Technical Data Vacuum Contactor and Starter Specifications Bulletin Numbers 1102C, 1104C, 1109 Additional Resources These documents contain additional information concerning related products from Rockwell Automation. You can view or download publications at http://www.rockwellautomation.com/literature/ . To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Topic Page Specifications 2 1102C Approximate Dimensions 3…4 1104C Approximate Dimensions 5 1109 Approximate Dimensions 6…11 Resource Description Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.

Upload: others

Post on 25-May-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

Technical Data

Vacuum Contactor and Starter SpecificationsBulletin Numbers 1102C, 1104C, 1109

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Topic Page

Specifications 2

1102C Approximate Dimensions 3…4

1104C Approximate Dimensions 5

1109 Approximate Dimensions 6…11

Resource Description

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.

Page 2: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

2 Rockwell Automation Publication 1100-TD004A-EN-P

1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications

200 A 400 A 600 A

Standards UL 508 CSA 22.2 1500V UL 508 CSA 22.2 1500V UL 508 CSA 22.2 1500V

Power Ratings

Insul. & Operating Voltage 200…1500V 200…1500V 200…1500V

Rated Fequency 50…400 Hz 50…400 Hz 50…400 Hz

Making Current Capacity 1600 A 3200 A 4800 A

Breaking Current Capacity 1600 A 3200 A 4800 A

Dielectric Strength 6Kv - 1 Min. Interrupter GAP 6Kv - 1 Min. Interrupter GAP 6Kv - 1 Min. Interrupter GAP

Interrupting Current (Max.) 2.2 kA 4.6 kA 6 kA

Short Circuit Withstand (Max.) 10 kA symmetrical amps @ 1500V AC 18 kA symmetrical amps @ 1500V AC 30 kA symmetrical amps @ 1500V AC

Mechanical Life 1 200 000 1 000 000 750 000

Elect. Life AC3 Duty 500 000 500 000 250 000

Switching Frequency(Mechanical)

1102C, 11091104C

600/hr (max.)6 s (full cycle)

600/hr (max.)6 s (full cycle)

600/hr (max.)6 s (full cycle)

Withstand current for 3 sec [kA] 3.2 6.0 6.5

Chop Current Max. 0.9 A 0.9 A 0.9 A

Control Ratings

Coil Voltage Operation -15% +10% -15% +10% -15% +10%

Inrush Power VA 1200VA 1100VA 1600VA

Sealed Power VA 12VA 12VA 14VA

Opening Time [ms] 120 160 160

Closing Time [ms] 20…40 20…40 30…40

Pick-Up Voltage 80% Cold 85% Hot 80% Cold 85% Hot 80% Cold 85% Hot

Drop-Out Voltage 70% or less 70% or less 70% or less

Application Ratings

Mounting Installation All planes All planes All planes

Altitude 6600 ft (2000 m) 6600 ft (2000 m) 6600 ft (2000 m)

Ambient Storage -65…+160 °F (-54…71 °C) -65…+160 °F (-54…71 °C) -65…+160 °F (-54…71 °C)

Operating Temperature -40…+135 °F (-40…57 °C) -40…+135 °F (-40…57 °C) -40…+135 °F (-40…57 °C)

Vibration/Shock 40 Hz: 2 G/30 G 40 Hz: 2 G/30 G 40 Hz: 2 G/30 G

Page 3: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

3Rockwell Automation Publication 1100-TD004A-EN-P

Approximate Dimensions 1102C Vacuum Contactor

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1102C (200 A)

6.44(163.5)

5.3(134.5)

3.5 (89)0.9(22.7)

0.68(17.1)

Optional Aux.Contact Kit

1.0(25.1)

3.3(84.3)

7.5(190.6)

8.32(211.3)

(4) Mounting for 1/4 Screws0.34(8.5)0.32

(8.1)

5.93(150.6)

8.66(219.9)

Page 4: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

4 Rockwell Automation Publication 1100-TD004A-EN-P

1102C Vacuum Contactor Approximate Dimensions

0.38 (9.7)

0.81 (20.5)

10.25(260.4)

0.38 (9.7)

0.6(15.2) R 0.19 (4.8)

(4) Mtg. Holes

Ø 0.4(10.2)

0.6(15.2)

0.88 (22.4)

0.88 (22.4)

0.6(15.2)

Ø 0.4(10.2)

0.38 (9.7)0.6

(15.2)

R 0.19 (4.8)(4) Mtg. Holes

400 A

600 A

8.0(203.2)

6.83(173.5)

8.25(209.5)

8.2(208.3)

9.25(234.9)

2.54(64.5)

9.1(231.1)

6.46(164.1)

4.77(121.2)

9.15(232.4)

8.0(203.2)

6.83(173.5)

8.25(209.5)

2.54(64.5)

9.1(231.1)

11.88(301.8)

6.46(164.1)

9.15(232.4)

2.87(72.9)

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1102C (400 A and 600 A)

Page 5: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

5Rockwell Automation Publication 1100-TD004A-EN-P

Approximate Dimensions 1104C Reversing Vacuum Contactor

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1104C (200, 400, 600 A)

B

DA

E C

Contactor Size [A]A

HeightB

WidthC

DepthD

Mounting HeightE

Mounting Width

200 8.375(213)

14(358)

6.5(202)

7(210)

13(322)

400 9.25(235)

21(533)

7.10(232)

7.85(272)

19.5(495)

600 12(305)

21(533)

7.10(232)

10.82(280)

19.5(495)

Page 6: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

6 Rockwell Automation Publication 1100-TD004A-EN-P

1109 Vacuum Starter Approximate Dimensions

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1109 (200 A)With E1 Plus Overload

0.50(12.7)

2.59(65.8)

RESET CL

0.37(9.5)

3 places

11.96(303.7)

RESET CL15.83(402)

14.88(377.8)

9.81(249.1)

1.52 (38.6)

4.75 (120.7)

8.44 (214.4)

6.8 (172.1)

4.92 (125.1)

3.28 (83.4)

5.79 (147.1)

4.98 (126.6)

Page 7: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

7Rockwell Automation Publication 1100-TD004A-EN-P

Approximate Dimensions 1109 Vacuum Starter

CL

0.50(12.7)

1.78(45.1)

RESET CL

0.37(9.5)

3 places

5.79 (147.1)

4.98 (126.6)

15.83(402)

14.88(377.8)

9.81(249.1)

12.62(320.6)

RESET CL

1.52 (38.6)

4.75 (120.7)

8.44 (214.4)6.44 (163.4)

4.92 (125.1)

3.28 (83.4)

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1109 (200 A), ContinuedWith Eutectic Overload

Page 8: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

8 Rockwell Automation Publication 1100-TD004A-EN-P

1109 Vacuum Starter Approximate Dimensions

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1109 (400 A)With E1 Plus Overload

Page 9: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

9Rockwell Automation Publication 1100-TD004A-EN-P

Approximate Dimensions 1109 Vacuum Starter

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1109 (400 A), Continued

With Eutectic Overload

Page 10: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

10 Rockwell Automation Publication 1100-TD004A-EN-P

1109 Vacuum Starter Approximate Dimensions

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1109 (600 A)

With E1 Plus Overload

Page 11: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

11Rockwell Automation Publication 1100-TD004A-EN-P

Approximate Dimensions 1109 Vacuum Starter

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1109 (600 A), Continued

With Eutectic Overload

Page 12: Vacuum Contactor and Starter Specifications...2 Rockwell Automation Publication 1100-TD004A-EN-P 1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications 200 A 400 A 600 A

Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1100-TD004A-EN-P - August 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400