user manual pvs-8mh-db/ pvs-12mh-db/pvs-16mh-db pv …

52
PVS-12MH_16MH-DB-V11-UEN-Ver10-201811 User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV Array Combiner Box

Upload: others

Post on 01-Nov-2021

24 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

PVS-12MH_16MH-DB-V11-UEN-Ver10-201811

User Manual

PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB

PV Array Combiner Box

Page 2: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …
Page 3: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

Contents

1 About This Manual .............................................................. 1

1.1 Contents .................................................................................... 1

1.2 Target Readers ......................................................................... 1

1.3 How to Use this Manual ............................................................ 1

1.4 Others ....................................................................................... 2

1.5 Symbol Explanation ................................................................... 2

1.6 Picture Explanation ................................................................... 4

2 Safety Instructions .............................................................. 5

3 Product Description ............................................................ 9

3.1 System introduction ................................................................... 9

3.2 Main features........................................................................... 10

3.3 Demonstration of the type ....................................................... 10

3.4 Dimensions ............................................................................. 11

3.5 Identifying the PVS .................................................................. 11

4 Mechanical Installation ..................................................... 13

4.1 Scope of Delivery .................................................................... 13

4.2 Installation site requirements ................................................... 14

4.3 Installation Tools ..................................................................... 14

4.4 Installing PVS .......................................................................... 15

4.4.1 Overview ................................................................................. 15

4.4.2 Fix the Hangers to PVS ........................................................... 15

4.4.3 Fixing PVS to Installation Surface ........................................... 16

Page 4: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation......................................................... 19

5.1 Internal structure ...................................................................... 19

5.2 Water-proof terminals .............................................................. 21

5.3 Wiring preparations .................................................................. 22

5.4 Connections ............................................................................. 23

5.4.1 Input connections .................................................................... 23

5.4.2 Output connections ................................................................. 27

5.4.3 Grounding connections ........................................................... 29

5.4.4 Communication Connections .................................................. 30

5.4.5 Cable Layout ........................................................................... 33

5.5 Communication settings ........................................................... 33

5.6 Start/Stop of operation ............................................................. 35

6 Commissioning................................................................. 36

7 Routine Maintenance ....................................................... 37

7.1 Replace the Fuse ..................................................................... 37

7.2 Replace the sealing strip .......................................................... 38

8 Troubleshooting ............................................................... 40

8.1 Before troubleshooting ............................................................. 40

8.2 Common faults and troubleshooting ........................................ 40

9 Appendix .......................................................................... 43

9.1 Technical data ......................................................................... 43

9.2 Quality Assurance .................................................................... 45

9.3 Contact Information.................................................................. 46

Page 5: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

1

1 About This Manual

1.1 Contents

Safety instructions

Safety instructions for the installation, operation, commissioning and

maintenance of PVS.

Product description

Location of PVS in the PV system, structure, function and classification.

Installation guide

The installation methods and electrical connections of PVS.

Routine maintenance

How to replace the fuses of PVS.

Others

Technical data of PVS, exclusion of liability and the way to contact us.

1.2 Target Readers

This manual is for users who operate the PVS or conduct the maintenance work.

The operators must be trained and qualified personnel.

1.3 How to Use this Manual

Read this manual and other related documents before installation of the PVS.

Page 6: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

1 About This Manual User Manual

2

Documents must be stored in a convenient place for future reference.

The contents of the manual will be periodically updated or revised due to the

product development. It is probably that there are changes of manual in the

subsequent converter edition.

1.4 Others

This document will take the PVS-16MH-DB for example. For the installation and

use of other types of combiner boxes, please also refer to this manual.

PVS-8MH-DB

PVS-12MH-DB

PVS-16MH-DB

The electrical structure, installation and use method of PVS-12MH-DB are the

same with that of PVS-16MH-DB. The only difference between them is the

numbers of DC input string.

1.5 Symbol Explanation

This manual contains important safety and operational instructions that must be

accurately understood and followed during the installation and maintenance of

the equipment.

To ensure optimum use of this manual, note the following explanations of

symbols used.

DANGER indicates a hazard with a high level of risk which, if not avoided,

will result in death or serious injury.

Page 7: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 1 About This Manual

3

WARNING indicates a hazard with a medium level of risk which, if not

avoided, will result in death or serious injury.

CAUTION indicates a hazard with a low level of risk which, if not avoided,

will result in minor or moderate injury.

NOTICE indicates a situation which, if not avoided, will result in equipment

malfunction or property damage.

NOTE indicates additional information, emphasized contents or tips

to help you solve problems or save time.

The following symbols on the device enclosure must be paid attention to.

Symbols Explanation

Risk of electric shock! If not avoided, lethal hazard can be caused.

Hot surface! Do not touch!

The symbol represents protective conductor terminal. The terminal

should be connected firmly to avoid potential injury or property

damage.

Page 8: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

1 About This Manual User Manual

4

1.6 Picture Explanation

Pictures used in this manual all take the PVS with standard configuration for

example.

The real PVS you received may differ from the example pictures in the numbers

of the installation hangers and etc. please refer to the actual product you

receive.

Page 9: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5

2 Safety Instructions

This chapter describes some important safety instructions about PVS.

Please read the manual carefully before installation. If any device damage

occurs when ignoring the safety instructions, our company has the right to

exclude all warranty claims.

Lethal Voltage!

Death resulting from burning and electric shock upon touching the live

components of the PVS.

Disconnect the end connection of the PV string before cable connection;

Do not use ordinary ammeter to measure the DC voltage before cable

connection. An ammeter with withstanding voltage of 1500V is

recommended. Serious consequences may follow if otherwise.

Observe all safety instructions required by the PV cell manufacturer.

Device damage or system fault may cause fire and electric shock!

Optical check the device for any possible damages or dangerous states

before operation.

Check if other external devices or circuit connection are in safe state.

Work on the device only when it is safe to do so.

Page 10: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

2 Safety Instructions User Manual

6

Death or burning hazard by touching the internal terminals of the device!

Do not touch the terminals or conductors in contact to the inverter or PV

string.

Observe all the instructions and safety regulations related to PVS

connection.

High voltage is present inside the device!

Follow all the warning signs in the device.

Respect all the safety instructions in this manual and other documents.

The ground cable must be grounded properly, otherwise,

lethal electric shock happens to the operator or installer once a fault

occurs.

device may be damaged after lightening stroke.

Incorrect cable connection may cause damages to the PV cells, the PVS and

inverter. Respect the following instructions during cable connection:

Connect by strictly following the circuit diagram;

Measure and make sure the string open-circuit voltage meets the

requirements of the PVS before inserting the fuse;

Identify the positive pole and negative pole before connection.

Page 11: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 2 Safety Instructions

7

Only qualified personnel or professional electrician can perform the

operation and wiring described in this manual.

All operations and wirings must in full accordance with the national and

local standards and requirements.

All warning marks and labels must be clear and intact. Replace them if any

damages are found.

Make sure the terminals are firmly connected during wiring. If the cable

copper core and the terminals are not connected firmly, terminals will be

over-heating and burnt. Anti-flaming cables with multi-strand are advisable

and the cable cross-sectional area should be no less than the recommended

value.

The nuts of the water-proof terminals must be firmly screwed to prevent

water leakage and PVS damages.

Pull the fuse out of the fuse holder for personal and device safety.

Lock the cabinet door and seal the water-proof cover of the lock core after

operation.

No not open the cabinet door frequently.

Page 12: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

2 Safety Instructions User Manual

8

Touching or improper operation on the PCB or other sensitive components

may damage the device.

Do not touch any parts inside the cabinet other than the connection

terminals.

Respect all ESD related safety regulations and wear antistatic wrist strap.

Page 13: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

9

3 Product Description

3.1 System introduction

For a large-scale grid-connected PV system, it is widespread to install a DC

combining device between PV modules and inverters to minimize cable

connections, facilitate maintenance and enhance reliability.

PVS is designed for meeting these requirements, which provides a turnkey

solution for PV plant systems.

Considering different types of PVS, a certain number of PV strings can be

connected to the input side of PVS. After combining work done, at the output

side, there will be one DC+ and one DC- main line. By using of surge protection

device (SPD) and DC switch, the output can be connected to inverters directly.

The PV generation system including a PVS is shown in following figure.

Fig. 3-1 Composition of PV generation system

Page 14: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

3 Product Description User Manual

10

Tab. 3-1 Device in above figure

No. Device

A PV arrays

B PV Array combiner box

C Inverter

D Data acquisition device

E Environment monitoring device

F Grid

3.2 Main features

Meet outdoor installation requirement

Connect to multiple PV inputs with fuse for each input (can be replaced to

other degree)

PV-specific high voltage SPD equipped, lightening protection function for

positive and negative pole

Current sensor inside to monitor the current of each string; the monitored

information can be displayed by the LED or sent by RS485

Monitor busbar voltage and the monitored information can be displayed by

the LED and sent by RS485

3.3 Demonstration of the type

Model Max. Number of

DC inputs

Max.Number

of PV strings

Monitoring

function

PVS-8MH-DB 8 16 YES

PVS-12MH-DB 12 24 YES

PVS-16MH-DB 16 32 YES

Page 15: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 3 Product Description

11

3.4 Dimensions

The dimensions of the PVS are shown in the figure below, unit: mm.

Width(W)

Depth(D)

Height(H)

Model Width(W) Height(H) Depth(D)

PVS-8MH-DB 730 mm 580 mm 260 mm

PVS-12MH-DB

PVS-16MH-DB 930 mm 730 mm 260 mm

3.5 Identifying the PVS

The appearance of the PVS is shown in the figure below (take PVS-16MH-DB

for example).

Page 16: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

3 Product Description User Manual

12

A

No. Name Description

A Lockhole A total of 6, two on the side surface, two on the top

and the bottom respectively.

Note: The figure above is based on PMS-16MH-DB, and the appearance of

other device type may slightly differ.

Page 17: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

13

4 Mechanical Installation

4.1 Scope of Delivery

A B C

ED F

No Name Note Quantity

A PVS - 1

B Related documents

Including FQC test report,

Quality Certificate, Warranty

card, Manual, etc.

1

C Keys To open the cabinet of PVS. 2* / 2** / 4***

D Bolt kit M8 x 16 4

E Hanger Need to be installed to the PVS

cabinet onsite. 4

F MC4 connector Used to connect the PV input 8*/ 12** /

16***

Note: * is for the PVS-8MH-DB;** is for the PVS-12MH-DB; and *** is for the

PVS-16MH-DB.

Page 18: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

14

4.2 Installation site requirements

With IP65 protection degree, the PVS can be installed outdoors. Please meet

the following requirements:

Dimensions and weight of PVS should be considered sufficiently.

Ambient temperature-30℃~+60℃; Relative humidity 0~95%

Installation site should be as close as possible to PV arrays for minimum

cables and wires usage.

Installation site should be safe venting.

Never install the device in direct sunlight to guarantee optimal performance.

For big PV plants, it is suggested that the device is installed on the back side

of PV arrays.

For better heat dissipation and convenient maintenance, enough space must

be maintained around the PVS.

For large-scale PV plant, install the PVS on the back of the PV cell

installation bracket.

Humidity during installation may damage the PVS. Do not install the PVS

during rainy or humidity days.

Screw the water-proof terminals tightly to prevent moisture penetration no

matter the installation is vertically or horizontally. Seal the unused terminals

after cable connection.

4.3 Installation Tools

Electric drill

Hex wrench

Page 19: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 4 Mechanical Installation

15

Bolt (M8 x 16)

M8 Allen wrench for tightening of output terminal

Screwdriver with withstanding voltage of 1500Vdc:

− Recommended model: 65-416-1

− Specification: 2#x125

4.4 Installing PVS

4.4.1 Overview

The PVS is fixed to the installation surface via the hangers in the scope of

delivery. Therefore, first fix the hangers to the PVS on site.

Mounting the PVS onto the installation surface is as described in the following

table.

Step Description Refer to

1 Fix the hangers to PVS. 4.2.2 Fix the hangers to PVS.

2 Fixing PVS to installation

surface.

4.4.3 Fixing PVS to Installation

Surface

4.4.2 Fix the Hangers to PVS

Install the hangers to the installation holes on the back of PVS with delivered

M8 x 16 bolts. The hangers can be installed horizontally or vertically.

For the vertical installation, the distances between hangers are shown in the following figure "Solution 1".

For the horizontal installation, the distances between hangers are shown in the following figure "Solution 2".

Page 20: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

16

W1

H1

W2

H2

Solution 1 Solution 2

Hanger

Model Solution 1 Solution 2

W1 H1 W2 H2

PVS-8MH-DB 621 mm 551 mm 702 mm 470 mm

PVS-12MH-DB

PVS-16MH-DB 816 mm 701 mm 897 mm 620 mm

On site, select an appropriate hanger installation solution according to the installation plane, such as space condition of the bracket.

For ease of description, Solution 1 is used as an example hereinafter to give a

brief description of PVS mounting steps.

4.4.3 Fixing PVS to Installation Surface

The PVS can be installed in two manners: direct wall-mounted manner and

stainless steel wall-mounted manner.

On site, install the device in appropriate manner selected according to actual conditions.

Direct wall-mounted

Step 1 Mark position and drill holes on the installation surface according to the

distance of the hangers on the four corners of the PVS.

Page 21: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 4 Mechanical Installation

17

Step 2 Fix the PVS to the surface according to the following sequence.

Recommended torque:51±0.7 N.m.

A B C D FE

No Name Note

A M10 Bolt Not included in the scope of delivery.

B Flat washer -

C Spring washer -

D PVS hangers -

E Stainless steel support -

F Nut -

Stainless steel wall-mounted

Step1 Mark position and drill holes on the frame according to the distance of the

hangers on the four corners of the PVS.

Step2 Fix the PVS to the surface according to the following sequence.

Recommended torque:51±0.7 N.m.

Page 22: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

18

A B C D FE

No Name Note

A M10 Bolt Not included in the scope of delivery.

B Flat washer -

C Spring washer -

D PVS hangers -

E Stainless steel support -

F Nut -

Step3 Check to ensure PVS is installed correctly and securely.

Page 23: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

19

5 Electrical Installation

5.1 Internal structure

Two schemes are available for the combiner box: floating grounding and

negative grounding. Correspondingly, the internal structural diagram differs.

C D

I

J

K

L

AB

E F

G

H

Fig. 5-1 Floating grounding

C D

I

J

K

L

A

E F

G

H

Fig. 5-2 Negative grounding

Page 24: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

20

No. Description

A DC+ fuse cartridge

B DC- fuse cartridge

C RS485 ports

D Ground copper bar

E Output of DC negative pole

F Output of DC positive pole

G DC switch

H Power supply board

I Indicator(for more details, please refer to the Tab 8-1)

J LED display

K Push switch

L SPD (Surge protection device)

Fuse

A PV special fuse is set for each string as the upstream protection device of the

whole PV power generation system. Measure the voltage between the positive

and negative polarity of each input before inserting the PVS fuse to make sure

the voltage is within the range of 0 – 1500Vdc. Make sure no PV module string

is connected reversely.

The monitoring board

The monitoring board monitors the current of each string. The monitored

current value is sent to the PC through RS485. The PC can judge if a fault is

occurred to the module through the set value.

SPD(Surge Protection Device)

A SPD is quipped inside the PVS to prevent the transient overvoltage caused

by lightning. The SPD failure signal can be sent to the PC through the RS485.

Page 25: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

21

Grounding

It must be grounded properly for overvoltage protection. The PVS provides a

ground terminal for grounding connection.

5.2 Water-proof terminals

Water-proof terminals of PVS are shown as followings.

Label Description Model Cable(mm)

INPUT DC- Negative pole input

waterproof terminal M24 x 1.5 /

MC4 2 x 8

INPUT DC+ Positive pole input

waterproof terminal

Monitor Input Communication input

waterproof terminal PG-11 5~10

Monitor Output Communication output

waterproof terminal

Grounding waterproof

terminal PG-16 10~14

Output DC- Negative pole output

waterproof terminal M40 /

PG-48

22~32/

30.5~40 Output DC+

Positive pole output

waterproof terminal

Note: This table is based on the standard PVS, and the output terminals of

products actually received may differ.

If the actual PV string numbers are less than the nominal numbers, the

terminals can be left unconnected. Seal the unconnected terminals with

Page 26: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

22

waterproof plug.

5.3 Wiring preparations

Step 1 Open the door.

1 2 3

Step 2 Remove the protection cover.

Step 3 Turn the switch to “OFF” position.

Step 4 Remove fuse.

Page 27: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

23

5.4 Connections

5.4.1 Input connections

High voltage is present inside the device!

Follow all the warning signs in the device.

Respect all the safety instructions in this manual and other documents.

Incorrect cable connection may cause damages to the PV cells, the PVS and

inverter. Respect the following instructions during cable connection:

Connect by strictly following the circuit diagram;

Measure the positive and negative polarity of each string by ammeter with

withstanding voltage no less than 1500V and make sure there is no

reversed connection before cable connection.

Measure and make sure the string open-circuit voltage meets the

requirements of the PVS before inserting the fuse;

Identify the positive pole and negative pole before connection.

Brief Description

There are two types of input terminals: gland waterproof terminals and MC4

terminals.

For the MC4 terminal, perform cable connection referring to Scheme 1.

For the gland waterproof terminal, perform cable connection referring to

Scheme 2.

Page 28: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

24

Scheme 1: MC4 Terminal

Step 1 Strip off 7mm insulation layer from the positive and negative DC cable.

Step 2 Assemble the cable ends with crimp contacts by crimping pliers.

Step 3 Connect the cables according to the method illustrated below. Pull the

cable gently to make sure it is secured.

− Connect the positive input cable according to the figure below.

B

A

C

A B C

PVS positive input terminal positive input cable Sealing cover

− Connect the negative input cable according to the figure below.

A

B

C

A B C

PVS negative input

terminal negative input cable Sealing cover

Page 29: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

25

Scheme 2: Gland terminal

Step 1 Loosen the union nut of gland terminals.

Step 2 Insert the “PV1+” cable through terminals of positive input area, and

connect the cable to the “PV1+” terminal inside the device. Enough wire

bending space should be ensured.

B

A

No. Description

A Cable (e.g. “PV1+”, “PV2+”… “PV1-”, “PV2-” etc.)

B Conduit

Step 3 Stripped off the cable insulation layer, using wire stripper, to reveal the

copper core, length as specified in above table.

Do not break the copper wire during stripping.

Select proper terminal to the corresponding cable. For example, LT160012, 16

stands for 16 mm2, the cross-sectional area of the crimping cable; 12 stands for

12mm, the length of the crimping tube, see the following figure.

12mm

16mm2

Cross-section Terminal type Stripped length (mm) Force (N)

2.5mm2 LT025008 10±0.5 190

4mm2 LT040010 12±0.5 275

Page 30: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

26

Cross-section Terminal type Stripped length (mm) Force (N)

6mm2 LT060012 15±0.5 360

10mm2 LT100012 15±0.5 414

16mm2 LT160012 16±0.5 445

Step 4 Crimp the cable. Insert the stripped cable into the terminal. Crimp the

cable using special tool (mouth of the crimping plier should match the

cable cross section), see the following figure.

Step 5 As shown in the following figure, connect the terminal to the

corresponding terminal of the PVS.

Step 6 Follow the same procedure to connect rest cables. Comb all the input

cables together with cable ties and firm them onto the cable support bar.

Appropriate cable bending space shall be ensured.

Page 31: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

27

Press the bolt toward the side with indentation during fixation. Make sure the

terminal is inserted into the PVS as much as possible.

5.4.2 Output connections

Lift the protective cover upwards. Then loosen the nut from gland terminals.

φ13

Step 1 Insert the “DC+” cable through “DC Output (+)” terminal. Enough cable

bending space should be ensured.

Step 2 Strip off both protective and insulating layers with the help of a hand

crimping pliers. The length of cable conductor shall be approx. 25mm.

25mm

Page 32: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

28

The copper cable is recommended for the PVS output terminal. If an

aluminum cable is selected, a copper aluminum terminal must be used and

the specification of the aluminum cable should meet the local technical

requirements.

Step 3 Connect the cable to the proper DT terminal.

Step 4 Install the DT terminal according to the following steps.

− 1. Use hexagon spanner to remove the nut of M12;

− 2. Insert DT terminal into the output terminal;

− 3. Use hexagon spanner to tighten the nut.

ED

C

B

ED

F

A

A Copper bar

B DT terminal

C Bolt

D Spring washer

E Flat washer

F Nut

Step 5 Screw the bolt of the gland terminal tight clockwise.

Step 6 Connect cable “DC-” to “DC Output (-)” following the procedures above.

Output wiring and connections have been finished.

Page 33: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

29

Make sure that the nuts have been screwed into place. If the cable conductor has

not been connected firmly, long-time work may burn the terminal. Stranded

flame-retarded copper wire shall be used, and its size shall be over the

recommended value.

Nuts of water-proof terminals must be screwed correctly and firmly. Otherwise,

water leakage can damage the PVS.

5.4.3 Grounding connections

Ground cables shall be connected correctly and firmly. Otherwise:

The electric shock caused by a malfunction can lead to lethal damage.

The device can be damaged when lightning.

Relevant standards must be observed.

Ground cables must be connected firmly with both device and ground

terminals.

Ground resistance shall be measured after finishing ground connections,

and the measured values should not be over 1Ω.

Step 1 Loosen the union nuts of “ ” gland terminals.

Step 2 Insert the green-yellow wire from the device outside into the “ ” gland

terminal, then pull the wire and connect it to the inner terminal. Enough

wire bending space should be ensured.

Step 3 Strip off both protection and insulation layers, with approx. 12mm

conductor length.

Step 4 Connect the OT terminal.

Page 34: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

30

Step 5 According to the sequence of screw, spring washer, flat washer, OT

terminal and ground hole to connect the OT terminal to the ground

copper bar.

Step 6 Tighten the nuts of gland terminal clockwise. Ground wirings have been

finished.

5.4.4 Communication Connections

Refer to the figure below for communication terminals inside the PVS.

A1,B1,FG

A2,B2,FG

Upper terminal connects to input and lower terminal connects to

output. User may adjust according to real need.

Step 1 Unscrew the gland terminals “Monitor Input” and “Monitor Output”.

Step 2 Pull the communication cable inside the PVS through the gland

terminals.

Step 3 Strip off the cables’ protection layer and the insulation layer until the

Page 35: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

31

copper core is 8mm outside.

Step 4 Insert the screwdriver inside the input cable terminal holes. Pull the

screwdriver until the leaf spring is bounced completely.

Step 5 Insert wires into bottom of wiring holes A1, B1, and FG. Among them:

− Connect communication cable RS485-A to A1;

− Connect communication cable RS485-B to B1;

− Connect communication cable shielding layer to terminal FG.

Step 6 Loosen the screwdriver to let the leaf spring connect to the cable.

Step 7 Follow the same steps to connect the output cables to the A2 ,B2 and FG,

to finish the communication connection.

Page 36: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

32

Communication cable must be shielded twisted pair cable. Communication

unstable or communication failure may follow if otherwise.

Communication cable should be far away from the high voltage cable. Place

the communication cables and power cables in parallel or strap them

together is strictly forbidden. Communication interface or device damage if

otherwise. If not prevented, lead the communication cable through

galvanized tube for shielding.

Communication solution

The communication method of PVS is shown below:

PVS 1

A1 B1 A2 B2

RS485A

RS485B PC

PVS 2

A1 B1 A2 B2

PVS n

A1 B1 A2 B2

(optional)

120Ω resistor

Logger

Connect A1 and B1 of first PVS to A1 and B1 of data collector;

Connect A2 and B2 of first PVS to A1 and B1 of second PVS;

Connect A2 and B2 of second PVS to A1 and B1 of third PVS;

And so forth: connect A2 and B2 of previous PVS to A1 and B1 of next PVS

After installation or commissioning, ensure the door and the cover of the key

is locked to avoid the water is in. If such a situation occurs, Sungrow takes

no responsibility for this.

Page 37: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

33

5.4.5 Cable Layout

Lay the cables connected the PVS and external devices in the cable trench for

easy installation and maintenance. Cable trenches are designed and

constructed in accordance to related regulations and the number & dimensions

of the devices.

Lay the PVS positive and negative pole output cables, communication cables in

different layer of the support arm in the cable trench to avoid short circuit

caused by cable insulation layer cracks. See the following picture; user can

design the number of supporting arms as per reality.

A

B

C

D

Cable trenches

No. Name

A Cable trench

B Positive output cable supporting arm

C Negative output cable supporting arm

D Communication cable support arm

Note: pictures here is indicative only, user can make adjustment according to

real needs.

5.5 Communication settings

Communication parameters of PVS can be set and viewed on the monitoring

board, as shown below.

Page 38: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

5 Electrical Installation User Manual

34

A Push switch

The upper switch is K1 and the lower switch is K2.

B LED display

The LED display can be divided into the first two digits and last three digits.

The first two digits is used to display the parameter type; the last three digits are

used to display the corresponding values.

Parameter type Description

Voltage and current

display

Press K1 to turn screen

1st current: 10A

2nd

current: 10A

16th current: 10A

Display voltage: 700V

For example: 0110.0 means that the current of the 1st

input is 10A.

But when the first two digits are 00, the last three digits

are the voltage. For example: 00700 means that the

present voltage is 700V.

Page 39: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 5 Electrical Installation

35

Parameter type Description

Communication

display

Communication address

A0 007

Baud rate b9600

Press K2 to turn screen once

Ambient temperature

display Ambient temperature

C0 16.8

Press K2 to turn screen twice

Setting Communication Address

Step 1 Press and hold K1 for 3s until "A=001" is displayed and flashing on the

LED.

Step 2 press K1 to add address number; and press K2 to reduce address

number. The communication address can be set to 1-247.

Step 3 Press K1 and K2 at the same time to save the setting.

Step 4 Press and hold K2 for 3s to switch to another input branch of the

combiner box. Complete settings according to the foregoing methods.

5.6 Start/Stop of operation

PVS runs automatically when power on and stop when power off. User can

control the DC output of the PVS manually through the PVS internal DC switch

Page 40: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

36

6 Commissioning

Check if the PVS can operate normally after installation:

Step 1 Connect the connection terminal of each PV string.

Step 2 Measure the input voltage of positive pole and negative pole of each

input to make sure they are basically same and the positive pole and

negative pole are connected correctly.

Step 3 Fasten the fuse holder.

Step 4 Close the DC switch; monitoring unit power indicator “POWER/PWR”

lights up and status indicator “RUN” flashes. When push switch K1 is

pressed, if there is a value on the LED digitron, the operation is normal.

+5V

GND

Step 5 Lock the door, remove the key and tighten the key-hole water-proof

cover.

Page 41: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

37

7 Routine Maintenance

Due to ambient temperature, relative humidity, windblown dust and vibrations,

components of PVS will get aging. It is necessary to do the routine maintenance

work periodically on the device.

Only qualified electricians can do the maintenance work described in this

chapter.

After the maintenance work finished, be sure not to leave screws, washers

and the like in the PVS. The device can be damaged!

Only work on the PVS when it is switched off and voltage free. Fuses are

non-resetting once they are broken. After many times replacement, the fuse

holders will get loose. Users should fasten the fuse holders periodically to

ensure valid connections.

7.1 Replace the Fuse

Once the fuse is blown, the damage is irrecoverable. Replace the fuse by

qualified operators in time.

Replace the fuse with new one with the same model and the same grade.

Method to replace fuse:

Page 42: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

8 Troubleshooting User Manual

38

Fig. 7-1 Steps to replace the fuse

Tighten the fuse cover after replacing the fuse.

Disconnect the DC switch before checking and replacing fuse. Please notice

that high voltage still exist in all terminals of the DC switch. Make sure the

current of each input is zero by pliers and then replace the fuse.

7.2 Replace the sealing strip

The sealing strip inside the PVS is located in the PVS internal door cover, as

shown by A in the figure below. It is advisable to check this sealing strip once

every month. If it is damaged by non-human factors, please contact Sungrow

immediately to replace the PVS door cover.

Page 43: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 7. Routine maintenance

39

A

Page 44: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

40

8 Troubleshooting

This chapter gives the basic troubleshooting methods for customer as a

reference.

8.1 Before troubleshooting

Please notice the following items before troubleshooting:

Disconnect the DC switch before operation.

Please do not touch the bare metal parts of the copper bar under the

protection plate.

Pull the fuse holder for maintenance of the combining busbar and to

disconnect the input cable.

High voltage still exists after DC switch is switched off.

The fuse holders are still live after fuses are removed.

8.2 Common faults and troubleshooting

Fault Possible cause Method of correction

On the monitoring

unit, neither “RX” nor

“TX” lights up.

RS485

communication fault

Check communication line.

Refer to “5.4.4 Communication

Connections”.

Page 45: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 9 Troubleshooting

41

Fault Possible cause Method of correction

On the monitoring

unit, “RX” flashes and

“TX” does not light

up.

Incorrect address Refer to "5.5 Communication

settings"

Communication

failure sometimes

Disturbance to

communication line

Twisted pair shielded cable

shall be used, with shielding

layer grounded.

Refer to “5.4.4 Communication

Connections”.

On the monitoring

unit, indicator

"POWER/PWR" does

not light up.

No 5V output on

switching power

supply board

Check voltage on monitoring

unit +5V plug, which shall be

about 5V; otherwise switching

power supply board is faulty

and please contact us for

repair.

On the monitoring

unit, indicator “RUN”

does not flash.

Faulty CPU board Contact us for replacement of

the monitoring unit

On the monitoring

unit, indicator “SPD”

lights up.

Failure of surge

protection device

Replace surge protection

device in time

Current of a branch

apparently smaller or

larger than current of

other branches

Abnormal current

Check size of PV strings of this

branch for consistency.

Check if this branch has

shaded PV string.

Display of open

circuit fault of a

branch

No PV string

connected to this

branch

Set this branch to unconnected

status.

Page 46: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

9 Troubleshooting User Manual

42

Fault Possible cause Method of correction

Dropped out cable or

molten fuse

Check PV cables for

disconnection.

Or, replace fuse.

The following figure illustrates terminals and layouts of metering board.

+5V

GND

Tab. 8-1 Descriptions

Indicator Meaning

TX Transmitted communication data signal indicator

RX Received communication data signal indicator

RUN Monitoring unit running status indicator

SPD Surge protection device fault indicator

CB DC switch status indicator

POWER/PWR Monitoring unit power supply status indicator

+5V +5V plug on the monitoring unit

Page 47: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

43

9 Appendix

9.1 Technical data

Application Data PVS-8MH-

DB

PVS-12MH-

DB

PVS-16M

H-DB

Operating ambient temperature

range -40℃ to +60℃

Operating relative humidity range 0~95%

Degree of protection (acc.to IEC

60529) IP65

Conformity with norms

EN 62109-1:2010

IEC 61439-1:2011, EN 61439-1:2011

IEC 61439-2:2011, EN 61439-2:2011

Electrical Characteristics

Max. Number of DC inputs 8 12 16

Max. Number of PV strings 16 24 32

Rated DC voltage (Un) 1500 Vdc

Fuse Type 30 A

Max. input current per string 30 A

Rated current output 160 A 240 A 320 A

Switch disconnector (acc. to IEC

60947-3) 400 A (DC1500 V)

Voltage detection Range 0~1500V

Current detection Range 0~25A

Switch-disconnector handle

location Internal handle (inside enclosure)

DC grounding system Floating / Negative grounding

Page 48: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

9 Appendix User Manual

44

Surge protection 1500V, Type 2, In=20kA,Imax=40kA, Up≤

3.4/6.8kV

Enclosure

Enclosure dimensions (H x W x D) 730 x 580 x 260 mm 930 x 730 x 260

mm

Box Cabinet with hinged door(s)

Material SMC Plastic

Fixing system Direct wall mount + stainless steel wall

mount lugs

Inputs

Positive / Negative DC input MC4 terminal/ gland terminal

Fuse size 10 x 85 mm

Location of fuses Positive and negative inputs

Fuse-link rated current (In) 30A

Fuse-link time-current

characteristic gPV (EN 60269-6)

Earth wire to be connected to /

cross‐section(stranded) OT terminal connection / 16 - 35 mm²

Earth wire outer diameter 10 - 14 mm

Outputs

Number of DC outputs (+ & ‒ being

one output) 1

DC output wires to be connected to

/Cross section (stranded)

M12 bolt and nut connection

300 mm² 400 mm²/

Customized

DC output wires outer diameter 22- 32 mm / 30.5 - 40 mm

Others

Exterior color RAL7035 Matte

Weight 28 kg 30 kg 40 kg

Page 49: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 9 Appendix

45

9.2 Quality Assurance

Where any fault occurs during the warranty period, Sungrow will maintain or

replace the product for free.

Evidence

Sungrow Power Supply Co., Ltd. needs the users to provide the receipt invoice

and the date you purchase. Meanwhile the trademark should be clearly legible.

Otherwise Sungrow Power Supply Co., Ltd. has the right to exclude liability

claims.

Conditions

The original unqualified product should return to Sungrow.

Users should permit appropriate time to maintenance the device with fault for

Sungrow.

Exclusion of liability

Guarantee or liability claims for damages of any kind are excluded if they are

caused by one or more of the following:

Improper, inappropriate use or installation of the product

Installing or operating the product in an inappropriate environment

Installing or operating the product when ignoring relevant safety regulations

in the deployment location

Ignoring safety warnings and instructions in all documents relevant to the

product

Installing or operating the product under incorrect safety or protection

conditions

Altering the product or supplied software without authorization

Page 50: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

9 Appendix User Manual

46

The product malfunctions due to operating attached or neighboring devices

beyond permissible limit values.

In case of unforeseen calamity or accidents

Where fault is caused by any of the above and users have the relevant demand,

Sungrow will do the paid maintenance work to the device after judgment.

Specifications are subject to changes without advance notice.

Text and illustrations are not binding. The right to make alterations is reserved.

9.3 Contact Information

We need the following information to provide you the best assistance:

Type of the product

Serial number of the product

Fault code/name

Brief description of the problem

China (HQ)

Sungrow Power Supply Co., Ltd

Hefei

+86 551 65327834

[email protected]

Australia

Sungrow Australia Group Pty. Ltd.

Sydney

+61 2 9922 1522

[email protected]

Brazil

SungrowDo Brasil

Sao Paulo

+55 11 2366 1957

[email protected]

France

Sungrow France – Siege Social

Paris

[email protected]

Germany

Sungrow Deutschland GmbH

München

Greece

Service Partner – Survey Digital

+30 2106044212

Page 51: User Manual PVS-8MH-DB/ PVS-12MH-DB/PVS-16MH-DB PV …

User Manual 9 Appendix

47

+49 89 324 914 761

[email protected]

[email protected]

India

Sungrow (India) Private Limited

Gurgaon

+9108041201350

[email protected]

Italy

Sungrow Italy

Milano

[email protected]

Japan

Sungrow Japan K.K.

Tokyo

+ 81 3 6262 9917

[email protected]

Korea

Sungrow Power Korea Limited

Seoul

+827077191889

[email protected]

Malaysia

Sungrow SEA

Selangor Darul Ehsan

+6019897 3360

[email protected]

Philippines

Sungrow Power Supply Co., Ltd

Mandaluyong City

+639173022769

[email protected]

Thailand

SungrowThailand Co., Ltd.

Bangkok

+66891246053

[email protected]

Spain

Sungrow Ibérica S.L.U.

Navarra

[email protected]

Romania

Service Partner - Elerex

+40 241762250

[email protected]

Turkey

Sungrow Deutschland GmbH Turkey Istanbul Representative Bureau

Istanbul

+90 2127318883

[email protected]

UK

Sungrow Power UK Ltd.