QUANTUMINVERTER HEAT PUMPDUCTLESS SPLIT SYSTEM
USER MANUAL
WIN09H1V51 WIN12HV51 WIN09H2V51 WIN12H2V51 WIN18H2V51 WIN24H2V51
WARNING
• The information contained in the manual is intended for use by a qualified service technicianfamiliar with safety procedures and equipped with the proper tools and test instruments• Installation or repairs made by unqualified persons can result in hazards to you and others.• Failure to carefully read and follow all instructions in this manual can result in equipmentmalfunction, property damage, personal injury and/or death.• This service is only for service engineer to use.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL
Contents
Remote controller operating instructions. See" remote controllerinstructions".
w w w . i n n o v a i r . c o m
Safety Precaution ...............................................................................
Safety Instructions .............................................................................
Preparation ..........................................................................................
Front Panel Maintenance .................................................................
Model Reference ...............................................................................
System Diagram .................................................................................
Display Introduction ..........................................................................
Protection ............................................................................................
Installation Guide ..............................................................................
Wiring Diagram ..................................................................................
Air Purging ..........................................................................................
Start-Up ................................................................................................
Troubleshooting .................................................................................
Spare Parts List ..................................................................................
1
3
4
5
6
7
8
9
10
17
24
25
26
35
INNOVAIR QUANTUM INVERTER WIRING DIAGRAM
To prevent personal injury, or property or unit damage, adhere to all precautionary measures and instructions outlined in this manual. Before servicing a unit, refer to this service manual and its relevant sections.
Failure to adhere to all precautionary measures listed in this section may result in personal injury, damage to the unit or to property, or in extreme cases, death.
WARNING indicates a potentially hazardous situation which if not avoided could result in serious personal injury, or death.
CAUTION indicates a potentially hazardous situation which if not avoided could result in minor or moderate personal injury, or unit damage.
1. In case of Accidents or Emergency
WARNING
• If a gas and ventilate the area if a gas leak is suspectedbefore turning the unit on.
• If strange sounds or smoke is detected from the unit,
cable. • If the unit comes into contact with liquid, contact an
authorized service center. • If liquid from the batteries makes contact with skin or
clothing, immediately rinse or wash the area well withclean water.
• Do not insert hands or other objects into the air inletor outlet while the unit is plugged in.
• Do not operate the unit with wet hands. • Do not use a remote controller that has previously
been exposed to battery damage or battery leakage.
CAUTION
• Clean and ventilate the unit at regular intervals whenoperating it near a stove or near similar devices.
• Do not use the unit during severe weather conditions.If possible, remove the product from the windowbefore such occurrences.
2. Pre-Installation and Installation
WARNING
• Use this unit only on a dedicated circuit.• Damage to the installation area could cause the unit
to fall, potentially resulting in personal injury, prop-erty damage, or product failure.
•remove, or repair the unit.
•work. For more information, contact your dealer,seller, or an authorized Innovair service center.
CAUTION
• While unpacking be careful of sharp edges around-
denser and evaporator.
3. Operation and Maintenance
WARNING
• Do not use defective or under-rated circuit breakers. • Ensure the unit is properly grounded and that a
dedicated circuit and breaker are installed. • Do not modify or extend the power cable. Ensure
the power cable is secure and not damaged duringoperation.
• Do not unplug the power supply plug duringoperation.
•unit.
• Do not open the inlet grill of the unit duringoperation.
•equipped with one.
•• Do not use harsh detergents, solvents, or similar items
to clean the unit. Use a soft cloth for cleaning. • Do not touch the metal parts of the unit when
• Do not step on or place anything on the unit oroutdoor units.
• Do not drink water drained from the unit • Avoid direct skin contact with water drained from the
unit. •
manufacturer procedures when cleaning ormaintaining the unit.
CAUTION
• Do not install or operate the unit for an extendedperiod of time in areas of high humidity or in anenvironment directly exposing it to sea wind or saltspray.
• Do not install the unit on a defective or damagedinstallation stand, or in an unsecure location.
• Ensure the unit is installed at a level position • Do not install the unit where noise or air discharge
created by the outdoor unit will negatively impact theenvironment or nearby residences.
• Do not expose skin directly to the air discharged bythe unit for prolonged periods of time.
• Ensure the unit operates in areas water or otherliquids.
• Ensure the drain hose is installed correctly to ensureproper water drainage.
• When lifting or transporting the unit, it isrecommended that two or more people are used forthis task.
• When the unit is not to be used for an extended time,
1
Safety Precaution
INNOVAIR QUANTUM INVERTER SAFETY PRECAUTION
w w w . i n n o v a i r . c o m 2
Be sure not to do.
ºPay attention to such a situation.
Safety Precaution
Grounding is essential.
Warning: Incorrect handling couldcause a serious hazard,
Symbols in this Use and Care Manual are interpreted as shown below.
Do not use the power supply circuitbreaker or pull off the plug to turn it offduring operation. This may cause a firedue to spark, etc.
Keep the power supply circuit breaker or plug from dirt. Connect the power supply cord to it firmly and correctly, lest an electric shock or a fire break out due to insufficient contact.
Use correct power supply inaccordance with the rating platerequirement. Otherwise, seriousfaults or hazard may occur or afire maybe break out.
Do not knit, pull or press the power supply cord, lest the power supply cord be broken.An electric shock or fire is probably causedby a broken power supply cord.
Never insert a stick or similar obstacleto the unit. Since the fan rotates at highspeed, this may cause an injury.
Do not repair the appliance by yourself.If this is done incorrectly, it may cause anelectric shock, etc.
Turn off the appliance by remote controlfirstly before cutting off power supply ifmalfunction occurs.
It is harmful to your health if the cool airreaches you for a long time. It is advisableto let the air flow be deflected to all the room.
Prevent the air flow from reaching the gasburners and stove.
Do not touch the operation buttonswhen your hands are wet.
Do not put any objects on the outdoorunit.
It is the user's responsibility to make theappliance be grounded according to local codes or ordinances by a licenced technician.
OFF OFF
ONON
ON/OFF
MODE FAN
SWING SLEEP SUPER
SMART IFEEL DIMMER
TIMER ON TIMER OFF CLOCK
OONN
O OFFFF
INNOVAIR QUANTUM INVERTER SAFETY INSTRUCTIONS
3
T 3.15A 250V T 20A 250V
A residual current device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule Warning: Risk of electric shock can cause injury or death: Disconnect all remote electric power supplies before servicing . The best length of the connecting pipe between the indoor unit and outdoor unit is less than 7.5 meters(24.6ft). It will affect the efficiency of the air conditioner if the distance longer than that length.This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. The batteries in remote controller must be recycled or disposed of properly. Disposal of Scrap Batteries --- Please discard the batteries as sorted municipal waste at the accessible collection point. If the appliance is fixed wiring, the appliance must be fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.The appliance shall be installed in accordance with local electrical safety regulations and National Electrical Codes(NEC). The air conditioner must be installed by professional or qualified persons. The appliance shall not be installed in the laundry.
Model
9K-12K(208/230V)
Fuse of Indoor unit
18K(208/230V)24K-36K(208/230V)
Fuse ot outdoor unit
T 3.15A 250V T 3.15A 250V
To guarantee the unit work normally, please read the manual carefully before installation, and try to install strictly according to this manual.
Do not let air enter the refrigeration system or discharge refrigerant when moving the airconditioner.
Properly ground the air conditioner into the earth. Check the connecting cables and pipes carefully, make sure they are correct and firm before
connecting the power of the air conditioner. There must be an air-break switch. After installing, the consumer must operate the air conditioner correctly according to this
manual,keep a suitable storage for maintenance and moving of the air conditioner in the future.
The Fuse of the unit:
T 3.15A 250V 12K(115V) T 25A 250V T 3.15A 250V 9K(115V) T 20A 250V
T 15A 250V
T 30A 250V
Safety Instructions
INNOVAIR QUANTUM INVERTER PREPARATION
w w w . i n n o v a i r . c o m 4
Preparation before use
Note
Preset
Safeguarding the environmentThis appliance is made of recyclable or re-usable material. Scrapping must be carried out in compliance with local waste disposal regulations. Before scrapping it, make sure to cut off the mains cord so that the appliance cannot be re-used. For more detailed information on handling and recycling this product, contact your local authorities who deal with the separate collection of rubbish or the shop where you bought the appliance.
SCRAPPING OF APPLIANCE
• When charging refrigerant into the system, make sure to charge in liquid state,if therefrigerant of the appliance is R410A.Otherwise, chemical composition of refrigerant(R410A) inside the system may change and thus affect performance of the airconditioner.• According to the character of refrigerant (R410A,the value of GWP is 2088), thepressure of the tube is very high, so be sure to be careful when you install and repairthe appliance.• If the supply cord is damaged, it must be replaced by the manufacturer, its serviceagent or similarly qualified persons in order to avoid a hazard.• The air conditioner must be installed by a professional engineer.• The temperature of refrigerant circuit will be high, please keep the interconnectioncable away from the copper tube .
Before using the air conditioner, be sure to check and preset the following.• Remote Control presettingEach tim e after the remote control is replaced with new batteries or is energized, re motecontrol auto presetting heat pump.If the air conditioner you purchased is a Cooling Only one,heat pump remote controller can also be used.• Back-light function of Remote Control(optional)Hold down any button on remote control to activate the back light. It automatically shuts off10 seconds later.Note: Back-light is an optional function.
• Auto Restart PresettingThe air conditioner has an Auto-Restart function.
This marking indicates that this product should not be disposed with other household wastes throughout the North America. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased.
They can take this product for environmental safe recycling.
INNOVAIR QUANTUM INVERTER FRONT PANEL MAINTENANCE
5
• Air �lter maintenance
Cut off the power supply
Front panel maintenance
Turn off the appliancefirst before disconnectingfrom power supply.
Grasp position "a" andpull outward to remove thefront panel.
Wipe with a softand dry cloth.Use soft moisture clothto clean if the front panelis very dirty;
Never sprinkle water onto theindoor unit
Never use volatile substance such as gasoline or polishing powder to clean the appliance.
Reinstall and shut the front panel.Reinstall and shut the front panel bypressing position "b" downward.
1 2
1
3
2
3 4
5 6
Stop the appliance, cut off thepower supply and remove the airfilter. Clean and reinstall the air filter.
1. 0pen the front panel.2. Press the handle of the filter gently3. Grasp the handle and slide out the filter.
Close the front panel again.II Clean the air filter every two weeksIf the air conditioner operates In anextremely dusty environment.
It is necessary to clean the air filterafter using it for about 100 hours.
If the dirt is conspicuous,wash it with a solution ofdetergent in lukewarm water.After cleaning, dry well inshade.
INNOVAIR QUANTUM INVERTER MODEL REFERENCE
w w w . i n n o v a i r . c o m 6
Model Reference
Nomenclature
Indoor Unit Model Outdoor Unit Model Capacity (Btu/h) Power Supply
WIN09H1V51(I) WIN09H1V51(O) 9k 115V~, 60Hz, 1PhaseWIN12H1V51(I) WIN12H1V51(O) 12k
WIN09H2V51(I) WIN12H2V51(O) 9k
208/230V~, 60Hz, 1Phase
12kWIN12H2V51(I) WIN12H2V51(O)
WIN18H2V51(I) WIN18H2V51(O) 18k
WIN24H2V51(I) WIN24H2V51(O) 24k
W IN 12 H 2 V 5 11 2 3 4 5 6 7 8
1— BrandW = Quantum
2— System PerformanceIN = Inverter TypeE = Fixed Speed
3— Nominal Capacity09 = 9,000 BTU/H12 = 12,000 BTU/H18 = 18,000 BTU/H24 = 24,000 BTU/H
4—System TypeC = Cool Only H = Heat Pump5—Voltage1 = 115V/60Hz2 = 208~230V/60Hz4 = 220V/50Hz
6—Compressor TypeR = Fixed Rotary SpeedV = Variable Rotary Speed
7—Installation Kit Length0 = No Kit3 = 3M (10FT)5 = 5M (16FT)
8—Version1 = 1st Version
9—Unit Identification I = Indoor UnitO = Outdoor Unit
(I)9
Outdoor unit
INNOVAIR QUANTUM INVERTER SYSTEM DIAGRAM
7
The figures in this manual are based on the external view of a standard model.Consequently, the shape may differ from that of the air conditioner you have selected.
5. Pipes and PowerConnection Cord
6. Drain Hose
4. Front Panel
3. Horizontal Louvers
2. Air Filter
1. Remote Controller
ON/OFF
MODE
FANSWINGSLEEP
SUPER
SMART
IFEELDIMMER
TIMER ONTIMER OFF
CLOCK
OOOO
FFNN
FF
1
5
6
23
4
Part Name
System Diagram
Indoor unit
INNOVAIR QUANTUM INVERTER DISPLAY INTRODUCTION
w w w . i n n o v a i r . c o m 8
Display introduction
The symbols may be different from these models, but the functions are similar.
Display set temperature.It shows FC after 200 hours of usage as reminder to clean the filter.After filter cleaning press the filter reset button located on the indoor unit behind the frontpanel in order to reset the display.(optional)
Temperature indicator
Timer
Sleep
1
Timer indicatorIt lights up during set time.
Sleep indicatorIt lights up in sleep mode.
2
3
4
5
1
5
3
2
4
optional
optional
Signal Receptor
Smart WIFI indicatorIt lights up during WIFI is on.
Emergency button 6
6ON/OFF To let the AC run or stop by pressing the button.
6
INNOVAIR QUANTUM INVERTER PROTECTION
9
Protection
Features of HEATING mode
Preheat
At the beginning of the HEATING operation, the airflow from the indoor unit is discharged 2-5 minutes later.
Defrost
In HEATING operation the appliance will defrost (de-ice) automatically to raise efficiency. This procedure usually lasts 2-10 minutes. During defrosting, fans stop operation. After defrosting completes, it returns to HEATING mode automatically.
Note: Heating is NOT available for cooling only air conditioner models.
Noise pollutionOperating condition
The protective device maybe trip and stopthe appliance in the cases listed below.
HEATINGOutdoor air temperature is over 75℉(24℃)
COOLING
DRY
Outdoor air temperature is below 5℉(-15℃)
Room temperature is over 80.6℉(27℃)
Outdoor air temperature is over *115℉(46℃)
Room temperature is below 70℉(21℃)
Room temperature is below 64.5℉(18℃)
The protective device will work at following cases.
Restarting the unit at once after operation stops or changing mode during operation, you need towait 3 minutes.
If all operation has stopped, press ON/OFFbutton again to restart, Timer should be set again if it has been canceled.
Install the air conditioner at a place thatcan bear its weight in order to operate more quietly.
Install the outdoor unit at a place where the air discharged and the operation noise would not annoy your neighbors.
Do not place any obstacles in front of theair outlet of the outdoor unit lest it increasesthe noise level.
Features of protector
*For Tropical (T3) Climate condition models, the
temperature point is 131℉(55℃) instead of 109℉(43℃).The temperature of some products is allowed beyond therange. In specific situation, please consult the merchant.
If the air conditioner runs in COOLING or DRY mode withdoor or window opened for a long time when relative humidity is above 80%,dew may drip down from the outlet.
10
Installation Diagram
Above figure is only a simple presentationof the unit, it may not match the externalappearance of the unit you purchased.
Installation must be performed in accordance withthe national wiring standards by authorized personnel only.
INNOVAIR QUANTUM INVERTER INSTALLATION
w w w . i n n o v a i r . c o m
Distance from ceiling
Distance from wallshould be over 50mm/2in
Air intake distance from the wall should be over 250mm/10in
over 250mm/10in
air outlet distance from the wall
should be over 500mm/20in
should be over 200 mm/7.9in
Distance from the wallshould be over 50mm/2in
Distance from floor over 2.4m/8ft.
should be
Air intake distance from the wallshould be over 250mm/10in
INNOVAIR QUANTUM INVERTER INSTALLATION
11
Model Max. Allowable Tubing Length at Shipment (m/ft)
Limit of Tubing Length (m/ft)
Limit of Elevation Difference H (m/ft)
Required amount of additional refrigerant (g/m) (oz/ft)
9K-18K 5m (16.4ft) 15m (50Ft) 5m (16.4ft)
24K
30~36K
If the height or pipe length is out of the scope of the table, please consult the dealer.
20g/m (0.22oz/ft)
30g/m (0.32oz/ft)
40g/m (0.43oz/ft)
Site for Installing Outdoor Unit
Where it is convenient to install and well ventilated.Avoid installing it where flammable gas could leak.Keep the required distance apart from the wall.Keep the outdoor unit away from greasy dirt, vulcanization gas exit.
Avoid installing it by the roadside where there is a risk of muddy water.
A fixed base where it is not subject to increased operation noise.
Where there is not any blockage of the air outlet.
Site for Installing Indoor Unit
Where there is no obstacle near the air outlet and air can be easily blown to every corner. Where piping and wall hole can be easily arranged. Keep the required space from the unit to the ceiling and wall according to the installation diagram on previous page.Where the air filter can be easily removed. Keep the unit and remote controller 1m(3.28ft) or more apart from television, radio etc. keep as far as possible from fluorescent lamps.Do not put anything near the air inlet to obstruct it from air absorption. Install on a wall that is strong enough to bear the weight of the unit.Install in a place that will not increase operation noise and vibration.Keep away from direct sunlight and heating sources. Do not place flammable materials or combustion apparatuses on top of the unit.
Avoid installing under direct sunlight, in an aisle or sideway, or near heat sources and ventilation fans. Keep away from Outdoor unit is higher than indoor unitflammable materials, thick oil fog, and wet or uneven places.In case the pipe length is more than 7.5m(24.6ft), the refrigerant should be charged additionally, according to below table.
Outdoor unit
Indoor unit
Pipe length is20 meters(65.4ft) Max.
be
less
than
5m
(16.
4ft)
Hei
ght
shou
ld
Outdoor unit
Indoor unit
Pipe length is20 meters(65.4ft) Max.
Hei
ght
shou
ld
be
less
than
10m
(32.
8ft)
Indoor unit is higher than outdoor unit
LocationInstallation Site
5m (16.4ft)
5m (16.4ft)
15m (50Ft)
15m (50Ft)
5m (16.4ft)
5m (16.4ft)
12
After connecting the piping , install the drain hose. Then connect the power cords. After connecting, wrap the piping, cords and drain hose together with thermal insulation materials.
INNOVAIR QUANTUM INVERTER
Indoor Installation
INSTALLATION
w w w . i n n o v a i r . c o m
• Put the piping (liquid and gas pipe) and cables through the wall hole from outside or put them throughfrom inside after indoor piping and cables connection is complete to connect to the outdoor unit.• Decide whether to saw the unloading piece off in accordance with the piping direction.(as shown below)
1. Installing the Mounting Plate
Note: The shape of your mounting plate may be different from the one above, but the installation method is similar.Note: As the above figure shown, the six holes matched with tapping screw on the mounting plate must be used tofix the mounting plate, the others are prepared.
3. Indoor Unit Piping Installation
2. Drill a Hole for Piping• Decide the position of the hole for piping according to thelocation of mounting plate.• Drill a hole in the wall. The hole should tilt a littledownward toward outside.• Install a sleeve through the wall hole to keep the walltidy and clean.
• Decide an installing location for the mounting plate according to the indoor unit location and piping direction.• Keep the mounting plate horizontal with a horizontal ruler or dropping line.• Drill holes of 32mm in depth on the wall for fixing the plate.• Insert the plastic plugs to the hole, fix the mounting plate with tapping screws.• Inspect if the mounting plate is well fixed. Then drill a hole for piping.
Piping direction
1
2
3
4
Trough
Rubber plug
Drainhole Drainage
structure
Note: When installing the pipe at the directions 1,2 or 4, saw the corresponding unloading piece off the indoor unit base.
Unloadingpiece
Saw the unloading piece off along the trough
Mounting plate
Tapping screw
Indo
or
Outd
oor
Wall hole sleeve( hard polythene tube prepared by user)
5mm 0.2in(tilt downward)
INNOVAIR QUANTUM INVERTER INSTALLATION
13
Indoor Installation
• Piping Joints Thermal Insulation:Wrap the piping joints with thermalinsulation materials and then wrapwith a vinyl tape.
• Piping Thermal Insulation:a. Place the drain hose under the piping.b. Insulation material uses polythene foam over 6mm in thickness.
Note: Drain hose is prepared by user.
• Do not arrange the drain pipe in a way that leaves it twisted, stickingout or waving around. Do not immerse the end of it in water.
• If an extension drain hose is connected to the drain pipe, make sureto insulated when passing along the indoor unit.
• When the piping is directed to the right, piping, powerCord and drain pipe should be thermal insulated andfixed onto the back of the unit with a piping fixer.
Piping Connection:
a. Connect indoor unit pipes with two wrenches. Pay special attentionto the allowed torque as shown below to prevent the pipes, connectorsand flare nuts from being deformed and damaged.
b. Pre-tighten them with fingers at first, then use the wrenches.
NOTE:Dimensions are in “mm or inch” unless otherwise stated in the table.
Pipe sizeModel9K-18K
18K
24K-36K
24K-36K9K-12K
Liquid Side (φ6 or 1/4) 0.5 or 0 15~20N·m or 1~15ft-lbs 17 or 5/8 22 0.6 or 0.
22 0.6 or 0.
24 o 0.6 or 0 27 o 0.6 or 0.
30~35N·m or 22~26ft-lbs
50~55N·m or 37~41ft-l 30~35N·m or 22~26f
60~65N·m or 44~48ft-lb
Gas Side (φ9.53 or 3/8 )
Gas Side (φ12 or 1/2 ) Gas Side (φ16 or 5/8)
Liquid Side (φ9.53 or 3/8)
Torque Nut width Min.thickness
Thermal insulation
wrapped with vinyl type
Small pipe
Thermal insulation tube
Large pipe
Power cord
Drain hose(prepared by user)
A. Insert the pipe fixer to the slot. B. Press to hook the pipe fixer onto the base.
Base Base BasePiping fixer Piping fixer Hook here
Insert here
drainhose
drainhose
largepipe
largepipe
smallpipe
smallpipe
14
INNOVAIR QUANTUM INVERTER
Outdoor Installation
INSTALLATION
w w w . i n n o v a i r . c o m
Florida wind load requirements state that outdoor unit must be anchored to
concrete pad using four 3/8-in diameter power wedge bolt plus(or equivalent)
with 1-in diameter fender washers. Anchor bolts must be embedded into
3000 PSI minimum concrete at a distance of 4 1/2- in from any concrete edge. The concrete thickness must exceed 1.5 times the anchor depth.
The condensate drains from the outdoor unit when the unit operates in heating mode. In order not to disturb your neighbor and protect the environment, install a drain port and a drain hose to direct the condensate water. Just install the drain port and rubber washer to the chassis of the outdoor unit, then connect a drain hose to the port as the right figure demonstrates.
2. Install Ground Pad or Wall Hangers
1. Install Condensate Drain for Outdoor Unit
1.Determine proper location for outdoor unit.2.Follow all instructions provided by manufacturer for installing wall hangersrubber pad.3.Verify the wall hangers or rubber pad can safely support the weight of theoutdoor unit.4.Verify the wall hangers or rubber pad is level and meets all outdoordimensional clearance.5.Fix with bolts and nuts tightly on a flat and strong floor.If installed on the wall or roof, make sure to fix the supporter well to prevent itfrom shaking due to serious vibration or strong wind.
WARNING
Drain hose(prepared by user)
Washer
Drain port
Rubber pad (optional)
Place under the leg pedestal
INNOVAIR QUANTUM INVERTER INSTALLATION
15
Outdoor Installation
3. Piping Connections to Outdoor Unit
Service Valve Cover
Remove service valve cover( if provided) to access the servicevalves and refrigerant ports.Carefully bend and adjust length of refrigerant pipes to meetoutdoor unit service valves connection with proper tools toavoid kinks.Apply a small amount of refrigerant oil to the flare connectionon the refrigerant pipe.
Properly align piping and tighten flare nut using a standardwrench and a torque wrench as shown in the indoor piping section.
Carefully tighten flare nuts to correct torque level referring to thefollowing Torque Table:
Pipe diameter/inch(mm)
Nut Size/inch(mm)
Tightening Torque
ft-lbs N-m
1/4(6.35) 1/4(17) 11 to 15 15 to 20
3/8(9.5) 3/8(22) 22 to 26 30 to 35
1/2(12.7) 1/2(25) 37 to 41 50 to 55
5/8(15.9) 5/8(29) 44 to 48 60 to 65
Torque Table
Note: Over tightening may damage flare connections and cause leaks.
16
INNOVAIR QUANTUM INVERTER
Outdoor Installation
INSTALLATION
w w w . i n n o v a i r . c o m
• Indoor UnitConnect the power cord to the indoor unit by connectingthe wires to the terminals on the control board individuallyin accordance with the outdoor unit connection.Note: For some models, it is necessary to remove the cabinet toconnect to the indoor unit terminal.
• Outdoor Unit1) Remove the access door from the unit by looseningthe screw. Connect the wires to the terminals on thecontrol board individually as follows.2) Secure the power cord onto the controlboard with cable clamp.3) Reinstall the access door to the original positionwith the screw.
4) Use a recognized circuit breaker for 24K model betweenthe power source and the unit. A disconnecting device toadequately disconnect all supply lines must be fitted.
4. Connecting of the Cable
CAUTION1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method ofwiring, refer to the circuit diagram posted on the inside of the access door .2. Comfirm that the cable thickness is as specified in the power source specification.3. Check the wires and make sure that they are all tightly fastened after cable connection.4. Be sure to install an earth leakage circuit breaker in wet or moist areas.
Cable Specifications
Outdoor unit
The figures in this manual are based on the external view of a standard model. Consequently, the shapemay differ from that of the air conditioner you have selected.
Chassis
Cabinet
Front panel Terminal (inside)
Indoor unit
Wire Hole
Cable Cross Board
Attention: The plug must be accessible even after the installation of the appliance in case there is a need to disconnect it. If not possible, connect appliance to a double-pole switching device with contact separation of at least 3 mm placed in an accessible position even after installation.
capacity(Btuh) Power cord Power connecting cord
Type Normal cross-sectional areas Type Normal cross-
sectional areas
9K-12K(208/230V) SJ TW 3X16 AWG SJ TW 4X18 AWG
18K-24K(208/230V) SJ TW 3X14 AWG SJ TW 4X18 AWG
24K-36K(208/230V) SJ TW 3X12 AWG SJ TW 4X18 AWG
9K(115V) SJ TW 3X14 AWG SJ TW 4X18 AWG
12K(115V) SJ TW 3X12 AWG SJ TW 4X18 AWG
INNOVAIR QUANTUM INVERTER WIRING DIAGRAM
17
Wiring DiagramWarning: Before obtaining access to terminals, all supply circuits must be disconnected. Make sure that the color of the wires in the outdoor unit and terminal No. are the same as those of the indoor unit.
To power the Indoor unit, connect the power cord to the indoor unit by connecting the wires to the terminals on the control board individually in accordance with the outdoor unit connection.
The diagram is reference only, and the actual terminal shall prevail.
Terminal Indoor unit
1)) 208/230Outdoor unit
Terminal
Power connecting cord
Green
White
RedBlack1(N)
2(L)
3(SI)
Green
WhiteBla kRedc 1(N)
2(L)
3(SI)
Power supply
L1
L2
GN
WHT
BLK
Abbreviation Paraphrase
L1 LIVE 110V
L2 LIVE 110V
Power Supply (Outdoor Only) Abbreviation
Abbreviation Paraphrase
1(N) LIVE 110V
2(L) LIVE 110V
3(SI) SIGNAL
Power Connecting (Outdoor to Indoor) Abbreviation
GROUND
GROUND
w w w . i n n o v a i r . c o m
WIRING DIAGRAM
18
Wiring Diagram
INNOVAIR QUANTUM INVERTER
Terminal Indoor unit
2))115VOutdoor unit
Terminal
Power connecting cord
Green
White
RedBlack1(N)
2(L)
3(SI)
Green
White
RBlacked
1(N)
2(L)
3(SI)
Power supply
N
L
GN
WHT
BLK
Abbreviation Paraphrase
N NEUTRAL
L LIVE 110V
Power Supply (Outdoor Only) Abbreviation
Abbreviation Paraphrase
1(N) NEUTRAL
2(L) LIVE 110V
3(SI) SIGNAL
Power Connecting (Outdoor to Indoor) Abbreviation
GROUND
GROUND
The diagram is reference only, and the actual terminal shall prevail.
To power the Indoor unit, connect the power cord to the indoor unit by connecting the wires to the terminals on the control board individually in accordance with the outdoor unit connection.
INNOVAIR QUANTUM INVERTER WIRING DIAGRAM
Wiring DiagramINDOOR UNIT
WIN09H1V51(I) ,, WIN12H1V51(I))
19
w w w . i n n o v a i r . c o m
WIRING DIAGRAM
Wiring DiagramINDOOR UNIT
WIN09H2V51(I),)WIN12H2V51(I),)WIN18H2V51(I))
INNOVAIR QUANTUM INVERTER
20
INNOVAIR QUANTUM INVERTER WIRING DIAGRAM
Wiring DiagramINDOOR UNIT
WIN24H2V51(I))
21
w w w . i n n o v a i r . c o m
WIRING DIAGRAM
Wiring DiagramOUTDOOR UNIT
WIN09H1V51(O) , WIN12H1V51(O))
INNOVAIR QUANTUM INVERTER
22
INNOVAIR QUANTUM INVERTER WIRING DIAGRAM
23
Wiring DiagramOUTDOOR UNIT
WIN09HV51(O) ,)WIN12H2V51(O) , )WIN18H2V51(O) , WIN24H2V51(O))
24
INNOVAIR QUANTUM INVERTER
Air Purging
AIR PURGING
w w w . i n n o v a i r . c o m
1. Unscrew and remove caps from 2 and 3-way valves.2. Unscrew and remove cap from service valve.3. Connect vacuum pump flexible hose to the service valve.4. Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.5. With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop
the vacuum pump.6. Open 2-way valve , 1/4 turn, then close it after 10 seconds. Check tightness of all joints using liquid
soap or an electronic leak detector.7. Turn 2 and 3-way valves stem to fully close the valves. Disconnect the flexible vacuum pump hose.8. Replace and tighten all valve caps.
The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor. After connecting the indoor and outdoor units, release air and moisture from the refrigerant cycle using a vacuum pump, as shown below.
Note: To protect the environment, be sure not to discharge the refrigerant to the air directly.
How to Purge Air Tubes:
Vacuum pump
valve cap
(1) Turn
(8) Tighten
(2) Turn
Refrigerant flow direction
3-way valve
(8) Tighten
(7) Turn to fully open the valve
(1) Turn
2-way valve
(6) Open 1/4 turn(7) Turn to fully open the valve
(8) Tighten
3-way valve diagram
connect to indoor unit
open position
spindle
service port cap
Service port
Connect to outdoor unit
Valve core
needle
indoor unit
Valve cap
INNOVAIR QUANTUM INVERTER START-UP
Installation Check List
Start-up
Test Operation
System Checks
Indoor Unit
Outdoor Unit
Perform test operation after completing gas leak and electrical safety check.1.Turn on electrical disconnect to outdoor unit.2.Push the “ON/OFF” button on Remote Controller to begin testing.3.Push MODE button, select COOLING, HEATING, FAN mode to confirm all functions.
1.Conceal refrigerant pipes where possible.2.Make sure drain hose slopes downward along entire length.3.Ensure all refrigerant pipes and connections are properly insulated.4.Fasten pipes to outside wall, when possible.5.Seal and weatherproof wall hole which the interconnecting wires and refrigerant pipes pass through.
1.Do all Remote controller’s buttons function properly?2.Do the display panel lights work properly?3.Does the swing louver function properly?4.Does the drain work?
1.Push the mode button to COOL and adjust the room setting to 61 deg. wait up to 3 minutes from compressor time guard. Does compressor and outdoor fan turn on in cooling mode?2.Push the mode button to HEAT and adjust the room setting to 85 �( 30�) deg. wait up to 3 minutes forcompressor time guard. Does compressor and outdoor fan turn on in heat mode?
�( 16� )
000022
25
w w w . i n n o v a i r . c o m
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
Trouble Analysis
Does not run
No cooling or heating air
Ineffective control
Does not operate immediately
Peculiar odor
A sound of flowing water
Cracking sound is heard
Spraying mist from the outlet
The compressor indicator lights on constantly,running indicator flashes and indoor fan stops.
The unit is shifting from heating mode to defrost.The indicator will light off and return to heating mode.
Is the air filter dirty?Are the intakes and outlets of the air conditioner blocked?Is the temperature set properly?
don't run
If the protector trip or fuse is blown,please wait
Check to see if the appliance is properly plugged in.The batteries in the remote control may be dead
3 minutes and start again.The may be preventing unit from working.
protector device
The following cases may not always be a malfunction, please check it before asking for service.
If there is strong interference (from excessivestatic electricity discharge or power supply voltageabnormality), the appliance may operate abnormally. Disconnect the power supply and connect back 2-3 seconds later.
Changing mode during operation,3 minutes will delay.
This odor may come from another source such as furniture, cigarette etc, which issucked in the unit and blows out with the air.
Caused by the flow of refrigerant in the air conditioner.Not a cause for concern.Sound of defrosting during heating mode.
The sound may be generated by the expansion or contraction of the front panel due to changeof temperature.
Mist appears when the air in the room becomes very cold. This is because of the cool air discharged from the indoor unit during COOLING or DRY modes.
Are doors or windows open?
000009
26
Troubleshooting
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
27
Error Code Indicators
1. Indication on the outdoor unit:When the unit has the following trouble and the compressor stops running, the LED of outdoor control board will show the error sequence automatically:NOTE: ★:LIGHT O:FLASH ×:OFFError code
Outdoor Failure Description LED1 LED2 LED3
The cause may be one of the following
Mark description: the lights flash every second for the following faults Normal � × � × � ×
Outdoor coil temperature sensor in trouble
★ ×� ★ a. the outdoor coil sensor connect is loose;b. the outdoor coil temperature sensor fails;c. the outdoor control board fails
Compressor exhaust temperature sensor in trouble
★ × ×
a. the compressor exhaust temperature sensorconnect is loose;b. the compressor exhaust temperature sensorfails;c. the outdoor control board fails
Communication failure between the indoor unit and outdoor unit
� × ×� O�
a. the communication cable connect is loose;b. the communication cable fails;c. the connection between the filter board and theoutdoor control board is incorrect or loose;d. the connection between the filter board and theterminal is incorrect or loose; e. the indoor control board fails;f. the PFC board fails;g. the power board fails;h. the outdoor control board fails.
Current overload protection ★ O� ×
a. the fan motor runs abnormally;b. the condenser and evaporator is dirty;c. the air inlet and outlet is abnormal
Maximum current protection ★ O� ★
a. the outdoor control board is short circuit;b. the drive board is short circuit;c. the other components is short circuit
Communication trouble between outdoor unit and driver
× ★ ★ a. the connection wires connect looseb. the outdoor board or drive board fails;
28
Error Code Indicators
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
w w w . i n n o v a i r . c o m
Outdoor EEPROM in trouble ★ ★ ★
a. the EEPROM chip is loose;b. the EEPROM chip is inserted with opposite direction;c. the EEPROM chip fails
Compressor exhaust temperature too high protection
×� O ★ a. the compressor exhaust temperature sensor fails;b. the refrigerant of the unit is not enough
Outdoor ambient temperature sensor in trouble
★ ★ ×
a. the outdoor ambient temperature sensor connect isloose;
ambient temperature sensor fails; b. the outdoor c. the outdoor control board fails
Compressor shell temperature too high protection
× ★ O a. the compressor exhaust temperature sensor connectis looseb. the refrigerant of the unit is not enough
Anti-freeze protection with cooling or overload protection with heating in indoor unit
� × � O � O
a. the indoor coil temperature sensor connect is loose;b. the indoor coil temperature sensor fails;
c. the indoor control board failsd. the refrigerant system is abnormal.
Compressor drive in trouble O � O
a. the outdoor drive board fails;b. the compressor fails
outdoor control board failsc. the
Outdoor fan motor locked rotor protection
O O ★
a. the connection of the outdoor fan motor is loose;b. there is something blocking the outdoor fan;c. the fan motor fails;d. the outdoor control board fails
Outdoor coil anti-overload protection with cooling
× ★ ×
a. the refrigerant is too much;b. the outdoor fan motor fails;c. the outdoor fan is broken;d. the condenser is dirty;e. the air inlet and air outlet of the indoor unitand the outdoor unit is not normal
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
29
Error Code Indicators
IPM module protection × O� ×�
a. The IPM board fails;b. The outdoor fan is broken;c. The outdoor fan motor fails;d. The outdoor fan has been blocked ;e. The condenser is dirty;f. The outdoor unit has been installed withoutstandard.
PFC protection O × ×� a. the PFC fails; b. theoutdoor drive board fails
Compressor pre heating process O ★ O it is normal mode in cold weather
Chip in outdoor board in trouble ★ × O a. Using the wrong drive board;
b. Using the wrong compressor.
AC voltage higher or lower protection
★ ★ O
a. the supply voltage is higher or lower thannormal;b. the inner supply voltage of the unit is higher orlower than normal
DC compressor start failure O O� × a. the outdoor drive board fails;
b. the compressor fails
Outdoor ambient temperature too low protection
★ O O� a. Outdoor ambient temperature too low
Mark description: the lights flash every two seconds for the following faults:
Protection against overheated outdoor radiator
Ο × × a. Radiator sensors failb. Detection circuit of the sensor on the controlpanel fails
Protection of the system against too high pressure
Ο Ο ×
a. The pressure switch failsb. The pressure detection switch on the controlpanel failsc. The measured value of the system pressureexceeds the limit
When the compressor is in operation: Mark description: ★:Light Ο:Flash ×:Off; the flash cycle is 1S No. LED1 LED2 LED3 Reasons for the current operating frequency
of the compressor are limited 1 Ο Ο Ο Normal frequency rising and decreasing, no
limitation 2 × × ★ Frequency decreasing or prohibition of
frequency rising caused by over-current
30
Error Code Indicators
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
w w w . i n n o v a i r . c o m
3 × ★ ★ Frequency decreasing or prohibition of frequency rising caused by anti-freezing of refrigeration or anti-overload in heating
4 ★ × ★ Frequency decreasing or prohibition of frequency rising caused by too high compressor discharge temperature
5 Limit to the max operating frequency caused by too low power voltage
6 ★ ★ ★ Operation at fixed frequency (in the case of capability measuring or compulsory operation at fixed frequency)
7 Ο × × Protective frequency decreasing against outdoor overload (overpower, over frequency conversion rate, over torque, detection of DC under-voltage)
8 ★ × × Frequency decreasing caused by indoor and outdoor communication fault
9 × ★ Ο Frequency decreasing or prohibition of frequency rising protection against overload of outdoor coiled pipe
10 × ★ × Frequency decreasing or prohibition of frequency rising for power-saving when it is being used simultaneously with other appliances
2. Indication by the indoor unit:2.1. The 7-segment tube of the indoor display board will show the error code
automatically when the unit has the following trouble:
Error code
Power Timer Running Sleep Remark:★Light o Flash x OFF
1 2 3 4 Content Remark The root cause is may be one of the following
EA
the error code will display when the communication between display board and control board is in trouble
a. The connection betweenthe display board andcontrol board is loose;b. The indoor control boardfails.c. The wiring of the displayboard fails.
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
31
Error Code Indicators
2.2. When the unit has the following trouble and the compressor stops running, press the sleep button on the remote controller 4 times in ten seconds and the 7-segment tube of the display board will show the error code as the following. If two malfunctions happened at the same time, you must press the sleep button 4 times again, and the LED will show the other error code.
Refer to the remote controller where the sleep key can set into 4 different combination ways (new design remote controller), when using to check the error codes only takes effect for pressing the sleep key 10 times in ten seconds instead of 4 times.
NOTE: If the troubleshooting inquiry display by 7-segment tube, then the error code will be displayed, otherwise only the LED of the display board will show.
Error code
Running Timer Sleep Power Remark:★Light o Flash x OFF
1 2 3 4 Content Remark The root cause is may be one of the following
0 Normal
1 x o x x
Failure of temperature sensor of outdoor coil
a. The outdoor temperaturesensor is loose;b. The outdoor temperaturesensor fails;c. The indoor control board fails
2
× Ο ★ ×
Compressor exhaust temperature sensor in trouble
a. the compressor exhausttemperature sensor connection isloose;b. the compressor exhausttemperature sensor fails;c. the outdoor control board fails
5
★ Ο × ×
IPM module protection
a. The IPM board fails;b. The outdoor fan is broken;c. The outdoor fan motor fails;d. The outdoor fan has beenblocked ;e. The condenser is dirty;f. The outdoor unit has beeninstalled without standard.
6
★ Ο × ★
AC voltage higher or lower protection
a. the supply voltage is higher orlower than normal;b. the inner supply voltage of theunit is higher or lower than normal
32
Error Code Indicators
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
w w w . i n n o v a i r . c o m
7
★ Ο ★ ×
Communication failure between the indoor unit and outdoor unit
a. the communication cableconnection is loose;b. the communication cable fails;c. the connection between the filterboard and the outdoor control boardis incorrect or loose;d. the connection between the filterboard and the terminal is incorrect orloose; e. the indoorcontrol board fails; f. the PFC board fails;g. the power board fails;h. the outdoor control board fails.
8
★ Ο ★ ★
Current overload protection
a. the fan motor runs abnormally;b. the condenser and evaporator aredirty;c. the air inlet and outlet is abnormal
9
× × Ο ×
Maximum current protection
a. the outdoor control board has shortcircuit;b. the drive board has short circuit;c. the other components have shortcircuit
10
× × Ο ★Communication trouble between outdoor unit and driver
a. the connection wires connect looseb. the outdoor board or drive boardfails;
11
× ★ Ο ×
Outdoor EEPROM in trouble
a. the EEPROM chip is loose;b. the EEPROM chip inserted withopposite direction;c. the EEPROM chip fails
12
× ★ Ο ★Outdoor ambient temperature too low protection
Outdoor ambient temperature too low
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
33
Error Code Indicators
13
★ × Ο × Compressor exhaust temperature too high protection
a. the compressor exhausttemperature sensor fails;b. the refrigerant of the unit is notenough
14
★ × Ο ★ Outdoor ambient temperature sensor in trouble
a. the outdoor ambient temperaturesensor connect is loose;b. the outdoor ambient temperaturesensor fails;c. the outdoor control board fails
15 ★ ★ Ο × Compressor
shell temperature too high protection
a. the compressor exhausttemperature sensor connect ion islooseb. the refrigerant of the unit is notenough
16
Anti-freeze protection with cooling or overload protection with heating in
a. the indoor coil temperature sensorconnect is loose;b. the indoor coil temperature sensorfails;c. the indoor control board failsd. the refrigerant system is abnormal.
17 PFC protection
a. the PFC fails;b. the outdoor drive board fails
18 DC compressor start failure
a. the outdoor drive board fails;b. the compressor fails
19 × × × Ο Compressor
drive in trouble
a. the outdoor drive board fails;b. the compressor failsc. the outdoor control board fails
20
★ × × Ο Outdoor fan motor locked rotor protection
a. the connection of the outdoor fanmotor is loose;b. there is something blocking theoutdoor fan;c. the fan motor fails;d. the outdoor control board fails
21
Outdoor coil anti-overload protection with cooling
a. the refrigerant is too much;b. the outdoor fan motor fails;c. the outdoor fan is broken;d. the condenser is dirty;e. the air inlet and air outlet of theindoor unit and the outdoor unit are notnormal
22 Compressor pre heating process
it is normal mode in cold weather
34
Error Code Indicators
INNOVAIR QUANTUM INVERTER TROUBLESHOOTING
w w w . i n n o v a i r . c o m
39 o x ★ ★Indoor fan motor run abnormally
a. There are something blocking theindoor fan motor;b. The fan motor cord connection isloose;c. The fan motor fails;d. The indoor control board fails
41 ★ ★ o ★Detecting failures by zero-crossing
The indoor control board fails
The failure is detected when the room temperature sensor broken or shorted over 5 sec. The failure is detected when the temperature sensor of heater exchange is broken or shorted over 5 sec.The failure is detected when each setting data is not a match after the EEPPOM self-check two times.The failure occurs when the grounding signal is not detected after the appliance is powered ON.
24 Chip in outdoor board in trouble
a. Using the wrong drive board;b. Using the wrong compressor.
26 Overheated outdoor radiator
a. Radiator sensor failsb. Detection circuit of the sensoron the control panel fails
27 Protection against too high system pressure
a. The pressure switch failsb. The pressure detection switchon the control panel failsc. The measured value ofsystem pressure exceeds thelimit
33 o x x ★
Failure of temperature sensor of indoor room
a. The indoor room temperaturesensor is loose;b. The indoor room temperaturesensor fails;c. The indoor control board fails.
34 o x ★ x
Failure of temperature sensor of indoor coil temperature
a. The indoor coil temperature sensoris loose;b. The indoor coil temperature sensorfails;c. The indoor control board fails.
36
Ο ★ × ★
Communication failure between the indoor unit and outdoor unit
a. the communication cableconnection is loose;b. the communication cable fails;c. the connection between the filterboard and the outdoor control boardis incorrect or loose;d. the connection between the filterboard and the terminal is incorrect orloose;e. the indoor control board fails;f. the PFC board fails;g. the power board fails;h. the outdoor control board fails.
38 o ★ ★ ★Indoor EEPROM failure
a. The EEPROM chip is loose;b. The indoor control board fails
INNOVAIR QUANTUM INVERTER SPARE PARTS LIST
35
WIN09H1V51(I))
SR PART CODE DESCRIPTION
1 1465666 baffle
2 1906605 installation plate assy
3 1856104 base holder part
4 1465662 Vertical Level Vane
5 1831008 level vane
6 1466013 cross-flow fan blade
7 1223739 bearing
8 1465670 baffle
9 1826755 Refrigeration system
10 1849430 ornamental part
11 1849418 shell12 1849432 ornamental part
13 1831006 panel
14 1874998 Display Component
15 1831007 decorative strip
16 1465756 motor guard
17 1487147 fan motor
18 1465757 motor cover
19 1260259 Step motor
20 1222824 axis sheath
21 4024474 Remote Controller
22 1465763 electric box cover
23 1387643 Temperature sensor
24 1471151 Temperature sensor
25 NA Power cord
26 1840039 electric box cover
27 1839902 Over clamp
28 1852126 Wire terminal board
29 1465761 elec joint box plate
30 1906584 Indoor Main Control Board Component
31 1868909 electric box
32 1465762 elec joint box plate
33 1470426 Water pipe parts
1505714 Filter net
36
SPARE PARTS LIST
w w w . i n n o v a i r . c o m
SR PART CODE DESCRIPTION
1 1832902 panel parts
2 1405123 propeller fan blade
3 1457759 fan motor
4 1824869 motor supporter
5 1824871 mounting plate
6 1824865 upper board
7 1824902 back guard
8 1855257 Condenser assembly
9 1854218 base holder part
10 1895382 clapboard
11 1302261 PFC inductance
12 1906761 4-way valve assembly
13 1258654 4-way valve
14 1906608 Four-way valve coil
15 1838380 Compressor
16 1822371 Compressor connect wire
17 1824870 valve seat
18 1838379 Capillary assembly
19 1258653 2-way valve
20 1407169 3-way valve
21 1855206 right side board
22 1854033 wiring distribution cover assy
23 1854034 fixed board
24 1916000 electric box
25 1843011 connecting board
26 1912060 Wire terminal board
27 1906357 Outdoor Main Control Board Component
28 1916001 electric box cover
29 1472663 Temperature sensor
30 1472664 Temperature sensor
31 1831029 Temperature sensor
INNOVAIR QUANTUM INVERTER
WIN09H1V51(O)
INNOVAIR QUANTUM INVERTER SPARE PARTS LIST
37
SR PART CODE DESCRIPTION
1 1906600 installation plate assy
2 1465666 baffle
3 1854463 base holder part
4 1465662 Vertical Level Vane
5 1555374 level vane
6 1466014 cross-flow fan blade
7 1223739 bearing
8 1465670 baffle
9 1512275 Refrigeration system
10 1465756 motor guard
11 1487147 fan motor12 1465757 motor cover
13 4065140 Remote Controller
14 1465763 electric box cover
15 1387643 Temperature sensor
16 1471151 Temperature sensor
17 1839902 Over clamp
18 1852126 Wire terminal board
19 1840039 electric box cover
20 1465761 elec joint box plate
21 1906584 Indoor Main Control Board Component
22 1868909 electric box
23 1465762 elec joint box plate
24 1470426 Water pipe parts
25 1222824 axis sheath
26 1260259 Step motor
27 1816270 shell
28 1874771 Display Component
29 1855066 ornamental part
WIN12H1V51(I)
38
SPARE PARTS LIST
w w w . i n n o v a i r . c o m
SR PART CODE DESCRIPTION
1 1832902 panel parts
2 1405123 propeller fan blade
3 1457759 fan motor
4 1824869 motor supporter
5 1824871 mounting plate
6 1824865 upper board
7 1824902 back guard
1824903 back guard
8 1854202 Condenser assembly
9 1832900 base holder part
10 1895382 clapboard
11 1302261 PFC inductance
12 1906478 4-way valve assembly
13 1258654 4-way valve
14 1906608 Four-way valve coil
15 1821191 Compressor
16 1822371 Compressor connect wire
17 1824870 valve seat
18 1821167 Capillary assembly
19 1258653 2-way valve
20 1407169 3-way valve
21 1855206 right side board
22 1854033 wiring distribution cover assy
23 1854034 fixed board
24 1916000 electric box
25 1843011 connecting board
26 1912060 Wire terminal board
27 1906358 Outdoor Main Control Board Component
28 1916001 electric box cover
29 1472663 Temperature sensor
30 1472664 Temperature sensor
31 1831029 Temperature sensor
INNOVAIR QUANTUM INVERTER
WIN12H1V51(O))
IINNOVAIR QUANTUM INVERTER SPARE PARTS LIST
39
SR PART CODE DESCRIPTION
2 1465666 baffle
3 1854463 base holder part
4 1465662 Vertical Level Vane
5 1555374 level vane
6 1466014 cross-flow fan blade
7 1223739 bearing
8 1465670 baffle
9 1823341 Refrigeration system
10 1465756 motor guard
11 1857574 fan motor
12 1465757 motor cover13 4062911 Remote Controller
14 1465763 electric box cover
15 1387643 Temperature sensor
16 1471151 Temperature sensor
17 1839902 Over clamp
18 1852126 Wire terminal board
19 1840039 electric box cover
20 1465761 elec joint box plate
21 1854801 Indoor Main Control Board Component
22 1868909 electric box
23 1465762 elec joint box plate
24 1470426 Water pipe parts
25 1222824 axis sheath
26 1260259 Step motor
27 1555389 shell
28 1874748 Display Component
29 1816271 panel
30 1817446 displey film pattern
WIN12H2V51(I)
40
SPARE PARTS LIST
w w w . i n n o v a i r . c o m
SR PART CODE DESCRIPTION
1 1832902 panel parts
2 1405123 propeller fan blade
3 1820938 fan motor
4 1824869 motor supporter
5 1824871 mounting plate
6 1824865 upper board
7 1824902 back guard
1824903 back guard
8 1854202 Condenser assembly
9 1832900 base holder part
10 1843005 clapboard
11 1343046 PFC inductance
12 1864878 4-way valve assembly
13 1258654 4-way valve
14 1511783 Four-way valve coil
15 1821191 Compressor
16 1822371 Compressor connect wire
17 1824870 valve seat
18 1821167 Capillary assembly
19 1258653 2-way valve
20 1407169 3-way valve
21 1855206 right side board
22 1854033 wiring distribution cover assy
23 1854034 fixed board
24 1918705 electric box
25 1843011 connecting board
26 1854383 Wire terminal board
27 1855422 Outdoor Main Control Board Component
28 1823292 electric box cover
29 1472663 Temperature sensor
30 1472664 Temperature sensor
31 1831029 Temperature sensor
INNOVAIR QUANTUM INVERTER
WIN12H2V51(O)
INNOVAIR QUANTUM INVERTER SPARE PARTS LIST
41
SR PART CODE DESCRIPTION
1 1541379 wiring distribution cover assy
2 1840141 Over clamp
3 1541500 elec joint box plate
4 1870720 electric box
5 1855041 Indoor Main Control Board Component
6 1541507 electric box cover
7 1837043 electric box cover
8 1858726 fan motor
9 1541374 motor cover
10 1541369 motor guard
11 1819726 Step motor12 1470426 Water pipe parts
13 1465670 baffle
14 1541361 baffle
15 1907022 installation plate assy
16 1953451 base holder part
17 1541365 Vertical Level Vane
18 1550294 Vertical Level Vane
19 1541362 level vane
20 1222824 axis sheath
21 1541370 baffle
22 1223738 bearing
23 1541622 cross-flow fan blade
24 1552313 Refrigeration system
25 1541381 shell
26 1541388 ornamental part
27 1541389 ornamental part
28 4062911 Remote Controller
29 1387643 Temperature sensor
30 1471151 Temperature sensor
31 1852126 Wire terminal board
33 1852126 Wire terminal board
34 1554307 Display Component
35 4062942 panel
36 1565617 ornamental part
WIN18H2V51(I)
42
SPARE PARTS LIST
w w w . i n n o v a i r . c o m
SR PART CODE DESCRIPTION
1 1847919 panel parts
2 1556766 propeller fan blade
3 1854829 fan motor
4 1849292 motor supporter assy
5 1846086 mounting plate
6 1846082 upper board
7 1854579 back guard
1854580 back guard
8 1854847 Condenser assembly
9 1850352 base holder part
10 1847982 clapboard
11 1513622 PFC inductance
12 1850547 4-way valve assembly
13 1511783 Four-way valve coil
14 1408045 4-way valve
15 1850482 Inverter compressor
16 1847142 Strong electricity connect wire
17 1854848 Capillary assembly
18 1844583 2-way valve
19 1844499 3-way valve
20 1846084 right side board
21 1854040 wiring distribution cover assy
22 1854034 fixed board
23 1842392 connecting board
24 1852124 Wire terminal board
25 1841985 electric box
26 1854308 Controller Component
27 1546706 electric box cover
28 1472663 Temperature sensor
29 1472664 Temperature sensor
30 1831029 Temperature sensor
31 1546721 sensor mounting plate
INNOVAIR QUANTUM INVERTER
WIN18H2V51(O)
INNOVAIR QUANTUM INVERTER SPARE PARTS LIST
43
SR PART CODE DESCRIPTION
1 1907022 installation plate assy
2 1918024 base holder part
3 1541457 level vane
4 1550294 Vertical Level Vane
5 1541363 level vane
6 1222824 axis sheath
7 1541633 cross-flow fan blade
8 1223738 bearing
9 1465670 baffle
10 1556041 Refrigeration system
11 1816294 shell12 1824935 Display Component
13 4065151 panel
14 1855126 ornamental part
15 1383891 Temperature sensor
16 1387643 Temperature sensor
17 1561456 fan motor
18 1541374 motor cover
19 1541373 motor guard
20 1541361 baffle
21 1541370 baffle
22 1470426 Water pipe parts
23 1819726 Step motor
24 1541500 elec joint box plate
25 1870720 electric box
26 1854882 Indoor Main Control Board Component
27 1541507 electric box cover
28 1837043 electric box cover
29 1852126 Wire terminal board
30 1840141 Over clamp
31 1541379 wiring distribution cover assy
32 4065140 Remote Controller
WIN24H2V51(I)
44
SPARE PARTS LIST
w w w . i n n o v a i r . c o m
SR PART CODE DESCRIPTION
1 1844019 panel parts
2 1841783 propeller fan blade
3 1841930 fan motor
4 1841749 motor supporter
5 1841772 mounting plate
6 1841779 upper board
7 1871792 back guard
1854661 back guard
8 1854467 Condenser assembly
9 1844016 base holder part
10 1841986 clapboard
11 1205797 PFC inductance
12 1851363 4-way valve assembly
13 1511783 Four-way valve coil
14 1408045 4-way valve
15 1830018 Compressor
16 1847142 Strong electricity connect wire
17 1854469 Capillary assembly
18 1849152 2-way valve
19 1849153 3-way valve
20 1841776 right side board
21 1854040 wiring distribution cover assy
22 1854034 fixed board
23 1842392 connecting board
24 1852124 Wire terminal board
25 1841985 electric box
26 1854505 Controller Component
27 1546706 electric box cover
28 1472663 Temperature sensor
29 1511780 Temperature sensor
30 1831029 Temperature sensor
31 1546721 sensor mounting plate
INNOVAIR QUANTUM INVERTER
WIN24H2V51(O)