8
79.646 40.646 24 15 AirFlow 62.38 63.75 Square Wall Opening 2B - Flush Interior Standard Supply For Interior Service Applications Exterior Interior Static Pressure (in wg) 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Brake Power (hp) 0 1 2 3 4 5 6 7 8 Volume (CFM) x 1,000 0 5 10 15 20 25 30 35 40 45 Syst e m RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 95) Qty 2 Model SBS-2L54-50 Volume (CFM) 24,000 SP (in wg) 0.2 FRP M (RP... 491 Operating Power (hp) 5.16 Motor Information Size (hp) 5 V/C/P 460/60/3 Encl: TEFC Motor RPM: 1725 Windings 1 NEC FLA (A) 7.6 SOUND 62.5 99 125 94 250 89 500 85 1000 82 2000 79 4000 76 8000 76 Inlet Sound Power by Octave Band Lwa 88 dBA 77 Sones 32 NOTES: All dimensions shown are in units of inches DIMENSIONS Approx. Fan Weight (lb) 1,118 Recommended Roof/Wall Opening: (in) 63.75 x 63.75 SBS Sidewall Belt Drive Supply Fan TAGS SWSF - 04 SWSF - 05 STANDARD CONSTRUCTION FEATURES • Galvanized steel fan panel • Die formed, galvanized steel drive frame assembly • Fabricated steel propeller for Levels 1 and 2, welded and painted steel for Level 3 • Adjustable motor pulley • Ball bearing motors • Fan shaft mounted in ball bearing pillow blocks • Static resistant belts • Corrosion resistant fasteners SELECTED OPTIONS & ACCESSORIES NEMA Premium Efficient Motor - meets NEMA Table 12-12 No UL Listing Wall Hsg - Filtered Flush Interior, w/ 2 in Alum. Filters, (2B-Supply), w/ Grd Weatherhood, Galvanized 90 deg. with Bird Screen Bearings with Grease Fittings FLA -Based on tables 148 or 150 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory. LwA - A weighted sound power level, based on ANSI S1.4. Sones calculated using AMCA 301 at 5.0 ft. dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 5.0 ft. dBA levels are not licensed by AMCA International. 11/10/2011 Printed Date: ENERCOM 10NOV11 (Hannes-Indelva) Job: Fan Product Type: SWSF - 01 to 05 Mark: CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 1 of 8

Upload: joravica

Post on 16-Dec-2015

229 views

Category:

Documents


2 download

DESCRIPTION

BOMBAS CHILLER

TRANSCRIPT

  • 79.646

    40.646 24 15

    AirFlow

    62.38

    63.75 Square Wall Opening

    2B - Flush Interior Standard Supply For Interior Service Applications

    Exterior Interior

    Stat

    ic P

    ress

    ure

    (in w

    g)

    0.0

    0.2

    0.4

    0.6

    0.8

    1.0

    1.2

    1.4

    1.6

    Bra

    ke P

    ower

    (hp)

    0

    1

    2

    3

    4

    5

    6

    7

    8

    Volume (CFM) x 1,000

    0 5 10 15 20 25 30 35 40 45

    Syste m

    RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve

    PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 95)

    Qty

    2

    Model

    SBS-2L54-50

    Volume(CFM)

    24,000

    SP (inwg)

    0.2

    FRPM

    (RP...491

    OperatingPower(hp)5.16

    Motor Information

    Size (hp)

    5

    V/C/P

    460/60/3

    Encl:

    TEFC

    Motor RPM:

    1725

    Windings

    1

    NEC FLA(A)7.6

    SOUND

    62.599

    12594

    25089

    50085

    100082

    200079

    400076

    800076

    Inlet Sound Power by Octave Band Lwa

    88

    dBA

    77

    Sones

    32

    NOTES: All dimensions shown are in units of inches

    DIMENSIONSApprox. FanWeight (lb)

    1,118

    RecommendedRoof/Wall Opening: (in)

    63.75 x 63.75

    SBSSidewall Belt Drive Supply Fan

    TAGSSWSF - 04 SWSF - 05

    STANDARD CONSTRUCTION FEATURES Galvanized steel fan panel Die formed, galvanized steel drive frame assembly Fabricated steel propeller for Levels 1 and 2, welded and painted steel for Level 3 Adjustable motor pulley Ball bearing motors Fan shaft mounted in ball bearingpillow blocks Static resistant belts Corrosion resistant fasteners

    SELECTED OPTIONS & ACCESSORIESNEMA Premium Efficient Motor - meets NEMA Table 12-12No UL ListingWall Hsg - Filtered Flush Interior, w/ 2 in Alum. Filters, (2B-Supply), w/ GrdWeatherhood, Galvanized 90 deg. with Bird ScreenBearings with Grease Fittings

    FLA -Based on tables 148 or 150 of National Electrical Code 2002.Actual motor FLA may vary, for sizing thermal overload, consultfactory.LwA - A weighted sound power level, based on ANSI S1.4.Sones calculated using AMCA 301 at 5.0 ft.dBA - A weighted sound pressure level, based on 11.5 dBattenuation per octave band at 5.0 ft.dBA levels are not licensed by AMCA International.

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: SWSF - 01 to 05Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 1 of 8

  • AMCA Licensed for Sound and Air Performance Without Appurtenances (Accessories). Power (BHP/kW) excludes drives.

    GreenheckFanCorporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A:Free inlet, Free outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not includethe effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) ina hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlethemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal appliesto sone ratings only.

    The AMCA licensed air and/or sound performance data has been modified for installation, appurtenances or accessories,etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selectionand applications of the product.

    AMCA

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: SWSF - 01 to 05Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 2 of 8

  • 61.25

    62.25

    62

    WH 90 WeatherhoodSTANDARD CONSTRUCTION FEATURES Galvanized steel or aluminum construction 0.5 welded wire birdscreen Prepunchedmounting holes Field assembled.

    NOTES: All dimensions shown are in units of inches

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: SWSF - 01 to 05Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 3 of 8

  • 62.38

    2.88

    62.38

    79.646 40.646

    24

    15

    WH Wall Housing (Filtered)STANDARD CONSTRUCTION FEATURES Galvanized steel construction Heavy gauge mounting flanges Pre-punched mountingholes Inside flanges allow damper to be mounted Overlapping weatherhood flange keepsrain out Protective guard of welded steel wire completely protects the drive side of the wallhousing. Permanent 2 in. washable filters are accessed through a bolted panel and can beeasily removed for cleaning.Note: Additional bracing (by others) above or below the housing is required for support of thefiltered supply wall housing. Attach at least two supports (either vertical or angled) to the end ofthe housing.

    NOTES: All dimensions shown are in units of inches

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: SWSF - 01 to 05Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 4 of 8

  • 49.83

    51.5

    59.63

    19.63

    2.25 * Sizes greater than 36 with High Temp Option will be 5 in. larger

    *

    Stat

    ic P

    ress

    ure

    (in w

    g)

    0.0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    Bra

    ke P

    ower

    (hp)

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    Volume (CFM) x 1,000

    0 5 10 15 20 25

    Syste m

    RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve

    PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 110)

    Qty

    3

    Model

    RBUMO-2L42-20

    Volume(CFM)

    20,000

    SP (inwg)

    0.05

    FRPM

    (RP...494

    OperatingPower(hp)1.76

    Motor Information

    Size (hp)

    2

    V/C/P

    460/60/3

    Encl:

    TEFC

    Motor RPM:

    1725

    Windings

    1

    NEC FLA(A)3.4

    SOUND

    62.590

    12589

    25083

    50081

    100078

    200076

    400071

    800065

    Inlet Sound Power by Octave Band Lwa

    83

    dBA

    72

    Sones

    22

    NOTES: All dimensions shown are in units of inches

    DIMENSIONSApprox. FanWeight (lb)

    537

    RecommendedRoof/Wall Opening: (in)

    48 x 48

    RBUMOPropeller Upblast Belt Drive MotorOut-of-AirstreamTAGS

    REF - 04 REF - 05 REF - 06

    STANDARD CONSTRUCTION FEATURES Fan base, motor cover and windband of galvanized steel Panel and drive frameassemblies of galvanized steel for sizes 18 to 48, painted steel for sizes 54 and 60 Windband has built in damper stops Aluminum butterfly dampers Fabricatedsteel propeller Ball bearing motors Adjustable motor plate Variable pitch motorpulley Fan shaft mounted in pillow block bearings with grease zerks Sizes 42and larger use fixed pitch drives Static free belts Corrosion resistant fasteners.

    SELECTED OPTIONS & ACCESSORIESUL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-3R, Toggle, Junction Box Mounted & WiredCoating Baked Enamel, 040, Entire UnitSteel PropellerBelt TubeSteel Butterfly DamperExtended Lube LinesBearings with Grease Fittings

    FLA -Based on tables 148 or 150 of National Electrical Code 2002.Actual motor FLA may vary, for sizing thermal overload, consultfactory.LwA - A weighted sound power level, based on ANSI S1.4.Sones calculated using AMCA 301 at 5.0 ft.dBA - A weighted sound pressure level, based on 11.5 dBattenuation per octave band at 5.0 ft.dBA levels are not licensed by AMCA International.

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: REF - 01 to 06 Bldg 12Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 5 of 8

  • AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) does not include transmission losses.

    GreenheckFanCorporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A:Free inlet, Free outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not includethe effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) ina hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlethemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal appliesto sone ratings only.

    AMCA

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: REF - 01 to 06 Bldg 12Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 6 of 8

  • 46.38

    54

    55

    59.25

    57.25

    47.25

    31.75

    46.75

    *Maximum w/Motor Cover

    *

    0.56 DIA

    16 B.C. HOLES

    Stat

    ic P

    ress

    ure

    (in w

    g)

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    3.5

    Bra

    ke P

    ower

    (hp)

    0

    2

    4

    6

    8

    10

    12

    14

    Volume (CFM) x 1,000

    0 5 10 15 20 25

    System

    RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve

    PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 100)

    Qty

    1

    Model

    TCB-2-36-150

    Volume(CFM)

    15,600

    SP (inwg)

    2.5

    FRPM(RPM)

    905

    OperatingPower (hp)

    11.55

    Motor Information

    Size (hp)

    15

    V/C/P

    460/60/3

    Encl:

    TEFC

    Motor RPM:

    1725

    Windings

    1

    SOUND

    62.590

    12593

    25087

    50080

    100080

    200074

    400072

    800068

    Inlet Sound Power by Octave Band Lwa

    85

    dBA

    74

    Sones

    25

    NOTES: All dimensions shown are in units of inchesFan weight is without motors and accessoriesDIMENSIONS

    Approx. FanWeight (lb)

    882

    TCBInline Centrifugal Fan

    Tag ILEF-02STANDARD CONSTRUCTION FEATURESHOUSING: Continuously welded steel or aluminum housing Inlet and outletflanges with mounting holes Aluminum rub ring Meets AMCA type B sparkresistance Structural steel parts are phosphatized and coated with PermatectorBEARINGS, SHAFT, AND WHEEL: Heavy duty, self-aligning ball or roller pillowblock bearings with extended lubrication lines Polished, solid steel shafts Backward inclined aluminum wheel

    SELECTED OPTIONS & ACCESSORIESClass B Motor Insulation or GreaterVFD Rated Motor, Meets NEMA MG-1 Standard, S.F. is 1.0NEMA Premium Efficient Motor - meets NEMA Table 12-12Hi-Pro Polyester - Dark Gray (041), Coat Entire Fan & Fctry. Attchd. Acc's.Switch - Nema-1, Toggle, Ship Separate, Field Mounted

    LwA - A weighted sound power level, based on ANSI S1.4.Sones calculated using AMCA 301 at 5.0 ft.dBA - A weighted sound pressure level, based on 11.5 dBattenuation per octave band at 5.0 ft.dBA levels are not licensed by AMCA International.

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: ILEF-01 to 02Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 7 of 8

  • AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) does not include transmission losses.

    GreenheckFanCorporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in acccordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B:Free inlet, Ducted outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do notinclude the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft.(1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: freeinlet hemispherical sone levels. The AMCA Certified Ratings Seal applies to sone ratings only.

    AMCA

    11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:

    FanProduct Type: ILEF-01 to 02Mark:

    CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 8 of 8