wall c min 38 clear - home - crest precast concrete · 2009-11-18 · scale date drawn by: revision...
TRANSCRIPT
Scale
Date
Drawn By:
Revision
Drawing Number
KGT
Crest Precast, Inc. La Crescent, MN & Barneveld, WI 800-658-9045
Contractor:
Project:
1
Section Thru Box
Typ. Electric Vault (6'-0' Wide x 12'-0" Long x 7'-0" Deep)
13'-0"
7'-0
"
6" 12'-0" 6"13'-0"
6"6'
-0"
6"7'
-0"
Wall A
Wall C
Wal
l B
Wal
l B
12"Ø x 4" Deep Sump
Pulling Irons As Req'd
Top View Base View
Neenah R-1792-JL Min 38" Clear2'-0"
1'-6
"
Dayton-Superior P-525L 2 Ton x 6"
Lifting Anchors 4 Req'd
3'-6
"3'
-6"
#5 Corner Bars @ 6" O.C. - Typ.
2'-0"2'-0"
Ground Rod
Dayton-Superior P-535L 5 Ton W/
P-60 Bar - 4 Req'd
6" 6'-0" 6"#4 Bars @ 12" OCEW
6"7'
-0"
8 1/
2"
Horizontal Bars Long Wall #4 Bars @ 12" O.C.
Verticall Bars All Wall #6 Bars @ 8" O.C. Hold 3" From Bottom
#6 Bars @ 6" OC #6 Bars @ 2" OC
General Notes: • Concrete - 5,000 PSI • HS20 Wheel Load Design • Sumps and pulling irons by Penn Insert • Joint Sealer - EZ-Stick • Optional Waterproof Exterior Walls with TremProof 60 • Covers to be marked - Neenah R-1792-JL • Weights Base - 16,000 Top Section - 18,000 • Options - Ladder Manhole location near wall
Section Thru Box
6" 12'-0" 6"#4 Bars @ 12" OCEW
6"7'
-0"
8 1/
2"
Horizontal Bars Short Wall #5 Bars @ 12" O.C.
Verticall Bars All Wall #6 Bars @ 8" O.C. Hold 3" From Bottom
Ground Rod
#4 Bars @ 12" OCEW
Clea
r 2"
Precast Chimney Blocks
(2) Unistrut P3260 (Typ. Opp Side)
1 1/2" Clear
1'-2
"
Sch 40 Bell End Terminators
Extension Not Standard
Seal BothLips With 1" EZ Stick
38"
10"4
"
8'-2
1/2
"
6'-0" x 12'-0" x 7'-0" Electric Vault