Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface (6EP1931-2DC31) 6A with USB interface (6EP1931-2DC42) 15A with serial interface (6EP1931-2EC31) 15A with USB interface (6EP1931-2EC42) 40A with USB interface (6EP1931-2FC42) 500S (15A / 2.5kWs capacitor) (6EP1933-2EC41) 500S (15A / 5kWs capacitor) (6EP1933-2EC51) Release 1.0

Upload: phungnhu

Post on 18-Jul-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Page 1 of 30

User Instructions

SITOP DC UPS Software

“Application”

for SITOP DC UPS Modules

6A with serial interface (6EP1931-2DC31) 6A with USB interface (6EP1931-2DC42) 15A with serial interface (6EP1931-2EC31) 15A with USB interface (6EP1931-2EC42) 40A with USB interface (6EP1931-2FC42) 500S (15A / 2.5kWs capacitor) (6EP1933-2EC41) 500S (15A / 5kWs capacitor) (6EP1933-2EC51)

Release 1.0

Page 2: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Page 2 of 30

Contents 1. Download SITOP DC UPS Software.........................................................................3 2. Installation of Application ..........................................................................................4 2.1. Basic Installation ...................................................................................................4 2.2. Installation USB Drivers ......................................................................................11 2.3. Update USB Drivers ............................................................................................15 3. Program Operation..................................................................................................17 3.1. Program Start ......................................................................................................17 3.2. Configuration .......................................................................................................18 3.3. SITOP DC UPS Monitoring .................................................................................23 3.4. Protocol Window .................................................................................................24 3.5. Logfile..................................................................................................................25 3.6. Further Settings...................................................................................................26 4. OPC Server .............................................................................................................27 4.1. Manual Registration of OPC Server ....................................................................27 4.2. Description of OPC Server Interface ...................................................................28 5. Help and Support ....................................................................................................29

Page 3: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

1. Download SITOP DC UPS Software

Software download from our homepage (www.siemens.com/sitop).

Page 3 of 30

Page 4: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

2. Installation of Application

2.1. Basic Installation Execute file “Setup_Sitop_3.x.2.x.exe“.

Select your language.

Installation is started.

Page 4 of 30

Page 5: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Accept the license agreement.

Page 5 of 30

Page 6: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Select the program components required. For installation as application the components “Application” and “Driver“ (when using a USB connection) are required.

Page 6 of 30

Page 7: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Choose the destination folder in which to instal the program packages.

Page 7 of 30

Page 8: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Select a start menu folder, if you would like to create an entry there.

Page 8 of 30

Page 9: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Typical settings of the SITOP software can be preset here: • Communication interface • Location of logfile (please note: write permission is required) • Service actions in UPS buffer mode (mains failure) • Automatic installation of OPC server interface (see chapter 4)

Page 9 of 30

Page 10: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Completion of installation.

Page 10 of 30

Page 11: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

2.2. Installation USB Drivers The installation of drivers is only required for versions with USB interface. Before starting the installation please make sure that the SITOP DC UPS software (freeware download under www.siemens.de/sitop) is installed completely. Then connect the SITOP DC UPS module with a free USB interface. The SITOP DC UPS module is now identified automatically, the hardware wizard opens:

Page 11 of 30

Page 12: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Select “Install software from a list or specific location”. Click “Next“ to continue. In the next window you choose the location from where the driver will be installed, normally: ”C:\Program Files\Sitop\DRIVER“. If you have installed the SITOP DC UPS software in a different location, please enter it in the browse field. Click “Next” to continue.

Page 12 of 30

Page 13: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Please acknowledge the following warning with a click on “Continue Anyway“.

In the next window you complete the driver installation with a click on “Finish“.

Page 13 of 30

Page 14: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Following the same steps, the driver for a new serial COM port is installed.

In this window you complete the driver installation with a click on “Finish“. The driver for the SITOP DC UPS module is now installed successfully. Yon can control in the device manager whether the SITOP DC UPS module has been identified correctly:

Page 14 of 30

Page 15: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

2.3. Update USB Drivers For the correct function of the SITOP DC UPS software it is necessary to install an up-to-date USB driver. From driver version 2.2.4.0 upwards this is guaranteed. If an older driver is installed already, an update of the USB driver has to be made. Before starting the driver update please make sure that the SITOP DC UPS software (freeware download on www.siemens.de/sitop) is installed completely. Search the entry ”SITOP xx“ in the folder “USB controllers” of the device manager. Mark the entry and by clicking the right mouse button open the context menu “Properties“. Here you can check the driver version.

Page 15 of 30

Page 16: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

If the driver version is less than 2.2.4.0, an update has to be made. In order to do this please activate the button “Update Driver“. Then continue as described in chapter 2.2, “Installation USB drivers”.

Page 16 of 30

Page 17: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

3. Program Operation

3.1. Program Start

Double click on ”SITOP_DC_USV.exe.

On the first program start the language selection opens.

Page 17 of 30

Page 18: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

3.2. Configuration

• Selection of communication interface (COM or USB) • Option for display of monitoring window on status change (optionally after a time

that can be set) • Option for an acoustic signal on status change

• Selection of location of logfile (write permission required!)

• Option for sending a signal on manual Windows shutdown (latching shutdown of

SITOP DC UPS module; only available when communicating via USB of the following versions: 6EP1931-2DC42; 6EP1931-2EC42 und 6EP1931-2FC42)

• Option for saving the configuration with write protection

Page 18 of 30

Page 19: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

• Option for starting an application after a set time when buffering

(example: *.exe, *.bat, *.vbs or *.js) • Option for PC shutdown after a set time when buffering (note: if the mains

voltage returns during the set time, the PC will NOT shut down)

• Option for signalizing the DC UPS on Windows shutdown (remote off)

Page 19 of 30

Page 20: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

• Option for starting an application after a set time at ALARM (buffer not ready), (example: *.exe, *.bat, *.vbs or *.js)

• Option for starting an application after a set time at interrupted data communication (example: *.exe, *.bat, *.vbs or *.js)

Page 20 of 30

Page 21: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

• Option for starting an application after a set time at recommended “battery replacement depending on aging“ (example: *.exe, *.bat, *.vbs oder *.js)

Page 21 of 30

Page 22: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

• Option for starting an application after a set time at reaching battery charge >85% (battery fully charged), (example: *.exe, *.bat, *.vbs oder *.js)

• Option for starting an application after a set time at falling below battery charge

>85% (battery not fully charged), (example: *.exe, *.bat, *.vbs oder *.js)

Page 22 of 30

Page 23: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

3.3. SITOP DC UPS Monitoring

Display of version number Display of SITOP DC UPS module connected Display of operating states in accordance with the LEDs on the SITOP DC UPS module

• DC o.k. • Alarm • Normal mode / buffer mode • Battery charge condition

Buttons:

opens configuration menu

opens protocol window

opens additional window with received data words

minimizes monitor window to system tray, can be displayed again by clicking the right mouse button

Page 23 of 30

Page 24: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

3.4. Protocol Window The protocol window opens after clicking the button “Protocol“.

Display protocol file, all events are registered here with timestamp. Button:

opens logfile with Windows editor

Page 24 of 30

Page 25: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

3.5. Logfile

In the logfile all events are registered and made available for later evaluation.

Page 25 of 30

Page 26: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

3.6. Further Settings

In the “SITOP_DC_USV.INI“ file further individual program settings can be made.

Page 26 of 30

Page 27: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

4. OPC Server The SITOP DC UPS software “Application” has an integrated OPC server interface. This software interface allows access to information sent by the SITOP DC UPS module out of own applications.

4.1. Manual Registration of OPC Server Before the OPC server interface can be used, it is necessary to register the SITOP DC UPS software in the operating system. If this was not effected during installation, the OPC server can also be registered manually. On clicking the Windows buttons “Start“ -> “Run...“ the following window opens:

As destination the path has to be selected where the program file “SITOP_DC_UPS.exe“ – unpacked in step “Basic Installation“ - is located. The OPC server can be removed by following the same steps, using the parameter “-unregserver“.

Page 27 of 30

Page 28: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Page 28 of 30

4.2. Description of OPC Server Interface Addressing the OPC server interface implicates an automatic start of the SITOP DC UPS software “Application“. Note: On starting the program a stable data connection to the SITOP DC UPS module is built up. This process may last a few seconds. A resulting possible delay of data availability at the OPC server interface must be taken into account. Sitop DC UPS OPC server - name: SITOP_UPS.OPC Sitop DC UPS OPC server – available items: Table1: Item name Type Description AKKU

Bool – active: battery exchange required

ALARM

Bool – active: buffer not ready

BAT

Bool – active: buffer mode

BAT85

Bool – active: battery fully charged

DC_OK Bool – active: input voltage o.k.

Variables describing the status of the SITOP UPS. “True” corresponds to the active LED on the device.

Connection Longint Status: 0 – no connection 1, 2 – connection available Status changes between 1 and 2 for monitoring connection

Status Longint Binary-coded status word, see table 2

Device String Type of connected device (example.: SITOP DC UPS 40)

last_Message String Last message/ logfile entry Received String Last telegram from UPS

Page 29: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Table 2: Coding status word The status word consists of 2 bytes, always 4 bits belonging to a LED of the SITOP UPS. Bits Correlation Status binary Description 0-3 Battery charge 1000

0010

Battery not fully loaded Battery fully loaded

4-7 Input voltage 1000 0010

No input voltage Input voltage available

8-11 Buffer mode 1000 0100

Normal mode Buffer mode

12-15 Alarm 1000 0001 0100

No alarm Buffer not ready Battery replacement required (LED flashing)

5. Help and Support

Further information is available in “ReadMe.rtf“.

Page 29 of 30

Page 30: User Instructions SITOP DC UPS Software “Application” · Page 1 of 30 User Instructions SITOP DC UPS Software “Application” for SITOP DC UPS Modules 6A with serial interface

Page 30 of 30

Note: The information provided in these user instructions contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. Technical specifications are subject to change without prior notice, errors excepted. © Siemens AG, 2008 Industry Sector, Industry Automation SE IP Postfach 2355, D-90713 Fürth