vertical mount evolution series - iceqube.com · iq6000ev 6500/1905 480/50 2.02 140/60 117.5 / 53.3...
TRANSCRIPT
Technical Data
Ice Qube, Inc., 141 Wilson Ave., Greensburg, PA 15601 Call: 724.837.7600 Fax: 724.837.3386www.iceqube.com Email: [email protected] Rev 6
Model BTU/Watts Volts/Hz Max Amps Max Temp ºF/ºC Weight (lbs/Kg) Dimensions (In/mm)
IQ6000EV 6500/1905 120/60 8.31 140/60 97.5 / 44.2 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
IQ6000EV 6500/1905 220/50 3.82 140/60 97.5 / 44.2 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
IQ6000EV 6500/1905 230/60 4.32 140/60 97.5 / 44.2 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
IQ6000EV 6500/1905 400/50 2.52 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
IQ6000EV 6500/1905 400/60 2.52 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
IQ6000EV 6500/1905 480/50 2.02 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
IQ6000EV 6500/1905 480/60 2.11 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)
6000
BTU
EV
Ser
ies
0
2000
4000
6000
8000
10000
20 25 30 35 40 45 50 55 60
Cap
acity
(BTU
/hr)
Return Air Temperature - ° C
IQ6000EV 60Hz Capacity Chart
25º C Ambient
35º C Ambient
45º C Ambient
55º C Ambient Conditioned EnclosedAir Flow
Internal CabinetAir Flow
Enclosure Air Flow
The next evolution of cutting edge design is here now. The EV Evolution Series fromIce Qube is a certified for general purpose and hazardous locations Class I Division2 Groups A, B, C, & D air conditioner taking our Ice Qube product line to new levels.
Vertical Mount Evolution SeriesCertified for General Purpose & Hazardous LocationsClass I Division 2 Groups A, B, C, & D6,000 BTUH - 1905 Watt Cooling Capacity Air Conditioner
Standard FeaturesOptionsTechnical Data
Cooling Solutions
Standard Features• Compact 11” (287mm) width to fit on smaller cabinets.• Three position condenser air flow with the option to direct hot discharge air
in different directions.• Standard Digital Controller with programmable temperatures and alarm.• Controller can be installed on either front or rear of the unit (inside or outside of enclosure).• Can be used with or without purge system.• UL Listed, (third party certified).• Outdoor model operating temperature range from -40O F/-40O C to 140O F/60O C.• Environment friendly refrigerant.• Efficient, quiet, and long lasting rotary compressor.• Powder Coat finish on durable 16 gauge welded steel.• Easy pull out cleanable, reusable electrostatic 10 micron filter.• Every unit 100% factory tested before shipping.• Minimal visible fasteners.• NEMA type 12, 3R, 4, 4X available.
Options & Accessories• Custom finishes.• 304 or 316 Stainless steel.• Ethernet controller (ETHR).
• Low ambient (LA).• Alarm output (XO3).• 4 Micron condenser filter.• Total corrosive e-coating (CP3).
• 120V 60Hz.• 220/230V 50/60Hz.• 400V 50/60Hz.• 480V 50/60Hz.
Class I Division 2Groups A, B, C, & D
Ice Qube, Inc., 141 Wilson Ave., Greensburg, PA 15601 Call: 724.837.7600 Fax: 724.837.3386www.iceqube.com Email: [email protected] Rev 6
Drawings depict all voltages. Data is subject tochange.
Specification Drawings
Vertical Mount Evolution SeriesCertified for General Purpose & Hazardous LocationsClass I Division 2 Groups A, B, C, & D6,000 BTUH - 120V 60Hz, 220/230V 50/60Hz, 400V 50/60Hz, &480V 50 & 60 Hz Air Conditioners
Cooling Solutions
287.26 11.309
14.150359.40
AMBIENT INTAKE FILTER
203.20 8.000
14.000355.60
STANDARD
CONTROLLERLOCATION
2.05252.12
9.046229.77
DRAIN TUBE .375" [9.53] O.D.
EXHAUST
INTAKE
(6) PEM, NUT, #1/4-20
LOCATION
ENCLOSURE
ENCLOSURE
OPTIONAL CONTROLLER (2) PEM, STUD, 1/4"-20, 1"LG
179.47
203.20 8.000
7.066
5.500139.70
WITH GUARD
lbs
N
DATE
U
REV 0R
IQ6000EV
AMBIENT EXHAUSTIQ6000EVNOMINAL COOLING CAPACITY:6500 BTUH @ 140-140 F5800 BTUH @ 95-95 FINTERNAL HEAT OPTION: 400W MAXIMUMMAXIMUM AMPS: 8.31 @ 120V/60Hz w/ INTERNAL HEAT 4.00AMAXIMUM AMPS: 3.82 @ 220V/50Hz w/ INTERNAL HEAT 2.20AMAXIMUM AMPS: 4.32 @ 230V/60Hz w/ INTERNAL HEAT 2.10AMAXIMUM AMPS: 2.02 @ 480V/50Hz w/ INTERNAL HEAT 2.20AMAXIMUM AMPS: 2.11 @ 480V/60Hz w/ INTERNAL HEAT 2.10AMAXIMUM AMPS: 2.52 @ 400V/50Hz w/ INTERNAL HEAT 2.21AMAXIMUM AMPS: 2.52 @ 400V/60Hz w/ INTERNAL HEAT 2.10AM
AMBIENT EXHAUST
28.584726.04