user manualadvdownload.advantech.com/productfile/downloadfile2/1-1i... · 2018. 6. 9. · 5.5...

68
1 Zlinx™ Xtreme IP67 Wireless I/O USER MANUAL ZXT9-IO-222R2 ZXT24-IO-222R2

Upload: others

Post on 16-Jun-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

1

Zlinx™ Xtreme IP67 Wireless I/O USER MANUAL

ZXT9-IO-222R2 ZXT24-IO-222R2

Page 2: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

2

Advantech B+B SmartWorx - Americas

707 Dayton Road Ottawa, IL 61350 USA Phone (815) 433-5100

Fax (815) 433-5105

Advantech B+B SmartWorx - European Headquarters Westlink Commercial Park

Oranmore, Co. Galway, Ireland Phone +353 91-792444

Fax +353 91-792445

www.advantech-bb.com [email protected]

ADVANTECH B+B SMARTWORX TECHNICAL SUPPORT Phone: 1 (800) 346-3119

Monday - Friday, 7 a.m. to 5:30 p.m. (CST) Fax: (815) 433-5109 Email: [email protected] Web: www.advantech-bb.com

2018 B+B SmartWorx. No part of this publication may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photography, recording, or any information storage and retrieval system without written consent. Information in this manual is subject to change without notice, and does not represent a commitment on the part of B+B SmartWorx. B+B SmartWorx shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use of this manual. All brand names used in this manual are the registered trademarks of their respective owners. The use of trademarks or other designations in this publication is for reference purposes only and does not constitute an endorsement by the trademark holder.

Documentation Number: ZXTx-IO-222R2_1818m

Page 3: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

3

CONTENTS Advantech B+B SmartWorx Technical Support .................................................................................................................... 2 1 - Overview ............................................................................................................................................................................... 6

1.1 Product Overview ........................................................................................................................................................... 6 1.2 Prerequisites.................................................................................................................................................................... 6 1.3 Safety Information .......................................................................................................................................................... 6 1.4 Installation Information ................................................................................................................................................... 6 1.5 About This Manual .......................................................................................................................................................... 7 1.6 Zlinx Xtreme I/O Product Specification Summary...................................................................................................... 8

2 - Product Introduction ............................................................................................................................................................ 9 2.1 Zlinx Xtreme I/O Product Models ................................................................................................................................. 9 2.2 Package Contents .......................................................................................................................................................... 9 2.3 Zlinx Xtreme I/O Modes of Operation ........................................................................................................................ 10

2.3.1 Peer-to-Peer I/O Mode ......................................................................................................................................... 10 2.3.2 Modbus I/O Mode .................................................................................................................................................. 11 2.3.3 Repeater Mode (900 Mhz Model only) ............................................................................................................... 11

2.4 I/O Types and Characteristics .................................................................................................................................... 12 2.4.1 Digital / Pulse Inputs ............................................................................................................................................. 12 2.4.2 Digital Outputs ....................................................................................................................................................... 12 2.4.3 Analog Inputs ......................................................................................................................................................... 12 2.4.4 Analog Outputs ...................................................................................................................................................... 12

2.5 User Interface Components ........................................................................................................................................ 13 2.5.1 Radio Signal Strength Indicator (RSSI) LEDs ................................................................................................... 14 2.5.2 Mode LEDs ............................................................................................................................................................. 14 2.5.3 Wireless LED ......................................................................................................................................................... 14 2.5.4 Power LED ............................................................................................................................................................. 14 2.5.5 I/O Status LEDs ..................................................................................................................................................... 14 2.5.6 Configuration Pushbutton ..................................................................................................................................... 14 2.5.7 Power & I/O Terminals ......................................................................................................................................... 15 2.5.8 USB Port ................................................................................................................................................................. 15

3 - Hardware Installation ........................................................................................................................................................ 16 3.1 Recommended Practice Before Installation ............................................................................................................. 16 3.2 RF Site Considerations ................................................................................................................................................ 16 3.3 Dimensional Information .............................................................................................................................................. 17 3.4 Mounting Options .......................................................................................................................................................... 17

3.4.1 Without the mounting ears ................................................................................................................................... 17 3.4.2 With Mounting ears ............................................................................................................................................... 17

Page 4: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

4

3.5 Cabling Options ............................................................................................................................................................ 18 3.5.1 Cable Glands ......................................................................................................................................................... 18 3.5.2 Conduit Installation ................................................................................................................................................ 19 3.5.3 IP67 Membrane Cable Gland .............................................................................................................................. 19 3.5.4 Supplied Antenna .................................................................................................................................................. 20

2.4 GHz Supplied Antenna: ............................................................................................................................................... 20 3.5.5 Optional Hardware .................................................................................................................................................... 21

4 - Electrical Installation ......................................................................................................................................................... 26 Power Wiring ........................................................................................................................................................................ 26 4.2 I/O Wiring ......................................................................................................................................................................... 27

4.2.1 DI Wiring ................................................................................................................................................................... 27 4.2.2 DO (Relay) Wiring ...................................................................................................................................................... 28 4.2.3 AI Wiring ................................................................................................................................................................... 28 4.2.4 AO Wiring .................................................................................................................................................................. 28

5 - Software Installation ............................................................................................................................................................. 29 5.1 Zlinx Manager Software Overview ................................................................................................................................... 29 5.2 Computer System Requirements ..................................................................................................................................... 29 5.3 Installing Zlinx Manager Software .................................................................................................................................... 29 5.4 Installing USB Drivers ....................................................................................................................................................... 30 5.5 Establishing Connection to PC.......................................................................................................................................... 30 5.6 Starting Zlinx I/O Configuration Software ........................................................................................................................ 31 5.7 Unit Discovery .................................................................................................................................................................. 31 5.8 I/O Configuration Options ............................................................................................................................................ 33

5.8.1 Information Tab ...................................................................................................................................................... 33 5.8..2 Configuration Tab ................................................................................................................................................. 33 5.8.3 Input/Output Tab .................................................................................................................................................... 33

6 - Configuration & Operation ................................................................................................................................................ 34 6.1 Configuring the I/O ....................................................................................................................................................... 34

6.1.1 Wireless Settings ................................................................................................................................................... 34 6.1.2 Modbus Mode Settings ............................................................................................................................................. 39 6.1.3 Modbus I/O Addressing ............................................................................................................................................ 40 6.1.4 Peer-to-Peer Mode Settings...................................................................................................................................... 43 6.1.5 Input/Output Settings ............................................................................................................................................... 45 6.1.6 Exception Reporting .................................................................................................................................................. 48 6.1.7 Calibration ................................................................................................................................................................. 49 6.1.8 Zlinx I/O Monitor .................................................................................................................................................... 51 Note: Monitor does not show the inverted values for the DOs if such option is enabled..................................... 51

6.1.9 Saving the Configuration .......................................................................................................................................... 51

Page 5: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

5

6.2 Updating Zlinx I/O Firmware ............................................................................................................................................ 51 6.3 Diagnostics and Testing.................................................................................................................................................... 53

6.3.1 Testing Modbus Mode Operation ............................................................................................................................. 53 6.3.2 Testing Peer-to-Peer Mode Operation ..................................................................................................................... 53

7 - Troubleshooting .................................................................................................................................................................... 54 7.1 Testing Digital and Analog I/O ......................................................................................................................................... 54

7.1.1 Testing DI .................................................................................................................................................................. 54 7.1.2 Testing DO (Relay O/P) .............................................................................................................................................. 55 7.1.3 Testing AI in “Voltage” Mode .................................................................................................................................... 55 7.1.4 Testing AO in “Voltage” Mode .................................................................................................................................. 55

Appendix A – Default Configuration Settings ............................................................................................................................ 56 Appendix B – Product Specifications ......................................................................................................................................... 57 Appendix C – Expected Latency ........................................................................................................................................... 59 Appendix D – Modbus I/O Assignments .............................................................................................................................. 60 Appendix E – Xlinx Xtreme I/O Models & Features ........................................................................................................... 61 Appendix F – Convert Voltage/Current to DAC .................................................................................................................. 62 Appendix G – Radio Frequency Basics ....................................................................................................................................... 63 Appendix H – Transmit Power – dBm to mW Conversion ................................................................................................ 66 Glossary .................................................................................................................................................................................... 67

Page 6: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

6

1 - OVERVIEW Thank you for purchasing a Zlinx Xtreme I/O product. This product has been manufactured to the highest standards of quality and performance to ensure your complete satisfaction.

1.1 PRODUCT OVERVIEW Zlinx Xtreme I/O is an outdoor rated, industrial grade wireless product. Its IP67 rating and wide temperature ratings make it suitable for monitoring and controlling remote analog and discrete devices without the need for a separate enclosure resulting in cost and space savings.

1.2 PREREQUISITES This manual assumes that the user has basic electronics knowledge and basic understanding of wireless communications. Users are strongly encouraged to read and understand the manual in its entirety. Setting up the wireless device without proper knowledge and understanding could result in equipment damage and bodily injury.

1.3 SAFETY INFORMATION

WARNING

Exposure to RF energy is an important safety consideration. The FCC has adopted a safety standard for human exposure to radio frequency electromagnetic energy emitted by FCC regulated equipment as a result of its actions in Docket 93-62 and OET Bulleting 65 Edition 97-01. DO NOT:

Operate unless all RF connectors are secure and any open connectors are properly terminated. Operate the equipment near electrical blasting caps or in an explosive atmosphere.

All equipment must be properly grounded for safe operations. All equipment should be serviced only by a qualified technician.

1.4 INSTALLATION INFORMATION

Electrical Ratings INPUT 10.0 - 30.0 VDC Class 2 input only AMBIENT TEMPERATURE: 74°C maximum surrounding air ambient WIRING TERMINALS Copper wire only One conductor per terminal Wire Range: 10-28 AWG Tightening Torque: 0.5 to 0.6 Nm. Temperature Rating of Field Wiring: 105 °C minimum (sized for 60°C ampacity). Note: Please see the Quick Start Guide for UL Class 1/Division 2 installation instructions.

Page 7: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

7

1.5 ABOUT THIS MANUAL

This manual has been created to assist you in installing, configuring and using your Zlinx Xtreme I/O modules. Please read it carefully and follow the instructions to achieve best results. The manual is divided into the following major sections:

Table of Contents - The table of contents is hypertext linked in the electronic documentation. This allows rapid navigation to each chapter.

Overview - Overview section gives general information on product standards compliance, prerequisites and safety information.

Product Introduction - covers Zlinx Xtreme I/O models, package contents, modes of operation, IO types and characteristics and User Interface component main features.

Hardware Installation - provides necessary information for mechanical installation of Zlinx Xtreme I/O modules. Panel/machine mount and conduit mount options are covered. Range estimates are shown for various terrains under different antenna options. Installation instructions are included for both standard antenna and high gain antenna and cable options.

Electrical Installation - This section guides you through the wiring and termination for power supply as well as analog and digital I/Os.

Software Installation - This section guides you through the software and USB driver installation process. Software Configuration screens are explained in detail.

Startup & Configuration - In this section, both easy setup (via push button) and advanced setup using software are explained. Information about setting the Zlinx Xtreme I/O module in Peer-to-Peer (wire replacement) and Modbus modes are explained. Setting up I/Os, calibration, exception reporting and configuring alarms is detailed.

Use Cases - This section provides setup & configuration instructions for setting up the product in Peer-to-Peer mode, and in Modbus mode when configured with a Radio Modem.

Testing & Troubleshooting - Bench testing of the Zlinx Xtreme modules is explained in Peer-to-Peer and Modbus modes. The Built-in-Self-Diagnostics section explains self-diagnosis reporting by the module using supplied software.

Appendices - all essential reference information for Zlinx Xtreme I/O modules. Information found here includes a comprehensive references and useful tables of product properties.

Product Technical Specification - detailed technical specifications about the Zlinx Xtreme I/O modules.

Default Configuration Settings - All parameter default settings are listed.

Dimensional Drawings - The hardware dimensional drawings are shown.

Modbus I/O Register Mapping - This section explains the Modbus register mappings when I/O modules are communicating to a Modbus master (PLC/SCADA/etc.) through a radio modem.

Convert Voltage / Current to DAC - Analog to Digital conversation for voltage and current I/Os are explained.

RF Basics - This section offers a good description of Proprietary Radio Frequency Communication.

Zlinx Xtreme to Zlinx Gen II Compatibility - This section shows the compatibility of both indoor and outdoor versions of I/O modules and radio modems

Glossary - Glossary covers main terms which are relevant to the understanding of the Zlinx Xtreme I/O concept.

Page 8: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

8

1.6 ZLINX XTREME I/O PRODUCT SPECIFICATION SUMMARY Need to get an analog or a digital signal across a highway or river? Or just to the other end of your big warehouse? Zlinx Xtreme I/O can do the job faster, easier, and less expensively than stringing cable. Easy plug-and-play set-up saves installation and maintenance time. Zlinx Xtreme I/Os are built to handle extreme hot and cold outdoor weather conditions.

IP67, outdoor rated

Ranges to 40 mi (64.4 km)

Frequency ranges: ISM band, 902 to 928 MHz (long-range); 2.4 to 2.5 GHz (short range).

Modulation: FSK – Frequency Shift Keying

DSSS (2.4 GHz) and FHSS (900 MHz) technology

Signal strength indicator aids troubleshooting

3 dBi for 900 MHz; 2.1 dBi for 2.4 GHz RPSMA male dipole

Wide temperature range: -40 to +74 Cº

Versatile power: 10 to 30 VDC

Software for Windows XP (Home or Professional SP3); 2000 SP4; Vista, 7, 8, 8.1, 10

I/O Status Monitoring

CE, CSA approvals

Compatibility with Zlinx Gen II indoor models

AES Encryption – 128-bit on Short-Range models, 256-bit on Long-Range models

Software Selectable Transmitter Power

Software Selectable Over-the-Air Data Rate on Long-Range models

Exception Reporting option

Analog I/O Calibration option

Failsafe Option for Analog and Digital Outputs

Communication Failure Alarm option

Analog Inputs - True 16-bit with 0-20mA, 4-20mA, 0-5V, 0-10V independent selections

Digital Inputs – PNP or NPN independent selections

Relay Driven Digital Outputs

R

Page 9: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

9

2 - PRODUCT INTRODUCTION

2.1 ZLINX XTREME I/O PRODUCT MODELS Zlinx Xtreme I/O modules provide easy-to-use, cost-effective Peer-to-Peer (wire replacement) or Modbus connectivity solutions through license-free wireless spectrum.

Figure 2-1 Zlinx Xtreme I/O Modules . The following I/O models are available: 1) ZXT24-IO-222R2 ........ 2.4 GHz, Short Range, IP67 I/O module (2 Analog In, 2 Analog Out, 2 Digital In, 2 Relay Out) 2) ZXT9-IO-222R2 .......... 900 MHz, Long Range, IP67 I/O module (2 Analog In, 2 Analog Out, 2 Digital In, 2 Relay Out)

2.2 PACKAGE CONTENTS Zlinx Xtreme IO Modules are shipped with the following items included:

Zlinx Xtreme I/O module Standard antenna Optional mounting ears Mounting screws

o M4-0.7 25mm SS Phillips Pan Head Machine Screws – qty. 4 o M4-0.7 x 25mm SS Hex Head Cap Screws – qty. 4 o M4-0.7 DIN 985 A4 S/S Nylon Insert Lock Nuts – qty. 4

A printed version of the Zlinx I/O Quick Start Guide. Product CD (consisting of Zlinx Xtreme I/O documentation and Zlinx Manager Configuration Software)

o Zlinx I/O Manager Configuration Software. o Zlinx I/O Firmware Updater. o USB Driver for Xtreme Module.* o Zlinx Xtreme I/O Manual in PDF format. o Zlinx Xtreme Radio Modem Manual in PDF format. o Zlinx Xtreme I/O Quick Start Guide in PDF format.

Note: *A separate USB cable (not included, sold separately) is necessary for programming the I/O module.

Note: the Cable Glands cannot be used for UL Class 1/Division 2 applications. Please see the Quick Start Guide for additional information about UL Class 1/Division 2 installation instructions.

Page 10: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

10

2.3 ZLINX XTREME I/O MODES OF OPERATION Zlinx Xtreme I/O systems can operate in Peer-to-Peer or Modbus Slave RTU modes. 900 MHz I/O modules can be configured as repeaters to extend the radio coverage distance.

2.3.1 PEER-TO-PEER I/O MODE Peer-to-Peer configuration of IO modules is used in wire replacement applications for analog/digital IOs where cabling is not possible or is very expensive. Typical examples include remote monitoring and control applications in clean rooms, buildings across parking lots or highways, remote water or fuel tank level monitoring, remote pump station control, etc. In Peer-to-Peer mode, two Zlinx I/O modules of the same type can be configured to provide wire replacement functionality. Input count of one module must match the output count of the other module for both digital and analog types. For example, a pair of 2 analog input, 2 analog output, 2 digital input and 2 digital output I/O modules or a pair of 4 digital input and 4 digital output modules can be configured in peer-to-peer mode. A pair of the following I/O modules is suitable for Peer-to-Peer configuration:

- ZXT9-IO-222R2 - ZXT24-IO-222R2

In this mode, one Module is configured as a Master and the other as a Slave. It does not matter which end of the link is the Master and which is the Slave. Analog and Digital Input signals connected to one module are mapped to the corresponding analog and digital outputs on the other module and vice versa. Peer-to-Peer mode configuration can be established between outdoor rated Zlinx Xtreme IOs and indoor rated Zlinx Gen II IOs.

Figure 1-2 Peer-to-Peer Mode

Page 11: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

11

2.3.2 MODBUS I/O MODE In Modbus mode, the Zlinx Xtreme I/O modules are configured as Modbus Slaves and can be controlled and monitored by a Modbus RTU Master (such as a PLC, SCADA, HMI, etc). A serial radio modem acts as a data pipe & has to be connected to the Modbus Master through its serial port. Up to 247 wireless I/O modules can be remotely monitored and controlled by the Modbus master. The I/O signals appear in the Modbus register map resident in the I/O module memory that can be accessed by the master through the radio modem. Refer to Appendix D for information about the Modbus register mapping.

Figure 2-2 Modbus I/O Mode

In Modbus I/O mode, up to 247 Zlinx I/O modules can be connected to a Modbus RTU master through a radio modem. Modules of both Zlinx Xtreme (outdoor) and Zlinx Gen II (indoor) types can be mixed and matched as long as their frequency rating is the same.

2.3.3 REPEATER MODE (900 MHZ MODEL ONLY)

Figure 2-3 I/O Module as a Repeater When a Zlinx Xtreme I/O Module is configured as a repeater, it relays data from a Modbus modem or an I/O Module and extends the range of communication. In a Peer-to-Peer system, a repeater unit can be placed between the Master and the Slave IO modules. Note: Placing a repeater in a system will introduce an additional delay of 4ms.Each repeater introduced in a system will cut the data bandwidth to half.

Page 12: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

12

2.4 I/O TYPES AND CHARACTERISTICS The analog inputs, analog outputs and digital inputs are not isolated. They share the same common within the module. Digital outputs are isolated through relay contacts.

2.4.1 DIGITAL / PULSE INPUTS Digital Inputs can detect the status of discrete control devices, contact closures, transistor switches or on/off DC voltage signals (low or high logic levels). Voltages below 1 VDC are interpreted as a low state. Voltages above 1 VDC up to 48 VDC are interpreted as a high state. Each digital input is selectable between NPN (sinking) and PNP (sourcing) types. The digital Input terminals can accept voltages in the range 0-48VDC. The digital inputs can also be used as a pulse/frequency input in Modbus Mode only. The maximum pulse frequency is 20 KHz.

2.4.2 DIGITAL OUTPUTS Digital Outputs send on/off signals (low or high logic levels) to drive external devices such as indicators, relay coils or the inputs of other equipment such as PLCs, SCADA, etc. Digital Outputs in Zlinx Xtreme I/O modules have a Form C Relay (common, normally open and normally closed) rated at 4A and 250VAC.

2.4.3 ANALOG INPUTS Each analog input can be individually configured as voltage or current types. Following selections are available:

a) 0-10 VDC b) 0-5 VDC c) 0-20 mA d) 4-20 mA

The data is automatically scaled as a 16-bit register (0-65,535) for full scale in the Modbus register. To see how to calculate corresponding values in Modbus, refer to section Appendix F.

2.4.4 ANALOG OUTPUTS Each analog output can be individually configured as voltage or current types. Following selections are available:

a) 0-10 VDC b) 0-5 VDC c) 0-20 mA d) 4-20 mA

The data is automatically scaled as a 12-bit register (0-4,096) for full scale in the Modbus register. To see how to calculate corresponding values in Modbus, refer to section Appendix F.

Page 13: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

13

2.5 USER INTERFACE COMPONENTS

External and internal views of the I/O module are shown as below.

Figure 2-4 External View of Zlinx Xtreme I/O module

USB Port Configuration Pushbutton

Power & I/O Terminals

Figure 2-5 Internal View of Zlinx Xtreme I/O module

Page 14: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

14

2.5.1 RADIO SIGNAL STRENGTH INDICATOR (RSSI) LEDS Signal Strength LEDs provide an indication of the signal strength of the received radio signal. Eight Green LEDs in a bar graph format show the signal strength from Weak to Strong. The table below explains the RSSI LEDs:

LEDs Number Turned ON Signal Strength

0 No Signal 1-3 Weak 4-6 OK 7-8 Strong

Figure 2-7 RSSI LED Status Table

2.5.2 MODE LEDS The I/O module operates in one of the following 3 modes and its status is shown by the corresponding green LEDs:

- Modbus - Peer-to-Peer Master - Peer-to-Peer Slave

2.5.3 WIRELESS LED This LED will flash whenever wireless data is transmitted or received.

2.5.4 POWER LED 1) A green status LED indicates that an adequate DC power is available to the module. 2) This LED will flash on Comm. Fail.

2.5.5 I/O STATUS LEDS Green status LEDs show the status of the Digital Inputs and Relay Outputs in the I/O module.

2.5.6 CONFIGURATION PUSH BUTTON The Configuration Button allows the user to select one of the following I/O operation modes without a PC:

- Modbus - Peer-to-Peer Master - Peer-to-Peer Slave

Follow the steps below to change the I/O module configuration mode using the Configuration push-button. 1) Press and HOLD the push-button until all Mode LEDs flash. 2) A single LED will begin to flash, which depends on the mode the device is currently in. An example would be the P2P Master LED

will flash if the device was in P2P Master Mode. 3) Pressing the Configuration push-button will increment through the other modes; P2P Slave, Modbus, etc. 4) If the push-button is not pressed for 4 seconds, the device will exit and select the mode that was indicated by the flashing LED.

Page 15: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

15

The following default settings established when the mode is changed:

ZXT24-IO-222R2 ZXT9-IO-222R2 Peer-to-Peer Master Mode

Radio Network 0x0c 0x00 Radio ID Number 0x11 0x11 Radio Output Power (4) 63mw (4) 1w Number of Retries 10 10 AES Security Disabled Disabled P2P Address 1 1 OTA Baud Fixed* 115200 P2P Polling Rate 0 sec 0 sec

Peer-to-Peer Slave Mode Radio Network 0x0c 0x00 Radio ID Number 0x11 0x11 Radio Output Power (4) 63mw (4) 1w Number of Retries 10 10 AES Security Disabled Disabled P2P Address 1 1 OTA Baud Fixed* 115200 P2P Slave Timeout 30 sec 30 sec

Modbus Mode Radio Network 0x0c 0x00 Radio ID Number 0x11 0x11 Radio Output Power (4) 63mw (4) 1w Number of Retries 10 10 AES Security Disabled Disabled Modbus Address 1 1 OTA Baud Fixed* 115200 Modbus Slave Timeout 30 sec 30 sec

* “Fixed” for OTA Baud means that this parameter cannot be changed and is equal to 250 Kbps. Refer to section 6 for parameter descriptions.

2.5.7 POWER & I/O TERMINALS Screw terminals are provided for Power & I/O interface connections as shown. Refer to Chapter 4 for wiring information.

2.5.8 USB PORT The USB port is used to configure the I/O module and for firmware updates. The I/O module must be connected and powered for the Zlinx Manager software to detect the IO module. Refer to section 4 for software installation and section 5 for programming the unit.

Page 16: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx™ Xtreme Wireless I/O

3 - HARDWARE INSTALLATION 3.1 RECOMMENDED PRACTICE BEFORE INSTALLATION Before installing a new system, it is recommended to bench test the complete system and make sure the modules function satisfactorily. Refer to appropriate sections for your setup in Chapter 8 for reference. In actual installations, poor communications can be caused by:

Incorrectly installed antennas Radio interference Obstructions in the radio path Bad weather Signal out of range

If the radio path is a problem, higher gain antennas would help improve the range.

3.2 RF SITE CONSIDERATIONS When installing any radio equipment, it is important to give careful consideration to the installation location and the surrounding area. Radio transmission and reception is affected by absorption, reflection and refraction of the radio signals. These factors are determined by the distance between the transmitting and receiving antennas, the type, position and amount of obstructions, antenna heights, frequency band and RF power used and other factors. There are several ways to optimize the RF environment to ensure satisfactory performance. A partial list of these follows:

Select the Zlinx Xtreme I/O radio option that provides sufficient power for your application. Lower frequencies travel farther and are less affected by absorption in materials. Higher power levels generally provide greater penetration through objects.

Select installation locations that come as close as possible to providing line-of-sight access between the antennas.

Avoid installation locations where metal objects may block, reflect, refract or cause multi-pathing of radio frequencies. In some cases, reflections may enhance reception but, in others, it can cause problems.

Select installation locations to increase antenna heights. Consider signal loss across antenna cables and connectors. User larger cables for low signal loss. Select equipment enclosures made of materials that minimize RF attenuation. Avoid locations with other radio equipment that may cause interference. In some cases alternate types of antennas (more directional) or remote antenna mounting (outside

of enclosures or at a higher elevation) may be required. As necessary, a site-survey should be carried out. Sometimes small changes in location can make a significant improvement to coverage. For RF information, see Appendix G.

Page 17: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

17

3.3 DIMENSIONAL INFORMATION The dimensional information with mounting holes is shown below.

Figure 3-1 Dimensional Information

3.4 MOUNTING OPTIONS The Zlinx Xtreme I/O module can be panel or machine mounted. The module can be mounted with or without the optional mounting ears.

3.4.1 WITHOUT THE MOUNTING EARS The Zlinx Xtreme can be mounted on a back panel or a machine by removing the top lid. The top lid is removed by unscrewing the 4 corner screws. The module can be mounted using the supplied screws and nuts through the corner holes. Once secured, fasten the top cover.

3.4.2 WITH MOUNTING EARS 4 optional mounting ears and screws are supplied as accessories. The ears can be attached to the Zlinx Xtreme by removing the top cover and securing through the corner holes. The module then can be mounted on the panel by marking the position of the holes on the back panel. Fig 3-2 shows the mounting scheme with ears.

Page 18: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

18

Figure 3-2 Mounting Ear dimensions

3.5 CABLING OPTIONS The Zlinx Xtreme module has two holes of 0.875” diameter for cable installation. Cable gland or conduit mounting is possible. A cable gland and conduit hub are included as accessories. Unused hole must be plugged by the supplied membrane gland in order to maintain IP67 rating.

3.5.1 CABLE GLANDS Note: The Cable Glands cannot be used for UL Class 1/Division 2 applications. Please see the Quick Start Guide for UL Class 1/Division 2 installation instructions.

A Cable Gland is used to maintain the water tight rating while allowing a cable to enter the enclosure. The assembly consists of black molded nylon body, hex nut, cable nut and a rubber gasket and cable seal.

Figure 3-3 IP67 Cable Gland

Page 19: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

19

Follow the steps below to install the cable gland: 1. Insert the non-tapered end of the body (D) through the conduit knock-out on the I/O module enclosure. 2. Place the gasket around the body on the outside of the enclosure. 3. Thread the hex nut onto the body from the inside of the enclosure. 4. Insert the cable through the cable gland into the enclosure. Ensure you leave enough slack in the cable

to reach the terminal blocks. 5. Place the cable nut onto the cable being careful to position the threaded side so that it can be attached to

the cable body. 6. Tighten the cable nut. This will cause the tapered end of the cable to compress, ensuring a water-tight

seal.

3.5.2 CONDUIT INSTALLATION Note - Unused Conduit Openings: UL Class 1/Division 2 installations require a UL Recognized plug (UL Category Code QCRV2) be used when a conduit opening is not being used.

A conduit hub is supplied with the Zlinx Xtreme I/O module where conduit installation is preferred to route the cables. It is suited to connect ½” or 3/8” conduit fittings and consists of a Body, Nut, and Gasket suitable for IP67 rating. It is used to secure threaded ½ inch rigid service entrance conduit.

Figure 3-4 ½ inch Threaded Conduit Hub with dimensions

1. Insert the treaded end of the body into the conduit knock-out from the outside of the enclosure. The rubber gasket should be on the outside of the enclosure.

2. Thread the nut onto the conduit body from inside the enclosure. 3. ½ Inch, rigid, threaded conduit can be attached to the threaded hub.

3.5.3 IP67 MEMBRANE CABLE GLAND Note: The cable glands cannot be used for UL Class 1/Division 2 applications. Please see the Quick Start Guide for UL Class 1/Division 2 installation instructions.

The membrane cable gland can be used to plug an unused hole in the enclosure or to route a cable.

Figure 3-5 IP67 Membrane Gland

Stuff the cable gland into the knock-out hole with the narrow end toward the inside of the I/O module enclosure. The enclosure wall will fit into the indentation between the inside and outside portions of the gland.

Page 20: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

20

3.5.4 SUPPLIED ANTENNA 900 MHz Supplied Antenna: Your 900 MHz product comes supplied with a “rubber duck” style antenna which can be articulated up to 90 degrees. Then antenna is a ¼-wave dipole with an omni-directional pattern and vertical polarization. It is recommended that your I/O product be mounted with the antenna on the top, perpendicular with the horizon.

Figure 3-6 ZXT9-IO-222R2 Supplied Antenna

Antenna Specifications:

Impedance: 50Ω Connector: RPSMA Female VSWR: 2.0 maximum (in band) Gain: 3.0 dBi Polarization: Vertical Part Number: ZXT9-ANT1

2.4 GHZ SUPPLIED ANTENNA: Your Zlinx Xtreme 2.4 GHz product comes supplied with a “rubber duck” antenna which can be articulated up to 90 degrees. Then antenna is a ¼-wave dipole with an omni-directional pattern and vertical polarization. It is recommended that your Zlinx Xtreme product be mounted with the antenna on the top, perpendicular with the horizon.

Figure 3-7 ZXT24-IO-222R2 Supplied Antenna

Antenna Specifications:

Impedance: 50Ω Connector: RPSMA Female VSWR: 2.0 maximum (in band) Gain: 2.1 dBi Polarization: Vertical Part Number: ZZ24D-ANT1

Page 21: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

21

3.5.5 OPTIONAL HARDWARE Optional high gain antennas may be necessary to extend the range of the wireless radios. Omni-directional antennas help propagate the radio frequency signals 360°. Yagi antennas are used for directional pointing. For point-to-point (aka peer-to-peer) applications, 2 Yagi antennas would offer the best performance. For point-to-multi point applications, an omni-directional antenna at the central location with Yagi antennas at remote radios would offer the best performance. These high gain antennas must be mounted at elevated locations. Line-of sight is necessary for better communication. The figures below show Point-to-Point and Point-to-Multipoint installations using Omni and Yagi antennas.

Figure 3-8 Point-to-Point System Figure 3-9 Point-to-Multi Point Modbus System Extension cables are available to connect the radios to the antennas. Lightning arrestors are highly recommended in outdoor installations where thunderstorms and lightning are commonplace.

3.5.5.1 HIGH GAIN OMNI ANTENNA An omni-directional antenna is an antenna system that radiates power uniformly in one plane with a directive pattern shape in a perpendicular plane. This pattern is often described as "donut shaped". Omni-directional antenna can be used to link multiple directional antennas in outdoor point-to-multipoint communication. These omni-directional antennas are a good choice if you need to mount your antenna on a mast to increase its elevation. Please note that mounting brackets must also be purchased. Also note that these antennas have an N style connector. Refer to section 3.9 to select the correct cable.

Figure 3-10 Representative Omni Antenna

Page 22: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

22

FG9023 – High Gain Omni Directional (900 MHz) Use with: ZXT9 radios (900 MHz) Impedance: 50Ω Connector: N Female VSWR – 2:1 maximum (in band) Gain – 3 dBi Polarization – Vertical Length – 25 inches Mounting Brackets (Sold Separately) – FM2

FG9026 – High Gain Omni Directional (900 MHz)

For Use with: ZXT9 radios (900 MHz) Impedance: 50Ω Connector: N Female VSWR – 2:1 maximum (in band) Gain – 3 dBi Polarization – Vertical Length – 65 inches Mounting Brackets (Sold Separately) – FM2

FG24008 – High Gain Omni Directional (2.4 GHz)

For Use with: ZXT24 radios (2.4 GHz) Impedance: 50Ω Connector: N Female VSWR – 1.5:1 maximum (in band) Gain – 8 dBi Polarization – Vertical Length – 24.5 inches Mounting Brackets (Sold Separately) – FM2

3.5.5.2 HIGH GAIN YAGI ANTENNA A Yagi-Uda antenna, commonly known simply as a “Yagi antenna” or “Yagi”, is a directional antenna system consisting of an array of a dipole and additional closely coupled parasitic elements (usually a reflector and one or more directors). The dipole in the array is driven, and another element, typically 5% longer, effectively operates as a reflector. Other parasitic elements shorter than the dipole may be added in front of the dipole and are referred to as directors. This arrangement increases antenna directionality and gain in the preferred direction over a single dipole. Since Yagi antennas are directional, they must point directly at the other antenna through a clear line-of-sight. These directional antennas are a good choice if you need to mount your antenna on a mast to increase its elevation. Note that these antennas have an N style connector. Refer to section 3.9 to select the correct cable.

Figure 3-11 Enclosed Yagi – Model YE240015 for 2.4 GHz Models

Page 23: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

23

Figure 3-12 Representative Yagi Antenna

YS8963 – High Gain Yagi (900 MHz) - For Use With: ZXT9-RM (900 MHz)

Impedance: 50 Ω Connector: N Female VSWR – 1.5:1(in band) Gain – 6 dBi Polarization – Vertical Length – 16.8 in Mounting Brackets – Included

YS8966 – High Gain Yagi (900 MHz) - For Use With: ZXT9-RM (900 MHz)

Impedance: 50 Ω Connector: N Female VSWR – 1.5:1(in band) Gain – 9 dBi Polarization – Vertical Length – 27.8 in Mounting Brackets – Included

YS89612 – High Gain Yagi (900 MHz) - For Use With: ZXT9-RM (900 MHz)

Impedance: 50 Ω Connector: N Female VSWR – 1.5:1(in band) Gain – 11 dBi Polarization – Vertical Length – 49 in Mounting Brackets – Included

YE240015 – High Gain Yagi (2.4 GHz) - For Use With: ZXT24-RM (2.4 GHz)

Impedance: 50 Ω Connector: N Female VSWR – 1.5:1(in band) Gain – 12.5 dBi Polarization – Vertical Length – 18 in Mounting Brackets – Included

3.5.5.3 ANTENNA CABLES& CONNECTORS Antenna cables and connectors must be used when extending the standard or high gain antenna for outdoor antenna applications. Appropriate cable and connector must be chosen. It is important to know that RF signal is lost across the cables and connectors and hence for better performance, the cable length and connectors must be kept to a minimum. Also, it is important to select a cable that matches the radio’s impedance. An impedance mismatch will cause the radio link to become inefficient and could damage the radio. Selecting the incorrect cable could also cause significant signal loss. A rule of thumb is, for every 3 dB of loss, your system will lose one-half the output power emitted from the radio.

Page 24: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

24

Three cable types are available, viz. LMR100, LMR195, and LMR400. LMR400 cable offers lower loss but is thicker and more difficult to work with. LMR100 is thin and easy to work with, but has a larger loss. It is recommended that you use the shortest possible cable run in your application.

Cable Type 900 MHz Loss Per 100 Feet 2.4 GHz Loss Per 100 Feet Diameter

LMR-100 22.8 dB 38.9 dB 0.110 in

LMR-195 11.5 dB 19.0 dB 0.195 in

LMR-400 3.9 dB 6.8 dB 0.405 in

Figure 3-13 Antenna Cable Options and Signal Loss Information

Figure 3-14 LMR400 Cable Cross Section

Figure 3-15 LMR195 Cable Cross Section

Figure 3-16 LMR100 Cable Cross Section

Along with the cable, a proper connector must be chosen. The I/O module uses an RPSMA Male (plug) connector. The optional high gain antenna has an N type Female connector. Therefore, an antenna cable that has a RPSMA Female jack at the module end and a N type Male connector at the antenna end must be chosen. If the supplied antenna needs to be extended, a cable with an RPSMA Female jack at the module end and an RPSMA Male (plug) at the antenna end must be selected since the supplied antenna has an RPSMA female (jack).

Page 25: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

25

Antenna Cable Part Numbers Following are standard cables available for purchase. The cable part numbering format is as follows:

TTTT-AABB-LLLL Where,

TTTT = Cable Type (400M = LMR400, 195M = LMR195, 100M = LMR195) AA = Connector A (NM = N-Male, SL = RPSMA (Plug)

BB = Connector B (NM = N-Male, SL = RPSMA (Plug)

LLLL = Length in inches (ex: 6 = six inches, leading zeros are not necessary)

For example, a 400M-NMSL-24 is an LMR400 cable with an N Male on one end and a RPSMA plug on the other, 24 inches in length.

3.5.5.4 LIGHTNING ARRESTORS A lightning arrestor can prevent damage to the radio due to high energy transients during lightning strikes. The arrestors limit surges to less than 45 Volts in approximately 100 nanoseconds. A gas discharge tube changes from an open circuit to a short circuit in the presence of energy and voltage surges giving those surges a direct path to ground, thus protecting equipment. They are designed with a rugged housing and high quality plated brass "N" connectors. It also features a user replaceable gas discharge tube (LA350GT) and are available in three models: the LABH350NN and the LABH2400N both allow bulkhead mounting and connector pass-through and the LAIL350NN allows inline placement only.

3.5.5.5 IP67 POWER SUPPLY

Figure 3-17 IP67 Power Supply

An optional IP67 power supply (Model# CLG-60-24) is available suitable for outdoor applications. The Power Supply Specifications:

Input Voltage: 90 ~ 295 VAC Output Voltage: 24 VDC Rated Power: 60 W Environmental Rating: IP67, Indoor / Outdoor Temperature Rating: -30 to +70 °C

Page 26: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

26

4 - ELECTRICAL INSTALLATION Please see the Quick Start Guide for UL Class 1/ Division 2 installation instructions. Both power and I/O signals are connected to the terminal block provided in the I/O module. The terminal block can be accessed by removing the top cover and are provided at the bottom. Figure 4-1 shows the layout. Consider the following requirements for cable connections and terminations.

Wiring Terminals – Use Copper Wire Only, One Conductor per Terminal Wire Range: 10-28 AWG Tightening Torque – 0.5 to 0.6 Nm Temperature Rating of field installed conductors – 105 °C minimum, sized for 60 °C ampacity

Figure 4-1 I/O Terminal Layout

POWER WIRING The radio modem requires a DC power supply from an external source. The permissible voltage range is 10 to 30 VDC. The typical power consumption is as follows: ZXT24-IO-222R2:

Type: 1.7W Max: 4.5W

ZXT9-IO-222R2:

Type: 2.1W Max: 6.8W

An optional IP67 power supply shown in Section 3.5.5.5 may be used. Connect the positive and negative power leads to the Power In(+) and Power In(-) terminals on the terminal block.

PWR IN +10-30 Vdc

(External Supply)PWR IN -

V+

Com

Figure 4-2 Power Wiring Connection

Page 27: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

27

4.2 I/O WIRING The I/O module has the following options: PNP/NPN for digital I/Os and voltage/current for analog I/Os. The follow the wiring recommendations help the user to connect the devices to the I/O module.

4.2.1 DI WIRING The digital inputs are software configurable for PNP (sourcing) and NPN (sinking) connections. Each Input selection can be independent of the other I/Os. PNP is chosen as the default setting. The configuration can be changed using the Manager Software as explained in Chapter 6. The following diagrams show typical connection wiring for both PNP and NPN connections with internal module power supply:

PWR IN +

DIx

(a) PNP (Sourcing) Input Wiringwith Internal Power Supply

DIx

(b) NPN (Sinking) Input Wiring with Internal Power Supply

Com

Figure 4-3 Typical Digital Input Wiring for PNP and NPN Connection Types (with internal PS)

If an external power source is used for the digital input connections, the external power supply common should be connected to the module power supply common. The diagrams below show the connection scheme:

+VDIx

(c) PNP (Sourcing) Input Wiring with External Power Supply

ComCom

DIx

(d) NPN (Sinking) Input Wiring with External Power Supply

ComCom

Figure 4-4 Typical Digital Input Wiring for PNP and NPN Connection Types (with external PS) A pulse/frequency input can be connected to the digital input as follows:

DIx

(e) Pulse Input

Com

Figure 4-5 Pulse Input Connection

Page 28: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

28

4.2.2 DO (RELAY) WIRING Common, NO (normally open) and NC (normally closed) contacts of the relays are brought to terminals for wiring. The following diagram shows typical connection wiring for relay outputs:

NO

(a) NO Connection

Com

NC

V+ / Line

V- / Neutral

Solenoid

(b) NC Connection

NO

Com

NC

V+ / Line

V- / Neutral

Light

Figure 4-6 Typical Digital Output Wiring for Relay Outputs

4.2.3 AI WIRING The following diagram shows typical connection wiring for Analog Inputs:

AINx

COM

Voltage or current Input

+

-

Figure 4-7 Typical Analog Input Wiring

4.2.4 AO WIRING The following diagram shows typical Analog Output wiring:

AOutx

COM

(a) Voltage Output

AOutx

COM

(b) Current Output

Figure 4-8 Typical Analog Output Wiring

Page 29: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

29

5 - SOFTWARE INSTALLATION

5.1 ZLINX MANAGER SOFTWARE OVERVIEW Zlinx Manager Software is supplied along with the module in a CD. The software must be installed in a PC and launched to change the configuration of the wireless I/O module.

5.2 COMPUTER SYSTEM REQUIREMENTS The Zlinx Manager software requires the following computer hardware and operating systems:

A PC with one USB port available. Support Windows O/S:

o XP, 32 & 64 bit (Home or Professional with SP1, SP2 or SP3) o 2000, 32 & 64 bit o Vista, 32 & 64 bit o 7, 32 & 64 bit o 8 & 8.1, 32 & 64 bit o 10, 32 & 64 bit

5.3 INSTALLING ZLINX MANAGER SOFTWARE The Zlinx manager software is available in the CD ROM which is included with the I/O module. Insert the CD into the CD drive. The installation process will start automatically. If it does not, then navigate to the CD ROM drive using Windows Explorer software and then double click the executable file on the CD.

Note: 1) Install the Zlinx Manager Software before connecting the I/O module to the PC.

2) The software is also available for download from: http://www.advantech-bb.com.

1. The Welcome screen will be displayed.

Figure 5-1 Installation Welcome Screen

2. Follow the prompts to install the software.

3. The Installation Complete screen as shown below will be displayed. Click the Finish button.

Page 30: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

30

Figure 5-2 Installation Completion Screen

5.4 INSTALLING USB DRIVERS The USB drivers will automatically be installed when the software is installed. If the "Add New Hardware" wizard appears when the hardware is attached, the USB drivers are available in the "USB Drivers" folder on the CD-ROM.

5.5 ESTABLISHING CONNECTION TO PC To connect Zlinx Xtreme I/O to a PC:

1. Open the front cover of the Zlinx Xtreme I/O module. 2. Apply power to the I/O unit. 3. Connect the PC USB port to the USB port of the Zlinx Xtreme I/O Module using a USB cable. 4. Now the Zlinx Xtreme I/O module is ready to be configured from the PC.

Zlinx Xtreme I/O (inside

view)

Configuration PC

USB Cable

Figure 5-3 PC to I/O Module Connection

Note: In order for the PC to see the Xtreme module’s COM port, the Xtreme module must be powered. If power is removed from the Xtreme module, the COM port will disappear from the PC even if you are configuring or monitoring the Xtreme module.

Page 31: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

31

5.6 STARTING ZLINX I/O CONFIGURATION SOFTWARE

1) From the Windows Start menu, start the Zlinx Manager software. Zlinx Manager is common for both the I/O Module Configuration and the Radio Modem configuration. The default path is:

Programs/B+B SmartWorx/Zlinx/Zlinx Manager/Zlinx Manager

Zlinx Manager screen opens offering navigation to Zlinx Manager or Radio Modem Manager.

Fig 5.4 Zlinx Manager Start Menu

2) Click on the Zlinx I/O. The following I/O menu screen opens. This screen allows access to I/O Configuration, Firmware Update and Monitor I/O Status

Fig 5.5 Zlinx Manager I/O Menu Screen

5.7 UNIT DISCOVERY

1. To go to the configuration window, click on the Zlinx I/O Configuration.

2. The Zlinx Xtreme I/O splash window appears briefly, followed by the discovery window.

3. The Connection drop down list defaults to Automatic discovery. The software scans through COM ports looking for Zlinx Xtreme I/O devices. The scan starts with the most recently used COM port in which a device was found.

Page 32: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

32

Fig 5.6 I/O Module Discovery Window

During the scan, the Progress box displays information about the scanning process. The bar graph near the bottom of the window indicates progress.

4. If the device is not found, the Progress box displays: “The device was not found on any serial port.”

a. Check the power supply and serial cable connections.

b. Click the Connect button. The connection process will be repeated and the device should be found.

5. If automatic connection is not desired, a particular COM port (1 to 16) can be specified:

a. Select the COM port number from the Connection drop down list.

b. Click the Connect button to initiate the connection process.

Note: Clicking the Stop button stops the module discovery process.

6. If the device is found, the I/O Configuration Menu screen opens.

Fig 5.7 I/O Configuration Menu

Page 33: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

33

The I/O Configuration Menu contains:

Three tabbed panes: Information, Configuration, Input/Output.

A Help sidebar containing information and hints related to the current tab. If the sidebar is not visible, enable it by going to Help > Sidebar.

A graphic display of the I/O modules discovered.

A Status bar (at the bottom) showing the COM port and communications parameters: baud rate, parity, data bits, stop bits and flow control.

An Update button used to save configuration parameters to the modules.

An Exit button.

5.8 I/O CONFIGURATION OPTIONS The following tabs are available in the I/O Configuration Manager. The configuration details are explained in Chapter 6.

5.8.1 INFORMATION TAB The Information tab displays a tree structure listing:

I/O Modules detected and their model numbers.

Generation number.

Firmware version number for each module.

Hardware version number for each module.

Radio firmware version number for the Xtreme Module.

Radio hardware version number for the Xtreme Module.

5.8..2 CONFIGURATION TAB The Configuration tab contains fields that allow configuration of:

Wireless (Radio) parameters: Transmit Power, Channel Number, Network Identifier, Repeater Mode and AES Encryption settings.

Communications Modes: Peer-to-Peer Master, Peer-to-Peer Slave, Modbus and related parameters.

Parameters corresponding to the chosen communication mode.

5.8.3 INPUT/OUTPUT TAB The Input/Output tab contains:

A tree structure listing input and output types for each module.

Input and output configuration options.

Page 34: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

34

6 - CONFIGURATION & OPERATION The I/O Configuration software is used to configure the wireless I/O module. The I/O module can be configured to operate in Peer-to-Peer (wire-replacement) or Modbus Modes receiving commands from a Modbus RTU Master. Digital Inputs can be configured to operate in Discrete (on/off) or Counter modes in PNP or NPN configuration, and Analog Inputs and Outputs are configurable for voltage or current loop operation with selectable ranges. Digital Outputs are Relay Outputs. Section 2.4 provides more information on I/O types and characteristics.

6.1 CONFIGURING THE I/O To enable the features described below (except Monitor):

5. Connect the I/O module to the Configuration PC

6. Start the Configuration Manager.

7. Choose Zlinx I/O Configuration.

8. The Configuration Menu opens as shown in Figure 6-2. (See Section 5.6 for more details).

6.1.1 WIRELESS SETTINGS These settings are common for the I/O module irrespective of its operating mode, viz. Peer-to-Peer or Modbus I/O. The I/O Modules can be configured for operation with different transmitter output power. They can also be configured to operate on several different radio channels. This allows multiple Zlinx Xtreme I/O systems to operate in the same area without interference. The number of different systems can be further increased by configuring a unique Network Identifier (which selects the Frequency Hopping sequence). 900 MHz modules also can be used as repeaters, to extend the range of a system. Over-The-Air (OTA) data rate can also be adjusted to increase range. A lower OTA data rate will increase the effective range of the radio, but will also increase the total throughput time.

Xtreme Module Transmit Power Selectable

RF OTA Data Rate AES Encryption

ZXT24-IO-222R2 (SR) Yes No 128-bit

ZXT9-IO-222R2 (LR) Yes Yes 256-bit

Fig 6-1 Transmit Power vs. OTA and AES Encryption for Radios

Page 35: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

35

Fig 6-2 I/O Configuration Tab

6.1.1.1 TRANSMIT POWER In the Transmit Power drop down list, select your desired output power in mW. The conversion between dBm and mW is shown in Appendix H. Increasing the power will increase maximum range and electrical power consumption. Setting this value too high may violate regulatory transmission limits for your region and could cause harmful interference to other devices. As a responsible user, make sure the transmitted power is within allowed limits for your region.

Xtreme Module Power Selections Factory Default

ZXT24-IO-222R2 10mW, 16mW, 25mW, 40mW, 63mW 63mW

ZXT9-IO-222R2 1mW, 10mW, 100mW, 500mW, 1000mW 1000mW

Fig 6-3 Transmit Power Ranges

6.1.1.2 CHANNEL NUMBER Set the Channel Number field to match the channel used by the device with which it will communicate.

a. If that device is another Zlinx Xtreme I/O module, set the channel numbers the same when configuring each of them.

b. If the device is a Modbus Radio Modem, the modem must be configured by using Zlinx Radio Modem Configuration Manager to match the Xtreme Module’s channel number.

Page 36: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

36

c. Channel Number range is different for 900 MHz and 2.4 GHz Zlinx Xtreme I/Os. The table below shows the ranges and commands in hexadecimal values:

Type/Range Xtreme Module Channel

Number Range Factory Default

ZXT24-IO-222R2 0x0C to 0x17 0x0C ZXT9-IO-222R2 0x00 to 0x09 0x00

Fig 6-4 Channel Number Range

6.1.1.3 NETWORK IDENTIFIER

a. The Network Identifier field must match the Network Identifier used by the device with which it will communicate.

b. If that device is another Zlinx Xtreme I/O Module, set its Network Identifier the same as the local I/O Module.

c. If that device is a Modbus Radio Modem, its Network Identifier must be configured by using the Radio Modem Configuration Manager to match that of the I/O module. Refer to the Radio Modem manual for configuration information.

d. The Network Identifier range is different for both radio types (2.4 GHz and 900 MHz). The table below shows the channel number ranges in hexadecimal values.

Type/Range Xtreme Module Network

Identifier Range Factory Default

ZXT24-IO-222R2 0x00 to 0xFF 0x00

ZXT9-IO-222R2 0x11 to 0xFF 0x11

Fig 6-5 Network Identifier Range

e. If the Network Identifier is changed to outside the default value, it must be matched in the other device as well.

6.1.1.4 REPEATER MODE Select the Repeater checkbox if the Zlinx Xtreme I/O Module is to be used as a repeater, re-broadcasting I/O data received in Modbus or Peer-to-Peer Modes. The default value of the Repeater field is unchecked.

NOTE: Repeater Mode can only be implemented on the ZXT9-IO-222R2 900 MHz Xtreme I/O Modules.

6.1.1.5 RF DATA RATE 900 MHz Xtreme Modules allow you to configure the Over-The-Air RF data rate. This data rate may be configured for 9600 baud or 115200 baud. Using 9600 baud on these modules increases the effective range of the module.

Page 37: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

37

AES ENCRYPTION The following AES Encryption options are available

a. Disabled – Select this option if you do not desire to encrypt your network.

i. Check the Disable option and press the Update button on the bottom of the screen.

b. Hexadecimal Key - Select this option if you desire to use a hexadecimal stream to encrypt your network.

i. On the first Xtreme Module, check the Hexadecimal Key option. Press the Generate Random Key button. A random hexadecimal key will appear in the Key Box. (You can type your own hex key into the Key Box, but it is recommended that you use the random generator). This key will not be stored in the module until the Update button on the bottom of the screen is pressed. Do not press the update button yet!

ii. Copy this key into a text file. You will need it to configure the key in the downstream Zlinx Xtreme Module or radio modem.

1. Highlight the characters displayed in the Key Box using your mouse and left mouse button.

2. When all the characters are highlighted, press “CTRL” and “C” keys simultaneously on your keyboard. This copies the characters to the Windows clipboard.

3. Open Note Pad and press “CTRL” and “V” keys on your keyboard. The characters will appear. Save this file and use it to configure the key in the downstream module.

iii. Press the Update button on the bottom of the screen.

c. Text Key – Select this if you desire to use a text sequence to encrypt your network.

i. On the first Xtreme Module, select the Text Key option. Type text into the key box. The text is limited to 128 or 256 bits (as applicable). If your text is not long enough, the remainder will be filled in with zeros when it is converted to ASCII by the software. The ASCII conversion happens automatically. If you desire, you can view the ASCII code by selecting the Hexadecimal Key option. The ASCII code will be displayed.

ii. Copy and save your text stream into a file in the same manner as step b.ii above.

iii. Press the Update button on the bottom of the screen.

d. Use Existing Key – Select this option to use the key that is stored in the Xtreme Module.

e. To update the key in a downstream Xtreme Module

i) Hexadecimal key:

(1) Select Hexadecimal Key.

(2) If a key is displayed in the Key Box, delete it.

(3) Open the file generated in step b. above.

(4) Copy the key by using your mouse and left click to highlight all of the characters. Press the “CTRL” and “C” keys simultaneously on your keyboard.

(5) With your mouse, left click in the Key Box. On your keyboard, press “CTRL” and “V”.

(6) Press the Update button at the bottom of the screen.

Page 38: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

38

ii) If you are using a Text key, the key can be updated in two ways:

(1) Copy Text Key

(a) Select Text Key.

(b) If a key is displayed in the Key Box, delete it.

(c) Open the file generated in 6.c above.

(d) Copy the key by using your mouse and left mouse button to highlight all of the characters. Press “CTRL” and “C” keys on your keyboard.

(e) With your mouse, left click in the Key Box. On your keyboard, press “CTRL” and “V”.

(f) Press the Update at the bottom of the screen.

(2) Type Text Key

(a) Select Text Key.

(b) If a key is displayed in the Key Box, delete it.

(c) Type in the key you generated in 6.c above.

(d) Press the Update button at the bottom of the screen.

f. Configuring AES Encryption on a Zlinx Radio Modem:

Fig 6-7 Zlinx Radio Modem Encryption

Page 39: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

39

Figure 36 shows the Zlinx Radio Modem configuration screen. Click the ATKY Set button (for SR models, the ATEE command also needs to be set to 1). The Set Hex String box will appear. Copy the key generated for the I/O module above into the box.

6.1.2 MODBUS MODE SETTINGS When configured as a wireless Modbus node, Zlinx Xtreme I/O communicates with a Modbus RTU Master connected to a Zlinx Wireless Modbus Modem and provides remote I/O functionality. The configuration screen for Modbus Mode is shown below:

Fig 6-7 Modbus Mode Configuration

To configure the Zlinx Xtreme I/O for Modbus mode:

1. Select the Configuration tab.

2. Select the Modbus option button.

3. In the Modbus Address box, type the Modbus address to be used.

The allowable range of Modbus addresses is from 1 to 247. The default Modbus address is 1.

4. Set the value for the Communication failure timeout (in seconds). If, within the predefined timeframe, no data is coming from Modbus Master (Modbus Radio Modem), the Zlinx I/O device perceives it as a communication failure.

Page 40: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

40

6.1.3 MODBUS I/O ADDRESSING In Modbus Mode, Digital and Analog Input information from the Zlinx Xtreme I/O inputs is stored in the Zlinx Xtreme I/O memory in Modbus format and sent across the link to the Modbus modem. Digital and Analog Output information is sent from the Modbus modem to the Zlinx Xtreme I/O in Modbus format, which set the outputs to the desired states/levels. To use Modbus Mode successfully, an understanding of the Zlinx Xtreme I/O memory map assignments and Function Codes is necessary. What is a Modbus Map? A Modbus Map is simply a list for an individual slave device that defines:

What the data is (ex. pressure or temperature readings) Where the data is stored (which tables and data addresses) How the data is stored (data types, byte and word ordering)

Some devices are built with a fixed map that is defined by the manufacturer, while other devices allow the operator to configure or program a custom map to fit their needs.

6.1.3.1 MODBUS FUNCTION CODES The function code in the Master device query tells the addressed slave device what kind of action to perform. The data bytes contain any additional information that the slave will need to perform the function. The following Modbus function codes are supported:

Function 1: Read DO Status Function 2: Read DI’s Function 3: Read AO Status Function 4: Read AI’s Function 5: Write to Single DO (firmware v2.0 or higher) Function 6: Write to Single AO Function 15: Write to Multi DO’s

For example, function code 03 will query the slave to read holding registers and respond with their contents. The data field must contain the information telling the slave which register to start at and how many registers to read.

6.1.3.2 MODBUS I/O REGISTERS Messages sent between Zlinx Xtreme I/O and a Modbus modem use Modbus memory addresses to specify the type of information being sent and where it is stored. In the Modbus addressing scheme, each type of I/O (DO, DI, AI, and AO) is stored in a different section of the memory. The following sections show the memory register maps for different I/O types.

6.1.3.2.1 DIGITAL (RELAY) OUTPUTS There are 2 Digital (Relay) Outputs available in the I/O modules and their addressing is as follows:

Digital Outputs Modbus Memory Address Digital Output 1 00001 Digital Output 2 00002

Fig 6-8 Digital (Relay) Output Memory Table

When the Zlinx Xtreme I/O receives a Modbus message to write “1” to a discrete output register, the Zlinx Xtreme I/O module turns ON its corresponding Digital Output. As an example, to turn on the second Digital Output (DO2) on the Xtreme module, the Modbus Master must set a value of 1 in memory location 00002.

Page 41: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

41

6.1.3.2.2 DIGITAL INPUTS There are 2 digital inputs available in the I/O modules and their addressing is as follows:

Digital Outputs Modbus Memory Address

Digital Input 1 10001

Digital Input 2 10002

Fig 6-9 Digital Input Memory Table

When a digital input is ON, the I/O module sets the corresponding Modbus register as a ‘1’. Otherwise, the register value is ‘0’.

As an example, when the Digital Input (DO1) on the Xtreme Module goes ON, the Modbus register memory location 00002 will be set to a value of 1.

6.1.3.2.3 ANALOG INPUTS There are two 16-bit analog inputs available in the I/O modules and their addressing is as follows:

Analog Inputs Modbus Memory Address

Analog Input 1 30001

Analog Input 2 30002

Fig 6-10 Analog Input Memory Table

The I/O module sets the register value based on the analog signal level.

As an example, for a 0-10V selection, when the analog input 1 is 5V, the memory location 30001 will read 32,768

Refer to Appendix F for analog data scaling.

6.1.3.2.4 ANALOG OUTPUTS There are two 16-bit analog inputs available in the I/O modules and their addressing is as follows:

Analog Outputs Modbus Memory Address

Analog Output1 40001

Analog Output 2 40002

Fig 6-11 Analog Output Memory Table

To set a 5 mA output current at analog output terminal 2, when a selection of 0- 20mA is made, the Modbus Master must set a value of 16,384 in the memory location 40002.

Refer to Appendix F for analog data scaling.

6.1.3.2.5 MODBUS FREQUENCY / COUNTERS INPUTS In Modbus mode, a Zlinx Xtreme I/O supports the two Digital Inputs in the following modes:

Frequency

Counters (Accumulators)

Page 42: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

42

The table below shows the Modbus register mapping for Frequency and Counter Inputs:

Frequency / Counter Data Modbus Memory Address

DI1 - Frequency 40003 DI1 – Counter LS Register 40004 DI1 – Counter MS Register 40005 DI2 – Frequency 40006 DI2 – Counter LS Register 40007 DI2 – Counter MS Register 40008

Fig 6-12 Frequency/Counter Memory Table

Frequency Registers 40003 & 40006 hold the frequency values if Digital Inputs 1 and 2 are configured as Frequency Inputs. Maximum value of frequency is 20 KHz. Flow meters typically generate a frequency based on the amount of fluid flowing through the sensor. The flow and respective frequency varies on the manufacture and sensor. The frequency measurement is located in a separate Modbus holding register and may not be written to. The frequency register is formatted in cycles/sec and requires the user to convert the frequency to respective flow units. Counters The most and least significant counter registers if Digital Inputs 1 and 2 are configured as Counter Inputs are shown in Fig 6-12. Both the most and least significant counter registers have a range of 0 to 9999 and rollover. Time to save totals register counts down the number of seconds (from 300-0 seconds) until the Accumulators are saved internally. An example is a typical electric water meter that will generate a pulse per 1/10 gallon of water flowing through it. This type of application is best used with the Modbus accumulators. The accumulators are broken down into two registers, most significant count and least significant count. Both accumulators have a full count of 9999. When the least significant count exceeds 9999, it will increment the most significant count giving a total system count of 99,999,999. The accumulators reside in the holding register map and maybe written to in order to reflect what a typical water meter may have displayed on its display. There is also a holding register associated with the accumulators that indicates the number of seconds before the accumulators are saved. The accumulator data is saved every ~5min.

Note: “Appendix D: Modbus I/O Assignments” of this manual contains a list of Modbus I/O assignments for the Zlinx Xtreme I/O.

Page 43: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

43

6.1.3.3 MODBUS I/O ADDRESSING The following examples show how the Modbus addressing works especially when viewed from a Modbus Master: In general, Modbus protocol allows two types of I/O addressing: implied and extended. However, Zlinx Xtreme I/Os support implied I/O addressing only and uses HEX format. The addressing format ignores the I/O type digit (0 for DO, 1-for DI, 3 for AI and 4 for AO) and address number is the same irrespective of the I/O type.

DO DI AI AO Modbus Memory Address 00001 10001 30001 40001 Ox0001 00002 10002 30002 40002 Ox0002 00003 10003 30003 40003 Ox0003 00004 10004 30004 40004 Ox0004 00005 10005 30005 40005 Ox0005 00006 10006 30006 40006 Ox0006 00007 10007 30007 40007 Ox0007 00008 10008 30008 40008 Ox0008 00009 10009 30009 40009 Ox0009 00010 10010 30010 40010 Ox000A 00011 10011 30011 40011 Ox000B 00012 10012 30012 40012 Ox000C 00013 10013 30013 40013 Ox000D 00014 10014 30014 40014 Ox000E 00015 10015 30015 40015 Ox000F 00016 10016 30016 40016 Ox0010

Fig 6-13 I/O Addressing Table

The function code will specify the holding register operation. For example: - Function code 2 associated with register Ox000B means read from digital input register 10011 - Function code 6 associated with register Ox000B means write to analog output register 40011

6.1.4 PEER-TO-PEER MODE SETTINGS Peer-to-Peer Mode is ideal for wire replacement applications involving analog and/or digital I/Os. A typical application is to control/monitor remote devices from a PLC or SCADA system where laying cables is too expensive or cannot be done for any reason. In Peer-to-Peer Mode, digital and analog signals can be wirelessly transmitted, in both directions, between two Zlinx I/O modules. The Zlinx I/O modules shall be indoor or outdoor (Zlinx Xtreme) type. For successful communication, both Xtreme Modules must be of the same frequency type and have similar I/O count, i.e. analog and digital inputs of one module shall equal the analog and digital outputs of the other module and vice versa. One module is configured as Peer-to-Peer Master and other is configured as Peer-to-Peer Slave. It does not matter which one is configured as Master. Additionally, the Peer-to-Peer Master address MUST match the Peer- to-Peer Slave address (1-255).

6.1.4.1 PEER-TO-PEER MASTER To configure the Zlinx Xtreme I/O module for Peer-to-Peer Master Mode:

1. Select the Configuration tab.

2. Select the Peer-to-Peer Master option button.

3. Set the Peer-to-Peer Master address from 1 to 255. Please note the Peer-to-Peer Slave address must also match.

4. The Polling Rate box contains the number of seconds between polls by the Master. The default value of 1 second is usually satisfactory. The range of values is 0 seconds to 20 seconds. If the I/O points are not updating properly, try increasing the value.

Note: “0” causes the firmware to transfer data as fast as possible with no delays.

Page 44: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

44

5. The Retry Count box contains the number of attempts that will be made to communicate with the Slave device before the module indicates communication has been lost. Lost communication is indicated by the Power LEDs blinking. The default value of 10 is usually satisfactory. The range of values is 10 to 255.

Fig 6-14 Peer-to-Peer Master Configuration

6.1.4.2 PEER-TO-PEER SLAVE

Fig 6-15 Peer-to-Peer Slave Configuration

Page 45: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

45

To configure the Zlinx Xtreme I/O Module for Peer-to-Peer Slave Mode:

1. Select the Configuration tab.

2. Select the Peer-to-Peer Slave option button.

3. Set the Peer-to-Peer Slave address from 1 to 255. Note: Peer-to-Peer Master address must also match.

4. Communication Failure Timeout. If, within the predefined timeframe no data is coming from Peer-to-Peer Master, the Slave interprets it as a communication failure.

6.1.5 INPUT/OUTPUT SETTINGS Digital Inputs/Outputs and Analog Inputs/Outputs on Zlinx Xtreme I/O modules are configured from the Input/Output tab of the Zlinx Manager. The first two Digital Inputs on any module can be configured as Discrete Inputs or Counter Inputs. Any additional Digital Inputs operate as Discrete Inputs only. Counter operation is only functional when the Zlinx Xtreme I/O is set up in Modbus mode. Analog Inputs and Outputs can be configured for voltage or current loop operation.

To configure Digital and Analog I/O, select the Input/Output tab.

An input tree appears listing all modules in the system and the inputs/outputs available on them.

6.1.5.1 DIGITAL INPUT CONFIGURATION

Fig 6-16 Digital Input Configuration

1. Select the Digital Input to be configured.

2. Select Discrete or Counter.

Note: See section - “Function code 2 associated with register Ox000B means read from digital input register 10011

Function code 6 associated with register Ox000B means write to analog output register 40011”.

3. Select Digital Input type, PNP (Sourcing) or NPN (Sinking) based on the input connection.

4. For Exception Reporting, refer to Section 6.1.6.

Page 46: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

46

6.1.5.2 DIGITAL (RELAY) OUTPUT CONFIGURATION

1. Select the Digital (Relay) Output to be configured.

2. Select communication ‘Fail Safe’ condition if necessary.

3. Digital (Relay) Output 1 can be selected to indicate communication failure by selecting the check box. The high or low level selection is user configurable for the communication failure condition.

Fig 6-17 Digital (Relay) Output Configuration

6.1.5.3 ANALOG INPUT CONFIGURATION

1. Select the Analog Input to be configured.

2. Select the required Analog Mode (0-5 VDC, 0-10 VDC, 0-20 mA, 4-20 mA)

3. For Calibration, refer to section 6.1.7.

4. For Exception Reporting, refer to sections 6.1.6.

Page 47: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

47

Fig 6-18 Analog Input Configuration

6.1.5.4 ANALOG OUTPUT CONFIGURATION 1. Select the Analog Output to be configured.

2. Select the required Analog Mode (0- 10VDC, 0- 5 VDC, 0- 20 mA, or 4- 20 mA).

3. Set the value of the Analog Output on a communications fail safe condition.

4. For Calibration of the Analog Output, refer to the section 6.1.7.

Fig 6-19 Analog Output Configuration

Page 48: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

48

6.1.6 EXCEPTION REPORTING This feature provides the ability of reporting possible problems on input devices (AIs and DIs). It is applicable to Modbus mode only. For Analog Inputs, exception reports will be periodically sent if an input goes outside the low and high thresholds. Once an input enters the exception state, it must become greater than the low threshold plus the dead band value or less than the high threshold minus the dead band value in order to come out of the exception state. In general, the Modbus protocol does not support exception reporting. In a typical Modbus system, the Modbus Master sends a request to a respective Slave device and the Slave device will respond with an ACK. Typical Slave data does not contain I/O addressing data. Any data sent from the Slave to the Master, without the Master first requesting it, will be ignored by the Master. Therefore, the end user is required to use a custom driver to capture the exception data. Analog Exception errors are generated when user-defined High or Low limits are exceeded. If an Analog Input value rises above the High limit, an exception is generated and immediately sent out. Data is updated and retransmitted based on the Exception Retransmit timer. Exception is transmitted in the timeframe predefined by the user within the allowable range. If the Exception reporting timeout is set to zero, the exception is sent only once to the Modbus Master.

Analog Value > HIGH LIMIT = Exception Error.

The High exception error is cleared when the Analog Input value falls below the high limit – the dead band value.

Analog Value < (HIGH LIMIT – DEAD BAND) = Exception Error Cleared.

If an Analog Input value falls below the LOW limit, an exception is generated and immediately sent out. Data is updated and retransmitted based on the Exception Retransmit timer.

Analog Value < LOW = Exception Error.

The Low exception error is cleared when the Analog Input value rises above the low limit + the dead band value.

Analog Value > (Low + DEAD BAND) = Exception Error Cleared.

6.1.6.1 SAMPLE MODBUS EXCEPTION PACKET Exception Modbus packets do not follow the typical Modbus protocol. The Xtreme Module is a Slave device and, in a typical system, Slave devices do not generate outgoing requests. When the Xtreme Module generates an exception, the Xtreme Module will generate a Modbus packet that emulates a “Master Poll”. The exception packet is sent to the Master and does not require an ACK.

6.1.6.2 DIGITAL EXCEPTION FORMAT Xtreme Module DI exception 01 02 00 01 0E 98 2C 01 Slave Address 02 Function (Read DI’s) 00 I/O Address High (0-15 = Base) 01 Byte Count 0E Digital Inputs (8-DI’s) 1110 98 Checksum High 2C Checksum Low

Page 49: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

49

6.1.6.3 ANALOG EXCEPTION FORMAT Xtreme Module AI exception 01 04 00 08 00 00 00 00 00 00 00 00 98 2C 01 Slave Address 04 Function (Read AI’s) 00 I/O Address High (0-15 = Base, 16-31=EXP module 1) 08 Byte Count 08 00 Analog Input-1 High Byte 00 Analog Input-1 Low Byte 00 Analog Input-2 High Byte 00 Analog Input-2 Low Byte 00 Analog Input-3 High Byte 00 Analog Input-3 Low Byte 00 Analog Input-4 High Byte 00 Analog Input-4 Low Byte 98 Checksum High 2C Checksum Low To set the option of Exception Reporting, go to the Digital Input Configuration screen or Analog Input Configuration screen as appropriate.

6.1.7 CALIBRATION It is possible to calibrate Analog Inputs or Outputs from the Zlinx Manager.

There are two methods of Calibration:

Single Point - only one data point is used. The gain is 1 and the offset is the difference between the reference and acquired values.

Two Point - the two data points are used to create a line. The gain is the slope of the line and the offset is the intercept.

Note: Power cycle does not reset Calibration settings.

To set Calibration for Analog Inputs:

1. Connect an analog source to the Analog Input and set it to a known value. (ex. 5V)

2. Enter this value in the Reference text box.

3. Click the Read Current Value button.

4. The Acquired text box will be filled in with the acquired value.

If using the two-point method, repeat these steps for the second calibration point.

Page 50: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

50

Fig 6-20 Analog Input Calibration

To set Calibration for Analog Outputs:

1. Enter a value in the Reference text box.

2. Click the Set Current Value button.

3. Supply power to the device.

4. Measure the output value and enter the measured value in the Acquired text box.

5. Values will be filled in automatically in the calibration field.

If using the two-point method, repeat these steps for the second calibration point.

Fig 6-21 Analog Output Calibration

Page 51: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

51

6.1.8 ZLINX I/O MONITOR From Zlinx Manager the user can choose the option Zlinx I/O Monitor. This option allows the monitoring of all Analog and Digital I/O values (in V, mA, on/off; degrees Celsius for RTD) real time. To start the Monitor feature:

1. Start Zlinx Manager.

2. Choose Zlinx I/O Monitor from the list.

3. Zlinx I/O Monitor window will open.

4. Choose the COM port that the system is connected to.

5. Click on the Start Monitoring button.

Fig 6-22 Zlinx Xtreme I/O Monitor

Note: Monitor does not show the inverted values for the DOs i f such opt ion is enabled.

6.1.9 SAVING THE CONFIGURATION When all configuration settings are complete, click the Update button to save them in the Zlinx Xtreme I/O Module.

1. After pressing the Update button the Configuration Manager switches to the Information tab.

2. The Progress bar at the bottom of the windows shows the progress of the update.

3. The Status bar displays the following text:

4. Sending radio parameters to the Xtreme module.

When the updating process is complete, it is possible to switch to any other tab to see or edit any parameters.

Note: When configuration is complete and saved, power can be removed from the Xtreme Module and it should be disconnected from the PC.

6.2 UPDATING ZLINX I/O FIRMWARE

B+B SmartWorx continually adds new features to Zlinx Xtreme I/O modules and updated firmware is downloadable at www.advantech-bb.com. Whenever the latest version of Zlinx Manager software is installed on your computer, the latest version of Zlinx Xtreme I/O Firmware Updater software is also installed. This can be used to update the firmware in your Zlinx Xtreme I/O modules. The following procedure describes the firmware updating process:

1. Disconnect power from the Xtreme Module.

2. Disconnect the Xtreme Module from external equipment. The easiest way to disconnect is to unplug all I/O terminal blocks.

3. Connect the PC USB port to the Zlinx Xtreme I/O USB port using a USB cable.

4. From the Windows Start menu, start the Zlinx Manager and choose Zlinx I/O Firmware Updater software.

The Zlinx I/O Firmware Updater Caution dialog box appears.

Page 52: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

52

Fig 6-23 Firmware Updater Caution Dialog Box

5. Select the USB COM port from the Connection drop down list.

6. Click Connect.

7. Re-apply power to the Zlinx Xtreme I/O Module. The Power LED should go on and stay on.

8. The Zlinx Xtreme I/O Firmware Updater window opens and displays a list of the Xtreme modules.

9. On the module list, select the Xtreme Module to be updated.

10. In the Firmware Image drop down box, select the image file (.hex).

11. Click the Program button to load the firmware into the module.

12. Repeat steps 9 to 11 for the other modules in the system.

13. When all updates are complete, click Exit.

14. Before reconnecting the I/O, run Zlinx Manager software and ensure all modules are configured properly.

15. When the configuration check is complete:

a. Exit the Zlinx Manager program.

b. Disconnect power from the Xtreme Module.

c. Disconnect the Xtreme Module from the PC.

d. Reconnect the I/O.

e. Re-connect power to the Xtreme Module.

Note: It is necessary to perform Power Cycle on all modules after firmware update.

Page 53: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

53

6.3 DIAGNOSTICS AND TESTING

Most problems are related to incorrect configuration or radio path problems. Before performing final installation of the Zlinx Xtreme I/O modules, bench test the functionality first. If it does not work properly in this test, it will not work properly installed. If problems are found, check wiring and software configurations. If the bench-test is successful, and problems are experienced after installation, check the radio path.

6.3.1 TESTING MODBUS MODE OPERATION Using a Modbus radio modem, a PC and Modbus simulation software (e.g. Modscan), you can test the link and hardware, and investigate the operation of the Zlinx Xtreme I/O. Modscan is a Windows application that simulates a Modbus Master node. You can read from and write to memory locations on the Zlinx Xtreme I/O. Modscan is available as a fully functional time-limited demo from www.win-tech.com

6.3.2 TESTING PEER-TO-PEER MODE OPERATION To diagnose possible problems in Peer-to-Peer mode, perform the following checks:

1. Configure one of the two Peer-to-Peer base devices as a MASTER and the other as a SLAVE.

2. Select a "Polling" rate on the Master device. Typically a setting of "0" or "1" seconds works best.

Note: “0” causes the firmware to transfer data as fast as possible.

3. Configure a Slave "Communications Failure Timeout". Recommended setting is "20" seconds.

4. Ensure the same Peer-to-Peer Address for both units.

5. Ensure same Wireless setting for: "Channel", "Network Identifier" and “AES Encryption” for both units.

Test communications between the units by performing the following tests.

1. Confirm that the RF Data LEDs on the Master and Slave devices are flashing, indicating communications between the Master and Slave devices.

2. If the RF Data and Bus LEDs are flashing in a "Railroad" manner, the system is NOT communicating.

3. On the Master system, connect an LED to DO-1 of the Xtreme Module. The LED should immediately come ON.

4. On the Slave system, connect a wire from VIN+ to DI-1 of the Xtreme Module (for NPN configuration, connect VIN- to DI-1). The LED of the Master device should shut OFF.

Page 54: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

54

7 - TROUBLESHOOTING

This section is designed to help you answer some of the more common questions asked regarding installation and configuration of Zlinx Xtreme I/O.

Problem Causes and Resolutions

Power LED is not On. Ensure that power connections to the Xtreme Module are properly connected and correct power voltage and current is applied.

Power LED is blinking. No wireless connection established.

RSSI – No Signal (No LEDs On) Or Weak Signal (3 or

less LEDs On)

and

Wireless LED intermittently blink.

Firmware does not match. Firmware for all Xtreme Modules must match. The firmware revision number may be viewed on the information tab of the configuration software. See section 6.2 “Updating Zlinx I/O Firmware”. If the firmware does not match, then update the firmware with the Zlinx I/O Firmware Updater software. No Peer-to-Peer communication link. The communication link is not established. Verify that all parameters in the configuration tab in the programming software are correct. Make sure that there are no obstacles in the path of the wireless transmission.

Figure 7-1 Problem-Cause-Resolution Table

7.1 TESTING DIGITAL AND ANALOG I/O There are simple tests that can be performed to confirm the functionality of the hardware and wiring configurations. The following diagrams can be used to aid in diagnosing problems with device connections. To properly connect a Digital Output to the Digital Input of your data acquisition equipment, you need to know whether the output is “sinking” or “sourcing”. A “sinking” output acts simply as a switch to ground and may be referred to as a dry contact. A “sinking” output requires an additional power source for connected devices or an internal pull-up resistor. A “sourcing” output supplies the voltage itself and requires a pull-down resistor between the digital input or output and ground to provide the low voltage condition when the output is turned off.

To test devices, you need to create a working system. For the purpose of the test, create a system in Peer-to-Peer mode. Create two systems: System-1 consisting of an Xtreme Module; System-2 consisting of an Xtreme Module. Both Xtreme Modules must be the same model. Analog and Digital Input signals connected to AIs and DIs on one system appear on the corresponding AOs and DOs on the other system and vice versa.

7.1.1 TESTING DI On System-1, connect one side of the switch to DI on the Zlinx Xtreme I/O device and the other side of the switch to high or ground, depending on PNP or NPN configuration (see Fig. 7-2). The LED corresponding to the DI should be ON.

PWR IN +

DIx

(a) PNP (Sourcing) Input Wiringwith Internal Power Supply

DIx

(b) NPN (Sinking) Input Wiring with Internal Power Supply

Com

Figure 7-2 Digital Input (Sourcing driver) Wiring

Page 55: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

55

7.1.2 TESTING DO (RELAY O/P) To test a “relay” output, the following can be performed. See “Appendix E: Zlinx Xtreme I/O Models and Features” to find out which modules are relay. On System-1 on the corresponding Zlinx Xtreme I/O device connect a Light through COM and NO contact of the relay output. Make sure to check the polarity of the LED while connecting it. On System-2 perform contact closure on the corresponding DI. The relay output should turn ON and the Light should turn ON.

NO

Com

NC

V+ / Ph

V- / N

Light

Figure 7-3 Relay Output Testing

7.1.3 TESTING AI IN “VOLTAGE” MODE Connect a AA battery (1.5 VDC) on the AI-1 on System-1 (see Fig 7-4) and a voltmeter on the corresponding AO-1 on System-2. Make sure the polarity is correct while connecting the battery. Measure the voltage on the Analog Output on System-2. It must indicate 1.5 VDC.

AINx

COM

+

-

Figure 7-4 Analog Input wiring

7.1.4 TESTING AO IN “VOLTAGE” MODE To test an Analog Output in “voltage” mode, the following can be performed. Refer to “Appendix E: Zlinx Xtreme I/O Models and Features” for the list of Analog Output modules. On the corresponding Zlinx Xtreme I/O device on System-1 connect an AO to a voltmeter as shown in the figure below (Fig 7-5). Supply a voltage signal on the AI side of System-2. Confirm on System-1 with a voltmeter that the voltage on the corresponding output matches the voltage input.

AOutx

COM

Figure 7-5 Analog Output (Sourcing driver) wiring

Page 56: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

56

APPENDIX A – DEFAULT CONFIGURATION SETTINGS

Power Setting: ZXT24-IO-222R2 Xtreme Module: 63mW ZXT9-IO-222R2 Xtreme Module: 1000mW

Wireless Channel Number: ZXT24-IO-222R2 Xtreme Module: 0x0C ZXT9-IO-222R2 Xtreme Module: 0x00

Wireless Network ID: 0x00 for ZXT24-IO-222R2 Xtreme Module 0x11 for ZXT9-IO-222R2 Xtreme Module

Repeater Mode: Not selected

Communication Mode: Modbus

Modbus Address: 1

Digital Inputs: Discrete & PNP

Analog Inputs: 4 to 20 mA

Analog Outputs: 4 to 20 mA

Page 57: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

57

APPENDIX B – PRODUCT SPECIFICATIONS

Xtreme I/O Module Models: ZXT24-IO-222R2 ZXT9-IO-222R2

Manual: Electronic version of this manual, PDF available

CD-ROM Disc: Zlinx Manager s/w PDF of Zlinx Xtreme I/O User Manual PDF of Quick Start Guide

Operating Systems: Windows 2000/XP/Vista/7/8/8.1/10 (32 & 64 bit)

Dimensions: 82l x 80w x 85h mm (3.23l x 3.15w x 3.35h in)

Radio Properties ZXT24-IO-222R2 (SR) Option: Up to 91.4m (300 ft) indoors / 1.61km (1mi) outdoors (line-of-sight)

ZXT9-IO-222R2 (LR) Option: Up to 914m (3000 ft) indoors / 22.5km (14mi) outdoors (line-of-sSight)

Antennas: For 2.4 GHz model ZXT24-IO-222R2: 4.25 inch Omni-directional rubber duck antenna, Model# ZZ24D-ANT1 For 900 MHz model ZXT9-IO-222R2: 7.7 inch Omni-directional rubber duck antenna, Model# ZXT9-ANT1

Receiver Sensitivity

ZXT24-IO-222R2, ZXT24-RM

-102 dBm

ZXT9-IO-222R2, ZXT9-RM

-100dbm @ 115.2K -110dbm @ 9600

LED Indicators Receive Signal Strength

Indicator: The RSSI indicator is 8 Green LEDs in a bar graph format from Weak to Strong

LEDs Number Turned ON Signal Strength

0 No signal 1-3 Weak 4-6 OK 7-8 Strong

RF Data Indicator: Green LED (blinks with TD or RD data traffic, Off = no data traffic)

Power Indicator: Green LED, Blinks with Communication Failure

I/O Connectors: Screw terminal

Digital Inputs Voltage Range: 0 to 48 VDC

Low Voltage (0): 1.0 VDC maximum

High Voltage (1): Greater than 1.0 VDC

Pull up/down Current: 38uA

Frequency Input: Two DI inputs per module software selectable as Counters, 0 to 20 kHz range (do NOT exceed more than 20 kHz)

Page 58: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

58

Analog Inputs/Outputs Ranges: 0-5VDC; 0- 10 VDC; 0- 20mA; 4-20mA

Resolution: 16-bit (analog inputs); 12-bit (analog outputs)

Input Accuracy: 0.2% full scale reading typical, 0.5 % maximum

Output Accuracy: 0.27% full scale reading typical, 0.63% maximum

AI Load Resistance: 100 Mega Ohms when configured for voltage input. 250 Ohms when configured for current input.

AO Max Output Current: 1mA when configured for voltage output

AO Max Source Load: 450 Ohms when configured for current output.

Input Protection: Over-voltage to 2x maximum input voltage.

Power Supply Voltage Requirements:

10- 30 VDC

Power Supply: Not included

Xtreme Module Power Connector:

Fixed screw terminal connector

Digital Outputs (Relay) Number of Relays: 2

Type: C (normally open and normally closed)

Output Connection: 3 terminals per relay (Common, NO, NC)

Common Connection: 3.5mm removable terminal block (1 per bank of 4 output)

Ratings: 250 VAC @ 4A, 30 VDC @ 4A

Power Consumption: ZXT24-IO-222R2 (SR) = 4.5W muximum ZXT9-IO-222R2 (LR) = 6.8W

Operating Temperature: -40 to +74 ºC (-40 to +165 º F)

Storage Temperature: -40 to +85 °C (-40 to +185 °F)

Humidity: 0 to 90% R.H. non-condensing

Enclosure Rating: IP67

Mounting: Wall mount

Certifications: FCC: Part 15 Class A CISPR (EN55022) Class A EN61000-6-2 Generic Standards for Industrial Environments

Accessories and Replacement Parts:

# ZZ24D-ANT1 2.4 GHz band antenna # ZXT9-ANT1 900 MHz band antenna # 195M-SLSW-24 Antenna cable

Page 59: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

59

APPENDIX C – EXPECTED LATENCY Before you lift a finger towards the perfect wireless installation, think about the impact of wireless communications on your application. Acceptable bit error rates are many orders of magnitude higher than wired communications. Most radios quietly handle error detection and retries for you - at the expense of throughput and variable latencies. Software must be well designed and communication protocols must be tolerant of variable latencies. Not every protocol can tolerate simply replacing wires with radios. Protocols sensitive to inter-byte delays may require special attention or specific protocol support from the radio. Do your homework up front to confirm that your software will not “choke”, that the intended radio is “friendly” towards your protocol, and that your application software can handle it as well. Assumptions:

No RF retries.

Units were less than 3 feet (0.9m) apart during the testing in a clean RF environment.

Modbus Mode Reading Inputs Setting Outputs

ZXT24-IO-222R2 ZXT9-IO-222R2 ZXT24-IO-222R2 ZXT9-IO-222R2

126 mS 164 mS 68 mS 69 mS

Peer-to-Peer Mode

Latency in Peer-to-Peer Mode

Xtreme Modules Digital Analog

ZXT24-IO-222R2 80 mS 126 mS

ZXT9-IO-222R2 115 mS 126 mS

Page 60: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

60

APPENDIX D – MODBUS I/O ASSIGNMENTS 00001-00112 Discrete Digital Outputs Modbus function codes supported: Function 1: Read DO Status Function 2: Read DIs Function 3: Read AO Status Function 4: Read AIs Function 5: Write to Single DO (firmware v2.0 or higher) Function 6: Write to Single AO Function 15: Write to Multi DOs

00001-00002 Discrete Digital Outputs /Relays Modbus Address

Description #Bytes Count V Range

00001 Digital Output-1 - 0-1 Refer to Appendix B 00002 Digital Output-2 - 0-1 Refer to Appendix B 10001-10002 Discrete Digital Inputs Modbus Address

Description #Bytes Count V Range

10001 Digital Input-1 - 0-1 Refer to Appendix B 10002 Digital Input-2 - 0-1 Refer to Appendix B 30001-30004 Analog Inputs/ Special Registers Modbus Address

Description #Bytes A/D Count

(V)/(I)Range

30001 Analog Input-1 2 0-65535 0-10vdc/0-20ma 30002 Analog Input-2 2 0-65535 0-10vdc/0-20ma 30003 Input Power Supply (0~30 VDC) 2 0-65535 0-10vdc/0-20ma 30004 Reserved 2 0-65535 0-10vdc/0-20ma 40001-40008 Analog Output /Counter Registers Modbus Address

Description #Bytes D/A Count

(V)/(I)Range

40001 Analog Output-1 2 0-4095 0-10vdc/0-20ma 40002 Analog Output-2 2 0-4095 0-10vdc/0-20ma 40003 DI1 – Frequency Input 2 0-4095 0-10vdc/0-20ma 40004 DI1 – Counter Low 2 0-4095 0-10vdc/0-20ma 40005 DI1 – Counter High 2 0-4095 0-10vdc/0-20ma 40006 DI2 – Frequency Input 2 0-4095 0-10vdc/0-20ma 40007 DI2 – Counter Low 2 0-4095 0-10vdc/0-20ma 40008 DI2 – Counter High 2 0-4095 0-10vdc/0-20ma

Page 61: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

61

APPENDIX E – XLINX XTREME I/O MODELS & FEATURES

Xtreme Modules

Model Number Module Type Frequency/Range I/O

ZXT24-IO-222R2 Base 2.4 GHz, short range

2AI, 2AO, 2DI, 2DO (relay DOs)

ZXT9-IO-222R2 Base/Repeater 900 MHz, long range

2AI, 2AO, 2DI, 2DO (relay DOs)

Compatible Radio Modems

Radio Modem Model Number Description Zlinx Xtreme I/O Model

Number

ZXT24-RM 2.4 GHz RS-232/422/485 radio modem 250kbps ZXT24-IO-222R2

ZXT9-RM 900 MHz RS-232/422/485 radio modem 115.2kbps ZXT9-IO-222R2

Accessories

Model Number Description

ZZ9D-ANT2 900 MHz band antenna

ZZ24D-ANT1 2.4 GHz band antenna

CLG-60-24 IP67 power supply, 24V, 60W

Page 62: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

62

APPENDIX F – CONVERT VOLTAGE/CURRENT TO DAC In Zlinx Xtreme I/O modules, analog inputs are 16-bit and analog outputs are 12-bit. The Modbus register scaling for the analog inputs and outputs for different selections are shown below:

1. Analog Output (0-10 VDC Selection): Voltage Full Range = 0-10VDC DAC full range is 4096 counts as AOs are 12-bit (0-4095 range), 4096 Holding Register Value to Send = Voltage Desired * 4096 / 10 (ex) For sending out 2.5V, Holding Register Value = 2.5 * 4096 / 10 = 1024

2. Analog Output (0-5 VDC Selection): Voltage Full Range = 0-5VDC DAC full range is 4096 counts as AOs are 12-bit (0-4095 range), 4096 Holding Register Value to Send = Voltage Desired * 4096 / 5 (ex) For sending out 2.5V, Holding Register Value = 2.5 * 4096 / 5 = 2048

3. Analog Output (0-20 mA Selection): Current Full Range = 0-20mA DAC full range is 4096 counts as AOs are 12-bit (0-4095 range), 4096 Holding Register Value to Send = Current Desired * 4096 / 20 (ex) For sending out 10 mA, Holding Register Value = 10 * 4096 / 20 = 2048

4. Analog Output (4-20 mA Selection): Current Full Range = 4-20mA DAC full range is 4096 counts as AOs are 12-bit (0-4095 range), 4096 Holding Register Value to Send = (Current Desired-4) * 4096 / 16 (ex) For sending out 10 mA, Holding Register Value = (10-4) * 4096 / 16 = 1536

5. Analog Input (0-10 VDC Selection): Voltage Full Range = 0-10VDC DAC full range is 65536 counts as AIs are 16-bit (0-65,535 range), 65,536 Input Register Value = Actual Voltage * 65536 / 10 (ex) Input register value for 2.5V = 2.5 * 65536 / 10 = 16384

6. Analog Input (0-5 VDC Selection): Voltage Full Range = 0-5 VDC DAC full range is 65536 counts as AIs are 16-bit (0-65,535 range), 65,536 Input Register Value = Actual Voltage * 65536 / 5 (ex) Input register value for 2.5V = 2.5 * 65536 / 5 = 32768

7. Analog Input (0-20 mA Selection): Voltage Full Range = 0-20 mA DAC full range is 65536 counts as AIs are 16-bit (0-65,535 range), 65,536 Input Register Value = Actual Current * 65536 / 20 (ex) Input register value for 10 mA = 10 * 65536 / 20 = 32768

8. Analog Input (4-20 mA Selection): Voltage Full Range = 4-20 mA DAC full range is 65536 counts as AIs are 16-bit (0-65,535 range), 65,536 Input Register Value = (Actual Current – 4)* 65536 / 16 (ex) Input register value for 10 mA = (10-4) * 65536 / 16 = 24576

Page 63: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

63

APPENDIX G – RADIO FREQUENCY BASICS What is dBm? Radio Frequency (RF) power is measured in milli-Watts (mW) or, more usually in a logarithmic scale of decibels (dB), or decibels referenced to 1 mW of power (dBm). Since RF power attenuates as a logarithmic function, the dBm scale is most useful. Here are some examples of how these scales relate:

1mW = 0dBm A 2-fold increase in power yields 3dBm of signal.

2mW = 3dBm A 10-fold increase in power yields 10dBm of signal.

4mW = 6dBm A 100-fold increase in power yields 20dBm of signal.

10mW = 10dBm

100mW = 20dBm

1W = 30dBm

Figure G-1 The dBm scale

Lower Frequencies - Better Propagation Industrial applications typically operate in “license-free” frequency bands, also referred to as ISM (Industrial, Scientific, Medical). The frequencies and power of these bands vary from country to country. The most common frequencies encountered are:

2.4 GHz band (Short Range) – nearly worldwide.

915 MHz band (Long Range) – North America, South America, some other countries.

As frequency rises, available bandwidth typically rises, but distance and ability to overcome obstacles is reduced. For any given distance, a 2.4 GHz installation will have roughly 8.5 dB of additional path loss when compared to 900 MHz. However, lower frequencies require larger antennas to achieve the same gain.

Range Performance The more sensitive the radio is, the lower the power signal it can successfully receive, stretching right down to the noise floor. There is so much variety in specifications for radio sensitivity, that it is difficult to make a meaningful comparison between products. The most meaningful specification is expressed at a particular bit error rate and will be given for an ideal environment shielded from external noise. Unless you are in a high RF noise environment, typically resulting from numerous similar-frequency radio transmitters located nearby, the odds are good that the noise floor will be well below the receive sensitivity, so the manufacturer’s rated receive sensitivity will be a key factor in your wireless system and range estimates.

You can often improve your receive sensitivity, and therefore your range, by reducing data rates over the air. Receive sensitivity is a function of the transmission baud rate so, as baud rate goes down, the receive sensitivity goes up. Many radios give the user the ability to reduce the baud rate to maximize range.

The receive sensitivity of a radio also improves at lower frequencies, providing another significant range advantage of 900 MHz (vs. 2.4 GHz) - as much as six to twelve dB!

RF Noise RF background noise comes from many sources, ranging from solar activity to high frequency digital products to all forms of other radio communications. That background noise establishes a noise floor which is the point where the desired signals are lost in the background ruckus. The noise floor will vary by frequency.

Typically, the noise floor will be lower than the receive sensitivity of your radio, so it will not be a factor in your system design. If, however, you are in an environment where high degrees of RF noise may exist in your frequency band, then use the noise floor figures instead of radio receive sensitivity in your calculations. If you suspect this is the case, a simple site survey to determine the noise floor value can be a high payoff investment.

When in doubt, look around. Antennas are everywhere nowadays - on the sides of buildings, water towers, bill boards, chimneys, even disguised as trees. Many sources of interference may not be obvious.

Page 64: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

64

Fade Margin Fade margin is a term critical to wireless success. Fade margin describes how many dB a received signal may be reduced by without causing system performance to fall below an acceptable value. Walking away from a newly commissioned wireless installation without understanding how much fade margin exists is the number one cause of wireless woes.

Establishing a fade margin of no less than 10dB in good weather conditions will provide a high degree of assurance that the system will continue to operate effectively in a variety of weather, solar, and RF interference conditions.

There are a number of creative ways to estimate fade margin of a system without investing in specialty gear. Pick one or more of the following and use it to ensure you will have a robust installation:

Some radios have programmable output power. Reduce the power until performance degrades, then dial the power back up a minimum of 10dB. Remember again, doubling output power yields 3 dB, and an increase of 10dB requires a ten-fold increase in transmit power.

Invest in a small 10dB attenuator - pick the correct one for your radio frequency! If you lose communications when you install the attenuator installed in-line with one of your antennas, you do not have enough fade margin.

Antenna cable has greater attenuation at higher frequencies. Specifications vary by type and manufacturer so check them yourself but, at 900 MHz, a coil of RG58 in the range of 50- 100 feet (15- 30 m) will be 10dB. At 2.4GHz, a cable length of 20-40 feet (6- 12 m) will yield 10dB. If your system still operates reliably with the test length of cable installed, you have got at least 10dB of fade margin.

Remember Your Math Contrary to popular opinion, no black art is required to make a reasonable prediction of the range of a given radio signal. Several simple concepts must be understood first, and then we can apply some simple rules of thumb.

The equation for successful radio reception is:

TX power + TX antenna gain – Path loss – Cabling loss + RX antenna gain – 10dB fade margin > RX Radio sensitivity or (less commonly) RF noise floor

Note that most of the equation’s parameters are easily gleaned from the manufacturer’s data. That leaves only path loss and, in cases of heavy RF interference, RF noise floor as the two parameters that you must establish for your particular installation.

In a perfect world, you will measure your path loss and your RF noise conditions. For the majority of us that do not, there are rules of thumb to follow to help ensure a reliable radio connection.

RF Attenuation and Line-of-Sight In a clear path through the air, radio signals attenuate with the square of distance. Doubling range requires a four-fold increase in power, therefore:

Halving the distance decreases path loss by 6dB.

Doubling the distance increases path loss by 6dB.

When indoors, paths tend to be more complex, so use a more aggressive rule of thumb, as follows:

Halving the distance decreases path loss by 9dB.

Doubling the distance increases path loss by 9dB.

Radio manufacturers advertise “line-of-sight” range figures. Line-of-sight means that, from antenna A, you can see antenna B. Being able to see the building that antenna B is in does not count as line of sight. For every obstacle in the path, de-rate the “line-of-sight” figure specified for each obstacle in the path. The type of obstacle, the location of the obstacle, and the number of obstacles will all play a role in path loss.

Visualize the connection between antennas, picturing lines radiating in an elliptical path between the antennas in the shape of a football. Directly in the center of the two antennas the RF path is wide with many pathways. A single obstacle here will

Page 65: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

65

have minimal impact on path loss. As you approach each antenna, the meaningful RF field is concentrated on the antenna itself. Obstructions located close to the antennas cause dramatic path loss.

Be sure you know the distance between antennas. This is often underestimated. If it is a short-range application, pace it off. If it is a long-range application, establish the actual distance with a GPS or Google Maps.

The most effective way to reduce path loss is to elevate the antennas. At approximately 6 ft (2 m) high, line-of-sight due to the Earth’s curvature is about 3 mi (5 km) so, anything taller than a well-manicured lawn becomes an obstacle.

Weather conditions also play a large role. Increased moisture in the air increases path loss. The higher the frequency, the higher the path loss.

Beware of leafy greens. While a few saplings mid-path are tolerable, it is very difficult for RF to penetrate significant woodlands. If you are crossing a wooded area, you must elevate your antennas over the treetops.

Industrial installations often include many reflective obstacles leading to numerous paths between the antennas. The received signal is the vector sum of each of these paths. Depending on the phase of each signal, they can be added or subtracted. In multiple path environments, simply moving the antenna slightly can significantly change signal strength.

Some obstacles are mobile. More than one wireless application has been stymied by temporary obstacles such as a stack of containers, a parked truck or material handling equipment. Remember, metal is not your friend. An antenna will not transmit out from inside a metal box or through a storage tank.

Path Loss Rules of Thumb To ensure basic fade margin in a perfect line-of-sight application, never exceed 50% of the manufacturer’s rated line-of-sight distance. This in itself yields a theoretical 6dB fade margin – still short of the required 10dB.

De-rate more aggressively if you have obstacles between the two antennas, but not near the antennas.

De-rate to 10% of the manufacture’s line-of-sight ratings if you have multiple obstacles, obstacles located near the antennas, or the antennas are located indoors.

Antennas Antennas increase effective power by focusing radiated energy in the desired direction. Using the correct antenna not only focuses power into the desired area but it also reduces the amount of power broadcast into areas where it is not needed.

Wireless applications have exploded in popularity with everyone seeking out the highest convenient point to mount their antenna. It is not uncommon to arrive at a job site to find other antennas sprouting from your installation point. Assuming these systems are spread spectrum and potentially in other ISM or licensed frequency bands, you still want to maximize the distance from the antennas as much as possible. Most antennas broadcast in a horizontal pattern, so vertical separation is more meaningful than horizontal separation. Try to separate antennas with like-polarization by a minimum of two wavelengths, which is about 26 inches (0.66 m) at 900 MHz, or 10 inches (0.25 m) at 2.4 GHz.

Cable Loss Those high frequencies you are piping to your antennas do not propagate particularly well through cable and connectors. Use high quality RF cable between the antenna connector and your antenna and ensure that all connectors are high quality and carefully installed. Factor in a 0.2 dB loss per coaxial connector in addition to the cable attenuation itself. Typical attenuation figures per 10 feet (3 meters) for two popular cable types are listed below.

Cable Types

Frequency RG-58U* LMR-400*

900 MHz 1.6 dB 0.4 dB

2.4 GHz 2.8 dB 0.7 dB

*Loss per 10 feet (3 meters) of cable length.

Figure G-2 Attenuation figures

While long cable runs to an antenna create signal loss, the benefit of elevating the antenna another 25 feet (7.6 m) can more than compensate for those lost dB.

Page 66: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

66

APPENDIX H – TRANSMIT POWER – DBM TO MW CONVERSION

Page 67: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

67

GLOSSARY ADC

Analog to digital converter.

Analog Input (AI)

An analog input is a measurable electrical signal with a defined range that is generated by a sensor and received by a controller. The analog input changes continuously in a definable manner in relation to the measured property.

Analog Output (AO)

An analog output is a measurable electrical signal with a defined range that is generated by a controller and sent to a controlled device, such as a variable speed drive or actuator. Changes in the analog output cause changes in the controlled device that result in changes in the controlled process.

Cu10

Copper 10 Resistance thermometers, also called Resistance Temperature Detectors (RTDs), are temperature sensors that exploit the predictable change in electrical resistance of some materials with changing temperature. They are slowly replacing the use of thermocouples in many industrial applications below 600 °C, due to higher accuracy and repeatability.

DCE

Data Communications Equipment. This indicates how a serial cable, DB9 or DB25 is pined out as far as inputs and outputs are concerned. A straight-through serial cable can be used when connecting a DTE device to a DCE device, but a null modem cable is required to connect a DCE to DCE or DTE to DTE device.

DIN

A standardized 35mm wide metal rail used for mounting industrial equipment inside racks and enclosures.

Digital Input (DI)

A digital input typically consists of a power supply (voltage source), a switch and a voltage-sensing device (analog-to-digital converter). Depending on the switch’s open/closed status, the sensing device detects a voltage or no-voltage condition, which in turn generates a logical 0 or 1, ON or OFF, alarm or normal or similarly defined state.

Digital Output (DO)

A digital output typically consists of a switch (either mechanical as in a relay, or electronic as in a transistor or triac) that either opens or closes the circuit between two terminals depending on the binary state of the output.

FCC

The Federal Communications Commission (FCC) is an independent United States government agency. The FCC was established by the Communications Act of 1934 and is charged with regulating interstate and international communications by radio, television, wire, satellite and cable. The FCC's jurisdiction covers the 50 states, the District of Columbia, and U.S. possessions.

Page 68: USER MANUALadvdownload.advantech.com/productfile/Downloadfile2/1-1I... · 2018. 6. 9. · 5.5 Establishing Connection to PC ... 56 Appendix B – Product Specifications ... Zlinx

Zlinx® Xtreme Wireless I/O

68

LOS

Line-of-sight propagation refers to electro-magnetic radiation including light emissions traveling in a straight line. The rays or waves are diffracted, refracted, reflected, or absorbed by atmosphere and obstructions with material and generally cannot travel over the horizon or behind obstacles.

PLC

Programmable Logic Controllers operate by producing signals that are sent to devices connected to PLC outputs.

Pt100

Platinum 100 Resistance thermometers, also called resistance temperature detectors (RTDs), are temperature sensors that exploit the predictable change in electrical resistance of some materials with changing temperature. As they are almost invariably made of platinum, they are often called platinum resistance thermometers (PRTs). They are slowly replacing the use of thermocouples in many industrial applications below 600 °C, due to higher accuracy and repeatability.

Pt1000

Platinum 1000 Resistance thermometers, also called resistance temperature detectors (RTDs), are temperature sensors that exploit the predictable change in electrical resistance of some materials with changing temperature. As they are almost invariably made of platinum, they are often called platinum resistance thermometers (PRTs). They are slowly replacing the use of thermocouples in many industrial applications below 600 °C, due to higher accuracy and repeatability. Suitable for air, water, oil and fuel temperature measurement applications.

RTD

Resistance thermometers, also called resistance temperature detectors (RTDs), are temperature sensors that exploit the predictable change in electrical resistance of some materials with changing temperature. As they are almost invariably made of platinum, they are often called platinum resistance thermometers (PRTs). They are slowly replacing the use of thermocouples in many industrial applications below 600 °C, due to higher accuracy and repeatability.

RSSI

In wireless communications, Received Signal Strength Indication (RSSI) is a measurement of the power present in a received radio signal.

Sinking

Refers to a device or component that accepts (absorbs) current. Conventional current flows into this sinking device.

Sourcing

Refers to a device or component that provides current. Conventional current flows out of a sourcing device

.

SCADA

Supervisory Control And Data Acquisition. It generally refers to an industrial control system: a computer system monitoring and controlling a process. The process can be industrial, infrastructure or facility based as described below.