user guide - con · pdf filecartridge (model 4102m) la249556 where xxx = 040, 045, 050, 060,...

52
4102C/M 100mm chart recorders User Guide E UR O T H E R M

Upload: lamkien

Post on 22-Mar-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

41

02C/M

10

0m

m c

hart

rec

ord

ers

User Guide

EUROTHERM

Page 2: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Major Functional items

Signal conditioning componentsShunt 100 .............LA246779UK10 Shunt 250 ............. LA246779UK25 Attenuator............... LA244180

ConsumablesBlue (channel 1)........................ LA249551Red (channel 2).........................LA249552Green (channel 3).....................LA249553Violet (channel 4).......................LA249554Annotator (black).......................LA249550

PENS (Model 4102C)

Z-fold (16 metres)....GD128970UxxxRoll (32 metres).......GD128971Uxxx

CHARTS

CARTRIDGE (Model 4102M)LA249556 Where

xxx = 040, 045, 050, 060, 070 or 075= number of chart divisions

EUROTHERM CHESSELL

CH4CH3CH2CH1

Scroll up Key

Scroll downKeyCursor Key

0 100

0 100

0 250

-10 0 10 20 30 40

CancelKey

Enter Key

Page 3: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

© 2006 Eurotherm Limited

All rights are strictly reserved. No part of this document may be reproduced, modified, or trans-mitted in any form by any means, nor may it be stored in a retrieval system other than for the purposeto act as an aid in operating the equipment to which the document relates, without the prior writtenpermission of Eurotherm limited.

Eurotherm Limited pursues a policy of continuous development and product improvement. Thespecifications in this document may therefore be changed without notice. The information in thisdocument is given in good faith, but is intended for guidance only. Eurotherm Limited will accept noresponsibility for any losses arising from errors in this document.

Eurotherm Recorders Limited hereby declares that the above products conform to the safetyand EMC specifications listed. Eurotherm Recorders Limited further declares that theabove products comply with the EMC Directive 89 / 336 / EEC amended by 93 / 68 / EEC,and also with the Low Voltage Directive 73 /23 / EEC

Declaration of Conformity

Manufacturer's name: Eurotherm Recorders Limited

Manufacturer's address Dominion Way, Worthing, West Sussex,BN14 8QL, United Kingdom.

Product type: Industrial chart recorder

Models: 4102C (Status level J12 or higher)4102M (Status level J12 or higher)

Safety specification: EN61010-1: 1993 / A2:1995

EMC emissions specification: EN50081-2 (Group1; Class A)

EMC immunity specification: EN50082-2

Signed: Dated:

IA249986U020 Issue 3 May 97

Signed for and on behalf of Eurotherm Recorders LimitedPeter De La Nougerde

(Technical Director)

Page 4: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform
Page 5: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 1HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

SAFETY NOTES

1. Before any other connection is made, the protective earth terminal shall be connected to a protective con-ductor. The Mains (supply voltage) wiring must be terminated in such a way that, should it slip in the cableclamp, the Earth wire would be the last wire to become disconnected.

2. In the case of portable equipment, the protective earth terminal must remain connected (even if the recorder isisolated from the mains supply), if any of the I/O circuits are connected to hazardous voltages*.

WARNING!Any interruption of the protective conductor inside or outside the apparatus, or disconnection of the protectiveearth terminal is likely to make the apparatus dangerous under some fault conditions. Intentional interruption isprohibited.

Note: In order to comply with the requirements of safety standard BS EN61010, the recorder shall have oneof the following as a disconnecting device, fitted within easy reach of the operator, and labelled as thedisconnecting device.a. A switch or circuit breaker which complies with the requirements of IEC947-1 and IEC947-3b. A separable coupler which can be disconnected without the use of a toolc. A separable plug, without a locking device, to mate with a socket outlet in the building

3. The mains supply fuse within the power supply unit is not replaceable. If it is suspected that the fuse is faulty, themanufacturer's local service centre should be contacted for advice.

4. Batteries within recorders are not user replaceable. Contact the manufacturer's local service centre if a problem issuspected.

5. Whenever it is likely that protection has been impaired, the unit shall be made inoperative and secured againstunintended operation. The nearest manufacturer's service centre should be consulted for advice.

6. Any adjustment, maintenance and repair of the opened apparatus under voltage, should be avoided as far as possi-ble and, if inevitable, shall be carried out only by a skilled person who is aware of the hazard involved.

7. Where conductive pollution (e.g. condensation, carbon dust) is likely, adequate air conditioning/filtering/sealingetc. must be installed in the recorder enclosure.

8. Signal and supply voltage wiring should be kept separate from one another. Where this is impractical, shieldedcables should be used for the signal wiring.

9. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipmentmight be impaired.

* A full definition of "Hazardous' voltages appears under 'Hazardous Live' in BS EN61010. Briefly, under normaloperating conditions, hazardous voltages are defined as > 30V RMS (42.2V peak) or > 60V dc.

SYMBOLS USED ON THE RECORDER LABELLING

One or more of the symbols below may appear on the recorder labelling.

! Refer to the Manual for instructions

Protective Earth

This recorder for ac supply only

This recorder for dc supply only.

Risk of electric shock

This recorder for either ac or dc supply

Page 6: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 2

100 MM RECORDER USER GUIDE

Section Page

USER GUIDE

LIST OF CONTENTS

SAFETY NOTES ........................................................................ 1SYMBOLS USED ON THE RECORDER LABELLING......................... 11 INTRODUCTION................................................................... 4

ANNOTATOR BATTERIES ..................................................41.1 Unpacking the recorder .............................................................4

2 INSTALLATION .................................................... 42.1 MECHANICAL INSTALLATION ............................................. 42.2 ELECTRICAL INSTALLATION ................................................. 42.3 PEN/PRINT CARTRIDGE REPLACEMENT ............................... 7

2.3.1 Continuous-trace recorders ......................................................72.3.2 Multipoint recorders ...............................................................7

2.4 CHART REPLACEMENT ....................................................... 82.4.1 Z-Fold charts .........................................................................82.4.2 Roll charts .............................................................................9

3 OPERATION AND CONFIGURATION .................... 103.1 OPERATION ...................................................................... 10

3.1.1 Channel Hold .......................................................................103.1.2 Channel scroll (Manual) .........................................................103.1.3 Units display .........................................................................103.1.4 dFlt display ...........................................................................103.1.5 rEn.n display .........................................................................113.1.6 Annotation ............................................................................11

POWER-UP MESSAGE ......................................................11ALARM ON/OFF MESSAGES ...........................................11CYCLIC MESSAGES .........................................................11ON/OFFLINE MESSAGES ................................................12

3.2 CONFIGURATION ............................................................. 12OPERATOR ACCESS LEVEL ...............................................12ENTER INDICATOR ..........................................................12NUMERIC ENTRY .............................................................13

3.2.1 Configurable items ................................................................14CHARACTER SET .............................................................15

3.2.2 Pen Park/Fan ........................................................................153.2.3 Chart speed ..........................................................................15

MULTIPOINT RECORDERS .................................................15CONTINUOUS-TRACE RECORDERS ...................................15

3.2.4 Zero ....................................................................................15MULTIPOINT RECORDERS .................................................15CONTINUOUS-TRACE RECORDERS ...................................15

3.2.5 Span ....................................................................................153.2.6 Time and date setting .............................................................163.2.7 ADJ ......................................................................................16

ZERO .............................................................................16SPAN .............................................................................16CLR ................................................................................16

3.2.8 Alarm set up .........................................................................17

Page 7: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 3HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

3.2.9 Range ..................................................................................18TYPE ...............................................................................19LO/HI .............................................................................19LIN .................................................................................19UNIT ..............................................................................19SCLO/SCHI ....................................................................19LO/HI .............................................................................19CJC ................................................................................19EJC.................................................................................19SHUN.............................................................................19RESP ...............................................................................19DECP ..............................................................................19

3.2.10 UNIT ..................................................................................203.2.11 INST ..................................................................................20

PASS ..............................................................................20CREL ...............................................................................20DESC..............................................................................20HYST ..............................................................................21N.NES ............................................................................ 21ACES .............................................................................21CASS .............................................................................21

4 OPTIONS ........................................................... 224.1 RELAY OUTPUTS ................................................................ 22

4.1.1 Three change-over relays board .............................................. 224.1.2 Four normally-open relays board ............................................. 234.1.3 Four normally-closed relays board ........................................... 23

4.2 TRANSMITTER POWER SUPPLY OPTION............................... 244.2.1 Introduction........................................................................... 24

FUSES ............................................................................ 24SAFETY ISOLATION .........................................................24

4.2.2 Signal wiring ........................................................................244.3 EVENT INPUT OPTION ....................................................... 25

4.3.1 Contact input 1 .....................................................................254.3.2 Contact input 2 .....................................................................254.3.3 Contact input 3 .....................................................................254.3.4 Contact input 4 .....................................................................254.3.5 Event input wiring .................................................................. 264.3.6 Safety isolation ......................................................................26

4.4 CHANNEL TAGS OPTION .................................................. 274.4.1 Units display .........................................................................274.4.2 Cyclic messages ....................................................................274.4.3 Range ..................................................................................28

5 COSHH DATA ..................................................... 295.1 RECORDING PENS ............................................................ 295.2 PRINTHEAD INKS............................................................... 305.3 NI-CAD BATTERIES ............................................................. 315.4 NICKEL - METAL HYDRIDE BATTERIES ................................... 326 TECHNICAL SPECIFICATION ................................. 336.1 TECHNICAL SPECIFICATION (Recorder) ............................... 336.2 TECHNICAL SPECIFICATION (Input board) ............................ 357 GLOSSARY OF TERMS ......................................... 37INDEX .................................................................... 41

LIST OF CONTENTSSection Page

Page 8: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 4

100 MM RECORDER USER GUIDE

100 mm. RECORDER USER GUIDE

1 INTRODUCTION

The main part of this manual describes recorders fitted with membrane switches on each side of the display unit. An-nex A contains information on older models, (those with status levels prior to L19 (Multi-point recorders) or L22(Continuous-trace recorders)). The status level appears as the last two or three character section of the recorder serialnumber.

The recorder comes in two versions - a continuous-trace recorder with up to four pens and a multipoint recorder giv-ing up to six traces on the chart. Chart annotation is standard with the multipoint version, but is an optional extra(specified at time of order) with the continuous trace recorder. Annotating recorders print power-on and alarm on/offmessages, time and date. Scales and channel tags are also printed on the chart to simplify trace interpretation.

Designed to fit a DIN cutout (138 x 138 mm) the recorders feature an exceptionally small back of panel dimension of220 mm. (no terminal cover) or 236 mm (with cover).

ANNOTATOR BATTERIES

When the batteries associated with the recorders are fully charged, they will maintain the real-time clock for approxi-mately one month (depending on temperature etc.), without power applied to the recorder. The batteries areuncharged when despatched from the factory, and it takes approximately 175 hrs to charge them fully. Should powerbe removed from the recorder before this, the retention time will be reduced accordingly.

1.1 Unpacking the recorder

The recorder is despatched in a special pack designed to give adequate protection during transit. Should the outer boxshow signs of damage, it should be opened immediately and the recorder examined. If there is evidence of damage,the instrument should not be operated and the local representative contacted for instructions. After the recorder hasbeen removed from its packing, the packing should be examined to ensure that all accessories and documentationhave been removed. Once the recorder has been installed, any internal packing should be removed, and stored withthe external packing, against future transport requirements.

2 INSTALLATION

2.1 MECHANICAL INSTALLATION

Figure 2.1 gives installation details.

The recorder is inserted through the panel aperture from the front of the panel. With the weight of the recorder sup-ported, the panel clamps are inserted into one pair of the rectangular apertures (either at the top and bottom or at theright and left sides) of the recorder. The jacking screws are then be tightened sufficiently to clamp the recorder intoposition. EXCESS FORCE SHOULD NOT BE USED IN TIGHTENING THESE SCREWS.

2.2 ELECTRICAL INSTALLATION

Warning!Refer to the safety notes on page 2 of this manual before proceding.

Figure 2.2 gives mains (line) and signal wiring information.

Page 9: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 5HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

Figure 2.1 Mechanical installation

137mm

View on underside

Alternative locationfor case clamp

View on right hand side

30mm

200 mm220 mm

Maximum panelthickness = 25 mm

137mm

236 mm(Short terminal cover)

Case clamp

275 mm(Closed long terminal cover)

390 mm(Open long terminal cover)

1.75 mm

Panel cutout details

144 mm

144

mm

Front view

30˚30˚

Ver

tical

Maximum installed angles Case clamping

Panel cutout138mm x 138 mm

(both – 0.0 + 1.0 mm)

Min. inter-recorderdistance: 35 mm

Page 10: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 6

100 MM RECORDER USER GUIDE

Figure 2.2 Electrical Installation

Line(DC+)

Neutral(DC-)

DC polarity not important,but + terminal is fused

Input board

Earth Line(DC+)

Neutral(DC-)

V+ V- I V+ V- I V+ V- I V+ V- I

Line input: 90 to 264V at 45 to 65 HzOR, if Low Voltage Option fitted,

20 to 53V dc or ac (45 to 400 Hz RMS)

Safety cover not shownfor clarity

Option board(s)

Option board(s)

Continuous-trace recorder

Input board

Earth

V+ V- I V+ V- I V+ V- I V+ V- I

Safety cover not shownfor clarity

Option board(s)

Option board(s)

V+ V- I V+ V- I

Multi-point recorder

DC V (-2V < Vin < 10V)DC mV

Thermocouples

+ –

V+ V- I

DC mA

Shuntassembly

V+ V- I

+ –

DC V

(– 20V to +100V)

Attenuatorassembly

V+ V- I

+ –

3-wire resistancethermometer

V+ V- I

2-wire resistancethermometer

V+ V- I

Potentiometer

V+ V- I

Resistance inputs not available at channel 1, if any other channel is a thermocouple input

Signal wiring

Wire sizes:Power: 0.5 mm2 (min)Signal: 2.5 mm2 (max)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

DC polarity not important,but + terminal is fused

Removal of the CJ sensor from the inputboard terminal block to allow use ofchannel 1 to measure resistive inputs(Input type = RTD or Ohm).

It is recommended that when mixed inputsare being used, thermocouples are wiredto the lowest channel numbers. If channel1 is set to RTD or Ohm, then the CJsensor must be disconnected, as shownabove, and any other channel set toThermocouple must use an External ColdJunction.

1. Prise cover off

2. Release terminals 11 and 12

3. Remove CJ sensor

Line input: 90 to 264V at 45 to 65 HzOR, if Low Voltage Option fitted,

20 to 53V dc or ac (45 to 400 Hz RMS)

Ch1 Ch2 Ch3 Ch4 Ch3 Ch4 Ch5 Ch6Ch1 Ch2

Page 11: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 7HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

BackgroundDisplay

Enter Password

Multi-point Continuous

Set pen / printheadto chart zero

Set pen/printheadto chart full scale

Figure 2.3.1 Cartridge removal

Figure 2.3.1 Pen removal

Figure 2.3 Pen park key strokes

2.3 PEN/PRINT CARTRIDGE REPLACEMENT

Notes:1. Care should be taken to avoid pen/cartridge contact with

skin or clothing2. The password is set to 010 at the factory but can be edited

in Instrument Configuration.

Before changing the pens/print cartridge, the pens should beparked (fanned) as follows (ref. figure 2.3).

1. From the background display, operate the 'Enter' key.2. Scroll-in the password, then operate 'Enter' twice.

The chart stops and the pens fan, or the printhead moves tothe centre of its travel; the 'H' symbol is illuminated to indi-cate that the instrument is in 'chart hold' mode.

Once replacement is complete, operate the Cancel (X) keythen use the 'Up arrow' key to access the zero and span set-ting keys. These allow the position of the new pens / print-head to be aligned with the 0% and 100% grid lines on thechart.

2.3.1 Continuous-trace recorders

Once the pens have fanned, open the recorder door and thedisplay unit (both hinged at their left edge) and pull each ofthe exhausted pens forwards off its guide bar.

Fit the new pens, by pushing them carefully onto the guidebar

2.3.2 Multipoint recorders

Once the printhead has parked, open the recorder doorand the display unit (both hinged at their left edge).

Remove the cassette (section 2.4) and pull the ex-hausted print cartridge vertically downwards out of itsholder.

Offer up the new cartridge to the printhead, and push itupwards into place.

Return the cassette to the chassis and close the displayunit and the recorder door.

Page 12: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 8

100 MM RECORDER USER GUIDE

Place new chart in pay-outtray

Chart guide

Retain chartbehind flanges

Close top

Fan new chart

Take-up retainer

Remove old chart

Lay two or three leaves intake-up tray, ensuring theyfold naturally. Close take-upretainer and chart guide.

Remove cassette

2.4 CHART REPLACEMENT

Note:For recorders with status levels K13 or higher, if thecassette type (i.e. roll or z-fold) is changed, or if therecorder loses its configuration, the recorder must bereconfigured for the correct cassette type (Instru-ment configuration) or the chart drive will not oper-ate correctly.

Before changing the chart, carry out a pen park/fan asdescribed in section 2.3 above. Once the chart replace-ment is complete, carry out an alignment procedure asdescribed in sections 3.2.4 and 3.2.5, below.

2.4.1 Z-Fold charts

Remove the cassette, by pulling on the two latches asshown in the top figure. If a used chart is present, openthe take-up retainer and remove the used chart.

Open the top of the paper pay-out tray, and remove anyresidual paper dust. Open the chart guide.

Unpack the replacement chart and fan it several times toseparate the leaves and to remove as much perforationdust as possible.

Orient the chart so that the circular holes are to the left,the slots to the right, and the red end-of-chart line to theback (all directions relative to the front of the cassette).Place the chart into the pay-out tray, unfolding three orfour leaves at the same time. Pull the free end of thechart over the drive roller and down behind the chartguide and lay the free leaves in the take-up tray.

Ensure that the paper folds naturally into the tray, thatthe printed grid is uppermost and that the slots are at theright hand edge of the chart (i.e. the circular holes are tothe left).

Close the take-up retainer and the chart guide, ensuringthe paper holes/slots fit over the sprockets on the driveroller. Close the top of the paper pay-out tray, ensuringthat the chart is contained behind the flanges on the top.

Page 13: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 9HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

Remove cassete by pressing down on, then pulling on theretaining clip.

1

4

5

6

Insert new chart roll

Lift 'ears' to eject take-upspool with used chart.

Remove inner tube

3

Pull off either end pinion

8

7

Slide the chart off the take-up spool, then push thepinion fully back onto the empty spool.

10Tear the corners off the chart, thenfold about 5mm of the point back

Insert the fold into the slot, then roll thepaper onto the take-up spool, and re-insertthe spool into the cassette.

11

9Feed chart underpaper guide/chart tear-off.

Close the cassette top

12

Close the paper guide/chart tear off strip,ensuring that the chart is 'square' with thecassette.

13

Tension the chart.

14

Open cassette top

2Open cassette top

2.4.2 Roll charts

Carry out the'Park procedure described in section 2.3 above. Once the chart has been replaced, return the cassette tothe recorder and check the pens' zeros/spans against the new chart as described in sections 3.2.4 and 3.2.5.

Page 14: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 10

100 MM RECORDER USER GUIDE

3 OPERATION AND CONFIGURATION

3.1 OPERATION

The four-character, blue display shows the process value (PV) of each channel in turn, with each channel remainingon display for 5 seconds. If 'Units' is selected 'yes' in 'Units configuration', the channel display units alternate with thePV at the display. Current channel number is indicated by a green numeric character to the left of the PV display. Redarrow heads to the right of the PV display indicate which (if either) of the displayed channel's alarms is active, andwhether the alarm is configured absolute high (up arrow) or absolute low (down arrow).

Operation of either the Enter or the Cancel key allows entry to the recorder's configuration menus, via a password.The password is set to 010 at the factory, but can be edited in 'Instrument Configuration' (section 3.2.11).

Notes:1. Channels configured as 'Off' do not appear in the scroll sequence. If all channels are off, then channel 1 is shown

'Off' continuously.2. Unit string characters k, w and x cannot be displayed by a seven-segment display and are replaced by the special

symbol ' '. Similarly, the letter 'm' is displayed as 'n.n'. Because 'n.n' takes two character spaces, if an 'm' is usedin a unit string, the right-most character of four-character strings is lost. The above applies only to the display - thecharacters are printed correctly on the chart.

3. If the actual input value exceeds the configured range, +999.9 is displayed for over range; -999.9 for under range.

3.1.1 Channel Hold

Operation of the cursor key causes the currently displayed channel's value to remain permanently on display (Channelhold). Channel hold is indicated by a red 'H' below the channel number. (This red 'H' symbol is also used to displaychart hold (pen park) mode.) To return to normal scroll mode, the cursor key is operated a second time.

3.1.2 Channel scroll (Manual)

The channels can be scrolled through in both normal and channel hold mode by operation of the scroll up/down keys.In manual scroll all fitted channels are displayed when called, even if they are configured to be 'Off'.

3.1.3 Units display

See section 4.4.1 instead, if the 'Channel Tags' option is fitted.

If 'Units' have been selected 'yes' in the top level configuration menu, then the PV and Units displays alternate, withthe PV being displayed for three and a half seconds, then the units string for a second and a half. See note 2 above forun-displayable characters.

3.1.4 dFlt display

If the recorder's configuration should be found to be corrupt at power-up, a default configuration is loaded instead and'dFlt' is displayed, as a warning to the user, until either the Cancel or Enter key is operated.

Current channelnumber

Channel holdsymbol

Channel value

Minussign

Alarm 2High

Alarm 1Low

Alarm 2Low

Alarm 1High

CancelKey

EnterKey

Scrollup Key

Scrolldown Key

CursorKey

Page 15: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 11HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

14:40_

400.0 800.0Ch1 Deg.C

30/08/95

300MM/H

Figure 3.1.6 Cyclic message printing example

3.1.5 rEn.n displayThis (remote operation) is displayed whilst configuration transfer is taking place via the configuration port

3.1.6 Annotation

Note: This applies to multi-point recorders and to those continuous-trace recorders that are fitted with the annotationoption. Message colours give below apply only to multi-point recorders: for annotating continuous-trace recorders,the messages are always in black.

The following types of message can be printed on the chart:

POWER-UP MESSAGEHH:MM:SS DD/MM/YY dddddddddddddddddddd

This message is printed in blue at each power-up, and consists of the folowing elements:HH:MM:SS Power-on timeDD/MM/YY Power-on date either as shown or as MM/DD/YY according to the format (fn.nt) selected in clock con-

figuration - section 3.2.6ddd-ddd A 20 character descriptor editable in 'Instrument configuration'. Initially set to 'Instrument'

CYCLIC MESSAGES

Note: If the 'Channel Tags' option is fitted see section4.4.2 instead.

Cyclic messages are printed on the chart approxi-mately every 2 cm. on a convenient time boundary.The messages are right-justified on the chart and areprinted in the following order:

Time; Date; Chart speed; Channel 1 tag, units andscale; Time; Date; Chart speed; Channel 2 tag, unitsand scale; ...and so on. Channel information isprinted on two lines, with Channel tag and scale 'zero'value at the left of the chart and units and span valueat the right of the chart, as illustrated in figure 3.1.6

ALARM ON/OFF MESSAGESHH:MM:SS ALARM ON(OFF) C:A

If so configured in the Instrument configuration (section 3.2.11), these messages, printed in black, appear when analarm becomes active or ceases to be active, and consist of the following elements:

HH:MM:SS Alarm on(off) timeALARM ON Specifies that the alarm became active at the above timeALARM OFF Specifies that the alarm ceased to be active at the above timeC Channel numberA Alarm number

Notes1. Alarm messages are printed in preference to cyclic messages, should they occur simultaneously.2. Alarm messages are inhibited when the Event Input option is fitted (section 4.3).

Page 16: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 12

100 MM RECORDER USER GUIDE

1234

P000

P000

P010

FAnPArc

Figure 3.2aEntry to configuration

Pen fan/printhead park 1Set chart speed 1Align traces to chart zero and full scale 1Set clock (date, time and date format) 1Carry out input adjust 2

FunctionMinimum access

level required

3.1.6 ANNOTATION (Cont.)

ON/OFFLINE MESSAGES

OFFLINE HH:MM:SS ONLINE HH:MM:SS

where HH:MM:SS are the times of occurrence, is printed in black whenever the recorder comes on-line (e.g. after thepens/printhead have been changed, or when the process value display is returned to from a configuration menu).

3.2 CONFIGURATION

Initial entry to configuration is achieved from the background display by operation of theEnter or Cancel key and then entering a password (initially 010). To enter the password010, carry out the following procedure.

From background display, press the Enter or Cancel key

Display changes to 'P000' with the left-most 0 flashing

Operate the cursor key.

Left-most 0 stops flashing, centre 0 flashes.

Operate Scroll Up key - centre 0 changes to 1

Operate Enter key

Display changes to FAn or PArc according to model

The rest of the Configuration menu (fig 3.2.1) is accessed using up/down arrow keys.

OPERATOR ACCESS LEVEL

Initially set to '0', this 'access level' requires the user to enter a password direct from the background display as de-scribed above. Once entered, the user has full access to the recorder's configuration. See section 3.2.11 (PASS) fordetails of password editing.

Setting the access level to 1 or 2 (AcES - Instrument configuration - section 3.2.11) allows the operator to carry outthe operations shown in table 3.2 without needing to enter the password.

Table 3.2 Operator access levelsENTER INDICATOR

Whenever a change is made to a configurable item, an E symbol appears in the channel number display. Operation ofthe Cancel (X) key resores the previous value and extinguishes the E. Operation of the Enter key, saves the new valueto the recorder's data base, and the E symbol disappears in three stages, as depicted below whilst the save takes place.

Page 17: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 13HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

0.000

0.000

1.000

2.000

3.000

3.000

3.100

3.200

3.300

3.400

3.400

3.400

03.40

03.40

13.40

23.40

23.40

23.40

23.40

023.4

023.4

123.4

123.4

Figure 3.2bEntering values greater than 9.999

3.2 CONFIGURATION (Cont.)

NUMERIC ENTRY

There are two types of numeric field which can be identified - thosewhich display one of a fixed number of choices which are scrolledthrough using the up/down arrow keys (e.g. chart speed), and thosewhich have to be entered character by character. Scrollable fields canbe recognised because all the displayed characters flash together,whereas character-by-character items flash only the currently editablecharacter.

For the latter type, numbers greater than 9.999 (e.g. alarm thresholds)are entered as described in the following example, which shows how toenter a value of '123.4'. Because this document cannot easily show aflashing character the currently editable character is shown underlined.

Notes:1. The flashing 'H' character indicates that the – sign is the editable

character, and this – sign can be toggled on and off using the up/down arrow keys.

2. The units character is entered first (after the +/- sign), then the deci-mal point position.

3. To move the decimal point to the 10s or 100s position, the cursorkey is operateda) when the editable character is the least significant (right-most)digit (LSD), ANDb) this LSD is 0.Operating the cursor with anything other than zero as the LSD failsto shift the decimal point position.

4. Unless the display format is already 0.000, setting the most signifi-cant character to zero, then operating the cursor key, moves thedecimal point position left. For example, if you were to reset thevalue from 123.4 to 23.4, the display would change from 023.4 to23.40 when the cursor key was operated.

Page 18: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 14

100 MM RECORDER USER GUIDE

Edit alarm setpoint.Select absolute high or low as typeALn.n

Scroll up

Scroll down

Enter (select field/ confirm edit)

Cancel (cancel changes / leave field)

Cursor (select next digit/character)

KEYS

Background Display

Set chart speed(Scroll list)

Align pen with chart 0%

Align pen with chart 100%

Include units in PV display(PV and units alternate on display)

Adjust input

Edit password; Select common relay on/off;Enter instrument descriptor; Select cassette type;Set alarm hysteresis; enable/disable alarm messages;Select operator access level

Set input type, range, linearisation function, units, CJ type,Shunt value and break response

Enter Password(if access level 0)

Changepens/chart

-88881

P010

FAn

PArc

SPd

ZEro

SPAn

rng

Unit

Adj

Inst

Set time and date.select DDMMYY or MMDDYYCLoC

CnFg Enter Password(if access level 1) P010

CnFg Enter Password(if access level 2) P010

Access level= 0 or 2

Access level = 1

Access level= 0 or 1

Access level = 2

Continuous trace

Multipoint

Access level= 1 or 2

Access level = 0

Continuous-trace recordersrequire annotator

3.2.1 Configurable items

Figure 3.2.1 shows the order in which configurable items appear in what is called 'the top level configuration menu'.The figure shows the 'up arrow' order. Use of the down arrow reverses the order. Use of the Enter key takes the userdown to the next level of menu - the Cancel key takes the user back up one menu level each time it is used.

Figure 3.2.1 Configuration items

Page 19: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 15HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

3.2.1 CONFIGURABLE ITEMS (Cont.)

CHARACTER SET

The printable character set is A to Z, 0 to 9, hyphen, space, degrees, underscore. The displayable characters are limitedby the nature of a seven-segment display; characters which cannot be displayed, even approximately (k, m, w, x), arereplaced by the special symbol ' '.

In scroll lists, mV for example is displayed as 'n.nU', and a type K thermocouple is displayed as 'Ca'.

3.2.2 Pen Park/Fan

As described in section 2.3, this is used to disable the chart and pen drives of the recorder so that the chart and pensor print cartridge can be changed safely. In the case of the continuous trace recorder, the pens 'fan' to allow easy ac-cess to them all.

3.2.3 Chart speed

Entry from the SPd display allows the chart speed to be chosen from a scroll list, using the scroll up and/or scrolldown keys. The chart speeds available are:

MULTIPOINT RECORDERSOff, 5 mm/hr, 10mm/hr, 20mm/hr, 30mm/hr, 60mm/hr, 120 mm/hr

CONTINUOUS-TRACE RECORDERSOff, 5 mm/hr, 10mm/hr, 20mm/hr, 30mm/hr, 60mm/hr, 120 mm/hr, 240mm/hr, 300 mm/hr, 600mm/hr, 1200mm/hr,3600mm/hr, 18m/hr (18n.n), 36m/hr (36n.n). If the annotator option is fitted, it will print only up to and including300mm/hr chart speed

3.2.4 Zero

This is used to align the traces to chart zero.

MULTIPOINT RECORDERSUpon entry, the chart advances, and a trace is placed on the chart where the recorder thinks chart zero is. The up anddown arrow keys are used to adjust the position of the trace so that it is aligned with the chart zero grid line.

CONTINUOUS-TRACE RECORDERSUpon entry, the up/down scroll keys are used to select a channel (default = channel 1). Use of the Enter key causesall pens but that associated with the selected channel to move to the centre of chart, whilst the selected pen moves towhere it believes chart zero is. The up and down scroll keys are used to align this pen's trace to the chart zero gridline. Operation of the Enter key confirms the new zero position.

To align another pen, use the cancel (x) key to return to the channel select page, use the up/down scroll keys to selectanother channel (annotator = A), and repeat the above process. Once all the required channel pens have been zeroed,two operations of the cancel key take the user back to the main menu.

3.2.5 Span

This is used to align the traces with chart full scale, and operates in exactly the same way as described above for chartzero, except, of course, that the alignment is carried out to the 100% chart grid line, not the 0% grid line.

Page 20: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 16

100 MM RECORDER USER GUIDE

Edit hours using up/down arrows;Enter confirms

CLoc

Hour

nnin

dAtE

nnth

YEAr

Fnnt

15

50

01

05

1998

Eu USA

Edit day number using up/down arrows;Enter confirms

Edit month number using up/down arrows;Enter confirms

Edit year using up/down arrows;Enter confirms

SelectDD/MM/YY orMM/DD/YYEnter confirms

Edit minutes using up/down arrows;Enter confirms

3.2.6 Time and date setting

Note: This section applies to continuous-trace recorders only if they are fitted with the annotation option.

Figure 3.2.6 shows the key strokes necessary to set the time and date (in this example to 10 minutes to 4 o'clock pmon the 1st May 1998), and how to set the date format to European (Eu) which is Day/Month Year, or American (USA)which is Month/Day/Year. The clock re-starts at each operation of the Enter key, although it is not printed on thechart until the recorder is returned to its 'on-line' status using the Cancel (X) key.

Figure 3.2.6 Time and date setting

3.2.7 ADJ

The adjust section allows the recorder's input circuits to be adjusted to make allowance for non-standard inputs. Ifboth zero and span are adjusted, a dual point gain and offset adjustment will be applied. If only zero or only span isadjusted, then a single point offset adjustment will be carried out.

Note: If the hardware capabilities are exceeded, or if the input is in ERROR, or if the input has been configured withan invalid range, the displayed value is ---- and in such cases the adjustment is ignored.

ZEroAfter selecting the required channel for adjustment, operate the Enter key whilst 'ZERO' is displayed. Apply a knowninput, as close to the required zero point as possible. Use the cursor and up/down arrow keys to set the displayedvalue to the known input value. A further operation of the Enter key confirms the change.

SPAnThis operates in the same way as described for 'ZERO' above, except the known input should be as near to the re-quired span value as possible.

CLrOperation of the Enter key whilst CLr is displayed calls a confirmation menu in which the up or down arrow is usedto select 'yes' or 'no'. Operation of the Enter key with 'yes' selected causes any adjustments previously made to therelevant channel to be removed.

Page 21: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 17HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

ALnn

SEtP2

Type2

AL 12

AL 11

AL 21

AL 12

SEtP2

12342

23452

Type2

Hi2

Lo2

ALnn

Channel No

Edit setpoint

3.2.8 Alarm set up

This allows an alarm threshold to be set, and the alarm type to be defined as absolute high or absolute low. The defaultthreshold setting is 0.000 and this can be edited using the up and down arrow keys and cursor as described in section3.2 above.

Figure 3.2.8 shows the keystrokes necessary to set the threshold of Channel 2, alarm 1, and how to define it as abso-lute low.

An alarm can be disabled only by setting its threshold outside the range of the input signal.

See also CREL (section 3.2.11) for details of how to use the relay associated with channel 1 alarm 1 as a global alarmindicator and HySt (section 3.2.11) for how to set a hysteresis value for all alarms. (See glossary for a description ofhysteresis.)

Figure 3.2.8 Alarm configuration example

Page 22: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 18

100 MM RECORDER USER GUIDE

rng

Lo

1

Hi

Lin

Unit

CJC

ECJ

resp

decp

rng

type

set channelnumber

1

1

1

1

1

1

1

1

1

Select linearisationfunction

Select ˚C or ˚F

Select CJC type(Only for Type = TC)

If CJC type = external,enter temp

Set break responsehigh, low or none

Set display decimalpoint position

Type = TC or RTDLin = TC or RTD type

rng

Lo

1

Hi

Lin

SCLo

SCHi

Unit

Shun1Enter shunt value(only for Type = mA )

decp

rng

type

set channelnumber

1

1

1

1

1

1

1

1

Type = Volts / mV / mA / ohmLin = Linear or square root

Select linearisationfunction

Enter scale low andhigh values

Enter units textstring

Enter input rangelow and high values

Set display decimalpoint position

rng

Lo

1

Hi

Lin

Lo

Hi

Unit

Shun

decp

rng

type

set channelnumber

1

1

1

1

1

1

1

1

1

Type = Volts / mV / mA / ohmLin = T/C or RTD

resp1Set break response

high, low or none

Select linearisationfunction

Enter linearisationrange low and high

values

Select ˚C or ˚F

Enter shunt value(only for Type = mA )

Set display decimalpoint position

respSet break responsehigh, low or none

1

Enter input rangelow and high values

Enter input rangelow and high values

3.2.9 Range

Note: See section 4.4.3 instead, if the 'Channel tags' option is fitted.

This section allows the configuration of the input channels to be entered. Figure 3.2.9 shows the top level range con-figuration menu for three cases:1. Input type = thermocouple or RTD; Linearisation = TC or RTD type.2. Input type = V, mV, mA or ohms; Linearisation type = linear or square root and3. Input type = V, mV, mA or ohms; Linearisation function = Thermocouple or RTD type.This last combination is used with transducer transmitters which do not incorporate their own linearisation tables.

Notes:1. Channel one must not be used whilst configured as 'Ohm' or 'RTD' unless the CJ sensor has been disconnected

(figure 2.2), or gross measurement errors will occur. When the CJ sensor disconnected, no other input channelshould be configured as T/C unless it uses an external CJC.

2. The background (PV) display will show 'brng' (bad range) if any one or more of the following obtain:a. Input range low ≥ Input range highb. Linearisation range low ≥ Linearisation range highc. Scale low = Scale highd. Hardware capabilities are exceedede. Linearisation type is inappropriate to the rest of the configuration

Figure 3.2.9 Channel range configuration menu

Page 23: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 19HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

3.2.9 RANGE (Cont.)type

Scrollable through Off, tc (thermocouple), mV, Volts, mA, RTD, Ohm. If Off, then none of the headings below ap-pears. Where different input types are to be used, resistive inputs (RTD or potentiometer) should not be connected tochannel 1. If channel 1 input must be resistive, the cold junction sensor must be disconnected as shown in figure 2.2above, and any thermocouple inputs must then use external cold junction compensation.

Lo/HiThese two input range entries represent the lowest and highest values the input is likely to have placed across it, inengineering units. (E.G. For a thermocouple, the input range would be in ˚C or ˚F.)

LINThis allows a linearisation function to be chosen for the input. The scrollable list consists of the following where theactual displayed item appears in parentheses (), if it is affected substantially by the constraints of the display:Thermocouples type: B, C, D, E, G2 ( 2), J, K (CA), L, N, R, S, T, U, NiNiMo (nini), Platinel (Plt).Resistance thermometers type: Pt100DIN (P100), Pt100ANSII (P10A), JPt100 (JP10), Pt1000 (1000),

Ni100 (N100), Ni120 (N120)Other linearisations: Linear, Square root.

UNITFor thermocouple or RTD types, the units string can be scrolled between ˚C and ˚F as required. For other types, afour character units string can be entered, using the text entry techniques described in section 3.2.1 (Character set).

SCLo/SCHiFor mV, mA and Volt input types only, this allows a scale low and scale high value to be entered. For example, a volt-age input of 0 to 5 Volts (input range) may be required to be displayed, for example, as 0% (Scale low) to 100%(Scale high), or 1000 to 5000 RPM and so on.

Lo/HiWhere this appears after the LIN menu item, these entries cater for the case where a remote transducer is attached to anon-linearising transmitter. In these circumstances a signal of, say, 4 to 20 mA (input range) might be equivalent to400 to 1600 ˚C (linearisation range). It is this linearisation range which is entered here.

CJCThis field appears only when 'type' = tc, and' Lin' is a thermocouple type, and allows the user to use no cold junctioncompensation (CJC) (none), the internal CJC supplied by the recorder (int), or an external cold junction held at aknown temperature (Etn). Where external is selected, the following item is 'EJC', which allows the temperature of theexternal CJC to be entered.

EJCAllows the temperature of an external cold junction to be entered. See CJC immediately above for more details. ThisEJC item appears only when CJC has been selected as external (Etn).

SHUNAllows a shunt value to be entered for mA type inputs.

RESPAllows the user to select none, Drive High (drhi) or Drive Low (Drlo) as the recorder's response to an open circuit(R>10MΩ) at its input. Where 'none' is selected, the channel drifts according to the induced voltages in the signalwiring. When selected high (low) the channel will be traced at >100% (<0%) on the chart.

DECPAllows the user to determine the position of the decimal point at the recorder display. The positions can be scrolledthrough, from 0.000 through 00.00 and 000.0 to 0000.

Page 24: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 20

100 MM RECORDER USER GUIDE

3.2.10 UNIT

This allows the user to choose whether or not to display the channel units or not. If 'No' is selected, the backgrounddisplay carries out its normal 5-second scroll through the channels as described in section 3.1 above. If 'Yes' is se-lected, then the normal 5-second scroll continues, but each channel's units are displayed for about a second and a halfjust before the next channel's PV appears. See Note 2 in Section 3.1 regarding non-displayable characters.

3.2.11 INST

This section of the configuration allows the Password to be edited, the 'Common Relay' function to be enabled/disa-bled, the chart cassette type to be defined (roll or z-fold (fanfold)), Alarm Hysteresis to be set, Alarm messages to beenabled or disabled, an instrument descriptor to be entered and the operator access level to be defined.

Figure 3.2.11 Instrument configuration menu.

PASSAllows a new password to be set for entry to the configuration menus. If set to '000', no password is required for sub-sequent entry to configuration. See also 'Operator access' in section 3.2 above, and ACES below.

CRELCommon Relay enable. When set to 'On', Channel 1 Alarm 1 relay operates if any channel's alarm becomes active.When set to 'Off', the relay operates only when channel 1 alarm 1 becomes active.

DESCAllows a 20-character text string (descriptor) to be entered using the cursor and up and down arrows to enter eachcharacter in turn. When the cursor is operated from the 20th character position, it returns to the 1st character position.To indicate that this has happened, character 1 of the decriptor is always preceded by a special character ( ). Forexample, were the descriptor ' DOWNLINE TEMPERATURE' to be entered, (where the highlighted text indicates thefour characters on display) and the cursor operated from the final E, the display would change to : " DO NLINE

TEMPERATURE'.

As indicated above, characters which cannot be displayed (K, M, W, X) are represented by another special character( ). (These non-displayable characters do print correctly on the chart). See section 3.1 above for the full characterset available.

Inst

Pass

Crel

dESC

HySt

010 Enter new password

Off On

AbC Enter descripor

01.00

nnes yES no

ACES L 0 L 1

CASS Fan roll

Enter new value for alarmhysteresis (applies to all alarms)

(Common relay enable)

(Alarm message enable)

L 2 (Set access level)

(Set cassette type if changed)

Page 25: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 21HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

3.2.11 INSTRUMENT CONFIGURATION (Cont.)

HyStAllows a hysteresis value (as a percentage of channel scale) to be entered for all the alarms' thresholds, as a percent-age of Channel scale. See the Glossary of terms for a description of hysteresis.

n.nESAllows the printing of alarm messages to be enabled/disabled. When enabled, the messages:

HH:MM:SS ALARM ON C:A, and HH:MM:SS ALARM OFF C:Awill be printed on the chart, in black, at the appropriate time.HH:MM:SS is the time of occurenceC is the relevant channel numberA is the relevant alarm number

Note: If the 'Event input' option is fitted, the printing of alarm messages is inhibited.

ACESAllows operator access to be set to level 0, 1 or 2 as required. See 'Operator Access' in section 3.2 for further details.

CASSThe recorder is set up at the factory to suit the type of cassette fitted. Should the cassette type be changed (from roll toz-fold (fan fold) or vice versa), then this 'CASS' field needs to be accessed, and the new cassette type selected usingthe up/down arrow keys. If this is not done, the chart drive will become extremely noisy, or the chart time accuracywill be lost, according to type.

Page 26: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 22

100 MM RECORDER USER GUIDE

NC C NO NC C NO NC C NO

Ch4relay 1

Ch4relay 2

Ch5relay 1

NC C NO NC C NO NC C NO

Ch5relay 2

Ch6relay 1

Ch6relay 2

45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66

Input board

NC C NO NC C NO NC C NO

Chan. 1relay 1

Chan. 1relay 2

Chan. 2relay 1

NC C NO NC C NO NC C NO

Chan. 2relay 2

Chan. 3relay 1

Chan. 3relay 2

23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

Option board No 1

Option board No 3 Option board No 4

Option board No 2

10

20

304050

100

200

300

0.1 0.2 0.5 5 20

Max. DC load breaking capacity

1 2

inductive load(L/R = 20msec)

resistive load

DC

Vol

tage

(V

olts

)

DC current (Amps)

Figure 4.1a Figure 4.1b

F1

F2

1 0.8 0.6 0.4 0.20.3

0.4

0.5

0.6

0.7

0.80.9

1F

Red

uctio

n F

acto

r F

Power factor (cos φ)

4 OPTIONS

Up to four 1/2-width option boards can be fitted, as specified at time of order (i.e. options are not retro-fittable).

4.1 RELAY OUTPUTS

The relay output option comes in three versions, each of which uses a 1/2 - width circuit board. The relay specifica-tion for resistive loads is as given below. For inductive ac loads, contact life = resistive life x reduction factor in figure4.1a, in which F1 = measured on representative samples; F2 = typical values (according to experience)

Maximum ac switching power 500 VA

Maximum ac contact voltage 250V within the VA rating above

Maximum ac breaking current 2 A, within the VA rating above.

Maximum dc power/voltage/current See figure 4.1b.

Isolation (dc to 65Hz; BS EN61010) Installation category II; Pollution

degree 2 (See specification section

for definitions)

Contact to contact 300V RMS or dc (double insulation)

Contact to ground 300V RMS or dc (basic insulation)

Estimated life 30,000,000 operations

Each recorder channel has two alarm thresholds (alarm 1 and alarm 2),which can both be either absolute high or abso-lute low as defined at time of order. If the channel's value lies above a high threshold, the relevant relay for thatchannel alarm is active. If the channel's value lies below a low threshold, the relevant relay for that channel alarm isactivated.

Notes:1. The default hysteresis value of 1% can be edited as a part of the instrument configuration (HySt). This value is a

percentage of channel scale, and applies to all thresholds.2. The relays are de-energised in alarm and power off conditions, to provide fail-safe operation.

4.1.1 Three change-over relays board

This 1/2 board provides three change-over relays (i.e. with common, normally open and normally closed contacts).In alarm, the common and normally closed contacts are closed. Wiring details for up to 12 relays is shown in figure4.1.1.

Figure 4.1.1 Changeover relay wiring (alarm / power off state)

Page 27: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 23HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66

Input board

C NO C NO C NO C NO

Ch. 1relay 1

Ch. 1relay 2

Ch. 2relay 1

Ch. 2relay 2

Option board No 3

23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

C NO C NO C NO C NO

Ch. 3relay 1

Ch. 3relay 2

Ch. 4relay 1

Ch. 4relay 2

C NO C NO C NO C NO

Ch. 5relay 1

Ch. 5relay 2

Ch. 6relay 1

Ch. 6relay 2

Option board No 1 Option board No 2

Option board No 4

45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66

Input board

C NC C NC C NC C NC

Ch. 1relay 1

Ch. 1relay 2

Ch. 2relay 1

Ch. 2relay 2

Option board No 3 Option board No 4

23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

Option board No 1 Option board No 2

C NC C NC C NC C NC

Ch. 3relay 1

Ch. 3relay 2

Ch. 4relay 1

Ch. 4relay 2

C NC C NC C NC C NC

Ch. 5relay 1

Ch. 5relay 2

Ch. 6relay 1

Ch. 6relay 2

4.1.2 Four normally-open relays board

This 1/2 board supplies four relays with common and normally open contacts. In alarm or power off conditions, thecommon and normally open contacts are open. Figure 4.1.2 below, shows wiring details for 12 relays located at op-tion board positions 1, 2 and 3.

Figure 4.1.2 Normally-open relay wiring (alarm / powr off state)

4.1.3 Four normally-closed relays board

This 1/2 board supplies four relays with common and normally closed contacts. In alarm or power off conditions, thecommon and normally closed contacts are closed. Figure 4.1.3 below, shows wiring details for 12 relays located atoption board positions 1, 2 and 3.

Figure 4.1.3 Normally-closed relay wiring (alarm / power off state)

Page 28: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 24

100 MM RECORDER USER GUIDE

4.2 TRANSMITTER POWER SUPPLY OPTION

4.2.1 Introduction

This option supplies one or two sets of three iso-lated 25 Volt outputs wired to terminal blocks foruser connection. Each output is intended to sup-ply power to a remote transmitter in order to run a0 to 20 mA or a 4 to 20 mA current loop.

Figure 4.2.1 shows an overall view of a transmitterpower supply option fitted in the rear terminalcover.

FUSES

The fuse is a 63mA (220/240V) or 100mA (110/120V), 20mm anti-surge type T located on thecircuit board as shown in figure 4.2.1 above.Spare fuses are available from the manufacturer.

SAFETY ISOLATION

Isolation (dc to 65Hz; BS EN61010) InstaIlation category II; Pollution degree 2 (see section 6 for definitions)

Channel to channel = 100V RMS or dc (double insulation); Channel to ground = 300V RMS or dc (basic insulation)

4.2.2 Signal wiring

Each set of outputs is terminated at a terminal blockas shown in figure 4.2.2

In order to read input values successfully a resistormust be connected across V+ and V- of the inputchannel. This resistor should have a minimumspecification of 1.4 Watt, ±1% and should be either100Ω or 250Ω in value as required. Resistors of thiskind are available from the manufacturer.

User outputs

`

Transmitter powersupply fuse

Transmitter powersupply fuse

Plastic coverretaining screw

+ + +- - - + + +- - -

Output 1 Output 2 Output 3Output 1 Output 2 Output 3

User outputs

Bla

ck

Bla

ck

Bla

ck

Red

Red

Red

– +

Transmitter

+- Other transmitters

V+ V-Channel input

– + – +

Only one channelshown, for clarity.

Long terminal cover

Recorder rearterminal panel

User terminal block

I

R

Transmitter Power SupplyPCB

Figure 4.2.1 Transmitter power supply

Figure 4.2.2 Transmitter power supply signal wiring

Page 29: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 25HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

4.3 EVENT INPUT OPTION

This option offers four inputs to control chart on/off and annotation of events. Each event is initiated by a contactclosure (or opening) applied between the 'C' terminal and input terminals one to four.

Note: Alarm message printing is inhibited if the Event Input Option is fitted.

4.3.1 Contact input 1

With the contact closed, the chart runs normally, at its selected chart speed.

When the contact is opened, pens are parked at zero (continuous-trace recorders) or tracing is stopped (multipointrecorders), the chart winds forward eighty mm. and stops.

Contact input 1 may not be closed if contact input 2 (below) is closed.

4.3.2 Contact input 2

This function applies only to annotating recorders.

At closure, the current time and date is printed on the chart. For as long as the contact is closed, the chart runs at itsselected speed, but annotation of scales, time, date and chart speed is inhibited.

At contact opening, pens are zeroed (contiuous-trace recorders) or tracing is inhibited (multipoint recorders), time,date, scales and chart speed are printed on the chart, the chart is wound forwards 80 mm. and is then stopped.

Contact input 2 may not be closed if contact input 1 is closed.

4.3.3 Contact input 3

This function applies only to annotating recorders, and is effective only if contact 1 or 2 is closed.

On closure, the message "EVENT START HH:MM:SS" is printed at the left-hand side of the chart, whereHH:MM:SS shows the time of closure in hours, minutes and seconds.

On contact opening, the message "DURATION HH:MM:SS" is printed at the left edge of the chart, whereHH:MM:SS shows how long the contact has been closed to the nearest second. Should the duration of closure reach100 hours, the duration re-sets to zero.

4.3.4 Contact input 4

If contact 1 or 2 is closed, then channel four (continuous trace) or channel six (multipoint recorders) is used to showthe status of contact closure 4. Whilst contact 4 is open, the trace is at 100% of chart span; whilst closed, the tracemoves to 96% of span.

If neither contact 1 or 2 is closed, pen four (continuous-trace recorders) moves to chart zero or tracing by channel 6(multi-point recorders) is stopped.

Page 30: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 26

100 MM RECORDER USER GUIDE

45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66

Input board

23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

C1 3 42

Option board No. 1

C1 3 42

C1 3 42 C1 3 42

Option board No. 2

Option board No. 3 Option board No. 4

Event input number

C1 2 3 4

4.3.5 Event input wiring

Figure 4.3.5a Event input terminations

Figure 4.3.5b Event input wiring

4.3.6 Safety isolation

Isolation (dc to 65Hz; BS EN61010) Installation category II; Pollution degree 2 (see Specification section for definitions)

Event input to ground = 100V RMS or dc (double insulation); Event input to Event input = 0V

Page 31: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 27HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

4.4 CHANNEL TAGS OPTION

This option allows the user to enter a text string (tag) describing the input channel. The string can be of up to fourcharacters in length, using the character set described in section 3.2.1. If the option is fitted, the following sub-sec-tions replace the referenced topics in section 3 in the manual.

4.4.1 Units display(Replaces section 3.1.3)

If 'Units' have been selected 'yes' in the top level configuration menu, then the PV and tag text strings alternate, withthe PV being displayed for three and a half seconds, then the tag for a second and a half.

Unit string characters k, w and x cannot be displayed by a seven-segment display and are replaced by the special sym-bol ' '. Similarly, the letter 'm' is displayed as 'n.n'. Because 'n.n' takes two character spaces, if an 'm' is used in a unitstring, the right-most character of four-character strings is lost. The above applies only to the display - the charactersare printed correctly on the chart.

4.4.2 Cyclic messages(Replaces 'Cyclic messages' in section 3.1.6)

Cyclic messages are printed on the chart approximately every 2 cm. on a convenient time boundary. The messagesare right-justified on the chart and are printed in the following order:

Time; Date; Chart speed; Channel 1 identifier (Ch1), tag and scale; Time; Date; Chart speed; Channel 2 identifier(Ch2), tag and scale; ...and so on. Channel information is printed on two lines, with Channel number and scale 'zero'value at the left of the chart and units (or tag) and span value at the right of the chart, as illustrated in figure 4.4.2

Figure 4.4.2 Cyclic message printing example (with 'Channel Tags' option)

14:40_

400.0 800.0Ch1 Tag1

06/07/06

300MM/H

Page 32: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 28

100 MM RECORDER USER GUIDE

4.4.3 Range(Replaces section 3.2.9)

This section allows the configuration of the input channels to be entered. Figure 4.4.3 shows the top level range con-figuration menu for three cases:1. Input type = thermocouple or RTD; Linearisation = TC or RTD type.2. Input type = V, mV, mA or ohms; Linearisation type = linear or square root and3. Input type = V, mV, mA or ohms; Linearisation function = Thermocouple or RTD type.This last combination is used with transducer transmitters which do not incorporate their own linearisation tables.

Notes:1. Channel one must not be used whilst configured as 'Ohm' or 'RTD' unless the CJ sensor has been disconnected

(figure 2.2), or gross measurement errors will occur. When the CJ sensor disconnected, no other input channelshould be configured as T/C unless it uses an external CJC.

2. The background (PV) display will show 'brng' (bad range) if any one or more of the following obtain:a. Input range low ≥ Input range highb. Linearisation range low ≥ Linearisation range highc. Scale low = Scale highd. Hardware capabilities are exceedede. Linearisation type is inappropriate to the rest of the configuration

Figure 4.4.3 Channel range configuration menu ( 'Channel Tags' option items arrowed)

rng

Lo

1

Hi

Lin

Unit

CJC

ECJ

resp

decp

rng

type

set channelnumber

1

1

1

1

1

1

1

1

1

Select linearisationfunction

Select ˚C or ˚F

Select CJC type(Only for Type = TC)

If CJC type = external,enter temp

Set break responsehigh, low or none

Set display decimalpoint position

Type = TC or RTDLin = TC or RTD type

rng

Lo

1

Hi

Lin

SCLo

SCHi

tAg

Shun1Enter shunt value(only for Type = mA )

decp

rng

type

set channelnumber

1

1

1

1

1

1

1

1

Type = Volts / mV / mA / ohmLin = Linear or square root

Select linearisationfunction

Enter scale low andhigh values

Enter text string(4-character max.)

Enter input rangelow and high values

Set display decimalpoint position

rng

Lo

1

Hi

Lin

Lo

Hi

Unit

Shun

decp

rng

type

set channelnumber

1

1

1

1

1

1

1

1

1

Type = Volts / mV / mA / ohmLin = T/C or RTD

resp1Set break response

high, low or none

Select linearisationfunction

Enter linearisationrange low and high

values

Select ˚C or ˚F

Enter shunt value(only for Type = mA )

Set display decimalpoint position

respSet break responsehigh, low or none

1

Enter input rangelow and high values

Enter input rangelow and high values

tAg1Enter text string

(4-character max.)

tAg1Enter text string

(4-character max.)

Page 33: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 29HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

REACTIVITY DATA

SPILL OR LEAK PROCEDURES

Eyes and skin

Ingestion

FIRST AID PROCEDURES

Inhalation

STABILITY

Stable Unstable

Conditions to avoid

Hazardousdecomposition

products

Flush affected areas with water. If irritation develops, consult a physician

If swallowed, dilute with water. Induce vomiting. Obtain immediate medical attention

If inhaled, move to fresh air. If necessary, aid breathing and obtain medical attention

Yes Temperatures above 70˚C

None

Will not occur

Wipe up spills with towels and cloths. Remove stains with soap solution.

Dispose of waste in accordance with local environment control regulations

Hazardouspolymerisation

Chemical nature Solution of dyestuffs in water and organic solvents

SPECIAL PROTECTION INFORMATION

Respiratory

Ventilation

Protective clothing

Other

If vapours are generated, use organic vapour respirator

All colours contain dyes which are suspected carcinogens

HAZARDOUS INGREDIENTS

Product:

Part numbers:

PHYSICAL DATA

FIRE AND EXPLOSION DATA

HEALTH HAZARD DATA

Name % Range TLV Toxicological data

Boiling point

Vapour pressure

Odour

Specific gravity

Solubility inwater

Colours

Extinguishing media

Special fire-fighting procedures

Unusual fire and explosionhazards

Threshold limit value

LD 50 Oral

Skin and eye irritation

Over-exposure effects

LD 50 Dermal

FLAMMABLE LIMIT

LEL UEL

RECORDING PENS

LZ127886LZ127887LZ127888LZ127889LZ127890

LA125451LA125452LA125453LA128961LA128962LA128963

LA128964LA128965LA128966LA128969LA203211LA203212LA203213LA203214

LA230393LA233023LA233461LA233462LA233463LA233701LA233702LA233703

LA234423LA234424LA234425LA235347LA235348LA235349LA235350

LA243770LA243771LA243772LA243773

LA246521LA246522LA246523LA247158

Formamide 25 to 30 Notavailable

1.5 to 3 Notavailable

Not established

Not established

100 ˚ C 1.06 to 1.1

Due to H2O only. 0.62% approx Complete

Nearly odourless Various

Not flammable

Use medium appropriate to primarycause of fire. Not applicableNot applicable

Not established

Not established

Unknown

Not established

LA249550LA249551LA249552LA249553LA249554

None

None

None in normal use

Normal ventilation is adequate

Use gloves when handling pens to avoid stains on skin/clothing

Flash point (deg C) (Method used)

Acid dyes

5 COSHH DATA

5.1 RECORDING PENS

The COSHH data presented here is derived di-rectly from data sheets produced by the manufac-turer to cover all its products. This is reflected inthe fact that the list of part numbers includesmore than those items relevant to this product,

Page 34: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 30

100 MM RECORDER USER GUIDE

5 COSHH DATA (Cont.)

5.2 PRINTHEAD INKS

REACTIVITY DATA

SPILL OR LEAK PROCEDURES

SPECIAL PROTECTION INFORMATION

Eyes and skin

Ingestion

Respiratory

Ventilation

Protective clothing

Other

FIRST AID PROCEDURES

Inhalation

STABILITY

Stable Unstable

Conditions to avoid

Hazardousdecomposition

products

Hazardouspolymerisation

Flush affected areas with water. If irritation develops, consult a physician.

Yes Strong oxidising agents and temperaturesabove 90˚C

None

Will not occur

Wipe up spills with towels and cloths. Remove stains with soap solution.

Dispose of waste in accordance with local environment control regulations

Normal ventilation is adequate

Use gloves when handling printheads to avoid stains on skin/clothing

When printheads are being used for recording purposes, there areno known deletarious effects arising from the inks or pen tips.

HAZARDOUS INGREDIENTS

Product:

Part numbers:

PHYSICAL DATA

FIRE AND EXPLOSION DATA

HEALTH HAZARD DATA

Name % Range TLV Toxicological data

Boiling point

Vapour pressure

Odour

Specific gravity

Solubility inwater

Colours

Flash point (deg C) (Method used)

Extinguishing media

Special fire-fighting procedures

Unusual fire and explosionhazards

Threshold limit value

LD 50 Oral

Skin and eye irritation

Over-exposure effects

LD 50 Dermal

FLAMMABLE LIMIT

LEL UEL

WATER BASED INKS NOT CONTAINING FORMAMIDE

LA248163LA249556

Acid dye 1 to 4 Not available Not established

>212 ˚ C 1.05 to 1.1

<20 mm Hg Complete

None Various

Not flammable

Use medium appropriate to primarycause of fire.

None

None

Not availableNot available

Not established

> 5g/kg

None in normal use

Slight irritation of mucus membrane

Not established

If inhaled, move to fresh air. If necessary, aid breathing and obtain medical attention

If vapours are generated, use organic vapour respirator

If swallowed, dilute with water. Induce vomiting. Obtain immediate medical attention

Page 35: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 31HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

DISPOSAL

HAZARDOUS INGREDIENTS

Product:

Part numbers:

PHYSICAL DATA

FIRE AND EXPLOSION DATA

HEALTH HAZARD DATA

Name % Range TLV Toxicological data

Boiling point

Vapour pressure

Odour

Specific gravity

Solubility in water

Colours

Flash point (deg C) (Method used)

Extinguishing media

Special fire-fighting procedures

Unusual fire and explosionhazards

Threshold limit value

LD 50 Oral

Skin and eye irritation

Over-exposure effects

LD 50 Dermal

FLAMMABLE LIMIT

LEL UEL

NICKEL-CADMIUM BATTERY PACKS

PA244816PA250002PA250188

Positive electrode (nickel hydroxide,cobalt hydroxide, nickel sinter)

Electrolyte (potassiun hydroxide)

Notavailable

5 to 15 Notavailable

Highly toxic if ingested

Highly toxic, Highly corrosive.

Not applicable Not applicable

Use medium appropriate toprimary cause of fire

Not applicable

Batteries might explode due to excessive pressure build-up which might not be self-venting. Toxic fumes(cyanogen) might be generated.

Not applicableNot applicable

Should cells leak, the leak material will be a caustic solution. Avoid contact.

Negative electrode (cadmium metal,cadmium hydroxide, nickel sinter) 15 to 25

Notavailable

5 to 15

Highly toxic

Not applicable

Not applicable

Not applicable

Not applicable

Not applicable

Not applicable

Not applicable Not applicable

Not applicable

Chemical nature See above. There are no risks in normal use.

REACTIVITY DATA

SPILL OR LEAK PROCEDURES

SPECIAL PROTECTION INFORMATION

Eyes and skin

Ingestion

Respiratory

Ventilation

Protective clothing

Other

FIRST AID PROCEDURES

Inhalation

STABILITY

Stable Unstable

Conditions to avoid

Hazardousdecomposition

products

Hazardouspolymerisation

If leakage occurs, wash the affected area withplenty of water and cover with dry gauze.If eyes are affected, wash with plenty of water. Seek medical assistance.

If ingestion of leak material occurs, DO NOT induce vomiting. Give plenty of milk to drink. Obtainimmediate medical assistance, stating 'nickel-cadmium battery'.

Not applicable

YesMechanical damage, overcharging, short circuiting terminals,

storage temperatures outside the range 0 to 40˚ C

None

Will not occur

In normal use there is no risk of leakage. If batteries are abused, this may lead to the

leaking of a caustic alkaline solution which will corrode aluminium and copper. The leak

material should be neutralised using a weak acidic solution such as vinegar, or washed

away with copious amounts of water.

Not applicable

In addition to the electrolyte (potassium hydroxide), nickel-cadmium

batteries contain cadmium, cadmium hydroxide and nickel

hydroxide, all of which are highly toxic.

Contact should be avoided

Not applicable

Not applicable

Batteries must be disposed of in accordance with current local regulations. Batteries

should not be discarded with normal refuse.

5 COSHH DATA (Cont.)

5.3 NI-CAD BATTERIES

Page 36: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 32

100 MM RECORDER USER GUIDE

REACTIVITY DATA

SPILL OR LEAK PROCEDURES

SPECIAL PROTECTION INFORMATION

Eyes and skin

Ingestion

Respiratory

Ventilation

Protective clothing

Other

FIRST AID PROCEDURES

Inhalation

STABILITY

Stable Unstable

Conditions to avoid

Hazardousdecomposition

products

Hazardouspolymerisation

If leakage occurs, wash the affected area withplenty of water and cover with dry gauze.If eyes are affected, wash with plenty of water. Seek medical assistance.If ingestion of leak material occurs, DO NOT induce vomiting. Give plenty of milk to drink. Obtainimmediate medical assistance, stating 'nickel/metal-hydride battery'.

Not applicable

YesMechanical damage, overcharging, short circuiting terminals,

charging temperatures outside the range 0 to 65˚ C, direct soldering.

None

Will not occur

In normal use there is no risk of leakage. If batteries are abused, this may lead to the

leaking of a caustic alkaline solution which will corrode aluminium and copper. The leak

material should be neutralised using a weak acidic solution such as vinegar, or washed

away with copious amounts of water.

Not applicable

Contact should be avoided

Not applicable

Not applicable

DISPOSAL

Batteries must be disposed of according to current local regulations. Batteries should not

be discarded with normal refuse.

HAZARDOUS INGREDIENTS

Product:

Part numbers:

PHYSICAL DATA

FIRE AND EXPLOSION DATA

HEALTH HAZARD DATA

Name % Range TLV Toxicological data

Boiling point

Vapour pressure

Odour

Specific gravity

Solubility in water

Colours

Flash point (deg C) (Method used)

Extinguishing media

Special fire-fighting procedures

Unusual fire and explosionhazards

Threshold limit value

LD 50 Oral

Skin and eye irritation

Over-exposure effects

LD 50 Dermal

FLAMMABLE LIMIT

LEL UEL

NICKEL METAL-HYDRIDE (NiMH) batteries

PA250331 (mounted on circuit board assembly AH249812)PA261437 (mounted on circuit board assembly AH261438)

Potassium hydroxide 8 Highly toxic, Highly corrosive.

Not applicable Not applicable

Any

Not applicable

Batteries might explode due to excessive presure build-up which might not be self-venting. Toxic fumes mightbe generated.

Not applicableNot applicable

Should cells leak, the leak material will be a caustic solution. Avoid contact.

Nickel hydroxide 10 Not established Highly toxic if ingested

Not applicable

Not applicable

Not applicable

Not applicable

Not applicable

Not applicable

Not applicable Not applicable

Not applicable

Chemical nature See above. There are no risks in normal use.

Nickel metal 20 - 26 Not established

Misch metal alloy 10-11 Not established

Not established

5 COSHH DATA (Cont.)

5.4 NICKEL - METAL HYDRIDE BATTERIES

Page 37: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 33HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

6 TECHNICAL SPECIFICATION

INSTALLATION CATEGORY AND POLLUTION DEGREE

This product has been designed to conform to BS EN61010 installation category II and pollution degree 2. These aredefined as follows:

INSTALLATION CATEGORY IIThe rated impulse voltage for equipment on nominal 230V ac mains is 2500V.

POLLUTION DEGREE 2Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by con-densation shall be expected.

6.1 TECHNICAL SPECIFICATION (Recorder) I/O Board types

Universal input / control board (standard)

3- Change-over relay output board, 4 Normally open relay output board, 4 Normally closed relay output board

Option boardsTransmitter power supply

Event input board

Annotator board (Continuous pen recorders only)

Environmental PerformanceTemperature limits Operation: 0 to 50˚C. Storage: –20 to + 70˚C

Humidity limits Operation: 5% to 80% RH (non-condensing). Storage: 5% to 90% RH (non condensing)

Protection Door and Bezel: IP54. Sleeve: IP20. Transmitter Power Supply option rear cover: IP10

Shock BS EN61010

Vibration 2g peak at 10 Hz to 150Hz

Altitude (max.) <2000 metres

Electromagnetic compatibility (EMC)Emissions BS EN50081-2

Immunity BS EN50082-2

Electrical safetyBS EN61010. Installation category II ; Pollution degree 2

PhysicalPanel mounting DIN43700

Bezel size 144 x 144 mm.

Panel cutout dimensions 138 x 138 (both – 0 + 1 mm)

Depth behind bezel rear face 220 mm (no terminal cover); 236 mm (standard terminal cover); 275 mm (closed long terminal cover);

390 mm (open long terminal cover)

Weight < 3.5kg

Panel mounting angle Vertical ± 30˚

Page 38: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 34

100 MM RECORDER USER GUIDE

Off 5 10 20 30 60 120

240 300 600 1200 3600 18000 36000

Continuous only.Annotation (if fitted)inhibited above 300

mm/hr.

Multipoint andcontinuous recorders

All speeds in mm/hr

6.1 TECHNICAL SPECIFICATION (Recorder) (Cont.)

Printing system (continuous trace)Pen type Disposable fibre-tipped pens

Pen resolution 0.15 mm

Pen colours Channel Colour Channel Colour

1 (top) blue 4 (bottom) violet

2 red annotator black

3 green

Pen life 1.2 km (channel pens); 7.5 x 105 dots (annotator)

Update rate 4 Hz

Response time (10 to 90%) 2 sec max.

Annotator characters per line 38

Printing system (multipoint)

Pen type Six-nib cartridge

Print resolution 0.2 mm

Trace colours Channel Colour Channel Colour

1 violet 4 green

2 red 5 blue

3 black 6 brown

Printhead life 1.5 x 106 dots per colour

Update rate 2 Hz

Print rate (maximum) 1 pass every 5 seconds

Characters per line 42

Paper transportType Stepper motor driving sprocket tube

Chart speeds See table below

Chart type 16-metre z-fold (standard) or 32-metre roll (option)

Transport accuracy 0.5 cm in 16 metres (0.03% approx.)

Power requirementsLine voltage Standard: 90 to 264V 45 to 65 Hz

Enhanced interrupt protection: 90 to 132V 45 to 65 Hz

Low voltage option 20 to 53V dc or ac (45 to 400Hz RMS)

Power (Max) 100VA

Fuse type None

Interrupt protection Standard: 40ms at 75% max. instrument load

Enhanced: 120msec at 75% max. instrument load

Page 39: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 35HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

150mV

1 Volt

10 Volts

-30 mV

-0.2 Volt

-2 Volts

5.5µV

37µV

370µV

0.084% input + 0.053% range

0.084% input + 0.037% range

0.275% input + 0.040% range

80ppm of input per deg C

80ppm of input per deg C

272ppm of input per deg C

LowRange

HighRange

Resolution Maximum error(Instrument at 20˚C)

Worst case temperatureperformance

B

CDE

G2JKL

NRSTU

Ni/NiMoPlatinel

0 to + 1820

0 to + 23000 to + 2495

- 270 to + 10000 to + 2315

- 210 to + 1200- 270 to + 1372- 200 to + 900

- 270 to + 1300- 50 to + 1768- 50 to + 1768

- 270 to + 400- 200 to + 600

0 to + 14060 to + 1370

IEC 584.1

HoskinsHoskinsIEC 584.1HoskinsIEC 584.1IEC 584.1DIN43700:1985(To IPTS68)IEC 584.1IEC 584.1IEC 584.1IEC 584.1DIN 43710:1985IpsenEngelhard

T/CType

Overall range(˚C) Standard

0 to 400˚C: 1.7˚C400 to 1820˚C: 0.03˚C0.12˚C0.08˚C0.03˚C0.07˚C0.02˚C0.04˚C0.20˚C

0.04˚C0.04˚C0.04˚C0.02˚C0.08˚C0.14˚C0.02˚C

Max linearisation error

6.2 TECHNICAL SPECIFICATION (Input board)GeneralTermination Edge connector / terminal block

Maximum number of inputs Continuous trace recorder = 4. Multipoint recorder = 6.

Input ranges - 30 to + 150 mV; - 0.2 to + 1 Volt; - 2 to + 10 Volts;

Input types dc Volts, dc millivolts, dc milliamps (with shunt), thermocouple, 2 / 3-wire resistance temperature detector (RTD)

(Channel 1 can be RTD or Ohm only if no other channel is thermocouple - see section 3.2.9 Note 1))

Input type mix User configurable

Noise rejection (48 to 62 Hz) Common mode: >140dB (channel - channel and channel - to - ground). Series mode: >60dB.

Maximum common mode voltage 250 Volts continuous

Maximum series mode voltage 180 mV at lowest range; 12 Volts peak at highest range.

Isolation (dc to 65 Hz; BS EN61010) Installation category II; Pollution degree 2 (See section 5 above for definitions)

300V RMS or dc Channel to channel (double insulation), channel to common electronics (double insulation) and

channel to ground (basic insulation)

Dielectric strength (BS EN61010) Channel to ground =1350 Vac; Channel to channel = 2300 Vac (both 1 minute type tests)

Insulation resistance >10MΩ at 500 V dc

Input impedance 150 mV and 1 V ranges: >10 MΩ; 10 V range: 68.8 kΩ

Over voltage protection 50 Volts peak (150V with attenuator)

Open circuit detection ± 57 nA max.

Recognition time Continuous trace = 250 msec; Multipoint = 500 msec

Minimum break resistance 10 MΩ

DC Input rangesShunt/attenuator Externally mounted resistor modules

Additional error due to shunt 0.1% of input

Additional error due to attenuator 0.2% of input

Performance

Thermocouple dataTemperature scale ITS 90

Linearisation accuracy 0.05% of user entered span

Bias current 0.05 nA

Cold junction types Off, internal, external

CJ error 1˚C max; instrument at 25 ˚C

CJ rejection ratio 50:1 minimum

Upscale / downscale drive High, low or none

Types and ranges

Page 40: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 36

100 MM RECORDER USER GUIDE

600Ω6000Ω

0Ω0Ω

22mΩ148mΩ

0.045% input + 0.065% range

0.049% input + 0.035% range

35ppm of input per deg C

35ppm of input per deg C

LowRange

HighRange

Resolution Maximum error(Instrument at 20˚C)

Worst case temperatureperformance

JPT100Ni100Ni120Pt100

Pt100APt1000

-220 to + 630- 60 to + 250-50 to + 170

-200 to + 850-200 to + 600-200 to + 850

JIS C1604:1989DIN43760:1987DIN43760:1987IEC 751Eurotherm Recorders SAIEC 751

RTD Type Overall range (˚C) Standard Max linearisation error

0.01 ˚C0.01 ˚C0.01 ˚C0.01 ˚C0.09 ˚C0.01 ˚C

6.1 TECHNICAL SPECIFICATION (Recorder) (Cont.)

Resistance inputsRanges (including lead resistance) 0 to 600 Ω, 0 to 6k Ω

Linearisation accuracy 0.05% of user entered span.Influence of lead resistance Error = negligible; Mismatch = 1 Ω/ΩTemperature scale ITS90Ranges and tempreature performance

RTD ranges and standards

Page 41: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 37HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

Start

100

90Input signal value

End

Alarm off only when value falls below 90.

Alarm without hysteresis

Alarm with hysteresis

7 GLOSSARY OF TERMS

Alarm A function which is triggered when an input signal or a signal derived from it reaches a cer-tain value. Once triggered, the alarm can cause a relay output to change state.

Analogue input An input which changes in a smooth (non-stepped) way (e.g. thermocouples, resistance ther-mometers).

Attenuator A resistive device which reduces the signal voltage by a known ratio (usually 100:1)Break response The recorder can detect an open circuit at its input terminals and, the instrument’s response

to an open circuit can be defined as ‘None’, ‘Drive high’ or ‘Drive low’. If none’ is selectedthe trace is allowed to drift according to what the input wiring is picking up (acting as anaerial). Drive high (low) causes the trace to be drawn at the extreme right (left) side of thechart.

Chart cassette A mechanical paper transport system for containing and feeding the chart past the pens orprinthead at a known speed. The cassette includes reservoirs for unused (pay-out tray) andused (take-up tray) sections of chart.

Cold Junction Compensation Also known by the abbreviation CJC. The voltage generated by a thermocouple (TC) junc-tion depends on the temperature difference between the actual bonded junction (the hot junc-tion), and the other (non-bonded) end of the conductors (the cold junction (CJ)). Thus, forany reading from a TC to be accurate, the temperature of the CJ must be taken into account.This can be done in three ways: Internal, External or Remote.Internal. The recorder has integral temperature detectors measuring the temperature near theterminal blocks (the cold junction for directly connected TCs).External. For remote TCs, the cold junction can be held at a known temperature. This tem-perature is entered (in degrees) as a part of the CJC configuration.Remote. For remote TCs, an auxiliary temperature detector can be used to measure the coldjunction temperature. This detector is then connected to a separate input channel. This inputchannel number is entered as a part of the CJC configuration.

Configuration This is used as a verb to mean ‘the process of telling your recorder what you want it to do’,and as a noun to mean ‘the way in which the recorder has been set up (or configured)’.

Continuous trace This is used to describe recorders which have a single pen associated with each processvariable, and this pen traces the value continuously. See also multipoint recorder.

Digital (discrete) input An input which has only two states (on or off). Examples are switch inputs or voltage pulseinputs.

Event input A discrete (switch) or digital (voltage level) input.Hysteresis When an input signal is ‘hovering’ near a setpoint, then an annoying and potentially damag-

ing series of alarms can be generated, instead of just one alarm the cause of which can bedealt with if necessary. To avoid this, a ‘hysteresis’ value of 1% span is applied, whicheffectively puts a dead band round the set point. For example with a span of 0 to 1000 anabsolute high alarm with a set point of 100 will have a hysteresis value of 10. The alarm istriggered when the input signal value rises above 100, but will not re-trigger until after thealarm has been ‘cleared’ by the process value falling below 90. An attempt to depict thisexample is given in the figure below.

Input channel An input circuit which accepts voltage, current or digital input signals from the user.Input signal A voltage, current or digital input applied to the recorder input circuits. See also Analogue

input and Digital (discrete) input.

Page 42: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 38

100 MM RECORDER USER GUIDE

7. GLOSSARY OF TERMS (Cont.)

Linearisation table Most transducers produce an output which is not directly proportional to the input. Forexample, the voltage output from a thermocouple does not vary linearly with the tempera-ture it is exposed to. The recorder uses a ‘look-up’ table to find a temperature value for anymV input from a specified thermocouple type. Similar tables exist for other transducerssuch as resistance thermometers.

Measured value An umbrella term which means: the value of an input channel, derived channel, totaliser,counter, timer etc. measured in mathematical units as a proportion of the span. See alsoProcess variable.

Multipoint recorder This is used to describe recorders which have multiple pen printheads rather than individualpens to produce the trace on the chart. Each trace is made up of dots, produced by the print-head as it traverses across the chart at regular intervals. Advantages are that many moretraces can be laid down on the chart, the traces can be annotated for identification and mes-sages can be printed on the chart. Disadvantages are that fast transients may be missed atlow chart speeds.

Operator interface A term used to describe the controls (e.g. pushbuttons, keypads) that are used to operate andconfigure the unit.

Paper transport system This includes the chart cassette and the mechanical system, motors etc. needed to move thechart through the cassette. The paper transport system is often considered to be an integralpart of the writing system.

Pen A fibre-tipped disposable stylus with an integral ink reservoir. Used to draw (trace) thevalue of a single process variable on the chart in continuous trace recorders.

Pen tray With modular recorder designs, each pen has its own mechanical system (including motorand feedback device) associated with it to drive it backwards and forwards across the chart.Pen tray is the general term for such mechanical systems. With some recorders, the pendrive electronics are integral with the pen tray.

Printhead This is a device which, together with a disposable multi-colour cartridge, allows multi-pointrecorders to mark the chart.

Process variable An umbrella term which means: the value of an input channel, derived channel, totaliser,counter, timer etc. measured in engineering units (e.g. Degrees Celsius). See also Measuredvalue.

Relay output A set of contacts which changes state as a result of an alarm becoming active. Relays areenergised continuously except when ‘in alarm’, so that if power to the recorder fails they gointo their ‘alarm’ state.

Resistance thermometer Also known as a resistance temperature detector (RTD), a resistance thermometer is con-structed of a material whose resistance varies in a known way with the temperature it is ex-posed to. The resistance variation is non-linear, but for any given type, this non-linearity iswell known and invariable and is compensated for by linearisation tables in the recordermemory.

Setpoint Also known as ‘threshold’, this is the point at which an alarm becomes active or inactive.See also hysteresis.

Shunt The input circuit of each recorder channel measures voltage signals. If current signals areconnected to the recorder, a low value resistor must be placed across the inputs, to convertthe current signal to Volts, according to Ohms law (Volts = Amps x Ohms). Thus, a 0 to20 mA (0.02 Amps) signal applied across a 250 Ω resistor produces a voltage range of

0 to (0.02 x 250) Volts = 5 Volts.Such resistors are called ‘Shunt resistors’ or ‘Shunts’ for short, and are usually of very closetolerance.

Span Span has two common meanings: the right-most grid of the chart, or the value given by(maximum value - minimum value). The two meanings are identical where the minimumvalue is zero.

Page 43: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 39HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

Trace The line produced on the chart or display screen showing the value of the process variablebeing measured.

Thermocouple A junction of two dissimilar metals which produces a small voltage, the value of which de-pends on the temperature of the junction. The voltage varies in a non-linear way with tem-perature, but for any given type, this non-linearity is well known and invariable and iscompensated for by linearisation tables in the recorder memory.

Threshold See setpoint.Transducer A device which produces an electrical output proportional to temperature, flow rate, pres-

sure, speed, position etc. Common transducers are potentiometers, thermocouples, resistancethermometers (RTDs) and flow meters.

Transmitter Thermocouple wire (compensation wire) is expensive, and if the thermocouple is a longway from the measuring device, it is often cheaper to instal a ‘transmitter’ local to the ther-mocouple. This device converts the mV signal from the thermocouple to a mA signal whichcan then be wired to the recorder using normal copper wire. Transmitters can be self pow-ered, or they may need power generated for them. Most recorders can be fitted with Trans-mitter Power Supplies as an option.

Writing system A general term used to describe the mechanical means of moving pens/printheads across thechart width. The term often includes the paper transport system used to drive the chartthrough the cassette.

Zero Zero is generally taken to mean the value associated with the left-most grid line on the chart.Its actual value need not be zero, as long as it is less than the Span value.

Page 44: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 40

100 MM RECORDER USER GUIDE

This page is deliberately left blank

Page 45: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Page 41HA249928Issue 15 Jly 06

100 MM CHART RECORDER USER GUIDE

AAccess levels ...................................................... 21ACES ................................................................ 21ADJ ................................................................... 16Alarm

Configuration .................................................. 17Global ........................................................... 20Hysteresis value............................................... 21On/Off message printing ................................. 21On/Off messages ........................................... 11

Aligning the trace with the chart grid .................... 15Annotation ......................................................... 11

Alarm messages enable/disable ....................... 21Alarm On/Off messages .................................. 11Cyclic messages .............................................. 11On/Off line messages ..................................... 12Power-up message ........................................... 11

Annotator batteries ............................................... 4

BBreak response ................................................... 19brng (bad range) .......................................... 18, 28

CCASS ................................................................ 21Cassette change configuration.............................. 21Channel

Adjust ............................................................ 16Configuration ............................................ 18, 28Hold .............................................................. 10Tags (option) ................................................... 27

Character set ..................................................... 15Chart

Replacement ............................................. 8 to 10Speed

Printing on chart ........................................... 11Selection ..................................................... 15

Type change ................................................... 21CJC .................................................................. 19cLOc ................................................................. 16Cold junction

External temperature entry ................................ 19Sensor removal .................................... 6, 18, 28Type selection ................................................. 19

Common relay.................................................... 20Configuration

Entry to .......................................................... 12Overview ....................................................... 14

COSHH dataNiCad batteries .............................................. 31NiMH batteries ............................................... 32Print head inks ................................................ 30Recording pens ............................................... 29

CrEL .................................................................. 20Cyclic messages ................................................. 11

DDate

Printing on the chart ......................................... 11Setting ........................................................... 16

Decimal point position ......................................... 19dECP................................................................. 19Default display ................................................... 10Descriptor entry .................................................. 20dFlt ................................................................... 10Dimensions .......................................................... 5Display interpretation .......................................... 10Display of channel value...................................... 10

EE display ........................................................... 12EJC ................................................................... 19Enter indicator .................................................... 12Event input description ................................ 25 to 26External cold junction temperature entry ................ 19

FFAn ................................................................... 15

GGlobal alarm ..................................................... 20

HHi input range .................................................... 19HySt .................................................................. 21

IInput

Range setting .................................................. 19Type selection ................................................. 19

InstallationElectrical .......................................................... 4Mechanical ...................................................... 4

Installation category ............................................ 33Instrument Configuration ...................................... 20

C (Cont.)

INDEX

Page 46: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

HA249928Issue 15 Jly 06Page 42

100 MM RECORDER USER GUIDE

LLIN ................................................................... 19Linearisation function selection ............................. 19Lo

Input range ..................................................... 19Linearisation range entry .................................. 19

MmA/mV Input type selection ................................. 19Mains wiring ........................................................ 6mES .................................................................. 21Message printing ................................................ 11

NNumber of decimal places ................................... 19Numeric entry techniques .................................... 13

OOhm as channel 1 input type ......................... 18, 28On/Offline messages .......................................... 12Operator access level

Overview ....................................................... 12Setting of ........................................................ 21

PPArc .................................................................. 15Password

Editing ........................................................... 20Factory entered ............................................... 12

Pen Park ........................................................ 7, 15Pen/Print cartridge replacement ............................. 7Pollution degree.................................................. 33Power-up message .............................................. 11PV display ......................................................... 10

RRecorder

Dimensions ....................................................... 5Specification ................................................... 33

RelayCommon ........................................................ 20Option description ................................... 22 to 23

rEm ................................................................... 11rESP .................................................................. 19rng ............................................................. 18, 28RTD

As channel 1 input type.............................. 18, 28Selection as input type ..................................... 19

SSafety notes ......................................................... 1Scale high/low entry .......................................... 19Scale printing ..................................................... 11SCHi ................................................................. 19SCLo ................................................................. 19Setting

Alarm hysteresis .............................................. 21Alarm messages on/off .................................... 11Alarm setpoints (thresholds) .............................. 17Alarm type ..................................................... 17Cassette type .................................................. 21Channel hold on/off ........................................ 10Channel parameters ........................................ 19Chart speed .................................................... 15Common relay on or off ................................... 20New password ............................................... 20Operator access level ...................................... 12Pen span ........................................................ 15Pen zero ......................................................... 15Time and Date ................................................ 16Units display on/off ......................................... 20

SHUn ................................................................ 19Shunt value entry ................................................ 19Signal wiring ....................................................... 6SPd ................................................................... 15

TThermocouple, Selection as input type ................... 19Time printing ...................................................... 11Time/date setting ................................................ 16Transmitter power supply ..................................... 24tyPE .................................................................. 19

UUnits

Display enable ................................................ 20Display of ....................................................... 10Thermocouple/RTD .......................................... 19

VVolts as input type selection .................................. 19

WWiring (supply and signal) ..................................... 6

ZZEro Pen............................................................ 15

Page 47: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform

Inter-Company sales and service locations

Specification subject to change without notice. ©Eurotherm Limited.

AUSTRALIA SydneyEurotherm Pty. Ltd.Telephone (+61 2) 9838 0099Fax (+61 2) 9838 9288E-mail [email protected]

AUSTRIA ViennaEurotherm GmbHTelephone (+43 1) 7987601Fax (+43 1) 7987605E-mail [email protected]

BELGIUM & LUXEMBURG MohaEurotherm S.A/N.V.Telephone (+32) 85 274080Fax (+32 ) 85 274081E-mail [email protected]

BRAZIL Campinas-SPEurotherm Ltda.Telephone (+5519) 3707 5333Fax (+5519) 3707 5345E-mail [email protected]

DENMARK CopenhagenEurotherm Danmark ASTelephone (+45 70) 234670Fax (+45 70) 234660E-mail [email protected]

FINLAND AboEurotherm FinlandTelephone (+358) 22506030Fax (+358) 22503201

FRANCE LyonEurotherm Automation SATelephone (+33 478) 664500Fax (+33 478) 352490E-mail [email protected]

GERMANY LimburgEurotherm Deutschland GmbHTelephone (+49 6431) 2980Fax (+49 6431) 298119E-mail [email protected]

EUROTHERM LIMITEDFaraday Close, Durrington, Worthing, West Sussex, BN13 3PLTelephone: +44 (0)1903 268500 Facsimile: +44 (0)1903 265982

e-mail: [email protected]: http://www.eurotherm.co.uk

HA249928/15 (CN22496)

EUROTHERM

HONG KONG & CHINAEurotherm Limited North PointTelephone (+85 2) 28733826Fax (+85 2) 28700148E-mail [email protected]

Guangzhou OfficeTelephone (+86 20) 8755 5099Fax (+86 20) 8755 5831

Beijing OfficeTelephone (+86 10) 6567 8506Fax (+86 10) 6567 8509

Shanghai OfficeTelephone (+86 21) 6145 1188Fax (+86 21) 6145 1187

INDIA ChennaiEurotherm India LimitedTelephone (+9144) 2496 1129Fax (+9144) 2496 1831E-mail [email protected]

IRELAND DublinEurotherm Ireland LimitedTelephone (+353 1) 4691800Fax (+353 1) 4691300E-mail [email protected]

ITALY ComoEurotherm S.r.lTelephone +39 (0)31 975111Fax +39 (0)31 977512E-mail [email protected]

KOREA SeoulEurotherm Korea LimitedTelephone (+82 31) 2738507Fax (+82 31) 2738508E-mail [email protected]

NETHERLANDS Alphen a/d RijnEurotherm B.V.Telephone (+31 172) 411752Fax (+31 172) 417260E-mail [email protected]

NORWAY OsloEurotherm A/STelephone Oslo (+47 67) 592170Fax (+47 67) 118301E-mail [email protected]

SPAIN MadridEurotherm España SATelephone (+34 91) 6616001Fax (+34 91) 6619093E-mail [email protected]

SWEDEN MalmoEurotherm ABTelephone (+46 40) 384500Fax (+46 40) 384545E-mail [email protected]

SWITZERLAND FreienbachEurotherm Produkte (Schweiz) AGTelephone (+41 55) 4154400Fax (+41 55) 4154415E-mail [email protected]

UNITED KINGDOM WorthingEurotherm LimitedTelephone (+44 1903) 268500Fax (+44 1903) 265982E-mail [email protected] www.eurotherm.co.uk

U.S.A Leesburg VAEurotherm Inc.Telephone (+1 703) 443 0000Fax (+1 703) 669 1300E-mail [email protected] www.eurotherm.com

ED48

Page 48: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform
Page 49: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform
Page 50: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform
Page 51: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform
Page 52: User Guide - con · PDF fileCARTRIDGE (Model 4102M) LA249556 Where xxx = 040, 045, 050, 060, 070 or 075 ... Eurotherm Recorders Limited hereby declares that the above products conform