voltage drop and resistance calculations · copyright 1999-2019 dan dudley ohms law & voltage...
TRANSCRIPT
Copyright 1999-2019 Dan Dudley
Voltage Drop andResistance
Calculations
Copyright 1999-2019 Dan Dudley
Voltage Drop Diagram
SOURCE Sub-Panel LOAD
3 %
5 %
Total System Branch Circuit
2 %
Copyright 1999-2019 Dan Dudley
Voltage Drop Formulas
• Voltage Drop:ØVD = 2 X K X D X I
CM
Copyright 1999-2019 Dan Dudley
VD FORMULA PRACTICE
• Problem:
• #10 Str, 435 feet, 20-amp load
• What is the Voltage Dropped
• Look at Table 8 Resistance
• #10 Str = 1.24 ohms per 1000’
Table 8
Copyright 1999-2019 Dan Dudley
Voltage drop formula
• Find ‘K’
• K = R X CM
1000
K = 1.24 x 10380
1000
K = 12.87 (OHMS PER CM FOOT)
Copyright 1999-2019 Dan Dudley
Plug the values into formula
• VD = 2 X K X D X I
10380
VD = 2 X 12.87 X 435 X 20
10380
VD = 223938 VD = 21.57 Volts
10380
Copyright 1999-2019 Dan Dudley
Voltage Drop Formulas
• Wire Size:
• CM = 2 X K* X D X I
VD permitted
Note the ‘*’ by the ‘K’.
Use 12.9 for Copper
Use 21.2 for Aluminum
Copyright 1999-2019 Dan Dudley
CM example
• First get VD allowed: 5% or 3% ?
• Branch Circuit = 3%
• Total System or Source = 5%
• Example:(from source)
• 230 volt, 325 feet, 15-amp load
• What size wire do I need ?
Copyright 1999-2019 Dan Dudley
VD PERMITTED (in volts)
• VD permitted = source X .05 or .03
• .05 = 5% .03 = 3%
• VD = 230 X .05 = 11.5 volts
Copyright 1999-2019 Dan Dudley
CM example continued
• CM = 2 X K* X D X I
VD Permitted
CM = 2 X 12.9 X 325 X 15
11.5 volts
CM = 125775 = 10936 CM
11.5
#8 cu = 16510 CM
Copyright 1999-2019 Dan Dudley
Voltage Drop Formulas• Distance:
• D = CM X VD permitted
2 X K X I
• D = 10380 X 11.5 volts
2 X 12.87 X 20
• D = 119,370
514.80
• D = 231.876 or 232 feet
Copyright 1999-2019 Dan Dudley
Voltage Drop Formulas
• Load:
• I = CM X VD permitted
2 X K X D
§ I = 10380 X 11.5
2 X 12.87 X 325
§ I = 119370
8365.5
§ I = 14.269 amps
Copyright 1999-2019 Dan Dudley
Calculating ‘K’
• K = R X CM
1000
* From Table 8
Copyright 1999-2019 Dan Dudley
Voltage Drop Rules:
• The ‘2’ is for 1Æ
• For 3Æ Change ‘2’ to ‘1.732’
• ‘D’ is the distance ‘ONE WAY’
• ‘I’ is the total load in Amperes
• ‘CM’ is the conductor size (T.8)
• ‘K’ is the RESISTANCE of a CM foot
* Note: Ø = Phase
Copyright 1999-2019 Dan Dudley
Voltage Drop Notes:
• * when using the formula for ‘CM’ or Wire Size always use the approximate‘K’ of 12.9 Cu and 21.2 Al.
• * VD permitted is:
• 3% for a BRANCH CIRCUIT
• 5% for the TOTAL SYSTEM
Copyright 1999-2019 Dan Dudley
UseUNCOATEDunless toldotherwise
Copyright 1999-2019 Dan Dudley
1 – Phase VD Example
VD = 2 X 12.87 X 500’ X 10A
10380
= 128,700
10380
= 12.39884 or 12.4 volts
Copyright 1999-2019 Dan Dudley
3 – Phase Example
VD = 1.732 X 12.87 X 500’ X 10A
10380
= 111,454.2
10380
= 10.7373 or 11 volts
Copyright 1999-2019 Dan Dudley
Short Circuit Calculation
• Circuit is 120v, 20A, with Inverse time CB• #12 Cu Circuit conductors, cut both the ungrounded and• grounded conductors 4 feet from circuit breaker.• #12 Cu wire resistance = 1.93 ohms 1000’• #12 Cu = 8’ 1.93 X .008 = .01544 ohms resistance• Current Flow = I = E/R = 120v / .01544 = 7,772.02 amps
• Cut conductors at 2 feet from circuit breaker:• #12 Cu = 4’ 1.93 X .004 = .00772 ohms resistance• Current Flow = E/R = 120v / .00772 = 15,544.04 amps
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Ohms Law & Voltage DropPractice Questions
30 minutes