w/ oregon approved septic tank & high head pump station d.wright 08/27/12 1 22 float 3 float 2...

8
24" MANWAY 1) MINIMUM DISTANCE BETWEEN TANKS WILL BE FIVE FEET. 2) ELEVATION LEVEL BETWEEN TANKS PER OREGON STATE RULES. 3) PIPE SIZE TO DRAIN FIELD PER OREGON STATE REGULATIONS. 4) ALL TANKS MUST BE WATERTIGHT. 6" 4 * * 40" 3 1.96 GAL PER INCH 18"x1.96= 35.28 gal. DRAW DOWN BASIN FLOAT LEVELS 34" 16" 1 2 46" 4 NO MORE THAN 20% DOSING OF SYSTEM VOLUME PER CYCLE EXAMPLE: 450GPD=90 GALLONS PER CYCLE * 6" 1'-6" 1'-4" 3 NO MORE THAN 20% DOSING OF EXAMPLE: 450GPD = 90 GALLONS PER CYCLE. SYSTEM VOLUME PER CYCLE 4" PUMP SEAT 2" UNION SPLICE BOX LIFT-OUT ROPE *NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED IN OAR 340-071-220(3) *NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS 1 2 CONFIGURATION 1 CP2056A/ECO CONTROL PANEL COMPRESSOR VENT DEP 24.5115V EFFLUENT PUMP STATION 4" VENT 24" MANWAY PER OREGON REGULATIONS FLOAT ASSEMBLY DEP 24.5 115V EFFLUENT PUMP STATION 6' APPROVED FOR USE IN OREGON SEPTIC TANK & VOLUME 4'-6" AS REQUIRED TO DRAIN FIELD ANTI-SIPHON OR CHECK VALVE 4" DISCHARGE OUTLET E50N AEROBIC TREATMENT UNIT 500 GALLON TREATMENT CAPACITY 4'-6 11 16 " 10'-7" 4'-1" 3'-10 1 2 " 22

Upload: trinhkhuong

Post on 27-May-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

24" MANWAY

1) MINIMUM DISTANCE BETWEEN TANKS WILL BE FIVE FEET.2) ELEVATION LEVEL BETWEEN TANKS PER OREGON STATE RULES.3) PIPE SIZE TO DRAIN FIELD PER OREGON STATE REGULATIONS.4) ALL TANKS MUST BE WATERTIGHT.

6"4

*

*

40"3

1.96 GALPER INCH18"x1.96=35.28 gal.

DRAWDOWN

BASINFLOATLEVELS

34"

16"1

2

46"4

NO MORE THAN 20% DOSING OF SYSTEM VOLUME PER CYCLE

EXAMPLE: 450GPD=90GALLONS PER CYCLE

*

6"

1'-6"

1'-4"

3

NO MORE THAN 20% DOSING OF

EXAMPLE: 450GPD = 90 GALLONS PER CYCLE. SYSTEM VOLUME PER CYCLE

4" PUMP SEAT

2" UNIONSPLICE BOX

LIFT-OUT ROPE

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED IN OAR 340-071-220(3)*NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS

1

2

CONFIGURATION 1

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

DEP 24.5115V EFFLUENTPUMP STATION

4" VENT

24" MANWAYPER OREGONREGULATIONS

FLOAT ASSEMBLYDEP 24.5 115VEFFLUENT PUMPSTATION

6'

APPROVED FOR USE IN OREGON SEPTIC TANK & VOLUME

4'-6"

AS REQUIRED TO DRAIN FIELDANTI-SIPHON OR CHECK VALVE4" DISCHARGE

OUTLET

E50N AEROBIC TREATMENT UNIT500 GALLON TREATMENT CAPACITY

4'-61116"

10'-7"

4'-1"

3'-1012"

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E50N

DELTA ECOPOD-N 500 GPD UNIT

W/ OREGON APPROVED SEPTIC TANK &DEP24.5115V HIGH HEAD PUMP STATION

08/27/12D.WRIGHT 1 1

22

mkucins
Approved

FLOAT 3FLOAT 2FLOAT 1

22 GALLONS PER INCH

1-1/4" UNION

APPROVEDFILTERPUMP VAULT

4" PUMP SEAT

CONFIGURATION 2

SPLICE BOX

REDUCER BUSHING

APPROVED FOR USE IN OREGON

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED ON OAR 340-071-220 (3) *NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS

DOSING SEPTIC TANK & VOLUME

4" VENT

24" MANWAY

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

E50N AEROBIC TREATMENT UNIT500 GALLON TREATMENT CAPACITY

4'-61116"

10'-7"

4'-1"

3'-1012"

4'-6"

4" DISCHARGEOUTLET

24" MANWAYPER OREGONREGULATIONS

*NOTE: 5' MINIMUM SEPARATION DISTANCE BETWEEN TANKS

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E50N

DELTA ECOPOD 500 GPD UNIT

W/ OREGON APPROVED DOSING SEPTICTANK

08/27/12D.WRIGHT 1 1

23

mkucins
Approved

min 3"

min 3"1000'

500'

100'

30'

MIN.PIPE SIZE

MAX.DISTANCEELEVATION

12 HP

PUMP

PUMP CHART

1 HP

**

*

*

3

100 GALPER CYCLE

BASED ON 500GALLON PUMP

TANK

DRAWDOWN

BASINFLOATLEVELS

*1

2

NO MORE THAN 20%DOSING OF SYSTEM

VOLUME PER CYCLEEXAMPLE: 450GPD=90GALLONS PER CYCLE

4

REFER TO NOTE

DOSING TANK & VOLUMEAPPROVED FOR USE IN OREGON

SPLICE BOX

TO CONTROL PANEL

24" MANWAYPER OREGONREGULATIONS

APPROVED FOR USE IN OREGON SEPTIC TANK & VOLUME

CONFIGURATION 3

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED IN OAR 340-071-220(3)

*NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS*NOTE: THE VOLUME OF THE DOSING TANK WILL BE AS REQUIRED IN OAR 340-071-220(6)

24" MANWAY

CP2056A/ECO CONTROL PANEL COMPRESSOR

4" DISCHARGEOUTLET

4" VENT

E50N AEROBIC TREATMENT UNIT500 GALLON TREATMENT CAPACITY

4'-6"APPROVEDFILTERPUMP VAULT

VENT

4'-61116"

10'-7"

4'-1"

3'-1012"

*NOTE: 5' MINIMUM SEPARATION DISTANCE BETWEEN TANKS

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E50N

DELTA ECOPOD 500 GPD UNIT

W/ OREGON APPROVED SEPTIC TANK &DOSING TANK

08/27/12D.WRIGHT 1 124

mkucins
Approved

24" MANWAY

1) MINIMUM DISTANCE BETWEEN TANKS WILL BE FIVE FEET.2) ELEVATION LEVEL BETWEEN TANKS PER OREGON STATE RULES.3) PIPE SIZE TO DRAIN FIELD PER OREGON STATE REGULATIONS.4) ALL TANKS MUST BE WATERTIGHT.

6"4

*

*

40"3

1.96 GALPER INCH18"x1.96=35.28 gal.

DRAWDOWN

BASINFLOATLEVELS

34"

16"1

2

46"4

NO MORE THAN 20% DOSING OF SYSTEM VOLUME PER CYCLE

EXAMPLE: 450GPD=90GALLONS PER CYCLE

*

6"

1'-6"

1'-4"

3

NO MORE THAN 20% DOSING OF

EXAMPLE: 450GPD = 90 GALLONS PER CYCLE. SYSTEM VOLUME PER CYCLE

4" PUMP SEAT

2" UNIONSPLICE BOX

LIFT-OUT ROPE

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED IN OAR 340-071-220(3)*NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS

1

2

CONFIGURATION 1

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

DEP 24.5115V EFFLUENTPUMP STATION

4" VENT

24" MANWAYPER OREGONREGULATIONS

FLOAT ASSEMBLYDEP 24.5 115VEFFLUENT PUMPSTATION

6'

APPROVED FOR USE IN OREGON SEPTIC TANK & VOLUME

AS REQUIRED TO DRAIN FIELDANTI-SIPHON OR CHECK VALVE4" DISCHARGE

OUTLET

E60N AEROBIC TREATMENT UNIT600 GALLON TREATMENT CAPACITY

4'-61116"

10'-7"

4'-1"

3'-1012"

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E60N

DELTA ECOPOD-N 600 GPD UNIT

W/ OREGON APPROVED SEPTIC TANK &DEP24.5115V HIGH HEAD PUMP STATION

08/27/12D.WRIGHT 1 1

25

mkucins
Approved

FLOAT 3FLOAT 2FLOAT 1

22 GALLONS PER INCH

1-1/4" UNION

APPROVEDFILTERPUMP VAULT

4" PUMP SEAT

CONFIGURATION 2

SPLICE BOX

REDUCER BUSHING

APPROVED FOR USE IN OREGON

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED ON OAR 340-071-220 (3) *NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS

DOSING SEPTIC TANK & VOLUME

4" VENT

24" MANWAY

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

E60N AEROBIC TREATMENT UNIT600 GALLON TREATMENT CAPACITY

4" DISCHARGEOUTLET

24" MANWAYPER OREGONREGULATIONS

4'-61116"

10'-7"

4'-1"

3'-1012"

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E60N

DELTA ECOPOD 600 GPD UNIT

W/ OREGON APPROVED DOSING SEPTICTANK

08/27/12D.WRIGHT 1 1

26

mkucins
Approved

min 3"

min 3"1000'

500'

100'

30'

MIN.PIPE SIZE

MAX.DISTANCEELEVATION

12 HP

PUMP

PUMP CHART

1 HP

**

*

*

3

100 GALPER CYCLE

BASED ON 500GALLON PUMP

TANK

DRAWDOWN

BASINFLOATLEVELS

*1

2

NO MORE THAN 20%DOSING OF SYSTEM

VOLUME PER CYCLEEXAMPLE: 450GPD=90GALLONS PER CYCLE

4

REFER TO NOTE

DOSING TANK & VOLUMEAPPROVED FOR USE IN OREGON

SPLICE BOX

TO CONTROL PANEL

24" MANWAYPER OREGONREGULATIONS

APPROVED FOR USE IN OREGON SEPTIC TANK & VOLUME

CONFIGURATION 3

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED IN OAR 340-071-220(3)

*NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS*NOTE: THE VOLUME OF THE DOSING TANK WILL BE AS REQUIRED IN OAR 340-071-220(6)

24" MANWAY

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

4" DISCHARGEOUTLET

4" VENT

E60N AEROBIC TREATMENT UNIT600 GALLON TREATMENT CAPACITY

APPROVEDFILTERPUMP VAULT

4'-61116"

10'-7"

4'-1"

3'-1012"

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E60N

DELTA ECOPOD 600 GPD UNIT

W/ OREGON APPROVED SEPTIC TANK &DOSING TANK

08/27/12D.WRIGHT 1 1

27

mkucins
Approved

FLOAT 3FLOAT 2FLOAT 1

22 GALLONS PER INCH

1-1/4" UNION

APPROVEDFILTERPUMP VAULT

4" PUMP SEAT

CONFIGURATION 2

SPLICE BOX

REDUCER BUSHING

APPROVED FOR USE IN OREGON

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED ON OAR 340-071-220 (3) *NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS

DOSING SEPTIC TANK & VOLUME

4" VENT

24" MANWAY

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

E75N AEROBIC TREATMENT UNIT750 GALLON TREATMENT CAPACITY

4" DISCHARGEOUTLET

24" MANWAYPER OREGONREGULATIONS

4'-61116"

10'-7"

4'-1"

3'-1012"

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E75N

DELTA ECOPOD 750 GPD UNIT

W/ OREGON APPROVED DOSING SEPTICTANK

08/27/12D.WRIGHT 1 1

29

mkucins
Approved

min 3"

min 3"1000'

500'

100'

30'

MIN.PIPE SIZE

MAX.DISTANCEELEVATION

12 HP

PUMP

PUMP CHART

1 HP

**

*

*

3

100 GALPER CYCLE

BASED ON 500GALLON PUMP

TANK

DRAWDOWN

BASINFLOATLEVELS

*1

2

NO MORE THAN 20%DOSING OF SYSTEM

VOLUME PER CYCLEEXAMPLE: 450GPD=90GALLONS PER CYCLE

4

REFER TO NOTE

DOSING TANK & VOLUMEAPPROVED FOR USE IN OREGON

SPLICE BOX

TO CONTROL PANEL

24" MANWAYPER OREGONREGULATIONS

APPROVED FOR USE IN OREGON SEPTIC TANK & VOLUME

CONFIGURATION 3

*NOTE: THE VOLUME OF THE SEPTIC TANK WILL BE AS REQUIRED IN OAR 340-071-220(3)

*NOTE: ALL EXTERIOR PIPE SIZE AS PER OREGON REQUIREMENTS*NOTE: THE VOLUME OF THE DOSING TANK WILL BE AS REQUIRED IN OAR 340-071-220(6)

24" MANWAY

CP2056A/ECO CONTROL PANEL COMPRESSOR

VENT

4" DISCHARGEOUTLET

4" VENT

E75N AEROBIC TREATMENT UNIT750 GALLON TREATMENT CAPACITY

APPROVEDFILTERPUMP VAULT

4'-61116"

10'-7"

4'-1"

3'-1012"

.

..

REVISION DESCRIPTIONREV. DATE

INFORMATION CONTAINED HEREIN IS CONFIDENTIAL,

SOLELY FOR THE PURPOSE PROVIDED, AND IT IS NOT TO BE DISCLOSED TO

COMPANY CONFIDENTIAL:

IT IS THE PROPERTY OF PENTAIR PUMP GROUP, IT IS TO BE USED

OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF PENTAIR PUMP GROUP.

BY

..

NTS

PLOT SCALE SHEET

OF

DRAWN BY DATE REV

A

DRAWING NUMBER

DEP248A E75N

DELTA ECOPOD 750 GPD UNIT

W/ OREGON APPROVED SEPTIC TANK &DOSING TANK

08/27/12D.WRIGHT 1 1

30

mkucins
Approved