- 1 -© 2014 Chromalox®, Inc.1-888-996-9258
Thank you for choosing the Chromalox® MaxPac™ - a complete power control solution with industry-best price and performance.
For more than 80 years, customers have relied on Chromalox for the utmost in quality and innovative solu-tions for industrial heating applications. Chromalox manufactures the world’s largest and broadest line of electric heat and control products.
The MaxPac Series SCR Controllers provide the best control for applications where consistent heater/pro-cess temperature is critical or where fine resolution of power is required.
Common MaxPac features include:• 120-575Vac@100-1200Amps• IsolatedControlCircuit• FlexibleI/OPowerWiring• EasyCustomerInterface• RemoteShutdown• CompactSizeandConstruction• Touch-SafeDesign(optionon100-650Ampmodels)• dv/dtTransientVoltageProtection• MOVProtection• Built-InPowerDistribution
Features for the MaxPac I, II, and III include:• ZeroCrossoverFiring• IsolatedControlCircuit
On/OffControlInputs: 120thru240Vac 5-32Vdc DryContactClosure
Proportional(DOTFiring)Inputs: 4-20mA,0-5Vdc,1-5Vdc,0-10Vdc RemoteManualAdjust(Optional) RemoteAuto/ManualSwitch(Optional)• ElectronicallyProtectedwithTemperatureWarningandShutdownSystem• Single-orThree-CycleResolution(JumperSelectable)• ShortedSCRDetection(Optional)
Features for the MaxPac IP include:• PhaseAngleFiring• IsolatedControlCircuitInputs
0-5mA,0-20mA 0-50mA,1-5mA 4-20mA,10-50mA 0-5Vdc,0-10Vdc
• OptionalCurrentLimit• SoftStart• LineVoltageCompensation• Zero&GainAdjustments• Built-InManualAdjustment• CurrentLimitAdjustment(Optional)
Ifyouhaveapplicationquestions,refertotheEngineeringResourcesectionofourwebsiteatwww.chromal-ox.com to find the answer you’re looking for, or call one of our application engineersat1-888-996-9258forpersonalassistance.
-2- © 2014 Chromalox®, Inc. 1-888-996-9258
Table of Contents
Section Topic Page
1................................................. ImportantSafeguards ..................................................................................... 32................................................. Description ..................................................................................................... 43................................................. BeforeYouInstall ............................................................................................ 54................................................. Installation ...................................................................................................... 6 4.1 ................................. Mounting ......................................................................................................... 8 4.2 .................................Wiring ............................................................................................................ 11 4.2.1 ............. Touch-SafeDesign ....................................................................................... 11 4.2.2 ............. CoverRemovalandInstallation .................................................................... 12 4.2.3 ............. Power/LoadWiring ....................................................................................... 12 4.2.4 ............. InstrumentPower ......................................................................................... 16 4.2.5 .............Grounding ..................................................................................................... 16 4.2.6 ............. CommandSignalWiring ............................................................................... 17 4.2.7 ............. Calibration .................................................................................................... 235 ................................................ Specifications ............................................................................................... 246 ................................................ Maintenance ................................................................................................. 257 ................................................ Troubleshooting ............................................................................................ 268 ................................................ PartsandAccessories .................................................................................. 279 ................................................WarrantyandReturnInformation ................................................................. 2810 .............................................. ECDeclarationofConformity ....................................................................... 37
-3-© 2014 Chromalox®, Inc.1-888-996-9258
1Please read all instructions before installing and operating your MaxPac™.
Toavoidelectricalshockorinjury,alwaysremovepowerbeforeservicingacircuit.
Personnel working with or near high voltages should be familiar with modern methods of resuscitation. Con-tact an area supervisor or safety personnel for more information.
Throughout the MaxPac User Manual, the safety alert and the international electric shock/electrocution sym-bolswillalertyoutopotentialhazards.Safetyprecautionsshouldalwaysbefollowedtoreducetheriskofpersonalinjurytopersonsfromfireandelectricalshockhazards.
SafetyAlertSymbol
InternationalShock/ElectrocutionSymbol
Eachsafetymessageisprecededbyasafetyalertsymbol andoneofthreewords:DANGER,WARN-ING,orCAUTION.
Thesemean:
Important Safeguards
YouWILLbekilledorseriouslyhurtifyoudonotfollowinstructions.
YouCANbekilledorseriouslyhurtifyoudonotfollowinstructions.
YouCANbehurtifyoudonotfollowinstructions.
DANGER
WARNING
CAUTION
DamagePreventionMessages:
YouwillseeotherIMPORTANTmessagesthatareproceededbytheword CAUTION that are intended to help prevent damage to the MaxPac™orotherequipment.NotethatDamagePreventionMessagesareNOTaccompaniedbytheSafetyAlertSymbol.
-4- © 2014 Chromalox®, Inc. 1-888-996-9258
2
† Thiscanbesettothreecycles‘On’/threecycles‘Off’(seesectiononinstallationoptions).
Description
MaxPac I, II, and IIITheChromaloxMaxPacI,II,andIIIcontrollersarehighlyversatileSCRPowerPakswithoptionalplug-inproportionalfiringandshortedSCRdetectionboards.FiringmodesincludeOn/OffandDOTproportionalzerovoltageswitching.ChromaloxexclusiveDOT(DemandOrientedTransfer)firingtechniqueswitchesthefewestnumberofcyclestoprovidethemostprecisezerocrossovercontrol.At50%output,theunit’soutputalternatesbetweenonecycle“On”andonecycle“Off.”At51%,theoutputcontinueswithonecycle“On,”onecycle“Off,”andgraduallyintegratesoneextra“On”cyclefortheadditional1%.ThisDOTfiredtech-niquealsominimizestemperatureovershoot,temperaturefluctuationsandhelpsextendtheload’selementlife due to reduced thermal shock.
ThepowerSCRassembliesconsistofone,two,orthreepairsofSCRsconnectedbacktoback(withanoptionalsemiconductorfuse),RCSnubber,andMOVprotection.ThefiringcircuitisbasedonacommonOn/OffcontrolboardwithplugandplayShortedSCRandDOTfiredplug-inboards.Diagnosticindicatorsare included. Plug-in terminal blocks for easy customer interface are also provided.
MaxPac IPTheChromaloxMaxPacIPutilizesSinglePhase,PhaseAnglefiringtomodulatepowertoaninductiveorresistiveload.PhaseAnglecontrolhastheadvantageofproportioningeverycycletherebyprovidingveryfine resolution of power. Fast responding loads in which the resistance changes as a function of temperature requirePhaseAnglecontrol.TheMaxPacIPoffersaSoftStartfeaturethatassuresthattheloadpowerisgraduallyincreasedfromzerotothevaluesetbythecommandsignalintheeventofapowerinterruption.Inaddition,optionalCurrentLimitisusedtoprotecttheload,SCRcontrollerandthetotalsystemfromlargesurge currents that could occur at start-up.
-5-© 2014 Chromalox®, Inc.1-888-996-9258
3Before You Install
ImmediatelyafterreceivingyourMaxPacI,II,IIIorIPSeriesController,visuallyinspecttheshipmentpackag-ing and record any damage on the shipping documents. Unpack the controller and carefully inspect for obvi-ousdamageduetoshipment.Ifanydamagehasoccurred,YOUmustfileaclaimwiththecarriercompany,sincethecarriercompanywillnotacceptaclaimfromtheshipper(Chromalox).
BesuretocheckthemodelnumberandverifythatyouhavereceivedthecorrectModelofcontroller.
Ifthecontrollerisnotinstalledandplacedintooperationimmediately,itshouldbestoredinacool,dryenvi-ronment. Temperature extremes and excessive moisture can damage the controller.
BeforechoosingalocationinwhichtomountyourMaxPac,pleaseconsiderthefollowing:
TemperatureWhenmountingtheSCRunitinacontrolpanel,attentionshouldbepaidtotheenclosuretempera-ture.TheSCRisratedtoperformatitsnameplatecurrentratingintemperaturesupto50˚C(122˚F).Ensurethatadequateventilationisprovidedorsomeothermethodofmaintainingthecorrectcabi-net temperature is used.
CleanlinessCarefulattentionmustbepaidinareassubjectedtoairborneparticles.Theefficiencyoftheheatsinksreliesontheirconductingsurfacesbeingmaintainedinacleanmanner.(SeetheMaintenanceSection.)
DampnessHigh humidity or hosing down a unit should be avoided.
ClearanceChoose a location that will provide adequate spacing around the unit when mounted. This will en-sureproperairflownecessarytocoolthedevice.
WARNING
Hazardous Voltage: Disconnectandlockoutpowerbeforeinstall-ingorservicing.Failuretocomplycouldresultinpersonalinjuryor equipment damage.
-6- © 2014 Chromalox®, Inc. 1-888-996-9258
InstallationSection(continuationofpage5)
TheforcedairdesignoftheMaxPacseriesallowsmountinginanydirection.Itisessentialthatairflowthrough the enclosure be planned to insure proper cooling.
The100ampthrough300ampopendesignMaxPacallowtheinputlinepowertoconnectfromeitheroftwodirections.The output power can only be connected from one direction. The three mounting configurations
areshownbelow(MaxPacIIThree-PhaseTwo-LegShown).
Opendesignsabove300ampsandallcloseddesignsallowincomingand outgoing wiring in either direction.
In In
Configuration One
CoolAirInWarmAirOut
Fan Phase 1 Phase 3
orIn Out orIn Out
Configuration TwoOut Out
In In
WarmAirOut CoolAirInPhase 1 Phase 3 Fan
orIn orIn
Configuration Three
WarmAirOut
Out
Phase 3
orInIn
Out
Phase 1
In orIn
Fan
CoolAirIn
-7-© 2014 Chromalox®, Inc.1-888-996-9258
InstallationSection(continuation of page 5)
ExamplesofProperAirFlow
Pagoda Top
Fan
Air
Louvers Louvers
MaxPac
AirFan MaxPac
Fan
Enclosure
Air Enclosure
FanFilter
Forced Air In
Forced Air OutLouvers
Since hot air rises naturally, it is not recommended that cooling air enterfrom the top and exhaust at the bottom of the enclosure.
- 8 - © 2014 Chromalox®, Inc. 1-888-996-9258
Figure Drawing Number ModelFigure Model1................100A,150A,&200A2-LegOpenType1................100A,150A,200A,&300A1-LegOpenType2................100A,150A,&200A3-LegOpenType3................300A2-LegOpenType4................100A,150A,200A,300A&400A1-LegTouch-Safe4................400A1-LegOpenType5................100A,150A,200A,300A&400A2-LegTouch-Safe5................400A2-LegOpenType6................100A,150A,200A,300A&400A3-LegTouch-Safe6................300A&400A3-LegOpenType7................550A&650A1-LegTouch-Safe7................550A&650A1-LegOpenType8................550A&650A2-LegTouch-Safe8................550A&650A2-LegOpenType9................550A&650A3-LegTouch-Safe9................550A&650A3-LegOpenType..................800-1200Ampunits,consultfactory
4Installation
Please read all information in this section before beginning the installation of your MaxPac.
InstallationoftheMaxPacrequiresthreesteps:1. Mounting2. Powerwiring3. 120or 230Vac50/60hzforinstrumentpower.See4.2.4,pg.16.
4.1 - Step 1: Mounting
BeforemountingyourMaxPac,pleasereadthesectiontitled“BeforeYouInstall’onpage5foradescriptionof an ideal environment for the unit’s operation.
The space required for mounting the MaxPac Power Pak depends upon the model. The table below refers to the figures on the following pages. These figures illustrate the dimensions and mounting holes for the vari-ous MaxPac Power Pak models. Please refer to these figures before mounting your unit.
IMPORTANT: Please note that the figures on the following pages are not drawn to the same scale.
- 9 -© 2014 Chromalox®, Inc.1-888-996-9258
Figure 1 Figure 2
Figure 3 Figure 4
Figure 5
4.7" [107mm]0.0" [0mm]
1.0" [25mm]
4.75" [121mm]
8.5" [216mm]9.5" [241mm]
6.0" [153mm]7.3" [185mm]
FIRING PACKAGE
FAN END
Ø0.280" [Ø7.11mm](6 HOLES)
4.2" [107mm]0.0" [0mm]
1.0" [25mm]
7.2" [184mm]
13.5" [342mm]14.5" [368mm]
6.0" [153mm]
7.28" [185mm]
FIRING PACKAGE
FAN END
Ø0.280" [Ø7.11mm](6 HOLES)
7.2" [183mm]0.0" [0mm]
1.3" [33mm]
7.3" [185mm]
13.3" [337mm]14.6" [371mm]
12.0" [305mm]13.3" [338mm]
FIRING PACKAGE
FAN END
Ø0.280" [Ø7.11mm](6 HOLES)
5.12" [130mm]0.0" [0mm]
1.3" [33mm]
9.3" [237mm]
13.3" [338mm]14.6" [371mm]
8.1" [206mm]9.1" [232mm]
FIRING PACKAGE
FAN END
Ø.3125 [Ø7.94mm](8 HOLES)
5.3" [135mm]
8.4" [214mm]0.0" [0mm]
1.3" [33mm]
9.3" [237mm]
13.3" [338mm]
14.6" [371mm]
14.7" [375mm]
15.75" [400mm]
FIRING PACKAGE
FAN END
Ø.3125" [Ø7.94mm](8 HOLES)
5.3" [135mm]
- 10 - © 2014 Chromalox®, Inc. 1-888-996-9258
Figure 9
13.8" [351mm]0.0" [0mm]
1.3" [33mm]
26.5" [673mm]
16.3" [414mm]17.6" [448mm]
11.3" [287mm]
25.5" [648mm]
FIRING PACKAGE
FAN END
Ø.3125" [Ø7.94mm](8 HOLES)
6.3" [160mm]
Figure 6 Figure 7
Figure 8
11.7" [298mm]0.0" [0mm]
1.3" [33mm]
9.3" [237mm]
13.31" [338mm]
14.62" [371mm]
21.4" [543mm]
22.4" [568mm]
FIRING PACKAGE
FAN END
Ø.3125" [Ø7.94mm](8 HOLES)
5.3" [135mm]
5.8" [148mm]0.0" [0mm]
1.3" [33mm]
11.3" [28mm]
16.3" [414mm]17.6" [448mm]
9.5" [241mm]10.5" [267mm]
FIRING PACKAGE
FAN END
Ø.3125" [Ø7.94mm](8 HOLES)
6.3" [160mm]
9.8" [249mm]0.0" [0mm]
1.3" [33mm]
11.3" [287mm]
16.3" [414mm]17.6" [448mm]
17.5" [444mm]18.5" [470mm]
FIRING PACKAGE
FAN END
Ø.3125" [Ø7.94mm](8 HOLES)
6.3" [160mm]
- 11 -© 2014 Chromalox®, Inc.1-888-996-9258
4.2 - Step 2: Wiring
4.2.1 - Touch-Safe Design
IftheMaxPacmodelyoupurchasedisofaTouch-Safedesign,followthestepsonthefollowingpagetoinstall the electrical wiring. This will ensure the wiring is done properly while maintaining the Touch-Safe feature.IfyourMaxPacisofanOpendesignbelow400Amps,disregardthissubsection.
ThefollowingisadetaileddrawingofaTouch-Safeunit:
Careful attention must be paid when attaching the wiring to the MaxPac to ensure proper and safe opera-tion. This section contains detailed information on how to connect the power, resistive load, ground, and command signal wiring.
IMPORTANT: SelectinstallationwiringthatisinaccordancewiththeNationalElectricalCodeandanylocalstandardsthatmaybeapplicable.
WARNING
Hazardous Voltage: OnlyqualifiedpersonnelshouldperformelectricalwiringfortheMaxPacPowerPaks.LETHALLYHIGHVOLTAGESareassociatedwiththisequipmentandaredanger-ous if improperly installed.
COOLING AIR
COOLING AIR
SCR
FUSE
HEATSINK FINS
COVER PROVIDES FOR TOUCH SAFE FEATURE
TOUCH-SAFE COVER PROVIDES WIRE ENTRANCE AND EXIT THROUGH SEALS COVERING THE WIRE WINDOW.
REMOVAL OF THE TAPE BEHIND THE WINDOWS TOBE USED ALLOWS WIRES TO PASS. THE TAPE
REMAINS ON UNUSED WINDOWS TO PROVIDE TOUCHSAFE FEATURE.
BUS BAR DESIGN ALLOWSFOR WIRING FROM EITHERDIRECTION AND MULTIPLELOAD CIRCUITS
BUS BAR DESIGN ALLOWSFOR WIRING FROM EITHERDIRECTION AND MULTIPLELOAD CIRCUITS
LONG LIFE, HIGH OUTPUT BALLBEARING FANS PROVIDE RELIABLE
COOLING
-12- © 2014 Chromalox®, Inc. 1-888-996-9258
4.2.3 - Power/Load Wiring
The following illustrations depict how to connect the MaxPac to a resistive or inductive load. Make sure you refer to the correct illustration for the MaxPac series you have purchased.
Forthepower/loaddrawings:
Onopendesignunitsupto300Amps,X1,X2,X3,L1,L2,andL3refertocopperlugs.
Onopendesignunits400AmpsandgreaterandallTouch-Safedesigns,X1,X2,X3,L1,L2,andL3referto bus bar connections.
MaxPac I
4.2.2 - Steps for Touch-Safe Design Cover Removal and Installation
RemoveCover: 1. Loosenthethumbscrewsonbothendsofthecover. 2. Liftthecoverfromthebase.
InstallWiring: 3. Attachthewirestothebusbarsinaccordancewiththeinstructionsinthenextsection. 4. Choosetheentranceandexitdirectionsforthewiringasdesired. 5. Afterthewiringiscomplete,removethetapefromtheinsideofthewiregasketsofthe windows that the power wiring will enter or exit.
ReplaceCover: 6. Angletheendofthecoverwithoutscrewstowardsthe“fan-end”oftheunit. 7. Slipthatendintoplacefirstwhileallowingthewiringtopassthroughthedesiredwindows. 8. Slip the opposite end of the cover into place. 9. Tighten all thumb screws.
WARNING
Hazardous Voltage: DONOTremovethetapefromthebackofthe windows that are not used, as this maintains the Touch-Safe feature.
MAX PAC I
L2
L1 X1
Single PhaseResistive
L2 Connection isNOT on MaxPac
-13-© 2014 Chromalox®, Inc.1-888-996-9258
MaxPac II
MaxPac III
Three Wire2 Leg ControlMAX PAC II
L1
L3
L2
X1
X3
L2 Connection isNOT on MaxPac
Four Wire�3 Leg Control
MAX PAC III
L1
L2
L3
X1
X2
X3
NN Connection is�NOT on MaxPac
IMPORTANT: TheI2t fuses installed on the SCR are designed to protect the SCR from faults on the load connection side. They are NOT intended to provide wire protection.
CAUTION
-14- © 2014 Chromalox®, Inc. 1-888-996-9258
MaxPac III
MaxPac IP
IMPORTANT: TheI2t fuses installed on the SCR are designed to protect the SCR from faults on the load connection side. They are NOT intended to provide wire protection.
CAUTION
Three Wire3 Leg Control
MAX PAC III
L1
L2
L3
X1
X2
X3
Single Phasetransformer
CoupledMAX PAC IP
L2
L2
L1 X1
L2 connection toMaxPac is instrument
power only
-15-© 2014 Chromalox®, Inc.1-888-996-9258
ThebusbarsaredesignedtoacceptNEMAstandardtwo-holecrimplugsinaccordancewiththechartsbelow.
Thefollowingdrawingsshowproperinstallationofthecrimplugsonthebusbars:
Illustration 1:ViewFromRearVentilatedPanel
FUSE
Smaller wire, #1 through #8, often usedfor power distribution, can be connectedtobothsidesoftheloadbus.Wiringmustbe bent slightly to align with the windowsin the top of the touch safe units.
LINEBUSBAR
LOADBUSBAR
FANEND
SCR
1/0through500mcmwire must mount on thefuse side of the busbar as shown tomaintain requiredelectrical clearances
Illustration 2:ViewFromTop
Touch-Safe Units100-400Amps
InputBusUpto(3)1/0-300mcm(70mm2—150mm2)
Upto(2)350-500mcm(185mm2—240mm2)
OutputBusUpto(10)#8-#1(10mm2—50mm2)
Upto(3)1/0-300mcm(70mm2—150mm2)Upto(2)350-500mcm(185mm2—240mm2)
550-650AmpsInputBus
Upto(4)1/0-300mcm(70mm2—150mm2)
Upto(3)350-500mcm(185mm2—240mm2)
OutputBusUpto(12)#8-#1(10mm2—50mm2)
Upto(4)1/0-300mcm(70mm2—150mm2)Upto(3)350-500mcm(185mm2—240mm2)
800-1200AmpsOpenDesign
Inputandoutputbusdrilledtoaccomodateqty(4)1/0-500mcmNEMAstandardtwo-holecrimplugsperphase.
Allboltsmustmountwith excess bolt lengths toward the fuse to main-tain required electrical
clearances.
-16- © 2014 Chromalox®, Inc. 1-888-996-9258
The power wiresmustalwaysconnecttothefuseside(refertoillustration1onpage15)ofthebusbar.Thisis essential to maintain the required spacing between the phases and sides, and to align with the openings in thetop.Theonlyexceptiontothisiswhenusingpowerdistributionusingconnectorsofsizes#8to#1.Thereis adequate spacing for these connectors to be mounted on both sides of the bus bar, if necessary.
The bolt headshouldalwaysbeontheoutsideofthebusbar(refertoillustration2onpage15)withtheboltextending towards the fuse.
Flat washers should be used on both the bolt head and the nut, and a lock-washer should be under the nut.
The Touch-Safe MaxPac is designed to allow both input and output wiring to enter/exit in either direction. Onthe550Ampand650Ampmodels,itisnecessarytomountthewireintheholesthatmaximizethedistanceforthewiretoexittheenclosure.Thismaximizesthedistancefromthecovertothenon-insulatedconnector.
Whenusingthepower distribution feature and mounting terminals on both sides of the bus bar, the wires mountedontheoutsideofthebusbarmustbebentinwardslightlytoalignwiththeopeninginthetop.Allwiring,especiallythelargerwires,shouldbebentpriortomountingtothebusbars.DONOTusethebusbars as an anchor to bend the power cables.
4.2.4 - Instrument Power
MaxPac requires 120 or 230 Vac 50/60Hz for instrument power. This voltage supplies power for the control circuits, fans, high temperature warning indicator, and shorted SCR Indicators (see Fig. 1 on page 21).
This supply is fused on the main circuit board.
4.2.5 - Grounding
ChasisisprovidedwithholepatternforstandardNEMAtwo-holecrimplugs.
WARNING
Hazardous Voltage: ThisElectricalEquipmentmustbeinstalledbya qualified person and effectively grounded in accordance to the NationalElectricCodeandlocalcodes.
IMPORTANT
-17-© 2014 Chromalox®, Inc.1-888-996-9258
4.2.6 - Command Signal Wiring
Pleaserefertothefiguresonpage19forillustrationsofthe6-,8-,and10-pininputterminals.
MaxPac I, II, and III
On/Off Control Signals
AC Input–The120thru230VacsignallinesareconnectedtoterminalJ1-7&8(seeFig.9onpage21).Aninputvoltageof120to230VacturnsthepowerOn.TheturnOFFvoltageis0Vac. DC Input–The5-32VdcsignallinesareconnectedtoterminalJ3-1&4(seeFig.10onpage21).Aninputvoltageof5to32VdcturnsthepowerOn.TheturnOFFvoltageis0Vdc.
Contact Closure Input–ThedrycontactsignallinesareconnectedtoterminalJ3-1&2(seeFig.11onpage21).AclosedcontactturnsthepowerOn.TheturnOFFvoltageisanopencontact.
Process Analog Control Signals
MaxPacI,II,andIIIhavebeenfactorycalibrated.Theseunitsaccept0-5,1-5,0-10Vdc,and4-20mAinputsignalsthatareconnectedtoTerminalBlockJ2.Thefollowingsignalsareconnectedto:
0-5Vdc: TerminalJ2-9(+)&7(-)(seeFig.7onpage21)1-5Vdc: TerminalJ2-5(+)&7(-)(seeFig.5onpage21)0-10Vdc:TerminalJ2-10(+)&7(-)(seeFig.8onpage21)4-20mA: TerminalJ2-6(+)&7(-)(seeFig.6onpage21)
Auto/Manual Input
TheMaxPacI,II,andIIIcanbe wired to make it possible to select an input from either a temperature process controller or a manual input potentiom-eter.Aswitchisusedtoselectbetween the input from a 1K potentiometer and a linear controlinput(seeFig.4onpage21).Theunitisshippedwithajumperfromterminals2and3ofterminalblockJ2(seeillustra-tion3).Removejumpertoinstallauto/manual input.
Demand IndicatorTheLEDdemandindicatorislocatedonthemainPCboardandisviewablethroughthecover.WiththeOn/Offcontroloption,theindicatorwilldisplaysteady“on”andsteady“off”.WiththeDOTFiringoption, the indicator will display the rapid firing sequence.
IMPORTANT: WhenenablingtheAuto/ManualInput,thejumperfromterminals2and3ofterminalblockJ2mustberemoved.
CAUTION
Illustration 3
NC NOCONTACTNORMALLY CLOSED
(SWNC)
CONTACTNORMALLY OPEN(SWNO)
SWITCHASSEMBLY(SW)
PANEL TO BEMOUNTED TO
LEGENDPLATE(LP)
AUTO HAND
SWITCH KNOB(SW)
AUTO HAND
WIRING
1
4
NC NO
1KPOTENTIOMETER
��
CW
2
3
- 18 - © 2014 Chromalox®, Inc. 1-888-996-9258
SCR Control Board TheBasiccontrolboardprovidesthefollowingfunctions: Thelowvoltagedctooperatethecircuitry: Aswitchingregulatorcircuitconvertstheinstrumentpowervoltageto+12Vdc.
Thepowerdistributionforthecoolingfans: The incoming instrument power is fused and then routed to the fan power terminals.
Thesignalconditionfortheon/offinputandanaloginputs: The120to240on/offinputisisolatedbyanopto-coupler.Thedcandcontact closureinputsarebufferedbythecircuitry.Amplifiersconverttheanaloginputsand the potentiometer input to a signal level compatible with the optional proportional firing board. The plug-in receptacle for the optional proportional board allows for an easy upgrade to proportional control.
ThedrivesignaltotheSCRtriggerboards: Thetemperaturealarm: The heat sink temperature is derived from a solid state sensor mounted on the heat sink. This is then compared to two set points. The first alarm is a warning and activates the externally connected device. This allows time to correct the problem before the second alarm inhibits the firing circuit. TheShortedSCRAlarm: The plug-in receptacle for the shorted SCR board is located on this board. Signals fromtheSCRareroutedtotheoptionboard.Whenashortisdetectedtheexternally connected device output is activated.
2AMP(2AG)CHROMALOXP/N0024-01097LITTLEFUSEP/N225002
( @ )
( )
( )
( )
- 19 -© 2014 Chromalox®, Inc.1-888-996-9258
Proportional DOT Firing Board
Chromalox’sexclusiveDOT(De-mandOrientedTransfer)firingtech-nique switches the fewest number of cycles to provide the most pre-cisezerocrossovercontrol.At50%output, the unit’s output alternates betweenonecycle“On”andonecycle“Off.”At51%,theoutputcontinueswithonecycle“On,”onecycle“Off,”andgraduallyinte-gratesoneextra“On”cyclefortheadditional1%.
Remote Shutdown
Whenitisnecessarytodisabletheoutput,connectadrycontactbetweenJ3-3&4(seeFig.12onpage21).Whenitisclosed,thepowercontrolwillshutOFF.
Shorted SCR Detection (optional)
Thisoptionprovidesameansofalertinganoperatortoaproblemwiththesystem.AnexternalindicatinglamporrelaycanbeconnectedtoJ1-5&6(seeFig.2onpage21).ThisindicatormustberatedfortheinstrumentpowerappliedtoJ1-1&2.ThreediagnosticLEDsshowwhichSCRpairisfaulted.Theselightsaresynchronizedwiththedemandindicatorandcanonlyindicatewhilethedemandisactive.ShortingJ3-5&6candisabletheoutputatJ1-5&6.Thealarmcanbeselectedas latching or non-latching.
Alatchingalarmmeansthatifthealarmactivatesandthesystemsubsequentlyreturnstonormal,thealarmwillremainlatcheduntilaresetbutton(externalswitch–customerprovided)ispressed.Anon-latching alarm resets automatically.
IMPORTANT: Thisshutdownoverridesthecontrolinputonly.ItwillNOTprotectagainst faulted or damaged SCRs.
CAUTION
SHORTEDSCRDETECTION
DEMAND
1 2 3
SHORTJ3-1&2FOR1CYCLEFIRING
SHORTJ3-2&3FOR3CYCLEFIRING
Unitshippedfor3cycleoperation
-20- © 2014 Chromalox®, Inc. 1-888-996-9258
Shorted SCR Detection (optional), cont’d.
Thelatchingandnon-latchingoptionisjumperselectable;thejumperislocatedontheplug-inshortedSCRdetectionboard.Latchingandnon-latchingoperationbytheoutputatJ1-5&6iscontrolledbyJ3ontheshortedSCRdetectionboard0135-28096.Whenthisjumperisinstalled,latchingoperationisachieved.ThedrawingbelowshowstheShortedSCRDetectionboard.
Heat Sink Over-Temperature
AnexternallamporrelaymaybeconnectedtoJ1-3&4(seeFig.2onpage21)(thismustberatedfortheinstrumentpowerappliedtoJ1-1&2).Thiswillprovideanindicationtotheoperatorthatthe heat sink is approaching an unsafe temperature level. The unit will enter a shutdown mode if the temperature continues to rise.
UNIT SHIPPED IN NON-LATCHING MODE.
-21-© 2014 Chromalox®, Inc.1-888-996-9258
Input Terminals (MaxPac I, II, and III):
120~240 ON/OFF CONTROL
4-20mA PROPORTIONAL INPUT SIG
COMMON4-20mAPROPORTIONALINPUT
66
0 TO +5 VDC PROPORTIONAL INPUT SIG
0TO+5VDCPROPORTIONALINPUT
5
12
43
J3
6
COMMON
109
78
0 +10 VDC PROPORTIONAL INPUT SIG
0+10VDCPROPORTIONALINPUT
J3
5
21
34
6
COMMON
109
78
5
21
34
J3
6
45
23
J21
MANUAL CONTROL INPUT SIG
10
789
65
AUTO
POTREFVOLTAGE
COMMONJ2
2
43
1
MANUAL
1-5 VDC PROPORTIONAL INPUT SIG
1-5VDCPROPORTIONALINPUT
45
23
1J2
10
COMMON789
65
J1
10
789
65
1 K
J2
2
43
1J2
2
43
1
J1 J3
120~230INSTRUMENTPOWER
REQUIRED ON ALL CONFIGURATIONS120~230 INSTRUMENT POWER
J1
SHORTED SCR ANDHI TEMP INDICATORS.
SHORTED SCR INDICATOR RESET.
FIG12.
FIG9.
FIG6.
L2
COMMON
REMOTE SHUTDOWNEXTERNAL +5~32 VDC ON/OFF
COMMON
FIG10.
+ -
DRY CONTACT ON/OFF
FIG11.
+
FIG7.
FIG4.
FIG8.
+
L1
FIG5.
JUMPER
EXTERNAL120~230
FIG2. FIG3.FIG1.
12345678
12345678
HITEMPINDICATOR.
SHORTEDSCRINDICATOR.
123456
12345678
JUMPER
JUMPER JUMPER ON/OFFCONTROL
TheseareACvoltageoutputsat100mAmax.,not contact closures. See model numberfor voltage rating.
-22- © 2014 Chromalox®, Inc. 1-888-996-9258
MaxPac IP
TheChromaloxMaxPacIPisasolid-stateproportionalpowercontrollerthatutilizesaPhaseAnglefiringtechniquetomodulatepowertoaninductiveorresistiveload.SeparateadjustableZero,Gain,ManualBias,andCurrentLimitpotentiometersareprovidedalongwithscrewtypeplug-inconnectorsforinputsignals,EmergencyShutdown,andoptionalRemoteManualBiaswith0 - 100%dial.Allunitshavethermostatpro-tectionwithN.C.contacts.
Start-up
TheMaxPacIPhasbeenfactorycalibratedfor4-20mAinput.Besuretheoperatingvoltageandsignalinputarecorrectlyapplied.Also,makesuretheEmergencyShutdown,ifused,hasN.O.contactsandjumperpins4&5onthe10-pinconnectorifremotemanualbiasarenotused.Pleaseread the information on calibration at the end of this section for current limit settings for loads with extremehottocoldratiosorthosethatareoverrated.Otherrangesmaybefieldcalibratedbyuse ofzeroandgainpotentiometers.
IMPORTANT: WiththeCurrentLimitoption,thecurrenttransformermustbeter-minated properly to prevent it from being damaged.
CAUTION
0-5MA(0-10V)
4-20mA
10-50mACOM
CLOSE FORREMOTE
SHUTDOWN
N/C
N/C
JUMPER 4 TO 5WHEN NOT USINGREMOTE POT
UNIT SHIPPED WITH JUMPER INSTALLED
INSTRUMENTWIRE
LOAD
SCR
FUSE
X1
L2
L1
CT
TB1CON1P
JB1JUMPER JB1 FOR 0-5mAOPEN JB1 FOR 0-10V
Customer Connection
-23-© 2014 Chromalox®, Inc.1-888-996-9258
1.SetCurrentLimit(ILIM)potto0%forfullcurrentoutput(CCW).
CurrentLimitisforlimitingcurrentforloadsthathave
extremehottocoldresistanceratiosorareoverrated.We
recommendforthesetypesofloadstoadjustILIM(Cur-
rentLimit)to50%orless.Thiswillalsodecreasevoltage
aswellascurrent.0%CurrentLimitgives100%current
output(CCW).100%CurrentLimitgives10%current
output(CW).
2.SetManual(MAN)pottozerosounitwillnotbebiasedabove
input(CCW).
Manualcontroladjustmentprovidesameansofsetting
the output level of the MaxPac Power Pak in the absence
of controlling instrumentation. The manual control signal
value“adds”tothecontrollinginstrumenttosetmini-
mum output. The desired output power level may be set
byadjustingthemanualcontrol.Thisvalueofoutputwill
then be present even in the absence of a control signal.
3.SetRemoteManualpottozerooutputsounitwillnotbebiased
aboveinput(CCW).(Jumperpins4&5ifnotused.)
RemoteManualcontroladjustmentprovidesameans
of setting the output level of the MaxPac Power Pak in
the absence of controlling instrumentation. The Remote
Manual control is also effective when a control signal
is connected. The Remote Manual control signal value
“adds”tothecontrollinginstrumenttosetminimum
output. The desired output power level may be set by
adjustingtheRemoteManualcontrol.Thisvalueofout-
put will then be present even in the absence of a control
signal.ConnectRemoteManualpotwiretoPin4(CCW),
Pin5(W),andPin6(CW)ofplug-inconnector.
4.CheckforopencontactforEmergencyShutdown.
EmergencyShutdowninhibitsallSCRtriggerpulses
regardless of the level of the input signal or manual
potentiometer.ForEmergencyShutdown,closecontact
Pin7toPin8ofplug-inconnector.Leavecontactsopen
for operation.
5.Checkforpolarityofinputsignal.
6.Adjustinputsignaltolowendofscale.
ZeroAdjustcontrolsetsthepoweroutputstartingpoint
or reference. Thus, it effectively cancels positive inputs
to the MaxPac Power Pak.
EXAMPLE: 0-5mAinputàsetto0mAinput
4-20mAinputàsetto4mAinput
7.Withpoweroff,connectlinevoltageandloadasshown.
8. Connect meter to input and output.
WARNING:Setmetertocorrectscaletoreadproperinput
or output.
9.Applypowertounit.
10.Adjustinputsignaltolowendofscale.
11.UsingtheZeropot,adjusttheoutputvoltagejusttozerovolts.
12.Adjustinputsignaltotopendofscale.
GainAdjustControlsetsthemaximumpoweroutputfor
maximum input signal.
EXAMPLE: 0-5mAinput:setto5mAinput
4-20mAinput:setto20mAinput
13.UsingtheGainpot,adjustoutputvoltagejusttomaximum
volts.
14.Repeatsteps11,12,13,and14untilnoadjustmentis
necessaryofZeroandGainpotsforproperoutputvoltage
indication.Voltageoutputshouldincreaseproportionallytothe
signal input applied.
15.Adjustinputsignaltolowendofscale(zerovoltageoutput).
16.WithManualpotatzeroforzerovoltageoutput,adjust(CW)
to100%forfullvoltageoutput.Voltageoutputshould
increaseproportionally.ReturntoCCWpositionandoutputwill
decreasetozerooutput.
17.WithRemoteManualatzeroforzerovoltageoutput,adjust
(CW)to100%forfullvoltageoutput.Voltageoutputshould
increaseproportionally.ReturntoCCWpositionandoutputwill
decreasetozerooutput.
18.WithManualpot(CW)at100%andILIM(CurrentLimit)at
0%, adjustILIMtowards100%notingthatvoltage
outputde creaseswiththeadjustmentofthe
CurrentLimitpot.Adjust CurrentLimitpotforyour
application, if needed.
19.TurnPOWEROFFandremovemeters.TESTCOMPLETE.
4.2.6 - Calibration (MaxPac IP):Many high-temperature heating elements exhibit extreme hot to cold resistance ratios. Heating elements composed of Platinum,
Molybdenum,Tungsten,andTantalum,tonameafew,drawexcessivecurrentonstart-up.Dependingonthemassoftheelements,
these“highstartingcurrents”mayexistforextendedperiodsoftime.Generally,oncetheelementshaveachievedtheirnormaloperat-
ing temperatures, the current drawn through the MaxPac Power Pak will fall within the rating of the unit. For these types of loads, we
recommendadjustingtheILIM(CurrentLimit)to50%orless.Thiswilldecreasevoltageaswellascurrent.
-24- © 2014 Chromalox®, Inc. 1-888-996-9258
5Specifications
Control InputsAcceptsallofthefollowingasstandards:
On/Off ControlSignalInput120thru230Vac±10%5-32VdcContact Closures
Proportional ControlSignalInput InputImpedance4-20mA ................. 250Ohms1-5Vdc .................. 10kOhmsorgreater0-5Vdc .................. 10kOhmsorgreater0-10Vdc ................ 10kOhmsorgreater
OptionalRemoteManualAdjustAuto/ManualSwitch
Instrument Power ...... 120or230Vac 50/60Hz
Output Voltage ........... 0-99%RMSlinevoltage (Eo=Vsupply-1.5VSCR forwarddrop)
Resolution (proportional)Betterthan0.1%
Line Voltage ...................120-575Vac,60Hz CE400Vac50Hz
Load Current Rating ......100,150,200,300,400, 550,650,800,1000,1200A
Ambient Temperature ....0-50°C(32-122°F)
SCR Capability Dielectric .................Withstandcapability Surge Rating 1500VRMSmin. Typicallyfifteen(15)times nominal RMS rating for 8.3milliseconds
Isolation .....................SCRsisolation2500V Input-outputisolation1500V
Heat Sink ........................Groundpotentialupto 650Amps
High Temperature ..........ACVoltageOutputIndicator Output 100mA@InstrumentPower
Shorted SCR ..................ACVoltageOutputIndicator Output 100mA@InstrumentPower
MaxPac I, II, and III
MaxPac IPControl InputsAcceptsallofthefollowingasstandards:
Phase Angle ControlSignalInput InputImpedance1-5,0-5mA .......... 1KOhms4-20,0-20mA ...... 250Ohms10-50,0-50mA .... 100Ohms
OptionalRemoteManualAdjust
Fan Power .................. 120or230VAC 50/60Hz
Output Voltage ........... 0-99%RMSlinevoltage (Eo=Vsupply-1.5VSCR forwarddrop)
Resolution (proportional)Betterthan0.1%
Line Voltage ............... 120,208,240,277,380,...................................... 480 and575Vac ±10%50/60Hz
Load Current Rating .. 100,150,200,300,400, 550,650,800,1000,1200A
Ambient Temperature ....0-50°C(32-122°F)
SCR Capability ...............Withstandcapability 1500VRMSmin. Typicallyfifteen(15)times nominal RMS rating for 8.3milliseconds
Surge Rating ..................Typicallyfifteen(15)times nominal RMS rating for 8.3milliseconds
Isolation ..........................SCRsisolation2500V Input-outputisolation1500V
Heat Sink ........................Groundpotentialupto 650Amps
Thermostat .....................4Amps@120Vresistive 2Amps@240Vresistive N.C.ContactStandard
Current Limit ..................10-100%ofrated output current
Soft Start ........................25%demandpersecond typical reset speed 8.3milliseconds
-25-© 2014 Chromalox®, Inc.1-888-996-9258
6Maintenance
Connections –Looseconnectionsinthepowerwiringwillgeneratehotspots.Thesewillcausedegradationof electronic equipment. Periodic inspections should be made to ensure that connections are secure and that there are no signs of excessive heating such as discoloration, and so on.
Corrosion–Ifthepowermoduleisinstalledinanenvironmentwithhighhumidityordampness,electricalconnections may suffer corrosion. Periodically check the power module for corrosion.
Damage – Periodically check for rodent damage to wiring and other components.
Filters – Many high-powered control enclosures rely on blowers or fans to maintain a safe operating temper-ature. The filters used with these devices should be changed on a periodic basis to insure adequate enclo-sure cooling is maintained.
Dust – Periodically check for dust or other particulate buildup on heatsinks and bus bars.
WARNING
Hazardous Voltage: Disconnectallpowerbeforeperforminganymaintenanceorexaminingthepowermodule.ExposedterminalsmaycarryLETHALLYHIGHVOLTAGESwhenpowerisapplied.
-26- © 2014 Chromalox®, Inc. 1-888-996-9258
7Troubleshooting
The following guidelines cover most of the common problems that could occur with the MaxPac. They are not intended to be, nor can they be, absolutes to cover every possible failure.
Problem
No Power or unbalanced power to the load. IfDemandLightis“Off”
1. Check incoming line power.2. Checktheinstrumentpower.3. Checkthefuseonthemainboard.4. Verifytheinputsignal.5. CheckthatremoteshutdownJ3-3to4isopen.6. CheckthattheJ2-2to3isJumpered.7. Verifythatheatsinkisnotinovertemperaturemodebyremovingtemperaturesensor plugsfromJ10,J11,andJ12.
IfDemandLightis“On”1. Check the connections to SCR trigger board.2. Checkthepowerfuses(I2t).3. Lookfordamageonthetriggerboard.
-27-© 2014 Chromalox®, Inc.1-888-996-9258
8Parts and Accessories
Instrument Power Fuse Chromalox Part Number Description 0024-01097 Littlefuse#2250022AG2AMPI2T Fuses for 500 Vac Applications 0024-07634 200AmpI2t Fuse 0024-07630 250AmpI2t Fuse 0024-07632 400AmpI2t Fuse 0024-03116 500AmpI2t Fuse 0024-07633 700AmpI2t Fuse 0024-03118 800AmpI2t Fuse 0024-03200 1000AmpI2t FuseI2T Fuses for 575 Vac Applications 0024-07644 125AmpI2t Fuse 0024-07645 175AmpI2t Fuse 0024-07636 250AmpI2t Fuse 0024-07637 400AmpI2t Fuse 0024-07638 500AmpI2t Fuse 0024-07639 700AmpI2t Fuse 0024-07640 800AmpI2t Fuse 0024-07646 1000AmpI2t Fuse 0024-01191 1200AmpI2t Fuse
Fans Chromalox Part Number Description 0045-00231 120VacratedFan 0045-00235 230VacratedFan
Crimp Lug Chart ForOpenDesign400-1200AmpandallTouch-SafeModels:
Conductor Size Chromalox Part # Panduit Part ##8AWG(10mm2) 0135-10002 LCD8-14A-L#6AWGor#6Weld(16mm2) 0135-10003 LCD6-14A-L#4AWGor#4Weld(25mm2) 0135-10004 LCD4-14A-L#2AWG(35mm2) 0135-10005 LCD2-56B-Q#1AWGor#2Weld(50mm2) 0135-10006 LCD1-56C-E#1/0AWGor#1Weld(70mm2) 0135-10007 LCD1/0-12-X#2/0AWGor#1/0Weld(70mm2) 0135-10008 LCD2/0-12-X#3/0AWGor#2/0Weld(95mm2) 0135-10009 LCD3/0-12-X#4/0AWGor#3/0Weld(120mm2) 0135-10010 LCD4/0-12-X250MCMor#4/0Weld(150mm2) 0135-10011 LCD250-12-X300MCM(150mm2) 0135-10012 LCD300-12-X350MCM(185mm2) 0135-10013 LCD350-12-6400MCM(240mm2) 0135-10014 LCD400-12-6500MCM(240mm2) 0135-10015 LCD500-12-6
SCR ReplacementBesuretoreplacethermstrateinterfacematerialandtorqueasfollows:
MFG Part # SCR Part # Thermstrate Part # Torque inch/lb Torque inch/lb to Heat Sink to TerminalsSKKT92 0002-47560 0029-00700 44inch/lb(5Nm) 26inch/lb(3Nm)SKKT162 0002-47559 0029-00822 44inch/lb(5Nm) 44inch/lb(5Nm)SKKT250 0002-47537 0029-00719 44inch/lb(5Nm) 80inch/lb(9Nm)SKKT500 0002-47557 0029-00814 44inch/lb(5Nm) 106inch/lb(12Nm)
MaxPac I, II, and IIIAccessories:
Part Number Description0135-28096 Plug-InShortedSCRDetectionBoard0135-28095 Plug-InProportionalDOT-FiredControlBoard0135-28093 SCRTriggerBoard0135-28094 On/OffMainFiringBoard0135-20117 Potentiometer&Remote/ManualSwitch
For CE Application, the Following Filters are Required:0005-60055 LineFilterSinglePhase230Vac0005-60057 LineFilter120-230Vac3Amps0005-60056 LineFilterThreePhase440Vac
MaxPac IPAccessories:
Part Number Description0135-28002 FiringCircuit120,240Vac0135-28006 FiringCircuit208,277,480Vac0135-28037 FiringCircuit380Vac
-28- © 2014 Chromalox®, Inc. 1-888-996-9258
9Warranty and Return Information
Warranty NoticeTheWarrantybelowcomplieswiththefederallawapplicabletoproductsmanufacturedafterDecember31,1976.Thiswarrantygivesyouspecificlegalrightsandyoumayalsohaveotherrightswhichvaryfromstateto state.
Chromalox WarrantyChromaloxinstrumentsandcontrolsarewarrantedagainstdefectsinworkmanshipandmaterials.Nootherexpress warranty, written or oral, applies with the exception of a written statement from an officer of Chro-malox®,Inc.
Warranty PeriodThiswarrantyextendsforthreeyearsfromdateofshipmentfromthefactoryorauthorizeddistributor.
LimitationsProducts must be installed and maintained in accordance with Chromalox instructions. Users are responsi-ble for the suitability of the products to their application. There is no warranty against damage resulting from corrosion, misapplication, improper specification or other operating conditions beyond our control. Claims against the carrier company for damage in transit must be filed by the buyer.
ReturnsItemsreturnedtoChromaloxmustbeaccompaniedbyaReturnAuthorizationNumber.ThisnumbermaybeobtainedfromChromalox’CustomerServiceDepartmentatthephonenumberlistedbelow.
TheReturnAuthorizationNumbermustappearontheexterioroftheshippingcartonandontheshippingdocuments.
Defectiveitemswillberepairedorreplacedatouroptionandatnocharge.
Returnthedefectivepartorproduct,freightprepaid,tothefollowingaddress:Chromalox,Inc.1347HeilQuakerBlvd.LaVergne,TN37086-3536
Phone:(615)793-3900Fax:(615)793-3563
-29-© 2014 Chromalox®, Inc.1-888-996-9258
Ordering Information for MaxPac IModel SCR Power Pack
MXPC I Single Phase SCR Power Pack
Code Control Configuration
1 On/OffStandard(Accepts:120Vac,240Vac,5-32Vdc,DryContactClosure) 2 On/OffControlwithShortedSCRDetection 3 ProportionalControl,DOTFiring(Accepts:4-20mA,1-5Vdc,0-5Vdc,0-10Vdc) 4 ProportionalControl,DOTFiringwithShortedSCRDetection
Code Current at 50°C (122°F)
01 100Amp OpenDesign 02 100Amp TouchSafeDesign 03 150Amp OpenDesign 04 150Amp TouchSafeDesign
05 200Amp OpenDesign 06 200Amp TouchSafeDesign 07 300Amp OpenDesign 08 300Amp TouchSafeDesign
09 400Amp OpenDesign 10 400Amp TouchSafeDesign 11 550Amp OpenDesign 12 550Amp TouchSafeDesign
13 650Amp OpenDesign 14 650Amp TouchSafeDesign 15 800Amp OpenDesign 16 1000Amp OpenDesign 17 1200Amp OpenDesign
Code Line Voltage
1 120Vac-480Vac 2 575Vac
Code Instrument Power
1 120Vac50/60Hz 2 230Vac50/60Hz
Code Compression Lug Kits (Open Design up to 300 Amps)
ForOtherRangesSeeCrimpLugChart
L0 None L1 100-150AmpPAK1(#2-4/0)/connection L2 200-300AmpPAK1(1/0-500mcm)/connection
MXPC I - 2 03 1 1 L1 (Continued on next page)
-30- © 2014 Chromalox®, Inc. 1-888-996-9258
Ordering Information for MaxPac I (continued)
Code Fusing Option (1)
For<500VacApplications,SelectOne F00 None F01 100-150AmpPAK (200AmpFuse) F02 200AmpPAK (250AmpFuse) F03 300AmpPAK (400AmpFuse)
F04 400AmpPAK (500AmpFuse) F05 550AmpPAK (700AmpFuse) F06 650AmpPAK (800AmpFuse) F07 800AmpPAK (1000AmpFuse)
F08 1000AmpPAK (1200AmpFuses) F09 1200AmpPAK (Two1000AmpFuses)
For575VacApplications,SelectOne(2) F10 100AmpPAK (125AmpFuse) F11 150AmpPAK (175AmpFuse)
F12 200AmpPAK (250AmpFuse) F13 300AmpPAK (400AmpFuse) F14 400AmpPAK (500AmpFuse) F15 550AmpPAK (700AmpFuse)
F16 650AmpPAK (800AmpFuse) F17 800AmpPAK (1000AmpFuse) F18 1000AmpPAK (1200AmpFuse) F19 1200AmpPAK (Two1000AmpFuses)
Code Remote Man. Adjust/Auto Man. Switch
0 None 1 Potwith0-100%dialandLocal/Remote Switch(2)SingleTurn1KW Potentiometer
MXPC I - 2 03 1 1 L1 F01 1 Typical Model Number
Crimp Lug Chart
Chromalox # Panduit # Conductor Size
Torque
In-Lb. Nm0135-10002 LCD8-14A-L #8AWG 180 200135-10003 LCD6-14A-L #6AWGor#6Weld 180 200135-10004 LCD4-14A-L #4AWGor#4Weld 180 200135-10005 LCD2-56B-Q #2AWG 180 200135-10006 LCD1-56C-E #1AWGor#2Weld 180 200135-10007 LCD1/0-12-X #1/0AWGor#1Weld 480 540135-10008 LCD2/0-12-X #2/0AWGor#1/0Weld 480 540135-10009 LCD3/0-12-X #3/0AWGor#2/0Weld 480 540135-10010 LCD4/0-12-X #4/0AWGor#3/0Weld 480 540135-10011 LCD250-12-X 250MCMor#4/0Weld 480 540135-10012 LCD300-12-X 300MCM 480 540135-10013 LCD350-12-6 350MCM 480 540135-10014 LCD400-12-6 400MCM 480 540135-10015 LCD500-12-6 500MCM 480 54
Note:NEMAstandardtwoholecoppercrimplugsonly.
1) SCRFusingisforsemiconductor protection only, not wire protection.
2) SuppliedLooseforCustomer Mounting.
Note:StorageTemperature14ºFto158ºF(-10ºCto70ºC).CEapplicationrequiresfilters.
Chromalox Part Numbers0005-60055:Linefilter,singlephase, 230VAC0005-60057:Linefilter,120-230VAC
-31-© 2014 Chromalox®, Inc.1-888-996-9258
Ordering Information for MaxPac IPModel SCR Power Pack
MXPC IP Single Phase SCR Power Pack
Code Control Configuration
1 PhaseAngleControl (Accepts:0-5mA,0-20mA,0-50mA,105mA,4-20mA,10-50mA,0-5Vdc,0-10Vdc) 2 PhaseAngleControlwithCurrentLimit
Code Current at 50°C (122°F)
01 100 AmpOpenDesign 02 100 AmpTouchSafeDesign 03 150 AmpOpenDesign 04 150 AmpTouchSafeDesign
05 200 AmpOpenDesign 06 200 AmpTouchSafeDesign 07 300 AmpOpenDesign 08 300 AmpTouchSafeDesign
09 400 AmpOpenDesign 10 400 AmpTouchSafeDesign 11 550 AmpOpenDesign 12 550 AmpTouchSafeDesign
13 650 AmpOpenDesign 14 650 AmpTouchSafeDesign 15 800 AmpOpenDesign 16 1000 AmpOpenDesign 17 1200 AmpOpenDesign
Code Voltage
1 120Vac 2 208Vac 3 240Vac 4 277Vac 5 480Vac 6 575Vac
Code Fan Power
1 120 Vac 50/60 Hz 2 230 Vac 50/60 Hz
Code Compression Lug Kits (OpenDesignupto300Amps)
ForOtherRangesSeeCrimpLugChart
L0 None L1 100-150AmpPAK1(#2-4/0)/connection L2 200-300AmpPAK1(1/0-500mcm)/connection
MXPC IP - 2 03 1 1 L1 (Continued on next page)
-32- © 2014 Chromalox®, Inc. 1-888-996-9258
Ordering Information for MaxPac IP (continued)
Code Fusing Option (1)
For<500VacApplications,SelectOne F00 None F01 100-150AmpPAK (200AmpFuse) F02 200AmpPAK (250AmpFuse) F03 300AmpPAK (400AmpFuse)
F04 400AmpPAK (500AmpFuse) F05 550AmpPAK (700AmpFuse) F06 650AmpPAK (800AmpFuse) F07 800AmpPAK (1000AmpFuse)
F08 1000AmpPAK (1200AmpFuses) F09 1200AmpPAK (Two1000AmpFuses)
For575VacApplications,SelectOne(2) F10 100AmpPAK (125AmpFuse) F11 150AmpPAK (175AmpFuse)
F12 200AmpPAK (250AmpFuse) F13 300AmpPAK (400AmpFuse) F14 400AmpPAK (500AmpFuse) F15 550AmpPAK (700AmpFuse)
F16 650AmpPAK (800AmpFuse) F17 800AmpPAK (1000AmpFuse) F18 1000AmpPAK (1200AmpFuse) F19 1200AmpPAK (Two1000AmpFuses)
Code Remote Man. Adjust/Auto Man. Switch
0 None 1 Potwith0-100%dialandLocal/Remote Switch(2)SingleTurn1KW Potentiomete
MXPC IP - 2 03 1 1 L1 F01 1 Typical Model Number
Crimp Lug Chart
Chromalox # Panduit # Conductor Size
Torque
In-Lb. Nm0135-10002 LCD8-14A-L #8AWG 180 200135-10003 LCD6-14A-L #6AWGor#6Weld 180 200135-10004 LCD4-14A-L #4AWGor#4Weld 180 200135-10005 LCD2-56B-Q #2AWG 180 200135-10006 LCD1-56C-E #1AWGor#2Weld 180 200135-10007 LCD1/0-12-X #1/0AWGor#1Weld 480 540135-10008 LCD2/0-12-X #2/0AWGor#1/0Weld 480 540135-10009 LCD3/0-12-X #3/0AWGor#2/0Weld 480 540135-10010 LCD4/0-12-X #4/0AWGor#3/0Weld 480 540135-10011 LCD250-12-X 250MCMor#4/0Weld 480 540135-10012 LCD300-12-X 300MCM 480 540135-10013 LCD350-12-6 350MCM 480 540135-10014 LCD400-12-6 400MCM 480 540135-10015 LCD500-12-6 500MCM 480 54
Note:NEMAstandardtwoholecoppercrimplugsonly.
1) SCRFusingisforsemiconductor protection only, not wire protection.
2) SuppliedLooseforCustomer Mounting.
Note:StorageTemperature14ºFto158ºF(-10ºCto70ºC).CEapplicationrequiresfilters.
Chromalox Part Numbers0005-60055:Linefilter,singlephase, 230VAC0005-60057:Linefilter,120-230VAC
-33-© 2014 Chromalox®, Inc.1-888-996-9258
Ordering Information for MaxPac IIModel SCR Power Pack
MXPC II Three Phase SCR Power Pack
Code Control Configuration
1 On/OffStandard(Accepts:120Vac,240Vac,5-32Vdc,DryContactClosure) 2 On/OffControlwithShortedSCRDetection 3 ProportionalControl,DOTFiring(Accepts:4-20mA,1-5Vdc,0-5Vdc,0-10Vdc) 4 ProportionalControl,DOTFiringwithShortedSCRDetection
Code Current at 50°C (122°F)
01 100Amp OpenDesign 02 100Amp TouchSafeDesign 03 150Amp OpenDesign 04 150Amp TouchSafeDesign
05 200Amp OpenDesign 06 200Amp TouchSafeDesign 07 300Amp OpenDesign 08 300Amp TouchSafeDesign
09 400Amp OpenDesign 10 400Amp TouchSafeDesign 11 550Amp OpenDesign 12 550Amp TouchSafeDesign
13 650Amp OpenDesign 14 650Amp TouchSafeDesign 15 800Amp OpenDesign 16 1000Amp OpenDesign 17 1200Amp OpenDesign
Code Line Voltage
1 120Vac-480Vac 2 575Vac
Code Instrument Power
1 120Vac50/60Hz 2 230Vac50/60Hz
Code Compression Lug Kits (Open Design up to 300 Amps)
ForOtherRangesSeeCrimpLugChart
L0 None L1 100-150AmpPAK1(#2-4/0)/connection L2 200-300AmpPAK1(1/0-500mcm)/connection
MXPC II - 2 03 1 1 L1 (Continued on next page)
-34- © 2014 Chromalox®, Inc. 1-888-996-9258
Ordering Information for MaxPac II (continued)
Code Fusing Option (1)
For<500VacApplications,SelectOne F00 None F01 100-150AmpPAK (200AmpFuse) F02 200AmpPAK (250AmpFuse) F03 300AmpPAK (400AmpFuse)
F04 400AmpPAK (500AmpFuse) F05 550AmpPAK (700AmpFuse) F06 650AmpPAK (800AmpFuse) F07 800AmpPAK (1000AmpFuse)
F08 1000AmpPAK (1200AmpFuses) F09 1200AmpPAK (Two1000AmpFuses)
For575VacApplications,SelectOne(2) F10 100AmpPAK (125AmpFuse) F11 150AmpPAK (175AmpFuse)
F12 200AmpPAK (250AmpFuse) F13 300AmpPAK (400AmpFuse) F14 400AmpPAK (500AmpFuse) F15 550AmpPAK (700AmpFuse)
F16 650AmpPAK (800AmpFuse) F17 800AmpPAK (1000AmpFuse) F18 1000AmpPAK (1200AmpFuse) F19 1200AmpPAK (Two1000AmpFuses)
Code Remote Man. Adjust/Auto Man. Switch
0 None 1 Potwith0-100%dialandLocal/Remote Switch(2)SingleTurn1KW Potentiometer (RequiresProportionalBand)
MXPC II - 2 03 1 1 L1 F01 1 Typical Model Number
Crimp Lug Chart
Chromalox # Panduit # Conductor Size
Torque
In-Lb. Nm0135-10002 LCD8-14A-L #8AWG 180 200135-10003 LCD6-14A-L #6AWGor#6Weld 180 200135-10004 LCD4-14A-L #4AWGor#4Weld 180 200135-10005 LCD2-56B-Q #2AWG 180 200135-10006 LCD1-56C-E #1AWGor#2Weld 180 200135-10007 LCD1/0-12-X #1/0AWGor#1Weld 480 540135-10008 LCD2/0-12-X #2/0AWGor#1/0Weld 480 540135-10009 LCD3/0-12-X #3/0AWGor#2/0Weld 480 540135-10010 LCD4/0-12-X #4/0AWGor#3/0Weld 480 540135-10011 LCD250-12-X 250MCMor#4/0Weld 480 540135-10012 LCD300-12-X 300MCM 480 540135-10013 LCD350-12-6 350MCM 480 540135-10014 LCD400-12-6 400MCM 480 540135-10015 LCD500-12-6 500MCM 480 54
Note:NEMAstandardtwoholecoppercrimplugsonly.
1) SCRFusingisforsemiconductor protection only, not wire protection.
2) SuppliedLooseforCustomer Mounting.
Note:StorageTemperature14ºFto158ºF(-10ºCto70ºC).CEapplicationrequiresfilters.
Chromalox Part Numbers0005-60055:Linefilter,threephase, 440VAC0005-60057:Linefilter,120-230VAC
-35-© 2014 Chromalox®, Inc.1-888-996-9258
Ordering Information for MaxPac IIIModel SCR Power Pack
MXPC III Three Phase Six SCR Power Pack
Code Control Configuration
1 On/OffStandard(Accepts:120Vac,240Vac,5-32Vdc,DryContactClosure) 2 On/OffControlwithShortedSCRDetection 3 ProportionalControl,DOTFiring(Accepts:4-20mA,1-5Vdc,0-5Vdc,0-10Vdc) 4 ProportionalControl,DOTFiringwithShortedSCRDetection
Code Current at 50°C (122°F)
01 100Amp OpenDesign 02 100Amp TouchSafeDesign 03 150Amp OpenDesign 04 150Amp TouchSafeDesign
05 200Amp OpenDesign 06 200Amp TouchSafeDesign 07 300Amp OpenDesign 08 300Amp TouchSafeDesign
09 400Amp OpenDesign 10 400Amp TouchSafeDesign 11 550Amp OpenDesign 12 550Amp TouchSafeDesign
13 650Amp OpenDesign 14 650Amp TouchSafeDesign 15 800Amp OpenDesign 16 1000Amp OpenDesign 17 1200Amp OpenDesign
Code Line Voltage
1 120Vac-480Vac 2 575Vac
Code Instrument Power
1 120Vac50/60Hz 2 230Vac50/60Hz
Code Compression Lug Kits (Open Design up to 300 Amps)
ForOtherRangesSeeCrimpLugChart
L0 None L1 100-150AmpPAK1(#2-4/0)/connection L2 200-300AmpPAK1(1/0-500mcm)/connection
Note:550-1200AmpandallTouch-SafeDesigns:Buss
MXPC III - 1 04 1 1 L1 (Continued on next page)
-36- © 2014 Chromalox®, Inc. 1-888-996-9258
Ordering Information for MaxPac III (continued)
Code Fusing Option (1)
For<500VacApplications,SelectOne F00 None F01 100-150AmpPAK (200AmpFuse) F02 200AmpPAK (250AmpFuse) F03 300AmpPAK (400AmpFuse)
F04 400AmpPAK (500AmpFuse) F05 550AmpPAK (700AmpFuse) F06 650AmpPAK (800AmpFuse) F07 800AmpPAK (1000AmpFuse)
F08 1000AmpPAK (1200AmpFuses) F09 1200AmpPAK (Two1000AmpFuses)
For575VacApplications,SelectOne(2) F10 100AmpPAK (125AmpFuse) F11 150AmpPAK (175AmpFuse)
F12 200AmpPAK (250AmpFuse) F13 300AmpPAK (400AmpFuse) F14 400AmpPAK (500AmpFuse) F15 550AmpPAK (700AmpFuse)
F16 650AmpPAK (800AmpFuse) F17 800AmpPAK (1000AmpFuse) F18 1000AmpPAK (1200AmpFuse) F19 1200AmpPAK (Two1000AmpFuses)
Code Remote Manual Adjust
0 None 1 Potwith0-100%dialandLocal/Remote Switch(2)SingleTurn1KW Potentiometer (RequiresProportionalBand)
MXPC III - 2 04 1 1 L1 F02 1 Typical Model Number
Crimp Lug Chart
Chromalox # Panduit # Conductor Size
Torque
In-Lb. Nm0135-10002 LCD8-14A-L #8AWG 180 200135-10003 LCD6-14A-L #6AWGor#6Weld 180 200135-10004 LCD4-14A-L #4AWGor#4Weld 180 200135-10005 LCD2-56B-Q #2AWG 180 200135-10006 LCD1-56C-E #1AWGor#2Weld 180 200135-10007 LCD1/0-12-X #1/0AWGor#1Weld 480 540135-10008 LCD2/0-12-X #2/0AWGor#1/0Weld 480 540135-10009 LCD3/0-12-X #3/0AWGor#2/0Weld 480 540135-10010 LCD4/0-12-X #4/0AWGor#3/0Weld 480 540135-10011 LCD250-12-X 250MCMor#4/0Weld 480 540135-10012 LCD300-12-X 300MCM 480 540135-10013 LCD350-12-6 350MCM 480 540135-10014 LCD400-12-6 400MCM 480 540135-10015 LCD500-12-6 500MCM 480 54
Note:NEMAstandardtwoholecoppercrimplugsonly.
1) SCRFusingisforsemiconductor protection only, not wire protection.
2) SuppliedLooseforCustomer Mounting.
Note:StorageTemperature14ºFto158ºF(-10ºCto70ºC).CEapplicationrequiresfilters.
Chromalox Part Numbers0005-60055:Linefilter,threephase, 440VAC0005-60057:Linefilter,120-230VAC
-37-© 2014 Chromalox®, Inc.1-888-996-9258
EC Declaration of Conformity
We, ChromaloxPrecisionHeatandControl 1347HeilQuakerBoulevard LaVergne,Tennessee37086-3536 Phone:+1(615)793-7561 Fax:+1(615)213-8091
declare under sole responsibility that the following described product in our delivered version complies with theappropriatebasicsafetyandhealthrequirementsoftheECLowVoltageDirective(2006/95/EC)andECElectromagneticCompatibilityDirective(2004/108/EC)basedonitsdesignandtype,asbroughtintocircula-tionbyus.Incaseofalterationofthemachine,notagreeduponbyus,thisdeclarationwillloseitsvalidity.
DescriptionoftheElectricalEquipment:MaxPacSCRcontrollers
ModelNumber:MaxPacSeries;MaxPacI,II,III
Applicable Harmonized Standards:
Low Voltage Directive EMC Directive
Specification: EN60947-4-3:2000 1. RadiatedDisturbanceEmissions–30to1000 Low-voltageswitchgearand MHzElectricField controlgear EN61000-6-4:2001/EN55011:2007
Part4-3:Contactorsand 2. ConductedDisturbanceEmissions–Voltage motor-starters EN61000-6-4:2001/EN55011:2007 ACsemiconductorcontrollers andcontactorsfornon-motorloads 3. ConductedDisturbanceImmunityUtilization AC-51Non-inductiveorslightly EN61000-6-2:2005/EN61000-4-6:1996Category: inductiveloads,resistive furnaces 4. RadiatedDisturbanceImmunity EN61000-6-2:2005/EN61000-4-3:1995Pollution Normallyonlynon-conductiveDegree2 pollutionoccurs.Occasionally, 5. ElectricalFastTransients/BurstsImmunity atemporaryconductivity EN61000-6-2:2005/EN61000-4-2:1995 caused by condensation may beexpected. 6. VoltageDipsandInterruptsImmunity EN61000-6-2:2005/EN61000-4-11:1994VoltageRating: 400Vac50HzLine 230Vac50HzInstrumentmax 7. ElectrostaticDischargeImmunity 75watts EN61000-6-2:2005/EN61000-4-2:1995
ImpulseRating: 2.5KVfor5seconds 8. VoltageFluctuations/Flicker EN61000-3-3/A2:2005Overload 140%for1secondCurrentProfile: 9. HarmonicCurrentEmissions EN61000-3-2:2006Fuses: 500Volt,200KARMS symmetrical interrupting rating, I2tfusingprovidedwithallCE units.
-38- © 2014 Chromalox®, Inc. 1-888-996-9258
FiltersRequired: Instrumentpowerfilter: 10. SurgeImmunity ChromaloxP/N0005-60057 EN61000-6-2:2005/EN61000-4-5:1995 LineFilter,singlephase: ChromaloxP/N0005-60055 LineFilter,threephase: ChromaloxP/N0005-60056
TheTechnicaldocumentationrequiredbyAnnexIV(3)oftheLowVoltageDirectiveismaintainedby(Name)of(companyandlocationintheEuropeanUnion)
YearinwhichCEMarkingwasaffixed:2002
AuthorizedSignature/Date:__________________________________________________________________ JimBirnie Date
EngineeringManagerTitleofSignatory:________________________________
Chromalox,InternationalUnit1.22,LombardHouse2PurleyWayCroydonCRO3JPSurreyU.K.