user instructions - flowserve · user instructions installation operation maintenance ... this...
TRANSCRIPT
Experience In Motion
USER INSTRUCTIONS
InstallationOperation
Maintenance
Limitorque Actuation Systems Modutronic 20 IIFCD LMENIM4002-00 – 08/06 (Replaces 401-12000)
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
2
Contents1 Introduction 5
1.1 SafetyInformation 51.2 ProductIdentification 61.3 ProductDescription 61.4 ProductFeatures 61.5 ProductSpecifications 7
2 Operation 83 Definitions 104 InitialCheckoutandSetup 11
4.1 VerifyCorrectMotorRotation(Phasing)andOPEN/CLOSEPushbuttonOperation 114.2 VerifyLimitSwitchandTorqueSwitchSettings 134.3 AdjustingtheActuatorFeedbackPotentiometer 134.4 ConnectingtheMod20IItoCustomerCommandSignalLeads 14
5 Mod20IIPresets 166 CalibrationProcedure 187 Troubleshooting 238 WiringDiagram 259 Schematic 28
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
FiguresFigure1.1–Modutronic20II 6Figure2.1–LYwithaModutronic20IIandAssociatedActuatorComponents 9Figure3.1–CalibrationPositions 10Figure4.1–StandardMotorRotationandReverseMotorRotationWiringDiagrams
forDual-Voltage,Capacitor-Start,Induction-Run,andSingle-PhaseLow-VoltageMotors 12Figure4.2–StandardMotorRotationandReverseMotorRotationWiringDiagrams
forDual-Voltage,Capacitor-Start,Induction-Run,andSingle-PhaseHigh-VoltageMotors 13Figure4.3–PotentiometerCalibrationComponentsShownonaLYPositionIndicator 14Figure6.1–CalibrationAdjustmentsfortheModutronic20II 18Figure6.2–mACalibratorTypicallyConnects(suggestAltekModel334,www.altekcalibrators.com)
toanInterconnectBoardTerminalStriporTerminalStripsLocatedintheRearofaPanel-MountedMod20II 19
Figure6.3–Modutronic20IIBoardComponentLocations 19Figure6.4–FAILTOModeJP1Jumper 22Figure8.1–Modutronic20IITypicalThree-PhaseWiringDiagram 26-27Figure9.1–Modutronic20IISchematicDiagram 29-30
TablesTable1.1–Modutronic20IISpecifications 7Table4.1–Modutronic20IITerminalConnections 15Table5.1–ON/OFFPotentiometerTurnsforDesiredOperatingTime 16Table6.1–DIPSwitchSettingLevelsofDeadbandAccuracy 20
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
4
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
1Introduction
1.1 SafetyInformationThisInstallationandMaintenanceManualwaswrittenfortheuserwhoisaddingModutronic20IIcapabilitytoanexistingactuatororwhowantstoadjustand/ortroubleshootapreviouslyinstalledModutronic20IIController.Theseguidelinesprovidetheinformationthatisnecessarytocorrectlyinstall,setup,calibrate,andtroubleshoottheModutronic20IIController.
YoursafetyandsatisfactionareveryimportanttoFlowserve.Pleasefollowallinstructionscarefullyandpayspecialattentiontosafety.
Thefollowingmethodswillbeusedtoemphasizetextthroughoutthismanual:
WARNING:Referstopersonalsafety.Thisalertsthereadertopotentialdangerorharm.Failuretofollowtheadviceinwarningnoticescouldresultinpersonalinjuryordeath.
CAUTION:Directsattentiontogeneralprecautions,which,ifnotfollowed,couldresultinpersonalinjuryand/orequipmentdamage.
NOTE:Highlightsinformationcriticaltotheunderstandingoruseoftheseproducts.
Boldtexthighlightsotherimportantinformationthatiscriticaltosystemcomponents.
CAPITALIZEDtextstressesattentiontothedetailsoftheprocedure.
Underlinedtextemphasizescrucialwordsinsentencesthatcouldbemisunderstoodifthewordisnotrecognized.
Thepurposeoftheseemphasizedblocksoftextistoalertthereadertopossiblehazardsassociatedwiththeequipmentandtheprecautionsthatcanbetakentoreducetheriskofpersonalinjuryanddamagetotheequipment.
Readandbecomefamiliarwiththematerialintheseguidelinesbeforeattemptinginstallation,opera-tion,ormaintenanceoftheequipment.Failuretoobserveprecautionscouldresultinseriousbodilyinjury,damagetotheequipment,oroperationaldifficulty.
WARNING:ReadthisInstallationandMaintenanceManualcarefullyandcompletelybeforeattemptingtoinstalloroperatetheModutronic20II.BeawareofelectricalhazardswheninstallingorperformingmaintenanceontheModutronic.
c
a
c
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
6
1.2 ProductIdentificationFigure 1.1 – Modutronic 20 II
1.3 ProductDescriptionTheModutronic20IITMisasolid-stateintegratedcircuit-basedcontroller.Itisusedtooperateelec-tricvalveactuatorsinwastewater,petrochemical,andotherindustryapplicationsrequiringaccuratemodulationpositioning.Thestandardinputconsistsofa4-20mAsignalgeneratedbyaprocesscontroller;theresultingoutputisusedtoaccuratelyandrepeatablypositionavalveactuatorthroughconventionalorsolid-stateswitchingofeithersingleorthree-phaseACpower.
1.4 ProductFeaturesAccuracyandrepeatabilityofpositioningwithin1%offull-scaleforactuatorstroketimesgreaterthan30seconds.
Solidstatecircuitryforlongerlifeandreliableservice
4-20mAcommandsignal
Canbeusedtocontrolsingleorthree-phasesystems
JumperselectableLock-in-LastorFail-Closedconfigurationsifcommandsignalislost
Fiveparametersavailableforadjustmentallowsactuator/applicationmatch
AdjustableONandOFFmotorcontroltimers
LEDindicatorsdisplaysignal,power,andcontrolstatustosimplifycalibrationandmonitorperformance
•
•
•
•
•
•
•
•
MODUTRONIC20
MODEL II
CLOSE
OPENZERO
SPANGAIN
POWER ON
INPUT ACTIVE
ON TIME
OFF TIME
Zero, Span,Gain CalibrationPotentiometers
61-825-0713-1
SALES/SERVICE
434-528-4400
StatusIndicator Lights
On-Time/Off-TimeCalibrationPotentiometers
Cover
Open/CloseIndicatorLights
WiringHarness
1 2 3 4 5 6 7 8 9 10
Limitorque Actuation Systems
Lynchburg, VA. USA
MODUTRONIC20
MODEL II
CLOSE
OPENZERO
SPANGAIN
POWER ON
INPUT ACTIVE
ON TIME
OFF TIME
Zero, Span,Gain CalibrationPotentiometers
61-825-0713-1
SALES/SERVICE
434-528-4400
StatusIndicator Lights
On-Time/Off-TimeCalibrationPotentiometers
Cover
Open/CloseIndicatorLights
WiringHarness
1 2 3 4 5 6 7 8 9 10
Limitorque Actuation Systems
Lynchburg, VA. USA
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
1.5 ProductSpecificationsTable 1.1 – Modutronic 20 II Specifications
PowerRequirements Derivedfromactuatorsupply
Boardpower18VACor24VDC(±10%).3VA
ControlSignal 4-20mA
Accuracy Within±1%(>30secondstroke)
LossofCommandSignalSelections Fail-to-last-position
Fail-to-minimum-signal-position
Temperature -40°Cto+85°C(operating)
MaximumStarts Solidstatereverser–600/hour
PerHour Electromagneticcontactor–100/hour
MaximumDirectOutputLoading Motorcurrent–4.5AInrush,3AHolding
Dimensions Mod20–1.5”Hx3.25”Wx4”L
Separateenclosure
11.7”Hx12.75”Wx17.4”L
Deadband Adjustablebetween1%and10%
Resolution 1%
Linearity 1%
Humidity To95%(non-condensing)
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
8
2Operation
TheModutronic20IIreceivesaninputsignal,normally4-20mA,fromtheexternalprocesscontroller.Thissignaliscompared(withintheMod20IIcircuitry)tothepresentpositionoftheactuatorasindicatedbythesignalfromtheFeedbackPotentiometerattachedtothegeartrainoftheactuator.Thecomparisonofthesetwosignalsgeneratesanerrorsignalthatdictatesthedirectionanddistancetheactuatorneedstobedriven.
Upongenerationoftheerrorsignal,theappropriateoutputtriacisenabledand115-voltcontrolpowerisdirectedtotheoutputcontactor(thismaybeanelectromechanicalcontactororasolidstatereverserdependingupontheapplication).
Astheactuatordrivestowardtheset-point,itentersaregionsurroundingtheset-pointwherethecontrolfunctionwithintheMod20IIchangesfromacontinuouspowerapplicationtoapulsingmode(proportionalband).TheMod20IIcontinuouslycomparesthevalve’sactualpositiontothedesiredset-pointthroughitscircuitry;motorpulsingiscontinueduntiltheactuatorisaccuratelypositionedattheset-point.Thepointinthevalvetravelatwhichthepulsingmodeisenabledandspacing/durationofthepulsesarealluseradjustableontheMod20II.
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
Figure 2.1 – LY with a Modutronic 20 II and Associated Actuator Components
Motor
FeedbackPot(X2)
Control Transformer
4-20 mA out
InterconnectBoard
Gearing tovalve stem
Conventionalcontactor or
soild statereverser
Single orThree-Phase
Power
Input4-20mA
L1
L3L2
Actuator Body
MDPI
MotorCompartment
ControlCompartment
R-1Converter(Optional)
Mod 20 II34 Feed- Motor18 back ControlVAC IN IN/OUT1 2 3 4 5 6 7 8 9 1 0
Motor
FeedbackPot(X2)
Control Transformer
4-20 mA out
InterconnectBoard
Gearing tovalve stem
Conventionalcontactor or
soild statereverser
Single orThree-Phase
Power
Input4-20mA
L1
L3L2
Actuator Body
MDPI
MotorCompartment
ControlCompartment
R-1Converter(Optional)
Mod 20 II34 Feed- Motor18 back ControlVAC IN IN/OUT1 2 3 4 5 6 7 8 9 1 0
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
10
3Definitions
Figure 3.1 – Calibration Positions
CommandSignal Inputsignalprovidedbyusertoassignthedesiredvalveposition.
Deadband Adjuststhemaximumallowableerrorsignal.(DifferencebetweenthePositionCommandSignalandPositionFeedbackPotentiometerSignal).SelectableontheMod20IIDIPSwitch.SeeTable6.1forDIPSwitchsettingchart.
ProportionalBand(PulsingWindow) controlsthepointonthescaleofvalvetravelthatthemotorbeginsthepulsingmode.(IncreasingGAINdecreasesthewindowwidth).
AdjustingtheGAINPotentiometerfullyCWz(increasingGAIN/decreasingpulsingwindow),setstheGAINtoitsmaximumsettingcausingthemotortoruncontinuouslyuptotheSet-Pointbeforepoweristurnedofffromthemotor.
AdjustingtheGAINPotentiometerCCWu(decreasingGAIN/increasingpulsingwindow),causestheMod20IItobeginto“pulse”themotoronandoffasitapproachestheSet-Point.
OnTime AdjuststhetimethattheelectromechanicalcontactorsorSolid-StateReversersareengagedwhileinthepulsingwindow.
OffTime AdjuststhetimethattheelectromechanicalcontactorsorSolid-StateReversersaredisengagedwhileinthepulsingwindow.
Set-Point DesiredstoppingpositionforMod20II;determinedbytheCommandSignal.
Span CalibratestheMod20IItoaligntheMaximumCommandSignal(normally20mA)withthePositionFeedbackPotentiometerattheopenposition.
Zero CalibratestheMod20IItoaligntheMinimumCommandSignal(normally4mA)withthePositionFeedbackPotentiometeratthecloseposition.
•
•
Span
Valve Travel
(Zero/Minimum
Command Signal)
Valve Travel
Deadband
Proportional Band(Pulsing Window )
Set Point
(MaximumCommand Signal)
Span
Valve Travel
(Zero/Minimum
Command Signal)
Valve Travel
Deadband
Proportional Band(Pulsing Window )
Set Point
(MaximumCommand Signal)
11
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
4InitialCheckoutandSetup
4.1 VerifyCorrectMotorRotation(Phasing)andOPEN/CLOSEPushbuttonOperation
Itisveryimportanttocheckforcorrectmotorrotationtoinsurethatseriousdamagetothevalveorotherequipmentdoesnotoccur.Iftheactuatormotorrotatesinthewrongdirection,over-torquedamagecouldoccurtotheequipment.
Priortobeingshippedfromthefactory,eachactuatorisinspectedtoverifyproperoperationoftheTorqueandPositionLimitSwitchandtoensurethattheyfunctioncorrectly(i.e.closeswhentheCLOSEpushbuttonisdepressed,openswiththeOPENpushbutton,etc.).Theseinspectionsaremadewithaproperlyphasedpowersourceconnectedasdescribedintheactuatormanual.
CAUTION:Toensureproperoperationandtopreventyouractuatororotheractuatedequipmentfromdamage,verifythatyourunitisproperlyconnectedtoitspowersource.
NOTE:Yourapplicationmayvaryfromthefollowingstandardwiringconfigurationsforthree-phase,single-phase,andDCmotors.Refertoyouractuatorwiringdiagramforuser-specificwiringconfiguration.
Three-PhaseMotor1. UsingtheHandwheel,movethevalvetoamidtravelposition(midtravelpositionallowselectrical
operationinthevalve“safe”areaandkeepstheOPENandCLOSEDLimitSwitchesfromtrippingwhiletestingmotordirection).
2. TestmotordirectionbymomentarilypressingtheOPENpushbutton:a.IftheactuatormovestowardCLOSED,immediatelyturnallpowerOFFandreversethemotorleadsT1andT3.
NOTE:Refertoyouractuatorwiringdiagramforuser-specificwiringconfiguration.
b. IftheactuatormovestowardOPEN,themotoriswiredproperlyfortheapplication.
a
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
12
Single-PhaseMotor1. UsingtheHandwheel,movethevalvetoamidtravelposition(midtravelpositionallowselectrical
operationinthevalve“safe”areaandkeepstheOPENandCLOSEDlimitswitchesfromtrippingwhiletestingmotordirection).
2. TestmotordirectionbymomentarilypressingtheOPENpushbutton:
a. IftheactuatormovestowardCLOSED,immediatelyturnpowerOFFandproceedwiththefollowinginstructionsthatmatchyourapplication.
1. PermanentSplitCapacitorsingle-phasemotorscanbeconnectedforoppositerotationbyinterchangingtheleadsT1andT2comingfromthemotortotheterminalstrip.
2. Single-voltage,capacitor-start,induction-run,single-phasemotorsinterchangeleadsT2andT3comingfromthemotortotheterminalstrip.
3. Dual-voltage,capacitor-start,induction-run,single-phasemotorscanbeconnectedforoppositerotationbuttheconnectiondependsonwhetherthemotorisoperatedonlowvoltageoroperatedonhighvoltage.
Low-voltagemotorsareconnectedforoppositerotationasshowninthechangesbetweentheStandardRotationconfigurationandtheReverseRotationconfigurationinFigure4.1.ThisisaccomplishedbyinterchangingthetwoleadsT1andT3comingfromthemotorwiththetwoleadsT6andT8alsocomingfromthemotor.Nootherchangesarenecessary.
Figure 4.1 – Standard Motor Rotation and Reverse Motor Rotation Wiring Diagrams for Dual-Voltage, Capacitor-Start, Induction-Run, and Single-Phase Low-Voltage Motors
High-voltagemotorsareconnectedforoppositerotationasshowninthechangesbetweentheStandardRotationconfigurationandtheReverseRotationconfigurationinFigure4.2.Thisisaccomplishedbyinterchangingtwosetofleads.First,interchangetheleadsT1andT8comingfromthemotor.Second,interchangeleadsT3andT6atthestartingrelaysR1andR2.Nootherchangesarenecessary.
•
•
Standard RotationWiring
T6
T3
L1
L2
4 C5R2 T7
O
C
R1
R2Cap
1
21
2
O
C
R1 T54 5 O
T6 T9
T10
T3
T1
T4T8
T2
Reverse RotationWiring
T6
T3
L1
L2
4 C5R2 T7
O
C
R1
R2Cap
1
21
2
O
C
R1 T54 5 O
T8 T4
T2
T6
T8
T9
T1
T10
Standard RotationWiring
T6
T3
L1
L2
4 C5R2 T7
O
C
R1
R2Cap
1
21
2
O
C
R1 T54 5 O
T6 T9
T10
T3
T1
T4T8
T2
Reverse RotationWiring
T6
T3
L1
L2
4 C5R2 T7
O
C
R1
R2Cap
1
21
2
O
C
R1 T54 5 O
T8 T4
T2
T6
T8
T9
T1
T10
1
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
Figure 4.2 – Standard Motor Rotation and Reverse Motor Rotation Wiring Diagrams for Dual-Voltage, Capacitor-Start, Induction-Run, and Single-Phase High-Voltage Motors
b. TestMotordirectionagainbymomentarilypressingtheOPENpushbutton.IftheactuatormovestowardOPEN,themotoriswiredproperlyfortheapplication.Ifnot,checkthewiringdiagramforproperwiring.
4.2 VerifyLimitSwitchandTorqueSwitchSettings
SettheOPENandCLOSELimitSwitchandtheTorqueSwitchaccordingtotheinstructionsinthespecificActuatorinstructionmanual.
4.3 AdjustingtheActuatorFeedbackPotentiometer
WARNING:HazardousVoltage.TurnpowerOFFbeforecalibratingtheFeedbackPotentiometer.
1. Shutoffallpowertotheactuator.
2. UsingtheHandwheel,positiontheactuatortomid-travel(valveatthe50%position).
3. DisconnectthePotentiometerWiringHarnessfromwhereitispluggedinorconnectedtoaTerminalStrip.
4. UsinganohmmeterverifythatthePotentiometerisinmid-travelposition.TheresistancefromeachEndConnectiontotheCenterConnectionshouldbehalfofthefullresistanceofthePotentiometer.Example:1000ohmPotentiometershouldreadapproximately500ohmsfromoneoftheEndConnectionstotheCenterConnection.
c
Standard RotationWiring
T6
L1
L2
4 C5R2 T7
O
C
R1
R2Cap1
21
2
O
C
R1T5
4 5 O
T8 T10
T3
T4
T4
T1 T2 T3
T4
T6 T9
T4
Reverse RotationWiring
T6
L1
L2
4 C5R2 T7
O
C
R1
R2Cap1
21
2
O
C
R1T5
4 5 O
T1 T2
T3
T9
T4
T8 T10 T6
T4
T3 T4
T4
T3T6Standard RotationWiring
T6
L1
L2
4 C5R2 T7
O
C
R1
R2Cap1
21
2
O
C
R1T5
4 5 O
T8 T10
T3
T4
T4
T1 T2 T3
T4
T6 T9
T4
Reverse RotationWiring
T6
L1
L2
4 C5R2 T7
O
C
R1
R2Cap1
21
2
O
C
R1T5
4 5 O
T1 T2
T3
T9
T4
T8 T10 T6
T4
T3 T4
T4
T3T6
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
14
Figure 4.3 – Potentiometer Calibration Components Shown on a LY Position Indicator
5. Ifthereadingisnotcorrect,proceedtoStep6.IfthereadingiscorrectproceedtoStep7.
6.
a. LoosenthesmallSetScrewthatretainsthePotentiometerDriveSpurGeartothePotentiometerShaft.
b. RemovetheSpurGeartoallowmanualrotationofthePotentiometerShaft.
c. RotatethePotentiometerShaftuntilthecorrectreadingsareobtainedasdescribedinStep4.
d. RepositiontheSpurGeartore-engagewiththeGearTrain.
e. ProceedtoStep7.
7. DisconnecttheohmmeterandreconnectthePotentiometerwiringtooriginalconnection.
4.4 ConnectingtheMod20IItoCustomerCommandSignalLeads
WARNING:HazardousVoltage.TurnpowerOFFbeforeremovingtheactuatorcoverandconnectingthecommandsignal.
IftheMod20IIwasfactoryinstalled,theonlyconnectionrequiredistheuserinputcommandsignalleads(normally4-20mA).Theseconnectionsshouldbemadeattheterminalstripinaccordancewiththewiringdiagramenclosedwiththeactuator.
NOTE:iftheunitdoesnothavefactory-suppliedpushbuttons,refertoyourwiringdiagramtoinstallacustomer-suppliedpushbuttonstation.
IfretrofittingoraddingaMod20IItoanexistingactuator,usethefollowingconnectiontableandyourwiringdiagramforwireleaddesignations.
c
PotentiometerShaft
Spur Gear
Setscrew
EndConnection
CenterConnection
Ohmmeterto Pot Leads
PotentiometerDrive Gear
50 1000PERCENT OPEN
Limitorque
PotentiometerShaft
Spur Gear
Setscrew
EndConnection
CenterConnection
Ohmmeterto Pot Leads
PotentiometerDrive Gear
50 1000PERCENT OPEN
Limitorque
1
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
Table 4.1 – Modutronic 20 II Terminal Connections
Mod20IITerminals Description L120Non-CompactIntegralPCBoard(61-825-0337-3)
P1-1 18VAC 18VAC SeeNote
P1-2 18VAC PowerSource SeeNote
P1-3 Negative4-20mAsignal TB1-5 -4-20mA
P1-4 Positive4-20mAsignal TB1-4 +4-20mA
P1-5 Potentiometer TB1-8
P1-6 Potentiometer(wiper) TB1-9
P1-7 Potentiometer TB1-10
P1-8 115VAC(outputcommon) TB2-5
P1-9 CloseContactorOutput TB2-6
P1-10 OpenContactorOutput TB2-7
Note: To Terminal Strip or Control Power Transformer with 18-Volt tap.
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
16
5Mod20IIPresets
WARNING:HazardousVoltage.TurnpowerOFFbeforeremovingtheactuatorcoverandconnectingyourcommandsignal.
1. Turnoffallpowertotheactuatortoavoidequipmentdamageorpersonalinjury.
2. RotatetheGAINPotentiometerfullyCCWu,then15turnsCWztoreachthemidpointofthePotentiometer.(SeeFigure6.3forPotentiometerlocations).
NOTE:Each30-turnPotentiometerwillfaintly‘click’whenrotatedtoeitherthemaximumorminimumposition.
3. RotatetheZEROPotentiometerfullyCCWu,then15turnsCWztoreachthemidpointofthePotentiometer.
4. RotatetheSPANPotentiometerfullyCCWu,then15turnsCWztoreachthemidpointofthePotentiometer.
5. ThefollowinginitialadjustmentstotheONTIMEandOFFTIMEPotentiometersshouldbemadetoestablishtheproperpulsingsequenceanddurationforbothelectromechanicalandsolidstatecontactors.
a. Electromechanicalcontactor
1. RotateONTIMEandOFFTIMEPotentiometersfullyCCWu,then15turnsCWztothemidpointofthePotentiometer.
2. RotateboththeONTIMEandOFFTIMEPotentiometersthenumberoftimesindicatedintheTable5.1toobtainthedesiredoperatingtime.
Table 5.1 – ON/OFF Potentiometer Turns for Desired Operating Time
OperationTime OnTime OffTime
Lessthan60seconds 11turnsCWz 30turnsCWz
60-120seconds 13turnsCWz 30turnsCWz
Greaterthan120seconds 17turnsCWz 25turnsCWz
b. Solidstatereversers/VFDs
1. RotateONTIMEandOFFTIMEPotentiometersfullyCCWu.
2. RotateONTIMEPotentiometer6turnsCWz.
c
1
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
3. RotateOFFTIMEPotentiometer8turnsCWz.
4. Thiswillprovidea0.04secondONpulseanda0.5secondOFFpulse.
NOTE:
a. RotatingtheONTIMEPotentiometerCWzwillincreasetheONtime.
b. RotatingtheOFFTIMEPotentiometerCWzwillincreasetheOFFtime.
c. Adjustingonecontrol(ONorOFFTIMEPotentiometer)willaffecttheadjustmentoftheothercontrol(ONorOFFTimePotentiometer).
NOTE:
a. ElectromechanicalStartersshouldnotexceed100totalstartsperhour.
b. Solid-StateReversersshouldnotexceed600totalstartsperhour.
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
18
6CalibrationProcedure
WARNING:HazardousVoltageinControlCompartment.ExercisecautionwhilecalibratingtheMod20IIwiththeActuatorControlCompartmentopenandpowerON.
Thepurposeofperformingthecalibrationprocedureistoachievethemaximumaccuracyobtainableforeachparticularactuatorapplicationwhileprovidingstableoperation.Theactuatorgearratioandmanyotherfactorsdeterminetheoptimumcalibrationsettings.
FourDIPSwitchesmountedontheMod20II,aswellastheZERO,SPAN,GAIN,ONTIME,andOFFTIMEpotentiometers,areusedtoobtainthepropersettingsforyourapplication.Thisprocedurewillproceedfromthemostaccuratesettingstotheleastaccuratesettingsuntilunitstabilityisachieved.
Figure 6.1 – Calibration Adjustments for the Modutronic 20 II
1. TurnallpowertotheactuatorOFF.
2. VerifythattheproceduresfortheInitialCheckoutandSetup(Section4)andMod20IIPresets(Section5)havebeenproperlycompleted.
c
MODUTRONIC20
MODEL II
CLOSE
OPENZERO
SPANGAIN
POWER ON
INPUT ACTIVE
ON TI ME
OFF TIME
DIP Switch
61-825-0713-1
434-528-4400
Limitorque Actuation Systems
Lynchburg, VA. USA
MODUTRONIC20
MODEL II
CLOSE
OPENZERO
SPANGAIN
POWER ON
INPUT ACTIVE
ON TI ME
OFF TIME
DIP Switch
61-825-0713-1
434-528-4400
Limitorque Actuation Systems
Lynchburg, VA. USA
1
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
3. Tosimulateacommandsignal,connectthemACalibratortotheCommandInputLeadsontheMod20II.TheseterminationsaretypicallyconnectedtotheactuatorInterconnectBoard,oriftheMod20IIispanelmounted,ontheRearTerminalStripofthepanelmount.Ineithercase,theseleadsarelabeledonyourwiringdiagramandwillleadtoconnections3(P1-3[-])and4(P1-4[+])ontheMod20II.
Figure 6.2 – mA Calibrator Typically Connects (suggest Altek Model 334, www.altekcalibrators.com) to an Interconnect Board Terminal Strip or Terminal Strips Located in the Rear of a Panel-Mounted Mod 20 II
4. SettheMod20IIDIPSwitch#3totheONpositionandDIPswitchesnumbered1,2,and4totheOFFposition.Thiswillsettheerrormargin(DEADBAND)to1%accuracy.
Figure 6.3 – Modutronic 20 II Board Component Locations
16.00
INPUT OUTPUT
mA CALIBRATOR
OUTPUTmA
mA
24v
IN
OFF
OFF
POWERON
Interconnect Board
1 2 3 4 5 6 7 8 9 10 11 12
15 16 17 18 19 20 21 22 23 24
OR
0%
ADJUST
100%
FINECOARSE
16.00
INPUT OUTPUT
mA CALIBRATOR
OUTPUTmA
mA
24v
IN
OFF
OFF
POWERON
Interconnect Board
1 2 3 4 5 6 7 8 9 10 11 12
15 16 17 18 19 20 21 22 23 24
OR
0%
ADJUST
100%
FINECOARSE
Zero
Span
Gain
PowerON
InputActiveLED
ONTime
OFFTime
DIPSwitch
CloseLED
OpenLED
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
20
Table 6.1 – DIP Switch Setting Levels of Deadband Accuracy
DeadbandPercentage
DipSwitchNumber
1 2 3 4
±.5% Off Off Off On
±1% Off Off On Off
±1.5% Off Off On On
±2.5% Off On Off Off
±3.0% Off On Off On
±3.5% Off On On Off
±4.0% Off On On On
±6.0% On Off Off Off
±6.5% On Off Off On
±7.0% On Off On Off
±7.5% On Off On On
±8.5% On On Off Off
±9.0% On On Off On
±9.5% On On On Off
±10.0% On On On On
WARNING:HazardousVoltageinControlCompartment.ExercisecautionwhilecalibratingtheMod20IIwiththeActuatorControlCompartmentopenandpowerON.
5. SetthemACalibratorfortheminimumsignallevel(normally4mA).TheINPUTACTIVELEDontheMod20IIshouldbeilluminated.Ifnot,reversethepolarityofthemAcalibratorconnections.
6. IftheActuatorisequippedwithanAUTO/MANUALorLOCAL/REMOTEselectorswitch,turntheselectortotheAUTOorREMOTEposition.
7. ApplypowertotheActuatorandtheMod20II.ThePOWERONLEDontheMod20IIshouldbeilluminated.
8. TheActuatormayrunineitherdirectionandthenstop;
a. Iftheunitstops,proceedtoStep9.
b. Iftheunithuntsbackandforth,decreasetheDEADBANDaccuracybychangingtheDIPSwitchsetting(refertoTable6.1).ContinuetoStep9.
c. Iftheunitrunsallthewaytooneendoftravelandstops,thePotentiometerLeadsareprobablywiredbackwards;reversetheFeedbackPotentiometer’spolaritybyreversingtheendleadsattheTerminalStriporontheInterconnectBoard(ifyourapplicationusestheCompactIntegralInterconnectBoard,thePlug-inHarnessfromthePottotheInterconnectBoardcanberotated180˚toreversethepolarity).
9. AdjusttheZEROpoint.Thisstepcalibratestheminimumorzeroset-pointtocorrespondtotheend-of-traveloftheActuatorandoftheFeedbackPotentiometer.RotatetheZEROcontrolslowlyintheCWzdirection.ThiswillcausetheActuatortobedrivenslowlytowardstheminimumcontrolposition(normallyCLOSED).ContinuerotatingtheZEROcontrolCWzuntiltheminimum(CLOSED)PositionLimitSwitchtripsandthemotorstops.TheCLOSELEDshouldilluminateeachtimetheMotoroperates.
10. AdjustthecontrolSPAN.ThisstepcalibratesthetotalSPANofthecontrolfunctionandsetsthemaximumsettingtocorrespondtotheend-of-traveloftheActuatorandoftheFeedbackPotentiometer.
c
21
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
a. SetthemACalibratortothemaximumcommandsignal(normally20mA).
b. Theunitmay:
1. RuntowardthemaximumpositionandstopshortofthePositionLimitSwitchtrippoint,or
2. Remaininposition.
c. RotatetheSPANPotentiometerslowlyCWz.ThiswillcausetheActuatortomoveslowlytowardthemaximum(normallyOPEN)position.ContinuerotatingtheSPANcontrolCWzuntilthemaximum(OPEN)PositionLimitSwitchtripsandthemotorstops.TheOPENLEDshouldilluminateeachtimetheMotoroperates.
11. AfterinitiallysettingtheZEROandSPANsetting,usethemACalibratortosettheCommandSignalbacktotheminimumsetting(usually4mA);allowtheactuatortorununtilitstops.Nowfine-tunetheZEROsettingforthepositionwheretheLimitSwitchjusttrips.
12. UsethemACalibratortosettheCommandSignalbacktothemaximumsetting(usually20mA);allowtheactuatortorununtilitstops.Nowfine-tunetheSPANsettingforthepositionwheretheLimitSwitchjusttrips.
NOTE:Ifhuntingcontinuesduringcalibrationprocedure,itmaybenecessarytotemporarilydecreasetheGAINsettingorincreasetheDEADBANDsettingtogettheZEROandSPANsettingscalibrated.
13. AdjusttheONTIME(optional).ThisstepadjuststheperiodoftimetheMotorisenergizedinthepulsingmodewhenitisapproachingthefinalset-pointposition.
NOTE:TheONTIMEmustbeadjustedpriortoadjustingtheOFFTIME.AdjustingtheONTIMEafteradjustingtheOFFTIMEwillrequirerepeatingtheOFFTIMEadjustment.
ThedurationoftheONTIMEpulsetotheContactor/SolidStateReverserisincreasedbyrotatingtheONTIMEPotentiometerCWz.
14. AdjusttheOFFTIME(optional).ThisstepadjuststheperiodoftimetheMotorisde-energizedinthepulsingmodewhenitisapproachingthefinalset-pointposition.ThiscanalsobedescribedastheintervalbetweenONTIMEpulses.ThedurationoftheOFFTIMEpulsetotheContactor/SolidStateReverserisincreasedbyrotatingtheOFFTIMEPotentiometerCWz.
15. AdjusttheGAIN.Thisstepcalibratesthewidthofthepulsingwindowaroundtheset-point.ThiscontrolworksinconjunctionwiththefourDIPSwitcheslocatedontheMod20IIcircuitboardtodeterminethefinalaccuracyoftheunitinregardtosetpointposition.Thewiderthepulsingwindow,thegreaterthedistancefromtheset-pointtheunitentersthepulsingmode.ItisdesirabletominimizethepulsingwindowwithoutcausingtheActuatortohunt(oscillateuncontrollablyaroundtheset-point).
a. Fortheinitialcalibration,ensurethatDIPSwitch3isONandDipSwitches1,2,and4areOFF.Thiswillprovide1%DEADBAND.
NOTE:IfnoDIPSwitchissettotheONposition,theactuatorwillnotoperate.
b. MakesuretheGAINPotentiometerisatthemidpoint,thenrotatetheGAINPotentiometeroneturnCWz.
c. StartwiththemACalibratorat4mA,thenmakea5mAchangeintheoutputofthemACalibratortoprovideasignificantchangeofposition;nowwatchtheactionoftheactuator.
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
22
1. Iftheactuatorhuntsuponreachingthenewset-point,reducetheGAINcontrolbyturningintheCCWudirectionuntilthehuntingstopsandproceedtoStepe.
2. IftheunitcontinuestohuntaftertheGAINcontroladjustment,proceedtoStepd.
d. RotatetheGAINcontrolfullyCCWuandthen15turnsCWz;adjusttheDEADBANDtoalessaccuratesettingandrepeattheGAINsettingprocedurestartingwithStepa.Forexample,ifDIPSwitch3isONandDIPSwitches1,2,and4areOFFtheDEADBANDsettingisat1%accuracy;changetheDIPSwitchsettingto11/2%accuracyandrepeattheproce-dures13athrough13euntilthecorrectDIPSwitchandGAINcontroleliminatesactuatorhunting.SeeTable6.1forDIPSwitchsettinglevelsofdeadbandaccuracy.
e. RotatetheGAINcontrolanextra1/2turnCCWutoeliminatethepossibilityoffutureactuatorhunting.
16. SetdesiredFAILTOmode.SeeFigure6.4.
a. IfLOCK-IN-LAST-POSITIONisdesiredwhenlossofinputsignaloccurs,installajumperatJP1toconnectPin1and2.
b. IfFAIL-TO-4mA-POSITIONisdesiredwhenlossofinputsignaloccurs,installajumperatJP1toconnectPin2and3.
NOTE:Besuretouseoneofthetwojumperselectionsdiscussedabove;FAIL-TOoperationwillbeforfeitedifJP1isnotused.
Figure 6.4 – FAIL TO Mode JP1 Jumper
17. YourMod20IIshouldnowbeproperlycalibrated.
Lock-In-Last Fail-to-4 mA-PositionJP1
1 2 3JP1
1 2 3
Lock-In-Last Fail-to-4 mA-PositionJP1
1 2 3JP1
1 2 3
2
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
7Troubleshooting
Symptom PossibleCause CorrectiveAction
UnitwillnotoperateelectricallyinAUTOorMANUAL
1.Nopowertounit 1a.VerifyPowerSupplyiselectricallycorrectandpresentatactuator.
1b.VerifyPowerLeadsareconnectedinaccor-dancewiththeapplicablewiringdiagram.
1c.InspectforBlownFuse,trippedCircuitBreaker,orOPENDisconnectSwitch.
2.Wiringproblems 2a.(LYswithinternalMod20IIboard)Checkpush-onterminalbetweentheIntegralPCBoardandtheMicroSwitches.CheckforbadMicroSwitchesonSWStation.
3.Starterwiresloose 3a.CheckalltheconnectionsontheReversingStarter.
4.Thermaloverloadshavetripped 4a.Measurecontinuityinthecircuit.Ifyouhaveanopencircuit,waitforthemotortocool,thentrytooperateactuator.Youmayneedtoreducethenumberofstartsperhour.
UnitwillnotoperateelectricallyinAUTO
1.NopowertoMod20II 1a.Verifyincoming18VACbetweenterminalsP1-1andP1-2onMod20IIboard.
2.BadMod20IIboard 2a.Checkboardforburntorbrokencomponents.BypassMod20IIboardusingPushbuttonstoverifyproperoperation.SeeyourspecificwiringdiagramforbypassingMod20IIboard.
3.CommandSignalLeadsreversed
3a.(L120InterconnectPCBoard)CheckthattheCommandSignalLeadsarewiredtoterminalTB16(+)andTB17(-).
4.BadPotentiometer 4a.CheckthePotentiometerwithanohmmeterelectricallyinAUTO.UnplugthePotfromtheIntegralPCBoardandtakeameterreadingbetweenpins7-1and7-2or7-2and7-3.Themetershouldhaveasteadyreading.Ifthemeterreadinggoestozeroorjumpsaround,verifythatthePotiscentered.ReplacethePotifneeded.CheckforCablesthatmayhavebeenpinchedbetweentheHousingCoverorIntegralAssembly.
5.AllDIPswitchesturnedOff 5a.CheckDIPswitches.RefertoCalibrationProcedure(Section6),Step15a.
Continued on page 24
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
24
Symptom PossibleCause CorrectiveAction
Unitsruninonedirectiononly
1.Shortedoutput 1a.VerifyproperMANUALdirectionoperation.Usingammeter,verifypropercommandsignal,verifyallcalibrationshavebeencompletedproperly.IfyoustillhavedifficultycalibratingtheMod20IIafterverifyingtheabovesettings,replacetheMod20II.
NoLOCK-IN-LASTPOSITION
1.MissingJP1Jumper 1a.LocateJP1JumperontheMod20IIboardandverifyconnections.
Unitwillnotfollowsignal
1.BadPotentiometerorPotentiometerisnotcentered
1a.CheckPotasdiscussedinitem#7.IfPotisOK,placetheactuatorat50%andchecktheresistancebetweenterminals7-1and7-2or7-2and7-3withanohmmeter.See“AdjustingtheActuatorFeedbackPotentiometer”(Section4.3).
Inputsignaldoesnotresultinfulltravelofthevalve
1.Mod20IInotcalibratedcorrectly
1a.SeeSection6toreviewthecalibrationprocedurefortheMod20II.
2.ZEROandSPANadjustmentsincorrect
2a.RecalibrateaccordingtoprocedureinSection6.
Largeinputsignalvariationsresultinlittleornoactuatormovement
1.ImproperanalogInputSignalvalue
1a.CheckforproperInputSignalvalue.
2.LimitSwitch 2a.Checkforpropersetting.(SeeappropriateactuatormanualforsettingtheLimitSwitches.)
3.DEADBANDadjustment 3a.ChecktheDIPSwitchaccuracyadjustmentsshowninTable6.1.
4.ZEROandSPANadjustments 4a.RecalibrateaccordingtoprocedureinSection6.
2
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
8WiringDiagram
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
26
Figure 8.1 – Modutronic 20 II Typical Three-Phase Wiring Diagram
G Green indicatingR Red indicating
- Opening coil- Closing coil
Motor
7
3(7) (7C)
(3) (3C)
R
G
(18) (18C)
(17) (17C)
(5) (5C)
(1) (1C)
(8) (8C)
8
1
Local Remote
O
CO
C
C
C
C
O
O
O
T1
T2
T3
L1
L2
L3
4
5(4) (4C)
Th.O l
By-pass cir.
Ind lightOpen limitBy-pass ci r
Ind lightClose limit
SpareSpareSpareSpareSpareSpareSpareSpare
FullyOpen
FullyClosed
Valve shown in full open position
SsOff
Spare
Spare
3. See certification sheet for voltage supplied. Transformer unused wired to be separately covered with insulating heat shrink tubing.
JumpSee note#5
A B
Gnd
Cpt
18V115V 18V
Pb1Open
Pb2Stop
Pb3Close
Elec htr
Mtr htr
O
C
(Open)
4
2(Close)
3
(Common )
1
11
12
13
H2H1
6
5
Remote ind
Remote ind
21/22
10
19/20
A B C D E
4-20 mAInputSignal
(+)
(-)
Blue
Yellow
Orange
1000ohmPot
10
9
8765
4
3
12
Open
Close
CommonCWSweeperCCW
(+)
(-) Inpu
tSi
gnal
18 VACPower
18
1
Yellow
Blue
Orange
17
18
LEGEND
2.1.
Close contactOpen contact
NOTESLimit switch contact development
Valve positionRotor
Open
Close
Int.1
Int.2
Function
1234567
910111213141516
Cont
act
Opening torque switch interrupts control circuit ifmechanical overload occurs during opening cycle
Closing torque switch interrupts control circuit ifmechanical overload occurs during closing cycle
18
17
YellowRed
BlueWhite
YellowWhite
Brown
YellowBlack
BlueBlack
P1
P1
BrownRed
Red
Red
White
BlueRed
P1
Purple
Black
Black
Blac
k
Red
Black
P2
Gray
Black
Yellow
Green/white Green/white
Green
230 V500H1 and
To l1H2 and
To l2
480460415380
1ABEDE
AlternateTransformer types
600575550
--
32
Taps
Brown
Orange
Gray
Pink
Blue
L1f
L2f
Res
Res
BlackYellow
Green/white
Blue
Blue
Yellow
RedBrownBlack
Yellow/black
Blue/black
Mod
-20
mod
elII
Yellow
4. Rotors int.1 & Int.2 Can be set at valveposition full open, full closed or anyposition in between as indicated bypoints a and b.
5. Add jumper on ls#8 between terminals (8)and (8C) for torque seating valves
O-open contactC-close contact
Cpt-control power transformer+-Mechanical interlockTh.Ol-thermal overload contacts
Ss-selector switch (local-off-remote)Pb1-open pushbuttonPb2-stop pushbuttonPb3-close pushbuttonElec htr-compartment heaterMtr htr-motor heaterPot-potentiometerRes-lamp resistors
Red
Whi
te
Blue
Fuse
Fuse
Fus
Yello
w
Blue
8 G Green indicatingR Red indicating
- Opening coil- Closing coil
Motor
7
3(7) (7C)
(3) (3C)
R
G
(18) (18C)
(17) (17C)
(5) (5C)
(1) (1C)
(8) (8C)
8
1
Local Remote
O
CO
C
C
C
C
O
O
O
T1
T2
T3
L1
L2
L3
4
5(4) (4C)
Th.O l
By-pass cir.
Ind lightOpen limitBy-pass ci r
Ind lightClose limit
SpareSpareSpareSpareSpareSpareSpareSpare
FullyOpen
FullyClosed
Valve shown in full open position
SsOff
Spare
Spare
3. See certification sheet for voltage supplied. Transformer unused wired to be separately covered with insulating heat shrink tubing.
JumpSee note#5
A B
Gnd
Cpt
18V115V 18V
Pb1Open
Pb2Stop
Pb3Close
Elec htr
Mtr htr
O
C
(Open)
4
2(Close)
3
(Common )
1
11
12
13
H2H1
6
5
Remote ind
Remote ind
21/22
10
19/20
A B C D E
4-20 mAInputSignal
(+)
(-)
Blue
Yellow
Orange
1000ohmPot
10
9
8765
4
3
12
Open
Close
CommonCWSweeperCCW
(+)
(-) Inpu
tSi
gnal
18 VACPower
18
1
Yellow
Blue
Orange
17
18
LEGEND
2.1.
Close contactOpen contact
NOTESLimit switch contact development
Valve positionRotor
Open
Close
Int.1
Int.2
Function
1234567
910111213141516
Cont
act
Opening torque switch interrupts control circuit ifmechanical overload occurs during opening cycle
Closing torque switch interrupts control circuit ifmechanical overload occurs during closing cycle
18
17
YellowRed
BlueWhite
YellowWhite
Brown
YellowBlack
BlueBlack
P1
P1
BrownRed
Red
Red
White
BlueRed
P1
Purple
Black
Black
Blac
k
Red
Black
P2
Gray
Black
Yellow
Green/white Green/white
Green
230 V500H1 and
To l1H2 and
To l2
480460415380
1ABEDE
AlternateTransformer types
600575550
--
32
Taps
Brown
Orange
Gray
Pink
Blue
L1f
L2f
Res
Res
BlackYellow
Green/white
Blue
Blue
Yellow
RedBrownBlack
Yellow/black
Blue/black
Mod
-20
mod
elII
Yellow
4. Rotors int.1 & Int.2 Can be set at valveposition full open, full closed or anyposition in between as indicated bypoints a and b.
5. Add jumper on ls#8 between terminals (8)and (8C) for torque seating valves
O-open contactC-close contact
Cpt-control power transformer+-Mechanical interlockTh.Ol-thermal overload contacts
Ss-selector switch (local-off-remote)Pb1-open pushbuttonPb2-stop pushbuttonPb3-close pushbuttonElec htr-compartment heaterMtr htr-motor heaterPot-potentiometerRes-lamp resistors
Red
Whi
te
Blue
Fuse
Fuse
Fus
Yello
w
Blue
8
2
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
Figure 8.1 – Modutronic 20 II Typical Three-Phase Wiring Diagram (continued)
Electrical compartment
18
17
Open
Close
(17C) (17)
(18C) (18)
TorqueSwitch
Th.O l
Motor
Limit switches
Mtr htr
T1
T2
T3P1
H1H2P2
Limit switches
Cpt
Pb3Close
Pb2Stop
Pb1Open
LocalOf f
Remote
Wht Blk
(Note#3 )
Blu
Yel
Brn
Org
Gry
Pnk
Blk/wht
Red/wht
Blk
P2Grn/wht
Blk
WhtH2
H1
Grn/wht
L1
L2
L3
Wht
Blk
Wht
Blk
Blu/blk
Yel/blk
Blu
Yel
Org
Brn
Feedback pot1000 ohm
For signalConverter use
When supplied
Blu
Yel
Org
Primary
Secondary
Wht
RedBlk
BrnPur
Gry Pnk
Blu Yel
Org
Brn
RedBrn
Blk
Red Wht GrnWht
ElecHt r
BlueYellowPurpleBlackOrangeBrow nWhiteRedGreenPinkGrayColor/striped
Wire color legend
Motor ground lug
Grn/wht
1
L1
L2
Fuses
ChassisGround
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Selector switch inRemote indication
For signalConverter use
When supplied
Incoming power ground
L3 incoming power
L2 incoming power
L1 incoming power
Spare
: Blu: Yel: Pur: Blk: Org: Brn: Wht: Red: Grn: Pnk: Gry
L1f
L2f Reversing starter
L2f
L1f
Close rotor Open rotor123
1
23
4
12
34
YelYel
Yel/blkBlu/blk
BlkBrnRedOr gYelBlu
123456789
10
4-20 mAInputSignal
(-)
(+)
Spare
Spare
Spare
1
2
3
4
123
BlkBrnRed
BlkBrnRed
Yel
Red/whtBlk/wht
Blu
Blu
21
12
BluBlu1
2
18V
10Va
Yel
18V
10Va
115V
75Va
(1)
(1C)5
(5C)
(5)
(4)
(4C)(3)
(3C)(2)
(2C)
(8)8
(8C)
7(7C)(6)
6
(6C)
(12)12
(12C)(11)11
(11C)(10)10
(10C)(9)
9(9C)
(16)16
(16C)(15)15
(15C)(14)14
(14C)(13)13
(13C)
1
2
3
4
(7)
Yel/blk
Yel/red
Grn
Blk
Blu/red
Blue
Red
Blk
Yel/red
Yel
Int.2 Rotor Int.1 Rotor
Blu/blk
Blu/red
Yel/blk
Yel/red
Mod-20-
Model II
Fuse
RedWht
Blk
BluPurYel
PnkOrg
Brn
Gry
Grn
Lights
Buttons
Aux. Term.
Res
Res
Sw323 pushbutton station
Blu/wht
L3T3
L2T2
L1T1
Yel/wht
P1
L1T3
L2T2
L3T1
CO
Yel
Pur
Blu
Blu
Blk
Yel
Blk
Pur
R G
Red
Electrical compartment
18
17
Open
Close
(17C) (17)
(18C) (18)
TorqueSwitch
Th.O l
Motor
Limit switches
Mtr htr
T1
T2
T3P1
H1H2P2
Limit switches
Cpt
Pb3Close
Pb2Stop
Pb1Open
LocalOf f
Remote
Wht Blk
(Note#3 )
Blu
Yel
Brn
Org
Gry
Pnk
Blk/wht
Red/wht
Blk
P2Grn/wht
Blk
WhtH2
H1
Grn/wht
L1
L2
L3
Wht
Blk
Wht
Blk
Blu/blk
Yel/blk
Blu
Yel
Org
Brn
Feedback pot1000 ohm
For signalConverter use
When supplied
Blu
Yel
Org
Primary
Secondary
Wht
RedBlk
BrnPur
Gry Pnk
Blu Yel
Org
Brn
RedBrn
Blk
Red Wht GrnWht
ElecHt r
BlueYellowPurpleBlackOrangeBrow nWhiteRedGreenPinkGrayColor/striped
Wire color legend
Motor ground lug
Grn/wht
1
L1
L2
Fuses
ChassisGround
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Selector switch inRemote indication
For signalConverter use
When supplied
Incoming power ground
L3 incoming power
L2 incoming power
L1 incoming power
Spare
: Blu: Yel: Pur: Blk: Org: Brn: Wht: Red: Grn: Pnk: Gry
L1f
L2f Reversing starter
L2f
L1f
Close rotor Open rotor123
1
23
4
12
34
YelYel
Yel/blkBlu/blk
BlkBrnRedOr gYelBlu
123456789
10
4-20 mAInputSignal
(-)
(+)
Spare
Spare
Spare
1
2
3
4
123
BlkBrnRed
BlkBrnRed
Yel
Red/whtBlk/wht
Blu
Blu
21
12
BluBlu1
2
18V
10Va
Yel
18V
10Va
115V
75Va
(1)
(1C)5
(5C)
(5)
(4)
(4C)(3)
(3C)(2)
(2C)
(8)8
(8C)
7(7C)(6)
6
(6C)
(12)12
(12C)(11)11
(11C)(10)10
(10C)(9)
9(9C)
(16)16
(16C)(15)15
(15C)(14)14
(14C)(13)13
(13C)
1
2
3
4
(7)
Yel/blk
Yel/red
Grn
Blk
Blu/red
Blue
Red
Blk
Yel/red
Yel
Int.2 Rotor Int.1 Rotor
Blu/blk
Blu/red
Yel/blk
Yel/red
Mod-20-
Model II
Fuse
RedWht
Blk
BluPurYel
PnkOrg
Brn
Gry
Grn
Lights
Buttons
Aux. Term.
Res
Res
Sw323 pushbutton station
Blu/wht
L3T3
L2T2
L1T1
Yel/wht
P1
L1T3
L2T2
L3T1
CO
Yel
Pur
Blu
Blu
Blk
Yel
Blk
Pur
R G
Red
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
28
9Schematic
2
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
Figure 9.1 – Modutronic 20 II Schematic Diagram
R1
CW
3.74K
-15 VDC
200K
47.5K
R4
C1
10K
R6
10K
R5U1A 1
R27.5K R7
20KC2
1.2/25SPAN
5K
R10+15 VDC
47/25
P1-7
1K
47/2
R1351K
FEEDBACKPOTENTIOMETER
1000 ohm
ZERO
C6
10/25
-15 VDC
+15 VDC
5KR11
150K
R12
LM7815BT-
U5LM7915BT-
.1/25
C111.2/
R16
R17
R18
2M 3.3
1/21%2.5%6%
R939K
1N4454 CR1
7.15KR20
2N440
30.1KR2
CR31N445
CR41N4454
-15 VDC7.15K
1N445Q22N4401
R2830.1K
1%
21
LM1558
10K
U2A
C13.022/25
2.2M CR51N445
5 U2
R2610K
7
LM15
R210K
R210K
CR1N44
OH
CW
GAINR295K
.22/25
.22/25
INPUTCIRCUIT
C12
+15 V
C7
R155.1K
P1-2
P1-1CR171N40
1N40
C8200/
200/
HLMP47
+15 VDC
-15 VDC
CW
Controller
Deadband
Close Command
Open Command
-15 VDC
18 VAC
P1-6
P1-5
-15 VDC
(Page 30)
+15 VDC
AnalogInverter
Input Impedance (Zin)Zin (4 mA) = 850 ΩZin (8 mA) = 550 ΩZin (12 mA) = 450 ΩZin (16 mA) = 400 ΩZin (20 mA) = 370 Ω
R1
CW
3.74K
-15 VDC
200K
47.5K
R4
C1
10K
R6
10K
R5U1A 1
R27.5K R7
20KC2
1.2/25SPAN
5K
R10+15 VDC
47/25
P1-7
1K
47/2
R1351K
FEEDBACKPOTENTIOMETER
1000 ohm
ZERO
C6
10/25
-15 VDC
+15 VDC
5KR11
150K
R12
LM7815BT-
U5LM7915BT-
.1/25
C111.2/
R16
R17
R18
2M 3.3
1/21%2.5%6%
R939K
1N4454 CR1
7.15KR20
2N440
30.1KR2
CR31N445
CR41N4454
-15 VDC7.15K
1N445Q22N4401
R2830.1K
1%
21
LM1558
10K
U2A
C13.022/25
2.2M CR51N445
5 U2
R2610K
7
LM15
R210K
R210K
CR1N44
OH
CW
GAINR295K
.22/25
.22/25
INPUTCIRCUIT
C12
+15 V
C7
R155.1K
P1-2
P1-1CR171N40
1N40
C8200/
200/
HLMP47
+15 VDC
-15 VDC
CW
Controller
Deadband
Close Command
Open Command
-15 VDC
18 VAC
P1-6
P1-5
-15 VDC
(Page 30)
+15 VDC
AnalogInverter
Input Impedance (Zin)Zin (4 mA) = 850 ΩZin (8 mA) = 550 ΩZin (12 mA) = 450 ΩZin (16 mA) = 400 ΩZin (20 mA) = 370 Ω
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
0
Figure 9.1 – Modutronic 20 II Schematic Diagram (continued)
RESET
CONT V
4
TRIG
R38
R350K
C133/25
56
8
THOL
OU37
1DISC
+15 VDC
U7
9U6A1
4023
+15 VDC
R46
65
40231.5K
R52
JP1
3
12
U6C
13
11
40231.5K
+15 VDC
10K
10K
R50
1.5K
R49+15 VDC
4N2
U8
249.9 K1%
R59
To customer's 4-20 mA signal
To input circuit (Page 29)
CR12
1N44
Jumper pins 1 to 2 for lock in last positionJumper pins 2 to 3 for fail to 4ma position
NOTE:
CLOSELED
+15 VDC
200,1K
COUPLERS:MAX I
MOC3010
OUTPU TTRIAC
Q4010L4
U11
U12
U9
U10
C1.01/
R3510K
5K
100,1K
R5
100,1K
R61200K
R60
C160.04
0.04
C2.01/
P1-3 P1-4
LED4
+15 VDC
P1-10
P1-8
(+)
7.1K
756
LM15510K
U1
470K
R39
CR11MBR03
R338.25K
+15 VDC
12
LM1558U3
8
+15 VDC
-15 VDC
CR13
1N445
CR1
1N44
20K
R4CR9
1N44 221K C14.22/25
756
LM1558
CR15
1N445
CR1
1N44
20K
R43CR1
1N44221K
R48
C15.22/2
150K
R42
7.5K
R44
-15 VDC
R447
10K
R4
Signal DetectorPulseControl
P1-9
Close Enable
Open Enable
Pulse, if error is withinproportional band
Open Command
Close Command
Off Time
On Time
ProportionalBand Detector
SignalStatus
Input Impedance (Zin)Zin (4 mA) = 850 ΩZin (8 mA) = 550 ΩZin (12 mA) = 450 ΩZin (16 mA) = 400 ΩZin (20 mA) = 370 Ω
RESET
CONT V
4
TRIG
R38
R350K
C133/25
56
8
THOL
OU37
1DISC
+15 VDC
U7
9U6A1
4023
+15 VDC
R46
65
40231.5K
R52
JP1
3
12
U6C
13
11
40231.5K
+15 VDC
10K
10K
R50
1.5K
R49+15 VDC
4N2
U8
249.9 K1%
R59
To customer's 4-20 mA signal
To input circuit (Page 29)
CR12
1N44
Jumper pins 1 to 2 for lock in last positionJumper pins 2 to 3 for fail to 4ma position
NOTE:
CLOSELED
+15 VDC
200,1K
COUPLERS:MAX I
MOC3010
OUTPU TTRIAC
Q4010L4
U11
U12
U9
U10
C1.01/
R3510K
5K
100,1K
R5
100,1K
R61200K
R60
C160.04
0.04
C2.01/
P1-3 P1-4
LED4
+15 VDC
P1-10
P1-8
(+)
7.1K
756
LM15510K
U1
470K
R39
CR11MBR03
R338.25K
+15 VDC
12
LM1558U3
8
+15 VDC
-15 VDC
CR13
1N445
CR1
1N44
20K
R4CR9
1N44 221K C14.22/25
756
LM1558
CR15
1N445
CR1
1N44
20K
R43CR1
1N44221K
R48
C15.22/2
150K
R42
7.5K
R44
-15 VDC
R447
10K
R4
Signal DetectorPulseControl
P1-9
Close Enable
Open Enable
Pulse, if error is withinproportional band
Open Command
Close Command
Off Time
On Time
ProportionalBand Detector
SignalStatus
Input Impedance (Zin)Zin (4 mA) = 850 ΩZin (8 mA) = 550 ΩZin (12 mA) = 450 ΩZin (16 mA) = 400 ΩZin (20 mA) = 370 Ω
1
Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06
flowserve.com
flowserve.com
To find your local Flowserve representative:
FormoreinformationaboutFlowserveCorporation,visitwww.flowserve.comorcallUSA18002256989
FlowserveCorporationhasestablishedindustryleadershipinthedesignandmanufactureofitsproducts.Whenproperlyselected,thisFlowserveproductisdesignedtoperformitsintendedfunctionsafelyduringitsusefullife.However,thepurchaseroruserofFlowserveproductsshouldbeawarethatFlowserveproductsmightbeusedinnumerousapplicationsunderawidevarietyofindustrialserviceconditions.AlthoughFlowservecan(andoftendoes)providegeneralguidelines,itcannotprovidespecificdataandwarningsforallpossibleapplications.Thepurchaser/usermustthereforeassumetheultimateresponsibilityforthepropersizingandselection,installation,operation,andmaintenanceofFlowserveproducts.Thepurchaser/usershouldreadandunderstandtheInstallationOperationMaintenance(IOM)instructionsincludedwiththeproduct,andtrainitsemployeesandcontractorsinthesafeuseofFlowserveproductsinconnectionwiththespecificapplication.
Whiletheinformationandspecificationscontainedinthisliteraturearebelievedtobeaccurate,theyaresuppliedforinformativepurposesonlyandshouldnotbeconsideredcertifiedorasaguaranteeofsatisfactoryresultsbyreliancethereon.Nothingcontainedhereinistobeconstruedasawarrantyorguarantee,expressorimplied,regardinganymatterwithrespecttothisproduct.BecauseFlowserveiscontinuallyimprovingandupgradingitsproductdesign,thespecifications,dimensionsandinformationcontainedhereinaresubjecttochangewithoutnotice.Shouldanyquestionariseconcerningtheseprovisions,thepurchaser/usershouldcontactFlowserveCorporationatanyoneofitsworldwideoperationsoroffices.
©2006FlowserveCorporation,Irving,Texas,USA.FlowserveisaregisteredtrademarkofFlowserveCorporation.
UnitedStatesLimitorque5114WoodallRoadP.O.Box11318Lynchburg,VA24506-1318Phone:434-528-4400Facsimile:434-845-9736www.limitorque.com
UnitedKingdomLimitorqueAbexRoadNewburyBerkshire,RG145EYEnglandPhone:44-1-635-46999Facsimile:44-1-635-36034
JapanLimitorqueNipponGearCo.,Ltd.Asahi-SeimeiBldg.4thFloor1-11-11Kita-Saiwai,Nishi-KuYokohama-Shi,(220-0004)JapanPhone:81-45-326-2065Facsimile:81-45-320-5962
IndiaLimitorqueIndia,Ltd.15/4,MileStoneMathuraRoadFaridabad121002IndiaPhone:91-129-2276586Facsimile:91-129-2277135
AustraliaFlowserveAustralia,Pty.Ltd.14DalmoreDriveScoresby,Victoria3179AustraliaPhone:61397593300Facsimile:61397593301
SingaporeLimitorqueAsia,Pte.,Ltd.12,TuasAvenue20Singapore638824Phone:65-6868-4628Facsimile:65-6862-4940
FCDLMENIM4002-00 PrintedinUSA. (Replaces401-12000)