vgd series - scc inc siemens combustion controls elk … double gas valve bodies n7631us.… ·...

Download VGD Series - SCC Inc Siemens Combustion Controls Elk … Double Gas Valve Bodies n7631us.… · Technical Instructions VGD Series Double Valves Document Number CC1N7631us November

If you can't read please download the document

Upload: doanthuan

Post on 06-Feb-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • SiemensAGBuildingTechnologiesDivision

    VGDSeries

    TechnicalInstructionsDocumentNo.7631

    VGDxx.xxxUNovember08,2017

    VGDxx.xxxUGasValvesforusewithSKPxx.xxxUelectrohydraulicactuators

    VGD20.xxxU VGD40.xxxU ISO9001and14000REGISTEREDFIRM

    OnlywithseriesSKPxx.xxxUxactuators

    Description ThenormallyclosedVGDxx.xxxUseriesofmodulardoublebodygasvalvescombinewithSKPxx.xxxUserieselectrohydraulicactuatorstoprovidesafetyshutoff,gaspressureregulationand/orairgasratiocontrolforcommercialorindustrialgasburners.

    Table1.VGDxx.xxxUmodelnumbers

    ModelNumbers Bodystyle ConnectionVGD20.253U Double NPTthreadVGD20.323U Double NPTthreadVGD20.403U Double NPTthreadVGD20.503U Double NPTthreadVGD40.065U Double NPTthreadVGD40.080U Double NPTthreadVGD40.100U Double ANSIflangeVGD40.150U Double ANSIflange

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page2 SiemensAGBuildingTechnologiesDivision

    FeaturesAllModels

    ULlisted,FMapproved,CSAcertified,IRIapprovable,ISO9001and14000certified.CE,Australianapprovedversionsavailable

    inchNPTpressuretapsontheinletandoutletandbetweenmainvalves(seeTable2fordetails)

    Stainlesssteelmeshinletfilterprotectsthevalveseat(s)aswellasdownstreamcomponents

    Dualstemguidesensureprecisediscalignmentandtightshutoff ValvesinconnectionwithSKPxx.xxxUactuatorsopenslowlyandcloserapidly

    VGD20.xxxUmodels CompactVGD20.xxxUdoublevalvebodiesconsistof2safetyshutoffvalvesinseries.Thefirst(inlet)valvehasaflatvalvediscapplicableforsafetyshutofffunctiononly.Thesecond(outlet)valvehasacontouredvalvediscforusewithpressureregulatingactuators(SKP2x.xxxU,SKP5x.xxxU,SKP7x.xxxU)

    A1inchNPTventconnectionbetweenthevalves EachVGD20.xxxUdoublevalverequires2threadedmountingflanges(AGFxx.xxU).Each

    flangeincludesthenecessaryinstallationhardware(bolts,nutsandOring).EachmountingflangehasainchNPTpressuretap.Theflangescanbepremountedontothepipe,andthenboltedontotheVGD20.xxxUgasvalvebody.Thisfeatureeliminatestheuseofpipeunionsandpermitsthegasvalveassemblytobeeasilyremovedfromagastrain

    Connectingpatternofthe1...2inchAGFxx.xxUflangesareidentical.ThisspacepermitsanyAGFxx.xxUflangetobemountedtoanyVGD20.xxxUvalvebody

    NOTE:VGD20.xxxUvalvesandAGFxx.xxUflangesmustbeorderedasseparateitems(seeTables2and3).

    VGD40.xxxUmodels CompactVGD40.xxxUdoublevalvebodiesconsistof2safetyshutoffvalvesinseries Eachindividualsafetyshutoffvalvehasdoubleseatstoachievehighflow Patentedseatconstructionwithindividualclosingspringforeachseattoassurereliable

    shutoffandhighcloseoffpressurerating Fullportventlineconnectionplatesareavailable

    NOTE:VGD40.xxxUvalvesandAGA40.xxxxUventconnectionplatesmustbeorderedas

    separateitems(seeTables2and3).

  • VGDSeriesDoubleValves TechnicalInstructions DocumentNumberCC1N7631us November08,2017

    SiemensAGBuildingTechnologiesDivision Page3

    Application AllVGDxx.xxxUvalvescanbecombinedwithanySKPxx.xxxUseriesactuator.Theactuatorcanbemountedwhilethevalveisinstalledandunderpressure.SKPxx.xxxUregulatingactuatorsareapplicableforbothlowandhighsupplygaspressureapplications,eliminatingexcessiveregulatorinventories.Maximumpressureratingsvarywithvalvesize(seeTable2).AllVGDxx.xxxUvalvesperformthesefunctionsincombinationwitheachofthefollowingactuators:SKP15.xxxU SafetyshutoffSKP25.xxxU SafetyshutoffandconstantpressureregulationorzerogovernorSKP55.xxxU Safetyshutoff,pressureregulationanddifferentialpressureairgasratio

    controlSKP75.xxxU Safetyshutoff,pressureregulationandadjustableair/gasratiocontrolSincemorethanonefunctioncanbeperformedbyasinglevalve,fewercomponentsandfittingsarerequiredsignificantlyreducingboththesizeandweightofthegastrain.Inaddition,smallerdiametergasvalvescanbeused.Fordetailsonvalvesizingseetheflowchart(figure3).

    CAUTION: DonotoversizevalvesequippedwitharegulatingSKP2x.xxxU/SKP5x.xxxU/SKP7x.xxxUactuator.Oversizingmaylimitturndownandcouldcauseoscillations.

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page4 SiemensAGBuildingTechnologiesDivision

    Orderinginformation

    Gasvalvesandactuatorsareorderedseparately.ForadditionalSKPxx.xxxUactuatorinformation,seethefollowingtechnicalinstructions:SKP15.xxxU 155751P25SKP25.xxxU 155752P25SKP55.xxxU 155753P25SKP75.xxxU 155754P25

    NOTE:TheSKPxx.xxxUactuatorshaveanoperatingtemperaturerangeof14Fto140F(10Cto60C)!

    Table2.Productnumbers

    Product number

    Size Maximumoperatingpressure

    psi

    Closeoffpressure

    psi

    CapacityCFH

    Naturalgasat

    P=1"W.C.

    Numberof testpoints, 1/4"NPT

    Valvebodymaterial

    Inlet Outlet

    VGD20.253U*) 1" 20 30 600 Twoinchandone1inchportbetweenvalves

    AluminumVGD20.323U*) 1" 20 30 1200 AluminumVGD20.403U*) 1" 20 30 1,850 AluminumVGD20.503U*) 2" 20 30 2,300 Aluminum VGD40.065U 2"NPT 10 75 3,880 1 1 AluminumVGD40.080U 3"NPT 10 75 5,370 1 1 AluminumVGD40.100U** 4"flanged 10 30 9,680 1 1 AluminumVGD40.150U** 6"flanged 10 30 17,490 1 1 Aluminum

    *)VGD20.xxxUdoublevalvesrequire2AGFxx.xxUthreadedflangesforinstallation**)VGD40.1x0Uflangedvalvesmustbeinstalledusingnonmetallicflangegaskets.Gasketmaterialmustbechemicallycompatiblewiththefuelgasbeingusedintheapplicationandmustbesofterthanthealuminumflangesealingsurface.Acceptablegasketmaterialsincludebutarenotlimitedto:rubber,paper,andplastic.ObserveflangebolttorquespecificationsasstatedintheVGD40installationinstructions.AlsorefertoANSI/ASMEB16.24.

  • VGDSeriesDoubleValves TechnicalInstructions DocumentNumberCC1N7631us November08,2017

    SiemensAGBuildingTechnologiesDivision Page5

    Accessories

    Table3.AccessoriesPartNumber Description Notes

    AGF10.25U Single1"connectingflangewith"portforVGD20.xxxU 2requiredpervalve.OrderseparatelyAGF10.32U Single1"connectingflangewith"portforVGD20.xxxU

    AGF10.40U Single1"connectingflangewith"portforVGD20.xxxUAGF10.50U Single2"connectingflangewith"portforVGD20.xxxU AGA40.4050U 1NPTventconnectionplateforVGD40.xxxU Eachventconnection

    includesNPTtestport,seeMountinginstructionM7631.3(7431902780)

    AGA40.6580U 1NPTventconnectionplateforVGD40.xxxUAGA40.0100U 2NPTventconnectionplateforVGD40.xxxUAGA40.0150U 2NPTventconnectionplateforVGD40.xxxU

    AGA61

    ManualadjustingthrottleattachmentAGA61permitsVGDxx.xxxUseriesvalvestobeusedasadjustablelimitingorificevalves.Onceadjusted,theAGA61hasaprovisiontobesealedfromtampering.

    AGA66

    SealinggaskettoprovideNEMA3,NEMA3R,andNEMA4protection.GasketkittomountSKPxx.xxxUPlacebetweenactuatorSKPxx.xxxUandvalveVGDxx.xxxUIncreasesdegreeofprotectionfromIP54toIP65RefertoMountingInstructionM7643.2(7431904210)

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page6 SiemensAGBuildingTechnologiesDivision

    SpecificationsApprovals

    Agencyapprovals/standards UL/429,FM/7400,CSA/ANSIZ21.21/CSA6.5C/IIRIapprovableAgencymarksapplyonlyforVGDxx.xxxUseriesgasvalvebodiesassembledwithSKPxx.xxxUactuators.

    Operatingenvironment

    Maximumoperatingpressure SeeTable2Maximumbackpressure(differential) VGD20.xxxU:2psi(150mbar) VGD40.xxxU:4psi(300mbar)Closeoffpressure SeeTable2Permissiblegastemperature 14Fto140F(10Cto60C)Permissibleoperatingtemperature 14Fto140F(10Cto60C)

    Use SiemensgasvalvesareinaccordancewithUL429.Thevalveisusedas: Safetyshutoffvalve(inconnectionwithSKP15.xxxU) Controlvalvewithsafetyshutofffunction(inconnectionwithSKP25.xxxU,SKP5x.xxxUor

    SKP7x.xxxU)

    Perm.mountingposition

    7631z01us/0815

    Operatingpressure SeeTypesummary

    Typesofgases Suitablenaturalgases,propane,butaneandairFormoreinformationseeUse.

    Strainer Builtin,meshsize0.9mm

  • VGDSeriesDoubleValves TechnicalInstructions DocumentNumberCC1N7631us November08,2017

    SiemensAGBuildingTechnologiesDivision Page7

    SpecificationsPhysicalcharacteristics

    Bodymaterials SeeTable2Weight SeeTables4

    Connections Pipeconnections NPTthreadsorANSIclass150flanges(seeTable2)

    Pressureandventtaps SeeTables2and3

    Operation AllVGDxx.xxxUgasvalvesarenormallyclosed,twowayvalves.Thevalveshaveastandard,integral,stainlesssteelmeshfilter(0.9mm)intheinlettoprotectthedownstreamcomponentsagainstcontamination.AllvalveshaveNPTportsforpressuretestconnection.AfullsizeventconnectionplateisavailableasanaccessoryforVGD40.xxxUvalves.SeeTable2and3fordetailsonportsandventconnectionplates.

    AGF10... AGF10...

    7631z50us/0815

    Figure1.SectionalviewofVGD20.xxxUVGD20.xxxUdoublevalvesconsistoftwovalvesinseries.Thefirst(inlet)valvehasaflatvalvediscsuitableforthesafetyshutofffunctiononly.Thesecond(outlet)valvehasacontouredvalvediscforstableregulatingcontrolandsmoothreleaseofgas.

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page8 SiemensAGBuildingTechnologiesDivision

    Operation,continued

    7631z53us/1215

    Figure2.SecondviewofVGD40.xxxUflangemodelsVGD40.xxxUdoublevalvesconsistoftwovalvesinseries.Eachvalvehasadoubleseattoachievehighflow(seeFigure2).Closingsprings:Eachdoubleseatusesonepairofsprings.Thespringforcesactseparatelyasclosingforcesontheindividualvalveseats.

  • VGDSeriesDoubleValves TechnicalInstructions DocumentNumberCC1N7631us November08,2017

    SiemensAGBuildingTechnologiesDivision Page9

    Gasflowcharts

    100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 100000 2 3

    7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 100000 2

    7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 100000 2

    100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 100000 2 3

    3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7

    cf/h Natural gas 0.641

    cf/h Propane gas 1.522

    cf/h Butane gas 2.003

    cf/h Air 1.004

    m3/h Air 1.004

    Sp. Gr.

    1,000700500400300

    200

    100

    70504030

    20

    107543

    2

    10,70,50,40,3

    0,2

    1,000700500400300

    200

    100

    70504030

    20

    107543

    2

    10,70,50,4

    W.C. mbar

    Pres

    sure

    dro

    p

    p

    7631

    t06u

    s/12

    15

    VGD20...

    VGD40...

    Figure3.Sizingdoublevalves

    Assumptions:1)Pressuredownstreamofvalveisatmospheric2)Maximumgastemperatureof140F3)Valveinfullyopenposition

    NOTE:PressuredropistotaldropacrossbothvalveswhenusingaSKPx5.xxxUactuator,

    withorwithoutanAGA66.

    CAUTION:DonotoversizevalvesequippedwithregulatingactuatorsSKP2x.xxxU,SKP5x.xxxUorSKP7x.xxxU.Oversizingmaylimitturndownandcouldcauseoscillations.

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page10 SiemensAGBuildingTechnologiesDivision

    DimensionsDimensionsinInches(mm) VGD20.xxxU

    AG

    F10.

    ..

    AGF10...

    1/4" NPT

    D

    3-1/

    8(8

    0)

    2-3/4(69)

    2-1/2(63.5)

    2-1/2(63.5)

    3/4(19)

    3/4

    (19.

    5)2-

    7/16

    (61)

    4-1/

    16(1

    03)

    1-1/

    4(3

    0)

    Table4.VGD20.xxxUdimensionsininches(mm)with2flangesAGF10.xxUValvemodel NominalsizeD

    inchLength(L)

    inch(mm)

    Weightpounds(Kg)

    VGD20.xxxU 1 10.59+2x1.02(269+2x26)

    7(3.2)

    1 10.59+2x1.02(269+2x26)

    7(3.2)

    1 10.59+2x1.02(269+2x26)

    7(3.2)

    2 10.59+2x1.18(269+2x30)

    7(3.15)

  • VGDSeriesDoubleValves TechnicalInstructions DocumentNumberCC1N7631us November08,2017

    SiemensAGBuildingTechnologiesDivision Page11

    Dimensions,continuedDimensionsinInches(mm)VGD40.065U/VGD40.080U

    a)

    a)

    GS

    F

    A

    7631m21us/1215

    a)Baseplate

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page12 SiemensAGBuildingTechnologiesDivision

    Dimensions,continuedDimensionsinInches(mm)VGD40.100U/VGD40.150U

    M

    V

    SG

    A

    F

    a)

    a)

    7649

    m05

    us/0

    815

    Table5.VGD40.xxxUdimensionsininches(mm)Type A

    inch(mm)

    Binch(mm)

    Cinch(mm)

    Dinch(mm)

    Einch(mm)

    Finch(mm)

    Ginch(mm)

    Hinch(mm)

    Iinch(mm)

    JinchNPT

    K(SW*)inch(mm)

    L(d=)inch(mm)

    M(d=)inch(mm)

    Sinch(mm)

    Tinch(mm)

    Uinch(mm)

    Vinch(mm)

    VGD40.065U11.42(290)

    8.54(217)

    3.25(82.5)

    4.63(117.5)

    2.09(53.1)

    1.46(37)

    4.02(102)

    6.14(156)

    0.63(16)

    2" 4(100)

    5.5(139.7)

    0.75(19)

    1.77(45)

    3.64(92.5)

    0.80(20.4)

    7.01(178)

    VGD40.080U12.20(310)

    9.39(238.5)

    3.64(92.5)

    5.18(131.5)

    2.09(47)

    0.79(20)

    4.21(107)

    6.30(160)

    0.63(16)

    3" 4.7(120)

    6.0(152.4)

    0.75(19)

    1.2(30.5)

    3.94(100)

    0.88(22.4)

    7.56(192)

    VGD40.100U13.78(350)

    10.52(267.3)

    4.33(110)

    5.70(144.8)

    1.93(49)

    1.95(49.5)

    5.16(131)

    7.56(192)

    0.63(16)

    7.5(190.5)

    0.75(19)

    2.83(72)

    4.55(115.5)

    0.87(22)

    8.74(222)

    VGD40.150U18.90(480)

    13.29(337.5)

    5.71(145)

    7.40(188)

    2.09(53)

    2.30(58.5)

    6.61(168)

    10.31(262)

    0.63(16)

    9.5(241)

    0.91(23)

    3.92(99.5)

    5.61(142.5)

    0.90(22.9)

    10.63(270)

    *)SW=widthacrossflats

  • VGDSeriesDoubleValves TechnicalInstructions DocumentNumberCC1N7631us November08,2017

    SiemensAGBuildingTechnologiesDivision Page13

    Dimensions,continuedDimensionsinInches(mm) VGD40.xxxUvalvewithventconnectionplateOption: a)Baseplate b)VentconnectionplateAGA40.xxxxU(optional)tobeorderedseparately a)andb)areinterchangeable

    2A

    7631z49us/0815

    Table6. VGD40.xxxUdimensionsininches(mm)withmountedventconnectingplate.Valvemodel N

    inch(mm)

    Oinch(mm)

    Pinch(mm)

    Qinch(mm)

    Rinch(mm)

    Weightpounds(kg)

    VGD40.065U 7.13(181)

    4.06(103)

    5.34(135.6)

    3.02(76.59)

    1.46(37)

    1.6(7)

    VGD40.080U 7.28(185)

    4.13(105)

    5.49(139.5)

    3.17(80.5)

    0.79(20)

    19(8)

    VGD40.100U 8.54(210)

    4.76(121)

    6.26(159)

    3.94(100)

    1.95(49.5)

    29(13)

    VGD40.150U 11.30(287)

    6.14(156)

    7.80(198)

    5.47(139)

    2.28(58)

    53(24)

  • TechnicalInstructions VGDSeriesDoubleValvesDocumentNumberCC1N7631us November08,2017

    Page14 SiemensAGBuildingTechnologiesDivision

    Dimensions,continued

    Table 7. AGA40.xxxxU Models

    Ventconnectionplate(optional)

    1/4" NPT

    7631

    m18

    us/1

    215

    VGD4

    0.06

    5U

    VGD4

    0.08

    0U

    VGD4

    0.10

    0U

    VGD4

    0.15

    0U

    Ventconnectionthread"Z"

    AGA40.6580U 1"NPTAGA40.0100U 2"NPTAGA40.0150U 2"NPT

    Informationinthispublicationisbasedoncurrentspecifications.Thecompanyreservestherighttomakechangesinspecificationsandmodelsasdesignimprovementsareintroduced.Otherproductorcompanynamesmentionedhereinmaybethetrademarksoftheirrespectiveowners.SiemensAGBuildingTechnologiesDivisionBerlinerRing2376437RastattGERMANY

    Yourfeedbackisimportanttous.Ifyouhavecommentsaboutthisdocument,[email protected]

    DocumentNo.CC1N7631usCountryofOrigin:DE