voltage sag-piller datacentre dynamic dubai piller.pdf

54
A Langley Holdings Company Piller Power Systems Secure Power Supply DatacentreDynamics, Dubai 1st December 2008 Daniel Bianconi

Upload: -

Post on 27-Oct-2015

205 views

Category:

Documents


6 download

DESCRIPTION

Voltage sag

TRANSCRIPT

A Langley Holdings Company

Piller Power Systems

Secure Power Supply DatacentreDynamics, Dubai

1st December 2008 Daniel Bianconi

A Langley Holdings Company

Introduction Piller Power Systems

Why we need a Power Conditioning System

Dynamic Diesel UPS UNIBLOCK UBTD

Application Data Centre (Tier II to Tier IV)

What makes the difference?

A Langley Holdings Company

The only company which produces rotary and static technologies in the field of power protection

Founded in 1909

Approx. 750 employees

Represented in more than 30 countries of the world

Quality management as per ISO 9001

Uninterruptible Power Supplies & Power Conditioning Systems

400Hz Aircraft GroundPower Supplies

Power supplies for military applications

Frequency conversionsystems 50 / 60 Hz

Piller at a Glance

A Langley Holdings Company

Location of PILLER Power Systems facilities

Osterode

Bilshausen

A Langley Holdings Company

Piller Power Systems Group

Modern Manufacturing

Purpose-built manufacturing in

Osterode and Bilshausen / Germany

14 hectares total area

approx. 50,000m² accommodation

A Langley Holdings Company

Piller Turnover 2007

Europe55%

USA27%

AsiaPacific

18%

€ 206 million

A Langley Holdings Company

UPS & Power Conditioning

AP Premium: 100 kVA to 400 kVA APOTRANS : 25A to 1600A

UNIBLOCK UBR: 150 kVA to 1300 kVA UNIBLOCK UBTD: 400 kVA to 3000 kVA

AR Series: 3 kVA to 100 kVA

UNIBLOCK UBT: 400 kVA to 2000 kVA

A Langley Holdings Company

UNIBLOCK with water cooling

A Langley Holdings Company

Piller Power Systems world wide

Piller Taiwan

24h service with APOCONNECT

A Langley Holdings Company

Piller in Middle East / Turkey

• Installed Dynamic / Diesel UPS units in Middle East and Turkey > 40MW• Installed Static UPS units in Middle East and Turkey > 12MW

Some Diesel UPS installations in Gulf countries:

Bahrain Financial Harbour: 3 x UNIBLOCK UBTD 1500 / 1100 kVA

MBC Bahrain 1 x UBTD 800

New Doha International Airport 4 x UBTD 1600 Containerized

Qapco 1 x UBTD 1100 kVA

JCP Saudi Arabia 2 x UBTD 1670

etc……

A Langley Holdings Company

Dynamic Diesel UPS

UNIBLOCK UBTD

A Langley Holdings Company

Why do we need a Power Conditioning System ?

Mains disturbances

Short interruptionsTotal failuresFrequency fluctuationsVoltage fluctuationGlitchesHarmonics

Load disturbances

Load fluctuationsUnbalanced loadsOverloadsHarmonicsPeak currentsShort circuits

Power improvementSystem

Intrinsic safety of the Power improvement System

Your power improvement system must be able to cope with all of these disturbances

A Langley Holdings Company

UNIBLOCK UBTD Characteristics

Totally flexible configurations,Medium and Low Voltage

Different Diesel Engineselectable

Customisedbattery forshort backup

Powerbridgefor up to 39sshort backup

or

Totally flexible configurations,Medium and Low Voltage

Different Diesel Engineselectable

Customisedbattery forshort backup

POWERBRIDGEfor up to 39sShort backup

A Langley Holdings Company

UNIBLOCK UBTD – Dynamic Diesel UPS

HQ Bus

UNIBLOCKMachine

POWERBRIDGE

GG

M

Automatic Bypass

Coupling ChokeMains

LV or MV

Diesel Engine

Thyristor converter

A Langley Holdings Company

Complete System Arrangement

POWERBRIDGE

UTILITY

MOTOR INPUT

GENERATOROUTPUT

TO CRITICALLOAD

M

M

AUTOMATIC BYPASS

ISOLATING/ COUPLING CHOKE

BI-DIRECTIONALCONVERTER

D.C.

LINK

M

A Langley Holdings Company

UNIBLOCK-machine, the evolution

Rotating rectifier

Generator windingMotor winding

Ponymotor

Excitation

Fan

Hybrid machine invented in 1981 by PILLER

GeneratorMotor

Traditional system

Damperwinding

Motor winding Generator winding

Exciter winding

A Langley Holdings Company

UNIBLOCK UBTD Motor / Generator

Motor and Generator Windingsin a Common Stator

Common RotorWith Damper Winding

System FanBrushlessExcitation

Bearing

Bearing

A Langley Holdings Company

POWERBRIDGE Schematic

Magnetic SupportTop BearingTop Guard BearingRotating RectifierExcitation GeneratorMain Machine

Flywheel

Bottom Bearing

Bottom GuardBearing

A Langley Holdings Company

POWERBRIDGE bridging time

0

20

40

60

80

100

120

140

0 200 400 600 800 1000 1200 1400 1600 1800

UPS power /kVA

Brid

ging

time

/s

POWERBRIDGE 16.5 MJ bridging time versus load

Available in: 6 MJ , 16,5 MJ , 19 MJ

A Langley Holdings Company

The Choke

VM

Output:Short-circuit current:- 14 x nominal current 10 ms - 3 x nominal current 5 s

Load

VL

7%

Input:

Input Power factor: 0,99

50% 1%

GM

X

Harmonic attenuation: 99%

Mains

Voltage dip: -10% continuous

-20% for 10 min

-50% up top 30s

Harmonic attenuation: 99%

A Langley Holdings Company

Components

Diesel Control Panel Genset

UNIBLOCK UBTD Control Panel

Diesel starter battery

Control battery

A Langley Holdings Company

Components of the Generating-set

Flexible couplingPiller UNIBLOCKMotor / Generator

Diesel Control Cabinet

Diesel Engine

Base FrameMechanical

Overrun Clutch

Rubber Vibration-absorbing Pads

A Langley Holdings Company

Mains operation

1

THYRISTORCONVERTER

G

POWERBRIDGE

MG

UNIBLOCK Machine

DIESEL

MAINS UPS Bus

A Langley Holdings Company

POWERBRIDGE operation

2

THYRISTORCONVERTER

G

POWERBRIDGE

MG

UNIBLOCK Machine

DIESEL

MAINS UPS Bus

A Langley Holdings Company

Diesel operation

3

THYRISTORCONVERTER

G

POWERBRIDGE

MG

UNIBLOCK Machine

DIESEL

MAINS UPS Bus

A Langley Holdings Company

Function overview of a UNIBLOCK UBTD

UPS Output voltage

Diesel speed

POWERBRIDGE speed

Mains

A Langley Holdings Company

Function overview of a UNIBLOCK UBTDwith emergency bus

MG

UNIBLOCK T

THYRISTORCONVERTER

G

POWERBRIDGESHORT BREAK BUS

DIESEL

MAINS UPS

MG

UNIBLOCK T

THYRISTORCONVERTER

G

POWERBRIDGESHORT BREAK BUS

DIESEL

MAINS UPS

321 1

1

3

2

Diesel speed

UPS Outputvoltage

SpeedPOWERBRIDGE

Mains

5 s

15 s

1 min3 min

2 s

MG

UNIBLOCK T

THYRISTORCONVERTER

G

POWERBRIDGESHORT BREAK BUS

DIESEL

Mains UPS

2Short break bus

A Langley Holdings Company

UNIBLOCK UBTD Single unit ratings

LV 50Hz

400V / 415V 380V

420kVA 420kVA

500kVA 500kVA

625kVA 625kVA

800kVA 800kVA

1100kVA 1100kVA

1670kVA 1670kVA

2000kVA 2000kVA

2500kVA 2350kVA

LV 60Hz

380V 440V 480V

400kVA 460kVA 500kVA

500kVA 550kVA 600kVA

600kVA 690kVA 750kVA

750kVA 920kVA 1000kVA

1100kVA 1200kVA 1300kVA

1600kVA 1670kVA 2000kVA

1800kVA 2400kVA

3000kVA

MV

50Hz 60Hz

1670kVA 1670kVA

2000kVA 2000kVA

2500kVA 3000kVA

A Langley Holdings Company

UNIBLOCK UBTD Containerized Version

Advantages:Operating readiness immediately on connecting to the mains. No structural measures for noise attenuation, ventilation or cabling.No expenditure for on-site testing and commissioning.No outlay on complex installation or plant room construction.Temporary use in different locations.Reduced on site programme.

A Langley Holdings Company

Application: Parallel redundant configuration(Tier II)

Load evenly spread between UPS modules

Maintenance of UPS possible without switching to bypass

Disconnector for separation of UPS bus bar

Optional external automatic bypass and external bypass control

Distribution paths upstream and downstream still single-points-of-failure

Number of parallel connected UPS limited by short circuit current capability of UPS bus bar

DUPS1

Manual-Service-Bypass

Unprotected mains/Short break bus

Unprotected loadDUPS

nDUPSn+1

……

Disconnector

UPS distribution 2

UPS distribution 1

Data centre

UPS busbar

G

n

G

+1

Auto-Bypass

A Langley Holdings Company

Application: Data centre with A-B supply and n+1 isolated redundancy (Tier III)

Total installed UPS power (n+1)*100% of rated loadProtects against the loss of one UPSA shorted load has no effect on the other loadsNo limitation in powerRedundancy down to the loadConcurrently maintainableVery high availability

G G

n +1

DUPS1

Mains 1

Unprotected mains/Short break bus

DUPS2

DUPSn

DUPSn+1

Busbar A

Busbar B

STS STS STS STS STS STS

A Langley Holdings Company

Application Large-scale data centre Tier IV with 2 independent UPS systems (n+1)

System + System redundancyMultiple distribution paths simultaneously serving IT load Complementary systems and distribution paths physically separatedComb-like arrangement of bus barsIT equipment dual powered or supplied by STSRedundant supply of individual loadsIt is debatable if 1 x (n+1) gensetsare sufficient

Disconnector

Busbar

UPS busbar

DUPS1

DUPSn+1

DUPS2

Man

ual-S

ervi

ce-

Byp

ass

DisconnectorUPS busbar

DUPS1

DUPSn+1

DUPS2

Man

ual-S

ervi

ce-

Byp

ass

DP

DP

Mains 2

…..Load1

…..Load1

Loadx

Loady

…..Load1

Loadx

…..Load1

Loady

A

B

A

B

A

B

A

B

G

n

G

+1

G

n

G

+1

Unprotected mains/Short break bus

Mains 1

STSSTS

STS STS

A Langley Holdings Company

Why Piller UNIBLOCK UBTD

What makes the difference?

A Langley Holdings Company

What makes the difference?

3-times rated current does not allow a safe & fast clearing of downstream faults. Consequence during mains failure:UPS output voltage = 0 , all loads affected !

Ishort

circuit

?

Ishort circuit from the mains

14-times high short circuitcurrent for a quick switch-offof defective loads during all operation modes, mains, battery and Diesel.

14-times rated Current ensures that faulty load is disconnected in 10ms

High short- circuit capacity

A Langley Holdings Company

3-phase output short circuit

UNIBLOCK T Measurements

What makes the difference?

A Langley Holdings Company

22,3 kA

17,5 kA

= 13,6 x In

= 10,7 x In

3-phase output short circuit

UNIBLOCK T Measurements

What makes the difference?

A Langley Holdings Company

What makes the difference?

Crest Factor ExampleLoad current waveform of an IT load

Distortion (THD) 89%Crest Factor 5.5

A Langley Holdings Company

No crest factor limitation

HQ-power independent of the load conditions.

Load voltage

Consequence

Peak current

R M S current1

UBTDLoad current

Peak current

R M S current1

Load currentStatic UPSLoad current

Current limiting

1

Peak current

R M S current3

3

Load voltage

Consequence

What is the crest-factor ?

peak currentR M S current

Crest factor =

What makes the difference?

A Langley Holdings Company

Bridging time:

Bridging short term power interruptions without starting the Diesel Engine

What makes the difference?

A Langley Holdings Company

Bridging time:

No stress on Diesel Engine

What makes the difference?

A Langley Holdings Company

What makes the difference?Input Voltage tolerance: Compensation of the voltage dips without starting the Diesel Engine

Input Voltage tolerance -10% continuous -20% for 10 min -50% up to 20s

Optional (800 to 2000 kVA)-20% continuous-30% 10 min-50% up to 20s

VLVM

Mains Load

Motor-Generator G

M

G

Thyristor Converter

POWERBRIDGE

A Langley Holdings Company

Reversible function of POWERBRIDGEDealing with load changes:

What makes the difference?

VLVM

Mains Load

Motor-Generator G

M

G

Thyristor Converter

POWERBRIDGE

A Langley Holdings Company

What makes the difference?

A Langley Holdings Company

What makes the difference?

A Langley Holdings Company

What makes the difference?

Harmonic attenuation 99% :

Mains Load

VM VL

Motor-Generator

GM

6%

1%50%

A Langley Holdings Company

What makes the difference?Mains short circuit:

Motor-Generator

GM

Mains Load

VLVM

Input Choke:

• Piller: 50%

6%

1%50%

A Langley Holdings Company UNIBLOCK Measurements

Single phase inputshort

circuit

What makes the difference?

A Langley Holdings Company

Permissible input frequency deviation:

What makes the difference?

Mains Load

Mains frequency deviation +/-5%VM VL

Motor-Generator

GM

Piller: +/-1% (Adjustable to +/- 5%)If the load can accept

A Langley Holdings Company

Redundant Diesel start Power source.

Possibility to start the Diesel Engine by POWERBRIDGE

What makes the difference?

POWERBRIDGEDiesel starter battery

A Langley Holdings Company

What makes the difference?Piller Engineering / Quality

100 years of experience in design and manufacturing dynamic devices

A Langley Holdings Company

Other Diesel UPS40% of all mainsdisturbances compensated without engine start

UNIBLOCK UBTDUp to 99% of all mains disturbances compensated without engine start

Other Diesel UPS40% of all mainsdisturbances compensated without engine start

UNIBLOCK UBTDUp to 95% of all mains disturbances compensated without engine start

UNIBLOCK UBTDMains failure statistic for medium voltage

What makes the difference?

A Langley Holdings Company

Summery

Wide input voltage tolerance (+15%/-10%, -20% for 10 min, -50% up to 30s)

Very high MTBF Efficiency up to 96%Unlimited crest factorFault discrimination with 14x rated currentLarge overload capacity ( 10% for 1 h, 25% for 10 min, 50% for 2 min )

Fast energy delivery and absorptionConstant output during load fluctuationThe capacity can be extended

A Langley Holdings Company

Summery

RS 232, RS 485 or SNMP adapterUNIBLOCK can supply the UPS Load and the none sensitive load No need to start the engine for every mains failureFreedom to choose many Diesel engine manufacturerCompact constructionsLow maintenance costExcellent frequency stability

A Langley Holdings Company

Any Question