digitDecimalpointposition:WhenO2RS=PV1,SP1,orTSP1,
decimal point position is same as thatofPVinput.
WhenO2RS=PV2,SP2,orTSP2,decimal point position is same as thatofRSPinput.
WhenO2RS=PV,decimalpointposi-tionissameasthatofPVinputscale.
WhenO2RS=RSP,decimalpointpositionissameasthatofRSPinput scale.
WhenO2RS=AIN2,decimalpointpositionissameasthatofAIN2scale.
WhenO2RS=AIN4,decimalpointpositionissameasthatofAIN4scale.
-
(O2RL)
Minimumvalueofretransmission output scaleofOUT2currentoutput
-
(OU.A)OUTcurrentoutputrange
4-20:4to20mA0-20:0to20mA20-4:20to4mA20-0:20to0mA
4-20
(OU2.A)OUT2currentoutputrange 4-20
(RET.A)RETcurrentoutputrange 4-20
Heater Break Alarm Setting ParameterMenusymbol: (HBA)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(HB1.S)Heaterbreakalarm-1function selection 0:Heatercurrentmeasurement
1:Heaterbreakalarm
1
EASY
(HB2.S)Heaterbreakalarm-2function selection 1
(HB1)Heaterbreakalarm-1current setpoint
OFF,0.1to300.0Arms
OFF
(HB2)Heaterbreakalarm-2current setpoint OFF
(CT1.T)CT1coilwindingnumberratio
1to3300
800
(CT2.T)CT2coilwindingnumberratio 800
(HDN1)Heaterbreakalarm-1On-delaytimer
0.00to99.59(m.s)
0.00
STD
(HDN2)Heaterbreakalarm-2On-delaytimer 0.00
IncaseswherethecurrenttransformersmanufacturedbyU.R.D.Co.,Ltdareused,setthefollowingvalueforthecoilwindingnumberratio.CTL-6-S-H:800,CTL-12L-30:3000
RS-485 Communication Setting Parameter (E1/E3/E4-terminal Area)Menusymbol: (R485)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PSL)Protocol selection
PCL:PClinkcommunicationPCLSM:PClinkcommunication(with
checksum)LADR:LaddercommunicationCO-M:CoordinatedmasterstationMBASC:Modbus(ASCII)MBRTU:Modbus(RTU)CO-M2:Coordinatedmasterstation
(2-loopmode)P-P:Peer-to-peercommunication
MBRTU
EASY(BPS)Baud rate
600:600bps,1200:1200bps, 2400:2400bps,4800:4800bps, 9600:9600bps,19200:19.2kbps, 38400:38.4kbps*ThebaudrateforRS-485isupto19.2kbpsinE4-terminalarea.
19200
(PRI)Parity NONE:None,EVEN:Even,
ODD:Odd EVEN
(STP)Stopbit 1:1bit,2:2bits 1
(DLN)Datalength 7:7bits,8:8bits 8
(ADR)Address 1to99 1
Ethernet Communication Setting Parameter (E3-terminal Area)Menusymbol: (ETHR)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(HSR)High-speedresponsemode OFF,1to8 1
EASY
(BPS) Baud rate 9600:9600bps,19200:19.2kbps, 38400:38.4kbps 38400
(PRI) Parity NONE:None,EVEN:Even, ODD:Odd EVEN
to (IP1toIP4)
IP address 1 to 40to255Initialvalue:(IP1).(IP2).(IP3).(IP4)=
(192).(168).(1).(1)See left Table
below
to (SM1toSM4)
Subnetmask1to40to255Initialvalue:(SM1).(SM2).(SM3).
(SM4)=(255).(255).(255).(0)See left Table
below
to (DG1toDG4)
Defaultgateway1to40to255Initialvalue:(DG1).(DG2).(DG3).
(DG4)=(0).(0).(0).(0)See left Table
below
(PRT)Portnumber 502,1024to65535 502
(IPAR)IP access restriction OFF:Disable,ON:Enable OFF
to ,
to
(1.IP1to1.IP4,2.IP1to2.IP4)
Permitted IP address 1-1to1-4Permitted IP address 2-1to2-4
0to255Initialvalue:
(1.IP1).(1.IP2).(1.IP3).(1.IP4)=(255).(255).(255).(255) (2.IP1).(2.IP2).(2.IP3).(2.IP4)=(255).(255).(255).(255)
See left Tablebelow
(ESW)Ethernetsettingswitch
Settingthisparameterto“ON”en-ablestheEthernetcommunicationparametersettings.OFF,ON
OFF
UsethefollowingtabletorecordEthernetcommunicationsettingvalue.
Parameter n=1 n=2 n=3 n=4
IPn
SMn
DGn
1.IPn
2.IPn
PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)Menusymbol: (PROF)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BR)Baud rate
9.6K:9.6kbps19.2K:19.2kbps93.75K:93.75kbps187.5K:187.5kbps0.5M:0.5Mbps1.5M:1.5Mbps3M:3Mbps6M:6Mbps12M:12MbpsAUTO45.45K:45.45kbps
AUTO
EASY
(ADR)Address 0to125 3
(BPS)Baud rate
9600:9600bps19200:19.2kbps38400:38.4kbps
38400
(FILE)Profilenumber 0,11to15 0
SetupParameters(Continuedfrompage12)
PV Input Setting Parameter (Continued)
IM 05P02C41-15EN page 14/14
DeviceNet Communication Setting Parameter (E3-terminal Area)Menusymbol: (DNET)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BR)Baud rate
125K:125kbps250K:250kbps500K:500kbps
125K
EASY(ADR)
Address 0to63 63
(BPS)Baud rate
9600:9600bps19200:19.2kbps38400:38.4kbps
38400
(FILE)Profilenumber 0,11to15 0
CC-Link Communication Setting Parameter (E3-terminal Area)Menusymbol: (CC-L)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BR)Baud rate
156K:156kbps625K:625kbps2.5K:2.5kbps5M:5Mbps10M:10Mbps
10M
EASY(ADR)Address 1 to 64 1
(BPS)Baud rate
9600:9600bps19200:19.2kbps38400:38.4kbps
38400
(FILE)Profilenumber 0,11to15
(0,11:Ver.1.10)(12to15:Ver.2.00) 0
DisplayFunctionSettingParameterMenusymbol: (DISP)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PCMD)ActivecolorPVdisplayswitch
0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,
AlarmON:red)3:Linktoalarm1(AlarmOFF:red,
AlarmON:white)4:Linktoalarm1or2(AlarmOFF:
white,AlarmON:red)5:Linktoalarm1or2(AlarmOFF:
red,AlarmON:white)6:PVlimit(Withinrange:white,Out
ofrange:red)7:PVlimit(Withinrange:red,Outof
range:white)8:SPdeviation(Withindeviation:
white,Outofdeviation:red)9:SPdeviation(Withindeviation:red,
Outofdeviation:white)10:LinktoDI(ON:red,OFF:white)
0
EASY
(PCH)PVcolorchangehighlimit
SetadisplayvaluewheninPVlimitorSPdeviation.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsonthe input type.
0
(PCL)PVcolorchangelowlimit 0
(PTSL)Programdisplaypatternselection
PTN:PatterndisplaySK.RP:Rampandsoakdisplay PTN
STD
(BAR1)Upperbar-graphdisplayregistration
0:Disable1:OUT,Heating-sideOUT,Internalvalue
in Position proportional control2:Cooling-sideOUT3:PV4:SP5:Deviation6:Loop-2OUT,Loop-2heating-sideOUT7:Loop-2cooling-sideOUT8:Loop-2PV9:Loop-2SP10:Loop-2deviation11to16:Disable17:Feedbackinput(valveopening)18:PVterminalsanaloginput19:RSPterminalsanaloginput20:AIN2terminalsanaloginput21:AIN4terminalsanaloginput22:Segmentprogress23:Timeeventandalarmstatus24:TSP25:TSPdeviation26:Loop-2TSP27:Loop-2TSPdeviation
23
(BAR2)Lowerbar-graphdisplayregistration 0
(BDV)Bar-graphdeviationdisplayband
0.0to100.0%ofPVinputrangespan(EUS)
1.0%ofPVinput rangespan
STD(GUID)
GuidedisplayON/OFF OFF:Nondisplay,ON:Display ON
(ECO)Economymode
OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)
2:EconomymodeON(AllindicationsOFF)3:Brightness10%(wholeindication)
OFF
(BRI)Brightness (Dark)1to5(Bright) 3 EASY
(MLSD)LeastsignificantdigitalmaskofPVdisplay
OFF:WithleastsignificantdigitON:Withoutleastsignificantdigit OFF STD
(MKTP)
Methodforleastsignifi-cantdigitalmaskofPVdisplay
0:Rounding,1:Rounding-off 0 STD
SELECTDisplaySettingParameterMenusymbol: (CSEL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(CS1toCS5)
SELECTDisplay-1to-5registration
Registertheoperationparameter(excepttheOperationMode)thatisfrequentlymodi-fiedtodisplayitintheOperationDisplay.OFF,2201to5000,6701to6710Forthesettingrange,seeUser'sManual.
OFF STD
UsethefollowingtabletorecordSELECTDisplaysettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5
CSn
KeyLockSettingParameterMenusymbol: (KLOC)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF
STD
(DATA)Front panel parameter data(,)keylock
OFF:Unlock,ON:Lock
OFF
(RUN)FrontpanelRUNkeylock OFF
(RST)FrontpanelRSTkeylock OFF
(PTN)FrontpanelPTNkeylock OFF
(MODE)FrontpanelMODEkeylock OFF
DIFunctionRegistrationParameterMenusymbol: (DI.SL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PRG)SwitchtoPROG(Startofprogramoperation)
SetanIrelaynumberofcontactinput.Set“OFF”todisablethefunction.
Standard terminalsDI1:5025,DI2:5026,DI3:5027
E1-terminalarea DI11:5041,DI12:5042,DI13:5043,DI14:5044,DI15:5045,DI16:5046
E2-terminalarea DI21:5057,DI22:5058,DI23:5059,DI24:5060,DI25:5061,DI26:5062
E3-terminalarea DI31:5073,DI32:5074,DI33:5075,DI34:5076,DI35:5077
E4-terminalarea DI41:5089,DI42:5090,DI43:5091,DI44:5092,DI45:5093,DI46:5094
5025
STD
(RST)SwitchtoRESET(Stopofprogramoperation) 5026
(LOC)
SwitchtoLOCAL(LSP)(Startoflocal-modeoperation)
5027
(REM)SwitchtoREMOTE 5046
(P/R)PROG/RESETSwitch OFF
(P/H)PROG/HOLDSwitch OFF
(P/L)PROG/LOCAL(LSP)Switch OFF
(HOLD)SwitchtoHOLD(Startofhold-modeoperation) OFF
(ADV)Advanceofsegment OFF
(WAIT)WaitON/OFFswitch OFF
(A/M)AUTO/MANswitch OFF
(AT)Auto-tuningSTART/STOPswitch OFF
(LAT)Latchrelease OFF
(LCD)LCDbacklightON/OFFswitch OFF
(PVRW)PVred/whiteswitch OFF
DIFunctionNumberingParameterMenusymbol: (DI.NU)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PT.B0)Bit-0ofprogrampatternnumber
Seenexttable.
5089
EASY
(PT.B1)Bit-1ofprogrampatternnumber 5090
(PT.B2)Bit-2ofprogrampatternnumber 5091
(PT.B3)Bit-3ofprogrampatternnumber 5092
(PT.B4)Bit-4ofprogrampatternnumber 5093
(PT.B5)Bit-5ofprogrampatternnumber SetanIrelaynumberofcontactinput.
Set“OFF”todisablethefunction.
Standard terminals DI1:5025,DI2:5026,DI3:5027
E1-terminalarea DI11:5041,DI12:5042,DI13:5043,DI14:5044,DI15:5045,DI16:5046
E2-terminalareaDI21:5057,DI22:5058,DI23:5059,DI24:5060,DI25:5061,DI26:5062
E3-terminalarea DI31:5073,DI32:5074,DI33:5075,DI34:5076,DI35:5077
E4-terminalarea DI41:5089,DI42:5090,DI43:5091,DI44:5092,DI45:5093,DI46:5094
OFF
STD
(PN.B0)Bit-0ofPIDnumber OFF
(PN.B1)Bit-1ofPIDnumber OFF
(PN.B2)Bit-2ofPIDnumber OFF
(PN.B3)Bit-3ofPIDnumber OFF
(MP.B0)Bit-0ofmanualpresetoutputnumber OFF
(MP.B1)Bit-1ofmanualpresetoutputnumber OFF
(MP.B2)Bit-2ofmanualpresetoutputnumber OFF
AL1-AL3FunctionRegistrationParameterMenusymbol: (ALM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(AL1.S)AL1functionselection
SetanIrelaynumber.Fortheitemsotherthanbelow,seeUser'sManual.Ex.)Setthenumber4353forAL1.Sto use the alarm 1.Set“OFF”todisablethefunction.Settingrange:4001to6304Nofunction:OFF, PVevent1:4801,PVevent2:4802, PVevent3:4803,PVevent4:4805, PVevent5:4806,PVevent6:4807, PVevent7:4809,PVevent8:4810, Timeevent1:4817,Timeevent2:4818, Timeevent3:4819,Timeevent4:4821, Timeevent5:4822,Timeevent6:4823, Timeevent7:4825,Timeevent8:4826, Timeevent9:4833,Timeevent10:4834, Timeevent11:4835,Timeevent12:4837, Timeevent13:4838,Timeevent14:4839, Timeevent15:4841,Timeevent16:4842, Alarm1:4353,Alarm2:4354, Alarm3:4355,Alarm4:4357 Alarm5:4358,Alarm6:4359, Alarm7:4361,Alarm8:4362 AUTO(OFF)/MAN(ON)status:4177ProgramRESETstatus:4181ProgramRUNstatus:4182Localoperationstatus:4183Remoteoperationstatus:4185HOLDmodestatus:4189Programadvancestatus:4187Patternendsignal(1second):4265Patternendsignal(3seconds):4266Patternendsignal(5seconds):4267Waitendsignal(1second):4257Waitendsignal(3seconds):4258Waitendsignal(5seconds):4259Outputtracking(ON)switchingsignal:4186FAIL(NormallyON)output:4256
4801
STD
(AL2.S)AL2functionselection 4802
(AL3.S)AL3functionselection 4803
(OR.S)OUTrelayfunctionselection OFF
(OR2.S)OUT2relayfunctionselection OFF
DOSettingParameter(E1/E2/E3/E4-terminalArea)Menusymbol: (DO)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(DO1.S)DO11/DO21/DO31/DO41 function selection SameasAL1.S
Set“OFF”todisablethefunction.
Initialvalue:DO11=4805,DO12=4806 DO13=4807,DO14=4809, DO15=4810,DO21=4817, DO22=4818,DO23=4819 DO24=4821,DO25=4822, DO31=4823,DO32=4825, DO33=4826,DO34=4833, DO35=4834, DO41toDO45=OFF
See left
Tablebelow STD
(DO2.S)DO12/DO22/DO32/DO42 function selection See left
(DO3.S)DO13/DO23/DO33/DO43 function selection See left
(DO4.S)DO14/DO24/DO34/DO44 function selection See left
(DO5.S)DO15/DO25/DO35/DO45 function selection See left
UsethefollowingtabletorecordDOsettingvalue.
Parameter E1-terminalArea E2-terminalArea E3-terminalArea E4-terminalArea
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
SystemSettingParameterMenusymbol: (SYS)
Parameter symbol Name of Parameter Setting Range Initial value User
settingDisplay
level
(R.MD)Restartmode
Sethowthecontrollershouldrecoverfroma power failure of 5 seconds or more.CONT:Continueactionsetbefore
power failure.MAN:StartfromMAN.RESET:StartfromAUTOandRESET.
Outputsthepresetoutputvalue.
CONT
STD
(R.TM)Restarttimer
Settimebetweenpoweronandtheinstant where controller starts compu-tation.0to10s
0
(EPO)Input error preset output
SetpresetoutputvaluewhentheinputburnoutorADCerroroccurs.Manualoutputispriori-tizedwhentheinputburnoutoccursinMAN.0:Presetoutput1:0%output2:100%output
0 STD
(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO
EASY
(QSM)Quicksettingmode OFF:Disable
ON:Enable ON
(LANG)Guidedisplaylanguage
ENG:EnglishFRA:FrenchGER:GermanSPA:Spanish
Dependsonthe model andsuffixcodes
(PASS)Passwordsetting 0(Nopassword)to65535 0
ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)
Parameter symbol Name of Parameter Status record Display
level
(PA.ER)Parameter error status
EASY
(OP.ER)Optionerrorstatus
(AD1.E)A/Dconvertererrorstatus1
(AD2.E)A/Dconvertererrorstatus2
(PV1.E)Loop-1PVinputerrorstatus
(PV2.E)Loop-2PVinputerrorstatus
(LA.ER)Laddererrorstatus
(MCU)MCUversion
(DCU)DCUversion
(ECU1)ECU-1version(E1-terminalarea)
(ECU2)ECU-2version(E2-terminalarea)
(ECU3)ECU-3version(E3-terminalarea)
(ECU4)ECU-4version(E4-terminalarea)
(PARA)Parameterversion
(H.VER)Productversion
(SER1)Serialnumber1
(SER2)Serialnumber2
(MAC1)MACaddress1(E3-terminalarea)
(MAC2)MACaddress2(E3-terminalarea)
(MAC3)MACaddress3(E3-terminalarea)
*TheparametersforLoop-2areunavailableinSingle-loopcontrol.
ParameterDisplayLevelParameterMenusymbol: (LVL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(LEVL)Parameterdisplaylevel
EASY:EasysettingmodeSTD:StandardsettingmodePRO:Professionalsettingmode
STD EASY
*ForProfessionalsettingmode,seeUser’sManual.
Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. Ethernet is a registered trademark of XEROX Corporation in the United States. Modbus is a registered trademark of Schneider Electric. PROFIBUS-DP is a registered trademark of PROFIBUS User Organization. DeviceNet is a registered trademark of Open DeviceNet Vendor Association. CC-Link is a registered trademark of CC-Link Partner Association. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.