ventilacion (hannes-indelva) - submittal greenheck
DESCRIPTION
BOMBAS CHILLERTRANSCRIPT
-
79.646
40.646 24 15
AirFlow
62.38
63.75 Square Wall Opening
2B - Flush Interior Standard Supply For Interior Service Applications
Exterior Interior
Stat
ic P
ress
ure
(in w
g)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Bra
ke P
ower
(hp)
0
1
2
3
4
5
6
7
8
Volume (CFM) x 1,000
0 5 10 15 20 25 30 35 40 45
Syste m
RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve
PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 95)
Qty
2
Model
SBS-2L54-50
Volume(CFM)
24,000
SP (inwg)
0.2
FRPM
(RP...491
OperatingPower(hp)5.16
Motor Information
Size (hp)
5
V/C/P
460/60/3
Encl:
TEFC
Motor RPM:
1725
Windings
1
NEC FLA(A)7.6
SOUND
62.599
12594
25089
50085
100082
200079
400076
800076
Inlet Sound Power by Octave Band Lwa
88
dBA
77
Sones
32
NOTES: All dimensions shown are in units of inches
DIMENSIONSApprox. FanWeight (lb)
1,118
RecommendedRoof/Wall Opening: (in)
63.75 x 63.75
SBSSidewall Belt Drive Supply Fan
TAGSSWSF - 04 SWSF - 05
STANDARD CONSTRUCTION FEATURES Galvanized steel fan panel Die formed, galvanized steel drive frame assembly Fabricated steel propeller for Levels 1 and 2, welded and painted steel for Level 3 Adjustable motor pulley Ball bearing motors Fan shaft mounted in ball bearingpillow blocks Static resistant belts Corrosion resistant fasteners
SELECTED OPTIONS & ACCESSORIESNEMA Premium Efficient Motor - meets NEMA Table 12-12No UL ListingWall Hsg - Filtered Flush Interior, w/ 2 in Alum. Filters, (2B-Supply), w/ GrdWeatherhood, Galvanized 90 deg. with Bird ScreenBearings with Grease Fittings
FLA -Based on tables 148 or 150 of National Electrical Code 2002.Actual motor FLA may vary, for sizing thermal overload, consultfactory.LwA - A weighted sound power level, based on ANSI S1.4.Sones calculated using AMCA 301 at 5.0 ft.dBA - A weighted sound pressure level, based on 11.5 dBattenuation per octave band at 5.0 ft.dBA levels are not licensed by AMCA International.
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: SWSF - 01 to 05Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 1 of 8
-
AMCA Licensed for Sound and Air Performance Without Appurtenances (Accessories). Power (BHP/kW) excludes drives.
GreenheckFanCorporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A:Free inlet, Free outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not includethe effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) ina hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlethemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal appliesto sone ratings only.
The AMCA licensed air and/or sound performance data has been modified for installation, appurtenances or accessories,etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selectionand applications of the product.
AMCA
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: SWSF - 01 to 05Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 2 of 8
-
61.25
62.25
62
WH 90 WeatherhoodSTANDARD CONSTRUCTION FEATURES Galvanized steel or aluminum construction 0.5 welded wire birdscreen Prepunchedmounting holes Field assembled.
NOTES: All dimensions shown are in units of inches
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: SWSF - 01 to 05Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 3 of 8
-
62.38
2.88
62.38
79.646 40.646
24
15
WH Wall Housing (Filtered)STANDARD CONSTRUCTION FEATURES Galvanized steel construction Heavy gauge mounting flanges Pre-punched mountingholes Inside flanges allow damper to be mounted Overlapping weatherhood flange keepsrain out Protective guard of welded steel wire completely protects the drive side of the wallhousing. Permanent 2 in. washable filters are accessed through a bolted panel and can beeasily removed for cleaning.Note: Additional bracing (by others) above or below the housing is required for support of thefiltered supply wall housing. Attach at least two supports (either vertical or angled) to the end ofthe housing.
NOTES: All dimensions shown are in units of inches
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: SWSF - 01 to 05Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 4 of 8
-
49.83
51.5
59.63
19.63
2.25 * Sizes greater than 36 with High Temp Option will be 5 in. larger
*
Stat
ic P
ress
ure
(in w
g)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
Bra
ke P
ower
(hp)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
Volume (CFM) x 1,000
0 5 10 15 20 25
Syste m
RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve
PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 110)
Qty
3
Model
RBUMO-2L42-20
Volume(CFM)
20,000
SP (inwg)
0.05
FRPM
(RP...494
OperatingPower(hp)1.76
Motor Information
Size (hp)
2
V/C/P
460/60/3
Encl:
TEFC
Motor RPM:
1725
Windings
1
NEC FLA(A)3.4
SOUND
62.590
12589
25083
50081
100078
200076
400071
800065
Inlet Sound Power by Octave Band Lwa
83
dBA
72
Sones
22
NOTES: All dimensions shown are in units of inches
DIMENSIONSApprox. FanWeight (lb)
537
RecommendedRoof/Wall Opening: (in)
48 x 48
RBUMOPropeller Upblast Belt Drive MotorOut-of-AirstreamTAGS
REF - 04 REF - 05 REF - 06
STANDARD CONSTRUCTION FEATURES Fan base, motor cover and windband of galvanized steel Panel and drive frameassemblies of galvanized steel for sizes 18 to 48, painted steel for sizes 54 and 60 Windband has built in damper stops Aluminum butterfly dampers Fabricatedsteel propeller Ball bearing motors Adjustable motor plate Variable pitch motorpulley Fan shaft mounted in pillow block bearings with grease zerks Sizes 42and larger use fixed pitch drives Static free belts Corrosion resistant fasteners.
SELECTED OPTIONS & ACCESSORIESUL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-3R, Toggle, Junction Box Mounted & WiredCoating Baked Enamel, 040, Entire UnitSteel PropellerBelt TubeSteel Butterfly DamperExtended Lube LinesBearings with Grease Fittings
FLA -Based on tables 148 or 150 of National Electrical Code 2002.Actual motor FLA may vary, for sizing thermal overload, consultfactory.LwA - A weighted sound power level, based on ANSI S1.4.Sones calculated using AMCA 301 at 5.0 ft.dBA - A weighted sound pressure level, based on 11.5 dBattenuation per octave band at 5.0 ft.dBA levels are not licensed by AMCA International.
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: REF - 01 to 06 Bldg 12Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 5 of 8
-
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) does not include transmission losses.
GreenheckFanCorporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A:Free inlet, Free outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not includethe effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) ina hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlethemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal appliesto sone ratings only.
AMCA
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: REF - 01 to 06 Bldg 12Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 6 of 8
-
46.38
54
55
59.25
57.25
47.25
31.75
46.75
*Maximum w/Motor Cover
*
0.56 DIA
16 B.C. HOLES
Stat
ic P
ress
ure
(in w
g)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
Bra
ke P
ower
(hp)
0
2
4
6
8
10
12
14
Volume (CFM) x 1,000
0 5 10 15 20 25
System
RPM Curve System Curve Brake Power Curve Do not select to the left of this surge curve
PERFORMANCE (Elevation ft = 0, Airstream Temperature F = 100)
Qty
1
Model
TCB-2-36-150
Volume(CFM)
15,600
SP (inwg)
2.5
FRPM(RPM)
905
OperatingPower (hp)
11.55
Motor Information
Size (hp)
15
V/C/P
460/60/3
Encl:
TEFC
Motor RPM:
1725
Windings
1
SOUND
62.590
12593
25087
50080
100080
200074
400072
800068
Inlet Sound Power by Octave Band Lwa
85
dBA
74
Sones
25
NOTES: All dimensions shown are in units of inchesFan weight is without motors and accessoriesDIMENSIONS
Approx. FanWeight (lb)
882
TCBInline Centrifugal Fan
Tag ILEF-02STANDARD CONSTRUCTION FEATURESHOUSING: Continuously welded steel or aluminum housing Inlet and outletflanges with mounting holes Aluminum rub ring Meets AMCA type B sparkresistance Structural steel parts are phosphatized and coated with PermatectorBEARINGS, SHAFT, AND WHEEL: Heavy duty, self-aligning ball or roller pillowblock bearings with extended lubrication lines Polished, solid steel shafts Backward inclined aluminum wheel
SELECTED OPTIONS & ACCESSORIESClass B Motor Insulation or GreaterVFD Rated Motor, Meets NEMA MG-1 Standard, S.F. is 1.0NEMA Premium Efficient Motor - meets NEMA Table 12-12Hi-Pro Polyester - Dark Gray (041), Coat Entire Fan & Fctry. Attchd. Acc's.Switch - Nema-1, Toggle, Ship Separate, Field Mounted
LwA - A weighted sound power level, based on ANSI S1.4.Sones calculated using AMCA 301 at 5.0 ft.dBA - A weighted sound pressure level, based on 11.5 dBattenuation per octave band at 5.0 ft.dBA levels are not licensed by AMCA International.
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: ILEF-01 to 02Mark:
CAPS 4.7.1193 J:\Hannes ENERCOM\ENERCOM 10NOV11 (Hannes-Indelva).gcj Page 7 of 8
-
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) does not include transmission losses.
GreenheckFanCorporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shownare based on tests and procedures performed in acccordance with AMCA Publication 211 and AMCA Publication 311 andcomply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B:Free inlet, Ducted outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do notinclude the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft.(1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: freeinlet hemispherical sone levels. The AMCA Certified Ratings Seal applies to sone ratings only.
AMCA
11/10/2011Printed Date: ENERCOM 10NOV11 (Hannes-Indelva)Job:
FanProduct Type: ILEF-01 to 02Mark: