7/27/2019 Venturi Valve Specifications http://slidepdf.com/reader/full/venturi-valve-specifications 1/1 D:\Projects\word docs\VV Specifications.doc  page 1 of 1 Specification Guide for TRIATEK VV- Series Air Valve (non-insulated) CONSTRUCTION Valve housing shall be constructed of 16 gauge aluminum with internal components of aluminum and stainless steel. Critical moving parts shall use Teflon ® bushings for reduced friction, smooth operation and extended life. Internal moving parts shall be constructed of 316 stainless steel, except aluminum body valves shall have its cone constructed of aluminum. Valve body shall be formed in a venturi configuration to  produce smooth variation in delivered air flow control. Valve shall be pressure independent over a span of 0.4 to 3"WC pressure drop across the valve without means of external monitoring devices such as mechanical volume regulators, flow control tubing or duct static measuring devices. For acid resistance valves shall be manufactured with Stainless Steel 304 or 316 body, cone and all internal parts as specified options. As an alternate construction option, the aluminum valve body and cone shall be treated with two coats of Heresite P403 or equivalent phenolic coating. PERFORMANCE All valves shall be factory calibrated and the CFM modulation range factory set for the maximum and minimum indicated on the schedule. Pressure independent response to changes in duct static shall be no greater than one second to maintain the set airflow. Airflow accuracy shall be within five percent of reading. Airflow turndown ratio shall be no less than eight to one. The CFM setting shall be capable of being field adjusted by means of an external calibrated dial. At any given CFM setting, from minimum to maximum CFM, the valve shall require no periodic maintenance. A minimum of 6 feet of acoustically lined ductwork shall be installed downstream of the flow control valve and before each room outlet. The valve manufacturer shall supply sound power levels and NC rating based on ADC equipment test code 1062R3 and ASHRAE standard 36-72 with a reference level of 10-12 watts. VALVE ACTUATOR  Pneumatic Control - All variable volume valves shall be equipped with a pneumatic actuator furnished by the valve manufacturer and mounted on the valve and set up by the valve manufacturer. Actuator supplier shall  be as determined by the valve manufacturer. As an alternate the actuator may be supplied by others and mounted and set up by the valve manufacturer with prior authorization. Valve actuators shall be installed so that the valve shall be normally closed. As an alternate the valve can be specified to be supplied normally open. When a pneumatic actuator is supplied, the spring range shall be 8 to 13 psi. Alternate spring ranges may be specified and supplied accordingly if available.  Electronic Control - All variable volume valves shall be equipped with an electronic actuator furnished by the valve manufacturer and mounted on the valve and set up by the valve manufacturer. The actuator shall be  powered by a 24 VAC transformer supplied by the manufacturer. The electronic actuator shall be controlled  by a 4 to 20 mA input (across a precision 500-Ohm resistor, supplied) or a 2 to 10 VDC input signal. The valve manufacturer must be able to supply electronic actuators that can operate over the full range of the valve in 3 seconds maximum. CONSTANT VOLUME Constant volume valves shall be of the same construction and specification as the variable volume valve less any actuator. Air flow rate shall be factory set but manually adjustable in the field. ® Teflon is a Registered trademark of E.I. duPont de Nemours and Company

Upload: anonymous-xecnzkzvj

Post on 14-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Venturi Valve Specifications

7/27/2019 Venturi Valve Specifications

http://slidepdf.com/reader/full/venturi-valve-specifications 1/1

D:\Projects\word docs\VV Specifications.doc  page 1 of 1

Specification Guide for TRIATEK VV- Series Air Valve (non-insulated)

CONSTRUCTION

Valve housing shall be constructed of 16 gauge aluminum with internal components of aluminum and

stainless steel. Critical moving parts shall use Teflon®

bushings for reduced friction, smooth operation and

extended life. Internal moving parts shall be constructed of 316 stainless steel, except aluminum body valves

shall have its cone constructed of aluminum. Valve body shall be formed in a venturi configuration to produce smooth variation in delivered air flow control. Valve shall be pressure independent over a span of

0.4 to 3"WC pressure drop across the valve without means of external monitoring devices such as

mechanical volume regulators, flow control tubing or duct static measuring devices. For acid resistance

valves shall be manufactured with Stainless Steel 304 or 316 body, cone and all internal parts as specified

options. As an alternate construction option, the aluminum valve body and cone shall be treated with two

coats of Heresite P403 or equivalent phenolic coating.

PERFORMANCE

All valves shall be factory calibrated and the CFM modulation range factory set for the maximum and

minimum indicated on the schedule. Pressure independent response to changes in duct static shall be no

greater than one second to maintain the set airflow. Airflow accuracy shall be within five percent of reading.

Airflow turndown ratio shall be no less than eight to one. The CFM setting shall be capable of being field

adjusted by means of an external calibrated dial. At any given CFM setting, from minimum to maximum

CFM, the valve shall require no periodic maintenance. A minimum of 6 feet of acoustically lined ductwork

shall be installed downstream of the flow control valve and before each room outlet. The valve manufacturer

shall supply sound power levels and NC rating based on ADC equipment test code 1062R3 and ASHRAE

standard 36-72 with a reference level of 10-12 watts.

VALVE ACTUATOR 

 Pneumatic Control - All variable volume valves shall be equipped with a pneumatic actuator furnished by the

valve manufacturer and mounted on the valve and set up by the valve manufacturer. Actuator supplier shall be as determined by the valve manufacturer. As an alternate the actuator may be supplied by others and

mounted and set up by the valve manufacturer with prior authorization. Valve actuators shall be installed so

that the valve shall be normally closed. As an alternate the valve can be specified to be supplied normally

open. When a pneumatic actuator is supplied, the spring range shall be 8 to 13 psi. Alternate spring ranges

may be specified and supplied accordingly if available.

 Electronic Control - All variable volume valves shall be equipped with an electronic actuator furnished by

the valve manufacturer and mounted on the valve and set up by the valve manufacturer. The actuator shall be

 powered by a 24 VAC transformer supplied by the manufacturer. The electronic actuator shall be controlled

 by a 4 to 20 mA input (across a precision 500-Ohm resistor, supplied) or a 2 to 10 VDC input signal. The

valve manufacturer must be able to supply electronic actuators that can operate over the full range of thevalve in 3 seconds maximum.

CONSTANT VOLUME

Constant volume valves shall be of the same construction and specification as the variable volume valve less

any actuator. Air flow rate shall be factory set but manually adjustable in the field.