ETD750 Series Universal Vector Inverter CONTENTS ETD 750 Product Manual 1 CONTENTS 1. INTRODUCTION ............................................................................ 3 1.1 Unpacking Inspection: ............................................................... 4 1.2 ETD750 Series AC Drives Nameplate: ..................................... 4 2. SAFETY NOTE ............................................................................... 5 2.1 Installation ................................................................................. 5 2.2 Wiring ........................................................................................ 5 2.3 Power On .................................................................................. 6 2.4 Maintenance ............................................................................. 6 2.5 Others ....................................................................................... 6 2.6 About Mechanism Load ............................................................ 6 2.7 About AC Drives ........................................................................ 8 3. PRODUCT STANDARD SPECIFICATION .................................. 10 3.1 Product Design Specifications ................................................ 10 3.2 Product Technical Specifications..............................................11 4. INSTALLATION ............................................................................ 12 4.1 Installation Environment.......................................................... 12 4.2 Installation Requirements: ...................................................... 13 5. WIRING......................................................................................... 14 5.1 Wire Connections of Main Loop: ............................................. 14 5.2 Wire Connections of Terminals: .............................................. 15 5.3 Standard Connections:............................................................ 22 5.4 Main circuit accessories, Wire dimension ............................... 23 6. USAGE OF OPERATION PANEL ................................................ 25 6.1 Using operator panel ............................................................... 25 6.2 LED Operator Panel Introduction............................................ 29 6.3 LED Button Function Description............................................ 30 6.4 LED Operator Panel Description ............................................ 31 6.5 LED Parameter List................................................................. 33 6.6 LED Display Code Comparison table ..................................... 38 7. SIMPLE OPERATION .................................................................. 39 7.1 Inspection and preparation before running ............................. 39

Upload: vbscribd1234

Post on 03-Jan-2016

137 views

Category:

Documents


30 download

DESCRIPTION

VFD of ETD Drives YantaiMade in China Drives

TRANSCRIPT

Page 1: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter CONTENTS

ETD 750 Product Manual 1

CONTENTS 1. INTRODUCTION ............................................................................ 3

1.1 Unpacking Inspection:............................................................... 4 1.2 ETD750 Series AC Drives Nameplate: ..................................... 4

2. SAFETY NOTE............................................................................... 5

2.1 Installation ................................................................................. 5 2.2 Wiring ........................................................................................ 5 2.3 Power On .................................................................................. 6 2.4 Maintenance ............................................................................. 6 2.5 Others ....................................................................................... 6 2.6 About Mechanism Load ............................................................ 6 2.7 About AC Drives........................................................................ 8

3. PRODUCT STANDARD SPECIFICATION .................................. 10

3.1 Product Design Specifications ................................................ 10 3.2 Product Technical Specifications..............................................11

4. INSTALLATION ............................................................................ 12

4.1 Installation Environment.......................................................... 12 4.2 Installation Requirements: ...................................................... 13

5. WIRING......................................................................................... 14

5.1 Wire Connections of Main Loop:............................................. 14 5.2 Wire Connections of Terminals: .............................................. 15 5.3 Standard Connections:............................................................ 22 5.4 Main circuit accessories, Wire dimension............................... 23

6. USAGE OF OPERATION PANEL................................................ 25

6.1 Using operator panel............................................................... 25 6.2 LED Operator Panel Introduction............................................ 29 6.3 LED Button Function Description............................................ 30 6.4 LED Operator Panel Description ............................................ 31 6.5 LED Parameter List................................................................. 33 6.6 LED Display Code Comparison table ..................................... 38

7. SIMPLE OPERATION .................................................................. 39

7.1 Inspection and preparation before running ............................. 39

Page 2: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter CONTENTS

ETD 750 Product Manual 2

7.2 Operation Methods ................................................................. 39 7.3 Commissioning ....................................................................... 39

8. FUNCTION PARAMETERS ......................................................... 41

9. DETAILED EXPLAINATIONS ...................................................... 53

10. FAILURE COUNTERMEASURE.............................................. 105

10.1 Fault diagnosis and corrective measures ........................... 105 10.2 Alarm Display and Explanations ......................................... 107 10.3 Motor Failures and Corrective Measures............................ 108

11. MAINTENANCE ........................................................................111

11.1 Basic maintenance methods ................................................111 11.2 Regular Examination Items ..................................................112

12. SELECTION AND CONFIGURATION OF THE SURROUNDING FACILITIES......................................................................................113

12.1 Brake resistance configuration table....................................113

13. APPENDIX.................................................................................115

13.1 Installation dimension of Operator Base..............................115 13.2 Installation Dimension of Inverters:......................................116 13.3 External Dimension Table ....................................................117 13.4 External potentiometer explanation and example ...............118

Page 3: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter CONTENTS

ETD 750 Product Manual 3

1. INTRODUCTION

Thank you for using ETD750 series AC drives. ETD750 series AC drives use the unique current vector control; realize

high precision, high torque and flexible curve motor control. This manual introduces how to use ETD 750 AC drives. Before you using

(install, connections, running, maintenance, check etc.), please be sure to read the manual seriously. Besides, please understand the product's safety precautions before using the product.

General Notes

The illustrations in this manual, in order to explain the details section, there will remove the shell or safety shelter for description. When running the drives, be sure to install the shell to the original place according to the provision and operate the drives according to the manual.

In the manual due to product improvements, specifications change, as well as to their own user-friendly manual will be appropriate changes. At this point we will update the manual number and distribute revisions.

Damage or loss need to order manual, please note the drive type and serial number and contact with the company’s agent or HQ.

It is no responsibility of our company for customers on product adaptation, and the quality assurance does not belong to the Company.

Page 4: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter INTRODUCTION

ETD 750 Product Manual 4

1.1 Unpacking Inspection: Upon unpacking, please check for: Any damage occurred during transportation; Check whether the rated values on the nameplate of the drives are in

accordance with your order. If there is any error, please contact us or distributors.

1.2 ETD750 Series AC Drives Nameplate:

Page 5: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 5

2. SAFETY NOTE

2.1 Installation

1 Please install the drive on fire-retardant material. 2 Keep the drive away from combustible materials 3 Keep the drive away from explosive gas

4 Don’t carry the drive by its cover. The cover cannot support the weight of the drive and may drop.

5 Please install the drive on a strong support, failing which the drive may fall off.

6 Don't operate the drive if parts are not complete, otherwise there is a danger of a fire or human injury

7 Don't allow screws, washers and other metal foreign matters to fall inside the drive, otherwise there is a danger of fire or damage;

8 Don’t install the drive in places where water pipes may leak onto it.

2.2 Wiring 1 Only qualified personnel shall wire the drive.

2 Never wire the drive unless the input AC supply is totally disconnected.

3 The drive must be properly earthed to reduce electrical accident.

1 Don’t confuse the input and output terminals, otherwise there is an explosion or property may be damaged.

2 Don’t short circuit P and N, otherwise there is a danger of fire or property may be damaged.

3 Cable lugs must be connected to main terminals firmly, otherwise property may be damaged.

4 The bare portions of the power cables must be bound with insulation tapes.

For your safety, please pay particular attention to marks used in the manual.

Danger: Operations without following instructions can cause personal injury or death.

Warning: Operations without following instructions can cause personal injury or damage to product or other equipment.

Page 6: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 6

2.3 Power On 1 Install the cover before switching on the drive, to

reduce the danger of electric shock and explosion.

2

For drives that have been stored for longer than 2 years, increase its input voltage gradually before supplying full rated input voltage to it, in order to avoid electric shock and explosion.

3 Don't touch the live control terminals with bare hands.

4 Don’t operate the drive with wet hands.

2.4 Maintenance 1 Perform the maintenance job after confirming that

the DC Bus voltage is below 36V.

2 Only trained professionals can change the components, it is prohibited to leave wires or metal parts inside the drive so as to avoid the risk of fire.

3 Parameter settings of the control board that has been changed must be revised, otherwise accidents may occur.

2.5 Others 1 Modification is strictly prohibited without permission.

2 Disposing unwanted drives must as industrial waste, strictly prohibit set on fire.

2.6 About Mechanism Load

1

Driving a common motor at low speed for a long time, the drive’s life will be reduced due to the deteriorating heat dissipation effect, so a special variable frequency motor is needed if long time operation with constant torque is required.

2

The drive can protect the motor from over-temperature. If the ratings of the driven motor are not in compliance with the drive, be sure to adjust the protective threshold to ensure the motor is properly protected.

Page 7: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 7

3

When running the motor above 50Hz, there will be increase in vibration and noise. The rate at which the torque is available from the motor is inversely proportional to its increase in running speed. Ensure that the motor can still provide sufficient torque to the load.

4

Braking torque is developed in the machine when the drive is hoisting a load down. The drive will trip when it cannot cope with dissipating the regenerative energy of the load. Therefore, a braking unit with proper parameters setting in the drive is required.

5 The output current may fluctuant when drive reciprocating load, especially running in low frequency, recommend running at more than 20Hz.

6

The drive system may encounter mechanical resonance with the load when operating within certain band of output frequency. Skip frequencies have been set to avoid it.

7 Don’t connect or disconnect the motor when the drive running, otherwise will lead to over current or the main circuit may be damaged.

8 Please don’t close to the motor when you use the failure re-start function.

9 Please check the speed allowance range between the motor and mechanism because AC drives can run to high speed easily.

10 Disconnect the motor cable from AC drive before any test to cables.

11 Confirm safety before changing the motor direction.

12 Insure motor terminals not be connected to main power supply.

13 The motor max speed (frequency) must be set according to the motor and devices which connected to the motor.

14Install the motor correctly and ensure the mechanism load can allow the motor start before the motor running.

15 ETD 750 AC drives must be properly earthed from ground terminal.

Page 8: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 8

2.7 About AC Drives

1

Don’t connect any varistor or capacitor to the output terminals of the drive, because the drives’ output voltage waveform is pulse wave, otherwise tripping or damaging of components may occur. As following figure:

2 The drive is not suitable to be used out of the specified range of operation voltage. If needed, please use suitable voltage regulation device.

3 There are transient surge suppressors inside the drive which protects it against lighting strike.

4

When using one drive with more motors, we should pay attention to motor load can’t be a reciprocating load, otherwise it will bring instability, and for each motor must have a separate over-current protection device.

KM1~KMn must be matching with motor M1~Mn rated value, in this case, Ac drives can’t protect a single motor.

5 When the Ac drive connected to the power supply, don’t do any measurement to the internal circuit.

6 Ac drives have large capacitive leakage current.

7

When the ac drive connected to the power supply, even if the motor is not running, motor U, V, W terminals and DC Bridges / braking resistor terminals P + / PR is still charged.

KM1

KM2

KM3

KMn

Page 9: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 9

8

Although the control I / O terminals and power supply isolation, even if the inverter does not power on, but the relay outputs and other I / O terminals is still possible with a dangerous voltage.

9 If the inverter is used as a part of the machine, the machine manufacturer must provide the machine's main power switch.

10

When the altitude more than 1000 meters, the inverter need for derating due to the thin air cause the inverter cooling effect deterioration. Following is the inverter rated current and altitude curves.

11

When the ac drive connected to the power supply, the inverter power unit is charged. It will be extremely dangerous and even death if touch this voltage. Control unit and the main voltage isolation.

12 Can only use spare parts supplied or recommended by ETD company.

13 ETD750 inverter can only used in a fixed installation.

14Don’t do any voltage test for any part of ETD 750.This test requires a special test procedure. Neglect of the steps will lead to devastating results.

Meters

Page 10: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 10

3. PRODUCT STANDARD SPECIFICATION 3.1 Product Design Specifications

Model Rated Input Voltage Rated Power

G/P(KW)

Rated Output

Capacity(KVA)

Rated Output Current G/P(A)

Motor Power

G/P(KW)

750G/0000.4/200 Single/Three Phase 200V 50Hz 0.4/- 1.0/- 3.2/- 0.4/-

750G/0000.75/200 Single/Three Phase 200V 50Hz 0.75/- 2.0/- 6/- 0.75/-

750G/0001.5/200 Single/Three Phase 200V 50Hz 1.5/- 2.4/- 8/- 1.5/-

750G/0002.2/200 Single/Three Phase 200V 50Hz 2.2/- 3.7/- 11/- 2.2/-

750G/0000.75/400 Three phase 400V 50Hz 0.75/- 2.6/- 3.4/- 0.75/-

750G/0001.5/400 Three phase 400V 50Hz 1.5/- 3.7/- 4.8/- 1.5/-

750G/0002.2/400 Three phase 400V 50Hz 2.2/- 4.2/- 6.2/- 2.2/-

750G/0003.7/400 Three phase 400V 50Hz 3.7/- 6.6/- 9/- 3.7/-

750G/0005.5/400 Three phase 400V 50Hz 5.5/7.5 11/14 14/18 5.5/7.5

750G/0007.5/400 Three phase 400V 50Hz 7.5/11 14/21 18/27 7.5/11

750G/0011.0/400 Three phase 400V 50Hz 11/15 21/26 27/34 11/15

750G/0015.0/400 Three phase 400V 50Hz 15/18.5 26/34 34/41 15/18.5

750G/0018.5/400 Three phase 400V 50Hz 18.5/22 31/40 41/52 18.5/22

750G/0022.0/400 Three phase 400V 50Hz 22/30 40/50 52/65 22/30

750G/0030.0/400 Three phase 400V 50Hz 30/37 50/61 65/80 30/37

750G/0037.0/400 Three phase 400V 50Hz 37/45 61/73 80/96 37/45

750G/0045.0/400 Three phase 400V 50Hz 45/55 73/98 96/128 45/55

750G/0055.0/400 Three phase 400V 50Hz 55/75 98/130 128/165 55/75

750G/0075.0/400 Three phase 400V 50Hz 75/90 130/153 165/185 75/90

750G/0090.0/400 Three phase 400V 50Hz 90/110 153/170 185/224 90/110

750G/0110.0/400 Three phase 400V 50Hz 110/132 170/211 224/260 110/132

750G/0132.0/400 Three phase 400V 50Hz 132/160 211/230 260/302 132/160

750G/0160.0/400 Three phase 400V 50Hz 160/185 230/260 302/340 160/185

750G/0185.0/400 Three phase 400V 50Hz 185/220 260/340 340/450 185/220

750G/0220.0/400 Three phase 400V 50Hz 220/250 340/360 450/470 220/250

750G/0250.0/400 Three phase 400V 50Hz 250/280 360/390 470/520 250/280

750G/0280.0/400 Three phase 400V 50Hz 280/315 390/460 520/605 280/315

750G/0315.0/400 Three phase 400V 50Hz 315/350 460/520 560/640 315/350

750G/0355.0/400 Three phase 400V 50Hz 350/400 520/560 640/680 350/400

Page 11: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SAFETY NOTE

ETD 750 Product Manual 11

3.2 Product Technical Specifications Item Description

Input Rated voltage&frequence

permissible fluctuation range400V/50Hz/60Hz, Voltage:±15%;Frequency:±5%200V/50Hz/60Hz, Voltage:±15%;Frequency:±5%

Output Rated voltage Three phase:380V (direct ratio) Single phase:220V (direct ratio)

Control method PWM,Voltage vector SVPWM Control mode V/F/non-inductive current vector control mode

Frequency control range 0.10 ~ 400.00Hz Digital: ±0.01%(-10~ +50) Frequency precision

( Temperature range) Analog: max frequency× 0.2%Hz (25 ±10%) Digital: ±0.01%(-10~ +50)

Frequency precision Analog: max frequency× 0.2%Hz (25 ±10%)

Output resolution 0.01 Hz

Overload Capacity G:150% of rated output current in 1 minute, P:120% of rated output current in 1 minute

Frequency setting signal 0~10V(2~20kΩ), 0- 4~20mA(250Ω) Speed up/down time 0.0 ~3600.0 sec (setting of speed up/time time)

Brake torque No brake resistor-about 20%;125% of external brake resistor

Control Specifications

V/F Mode 14 preset for V/F, programmable V/F mode Overload protection Overheat relay protection

Instant current G:250% of rated current,P:200% of rated current

Overload

G: Ramp stop at 150% of rated output current in 1 minute, P: Ramp stop at 120% of rated output current in 1 minute

Overvoltage Stop over 410V of main DC voltage(200V); Stop over 820V of main DC voltage(400V)

Under voltage Stop below 190V of main DC voltage(200V); Stop below 380V of main DC voltage(400V)

Instant power down Stop when instantaneous power-down 15ms (default setting) or continue running in 2 sec.

Heatsink over temperature Heatsink and power module overheat protectionStall protection Stall protect in speed up/constant/down

Protection

Grounding fault Protect by electronic circuit Ambient

temperature/humidity -10~+50,90%RH

Suitable place Indoor (no corrosive gas or dust)

Environ-m

ent

Vibration Below 0.5G

Page 12: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter INSTALLATION

ETD 750 Product Manual 12

4. INSTALLATION 4.1 Installation Environment Please install ETD750 AC drive in the following place: ※ If need special installation requirement, please contact us or the distribution.

Avoid direct sunlight(Avoid using outdoors)

No corrosive gases or liquids

No oil sprays and splashes

No salt sprays No rain and moisture No dust and metallic particles

No physical shock and vibration Low humidity Ambient temperature

-10°C ~ +50°C

No magnetic noise (welding machines, big

power devices .etc)

No radioactive substances No combustibles

Page 13: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter INSTALLATION

ETD 750 Product Manual 13

4.2 Installation Requirements: Installation space and distance requirements as shown Fig.4-1:

Fig.4-1 Installation Spacing

When two drives are installed one on top the other down, an air flow diverting plate should be fixed in between as shown Fig.4-2:

Fig.4-2 Installation of several drives

Page 14: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 14

5. WIRING 5.1 Wire Connections of Main Loop:

Power Supply: Pay attention to the voltage grade.

No Fuse Switch: Refer to the corresponding table.Creepage Switch: Please use the creepage switch which can avoid higher harmonic.

Electromagnetic Contactor:Note: Don’t use electromagnetic contactor as the power switch of AC drive.

AC Reactor: Proposed to add input AC reactor to improve power factor when the output capacity more than 1000KVA.

AC drives:1、Be sure to right connect wires of main circuit and control signal. 2、Be sure to set the parameters well.

Motor:1、Ensure motor parameters are in compliance with connected mechanism load. 2、A special variable frequency motor is needed if the motor at low speed for a long time.

Page 15: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 15

5.2 Wire Connections of Terminals: (1) Main Circuit Connections of Terminals: 750G/0000.4/200—750G/0003.7/400:

750G/0005.5/400 (750P/0007.5/400) -750G/0015.0/400 (750P/0018.5/400):

750G/0018.5/400 (750P/0022.0/400) -750G/0055.0/400 (750P/0075.0/400):

750G/0075.0/400 (750P/0090.0/400) -750G/0090.0/400 (750P/0110.0/400):

750G/0110.0/400 (750P/0132.0/400) -750G/0355.0/400 (750P/0400.0/400):

P+ P1 N R S T

U V W Note: Some brands of drives make P+, N¯ marks as P, N, and R, S, T marks as

L1, L2, L3.

Page 16: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 16

(2)Control Terminals: 750G/0000.4/200 (750P/0007.5/400)- 750G/0055.0/400 (750P/0075.0/400)

750G/0075.0/400(750P/0090.0/400)- 750G/0355.0/400(750P/0400.0/400)

Page 17: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 17

(3) Function Description of Main circuit Terminals: Terminal Symbol Description

R/L1 S/L2 T/L3

Connect to single/three phase AC power supply.

Main circuit power supply terminals R/L1、S/L2、T/L3 are

connected to single/three phase AC power supply from circuit

protection breaker or creepage protection breaker. Needn’t to

consider the phase sequence of three phase power supply.

Proposed to connect an electromagnetic contactor in order to

remove power supply and prevent failure expansion when the

drives protect function working.

Don‘t use the main power supply “ON/OFF” to control the

operation of drive’s. Should be using S1 and S2 of control circuit

or “START” and “STOP” on operator panel to control the operation

of drives. If must use the main power supply “ON/OFF” to control

the operation of drive, then only once per hour.

200v grad input power supply: Single/three phase input sharing,

select any two of three terminals for single phase.

400v grad input power supply: No need single phase power

supply.

Page 18: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 18

Terminal Symbol Description

U/T1 V/T2 W/T3

Connect to three phase motor.

Connected AC drive’s output terminals to three phases motor

according to the right phase sequence. Change any two of U, V,

W wires if the motor rotation direction is not right.

If wires between drive and motor is very long, due to

distributed capacitance between lines have a greater

high-frequency current may result in over-current trip.

Otherwise, as the creepage current increasing the current

precision become bad. So the wire length between drive and

motor should less than 50 meters for drives below 3.7kW and

for the bigger drives should less than 100 meters. If the wire is

very long, you should connect filter options (OFL filter) on the

output side.

Drive’s device at the switch process will produce a surge

voltage when the drive driven motor, this surge voltage is

superimposed on the motor terminals. For 400v series, the

surge voltage may make the motor insulation deterioration if the

wire is very long. For 400v grade please consider the following

countermeasure:

Use enhanced insulation motor;

Connect filter options (OFL filter) on the output side;

To minimize length of connection wire between the drive and

the motor, such as 10~20 meters.

Page 19: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 19

Terminal Symbol Description

P+

PR

Connected to external brake resistance(≤15KW) (Options)

Drives less than 15KW have inside brake unit which connected

to P+、PR terminals. In order to increase brake ability, must

connect external brake resistance. External brake resistance

terminals P+、PR connected to P+、PR of drive. The wire should

less than 5 meters and double-twisted or two-adhesion.

P+

N-

Dc voltage output, can connect external brake unit(≥18.5KW,

Options)

Drives more than 18.5KW have no inside brake unit. In order to

increase brake ability, must connect external brake unit or brake

resistance (Options)

Brake unit terminals P+、N-connected to P+、N- of drive. The

wire should less than 5 meters and double-twisted or

two-adhesion.

Drive terminals P+, N- when noted used, should maintain its

original open state.

Note: If shorted P+, N- or connected brake resistance to P+, N- ,

this will damage the drives and cause accidents. Absolutely

can’t do so.

The auxiliary contacts 1 and 2 have polarity difference.

About the connection of power regeneration unit please refer

the product manual of power regeneration unit.

Page 20: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 20

Terminal Symbol

Description

EG

Grounding terminal of drive should be connected to ground.

Grounding terminal EG of drive must connected to ground for

safety and reduce noise.

In order to avoid electric shock and fire accident, the metal shell

and frame of electric device should be connected to ground

according to the national electric rule. The grounding wire

should be thick and short and drive system need to be

connected to special grounding.

Right Right Wrong

Page 21: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 21

(4) Control circuit terminal function description:

Sort Terminal symbol Terminal Name Function Description

FS Power supply for potentiometer

Power supply (+12VDC) for frequency setting potentiometer (1~5KΩ)

FV Voltage input

External analog input voltage to set frequency: 0~10V DC/0~100% Reverse running:+10V~0V DC/0~100%Input signal of PID. Input impedance:20kΩ

FI Current input

External analog input current/voltage to set frequency: 4~20mA DC/0~100% 0~10V DC/0~100% ( Set SW1:OFF) Feedback signal of PID. Input impedance:250Ω

Analog Input

FC Analog common terminal Common terminal of analog input signal.

S1 Forward run/Stop Terminals S1-SC:Close(ON),Forward run;Open(OFF),Stop。

S2 Reverse run/StopS3 Optional input 3 S4 Optional input 4 S5 Optional input 5 S6 Optional input 6 S7 Optional input 7 S8 Optional input 8

Terminals S2~S8: These terminals can set as external alarm, failure reset, multi-frequency and so on. For the detail please refer to the setting ways of terminals S2~S8.

SP 24V Auxiliary power supply Output current less than 100mA.

Input contact

SC Common contact Common terminal of input contact signal.

Analog Output FMA

Analog Diagnostics(FC:

Common terminal)

DC voltage:0 ~ +10V Diagnostic signal, following are the diagnostic content: output frequency (10V/max frequency 019) output current (10V drive rated current) output power (10V drive rated current) dc voltage 10V/400V (200V grad) 800V

(400V grad)

Contact output

Y1 Y2

Optional signal output relay

Multi-function terminals output running status, up to setting frequency, overload alarm and so on. For the detail please refer to the setting ways of output terminals.

OC output

Y3 Y4

Multi-function OC output Y3,Y4

Commu-nication

DA DB

RS485communication In/Out

RS485 communication In/Out terminal, it can connect 31 drives.

GND EG Grounding Grounding protection for control wires

Page 22: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 22

5.3 Standard Connections: Drive wiring can be divided into main loop and control loop. Users can see

the main loop and control loop terminals when open the cover. Users must

connect wires according to the following drawing.

Following are the standard connections of ETD750:

N P P1 PR

R/ L 1S/ L 2

T/ L 3

EG

SP

SC

FS

FV Main analogue reference

M

YC

FMA

FC

Dry contact output

Wet contact output

250Ω

FC

DA

DB

..

FI

Y4

S1S2S3

S4

S5S6

S7S8

24 )(+ V

U( T1 )

V( T2)

W ( T3 )

AY1

Y1C

BY1

Y2A

Y2B

Y2C

Y3

4-20mA

.

.

SW1-2

DC 24V/5A

AC 250V/2.5A

0-10V4.7K DC 0-10V/5mA

48V/ DC 50mA

Brake Unit(Opertional)Short Films

Brake Resistance(Operational)

Circuit Breaker

Forward/Stop

Reverse/Stop

Failure Reset

External Fault

Multi-Speed

JOG

Frequency power supply

Multi-function analog output

Analog signal common point

Auxiliary analog input RS 485

communication port

AC Motor

Multi-Speed

Multi-Speed

Page 23: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 23

5.4 Main circuit accessories, Wire dimension Model

Recommended Breaker

(MCCB)A

Recommended wire section area

(mm2 )

Recommended contactor work

current(A) 750G/0000.4/200 12/- 2.5/- 10/-

750G/0000.75/200 16/- 2.5/- 10/-

750G/0001.5/200 25- 4/- 16/-

750G/0002.2/200 32- 6/- 20/-

750G/0000.75/400 16/- 2.5/- 10/-

750G/0001.5/400 16/- 2.5/- 10/-

750G/0002.2/400 16/- 2.5/- 10/-

750G/0003.7/400 25/- 4/- 16/-

750G/0005.5/400 25/40 4/6 16/25

750G/0007.5/400 40/63 6/6 25/32

750G/0011.0/400 63/63 6/6 32/50

750G/0015.0/400 63/100 6/10 50/63

750G/0018.5/400 100/100 10/16 63/80

750G/0022.0/400 100/125 16/25 80/95

750G/0030.0/400 125/160 25/25 95/120

750G/0037.0/400 160/200 25/35 120/135

750G/0045.0/400 200/200 35/35 135/170

750G/0055.0/400 200/250 35/50 170/230

750G/0075.0/400 250/315 50/70 230/280

750G/0090.0/400 315/400 70/95 280/315

750G/0110.0/400 400/400 95/150 315/380

750G/0132.0/400 400/630 150/185 380/450

750G/0160.0/400 630/630 185/185 450/500

750G/0185.0/400 630/800 185/250 500/630

750G/0220.0/400 800/800 250/300 630/700

750G/0250.0/400 800/1000 300/370 700/780

750G/0280.0/400 1000/1200 370/480 780/900

750G/0315.0/400 1200/1400 480/510 900/1000

750G/0355.0/400 1400/1600 510/560 1000/1200

Page 24: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter WIRING

ETD 750 Product Manual 24

Note: A、The main circuit wires is 600V IV plastic isolation.

B、Ambience temperature is 20 for recommended wire area.

C、Wire maximum section area is maximum section area of connection

terminal plate.

Be sure to connect MCCB circuit breaker between power supply and

input terminals (R/L1, S/L2, T/L3).(Please use the creepage breaker which

have high frequency countermeasure)

Needn’t consider the phase sequence of wires connected to input

terminals (R/L1, S/L2,T/L3).

Right connect wires between motor and output terminals of drive (U/T1,

V/T2, W/T3).

Terminals of power lines, motor lines and control lines, please use the

pressure with a casing joint.

Input and output line length to 10 meters as the base, if more than 10

meters, use the recommended wire cross-sectional area than the thicker

wires.

Wires connected to control circuit terminals should use shield wire or

intertwist wire, in addition, the wiring should be fully away from the main

circuit, high power circuits (including the 200V relay sequence circuit).

Please use relay of small-signal or double contacts to prevent poor

contact relay which connected to the control circuit terminals.

Grounding terminals should be effectively grounded.

Page 25: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 25

6. USAGE OF OPERATION PANEL ETD750 series inverter has LCD and LED two kinds of operator panel.

The standard LCD operator panel has a 128 * 64 array LCD display which can

be used to indicate the inverter operation status, operation direction(except for

drives below 3.7kw), alarms, pre-alarm information, Loc/Rem control, I/O

status and parameters setting. Also can choose LED operator panel, for the

detail please refer to introduction of LED operator panel on Chapter 6.4.

The operator panel is removable, and isolated from the power line. The

operator panel support plug-and-play, and can be removed during operation,

but it is suggested not to remove the keypad if the inverter is controlled by the

panel.

6.1 Using operator panel Inverters below 3.7KW (3.7KW included) use the following panel:

Page 26: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 26

3.7KW and above use following panel:

Set frequency / left movementJog / right

movement

LCD

led light

Page 27: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 27

KEY NAME FUNCTION

Rotary knob Browsing the menu, increase or decrease the settings

ENTER Confirm the change of parameters, enter the submenu

ESC Escape from the current menu, back to the previous menu

Shift key Shift the cursor bits left or right

Set the reference frequency

At variables diagnostics status, press this key to enter the frequency reference setting

JOG At variables diagnostics status, press this key to start jog operation

RUN Run command (only valid when in keypad control mode)

STOP stop the inverter if the inverter is running

LOC/REM Switch the control modes, only valid at the stop and variables diagnostics status

RESET Reset the inverter if failure occurs

Operation of the keypad: Power on Initializing:

OP_Freq 50.00Hz OP_Volt 380V

Freq-set 50.00Hz------------MAIN MENU------------

ETD750Initilizing…… AC INVERTER

------------MAIN MENU------------

Table 6-1, function of the key buttons:

Page 28: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 28

Then variable monitoring page occurs after the Initialization: Suppose you want to set 3 to parameter 000, follow the below steps:

I/O Status

QuickStart------------MAIN MENU------------

Param-Setting

I/O StatusParam-Setting

------------MAIN MENU------------

QuickStart

OP_Freq 50.00Hz OP_Volt 380V

Freq-Set 50.00Hz------------MAIN MENU------------

MultiSpeed Param

------------MAIN MENU------------

Freq_volt ParamsBasic Parameters

002 G/P Select001 Control Mode000 Para Select

----------- par ------------

0~7 0

Para Select ---------- Set par ----------

0~7 3

Para Select ---------- Set par ----------

MultiSpeed Param

------------MAIN MENU------------

Freq_volt ParamsBasic Parameters

------------MAIN MENU------------

Modifyparameters

I/O Status

QuickStart------------MAIN MENU------------

Param-Setting

OP_Freq 50.00Hz OP_Volt 380V

Frea-Set 50.00Hz------------MAIN MENU------------

Back to Theoriginal

interface

002 G/P select001 Control Mode000 Para Select

----------- par ------------

ConfirmSave

Page 29: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 29

6.2 LED Operator Panel Introduction

2 0. 0 0

Hz A V

Run Fwd/Rev Loc/Rem Alarm

ETD AC750

ESC JOG START

>> FWD/REV STOP/RESET

(Shift)Remote/Local

Control

Pulse Knob

Confirm

Pulse knob can modify data and has “confirm”function.

Press“FWD/REV” to change the running directionsPress“FWD/REV”to set forward direction when stop statusPress“RUN”running at pre-set direction“ESC+STOP/RESET”to change REMOTE or LOCAL control mode

Page 30: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 30

6.3 LED Button Function Description

Key Name Functions

Pulse Knob Data or function menu up and down

Confirm Change display interface or confirm

ESC Escape Escape to previous menu

>> Shift Cursor shifting when setting data

JOG Jog Enter Jog under diagnostic status

FWD/REV Directions Change running directions when using operator panel control

START Running Run operation(only for panel control)

Stop Stop when at running status

LOC/REM ESC+STOP can change local or remote control under diagnostic menu when stop

STOP/RESET

Reset Reset alarms

Page 31: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 31

6.4 LED Operator Panel Description

Hz A V

Run Fwd/Rev Loc/Rem Alarm

E T D

Hz A V

Run Fwd/Rev Loc/Rem Alarm

1 0. 0 0

Operator Panel Power On

Hz A V

Run Fwd/Rev Loc/Rem Alarm

0. 0 0

Display current running frequency

Hz A V

Run Fwd/Rev Loc/Rem Alarm

0. 0

Display current output current

Hz A V

Run Fwd/Rev Loc/Rem Alarm

0

Hz A V

Run Fwd/Rev Loc/Rem Alarm

F – 0 0 0 0Press button

Hz A V

Run Fwd/Rev Loc/Rem Alarm

F – 0 1 0 0

Modify current parameter

Hz A V

Run Fwd/Rev Loc/Rem Alarm

4 0 0. 0 0

Hz A V

Run Fwd/Rev Loc/Rem Alarm

3 9 9. 0 0

Hz A V

Run Fwd/Rev Loc/Rem Alarm

F – 0 1 0 1

Parameter Setting Interface

After power on press ESC+STOP,change to

LOC mode

Right rotate

Right rotate

Display current output voltageRight rotate

Right rotate

Press button

Left rotate

Press button

Page 32: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 32

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Press ESC escape to monitor interface

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Press >> to modify running frequency quickly

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Press >> to move cursor

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Right rotate modify current frequency

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Press JOG, enter Jog interface

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Press RUN continuouslyto run jog frequency

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Remove RUN to stop

Hz A V

Run Fwd/Rev Loc/Rem Alarm

Re-press JOG escape to monitor interface

Press save current frequency

Page 33: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 33

6.5 LED Parameter List

ETD has LED and LCD two kinds of operators. Customers can choose any operator for drive. Because we normally use LCD, so the manual choose LCD operator as example for description. Parameters referred in the manual are LCD parameters. About LED function code please refer to the corresponding LCD code.

Comparison table for LED and LCD

LED Parameter Name LCD COM Address

000 Parameter Control 000 0x01 001 Control Mode 001 0x98 002 G/P Selection 002 0xA5 003 Mode of Operation 003 0x02 004 L/R Function 004 0x07 005 L/R Selection 005 0x8A 006 Display Mode 006 0x1C 007 Stop Mode 007 0x04 008 Stop Key 008 0x08 009 Confirm Key 009 0x09 010 Carrier Frequency 010 0x48 011 Power Phase 011 0x05 012 Reverse Forbidden 012 0x06 013 Input Voltage 013 0x03 014 Inverter Current 014 0xA0 015 Variable Selection 015 016 Line Selection 016 0x9D

Basic P

arameters A

rea

017 Spare

LED Parameter Name LCD COM Address 100 Rated Voltage 018 0x0B 101 Max Frequency 019 0x0C 102 Max Voltage 020 0x0D 103 Basic Frequency 021 0x0E 104 Intermediate Frequency 022 0x0F 105 Intermediate Voltage 023 0x10 106 Lowest Frequency 024 0x11 107 Lowest Voltage 025 0x12

Frequency voltage regulation area

108 1st Acc time 026 0x13

Page 34: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 34

LED Parameter Name LCD COM Address 109 1st Dec time 027 0x14 110 2nd Acc time 028 0x15 111 2nd Dec time 029 0x16 112 3rd Acc time 030 0x17 113 3rd Dec time 031 0x18 114 4th Acc time 032 0x19 115 4th Dec time 033 0x1A 116 AVR Select 034 0x91 117 V/F Compensation 035 0x0A 118 S Curve 036 0x1B 119 Step 1 Frequency 037 0x1D 120 Step 2 Frequency 038 0x1E 121 Step 3 Frequency 039 0x1F 122 Step 4 Frequency 040 0x20 123 Step 5 Frequency 041 0x21 124 Step 6 Frequency 042 0x22 125 Step 7 Frequency 043 0x23 126 Jog Frequency 044 0x24 127 High Frequency Limit 045 0x2C 128 Lower Frequency Limit 046 0x2D 129 Low-speed selection 047 0x8F 130 U/D Rememorizes 048 0x42 131 U/D Step 049 0x3E 132 Jump Hz1 050 0x50 133 Jump Hz2 051 0x51

Frequency voltage regulation area

134 Jump Amplitude 052 0x52

LED Parameter Name LCD COM Address

200 Running Mode 053 0x8c 201 Step 1 model 054 0x25 202 Step 2 model 055 0x26 203 Step 3 model 056 0x27 204 Step 4 model 057 0x28 205 Step 5 model 058 0x29 206 Step 6 model 059 0x2A

Multi-speed R

unning C

ontrol Area

207 Step 7 model 060 0x2B

Page 35: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 35

LED Parameter Name Properties COM Address 210 DC Voltage Read Only 0xAC

211 PID Feedback Read Only 0xAD

212 Power Output Read Only 0xAB

215 Module Temp 1 Read Only 0xB5

216 Module Temp 2 Read Only 0xB6

217 Module Temp 3 Read Only 0xB7

218 Module Temp 4 Read Only 0xB8

219 Module Temp 5 Read Only 0xB9

220 Module Temp 6 Read Only 0xBA

221 Module Temp 7 Read Only 0xBB

222 Module Temp 8 Read Only 0xBC

Variable M

onitor Area

223 Module Temp 9 Read Only 0xBD

LED Parameter Name LED COM Address

300 Function S2 061 0x31 301 Function S3 062 0x32 302 Function S4 063 0x33 303 Function S5 064 0x34 304 Function S6 065 0x35 305 Function S7 066 0x36 306 Function S8 067 0x36 307 Function Y1 068 0x3C 308 Function Y2 069 0x3D 309 Function Y3 070 0x3E 310 Function Y4 071 0x3F 311 ON Delay 072 0x63

Terminal I / O

Area

312 OFF Delay 073 0x64

LED Parameter Name LED COM Address

400 Main Analog 074 0x40 401 Auxiliary Analog 075 0x41 402 Frequency Loss 076 0x42 403 Frequency Gain 077 0x43 404 Frequency Offset 078 0x45 405 FMA Function 079 0x46 406 FMA Gain 080 0x47 407 Frequency Detection 081 0x5F

Analog A

djustment A

rea

408 FAR Frequency 082 0x89

Page 36: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 36

LED Parameter Name Properties COM Address 410 Software Version Read Only 0xB2

411 Motor Power Read Only 0x9B

Others 412 Inverter Current Read Only 0xA0

LED Operate Function Set Value COM Address

423 Parameter Read 519

Others 424 Parameter Write 517

LED Operate Function Set Value COM Address

500 Instantaneous stop method 083 0x49 501 Speed Search 084 0x4A 502 Blocking Time 085 0x4B 503 Search for V/F 086 0x4C 504 Instantaneous stop time 087 0x4D 505 Auto Restart 088 0x4E 506 Retry Contact 089 0x4F 507 Braking Frequency 090 0x38 508 Braking Current 091 0x56 509 Stop Brake 092 0x57 510 Start Braking 093 0x58 511 Zero Speed Compensation 094 0x67 512 Torque Compensation 095 0x59 513 Motor Tuning 096 0x3F 514 Line Resistance 097 0x5A

515 Motor Leakage Inductance

098 0x39

516 Motor Iron Loss 099 0x5B 517 Slip Gain 100 0x85 518 No-load Current 101 0x86 519 Delay Correction 102 0x87 520 Acceleration Reference 103 0x5D 521 Run Benchmark 104 0x5E 522 Dec Stall Prevent 105 0x5C 523 Timer Selection 106 0x53 524 Timer L 107 0x54

Special Usage Area

525 Timer H 108 0x55

Page 37: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 37

LED Parameter Name LCD COM Address 600 Overload Reference 109 0x2E 601 Overload Protection 110 0x2F 602 Torque Detection 111 0x60 603 Torque Reference 112 0x61 604 Over Torque T 113 0x62 605 SPI Reference 114 0x68 606 SPI Delay 115 0x69 607 SPO Reference 116 0x6A 608 SPO Delay 117 0x6B 609 OH Stop 118 0x30

Failure Protection A

rea

610 DBR Overheat 119 0x65

LED Parameter Name LCD COM Address

700 PID Selection 120 0x6C 701 Feedback Gain 121 0x6D 702 Prop Gain 122 0x6E 703 Integral Time 123 0x6F 704 Derivative Time 124 0x70 705 PID Offset 125 0x71 706 Integral Limit 126 0x72 707 Filter Time 127 0x73 708 Feedback Detection 128 0x74 709 Loss Thresh 129 0x75

PID

Setting A

rea 710 Loss Time 130 0x76

LED Parameter Name LCD COM Address

800 Energy-saving Selection 131 0x77

801 Energy-saving Gain 132 0x78

802 60Hz voltage 133 0x79

803 6Hz voltage 134 0x7A

804 Calculation Time 135 0x7B

805 Voltage Limit 136 0x7C

806 100% Anti jump 137 0x7D

Energy-saving settings area 807 5% Anti jump 138 0x7E

Page 38: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter USAGE OF OPERATION PANEL

ETD 750 Product Manual 38

LED Parameter Name LCD COM Address

900 Local Address 139 0x82

901 Baud Rate 140 0x83

902 Parity Check 141 0x84

903 Timeout 142 0x7F

904 CE Stop 143 0x80

Com

munications

and monitor Zone

905 Spare

6.6 LED Display Code Comparison table

Warnings and failures of LED and LCD have the same meanings, but

have different characters. The comparison table as follow;

A —

O —

S — T —

R —

D —

B —

M —

7 —

Page 39: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SIMPLE OPERATION

ETD 750 Product Manual 39

7. SIMPLE OPERATION 7.1 Inspection and preparation before running

Be sure to check the following items before start: Check the wiring is right or not. Especially check the output terminals U/T1、V/T2、W/T3 can’t connect to power supply, and ensure the grounding terminal is properly earthed. Confirm terminals or the exposure electrification parts are not short-circuited or short to the ground. Confirm terminals connections, pluggable connectors and bolts not loose. When connect to the power supply, make all the switches in open state and ensure the inverter can’t start and there are no unexpected actions. Check the following items after connect to the power supply:

No failure showed on the operator panel. No foreign body in cooling fan of inverter and wind channel

unobstructed.

Switch on the power supply after the cover board be installed. Can’t remove cover board when the power supply on. Can’t operate switches with wet hands to prevent electric shock accidents.

7.2 Operation Methods There are various operation methods, please refer to description of

“Chapter 6 Usage of operation panel” and “Chapter 8 Function parameters list”. Choose the most appropriate operation method according to application requirements and operation requirements. Operation of commonly used methods such as Table 7-1

7.3 Commissioning Verify that no abnormal situation, the right set up all the function

parameters for the inverter running. Do commissioning after set all the parameters done.

Page 40: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SIMPLE OPERATION

ETD 750 Product Manual 40

It is recommended running at lower frequency, no abnormal situation then gradually increase running frequency. Default setting to REM3 (remove control), can set by parameter “003” or switch by STOP key.

Table 7-1,Normally used operation methods:

For start press START key, for stop press STOP key. Check following items when running:

Motor rotation direction is right. Motor rotation is smooth (no howling or vibration)。 Acceleration/deceleration is smooth.

If no abnormalities then you can increase frequency from pulse knob .After the commissioning that can be put into operation.

If the inverter or motor operation exception occurs, should immediately stop running and refer to “Chapter 10 Failure Countermeasure” to verify the reasons for abnormal conditions. After the inverter stop output, terminals R/L1,S/L2,T/L3 still live if not disconnected the main contactor. At this time touch terminals U/T1、V/T2、W/T3 will be shocked. In addition, even if remove the main power supply, because of there is charging voltage on filter capacitor, it will take some time to discharge voltage. After remove main power supply 10 minutes and measure the middle dc circuit voltage by multi-meter, confirm the voltage is lower the safety voltage then can touch the internal circuit of inverter.

Operation Methods Freq Setting Operation

command Operation panel

control Press ,or pulse knob on the operation panel

Start: Press START Stop: Press STOP

Remove control

Potentiometer or analogue voltage、current

Input connection terminals S1-SC、

S2-SC

Administrator
高亮
Page 41: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 41

8. FUNCTION PARAMETERS Zone

Parameters Name Function definition Setting

range Default Com address

000 Parameter

control

0: Parameters can be modified and settings. 1: Forbid parameter modifying. 2~6:Undefined. 7: Reset all parameters.

0~7 0 0x01

001 Control mode

0: V / F control, 1:No inductance vector control, enhance the torque response, providing high-quality operating performance

0~1 1 0x98

002 G / P select

0: constant torque, 150% overload for 1 minute. 1: variable torque, blower, pump, 120% overload for 1 minute

0~1 *3 0xA5

003 Mode of operation

(Set) (control) (reference) 0: Keypad Keypad 1: Terminal Keypad 2: Keypad Terminal 3: Terminal Terminal 4: Keypad Communication 5: Terminal Communication 6: Communication Communication 7: Communication Keypad 8: Communication Terminal

0~8 3 0x02

004 L / R function

0: LOC / REM function is disabled 1: LOC / REM function enabled 0~1 1 0x07

005 L / R selection

0: LOC/REM switching will be valid after stopping the drive,

1: LOC/REM control will be valid immediately.

0~1 0 0x8A

006 Display Mode

0: 0.01 Hz unit 1: 0.1% of the units 2 ~ 39: R / min unit R / min = 120* Frequency ref (Hz) / Electric Machine poles 40~3999: the 4th bit of 006 set the location of the decimal Point, the other three bits indicates the percentage of the freq ref

0~ 3999 0 0x1C

Basic param

eters of area

007 Stop mode

0: decelerate to stop 1: Free stop 2: free stop according to timer 1 3: free stop according to timer 2

(conventional)

0~3 0 0x04

Page 42: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 42

Zone Parameters Name Function definition Setting range Default Com

address

008 Stop key

0: STOP key is valid only when the inverter is controlled by keypad; 1: STOP key always valid.

0~1 1 0x08

009 Enter key

0: when setting frequency via keypad, no need of pressing Enter. 1: when setting frequency via keypad, have to press Enter key.

0~1 1 0x09

010 Carrier frequency

1,2,4 ~ 6: Carrier frequency = set value * 2.5KHz 3: carrier frequency = 8.0KHZ. 7/8/9: carrier frequency = 12/24/36 * Fout

1~9 *3 0x48

011 Power Phase

0: Forward Rotating, Viewed at load-side 1: Reverse Rotating, Viewed at load-side

0~1 *3 0x05

012 Reverse

Forbidden

0: reverse running permitted 1: Reverse running is Forbidden 0~1 0 0x06

013 Input Voltage Set the inverter's input voltage.

150.0~255.0 V*1

200.0 V*1 0x03

014 Inverter Current

Inverter rated current value, read-only parameter

0.0~2000.0A *3 *4

015 Variable selection 0:m/s 1:Mpa/mm2 2:Kg/mm2 0~2 *3 *5

016 Wire selection Single or three-wire control definitions 0~2 0 0x9D

Basic param

eters of area 017

Language choose 0:Chinese 1:English 0~1 *3 *5

Zone Parameters Name Function definition Setting

range Default Com address

018 Rated Voltage Set motor rated voltage

150.0~ 255.0V*

1

200.0V*1 0x0B

019 Maximum frequency

024 < 022 < 019 50.00~400.00

Hz 50.00 0x0C

020 Maximum voltage 025<023<020

0.1~ 255.0 V*1

200.0V*1 0x0D

Frequency voltage regulation area

021 Basic frequency

The inverter output maximum voltage at this frequency

0.20~ 400.00

Hz

50.00 Hz 0x0E

Page 43: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 43

Zone Parameters Name Function definition Setting range Default Com

address022

Intermediate Frequency

0.10~ 399.99Hz 3.00 Hz 0x0F

023 Intermediate

voltage

0.1~50.0V*1

12.0V*1 0x10

024 Lowest

Frequency

0.10~3.00Hz 1.50 Hz 0x11

025 Lowest Voltage

0.1~50.0V*1

6.0 V*1 0x12

026 1st Acc time

0.0~ 3600.0S 10.0S 0x13

027 1st Dec time

Time of frequency from 0% to 100%, the unit of time setting is 0.1s 0.0~

3600.0S 10.0S 0x14

028 2nd Acc time

0.0~ 3600.0S 10.0S 0x15

029 2nd Dec time

2nd Acc/Dec time is valid in the multi-function terminal blocks or internal-controlled multi-speed. Same way setting as 26/027.

0.0~ 3600.0S 10.0S 0x16

030 3rd Acc time

0.0~ 3600.0S 10.0S 0x17

031 3rd Dec time

0.0~ 3600.0S 10.0S 0x18

032 4th Acc time

0.0~ 3600.0S 10.0S 0x19

033 4th Dec time

Acc/Dec time is valid in the multi-function terminal blocks or internal-controlled multi-speed. Same way setting as 26/027.

0.0~ 3600.0S 10.0S 0x1A

034 AVR Select

0:No Output Voltage stabilizing function 1:Output Voltage stabilizing enabled 2:Output Voltage stabilizing is disabled after stop

0~2 1 0x91

035 V / F

compensation

0~14: fixed V/F mode. 15: arbitrary V/F mode. 0~15 *3 0x0A

036 S Curve select

0: No S curve 1: 0.2 s 2: 0.5 s 3: 1.0 s

0~3 1 0x1B

037 Step 1 Freq Set the main frequency Reference。 0.00~

400.00Hz 0.00 Hz 0x1D

Frequency voltage regulation area

038 Step 2 Freq

External multi-stage speed 2, or internal-controlled multi-speed step 2 frequency

0.00~ 400.00Hz 0.00 Hz 0x1E

Page 44: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 44

Zone Parameters Name Function definition Setting range Default Com

address

039 Step 3 Freq

External multi-stage speed 3, or internal-controlled multi-speed step 3 frequency

0.00~ 400.00Hz 0.00 Hz 0x1F

040 Step 4

Frequency

External multi-stage speed 4, or internal-controlled multi-speed step 4 frequency

0.00~ 400.00Hz 0.00 Hz 0x20

041 Step 5

Frequency

External multi-stage speed 5, or internal-controlled multi-speed step 5 frequency

0.00~ 400.00Hz 0.00 Hz 0x21

042 Step 6 Frequency

External multi-stage speed 6, or internal-controlled multi-speed step 6 frequency

0.00~ 400.00Hz 0.00 Hz 0x22

043 Step 7 Frequency

External multi-stage speed 7, or internal-controlled multi-speed step 7 frequency

0.00~ 400.00Hz 0.00 Hz 0x23

044 Jog frequency

JOG frequency reference valid when the terminal was defined as JOG input, or pressing “JOG” key

0.00~ 400.00Hz 6.00 Hz 0x24

045 High freq limit

The higher limitation of input frequency. (Percentage of the Maximum frequency)

0~100% 100% 0x2C

046 Lower freq

limit

The lower limitation of input frequency. (Percentage of the Maximum frequency)

0~100% 0% 0x2D

047 Low-speed selection)

0: Free running 1: run at start freq 2: running at 0 speed.(The 0 speed torque controlled by 0 speed gain)

0~2 1 0x8F

048 U/D rememorizes

Memorize the frequency when the multi-function inputs are defined as U/D.

0~1 0 0x42

049 U / D Step Set the frequency step in U/D mode. 0.00~

2.50Hz 0.00 Hz 0x3E

050 Jump Hz1

0.00~ 400.00Hz 0.00 Hz 0x50

051 Jump Hz2

Jump frequency 1. This function is invalid if 052 is set to 0. 0.00~

400.00Hz 0.00 Hz 0x51

Frequency voltage regulation area

052 Jump amplitude

Jump frequency 2. This function is invalid if 052 is set to 0.

0.00~ 25.00Hz 1.00 Hz 0x52

Page 45: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 45

Zone Parameters Name Function definition Setting range Default Com

address

053 control mode

0: Normal operation; 1: internal control multi-stage speed mode. The inverter stop after running for a cycle time. 2: internal control multi-stage speed mode, the inverter runs continuously and repeatedly, only stop, fault, emergency stop commands are accepted when running. 3: internal control multi-stage speed mode, the inverters go on running at the final speed after a cycle.

0~3 0 0x8C

054 Step 1 model

F1~R4 0~4000S

F1 0S 0x25

055 Step 2 model

F1~R4 0~4000S

F1 0S 0x26

056 Step 3 model

F1~R4 0~4000S

F1 0S 0x27

057 Step 4 model

F1~R4 0~4000S

F1 0S 0x28

058 Step 5 model

F1~R4 0~4000S

F1 0S 0x29

059 Step 6 model

F1~R4 0~4000S

F1 0S 0x2A

Multi-segm

ent speed run control region

060 Step 7 model

example: F 2 100 100: running time for the step 100s 2: using acceleration and deceleration time 2 F: running direction F = Forward (counterclockwise) R = reverse (clockwise)

F1~R4 0~4000S

F1 0S 0x2B

Zone Parameters Name Function definition Setting

range Default Com address

061 S2 Function 0~26 0 0x31

062 S3 Function 2~26 2 0x32

Terminal I / O

Area

063 S4 Function

Input terminal function settings: 00: Reverse run command (2-wire mode) 01:Forward/reverse run command(3wires mode) 02:External fault (Normal Close contact input) 03:External fault (normally open contact input) 04: Fault Reset 05: Local / Remote selection 06:Communication / control circuit terminal selection 07: emergency stop 08:Main frequency reference input select (current / Voltage) 09: Multi- speed command 1 10: Multi- speed command 2

2~26 4 0x33

Page 46: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 46

Zone Parameters Name Function definition Setting range Default Com

address

064 S5 Function 2~26 9 0x34

065 S6 Function 2~26 10 0x35

066 S7 Function 2~26 11 0x36

067 S8

Function

11: Multi- speed command 4 12: Jog Run 13:Acceleration / deceleration time selection 1 14:Acceleration / deceleration time selection 2 15:External BB instructions (normally open contact input) 16:External BB instructions (NC contact input) 17:Speed search (search from the maximum frequency ) 18:Speed search (search from the start frequency) 19:parameter setting permission / forbidden 20: PID integral value reset 21: PID control forbidden 22: Timer Function 23: Inverter overheat alarm (OH3) 24: analog value for a given sample / hold 25: KEB command (A contact input) 26: KEB command (B contact input) 27:UP/DOWN command (only available in 067 )

2~27 12 0x37

068 Y1

Function 0~18 0 0x3C

069 Y2

Function 0~18 1 0x3D

Terminal I / O

Area

070 Y3

Function

Output terminal function settings: 00: Fault 01: running 02: Frequency Match 03: Any frequency Match 04:Frequency detection (output frequency ≤ Frequency Ref) 05:Frequency detection (output frequency ≥ frequency Ref) 06: Over torque detection (normally open) 07:Over torque detection(Normal close) 08: BB (base blocked) 09: running mode 10: Inverter ready for running 11: Timer Function 12: Auto re-start 13: OL (overload) Pre-Alarm 14: frequency reference Loss 15: Communication data output 1 (D0 function) 16: Communication data output 2 (D0 function) 17: PID feedback Loss

0~18 2 0x3E

Page 47: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 47

Zone Parameters

Name Function definition Setting range Default Com

address

071 Y4 function

18: OH1 Alarm 19: zero speed running 20: Output minimum frequency 21: Output Maximum frequency

0~18 3 0x3F

072 ON Delay

Input ON signal delay time, Unit 0.1 seconds.

0.0~ 25.5S *3 0x63

Terminal I / O

Area

073 OFF Delay

Output OFF signal delay time, Unit 0.1 seconds.

0.0~ 25.5S *3 0x64

Zone

Parameters Name Function definition Setting

range Default Com address

074 Main Analog

0: Main frequency Ref is the terminals V (0 ~ 10V). 1: Main frequency Ref is the terminals FI (4 ~ 20mA).

0~1 0 0x40

075 Auxiliary analog

0: FV is 0 ~ 10V input (open circuit SW1-1) 1: FI is 4 ~ 20mA input.

0~1 1 0x41

076 Frequency

Loss

0: Frequency Loss handling is invalid 1: Frequency Loss handling is valid 0~1 0 0x42

077 Frequency

Gain

The gain of the frequency analog input, voltage (current) 10V (20mA) stands for what percentage of the maximum frequency(019)

0~ 200%

100% 0x44

078 Frequency

Offset

The offset of the frequency analog input

-100~ 100% 0% 0x45

079 FMA function

0: Output frequency (10V---maximum frequency) 1: Output current (10V stand for the rated current) 2: Output power (10V inverter—inverter rated power) 3: DC voltage (10V/400V (200V Grade) 10V/800V (400V grade)

0~3 0 0x46

080 FMA gain Adjust the analog output level 0.01~2.

00 1.00 0x47

081 Frequency detection

Set the frequency for frequency detecting.

0.00~ 400.00

Hz 0.00 0x5F

Analog adjustment area

082 FAR Frequency

Set the frequency for frequency matching.

0.00~ 25.00

Hz 0.00 0x89

Page 48: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 48

Zone Parameters Name Function definition Setting range Default Com

address

083 Instantaneous stop

method

0: Do not continue running 1: Go on running within the Instantaneous compensation time 2: Always continue running (no Uu1, Uu3 Fault alarm)

0~2 0 0x49

084 Speed Search

Limitation of the current during the speed search 0~200% 110% 0x4A

085 Blocking time

Set the minimum time for blocking the inverter output, during the speed search.

0.5~5.0S *3 0x4B

086 Search for V / F Set V/F mode for the speed search. 0~100% *3 0x4C

087 Instantaneous stop

time

Set the compensation for instantaneous power failure, unit 0.1S. 0.0~2.0S *3 0x4D

088 Auto Re-start

Set the inverter auto-restart times when Inverter fault occurs. 0~10 0 0x4E

089 Retry contact

0: the contact closed during the re-start period 1: the contact open during the re-start period

0~1 0 0x4F

090 Braking frequency

When the “stop” instruction was assigned, the inverters decelerate to this frequency and then begin to brake with DC voltage input.

0.0~ 5.0Hz

0.0 Hz 0x38

091 Braking Current Set DC braking current value. 0~100

% 50% 0x56

092 Stop brake

Set the DC braking time when stopping the inverter.

0.0~10.0S 0.5S 0x57

093 Start braking

Set the DC braking time when starting the inverter

0.0~10.0S 0.0S 0x58

094 Zero Speed Gain Set the zero speed current. 0~100% 50% 0x67

095 Torque

Compensation

The torque output compensation gain. No need to change this value in most cases.

0.0~3.0 1.0 0x59

096 Motor Tuning

Measurement of motor parameters 0: No self-tuning function 1: static self- tuning (suitable for motors with load) 2: Dynamic self- tuning

0~2 0 0x3F

097 Line resistance

0.000~65.530

R *3 0x5A

098 Motor leakage

inductance

0~40.0H 1.2H 0x39

Special Usage Area

099 Motor iron loss

Internal use for the inverter torque compensation. No need to change in most cases.

0~ 9999W

440W 0x5B

Page 49: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 49

Zone Parameters Name Function definition Setting range Default Com

address

100 Slip gain

Gain of the slip frequency to compensate the speed drop due to the load.

0.0~ 9.9% 0.0% 0x85

101 No-load Current Set the no load motor current. 0~

99in% 30in% 0x86

102 Delay correction

Set the filter time for compensating the slip speed.

0.0~ 25.5 S 0.0 S 0x87

103 Acceleration

reference

Set Stall prevention reference during acceleration. Unit: 1% of inverter rated current 100%.

30~ 200in%

170in% 0x5D

104 Run Benchmark

Set Stall prevention reference during running. Unit: 1% of inverter rated current 100%.

30~ 200in%

170in% 0x5E

105 Dec stall Prevent

0: No stall prevention function during deceleration 1: with stall prevention function during deceleration

0~1 1 0x5C

106 Timer selection

0: the cumulative time of Power on 1: The cumulative time of running 0~1 1 0x53

107 Timer L

0~9999H 0H 0x54

108 Timer H

If 106 were chosen as the cumulative timer, accumulate the time from 107,108 values.

0~27 *10000

H 0H 0x55

109 Rated current Motor rated current. 20~

200 in % *2 0x2E

110 Overload Protection

0: No Protection 1: Standard motor (time constant 8 minutes) 2: Standard motor (time constant 5 minutes) 3: Inverter motor (time constant 8 minutes) 4: Inverter motor (time constant 5 minutes)

0~4 1 0x2F

Special Usage Area

111 Over Torque

Detection

0: No over torque detection 1:Only detect during the speed match, continue running after detection 2:run-time detection, continue running after detection 3:Only detect during the speed match, stop running after detection 4: run-time detection, stop running after detection

0~4 0 0x60

Page 50: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 50

Zone Parameters Name Function definition Setting range Default Com

address

109 Rated current Motor rated current.

20~ 200 in

% *2 0x2E

110 Overload Protection

0: No Protection 1: Standard motor (time constant 8 minutes) 2: Standard motor (time constant 5 minutes) 3: Inverter motor (time constant 8 minutes) 4: Inverter motor (time constant 5 minutes)

0~4 1 0x2F

111 Over Torque

Detection

0: No over torque detection 1:Only detect during the speed match, continue running after detection 2:run-time detection, continue running after detection 3:Only detect during the speed match, stop running after detection 4: run-time detection, stop running after detection

0~4 0 0x60

112 Over torque reference

Set the over torque detection reference.

30~ 200in%

160 in% 0x61

113 Over torque time Set the over torque detection time. 0.1~10.

0S 0.1S 0x62

114 SPI reference

Set input phase loss detection level, DC400V (200V type), DC800V (400V type) 100%

1~100% 20% 0x68

115 SPI Delay

Set input phase loss detection time = 1.28 seconds × (112 settings)

2S~255S 8S 0x69

116 SPO reference

Set output phase loss detection level, DC400V (200V type), DC800V (400V type) 100%

0~100% 0% 0x6A

117 SPO Delay Set output phase loss detection time 0.0~2.0

S 0.2S 0x6B

118 OH Stop

Stop when the heatsink over temperature: 0: decelerate to stop(failure) 1: Free stop 2: decelerat2 stop 2 (failure) 3: Continue running (alarm)

0~3 3 0x30

Special Usage Area

119 DBR overheating

Brake resistor overheat protection: 0: No braking resistor overheat protection 1: with braking resistor overheat protection

0~1 0 0x65

Page 51: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 51

Zone Parameters Name Function definition Setting range Default Com

address

120 PID selection

0: No PID Control 1: PID control (Error controlled by D) 2: PID control (feedback controlled by D)3: PID control (Fdbk value was reversed)

0~3 0 0x6C

121 Feedback gain PID feedback gain 0.00~

10.00 1.00 0x6D

122 Prop gain the proportional gain 0.0 ~

10.0 1.0 0x6E

123 Integ time the Integration gain 0.0~

100.0S10.0S 0x6F

124 Derivative Time the Derivative gain 0.0~

10.0S 0.0S 0x70

125 PID offset PID Offset after PID regulator. -109~

109% 0% 0x71

126 Integral Limit Upper Limitation of the Integral output 0

~109%100% 0x72

127 Filter Time

Set the output frequency delay time after PID regulator

0.0~2.5S 0.0S 0x73

128 Fdbk Detection

0: No PID feedback loss detection 1:PID feedback loss detection enabled 0 ~1 0 0x74

129 FB Loss Thresh Set the PID feedback threshold. 0 ~

100 % 0% 0x75

PID

settings area

130 Lost Time

Set PID feedback loss detection time. Unit 0.1S.

0.0~ 25.5S 1.0S 0x76

Zone Parameters Name Function definition Setting

range Default Com address

131 Energy-saving

enable

0: energy-saving control is invalid 1: Energy-saving control is enabled 0~1 0 0x77

132 Energy-Saving

Gain

Set the coefficient of maximum efficiency. The default value is set according to the standard motor.

0.00~ 655.00 *3 0x78

133 60Hz voltage

The lower limitation of the energy-saving voltage When running at 60Hz.

0~120% 50% 0x79

134 6Hz voltage

The lower limitation of the energy-saving voltage When running at 6Hz.

0~25% 12% 0x7A

135 calculation time

Set the average time of the power calculation in energy-saving mode. 1~200 1 0x7B

136 Voltage Limit

Limitation of the output voltage in the best-performance control mode.

0~100% 0% 0x7C

137 100% Anti jump

The range of voltage variation when the best running voltage is 100%.

0.1~10.0% 0.5% 0x7D

Energy-saving settings area

138 5% Anti jump

The range of voltage variation when the best running voltage is 5%.

0.1~10.0% 0.2% 0x7E

Page 52: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FUNCTION PARAMETERS

ETD 750 Product Manual 52

Zone Parameters Name Function definition Setting range Default Com

address139

Local Address 1~31: inverter charged with MODBUS communication address. 0~31 0 0x82

140 Baud Rate

0:1200 BPS 1:2400BPS 2:4800BPS 3:9600BPS 4:19200BPS 5:38400BPS

0~5 0 0x83

141 Parity Check

0:7N2 For ASCII 1:7E1 For ASCII 2:7O1 For ASCII 3: 8N1 For RTU 4: 8E1 For RTU 5: 8O1 For RTU

0~5 3 0x84

142 timeout

0: No timeout detection 1: timeout detection enabled 0~1 1 0x7F

Com

munications and S

urveillance Zone

143 CE Stop

0: deceleration to stop (use Dec time 1) 1: Coast to stop 2: deceleration to stop (use Dec time 2) 3: Continue running (alarm)

0~3 1 0x80

Note: Default values underlined can be modified when the drive running.

Description: * 1 Means: The upper limitation and default value of the Voltage doubled for the 400V type inverters. * 2 Means: The motor rated current settings is10% ~200% of the inverter’s rated current. * 3 Means: The default values will be different according to the size of inverters. * 4 Means: read-only data。 * 5 Means: No communication. These parameters will not change if the default values were restored.

The reserved functions are not available in this software version.

Page 53: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 53

9. DETAILED EXPLAINATIONS 000 parameters setting range: 0 ~ 7 default: 0

0: Parameters are allowed to be changed. 1: Parameters can not be changed. (Protect user’s parameters.) 2 ~ 6: reserved 7: change all parameters to default values. If the user changed the parameters by mistake and can not restore them properly, this function should be implemented. Set this parameter to 7, and then press "ENTER" button, you can make all the function code data values back to the initial value, and then re-set the required parameters.

001 Control mode Range: 0 ~ 1 Default: 1 0: V / F control. 1: Sensor less current vector control. In this move, the torque response can be improved and provide a high performance.

002 G / P options Range: 0 ~ 1 Default: * 0: G-type constant torque, overload 150% for 1min 1: P fan pump-type, overload 120% for 1min Note: Changing this parameter, No 099 parameters will subsequently change. The inverter rated power will shift to an upper grade if you change this parameter from 0 to 1.

003 Mode of operation Range: 0 ~ 8 Default: 3 ETD750 has 2 operate modes, LOCAL and REMOTE. Only when the inverter is stopped, these two control modes can be switched by pressing the "STOP" key. The selected mode can be confirmed by the control mode status indication shown on the keypad panel. The default setting is REMOTE (frequency reference from FV and FI, and the “start” and “stop” command from the terminals.) The Multi-function terminals S3-S8 works under both modes. LOC: The reference signal and running commands are from keypad panel. REM: The reference signal and running commands are assigned as the following table shows:

Page 54: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 54

Set Run Command Selection Frequency Reference

0 From Keypad Panel From Keypad Panel

1 From terminals From Keypad Panel

2 From Keypad Panel From the terminals FV and FI

3 From terminals From the terminals FV and FI

4 From Keypad Panel Serial communication

5 From terminals Serial communication

6 serial communication Serial communication

7 serial communication From Keypad Panel

8 serial communication From the terminals FV and FI

004 L / R function Range: 0 ~ 1 Default: 1

0: LOCAL / REMOTE key are disabled 1: LOCAL / REMOTE key enabled.

005 L / R option Range: 0 ~ 1 Default: 0 0: L/R switching will take effect after stopping the inverter; 1: L/R switching will take effect immediately.

006 Display Mode Range: 0 ~ 3999 Default: 0 0: 0.01Hz Units 1: 0.1% Units 2 ~ 39: 120 × Frequency Ref (Hz) / 006 (number of motor pole) = r / min 40 ~ 3999: The 4th bit set the decimal point position, the first 3 bits set the value which correspond to 100% of frequency Ref. For example: the variable corresponding to the maximum frequency is 1.60, and then this parameter should set to 2160. In the constant pressure water supply applications, the target pressure value 1.60Mpa can be displayed together with No 015 parameter settings.

007 Ways to stop Range: 0 ~ 3 Default: 0 Select the desired stopping method: 0: decelerate to stop using 1st Dec time (default value) 1: coast to stop 2: coast to stop using 1st Dec time 3: coast to stop using 2nd Dec time Settings: 0 with the first deceleration time, deceleration to stop (factory

Page 55: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 55

setting)

When the stop command is applied, the inverter will decelerate according to Dec time 1, and apply DC braking when the output frequency reaches the braking frequency, while the over-voltage (OU) alarm may occur during the deceleration if the Dec time is too short or the load inertia is too big. In this case, the Dec time should be increased or a braking resistor should be installed. Braking torque: About 20% of motor rated torque if no braking resistor, 150% of motor rated Torque if the braking resistor exists. Setting: 1 coast to stop

Output Instruction

Run command

When the stop command input inverter output disconnect

ON OFF

The motor begin to coast when the forward/reverse running instruction is canceled. Setting 2: coast to stop using 1st Dec time

Example: coast to stop using 1st Dec time: After the “stop” command applied, the inverter does not response to the “start” command within the 1st

Dec time. If the “start” command is applied, the inverter will run again after 085 (minimum base block time).

Page 56: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 56

Set 3: coast to stop using 2nd Dec time

008 Stop key Range: 0 ~ 1 Default: 1 0: STOP button is valid only when the inverter is controlled by keypad. 1: STOP button is valid in any cases.

009 Confirmation Key Range: 0 ~ 1 Default: 1 0: It’s no need to press “ENTER” for confirmation when changing frequency by keypad. 1: It’s necessary to press “ENTER” for confirmation when changing frequency by keypad.

Example: coast to stop using 1st Dec time: If the “start” command is applied within the deceleration time, the inverters will not response to the commands until the Dec time elapsed. The “start” command is invalid with the Minimum BB time.

Page 57: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 57

010 Carrier Frequency Range: 1 ~ 9 Default: *

Set the carrier frequency:

Setting Carrier (KHZ)

Metallic sound from the motor

Interference noise and leakage current

7 12 Fout 8 24 Fout 9 36 Fout 1 2.5 2 5.0 3 8.0 4 10.0 5 12.5 6 15.0

Bigger

Small

Little

Much

Page 58: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 58

0: When applying forward command, the revolution direction of the motor is counter- clockwise if viewed at the load side. 1: When applying forward command, the revolution direction of the motor is clockwise if viewed at the load side.

012 Prohibition of Reverse Range: 0 ~ 1 Default: 0 0: Reverse running is allowed. 1: Reverse running is forbidden.

013 Input Voltage Range: 150.0V ~ 255.0V *1 Default: 200.0V * 1 Set the input voltage, this value defines the protection level of the inverter.

014 Frequency Current Range: 0.0 ~ 2000.0A Default: * The rated current of the inverter; read-only parameter

015 variable selection range: 0 ~ 2 Default: * Set the units that will be displayed when 006 value is set between 40 ~ 3999, 0: m / s m / s 1: Mpa/mm2 2: Kg/mm2

016 wire selection range: 0 ~ 2 Default:0 This function is effective when using the terminal operation. 0: single-wire mode: S1 on – forward, S1 off - stop

2-wire mode: S1 on – forward, S1 off – stop, S2 on – reverse, S2 off – stop. 3-wire mode: S1 Rising-edge trigger – running, S2 off – stop, S3 – switch forward/reverse.

1: single-wire mode: S1 Rising-edge trigger-running and stop switch. 2-wire mode: S1 on – forward, S1 off – stop, S2 – switch forward/reverse.

3-wire mode: S1 Rising-edge trigger – forward, S2 off – stop, S3 – Rising-edge trigger – reverse.

2: single-wire mode: S1rising-edge trigger – running and stop switch. 2-wire mode: S1 on – forward, S1 off – stop, S2 rising-edge trigger – switch

forward/reverse. 3-wire mode: S1 rising-edge trigger – running, S2 off – stop, S3 rising-edge

trigger - switch forward/reverse. 017 Language selection range: 0 ~ 1 Default: *

0: Chinese menu 1: English menu

011 Power Supply Phase Range: 0 ~ 1 Default : 0

Page 59: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 59

Following are the connection sketch map of single-wire, 2-wire, 3-wire when parameter 016 is 0 or 1or 2.

SC

S1

016 = 0

Single-wire connection

S1S2

S3

SC

SC

S1

016 = 1

016 =1

S1

SC

016 = 0

016 = 0

SC

S1

016 = 2

S1

SC

016 = 1S1

SC

016 = 2S2

S1

S2S3

SC

016 = 2

S2

Single-wire mode :061>1:061=0:061=1

Note: When parameter 061 bigger than 1, multi-function junction has function define on page 59-60 except for choose single-wire, in addition, setting values of parameter 061-067 can’t be repeated.

S2

S1

S2

S3

SC

Single-wire connection

Single-wire connection 2-wire connection

2-wire connection 2-wire connection

3-wire connection 3-wire connection

3-wire connection 2-wire mode3-wire mode

Page 60: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 60

This parameter sets the motor rated voltage. The inverter calculates the V/F voltage according to this parameter.

※For 400V level inverters, the value is doubled. When a specific induction motor is utilized, or the mechanical equipments need a special torque adjustment, the exclusive values for above parameters must be set to meet certain requirements. The following relationship must be met when setting the above parameters: 025 ≤ 023 ≤ 020

The output torque will increase along with the increase of the V/F mode start voltage, while the excessive increase will cause the following problems: 1. Not work properly due to the over-field current. 2. Large vibration or overheating. Note: The V/F voltage should be increased step by step along with monitoring the motor current.

026 1st Acc time range: 0.0 ~ 3600s Default: 10.0s 027 1st Dec time range: 0.0 ~ 3600s Default: 10.0s 028 2nd Acc time range: 0.0 ~ 3600s Default: 10.0s 029 2nd Dec time range: 0.0 ~ 3600s Default: 10.0s 030 3rd Acc time range: 0.0 ~ 3600s Default: 10.0s 031 3rd Dec time range: 0.0 ~ 3600s Default: 10.0s 032 4th Acc time range: 0.0 ~ 3600s Default: 10.0s

018 Motor Rated voltage range: 150.0V ~ 255.0 Default: 200.0 V * 1

019 maximum frequency range: 50.00Hz ~ 400.00Hz Default: 50.00Hz 020 Maximum Voltage range: 0.1V ~ 255.0V * 1 Default: 200.0V * 1 021 reference frequency range: 0.20Hz ~ 400.00Hz Default: 50.00Hz 022 intermediate frequency range: 0.10Hz ~ 399.99Hz Default : 3.00Hz 023 intermediate voltage range: 0.1V ~ 50.0V * 1 Default: 12.0V * 1 024 minimum frequency range: 0.10Hz ~ 3.00Hz Default : 1.50Hz 025 minimum voltage range: 0.1V ~ 250.0V * 1 Default: 6.0V * 1

Page 61: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 61

033 4th Dec time range: 0.0 ~ 3600s Default: 10.0s Acceleration time: Acc time is the time taken for the motor to accelerate from 0Hz to the maximum frequency. Deceleration time: Dec time is the time taken for the motor to decelerate from maximum frequency to 0Hz.

0: No Output voltage regulation function 1: Output voltage regulation function enabled. 2: Output voltage regulation function will be canceled after stop.

0~14: Choose the fixed V/F curve. 15: choose arbitrary V/F curve. Setting: 0~14 fixed V / F curves Fig 8-1 shows the fixed V/F mode. (The Listed voltage is for 200V level inverters, the voltage for 400V level inverters is doubled.) The following items must be correct when choosing a certain V/F curve: A. The motor voltage and frequency characteristics; B. Maximum speed of the motor Only under the following conditions, a high starting torque is needed. Typically do need a high starting torque. A. The wires are very long. (150m or longer) B. The voltage drop too much when starting C. AC reactor has been connected to the inverter's input or output D. A motor which have a smaller power than the inverter was utilized.

034 AVR selection range: 0 ~ 2 Default : 1

035 V/F curve selection range: 0 ~ 15 Default: 15

Page 62: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 62

Figure 8-1

Usage Specification Setting V / F mode * 1

50HZ 0

1.5 2.5 50HZO

10

15

200V*1

[0]*3

12

6

60HZ (Saturated) 1

60HZ (Saturated) 1.5

General P

urpose 72HZ 3

Page 63: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 63

Usage Specification Setting V / F mode * 1

4

50HZ

Cubical

descending 5

square descending

6

Deceleration torque characteristics

60HZ

Cubical

descending

7

Usage Specification Setting V / F mode * 1

small

starting torque

8

50HZ

Large starting torque

9

small

starting torque

10

High-speed torque state * 2 60HZ

Large starting torque

11

Page 64: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 64

Usage Specification Setting V / F mode * 1

Constant torque

output

90HZ 12

120HZ 13

Constant torque output 180HZ 14

036 S Curve selection range: 0 ~ 3 Default: 1

To avoid the impact during starting/stopping, the inverter is able to accelerate and decelerate along with an S curve. 0: No S curve 1: 0.2 seconds (default) 2: 0.5 seconds 3: 1.0 seconds

S word characteristic time (Tsc)

Frequency command

Frequency Output

Output Frequency

Page 65: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 65

The above figure shows the switching between forward and reverse running. 037 Step 1 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz 038 Step 2 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz 039 Step 3 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz 040 Step 4 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz 041 Step 5 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz 042 Step 6 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz 043 Step 7 frequency range: 0.00 Hz ~ 400.00Hz Default: 0.00Hz

The step 1~ step 7 frequency can be selected by the combination of multi-function terminals S5, S6 and S7, or by the internal multi-step speed mode.

This parameter sets the jog frequency which will be used when the terminals are configured as jog start or pressing the jog key if the inverter is controlled by the keypad. 045 upper limitation frequency range: 0% ~ 100% Default: 100% 046 lower limitation frequency range: 0% ~ 100% Default: 0%

Upper limitation frequency: The upper limitation of the frequency set the maximum allowed operation frequency. The unit is 1% of the maximum frequency. Lower limitation frequency: The lower limitation of the frequency set the minimum allowed operation frequency. The unit is 1% of the maximum frequency. The inverter will continue running at the lower limitation frequency, if the reference frequency is 0. However, if the lower limitation is less than the minimum frequency (024), the inverter will not run.

044 Jog frequency range: 0% ~ 100% Default : 0%

Page 66: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 66

0: Free running, coast to stop. (Reserved function) 1: Run at the minimum frequency. (024) 2: Zero-speed running (zero-speed torque controlled by zero-speed gain) 048 U/D memorization setting range: 0 ~ 1 Default: 0 049 U/D Step range: 0.00 ~ 2.50HZ Default: 0.00

48 U / D memorization This function is valid when the multi-function input terminals are configured as UP/DOWM. The current operating frequency can be memorized when powered off. 0: Memorize the current operating frequency in parameter 037. 1: do not memorize the current operating frequency. 049 U/D step: When the up/Down features are valid, this parameter sets the step size of UP/DOWN instruction in the unit of 0.01Hz. 050 jump Hz1 range: 0.00Hz ~ 400.00Hz Default: 0.00Hz 051 jump Hz2 range: 0.00Hz ~ 400.00Hz Default: 0.00Hz 052 jump step range: 0.00Hz ~ 25.00Hz Default: 1.00Hz

This feature can jump off the vibration frequency in order to avoid the resonance point frequency. This function can also be used for the dead-zone control. This feature will be disabled if set to 0. Set the jump frequency according to the following formula: 046 ≤ 051-052. If this condition is not satisfied, the inverter will trip for “PAF” fault.

047 low-speed option range: 0 ~ 2 Default: 1

0 5 2

0 5 20 5 0

0 5 1

Output Frequency

F r e q u e n c y fo r a g iv e n0

Internal frequency com

mand

The frequency command lower limit (46)

Frequency command upper limit (45)

Page 67: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 67

Operation Mode (Internal simple PLC control): 0: Normal operation mode. 1: internal control multi-stage speed mode

After Run command issued, the inverter will run according to the preset parameter values and stop automatically after a cycle. Only when the run command is issued again, the inverter will run again.

2: internal control multi-stage speed, continuous operation mode. After Run command issued, the inverter run according to the preset

parameter values cyclically. No commands except for emergency stop, external fault, will be accepted during the running.

3: internal control multi-stage speed. After Run command issued, the inverter run according to the preset parameters. After an operation cycle, the inverter runs at the last speed.

Note: The above example demonstrates the settings of the step1~step7

modes. The users can set direction, Acc/Dec time and the operation time as the above example shows. If some steps are not needed, just set the frequency to 0. The inverter will skip this step and jump to the next step directly.

053 operation mode range: 0 ~ 3 Default : 0 054 Step 1 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S 055 Step 2 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S 056 Step 3 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S 057 Step 4 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S 058 Step 5 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S 059 Step 6 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S 060 Step 7 mode range: F1 ~ R4 0 ~ 4000S Default: F1 0S

Page 68: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 68

An example of the internal controlled multi-stage speed setting: Function settings run (set) frequency

053 mode 1 ————— 054 Step 1 model F1 10.0S 037 Step 1 Frequency 055 Step 2 model F2 20.0S 038 Step 2 Frequency 056 Step 3 model R3 30.0S 039 Step 3 Frequency 057 Step 4 model R4 0.0S 040 Step 4 Frequency 058 Step 5 model F2 10.0S 041 Step 5 Frequency 059 Step 6 model F3 20.0S 042 Step 6 Frequency 060 Step 7 model F1 0.0S 043 Step 7 Frequency

Note: During the above operation, if the inverter was stopped, the time counter will stop. The inverter will return to the previous speed when start again.

061 S2 configuration range: 0 ~ 26 Default: 0 062 S3 configuration range: 2 ~ 26 Default: 2 063 S4 configuration range: 2 ~ 26 Default: 4 064 S5 configuration range: 2 ~ 26 Default: 9 065 S6 configuration range: 2 ~ 26 Default: 10 066 S7 configuration range: 2 ~ 26 Default: 11 067 S8 configuration range: 2 ~ 27 Default: 12

Output frequency (m

otor speed)

1

3

2

4

5 6

Time

7 Speed

Page 69: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 69

Multi-function contact input S2-S8: Set Name Description

0 Reverse run command (2-wire) Only No 061 parameters can set to this value

1 Forward / Reverse run command (3-wire type)

Only No 061 parameters can set to this value

2 External fault (normally open contact input)

To inform the inverter there is an external fault, and the inverter will stop

3 External fault (NC contact input) Stop the output and the keypad display “EF”

4 Fault Reset Reset command is forbidden while running

5 Local/Remote control selection Panel / terminal control switching

6 Communication/terminal control selection

RS485 / terminal control selection

7 Emergency stop Stop the inverter according to Dec time 2

8 Frequency command input level selection

0: voltage input 1: current input

9 Multi-stage speed instruction 1/S5

10 Multi-stage speed instruction 2/S6

11 Multi-stage speed instruction 4/S7

The combination of terminal states corresponding to 8 frequencies.

12 Jog operation Terminal Jog function

13 Acceleration / deceleration time selection 1/RT1

Select Acceleration/Deceleration time 1

14 Acceleration / deceleration time selection 2/RT2

Select Acceleration/Deceleration time 2

15 External BB (normally open contact input)

Coast signal, when the signal input, the motor began to coast, ”BB” Shinning

16 External BB (NC contact input) when the signal open, the motor began to coast, ”BB” Shinning

17 Searching command from maximum frequency

Speed search command signal

18 Searching command from operation frequency

Frequency search command

19 Parameter setting permitted/ forbidden Allow/forbid parameter setting.

20 PID integral value reset PID integral value reset

21 PID control disabled PID forbidden

22 Timer function Terminal timer function selection

Page 70: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 70

Set Name Description

23 OH3 (Inverter overheating alarm) If this signal is active, the keypad will display “OH3”, the inverter continues to run.

24 Reference analog signal sample / hold Sample the analog signal when "Closed", and hold the signal when “OPEN”

25 KEB instructions (normally open contact input)

26 KEB instructions (NC contact input)

(Decelerate when Instantaneous power off occurs), this feature is special for textile industry. Switch the run command to stop. Decelerate when power off and generates the regenerative energy. The inverter continuing running by using this inertia energy.

27 UP / DOWN (up / down) command Only No 067 parameter can be set to this value, the frequency will increase or decrease a unit.

Page 71: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 71

Set 0, 1: 2-wire connection application example (setting: 0)

3-wire connection application example (setting: 1)

Set 5, 6:

LOCAL ( keypad) / REMOTE (remote) selection (setting: 5) Select the source of run amends. Only valid when the inverter at stopped. Open: run according the setting of No 003 parameter. Closed: run according to the keypad settings. (For example) the No 003 parameter is set to 3 Open: the reference frequency is from terminal FV and FI, and the run command is from terminal S1, S2. Closed: the reference frequency and the run command are from the keypads.

Communication / terminal control selection (setting: 6) Select the run commands between communication and terminals. Only valid when the inverter at stopped. Open: run according to the No 003 parameter setting. Closed: the run command and the reference frequency are from the communication.

Page 72: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 72

Setting 9,10,11: Combination of the terminals

11(S7) 10(S6) 9(S5) Frequency selected

OFF OFF OFF 037 Step 1 Frequency

OFF OFF ON 038 Step 2 Frequency

OFF ON OFF 039 Step 3 Frequency

OFF ON ON 040 Step 4 Frequency

ON OFF OFF 041 Step 5 Frequency

ON OFF ON 042 Step 6 Frequency

ON ON OFF 043 Step 7 Frequency

ON ON ON 044 Step 8 Frequency Configure the terminal functions as 9~11, then the certain multi-stage

frequency can be selected by the different “ON”/”OFF” combination of the terminals.

Note: the multi-stage frequency 1~7 can be selected by the different “ON”/”OFF” combination of the S5, S6 and 7. (Please refer to 061 for the definition of the terminal functions).

Page 73: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 73

Set 13, 14: selection of the Acc/Dec time

Combinations of terminals 14

(RT2) 13

(RT1) The Selected Acc/Dec time

OFF OFF 026 1st Acc, 027 1st Dec OFF ON 028 2nd Acc, 029 2nd Dec ON OFF 030 3rd Acc, 031 3rd Dec ON ON 032 4th Acc, 033 4th Dec

Note: The Acc/Dec time 1~4 can be selected by the different “ON”/”Off” combination of the RT1/RT2.

Set 22: Timer Function If the “closed” duration of the terminal is longer then “ON” delay time (072), the output of the timer function will close. If the “open” duration of the terminal is longer than “Off” delay time (073), the output of the timer function will be open.

Set 24: sample/hold of the analog reference If the “closed” duration of the input terminal lasts for 100ms or longer, the analog frequency reference will be sampled, and the sampled value will be help if the terminals become open.

Page 74: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 74

Note: t1, t3: equal or greater than 100ms, sample the analog reference signal. t2: less than 100ms, the previous sampled value was held. Set 27: UP / DOWN (increase/decrease) command (setting: 067 = 27) This setting is only valid when the run command is from the external terminals. The inverter can accelerate or decelerate operate at the desired speed by configuring S7 and S8 terminal as “UP/DOWN” function without changing the frequency reference. If No. 067 parameter is configured to “UP/DOWN”, then the No. 066 parameter will be configured to “UP” no matter what it was configured in previous.

Control terminal S7 (UP ) Closed open open Closed Control terminal S8

(DOWN) open Closed open Closed

Running status Accelerate Decelerate hold hold

The following diagram shows the timing diagram of UP / DOWN configuration.

U = UP (accelerating state) D = DOWN (decelerating condition) H = HOLD

(Hold state)U1 = UP status (stable at the upper limit) D1 = DOWN status (stable at the upper limit)

Note: When the UP/DOWN feature is configured, the inverter will accelerate to the

upper frequency limit no matter what the current frequency reference is. The lower limit of the frequency can be either from the terminals FV, FI input,

or the largest value of the frequency limitation.

Page 75: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 75

when the forward/reverse run command is activated, the inverter will run from the lower frequency limit even the UP/DOWN feature is not configure Output frequency while the “UP/DOWN” is running, the JOG command has the higher priority.

068 Y1 function range: 0 ~ 18 Default: 0 069 Y2 function range: 0 ~ 18 Default: 1 070 Y3 function range: 0 ~ 18 Default: 2 071 Y4 function range: 0 ~ 18 Default: 3

Description of the Multi-functional output options: Setting Name Description

0 Fault Closed when there is a fault.

1 Running Closed when the forward/reversed command is activated or the inverter has voltage outputs.

2 Frequency Match Output frequency consistent with target frequency

3 Any frequency Match Output frequency consistent with detection frequency

4 Frequency detection Output frequency ≤ Detection criterion

5 Frequency detection Output frequency ≥Detection criterion

6 Over-torque detection (normal open) Over torque detection output relay close

7 Over-torque detection (normal closed) Over torque detection output relay open

8 BB (base blocking) Closed when the inverter stop outputs

9 Run Mode Closed when the inverter is controlled by keypad

10 Inverter Ready Closed if no fault and ready for running.

11 Timer function Closed when time up to terminal timer function

12 Auto re-start Closed during the auto-restart period.

13 OL(overload) Pre-Alarm Closed when pre-warnings

14 Loss of the freq reference Closed when frequency reference lost

15 Communication output 1 Bit 1 of RS485 communication data output

16 Communication output 2 Bit 2 of RS485 communication data output

17 PID feedback loss Closed when PID feedback lost

18 OH1 Alarm Closed when OH1 alarm

19 Zero speed status Closed when zero speed 20 Up to lowest frequency Closed when output up to lowest limit 21 Up to highest frequency Closed when output up to highest limit

Page 76: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 76

Settings: 2, example of the “frequency match”

Settings: 3, example of the “any frequency match”

072 ON delay range: 0S ~ 25.5S Default: * 073 OFF delay range: 0S ~ 25.5S Default: *

Filtering the input/output contact terminals, can be used as a time relay. Refer to the setting of multi-function terminal settings S2~S8, setting 22.

074 Main Analog reference range: 0 ~ 1 Default: 0. The main analog reference signal can be provided from the control terminals. The reference signal can be either voltage signal or current signal, depending the setting of this parameter. 0: FV, 0 ~ 10V Input 1: FI, 4 ~ 20mA input 075 auxiliary analog reference range: 0 ~ 1 Default: 1

The auxiliary analog reference signal can be either voltage signal or current signal, depending the setting of this parameter. 0: 0 ~ 10V Input 1: 4 ~ 20mA input Note: The switch mounted on the control board SW1-1 should be placed at the “off” state, if this parameter is set to 0.

076 Ref frequency Loss range: 0 ~ 1 Default: 0 This parameter defined the handling if the frequency reference loses during the operation 0: does not handle 1: the inverter will go on running at the 80% of the previous reference, if the external analog frequency reference drops to 90% within 400ms.

Page 77: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 77

077 Frequency Gain range: 0% ~ 200% Default: 100% 078 Frequency Offset range: -100% ~ 100% Default: 0%

If the reference frequency is provided by the analog input FV and FI, these two parameters can set the frequency offset and gain. Frequency Gain: defines the reference frequency value responding to 10V (20mA) analog input. The unit is 1% of maximum frequency. Frequency offset: defines the reference frequency value responding to 0V (4mA) analog input. The unit is 1% of maximum frequency.

example: 0-5V analog input corresponding to reference frequency 0% -100%.

Gain: 077 = 200, offset: 078 = 0 0-10V analog input corresponding to reference frequency 50%-100% Gain: 077 = 100,offset: 078 = 50

Page 78: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 78

079 FMA function range: 0 ~ 3 Default: 0 080 FMA gain range: 0.01 ~ 2.00 Default: 1.00

Select the variables to be output at the analog output terminals FMA-FC for the purpose of monitoring. F M A function: 0: Output frequency (10V corresponding to maximum frequency) 1: Output current (10V corresponding to inverter rated current) 2: Output power (10V corresponding to inverter rated power) 3: DC bus voltage (10V/400V (200V type), 10V/800V (400V type) FMA Gain: this parameter is used to calibrate and adjust the analog output.

To calibrate the analog output, make the analog output 3V at he maximum frequency, Set No.080 parameter 0.3.

081 frequency detection range: 0.00Hz~400.00Hz Default: 0Hz 082 FAR frequency range: 0.00Hz ~ 25.00Hz Default: 0Hz

Only valid when the multi-function output terminals be configured as “frequency detection”. Frequency detection: When the output frequency is higher or lower than the detection target frequency 081, the multi-function output terminal contact closes. FAR Frequency: threshold of the frequency detection. The setting of the multi-function output terminal is “4”, (Output frequency ≤Detection target Frequency)

Page 79: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 79

The setting of the multi-function output terminal is “5”, (Output frequency >=Detection target Frequency)

083 Instantaneous power off range: 0 ~ 2 Default: 0 0: Do not continue to operate 1: continue running if power on again within the instantaneous power off compensation time (087). 2: continue running if power on again within the control logic time, no UU1 alarm. Note: The run command should be kept in order to continue running after restoring from instantaneous power off.

These parameters are used in restarting the inverter which is coasting and does not stop. This parameter makes it easy to switch the inverter between constant frequency running and variable frequency running. Speed Search: set the inverter current in speed searching. The inverter rated current is 100%. Block time: Set the minimum time to stop the inverter output during the instantaneous power off in speed searching. Configure the multi-function input terminal as "17" or “18”, to use the speed search feature. The speed search command must be activated before the run command or simultaneously. If this sequence is not satisfied, the speed search command is not valid. Here, the following is the sequence diagram:

084 speed search range: 0% ~ 200% Default: 110%085 block time range: 0.5S ~ 5.0S Default : *

Page 80: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 80

086 Search for V / F range: 0% ~ 100% Default: * Set V/F reduction during speed searching.

087 instantaneous stop time range: 0.0S ~ 2.0S Default: * Set the compensation time for instantaneous power failure

088 Auto restart time range: 0 ~ 10 Default: 0 This parameter set the times the inverter will restart and self-diagnose when fault occurs. This parameter can be set to up to the maximum value 10. The inverter will auto restart if the following failure occurs: 1. OC (over current) 2.OU (over voltage) 3. UV1 (under voltage) 4. GF (ground fault) 5. Rr (braking transistor fault) Note: this parameter will be cleared in the following cases: A. No other failure occurs for 10 minutes after the inverter restart. B. the fault reset signal is ON when the fault is detected C. Power off.

089 retry contact range: 0 ~1 Default: 0 This parameter defines the state of the fault output contact: 0: closed during restarting 1: open during restarting

0.0HZ: DC breaking is not valid. 0.1~5.0Hz: DC breaking will be implemented when the output frequency is lower than this value if stop command is activated.

Set DC braking current. 100% is corresponding to rated inverter current.

090 braking frequency range: 0.0 ~ 5.0HZ Default: 0.0 HZ

091 brake current range: 0% In ~ 100% Default: 50%

Page 81: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 81

092 Stop brake time range: 0.0S ~ 10.0S Default: 0.5S

Set the braking time after the inverter stopped. DC breaking will not be implemented if this parameter is set to 0.0S or the stop mode(007) is configured as coasting to stop.

093 start brake time range: 0.0S ~ 10.0S Default: 0.0S Set the braking time before the inverter starting. DC breaking will not be implemented if this parameter is set to 0.0S. By using this parameter, the free coasting inverter will stop and start at 0 speed.

094 zero speed gain range: 0 ~ 100% Default: 0%

Set the output current at zero speed. 100% is corresponding to the rated inverter current (reserved function).

095 torque compensation range: 0.0 ~ 3.0 Default: 1.0S The inverter output torque can be adjusted according to varying of the load. The inverter will adjust the V/F voltage according to the real requirements. ETD750 inverter adjusts this voltage automatically during accelerating and constant speed running. The inverter will calculate the torque automatically, thus to ensure the no-trip operation and super energy-saving performance. Output voltage ∝ torque compensation gain (095) × the required torque.

Page 82: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 82

Usually do not need to adjust the torque compensation gain (095 default setting: 1.0). Only needed if the distance between the inverter and motor is very long or the inverter vibrates. But too much compensation will cause the following problems: Over current. Motor overheating or vibration. The torque compensation gain should be increased gradually by monitoring the motor current at the same time.

096 motor tuning range: 0 ~ 2 Default: 0 0: do not tuning 1: static tuning (for motors already with load). By setting this parameter to 1 and start the inverter, the stator resistance will be measured. 2: Dynamic tuning (for motors without load). During this tuning process, the stator resistance and the no-load current will be measured. The motor will run at the rated frequency during dynamic tuning (Reserved function).

097 coupled resistance range: 0.000R ~ 65.530R Default: * 098 motor leakage inductance range: 0H ~ 40.0H Default: * 099 Motor iron loss range: 0W ~ 9999W Default: *

Compensation for the amount of torque converter internal calculations use data, the factory has set the appropriate value, usually no need to change.

100 Slip gain range:0.0% ~ 9.9% Default: 0.0% Motor load torque affects their transfer difference, resulting in changes in motor speed. Slip compensation is proportional to increase in the motor load torque converter output frequency method; to reduce the motor speed with the speed of change in load torque occurs.

101 no-load current range: 0% In ~ 99% Default: 30% InNo load motor current setting. Motor rated current is 100% In

102 corrections delay range:0.0S ~ 25.5S Default: 20.0S Set Slip correction filter with the current time parameters.

103 base speed range: 30% In ~ 200.0% Default: * Set Stall prevention during acceleration function moves the benchmark of 1% as a unit inverter rated current to 100%.

Page 83: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 83

104 run the benchmark range: 30% In ~ 200.0% Default: * Set the stall prevention function of movement during the operation level, to 1% as the unit inverter rated current to 100%.

105 deceleration stall range: 0 ~ 1 Default: 1 0: No stall prevention function during deceleration 1: There Stall prevention function during deceleration

106 time choose range: 0 ~ 1 Default: 1 0: the cumulative time of electricity 1: Run the cumulative time

107 timer L range: 0H ~ 9999H Default: 0H 108 timer H range:0 * 10000H ~ 27 * 10000H Default: 0H

106 was chosen to use when the cumulative operating time, with 1 hour as a unit, this parameter is set to time, the cumulative time since then.

109 Rated current range:10% In ~ 200.0% Default: * Motor nameplate rated current value, the electronic thermal protection device to protect the reference current as the motor is inverter rated current 10% to 200%.

110 overload range:0 ~ 4 Default: 1 Converter with internal electronic thermal overload relay protection motor overload. Correctly the following settings: 0: No Protection 1: Standard motor (time constant of 8 minutes) 2: Standard motor (time constant 5 minutes) 3: Inverter motor (time constant of 8 minutes) 4: Inverter motor (time constant 5 minutes) Electronic thermal overload function is based on the inverter output current / frequency and time simulation to monitor the motor temperature, protect motor from overheating, when the electronic thermal overload relay, to issue an "OL1" error, turn-off inverter output, to prevent the motor overheating. When a converter to connect an electric motor running when you do not need an external thermal relay. When an inverter operating several motors on each motor should be installed on a thermal relay. This case set the constant of 110 to 0.

111 torque detection range: 0 ~ 4 Default: 0 0: No over torque detection 1: Only the same in terms of speed for testing, post-test continue to operate 2: run-time testing, post-test continue to operate 3: The only consistent in terms of speed for testing, post-test inverter disconnect 4: The run-time testing, post-test inverter output disconnect

Page 84: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 84

In order to accelerate or decelerate the torque during the test had set into a 2 or 4. In order to turn away from the post-test than continue to operate, set to 1 or 2. In the testing period, the manipulator shows "OL3" alarm (flashes). In order to turn away from the fault detection had suspended converter, set to 3 or 4. In the testing period, the manipulator significantly shows the "OL3" fault (light).

112 torque benchmark range:30% In ~ 200.0% Default: 160% In Been transferred from the detection of the benchmark of 1% of the units to set-off switch from the current benchmark testing

113 over torque T range: 0.1S ~ 10.0S Default: 0.1S Been transferred from the detection time if the motor current is transferred from the test went beyond the baseline (112) is greater than the time-off switch from the detection time (113), then the off switch from the detection action.

114 SPI benchmark range: 1% ~ 100% Default: 20% Set input missing phase detection level of 1% as a unit, DC400V (200V class), DC800V (400V class) 100%

115 SPI Delay range: 2S ~ 255S Default: 8S Set input missing phase detection time detection time = 1.28 seconds × [112 settings]

116 SPO benchmark range: 1% ~ 100% Default: 0% Missing output phase detection level set to 1% as a unit, inverter rated current to 100%.

117 SPO delay range: 0.0S ~ 2.0S Default: 0.2 Set the output phase lack of detection time

118 OH stop range: 0 ~ 3 Default: 3 Stop when the radiator overheated way: 0: deceleration to stop a (failure) 1: Free stop 2: deceleration to stop 2 (failure) 3: Continue operation (alarm)

119 DBR overheated range: 0 ~ a Default: 0 Brake resistor overheat protection functions: 0: No brake resistor overheat protection 1: There are braking resistor overheat protection

120 PID selection rules range: 0 ~ 3 Default: 0 0: No PID Control 1: There are PID control (deviation D control) 2: There are PID control (feedback value is D-controlled)

Page 85: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 85

3: There PID control (feedback value of the reverse) target setting: ETD750 to select multiple target, set the target value can be used when the control circuit terminal FV-voltage signal (0-10) or the frequency of command parameters 037-044. control circuit terminal FV voltage signal: Set operation mode selection (003) for 2 or 3. Frequency command parameters (037-044): Set in the functioning of selection (003) to 0 or 1 (multi-function input contact, multi-stage speed instruction and jog frequency command combination thereof). Feedback value of the setting: Set the value of the use of feedback control circuit terminal FI current signal (4-20mA) or voltage signal (0-10V) current signal: Set FI function select (075) is 1. Voltage signal: Set the FI function select (075) is 0. (PC board SW1-1 set to OFF.)

121 feedback gain range:0.00 ~ 100.00 Default: 1.00 122 proportional gain range:0.0 ~ 10.0 Default : 1.0 123 Integral time range:0.0S ~ 10.0S Default: 10.0S 124 Differential time range:0.0S ~ 10.0S Default: 0.00S 125 PID Offset range: -109% ~ 109% Default: 0% 126 points to set limits range:0% ~ 109% Default: 100% 127 Filter Time range:0.0S ~ 2.5S Default: 0.0S

Feedback gain: It is the value of PID feedback detector with micro-adjustment of the gain. The proportional gain: Setting the control of the proportional gain, if P is set to 0.0, not to P control. Integration time: Set the control of the proportional gain, if I set to 0.0, not to I control. Differential Time: Set the control of the proportional gain, if D is set to 0.0, not to D control. PID Bias: The PID control of the frequency command value after the bias adjusted to 1% of the unit. Points Limit: For I control the output frequency after the ceiling limit, to 1% of the unit. Filter time: after controlling for the frequency of the PID instruction once a delay time parameter settings.

Page 86: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 86

128 feedback detection setting range: 0 ~ a Default: 0 Feedback loss detection (PID): 0: No PID feedback loss is detected 1: There PID feedback loss is detected

129 missing benchmarking range: 0% ~ 100% Default: 0% Feedback loss detection benchmark (PID), set the PID feedback loss detection level of 1% of set units.

130 lose time setting range: 0.0S ~ 25.5S Default: 1.0S Feedback loss detection delay time (PID), set the PID feedback loss detection time. Note: The following cases I reset the value to 0: A, stop orders or stop the importation of B, when the adoption of multi-function contact input selection (constant 061-067 in any one set to 20) enter the integral value of reset signal. I value the upper limit set by the constant 126. Increase the parameter value of 126 points can improve the ability to control, if the control system oscillation. But can not adjust the integration time or the time delay means to stop the oscillation parameters, etc., it should reduce the constant 126 settings. Multi-function contact input signals can be withdrawn from the PID control. As long as any of a set parameters 061-067 to 21, but the contact is closed during operation, PID control is canceled, the expected value of the signal itself is used as a frequency command signal.

Target P

122 I Limit

123 126

Limit

Deviation

125

D

124

120

13

2

1 3~

0

FilterTime

120

Frequency command

++

+

%109±

Feedback gain 121

feedbak

100%

077 120

D

+-

1 23 120

127

Page 87: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 87

131 energy-saving options range: 0 ~ 1 Default: 0 132 energy-saving gain range: 0.00 ~ 655.00 Default: * 133 60Hz voltage range: 0 ~ 120% Default: 50% 134 6Hz voltage range: 0 ~ 25% Default: 12%

Energy-saving options: 0: energy-saving control is invalid 1: Energy-saving control is effective Because the energy-saving control method has been used in a constant preset at the factory before delivery into the best value, so under normal operation do not have to adjust the value. If the motive of the features and ETD with standard electrical characteristics are very different time, please refer to the following instructions to change its constants. Energy gain (132): In the energy-saving control method using energy-saving run-time gain, in order to calculate the most efficient electric motors when the voltage and the output voltage of the voltage is given. The value is in the factory before delivery by ETD standard values for the motor home. When the energy saving gain increases, the output voltage also increases. Energy-saving voltage limits (133,134): Set the output voltage limit. If the energy-saving ways considered as the voltage for a given value is less than the specified lower limit, then the lower limit of the given value as a voltage output. In order to prevent stalling at light loads, to set the lower limit. Set In the 6Hz or 60Hz, when the voltage limits, 6Hz and 60Hz outside the limits of the value obtained by linear interpolation settings, set the motor rated voltage is based on the percentage of rows to.

※ For the 400V class, the value for the 200V class 2 times.

135 computing time range:1 ~ 200 Default: 1 Energy-saving mode set the computing power of the average time.

Page 88: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 88

136 voltage limit range:0 ~ 100% Default: 0% 137 100% anti-jump range:0.1 ~ 10.0% Default: 0.5% 138 5% anti-jump range: 0.1 ~ 10.0% Default: 0.2%

In the energy-saving control method, the optimum voltage is calculated in accordance with the load power supply load. However, the set of parameters may change with temperature or the use of other motor manufacturer change, so in some cases impossible to provide the best voltage. Best running through the micro-variable control voltage in order to achieve best operation status. Voltage limits: By the best operation to control the voltage range. Set is based on the percentage of motor rated voltage to conduct. Set the value to 0 can not be carried out. Best operation voltage range (137,138): Set one of the best operating cycle of the voltage range. Set is based on the percentage of motor rated voltage to conduct. To increase the value, the changes in speed larger. The voltage range is the optimum starting voltage of 100% and 5% of set. These values are outside the voltage value can be derived from the linear interpolation to set the value.

139 Machine Address range:0 ~ 31 Default: 0 140 baud rate range:0 ~ 5 Default: 0 141 Parity range:0 ~ 5 Default: 3

Local Address: 0: inverter from the RS485 bus control address, the non-charged address. 1 ~ 31: Inverter RS485 communications charged with addresses. Was charged with setting the machine address is necessary, it will not connect to other transmission lines at the same address was charged with duplicate numbers.

Page 89: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 89

Baud Rate: 0:1200 BPS 1:2400 BPS 2:4800 BPS 3:9600 BPS 4:19200 BPS 5:38400 BPS Parity mode: 0:7 N2 For ASCII 1:7 E1 For ASCII 2:7 O1 For ASCII 3:8 N2 For RTU 4:8 E1 For RTU 5:8 O1 For RTU

142 Communication Timeout range: 0 ~ 1 Default: 1 Communication with the PC, set the timeout detection: 0: No timeout detection 1: There timeout detection

143 CE to stop range: 0 ~ 3 Default: 1 Communication error (CE) when the stop method: 0: deceleration to stop (with a deceleration time) 1: Free Sliding Stop 2: deceleration to stop (using the deceleration time 2 slow down) 3: Continue operation (alarm) Note: * denotes the factory when the factory setting is based on inverter power levels vary, or not to restore the factory parameters of functions with the modified value. Communication error (CE) when the stop method: 0: deceleration to stop (with a deceleration time) 1: Free Sliding Stop 2: deceleration to stop (using the deceleration time 2 slow down) 3: Continue operation (alarm) Note: * denotes the factory when the factory setting is based on inverter power levels vary, or not to restore the factory parameters of functions with the modified value.

Page 90: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 90

MODBUS Communication protocol

Modbus communication protocol is applied to electronic controller on the lingua franca. With this agreement, the controller between the controller via the network (such as Ethernet) and other devices can communicate. It has become a common industry standard. With it, different manufacturers of industrial control equipment can be connected into a network for centralized monitoring. This agreement defines the use of a controller can recognize the message structure, regardless of what network they are communicating through. It describes a controller requesting access to other equipment, if the response to requests from other devices, as well as how to detect the error and recorded. It sets the pattern and content of the message the public domain format. When a modbus network traffic, this agreement and decision of each controller, the device need to know their address, identify the address sent by the news and decided what action to generate. If you need to respond, the controller will generate feedback and use Modbus protocol issue. In other networks, messages containing Modbus protocol into the network used in this frame or packet structure. This conversion has also expanded the network address according to specific section addresses, routing paths and error detection method. ETD750 series of AC motor drives using the Modbus networks communication protocols. The Modbus can use the ASCII (American Standard Code for Information Interchange) or RTU (Remote Terminal Unit) two kinds of data coding. ASCII code is the data to be transmitted into the first and then send the corresponding ASCII code, while the RTU is to send data directly, without undergoing conversion. The following instructions encoded ASCII data format.

Each byte is a combination of 2 ASCII characters. For example: value is 64 Hex, ASCII representation of way for '64 ', respectively, by '6' (36Hex), '4 '(34Hex) combination. The following table shows ASCII characters '0 '... '9', 'A' ... 'F' in Comparison

Char ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’

ASCII code 30H 31H 32H 33H 34H 35H 36H 37H

char 8 9 A B C D E F

ASCII code 38H 39H 41H 42H 43H 44H 45H 46H

Page 91: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 91

Communication data control word definitions explained in detail (1) 7N2 for ASCII 141=0

(2) 7E1 for ASCII 141=1

(3)7O1 for ASCII 141=2

(4) 8N1 for RTU 141=3

(5) 8E1 for RTU 141=4

(6) 8O1 for RTU 141=5

Page 92: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 92

ASCII mode

STX Start character = ':' (3AH) Address Hi Address Lo

Address:8-bit address code from the combination of two ASC11

Function Hi Function Lo

Function Code:8-bit function code combinations from two yards ASC11

DATA(n-1) ……

DATA0

Data content: n × 8-bit data content ASC11 yards from a combination of 2n n <= 20, maximum 40 ASC11 yards (20 Pen information)

LRC CHK Hi LRC CHK Lo

LRC Check Code:8-bit checksum code combinations from the two ASC11

END Hi END Lo

End of the characters: END Hi = CR (0DH), END Lo = LF (0AH)

RTU mode:

START To maintain non-input signal is greater than equal to 10ms

Address Mailing Address :8-bit binary address Function Function Code :8-bit binary address DATA(n-1) …… DATA0

Data content: n × 8-bit data, n <= 40 (20 pen 16bit data)

CRC CHK Low

CRC CHK High

CRC Check Code: 16-bitCRC checks yards from two 8-bit binary combination of

END To maintain non-input signal is greater than equal to 10ms

Mailing Address (Address) 00H: All drives Broadcast (Broadcast) 01H: the first 01 addresses on the drive 0FH: Address of article 15 of the drive 10H: the first 16 addresses on the drive, and so on. . . . . . , Maximum to 31. Function Code (Function) and data content (Data Characters) 03H: read out the contents of register 06H: Write a data to register 08H: Loop Detection 10H: multi-pen to write information on a continuous 03H: read out data to register more than pen

Page 93: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 93

Function Code 03H: read the register content (up to a row of 20 pens at the same time to read data) For example: the drive address 01H, read out two consecutive in the register of the information reads as follows, said: Starting register address 2102H ASCII mode: Inquired about the message string format: string format to respond to messages

STX ‘:’ ‘0’

Address ‘1’ ‘0’

Function ‘3’ ‘0’ ‘0’ ‘1’

Starting address

‘D’ ‘0’ ‘0’ ‘0’

Number of data

(count by word)

‘2’ ‘1’ ‘3’ ‘0’

Content Word1

‘0’ ‘1’ ‘0’ ‘0’

Content Word2

‘0’ ‘D’

LRC Check ‘D’ CR

END LF

STX ‘:’ ‘0’

Address ‘1’ ‘0’

Function ‘3’ ‘0’ Number of data

(count by byte) ‘4’ ‘1’ ‘3’ ‘0’

Content of startingAddress 001DH

‘0’ ‘1’ ‘0’ ‘0’

Content of address 001EH

‘0’ ‘7’

LRC Check ‘1’ CR

END LF

Page 94: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 94

RTU mode: Inquired about the message format: Response Message Format:

For example: the drive address 01H, writing 6000 (1770H) to drive within the set parameters 001DH. RTU mode: Inquired about the message format: Response Message Format:

Address 01H Function 03H

00H Starting Address 001DH 1DH

00H Number of data (count by word) 02H

13H Content Word1

00H 10H

Content Word2 00H

CRC CHK Low 54H CRC CHK High 0DH

Address 01H

Function 03H

Number of data (count by byte) 04H

13H Content of starting Address 001DH 00H

10H Content of starting Address 001EH 00H

CRC CHK Low FAH

CRC CHK High 9CH

Address 01H

Function 06H

00H Content of starting Address 001DH 1DH

17H Number of data (count by word) 70H

CRC CHK Low 17H

CRC CHK High D8H

Address 01H

Function 06H

00H Content of starting Address 001DH

1DH

17H Number of data (count by word)

70H

CRC CHK Low 17H

CRC CHK High D8H

Page 95: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 95

ASCII mode: Inquired about the message format: Response Message Format

Command Code: 08H, communication-loop testing this command is used to test the master device (usually a PC or PLC) communication between the drive whether it is normal, the drive will receive the data content sent back to the master device intact. RTU mode: Inquired about the message format: Response Message Format:

Address 01H

CMD 08H

00H DATA

00H

17H DATA

70H

CRC CHK Low 8EH

CRC CHK High 0EH

Address 01H

CMD 08H

00HDATA

00H

17HDATA

70H

CRC CHK Low 8EH

CRC CHK High 0EH

STX ‘:’ ‘0’ Address ‘1’ ‘0’ Function ‘6’ ‘0’ ‘0’ ‘1’

Data address

‘D’ ‘1’ ‘7’ ‘7’

Data content

‘0’ ‘9’ LRC Check ‘0’

‘CR’ END

‘LF’

STX ‘:’ ‘0’ Address ‘1’ ‘0’ Function ‘6’ ‘0’ ‘0’ ‘1’

Data address

‘D’ ‘1’ ‘7’ ‘7’

Data content

‘0’ ‘9’ LRC Check ‘0’

‘CR’ END

‘LF’

Page 96: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 96

ASCII mode: Inquired about the message format: Response Message Format:

STX ‘:’

Address1 ‘0’

Address0 ‘1’

CMD1 ‘0’

CMD0 ‘8’

‘0’

‘0’

‘0 Data

content

‘0’

‘1’

‘7’

‘7’ Data

content

‘0’

‘7’ LRC Check

‘0’

‘CR’END

‘LF’

STX ‘:’

Address1 ‘0’

Address0 ‘1’

CMD1 ‘0’

CMD0 ‘8’

‘0’

‘0’

‘0 Data

content

‘0’

‘1’

‘7’

‘7’ Data

content

‘0’

‘7’ LRC Check

‘0’

‘CR’END

‘LF’

Page 97: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 97

Command Code: 10H, the number of pens to write information on a continuous For example, change the drive (address 01H) of the multi-stage speed setting 001DH = 50.00 (1388H), 001EH = 40.00 (0FA0H) RTU mode: Inquiry message format: Response Message Format:

Address 01H

CMD 10H

00H DATA Start Address 1DH

00H DATA Number

02H

13H DATA1

88H

0FH DATA2

A0H

CRC CHK Low B2H

CRC CHK High 1CH

Address 01H

CMD 10H

00HDATA Start Address

1DH

00HDATA

Number 02H

CRC CHK Low 1DH

CRC CHK High CEH

Page 98: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 98

ASCII mode: Inquired about the message format: Response Message Format:

STX ‘:’

Address1 ‘0’

Address0 ‘1’

CMD1 ‘1’

CMD0 ‘0’

‘0’

‘0’

‘1’Data

Start Address

‘D’

‘0’

‘0’

‘0’ Data

Number

‘2’

‘1’

‘3’

‘8’ Data 1 content

‘8’

‘0’

‘F’

‘A’ Data 2 content

‘0’

‘8’ LRC Check

‘2’

‘CR’END

‘LF’

STX ‘:’

Address1 ‘0’

Address0 ‘1’

CMD1 ‘1’

CMD0 ‘0’

‘0’

‘0’

‘1 Data

Start Address

‘D’

‘0’

‘0’

‘0’ Data

Number

‘2’

‘D’ LRC Check

‘0’

‘CR’END

‘LF’

Page 99: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 99

Surveillance error value:

ASCII mode checksum (LRC ChETDk)

Checksum (LRC ChETDk) from the Address to the Data Content end of the

combined value. For example, question 3.3.1 above, the message check

code:

01H + 03H + 21H + 02H + 00H + 02H = 29H, and then take two's complement

= D7H.

RTU mode checksum (CRC ChETDk)

Checksum Data content from the Address to the end. The rules of its

operation are as follows:

Step 1: To enable 16-bit registers (CRC register) = FFFFH.

Step 2: Exclusive OR the first 8-bit byte message command and low 16-bit

CRC register, do Exclusive OR, the results stored within the CRC register.

Step 3: Also a CRC shift register will be 0 filled a high office.

Step 4: Check the value of the shift to the right, if it is 0, the new value in step

3 into CRC register, otherwise Exclusive OR A001H with the CRC register,

the results stored within the CRC register.

Step 5: Repeat Step 3 to Step 4, the 8-bit all the operations to complete.

Step 6: Repeat step 2 to step 5, remove an 8-bit message command, until the

completion of all messages instruction set computer. Finally, get the value of

CRC registers, that is, CRC check code. It is worth noting that the CRC check

code must be placed on the exchange of information in order examination

codes. The following C language in order to generate CRC values. This

function requires two parameters

Unsigned char data; // Refers to the target message buffer

Unsigned char lengh; // Message buffer in the number of bytes

Page 100: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 100

//This function will return the value of unsigned integer type of the CRC unsigned int crc_chk(unsigned char data,unsigned char lengh) int j; unsigned int reg_crc=0xffff; while (lengh--) reg_crc^=*data++; for(j=0;j<8;j++) if(reg_crc&0×01) /*LSB(b0)=1*/ reg_crc=(reg_crc>>1)^0xa001; else reg_crc=reg_crc>>1; return reg_crc;

Parameters of the letter agreement, the definition of the word address Definition address Function Description

Internal drives

0nnnH nnn: Indicated that they could set parameters (see Appendix 1)

Bit0 0:STOP 1:RUN Bit1 0:FWD 1:REV Bit2 0:Invalid 1:EF0 Bit3 0:Invalid 1:RESET Bit4 0:Invalid 1:DO0 Bit5 0:Invalid 1:DO1

2000H

Bit6~15 reserve

Com

mand on the drive

2001H MODBUS Frequency command

Page 101: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 101

Function Description

(Error code): 01H=Uu1

02H(reserve) 03H(reserve)

04H=SC 05H=oC 06H=ou 07H=GF 08H=FB 09H=oH1 0AH=oH2 0BH=oL1 0CH=oL2 0DH=oL3 0EH=EF0 0FH=EF2 010H=EF3 012H=EF4 013H=EF5 014H=EF6 015H=SPI 016H=Spo 017H=CE 018H= Rh 019H= rr

01AH=ATF

Definition address

01BH=EPF

Page 102: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 102

Definition address Function Description Warning code

Bit0 Uu AlarmBit1 ou AlarmBit2 oH1 AlarmBit3 OL3 AlarmBit4 BB AlarmBit5 EF AlarmBit6 SpareBit7 CALL AlarmBit8 oH3Bit9 CE

Bit10 OPE0Bit11 OPE1Bit12 OPE2Bit13 .OPE3

2101H

Bit14~15 .E= Alarm IO Status Code

Bit0 S1Bit1 S2Bit2 S3Bit3 S4Bit4 S5Bit5 S6Bit6 S7Bit7 S8Bit8 Y1Bit9 Y2

Bit10 Y3

2102H

Bit11 Y4 Run State

Bit0 OperationBit1 Reverse RunBit2 Inverter readyBit3 FaultBit4 Jog Status

Monitor drive status

2103H

Bit5 Pre-Alarm

Page 103: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 103

Definition address Function Description Bit6~7 reserve

Bit8 Run mode Bit9 Run mode

Bit10 Run mode Bit11 Run mode

Bit12 Frequency input ENTER key to enter the used

Bit13~15 reserve

2103H

2104H Set frequency 2105H Out frequency 2106H Output Current 2107H Output Voltage 2108H Output Power 2109H EDC Voltage 210AH PID feedback 210BH Radiator Temperature 210CH ROM Version 210DH Fault History 1 210EH Fault History 2 210FH Fault History 3

Monitor the D

rive`s status 2110H Fault History 4

Error communicating an additional response: When the drive to do communication links, if an error, this time the drive will respond to the error code and will command the highest level code (bit7) is set to 1 or Function code AND 80H) to respond to the main control system, so that main control system to know the error generated.

Page 104: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter DETAILED EXPLAINATIONS

ETD 750 Product Manual 104

For example: ASCII mode: RTU mode:

Error code meaning:

Error Code Description

01 Function Code Drive: The drive can identify the function code (03H, 06H, 01H, 10H)

02 Data Address Error: Data not recognize the drive address.

03 Data content error: data content too.

04 Drivers can not handle: drive on this command can not be implemented.

STX ‘:’ ‘0’

Address ‘1’ ‘8’

Function ‘6’ ‘0’

Exception code ‘2’ ‘1’

LRC Check ‘3’

‘CR’END

‘LF’

Address 01H

Function 86H

Exception code 02H

CRC CHK Low C3H

CRC CHK High A1H

Page 105: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FAILURE COUNTERMEASURE

ETD 750 Product Manual 105

10. FAILURE COUNTERMEASURE 10.1 Fault diagnosis and corrective measures When ETD 750 detects a failure, the number operator displays the failure, and to let the fault contact output and the motor coast to stop. Check the following table to find the reason and take corrective measures. If the following measures can’t solve the failures, please contact with ETD company. In order to reset the drive, switch on the reset input signal or press STOP key, or you can disconnect the main circuit power supply to reset the fault. Note:The drive can’t reset the fault when there is run dictate input.

Table 10-1 Fault diagnosis and corrective measures Failure Display Description Detail corrective measures

Main circuit under voltage

Main circuit under voltage: 1.200v grade: Line power voltage below 190v

2.400v grade: Line power voltage below 380v

Control circuit under voltage

Control circuit under voltage when running

Uu1

Contactor Fault Then main contactor open when running

Check the power connection

Correct the input line power voltage.

OC Over current (OC)

The output current over the value of OC

Check the motor insulation

Check with multi-meterCheck the coil

resistance of motor Add the time of

accelerate/decelerate

SC Output shorted Inverter output terminals are shorted.

Check output circuit

OU Over voltage (OU)

Main circuit dc voltage over the value of OU Detect electric level: 200V grad:about 400V 400V grad:about 800V

Prolong the decelerate time, add the brake resistance

GF GND fault (GF)

The inverter GND output current over 50% of inverter rated current

First check the isolation between inverter and motor

FB Main circuit fault(FB)

The fuses of DC circuit are broken. Output transistor are damaged

Check the transistor and the shorted, GND of load-side.

Page 106: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FAILURE COUNTERMEASURE

ETD 750 Product Manual 106

Failure Display Description Detail corrective measures

OH1 Heatsink overheat (OH1)

The temperature of transistor heatsink over the permitted value (Heatsink temp≥OH1 detection value) (about 95 )

Check Fans and the ambience temperature.

OH2 Heatsink overheat (OH2 )

The temperature of transistor heatsink over the permitted value (Heatsink temp≥OH2 detection value) (about 105 )

Check Fans and the ambience temperature.

OL1 Motor overload (OL1 )

Inverter output over the setting value of the motor overload

Reduce load.

OL2 Inverter overload (OL2 )

Inverter output over the setting value of the inverter overload

Reduce load and prolong the accelerate time

OL3 Over torque detection (OL3 )

Inverter output over the torque detection value

Reduce load and prolong the accelerate time

EFLn RS485 data bus external fault The fault of control circuit Check the external

control circuit

EF2~8 Terminal S2~S8 external fault The fault of control circuit

Check input terminals, if not connect terminals then change inverter.

SPI Big generatrix voltage fluctuate

Inverter input power supply phase-missing Input voltage not balance

Check the input line voltage. Screw down the input terminals bolt.

SPo Output phase-missing

Inverter output power supply phase-missing

Check output connections. Check the motor resistance. Screw down the output terminals bolt.

CE RS485 transmission fault

RS485 data bus can’t receive the data

Check transmission device or signal

Failure Display Description Detail corrective measures

Page 107: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FAILURE COUNTERMEASURE

ETD 750 Product Manual 107

rr Brake transistor fault

Brake transistor not work. Change inverter.

rH Brake reactor unit overheat.

Beyond the permit value of brake reactor unit

Reduce regenerative load

ATF Tuning error Motor tuning error Check motor and connections

Com Communication error

Operator panel and inverter transmission failure;

MPU external parts failure

Re-plug the digital operator and connector Check communication connections Change control board or panel

FAF Fan Failure Check if fan of inverter work or not

Remove dust Change fan

EPF EEPROM fault(EPF) Inverter control unit fault. Change control board.

ADF CPU A/D converter fault(ADF)

Inverter control unit fault. Change control board.

:Means that when the fault occurs can choose the stop mode.

10.2 Alarm Display and Explanations Alarm makes the failure contact to output action, and the converter shall

return to the pervious operating status automatically after the failure has been

settled. The following table gives out the illustration for various alarming status.

Table 10-2 Alarm display and explanation

Display Content Explanation

Uu Undervoltage detection Detect undervoltage when the inverter at stop process

OU Overvoltage when stop process

The main circuit EDC voltage exceed overvoltage detection value when the inverter at stop process

OH1 Heatsink overheat Heatsink temperature≥OH1 detection benchmark, choose the testing model while choosing the OH1, and keep on operating

OL3 Over torque detection Inverter output current>105 (over torque detection benchmark) while choose the torque testing and keep on operating

Page 108: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FAILURE COUNTERMEASURE

ETD 750 Product Manual 108

Display Content Explanation

EF Bad operating instruction for the forward and reverse position

Input the operating instruction for the forward and reverse position while input the 500ms to break

bb External BB Input the External BB instruction via the terminals of controlled circuit

CALL RS485 transmit waiting 003(choose the operating model) ≥4,can not receive the normal data flow from the RS485 on the converter after the electrified status

OH3 Overheat Pre-warning for the inverter

The Overheat Pre-warning for the Inverter is inputted via the terminal of the controlled circuit

VAF Wrong KVA Setting Wrong KVA setting for inverter

CE RS485 transmission mistake

Choose the go on operating while the RS485 turn out to be transmission mistake( breakdown during the data flow transmission)

VFE Wrong V/f data setting Wong setting for 018-025(V/F data)

EFF Wrong Multifunctional contact point setting

One of the following wrong setting occurred during the input of the multifunctional contact point(061-067) Set 2 or more than 2 parameter with the same value The contact point 17 and 18 are set at the same time The contact point 24 and 27 are set at the same time

PAF Wrong parameter setting

Inverter rated current×0.1 > ( 109 ) rated Inverter rated current×2 046(SkippingFrequency1) ≥050(SkippingFrequency2) 051(Skipping Frequency extent) 045(upper limited value of the output frequency) < 046 (lower limited value of the output frequency ) 。

10.3 Motor Failures and Corrective Measures If one of the following failures happened on the motor, need to dig out

the failure reason and apply the corrective measures accordingly

If the following examination and corrective measure can not solve the

Page 109: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FAILURE COUNTERMEASURE

ETD 750 Product Manual 109

problems; please do contact our company or the agency immediately

Table10-3 Motor Failures and Corrective Measures

Failures Examination Contents Corrective Measures

No rotation for motor

Check if the power and voltage are imposed on the power terminal R/L1,S/L2,T/L3

To be electrified Cut off the power and re-electrify Check the power and voltageConfirm if the screws of the terminals are screwed down tightly

Check the input voltage on the output terminals (U/T1,V/T2,W/T3) are correct by the rectified voltage meter

Cut off the power and re-electrify

Check if the motor are restrained or not due to the overloaded problem

Remove the overload and unlock

Check if the failure has been shown on the display of the operator

Check the failure researching list

Check if the operating instruction for the forward and reversed position operating has been input

Check the connections

Check if there is any input of reference voltage for frequency controlling

Correct the connections Check the reference voltage for frequency controlling

No rotation for motor

Check if the operating model setting is correct Input the correct setting

Check whether the connection among terminals U/T1,V/T2,W/T3 are correct

Connect the terminals among U/T1,V/T2,W/T3 according to the phase sequence

Opposite rotation

direction for motor

Check whether there is any input of the operating signals given by the connection of the FWD and REV

Correct the connection

Check if the connection for the reference current for frequency controlling is correct

Change the connection

Check if the operating model setting is correct

To operate to if the operating model is correct

Motor can rotate but the speed can not be adjusted

Check if there is any overload Reduce the overloading

Page 110: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter FAILURE COUNTERMEASURE

ETD 750 Product Manual 110

Failures Examination Contents Corrective Measures

Check if the rated value (pole and voltage) for motor is correct

Check the technical data on the motor nameplate

Check if there is the correct accelerated and decelerated scale for the gear

Check the speed-changing structure (eg. Gear)

Check if the max. output frequency setting value is correct

Check the max. output frequency setting value

Too high or too lower speed for

motor

Check if the voltage reduction among the terminals are redundant by the rectified voltage motor

Check the V/F value

Check if there is any overloading Reduce the overloading

Load alternation is excessive Reduce the load alternation Increase the motor capacity of inverter

Unstable rotation

speed on operating

Check if the three-phase or single-phase power are used, and if there is any phase missing for the three-phase power

Check if there any phase missing for the three-phase power connection For the single power supply, connect the AC reactor has been connected to the power.

Page 111: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter MAINTENANCE

ETD 750 Product Manual 111

11. MAINTENANCE 11.1 Basic maintenance methods

Basic maintenance methods

1 Do not touch the high-voltage terminals in inverter,

otherwise, electrical shock shall occur

2

Re-install all the covers before re-electrify inverter,

check if the breaker in plastic box is broken while

uncover the outer cover, otherwise electrical shock

shall occur

3

10 minutes after breaking the main circuit power,

conduct the maintenance work upon the confirmation

of the AC voltage is below 36V. It shall be dangerous if

there is any electric charge on the capacitor

4

Only qualified maintenance personnels can do the

maintenance, examination and part changing work

Please remove all the metal articles(e.g. watch,

bracelet) and use the insulation tool to resist the

electrical shock) , otherwise electrical shock shall

happen

1 PC board for controlling use shall apply CMOS IC, do

not touch CMOS components, or which can be

damaged by the static electricity

2 Do not connect or disconnect the connecting wire and

inker with the power on, otherwise there shall bring the

body injury

Page 112: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter MAINTENANCE

ETD 750 Product Manual 112

11.2 Regular Examination Items In order to avoid any failure happened to ETD750 and ensure smooth

operating with long term and high reliability, please do regular examination

according to instruction given in the following tables. In order to avoid

electrical shock, please break the main circuit power, 10 minutes after that,

confirm the AC voltage of the main circuit is blow 36 V, then do the regular

examination.

Check the voltage is in accordance to voltage needed for inverter (pay

attention to check if there is any damage for the power wire and motor)

If there is any loose between the wire terminal and connector (if any

broken strand for the power wires and terminals connection wires)

Check if there any dust, iron chipping and corrosive liquid and greasy dirt

NO measurement on inverter insulation impedance

Check the output voltage, current and frequency for inverter ( the

disparity between the value measured can not be too big)

Check if the environment temperature is among -5 ~40 , if the

ventilation status is sound or not

If there is any abnormal noise or vibration during operating (Inverter is

not allowed to put in the location with the big vibration)

Clean the blades for air vent and heat sink cleanness status and fan’s

operating status

Page 113: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SURROUNDING FACILITIES

ETD 750 Product Manual 113

12. SELECTION AND CONFIGURATION OF THE SURROUNDING FACILITIES 12.1 Brake resistance configuration table

Resistance Specification Model Power

(W) Resistance value (Ω)

Brake torque

%

Applicable motor /KW

G type

Applicable motor /KW

P type

750G/0000.4/200 80 200 125 0.4 - 750G/0000.75/200 100 200 125 0.75 - 750G/0001.5/200 300 100 125 1.5 - 750G/0002.2/200 300 70 125 2.2 - 750G/0000.75/400 80 750 125 0.75 1.5 750G/0001.5/400 300 400 125 1.5 2.2 750G/0002.2/400 300 250 125 2.2 3.7 750G/0003.7/400 400 150 125 3.7 5.5 750G/0005.5/400 500 100 125 5.5 7.5 750G/0007.5/400 1000 75 125 7.5 11 750G/0011.0/400 1000 50 125 11 15 750G/0015.0/400 1500 40 125 15 18.5 750G/0018.5/400 4800 32 125 18.5 22 750G/0022.0/400 4800 27.2 125 22 30 750G/0030.0/400 6000 20 125 30 37 750G/0037.0/400 9600 16 125 37 45 750G/0045.0/400 9600 14 125 45 55 750G/0055.0/400 12000 10 125 55 75 750G/0075.0/400 18000 7 125 75 90 750G/0090.0/400 18000 7 125 90 110 750G/0110.0/400 18000 7 125 110 132 750G/0132.0/400 36000 3.5 125 132 160 750G/0160.0/400 36000 3.5 125 160 185 750G/0185.0/400 36000 3.5 125 185 220 750G/0220.0/400 48000 3 125 220 250 750G/0250.0/400 48000 3 125 250 280 750G/0280.0/400 48000 3 125 280 315 750G/0315.0/400 48000 3 125 300 350 750G/0355.0/400 55000 2.5 125 350 400

Page 114: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter SURROUNDING FACILITIES

ETD 750 Product Manual 114

Less than 400V/18.5KW inverter need to be installed brake resistance ※

to achieve rapid braking. More than or equal to 400V/18.5KW inverter need to

be installed brake module to achieve rapid braking.

Select resistance and frequency constituted by ETD Company.

Use of brake resistance and brake module not provided by ETD company

lead to the inverter or other device damaged, the company does not bear

any responsibility.

Installation of brake resistance must consider the safety and flammability of

the environment.

If you want to change resistance value and power value, please contact

with your local dealer.

Braking resistor and braking modules need to be separate orders, for more

please contact with your local dealer.

Page 115: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 115

13. APPENDIX 13.1 Installation dimension of Operator Base

Below 3.7KW(include 3.7KW and all the single inverters)use square operator panel:

Above 3.7KW(barring 3.7KW)use rectangle operator panel:

Page 116: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 116

13.2 Installation Dimension of Inverters:

Page 117: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 117

13.3 External Dimension Table Model W W1 H H1 B D

750G/0000.4/200

750G/0000.75/200 105 95 150 139 132 M4

750G/0001.5/200

750G/0002.2/200 105 95 190 179 144 M4

750G/0000.75/400

750G/0001.5/400 105 95 150 139 132 M4

750G/0002.2/400

750G/0003.7/400 105 95 190 179 144 M4

750G/0005.5/400

750G/0007.5/400 123 95 350 334 220 M5

750G/00011.0/400

750G/0015.0/400 153 108 453 436 249 M6

750G/0018.5/400

750G/0022.0/400 180 120 480 463 305 M8

750G/0030.0/400

750G/0037.0/400 180 120 560 543 305 M8

750G/0045.0/400

750G/0055.0/400 273 185 750 720 347 M8

750G/0075.0/400

750G/0090.0/400 415 280 766 731 335 M10

750G/0110.0/400

750G/0132.0/400 475 340 976 941 397 M10

750G/0160.0/400

750G/0185.0/400

750G/0220.0/400

541 405 986 951 412 M10

750G/0250.0/400

750G/0280.0/400

750G/0315.0/400

750G/0355.0/400

638 502 1231 1190 489 M10

Page 118: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 118

13.4 External potentiometer explanation and example 13.4.1 External Potentiometer

External potentiometer for the main frequency of external control,

generally use 5-10K potentiometer.

13.4.2 Usage explanation

External adjustable potentiometer generally has three contacts, namely

potentiometer

fixed resistance

side A, B, and

adjustable side

C (as shown): A and B is

maximum resistance sides of adjustable potentiometer, the resistance value

is the same as marked resistance. Judgment method: Sum of resistance A C

and BC equal to resistance AB, that is to say: AB=AC+BC. For this method

can judge adjustable side C, and then connected C to FV (analog input), A

and B separately to FC and FS.

Examples: Example 1:Internal control of multi-speed:

NOTE: If adjustable side C is wrong connected to FC or FS, it will lead to external frequency setting lost for longer use!

MR/L1 U S/L2 V T/L3 W S1 SC

Time

S1

S2 S5

S6

S7

(Analog Input)

S3 S4

Page 119: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 119

The multi-speed shall stop after running for 1 round, if the above scheme can be achieved

Parameters Setting

Functions Setting Value Running Frequency

053 Running Mode 1 ------

054 Step 1 Mode F1 10.0S 037 Step 1 Frequency

055 Step 2 Mode F2 20.0S 038 Step 2 Frequency

056 Step 3 Mode R3 30.0S 039 Step 3 Frequency

057 Step 4 Mode R4 0.0S 040 Step 4 Frequency

058 Step 5 Mode F2 10.0S 041 Step 5 Frequency

059 Step 6 Mode F3 20.0S 042 Step 6 Frequency

060 Step 7 Mode F1 0.0S 043 Step 7 Frequency

Remarks: (1) Use 054-060 to control the running time for each phase (2) Automatically cycle 053=2 (3) After the running instruction is given, it shall stop after one round running according to the setting curve Example 2: Coupling for many inverters Mode 1: The main frequency of the main and subsidiary inverters shall be effective under the external operating mode.

Graph 1

Page 120: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 120

Mode 2: the operating modes for the main and subsidiary inverters can be chosen causally, the main frequency operating mode for the subsidiary inverter are controlled externally.

Graph 2

Mode 1: the frequency can be set by the potentiometer, as shown in

graph 1, achieve the coupling functions for multi-inverters by setting the

frequency of potentiometer, when the 1st inverter can not function

normally, adjust the potentiometer to make the following inverters to go on

working. Set the scale parameters of 045upper frequency to achieve the

output of the rotation rounds for two inverters can be output as certain

proportion

Mode 2: as shown in graph 2, the coupling of multi-inverters can be

achieved, if the first one can not work, other inverters shall stop working.

Use the main inverter to control subsidiary ones, connect the FC on main

inverter with the FC on the subsidiary inverter, and connect FMAs on the

Page 121: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 121

main with the FV on the subsidiary. Refer to the functions and increment

of the 079 FMA and 080FMA, adjust the operating mode and control

proportion of subsidiary inverter. E.g, set the 079 as 0, 080 as 0.80, which

means to use the frequency of the main inverter to control the subsidiary

inverter. The proportion is 80%, the main inverter is 50HZ, subsidiary is

40HZ, it can be effective under the operating of the main inverter, there

are some losing for the output of the FMA, which can be solved by add

the increment of the FMA.

Page 122: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 122

Example 3: Frequency/frequency conversion switching

Remarks:

K is the switch for the frequency and frequency conversion, FR is a

thermal relay.

K1 is the frequency start button; K2 is the frequency stop button.

Setting for “Stop operation” can be set as the freely running to stop

operation 007.

K3 is the start and stop switch under the frequency conversion status

The interlock shall be imposed between KM2 and KM3.

Example 4: Simple water supply system under constant pressure

Page 123: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 123

Remote differential pressure gauge

Parameters setting

120=1

074=0

003=3

Use the Remote differential pressure gauge to control the operation, stop

the external terminals, use the potentiometer to give out the target value, setting for the potentiometer: Power FS(+12VDC),Set the voltage input

as FV(0~10V), input the target signal to control the PID, F1 refers to the

current input, input feedback signal to control PID

If the current pressure gauge connection mode is chosen, please refer to

setting for 074 and 075 in the operation manual. Please contact the

agency and manufacturers for any queries. Example 5: Specification on parameters setting for ETD series inverter 1. Requirements Use potentiometer to control frequency, and use one button to control the start and stop for the inverter.

Page 124: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 124

2. Setting Modes Termination Mode

1) 220V power supply, for L1 and L2, only terminate two of the following terminals(R,S and T), three-phase 380V power supply, terminate R,S and T terminals, please pay attention to the machine types.

2) Terminate U, V and W terminals with Motor. 3) The three terminals shall connect FC,FV and FS terminals

separately, please refer to the external termination modes specification on Page 118.

Termination Graph

Graph13-4-1 three-phase 380V inverter

3. Parameters Setting 003 operation mode, choose 3, the function setting for 061 S2 is 0 Running Operation: 1) External switch, lock K, running, set the parameters if the motor reversed, change the power phase to 1 for 011 power supply, or change the termination terminals S1 to S2, or change the two output wire for U,V

Attention: Distinct the 220V and 380V machine type. Input 380V power supply to 220V inverter, which shall cause the burn damage of inverter, the ground line shall connect the ground separately.

Page 125: VFD of ETD Drives Yantai

ETD750 Series Universal Vector Inverter APPENDIX

ETD 750 Product Manual 125

and W, then this problems can be solved. 2) Work completed, adjust the potentiometer to 0 3) Break K to stop inverter 4) Cut off electricity supply Attention: No wrong termination allowed for power wires and motor wires on generators. Operating control button shall be controlled separately 13.4.4 Parameters for setting ordinary inverters 002 G/P choose(G: General, P: Pump) 003 Operating Mode 007 Stop Mode 011 Power Phase 012 No Reverse 026 First speed up time 027 First deceleration time 035 V/F choose (Set the V/F curve according to the special start requirement or change the V/F curve setting directly, refer to 018-025) 050-052(Avoid the resonance frequency for motor) 061 S2 function (Choose external start mode, apply the two-way or three-way configuration) 074 Main Analog Value 103 Speed up base 109 Rated Current (refer to rated current on the nameplate on the motor) 110 overloading protection 120 PID choose (Choose close-loop control mode)