© Munters Corporation , March 2015 QM1056r11 Instruction Manual VX36 Aerotech Fan Models: VX36F, VX365F VX36 Aerotech Fan

Upload: hoangkiet

Post on 04-Jun-2018

234 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 2015 QM1056r11

Instruction Manual

VX36 Aerotech FanModels: VX36F, VX365F

VX36Aerotech Fan

Page 2: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 20152 QM1056r11

VX36 Aerotech Fan Manual for use and Maintenance

Thank You:Thank you for purchasing a Munters Aerotech VX36 Fan. Munters equipment is designed to be the highest performing, highest quality equipment you can buy. With the proper installation and maintenance it will provide many years of service.

Please Note:To achieve maximum performance and insure long life from your Munters product it is essential that it be installed and maintained properly. Please read all instructions carefully before beginning installation.

Warranty:For Warranty claims information see the “Warranty Claims and Return Policy” form QM1021 available from the Munters Corporation office at 1-800-227-2376 or by e-mail at [email protected].

Conditions and Limitations:• Products and Systems involved in a warranty claim under the “Warranty Claims and Return Policy” shall have

been properly installed, maintained and operated under competent supervision, according to the instructions provided by Munters Corporation.

• Malfunction or failure resulting from misuse, abuse, negligence, alteration, accident or lack of proper installation or maintenance shall not be considered a defect under the Warranty.

Page 3: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

3© Munters Corporation , March 2015 QM1056r11

Index

Chapters Page

1. Unpacking the Equipment 4

1.1 Parts List 4

1.2 Fan Dimensions 5

2. Instalation Instructions 6-7

3. Electrical Wiring 8

4. Operation 9

5. Maintenance 10

5.1 Monthly Maintenance 10

5.2 Winterizing 11

6. Trouble Shooting 12

7. Exploded View 13-14

Page 4: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 20154 QM1056r11

1.1 Parts List

Unpacking the Equipment

1.Each VX36 includes:

1 - 36” Belt Drive or Direct Drive Fan 1 - Hardware Package (HP1031)

HP1031 for VX36 Aerotech Fan [A] ......37 -20 x 7⁄8” Truss Head Bolts, S.S [B] .......37 -20 Hex Flange, Nylock Nut, S.S. [C] ......12 - #14 x 1.5” Tapping Screws

[A]

[B]

[C]

Page 5: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

5© Munters Corporation , March 2015 QM1056r11

1.2 Fan Dimentions Before beginning installation, check the overall condition of the equipment. Remove packing materials,

and examine all components for signs of shipping damage. Any shipping damage is the customer’s responsibility and should be reported immediately to your freight carrier.

H

Unpacking the EquipmentChapter 1

I

G

A B B

ED

C

JF

Fan Specifications:

Hertz: 60 60 Power: 120/240 VAC or 208-240/480 VACPhase: 1 or 3

Hertz: 50 50 Power: 120/240 VAC or 208-240/480 VACPhase: 1 or 3

16"67⁄8"

AFAN DIA.36"

B CWALL OPENING (I.D., framed)D E F G H I43"W. x 43"H.

J16" 16"67⁄8" 453⁄4" 453⁄4" 241⁄16" 8" 363⁄4"

Page 6: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 20156 QM1056r11

Installation Instructions

2.2.1 INSTALL

Step 1 Construct the framed opening to correct size according to the chart below and your fan size. See Figure 1.

Figure 1

WALL OPENING(I.D., framed)

W.

43"H.

x 43"

FANDIA.

36"

Ceiling

Framing

H. -

Wal

l Ope

ning

(see

cha

rt)12

"

W. - Wall Opening (see chart)

12"Min.

Moving Parts: Disconnect Power before servicingWARNING

Step 2 Insert fan into the framed opening from the inside.

While lifting fan up tight to framing, fasten top of fan with the (3) Fastners [C] (provided). See Figure 2. Next, fasten bottom of fan, then both sides with remaining (9) Fasteners [C] screws (provided). Install flashing around opening tight to fan and caulk around fan to seal.

Step 3 Outlet of fan comes unguarded, it is recommended

that an Aerotech discharge cone with guard, a fan hood with guard or a guard by others is installed on outlet of fan at this time. Refer to QM1009 for Cone Installation.

Figure 2

#14 x 1.5" TappingScrews [C]

2 x 4 Framing

OUTSIDE INSIDE

Page 7: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

7© Munters Corporation , March 2015 QM1056r11

Instalation InstructionsChapter 2

Step 4 Make electrical connection to fan motor per instructions in electrical wiring section and as shown on motor.

Step 5 Insert shutter into fan by sliding the bottom flange of shutter into bottom shutter clips and pressing shutter

inward, See Figure 3A. Fasten shutter in place by rotating the side and top shutter clips over the shutter flanges, See Figure 3B..

Figure 3B

Figure 3A

Shutter clip

Shutter

Page 8: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 20158 QM1056r11

Electrical WiringChapter 3

WARNINGWARNING High Voltage: Disconnect power before servicing.WARNING

All wiring should be installed in accordance with National, State, and Local electrical codes. Fans used to ventilate livestock buildings or other rooms where continuous air movement is essential should be connected to individual electrical circuits, with a minimum of two circuits per room. For electrical connection requirements, refer to diagram on motor nameplate and to information enclosed with the Munters environmental control to be used.

Single Phase Fans: motor overload protection should be provided for each fan. A Circuit Breaker Switch or slow blow motor type fuses must be used See Figure 4A. See Munters form QM1400 for proper size.

Figure 4A Single Phase - Motor Overload Protection with Disconnect

(SY2000 or Equivalent)

KEY: L1 = Line 1 H = Hot L2 = Line 2 N = Neutral G = Ground

NOTE: Information in parenthesis refers to 120 VAC control.

120 or 240 VAC Power Supply for Fan

L1 (H)

L2 (N)

G

T1 (H)

T2 (N)

G

120 or 240 VACPower Out to Fan

L1 (H)

L2 (N)

T1 (H)

T2 (N)

Recommended wire routing:As the power cable exits the back of motor form a drip loop and then run power cable down along strut and "zip tie" the cable to strut to prevent cable from getting tangled in the pulley or belt. See figure 5. Then run the cable out the hole to the circuit breaker or control panel.

Zip tie

Power cable

Drip loop

NOTE: A safety cut-off switch should be located adjacent to each fan.

Three Phase Fans: motor overload protection should be provided for each fan. A three-pole motor starter or slow blow motor fuses must be used. See Figure 4B. If a frequency drive (inverter) is used, confirm that motors are rated for inverter duty at the voltage used. The installation of line reactors is recommended to reduce voltage spikes and harmonic distortion. Supplemental motor overload protection is also recommended.

Figure 4BThree Phase - Motor Overload Protection with Disconnect

Three Phase Power Supply for Fan

L1

L2

G

T1

T2

G

Three PhasePower Out to Fan Motor

L1

L2

T1

T2

L3 T3 L3 T3

Motor StarterSafety Cut-off

Switch

Figure 5

Page 9: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

9© Munters Corporation , March 2015 QM1056r11

OperationChapter 4

1) INITIAL START-UP: With electrical power off, verify that the fan propeller turns freely and that all fasteners are secure. Turn on electrical power and confirm that the fan operates smoothly.

2) ADJUSTMENTS: Set the fan control to the temperature shown on your Munters drawing, or to a value which will provide the desired environmental conditions.

3) BELT ADJUSTMENTS: After 3 days of operation you must tighten fan belt. See Maintenance Section: Belt Tightening.

Single Phase Fans: When variable speed controls are used, the fan's idle speed will need to be set to the recommended minimum airflow rate. Refer to the procedures included with each control. The table below provides airflow rates at various propeller speeds for fans wired for 240 VAC.

Moving parts: Disconnect power before servicing.WARNING

A = Fan with cone & shutter B = Fan with hood & shutter

CFM 0.02” Static Pressure 0.05” Static PressureA B A B

RPM VOLTS RPM VOLTS RPM VOLTS RPM VOLTS

36”

Fans

750 — — — — — — 350 1211000 — — — — 370 123 390 1281250 330 117 330 119 390 127 410 1301500 360 123 360 125 410 131 430 1341750 370 125 370 127 425 136 440 1362000 380 128 390 130 450 137 460 1392500 410 131 420 135 470 141 480 1433000 430 135 440 138 490 145 500 1464000 470 142 480 145 520 149 530 1515000 520 148 530 152 560 156 570 1586000 560 154 580 159 590 161 600 1627000 610 159 640 165 640 166 680 1728000 650 166 700 173 690 172 750 1799000 710 172 760 185 740 178 810 209

10,000 770 179 840 225 790 195 — —11,300 840 223 — — — — — —

Three Phase Fans:

1) 36" Direct Drive, 3 Phase fan is not suitable for frequency drive.

2) The use of a quality frequency drive and the installation of line reactors is recommended to reduce voltage spikes and harmonic distortion.

3) Minimum operating frequency of 30 Hz.

4) Will require three pole contactors with overload protection (by others).

Page 10: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 201510 QM1056r11

MaintenanceChapter 5

WARNING

Moving Parts: Disconnect Power before servicingWARNING

WARNING High Voltage: Disconnect power before servicing.WARNING

The following inspection and cleaning procedures should be performed monthly:

1) INSPECT PROPELLER: Check that propeller is secure on motor shaft and that there are no signs of damage. The blades are of a self-cleaning design and should not require maintenance.

2) CLEAN regularly for best results: • FAN MOTOR: Remove any dust accumulation from motor using a brush or cloth.

(DO NOT use a pressure washer). A clean motor will run cooler and last longer. At the same time, verify that the motor is secure in its mount.

• SHUTTER: Carefully clean dust from shutter blades and frame so that shutter opens and closes freely. A brush or cloth should be used.

• GUARD: Clean any dust or feathers from fan guards using a brush. Dirty guards can reduce airflow.

3) CHECK FASTENERS: For safety, all fasteners should be inspected. Tighten any loose connections.

4) INSPECT FAN CONTROL: With power disconnected, inspect all electrical connections. Wiring should be secure and in good condition. Remove any dust build-up from control case and sensor using a soft brush or cloth. NEVER CLEAN ELECTRICAL EQUIPMENT WITH A PRESSURE WASHER!

5) GREASE BEARINGS: Grease bearings every 4-6 months. Use no more than 2 shots when greasing fan. • A premium non-water based grease is recommended: - Shell Alvania #2 - Mobil Mobilux #2 - Exxon Unirex N2 - Texaco Premium RB - Mobil 532 - Texaco Multifak #2

6) CHECK DRIVE ALIGNMENT: Use a straight edge to check the alignment of the pulleys. If an adjustment is needed, remove the belt, then loosen the set screw in one pulley and move it. Remember to tighten the set screw after making an adjustment. Drive alignment is very important for long belt life and proper operation.

7) CHECKING PULLEYS: Roll the belt off and look at both pulleys. If the pulley has grooves in it or is no longer smooth, it needs replacement. A loose or slipping belt will reduce fan performance up to 60% and cause premature belt failure.

PulleyPulley

Straight Edge

BeltPulleyPulley

Straight Edge

Belt

SmoothPulley

GroovedPulley

Page 11: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

11© Munters Corporation , March 2015 QM1056r11

Maintenance / Winterizing FanChapter 5

8a) BELT tightening: All belts must be checked for proper tension after the first 3 days of fan operation and

every 4-6 months thereafter.

AeroLink Belt • Roll the belt off the pulleys by forcing it side ways off the larger pulley as you turn the drive by hand. • Reinstall the belt by wrapping it around the smaller pulley and then starting it over the larger pulley. • As you continue rolling it onto the larger pulley, the belt should become taut in the position shown below. • If the belt becomes taut before reaching the position shown, add one link and try again. • If the belt is loose when in the position shown, remove one link and try again.

8b) BELT tightening: To adjust the belt tensioner to the proper setting, loosen 10 mm bolt (using 16mm or 17mm end wrench)

to allow tensioner arm to rotate. Working from inlet/motor side of fan, place a 27 mm (11⁄16”) wrench onto the hex on the tensioner. Turn wrench clockwise until the single mark on base of the belt tensioner is aligned with mark 2 on the tensioner arm. Hold tensioner at this setting and tighten the 10mm bolt to 40 ft.-lbs torque

Moving Parts: Disconnect Power before servicingWARNING

Mark on Base

Second Mark on Tensioner Arm

Solid Belt with TensionerAeroLink Belt

In most climates, it is probable that the ventilation system will never need to operate at a total capacity during the colder winter months. Consequently, it is advisable to "winterize" those fans which will not be used in cold weather to avoid unnecessary heat loss and condensation.To winterize, turn fan control "off". Install the insulated closure panel over the fan intake. If you don't have an insulated closure panel, a piece of rigid insulation material can be used. Remember the insulation panel must be removed before warmer weather returns.

NOTE: At least one single speed fan should be left uncovered and with power available to provide air movement in the event of variable speed control difficulties.

Winterizing Fan

Page 12: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 201512 QM1056r11

Trouble ShootingChapter 6

WARNING

Moving Parts: Disconnect Power before servicingWARNING

WARNING High Voltage: Disconnect power before servicing.WARNING

WARRANTY: See Munters Limited Warranty Statement

SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION

Fan Not Operating

1. Fan control set above room temperature2. Blown fuse or open circuit breaker3. Propeller blade contacting fan housing4. Fan control defective5. Motor defective

1. Set to a lower temperature2. Replace fuse or reset breaker3. Realign motor in fan housing4. Repair or replace control5. Repair or replace motor

Fan Operating-Insufficient Airflow

1. Variable speed control improperly adjusted2. Damper door jammed3. Guard dirty4. Frequency drive improperly adjusted5. Incorrect Belt Tension

1. See Operation, Step 2 for adjustment guidelines2. Clean damper door & fan housing3. Clean guard4. See operation, Step 2 for adjustments guidelines5. See Maintenance Section, Belt Tightening

Excessive Noise

1. Variable speed control idle speed set to low2. Variable speed control defective3. Propeller blade contacting fan housing4. Motor bearing or shaft bearing defective

1. Increase idle speed setting2. Repair or replace control3. Sand fan housing to remove high spot4. Repair or replace motor or shaft bearings

Excessive Vibration1. Motor loose on mount2. Propeller damaged3. Motor or propeller shaft bent

1. Tighten fasteners2. Replace propeller3. Repair or replace motor or propeller shaft

Page 13: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

13© Munters Corporation , March 2015 QM1056r11

Exploded View

7.

Page 14: VX36 Aerotech Fan - Munters · VX36 Aerotech Fan Manual for use and ... of line reactors is recommended to reduce voltage spikes and harmonic distortion. ... non-water based grease

© Munters Corporation , March 201514 QM1056r11

Exploded ViewChapter 6

Munters Europe AB, Isafjordsgatan 1, P.O. Box 1150, SE-164 26 Kista, Sweden. Phone +46 08 626 63 00, Fax +46 8 754 56 66.

Munters Corporation 4215 Legion Drive Mason, MI 48854-1036 U.S.A. Phone +1 800-227-2376, Fax +1 517-676-7078

www.munters.us

Australia Munters Pty Limited, Phone +61 2 6025 6422, Brazil Munters Brasil Industria e Comercio Ltda, Phone +55 41 3317 5050, Canada/US MuntersCorporation Mason, MI Phone +1 517 676 7070, China Munters Air Treatment Equipment (Beijing) Co. Ltd, Phone +86 10 80 481 121, Denmark Munters A/S, Phone +45 9862 3311, India Munters India, Phone +91 20 3052 2520, Indonesia Munters, Phone +62 818 739 235, Italy Munters Italy S.p.A., Chiusavecchia, Phone +39 0183 52 11, Japan Munters K.K., Phone +81 3 5970 0021, Korea Munters Korea Co. Ltd., Phone +82 2 761 8701, Mexico Munters Mexico, Phone +52 818 262 54 00, Russia Munters AB, Phone +7 812 448 5740, Singapore Munters Pte Ltd., Phone +65 744 6828, South Africa and Sub-Sahara Countries Munters (Pty) Ltd., Phone +27 11 997 2000, Spain Munters Spain S.A., Phone +34 91 640 09 02, Sweden Munters AB, Phone +46 8 626 63 00, Thailand Munters Co. Ltd., Phone +66 2 642 2670, Turkey Munters Form Endüstri Sistemleri A.Ş, Phone +90 322 231 1338, USA Munters Corporation Mason, MI Phone +1 517 676 7070, Vietnam Munters Vietnam, Phone +84 8 3825 6838, Export & Other countries Munters Italy S.p.A., Chiusavecchia Phone +39 0183 52 11

Aerotech VX36 Fan is developed and produced by Munters Corporation, Mason, Michigan U.S.A. 1-800-227-2376

Catalog Number

Item 36" D.D. VX36FxCP

36" B.D. VX365FxCP Part Name/Description Qty

1 FH2136A FH2136A Fan Housing, Fiberglass 1

2 FH2736 FH2736 Left Tubular Strut, H-type 1

FH2737 FH2737 Right Tubular Strut, H-type 1

3 — FH2821 Bearing Support 1

4 FH2825 FH2820 Motor Support w/Tensioner Bracket 1

5 — Various* Aramid Fiber Belt 1

6 — Various* Propeller Sheave 1

7 — FH2057 Bearing 2

8 — FH2036 Shaft 1

9 FP1013SS FP1014SS Propeller 1

10 Various* Various* Motor: 1

11 — Various* Motor Sheave 1

12 — FH2402K Belt tensioner assembly with 3” idler pulley 1

— FH2406 3” idler pulley only, with bolt 1

— FH2419 Tensioner arm only, aluminum 1

13 FH3336 FH3336 Discharge Cone, Fiberglass 1

14 FH1336 FH1336 Guard 1

15 PZ36 PZ36 Plastic Shutter 1

* Contact office for replacement part numbers for your fan configuration.

Misc. Hardware Packages for 36” fan Fan Installation HP1031

Cone installation HP1034

Cone Guard Installation HP1085

Strut and Motor Mounting, H-type HP1028