WALL CONNECTOR, 8OA SINGLE PHASE INSTALLATION MANUAL Approved Markets: North America, Japan, Taiwan, South Korea For additional languages, please visit: www.tesla.com/wallconnector

Upload: vunhi

Post on 21-Mar-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

WALL CONNECTOR, 8OA SINGLE PHASE

INSTALLATION MANUAL

Approved Markets: North America, Japan, Taiwan, South Korea

For additional languages, please visit: www.tesla.com/wallconnector

About this Manual...........................2Communications Regulations.................................2Errors or Inaccuracies................................................2Copyrights and Trademarks....................................2

Safety Information..........................3Important Safety Instructions................................ 3Warnings.........................................................................3Cautions..........................................................................3Notes................................................................................4

Specifications................................... 5

Features..............................................6Optional Circuit Ratings........................................... 6Self-Monitoring and Recovery................................6Power Outages.............................................................6Load Sharing.................................................................6

Planning Your Installation............ 7Minimum Requirements............................................ 7Service Wiring.............................................................. 7120V Above Ground................................................... 7Ground Connection.................................................... 7240V Single-Phase..................................................... 7208V 3-Phase Wye-Connected............................. 8240V Three-Phase Delta-Connected.................. 8Determine the Circuit BreakerRequirements................................................................8Choose the Best Location for the WallConnector...................................................................... 9Installation Considerations.................................... 10

Check the Box Contents............. 12

Step-by-Step InstallationInstructions...................................... 14Tools and Materials Required................................ 14Overview of Installation Steps..............................14Install the Low Profile Bracket for Rearor Bottom Entry Wiring...........................................15Install the Top Entry Bracket for TopEntry Wiring................................................................ 16

Prepare for Installation............................................ 17Connect the Wiring...................................................18Set the Operating Current.................................... 20Secure the Cover and Power Up..........................21

Troubleshooting............................22Reset..............................................................................25Questions?...................................................................26

Appendix A: Testing forProper Operation..........................27

Appendix B: OptionalConnection for Load Sharing.. 28Daisy Chaining Multiple Wall Connectors....... 28Example of the Communication Wiring...........29

Charging EquipmentLimited Warranty......................... 30General Terms............................................................30Limits of Liability........................................................31Warranty Enforcement Laws andDispute Resolution.................................................... 31

Contents

Communications Regulations

This device complies with Part 15 of the FCCrules and Industry Canada license-exempt RSSstandard(s). Operation is subject to thefollowing two conditions: (1) This device maynot cause harmful interference and (2) thisdevice must accept any interference received,including interference that may causeundesired operation.

Important: Changes or modifications tothis product not authorized by Teslacould void the FCC compliance.

Errors or Inaccuracies

To communicate any inaccuracies oromissions, or to provide general feedback orsuggestions regarding the quality of thismanual, send an email to:

[email protected]

Copyrights and Trademarks

All information in this document is subject tocopyright and other intellectual propertyrights of Tesla Motors, Inc. and its licensors.This material may not be modified,reproduced or copied, in whole or in part,without the prior written permission of TeslaMotors, Inc. and its licensors. Additionalinformation is available upon request. Thefollowing are trademarks or registeredtrademarks of Tesla Motors, Inc. in the UnitedStates and other countries:

All other trademarks contained in thisdocument are the property of their respectiveowners and their use herein does not implysponsorship or endorsement of their productsor services. The unauthorized use of anytrademark displayed in this document or onthe vehicle is strictly prohibited.

About this Manual

2

Important Safety Instructions

This document contains important instructionsand warnings that must be followed wheninstalling and maintaining the Wall Connector.

Warnings

Warning: Read all the instructions beforeusing this product.

Warning: This device should besupervised when used around children.

Warning: The Wall Connector must begrounded through a permanent wiringsystem or an equipment groundingconductor.

Warning: Do not install or use the WallConnector near flammable, explosive,harsh, or combustible materials,chemicals, or vapors.

Warning: Turn off input power at thecircuit breaker before installing orcleaning the Wall Connector.

Warning: Use the Wall Connector onlywithin the specified operatingparameters.

Warning: Never spray water or any otherliquid directly at the wall mounted controlbox. Never spray any liquid onto thecharge handle or submerge the chargehandle in liquid. Store the charge handlein the dock to prevent unnecessaryexposure to contamination or moisture.

Warning: Stop using and do not use theWall Connector if it is defective, appearscracked, frayed, broken, or otherwisedamaged, or fails to operate.

Warning: Do not attempt to disassemble,repair, tamper with, or modify the WallConnector. The Wall Connector is not userserviceable. Contact Tesla for any repairsor modification.

Warning: When transporting the WallConnector, handle with care. Do notsubject it to strong force or impact orpull, twist, tangle, drag, or step on theWall Connector, to prevent damage to itor any components.

Warning: Do not touch the WallConnector’s end terminals with fingers orsharp metallic objects, such as wire, tools,or needles.

Warning: Do not forcefully fold or applypressure to any part of the WallConnector or damage it with sharpobjects.

Warning: Do not insert foreign objectsinto any part of the Wall Connector.

Warning: Use of the Wall Connector mayaffect or impair the operation of anymedical or implantable electronic devices,such as an implantable cardiacpacemaker or an implantable cardioverterdefibrillator. Check with your electronicdevice manufacturer concerningtheeffects that charging may have onsuch electronic devices before using theWall Connector.

Cautions

Caution: Do not use private powergenerators as a power source forcharging.

Caution: Incorrect installation and testingof the Wall Connector could potentiallydamage either the vehicle’s Batteryand/or the Wall Connector itself. Anyresulting damage is excluded from theNew Vehicle Limited Warranty and theCharging Equipment Limited Warranty.

Caution: Do not operate the WallConnector in temperatures outside itsoperating range of -22°F to 122°F (-30°Cto +50°C).

Safety Information

Safety Information 3

Notes

Note: Ensure that the Wall Connector’scharging cable is positioned so it will not bestepped on, driven over, tripped on, orsubjected to damage or stress.

Note: Do not use cleaning solvents to cleanany of the Wall Connector’s components. Theoutside of the Wall Connector, the chargingcable, and the connector end of the chargingcable should be periodically wiped with aclean, dry cloth to remove accumulation ofdirt and dust.

Note: Be careful not to damage the circuitboards or components during installation.

Safety Information

4

The maximum power rating for the Wall Connector is 20 kW or 80A at 250V AC single-phasepower.

Description Specifications

Voltage and Wiring 208V or 240V AC single-phase: L1, L2, and earth

Current Maximum output: 80A, 72A, 64A, 56A, 48A, 40A, 36A,32A, 28A, 24A, 20A, 16A, 12A

Frequency 50 to 60 Hz

Cable Length 8.5' (2.6 m) and 24' (7.4 m)

Wall Connector Dimensions Height: 15.0" (380 mm)

Width: 6.3" (160 mm)

Depth: 5.5" (140 mm)

Top Entry Bracket Dimensions Height: 10.8" (275 mm)

Width: 5.1 " (130 mm)

Depth: 2.0" (50 mm)

Weight (including bracket) 20 lb (9 kg)

Operating Temperature -22°F to 122°F (-30°C to 50°C)

Storage Temperature -40°F to 185°F (-40°C to 85°C)

Enclosure Rating Type 3R

Agency Approvals cULus listed for United States and Canada under filenumber E354307, FCC Part 15.

Ventilation Not Required

Specifications

Specifications 5

Optional Circuit Ratings

Use a single-phase circuit breaker rated for100A per phase to obtain the fastest charging.In certain installation locations, this level ofpower isn’t readily available. Therefore, youcan adjust the circuit breaker rating on theWall Connector from 15A to 100A (refer to Setthe Operating Current on page 20).

Note: Tesla vehicles must be configured withoptional onboard charging equipment toaccept higher amperages. Contact Tesla if youhave questions about the onboard chargingcapabilities of your vehicle.

Self-Monitoring and Recovery

The Wall Connector has a ground monitoringcircuit that continuously checks for thepresence of a safe ground connection andautomatically recovers from faults. Manualtesting and resetting is not required.

Temporary problems such as ground faults orutility power surges are overcomeautomatically. If a residual current fault occursthat interrupts charging, the Wall Connectorautomatically tries to clear the fault and re-attempt charging.

If the problem is immediately sensed a secondtime, the Wall Connector waits 15 minutesbefore trying to charge. This process repeats 4times and if all attempts are unsuccessful,power is removed and no further attempts aremade. In this case, you will see a red error lighton the front panel (refer to Troubleshootingon page 22). It is recommended that whenyou see a red error light, you power off theWall Connector by switching off the upstreamcircuit breaker, and then power it back onagain.

The Wall Connector can alternatively be resetwhen a red error light is encountered usingthe RESET button (refer to Reset on page25).

Power Outages

If a power outage occurs, the Wall Connectorautomatically resumes charging when poweris restored. If the charging cable is pluggedinto the vehicle when power is restored, thelights blink and the unit does not energize thecharging cable for approximately 15 secondsto three minutes. This prevents the utility gridfrom experiencing a large surge when power isrestored and allows vehicles to begin drawingcurrent at random times, rather than all atonce.

Load Sharing

The Wall Connector provides the capability towire 4 Wall Connectors to a single circuit,giving vehicle owners reassurance that theycan charge multiple vehicles at home (refer to Appendix B: Optional Connection for LoadSharing on page 28).

Features

6

Minimum Requirements

Installation of the Wall Connector requires thatyou:

• Calculate the existing electrical load todetermine the maximum operatingcurrent.

• Calculate the distance to ensure minimalvoltage drop.

• Obtain any necessary permits from thelocal authority that has jurisdiction andconfirm that the follow-up inspection hasbeen scheduled by an electrician after theinstallation is complete.

• Use only copper conductors.• Use conductors that are sized in

accordance with local wiring regulations.The selected cable must be able to sustainperiods of constant load of up to themaxium amperage selected by theelectrician.

• Use protective devices. The circuitprotection device chosen mustincorporate a suitable residual-currentdevice (RCD) and overcurrent protectionin relation to the electrical load selected.

Note: Consult with an electrician to ensurethat the installation meets local regulations.

Service Wiring

120V Above Ground

Warning: The Wall Connector is a single-phase device. Do not connect all threephases of a three-phase feed.

Warning: Before installing the WallConnector, identify the type of utilityservice connection available on site. If youare unsure about the type of connectionavailable at the service panel, consult anelectrician, or contact Tesla for assistance.

Caution: The two phases used must eachmeasure 120V to neutral. Earth groundmust be connected to neutral at only onepoint, usually at the breaker panel.

Caution: If a 240V three-phase feed isfrom a Delta-connected secondary, theleg used must have a center tap. Thiscenter tap must be grounded. Only thetwo phases on either side of the center-tapped leg can be used.

Only three wires are connected, but care mustbe taken that the service transformersecondary connection is definitely known, andthat the three wires from the main circuitbreaker panel are correctly connected andlabeled.

Note: The L1, L2, and ground outputs labeledon the illustrations correspond to the inputson the Wall Connector.

Ground Connection

Always connect the Neutral at the service toEarth Ground. Ground fault protection is notpossible unless the Neutral (center tap on theservice transformer) is connected to an EarthGround. If ground is not provided by theelectrical service, you must install a groundingstake nearby. the grounding stake must beconnected to the ground bar in the mainbreaker panel, and Neutral connected toGround at that point.

240V Single-Phase

L2

L1

120V

120V

GND

240VNEUTRAL(NOT USED)

Note: Illustrations in this document are fordemonstration purposes only.

Planning Your Installation

Planning Your Installation 7

208V 3-Phase Wye-Connected

With a Wye-connected secondary, any two ofthe legs can be used to provide 208V to theWall Connector. For example, L1 and L2, or L1and L3, or L2 and L3. The two used phasesmust each measure 120V to neutral.

Note: A current-carrying neutral is notrequired.

120V 208V

120V

L1

NEUTRAL(NOT USED)

L3 (NOT USED)

L2 (NOT USED)

GND

Caution: The unused leg (L3 in theillustration) must remain open. Do notconnect to a neutral bar, or to earthground.

Caution: The center point of the threephases (normally used as neutral) mustbe grounded to earth at only one point.This is usually at the breaker panel.

240V Three-Phase Delta-Connected

With the delta connection, one leg must becenter tapped, and only the two phases oneither side of the center tap can be used. Thetwo used phases must each measure 120V toneutral.

Consult the transformer manufacturer’sliterature to verify that the single leg cansupply the required power.

Note: The Wall Connector’s contactor closesonly if it detects the presence of an earthground wire connected to a neutral point onthe transformer secondary.

L1

L2

GND

120V

120V

240V

L3 (NOT USED)

NEUTRAL(NOT USED)

Caution: The third line (L3 in theillustration) of the delta is 208V, withrespect to neutral, and is sometimesreferred to as a “stinger.” Do not use thisthird line.

Caution: Do not use a three-phase delta-connected transformer secondarywithout a center tap on one leg. Noneutral point is available for the requiredearth ground connection.

Determine the Circuit BreakerRequirements

To determine the type of upstream circuitbreaker you need, examine the distributionpanel or circuit breaker box to identify theamperage available at the installation site.

Planning Your Installation

8

The Wall Connector has an internal rotaryswitch that allows you to adjust its operatingcurrent (refer to Set the Operating Current onpage 20). The circuit breaker should berated for the continuous current of: 12, 16, 20,24, 28, 32, 36, 40, 48, 56, 64, 72, or 80A.

Choose the Best Location for theWall Connector

Determine the parking location of the vehicleto ensure that the charge cable reaches thecharge port. The Wall Connector should belocated:

• In an enclosed garage, typically on thevehicle's charge port side.

• In a well-ventilated area. Avoid installationin an enclosed box, or adjacent to hotappliances.

• 4 ft (1.2 m) above the floor.• 8 in (190 mm) from any obstructions to

allow for cable looping.

Note: The Wall Connector is approved foroutdoor use, but it is not designed forcomplete immersion in liquid. Protection fromrain is recommended but not required.

Planning Your Installation

Planning Your Installation 9

Installation Considerations

Three methods are available to install the Wall Connector. The location of the conduit determineswhich installation method to follow. If the conduit runs along the floor or low on the wall, use thebottom entry configuration. If the conduit comes from inside the wall, use the rear entryconfiguration. If the available conduit comes from the ceiling, use the top entry installation.

Note: Throughout the manual, “conduit” is used as the standard term for the protective tubingthat houses the service wiring. In regions where conduit is not used (Europe for example), a cablecomprised of service wiring enclosed in a protective jacket may be substituted for conduit ifallowed by local regulations.

Here are some additional guidelines:

• Conduit openings are sized for 1" (25 mm) conduit.• Conduit needs to meet all local regulations.• Use an appropriate circuit breaker.• To keep the housing weatherproof, use cable glands.• Use a UL approved conduit connector to ensure proper seal.

Bottom or Rear Entry

Planning Your Installation

10

Top Entry

Planning Your Installation

Planning Your Installation 11

The shipping box contains parts for all installation methods, as well as this manual. If any parts aredamaged or missing, contact Tesla (refer to Questions? on page 26).

Note: Not shown is the supplied cardboard template.

1 2 3 4

5 6 7 8 9

10 11 12 13 14

Item Description (Quantity)

1 Wall Connector

2 Top entry bracket*

3 Low profile bracket **

4 Low profile bracket screws (2) **

5 Bottom or rear entry power conduit plug

6 Bottom or rear entry signal conduit plug

7 Top entry signal conduit plug*

8 Top entry power conduit plug*

9 Bottom conduit sealing gasket*

10 Top bracket-to-housing screw covers (2)

11 Bottom bracket-to-housing screw covers (2)

Check the Box Contents

12

Item Description (Quantity)

12 Bottom bracket-to-housing screws (2)

13 Top bracket-to-housing screws (2)

14 Top entry bracket mounting screws (2)*

* Items used in only top entry installations.

** Items used in only bottom or rear entry installations.

Check the Box Contents

Check the Box Contents 13

Tools and Materials Required

Before installing the Wall Connector, gather the following tools and materials:

• Pencil or marker

• Hole punch (optional, to push through cardboard template)

• Wire stripper

• Voltmeter or digital multimeter (to measure AC voltage at the installation site)

• Phillips screwdriver

• Small flathead screwdriver

• Large flathead screwdriver (optional, to remove plastic knock-outs)

• T20 security pin Torx driver

• T10 Torx driver

• M20 and M32 cable glands (also known as sealing hubs)

• Ferrules (the diameter of the ferrule depends on the diameter of the power wiring and the

construction)

• Wiring (use twisted pair communication cable 18AWG (Max diameter: .04 in (1.02 mm); Max

cross-sectional area:.03 in2 (0.82 mm2) for a maximum of 49 ft (15 m) between Wall

Connectors)

• Level

• Machine drill

• Torque driver (for terminal block connections)

Overview of Installation Steps

Warning: After you run service wiring to the installation site using metal flame retardantconduit, install the appropriate upstream circuit breaker, TURN OFF AND VERIFY POWER ISOFF BEFORE CONTINUING.

Then follow these steps to install the Wall Connector:

• Install the Low Profile Bracket for Rear or Bottom Entry Wiring on page 15• Install the Top Entry Bracket for Top Entry Wiring on page 16• Prepare for Installation on page 17• Connect the Wiring on page 18• Set the Operating Current on page 20• Secure the Cover and Power Up on page 21

Step-by-Step Installation Instructions

14

Install the Low Profile Bracket forRear or Bottom Entry Wiring

Use the low profile bracket, shown below, towire the Wall Connector from the rear orbottom.

1. Use the low profile bracket as a guide tomark the location on the wall for themounting screws.

• Use a level to ensure that the marksare perfectly vertical.

• Space the holes 4.5" (114 mm) apart.

• For U.S.A. installations, position thebracket so that the Wall Connector islocated at a maximum of 60" (150 cm)from floor level. The minimum heightis 18" (45 cm) if mounting indoors,

and 48" (122 cm) if mountingoutdoors.

• If using rear entry conduit, use at leastone set of the edge mounting holes sothat the conduit does not interferewith the wall stud.

• If using bottom entry conduit, use thecenter two mounting holes.

Note: Ensure that the minimum andmaximum height of the bracket is carefullyselected. It should be installed out of theway of any reasonably foreseeableimpacts.

2. Attach the bracket using fasteners thatare appropriate for the type of wallmaterial, drilling pilot holes if necessary.Use the supplied screws only if mountingthe bracket directly to a wooden stud. Ifmounting to another type of wall (hollow,masonry, etc.), use fasteners that are longenough to securely anchor the WallConnector and can hold at least 80 lb (36kg).

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 15

Install the Top Entry Bracket for TopEntry Wiring

The top entry bracket enables you to route theservice wiring into the Wall Connectorenclosure from the top of the enclosure, asshown below.

1. Use the cardboard template and a level asa guide to mark the location on the wallfor the mounting screws.

• Use a level to ensure that the marksare perfectly vertical.

• Space the holes 6.1" (155 mm) apart.• Position the bracket so that the Wall

Connector is located at a maximum of60" (150 cm) from floor level. Theminimum height is 18" (45 cm) ifmounting indoors, and 48" (122 cm) ifmounting outdoors.

Note: Ensure that the minimum andmaximum height of the bracket is carefullyselected. It should be installed out of theway of any reasonably foreseeableimpacts.

2. (Optional) There are two additionalmounting holes. To use these holes, use aflat-head screwdriver to knock-out theplastic that is closing the holes. Theseholes are spaced 2.75" (70 mm) apart.

3. Attach the bracket using fasteners thatare appropriate for the type of wallmaterial, drilling pilot holes if necessary.Use the supplied screws only if mountingthe bracket directly to a wooden stud. Ifmounting to another type of wall (hollow,masonry, etc.), use fasteners that are longenough to securely anchor the WallConnector and can hold at least 80 lb (36kg).

Step-by-Step Installation Instructions

16

Prepare for Installation

Follow these instructions to remove the coverand route the service wiring into the WallConnector.

1. Use a T10 Torx driver to remove the screwat the bottom of the outer cover. Carefullydisengage the snaps on the sides and topusing a flathead screwdriver andcompletely remove the cover. Save thescrew and cover for reassembly.

2. Use a T20 security pin Torx driver toremove the six screws on the sealingcover. Carefully remove the sealing coverand disconnect the ribbon cable. Save thescrews and cover for reassembly.

Caution: Do not allow the sealingcover to hang from the ribbon cable.Doing so can damage the ribboncable or its connectors.

3. For top entry configuration, install thewiring to the terminal block in the topentry bracket as shown in Connect theWiring on page 18, then return to thissection and proceed to the next step. Forback or bottom entry configurations, skipto the next step.

4. Place and hold the Wall Connector on thebracket, ensuring that all four mountingtabs are properly aligned.

5. Use a T20 Torx driver to install the twotop housing mounting screws. Push thecosmetic screw covers into place.

6. Use a T20 Torx driver to install the twobottom housing mounting screws. Pushthe cosmetic screw covers into place.

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 17

Connect the Wiring

Note: Consult with your local electrician orrefer to your local code for proper wire sizingappropriate for the currents in your WallConnector.

Note: It is the installer's responsibility toidentify whether additional grounding isrequired to ensure that local regulations aremet. Grounding must be installed at the powersource and not at the cable entry to the WallConnector.

Warning: Do not connect service wiringuntil you have read and fully understandthe concepts described in Service Wiringon page 7.

1. Turn off the power.

Warning: RISK OF ELECTRIC SHOCK!Before continuing, use a voltmeter toensure the power is off by confirmingthat NO VOLTAGE is present at theservice wiring or terminals.

2. For top entry installation, pull the servicewiring into the top entry bracket or theWall Connector. Use a 1" (25 mm) cablegland to seal the power conduit or cable.For 80A operation, use 3AWG 167°F(75°C) rated copper wire or follow localregulations.

Note: The meaning of wiring colors mightvary from country to country. Follow allapplicable national and local regulationsconcerning wiring color codes.

The following illustration shows anexample of the wiring for the top entrybracket.

The following illustration shows anexample of the wiring for the low profilebracket.

3. Strip the service wires going to theterminal block on the top entry bracket3/4" (18 mm). Ferrules are recommended.

Note: For top entry installation, theflexible pre-installed wires that go fromthe top entry bracket to the housing arealready terminated and do not need to bestripped.

4. Lead the preconnected service wires inthe main housing and connect thepreconnected service wires to the mainterminal block with L1 (or line), L2 (orneutral), and ground wires going to thelocations shown in the followingillustration.

Step-by-Step Installation Instructions

18

Caution: Cut each of the wire strandsand insert them fully into each theterminal block.

Note: To ensure proper operation, verifythat neutral is connected to the neutralline inside the circuit breaker box or themain electrical panel.

5. Tighten the terminal block to therecommended torque:

• 35 in-lb (4.0 N-m) for the terminalblock on the top entry bracket.

• 33 in-lb (3.8 N-m) for the terminalblock in the main housing.

• 18 in-lb (2.0 N-m) for the groundterminal block in the main housing.

6. Check for miswiring using a multimeterand verify that there are no shorts beforeturning the upstream circuit breaker ON.

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 19

Set the Operating Current

Follow these instructions to configure the DIPswitch. The following illustration shows anenlarged view of the DIP and rotary switches.

Warning: Power MUST remain OFF beforesetting or changing the DIP or rotaryswitches. Changing these switches withthe power ON will not be recognized bythe system and is dangerous due to therisk of electric shock.

1. Turn OFF power.2. Use a non-conductive object to adjust the

DIP switch settings:

• Switch Position 1:

• For a Line to Line connection(240V or less) set the DIP switchDOWN.

• For a Line to Neutral connection(greater than 240V) set the DIPswitch to UP (the ON position).

Warning: Before you set the DIPswitches, confirm which type ofinput service the utility provides.

• Switch Position 2:

• DIP Switch Position 2 shouldalways be in the UP position.

Wiring/Connection DIP SwitchPosition

Line to Neutral(greater than240V)

Line to Line (240Vor less)

3. Set the rotary switch for the appropriatecurrent setting supported by your circuitbreaker. Typical circuit breaker ratings are:15A, 20A, 25A, 30A, 35A, 40A, 45A, 50A,60A, 70A, 80A, 90A, and 100A.

Use a small flathead screwdriver to adjustthe rotary switch to the appropriate circuitbreaker capability setting. Thecorresponding rotary switch settings forthe typical circuit breakers are shown inthe following table:

Step-by-Step Installation Instructions

20

RotarySwitchPosition

MaximumOutputCurrent

CircuitBreaker

0 Test mode N/A

1 12A 15A

2 16A 20A

3 20A 25A

4 24A 30A

5 28A 35A

6 32A 40A

7 36A 45A

8 40A 50A

9 48A 60A

A 56A 70A

B 64A 80A

C 72A 90A

D 80A 100A

E Not a validselection

N/A

F Slave mode N/A

4. Reattach the ribbon cable to the sealingcover.

5. Reinstall the sealing cover. Use a T20security pin Torx driver to lightly securethe sealing cover by installing only the topscrew.

6. Turn ON power.7. If the installation is successful, the LEDs

briefly sequentially illuminate green with apattern that ends with the top green LEDstaying solid ON. If there is a solid orflashing red LED, refer to Troubleshootingon page 22 and resolve the error beforeyou continue.

Note: To review the pattern of blinkinglights, press and hold the RESET buttonfor 5 seconds.

8. Turn OFF power.9. Write the contact information of the

installer on the label on the inside of theWall Connector.

Secure the Cover and Power Up

1. Use a T20 security pin Torx driver toinstall the remaining screws on the sealingcover. Ensure that the cover is properlyaligned before fully tightening the screws.

2. Attach the outer cover to the sealingcover starting with the latch at the top.Engage the snaps on the sides and alignthe mounting tab with the housing at thebottom.

3. Use a T10 Torx driver to install the screwthat secures the bottom of the outer coverto the housing.

4. Close any unused openings with powerand signal conduit plugs.

Note: There should not be any visibleopenings to the inside of the WallConnector, and the Wall Connector shouldbe completely sealed from theenvironment.

5. Turn ON the power. The installation iscorrect if the LEDs go through a sequenceof flashing, ending with the top GreenLEDs staying solidly ON. If there is a solidor flashing Red LED, resolve the errorbefore you continue (refer to Troubleshooting on page 22).

Note: To review the pattern of blinkinglights, press and hold the Reset button for5 seconds.

6. Attempt to charge the vehicle to ensurethe Wall Connector is operating correctlyand charging at the selected operatingcurrent. For instructions on how to charge,refer to the owner information providedwith the vehicle.

Step-by-Step Installation Instructions

Step-by-Step Installation Instructions 21

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Top lighton

Off Off Notapplicable

Power on. The WallConnector ispowered and instandby but notcharging thevehicle.

Not applicable.

Streaminglights

Off Off Notapplicable

The Wall Connectoris charging thevehicle.

Not applicable.

Streaminglights

1 flash Off Notapplicable

Charging current isreduced due to hightemperaturedetected in theVehicle Connector.

Make sure theconnector is fullyinserted into thecharge inlet in thevehicle's chargingport, is not covered byanything, and there isno heat source isnearby. If the problempersists in normalambient temperatures(under 100°F or38°C), contact Tesla.

Streaminglights

2 flashes Off Notapplicable

Charging current isreduced due to hightemperaturedetected in the wallplug or on the inputterminals to theWall Connector.

If the Wall Conector isplugged into a walloutlet, make sure thatit is fully inserted intothe receptacle, it isnot covered byanything, and there isno heat source nearby.If the Wall Connectoris hard-wired, makesure it is not coveredby anything, andthereis no heat sourcenearby. If the problempersists in normalambient temperatures(under 100°F or38°C), contact Tesla.

Streaminglights

3 flashes Off Notapplicable

Charging current isreduced due to hightemperaturedetected inside theWall Connector.

Make sure the WallConnector is notcovered by anythingand there is no heatsource nearby. If theproblem persists innormal ambienttemperatures (under100°F or 38°C),contact Tesla.

Troubleshooting

22

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Off Off 1 flash After 15minutes andup to 4times

Groundfault. Current isleaking through anunsafe path.Possible Line toground or Neutralto ground fault.

Try again bydisconnecting theWall Connector fromthe vehicle andreconnecting. If theproblem persists, turnOFF the circuitbreaker servicing theWall Connector, wait10 seconds, turn thecircuit breaker ONagain, then tryreconnecting the WallConnector to thevehicle. If the problempersists, contact Tesla.

Off Off 2 flashes After 1minute andup to 4times

No groundconnectiondetected in the WallConnector.

Make sure the WallConnector is properlygrounded. If uncertain,consult yourelectrician to ensureproper grounding atyour circuit breaker orpower distributionbox and thatappropriateconnections are madeto the Wall Connector.

Off Off 3 flashes No Input miswired:possibly Line andNeutral areswapped.

The wiring betweenthe wall power andthe Wall Connectorhas been incorrectlyinstalled. Consult yourelectrician.

Off Off 4 flashes After 1minute andup to 4times

Over or undervoltage protection.

Consult yourelectrician to ensureappropriate voltageon the circuit breakerthat services the WallConnector.

Troubleshooting

Troubleshooting 23

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Off Off 5 flashes After 1minute retry(no limit onretries)

Over currentprotection.

Reduce the vehicle'scharge currentsetting. If the problempersists and theattached vehicle ismanufactured byTesla, contact Tesla. Ifthe problem persistsand If the attachedvehicle is notmanufactured byTesla, contact theoriginal manufacturer.

Off Off 6 flashes After 1minute retry(no limit onretries)

A communicationerror occurredbetween the WallConnector and thevehicle.

If possible, plug thevehicle into anotherWall Connector or aMobile Connector todetermine if thevehicle is able tocommunicate withother chargingequipment. Thencontact Tesla Service.

Top lighton

Off 1 flash No Over temperatureprotection (latch-off)

Make sure the WallConnector, vehicleconnectors, and wallplug (if used) are notcovered by anythingand there is no heatsource nearby. If theproblem persists innormal ambienttemperatures (under100°F or 38°C),contact Tesla.

Top lighton

Off 2 flashes No Non-Tesla vehicleattemptingconnection to non-compatible inputdistribution.

Compatible inputdistributions are:single-phasedistribution or 400V,three-phasedistribution.

Top lighton

Off 3 flashes No Incorrect rotaryswitch setting.

Consult yourelectrician.

Troubleshooting

24

GreenLights

YellowLight

Red Light Auto-Retry What it Means What to Do

Top lighton

Off 4 flashes NotApplicable

Circuit BreakerSharing Network:More than one WallConnector is set toMaster.

Only one WallConnector can be setto a masterconfiguration. Allother linked WallConnectors must beset to slave (positionF). Set one of the WallConnectors to Slave.

Top lighton

Off 5 flashes NotApplicable

Circuit BreakerSharing Network:More than threeWall Connectors areset to Slave.

Move one or moreWall Connectors to adifferent circuit anddisconnect it from thisCircuit BreakerSharing Network.

Top lighton

Off 6 flashes NotApplicable

Circuit BreakerSharing Network:The networked WallConnectors havedifferent maximumcurrent capabilities.

Contact Tesla.

Off Off Solid red No Wall Connectorhardware failure.Possible failuresinclude thefollowing:

• Contactor failed• Self test failed

in CCIDcircuitry

• Other possiblehardwarefailures mightbe MCU,3V3output, orthe thermalsensor.

Contact Tesla.

Reset

If a fault causes a RED error light to illuminate or flash and the fault condition is corrected, you useRESET the Wall Connector to resume normal operation. There are two ways to REST the WallConnector:

• Press the RESET button for two to three seconds until the top lights changes from RED toGREEN. This clears the fault message but does not reboot the Wall Connector.

• In a rare situation, you might need to force the Wall Connector to reboot without recycling theinput power. Hold the RESET button for five seconds. When the top light changes from REDto GREEN, release the RESET button. The top light should continue to illuminate GREEN. If thelight returns to flashing RED, the fault state has not been corrected.

Troubleshooting

Troubleshooting 25

Questions?

• United States and Canada:

[email protected]• +1-650-681-6133

• Mexico

[email protected]• +1-877-798-3752

Troubleshooting

26

1. Turn OFF power.

Warning: RISK OF ELECTRIC SHOCK!Before continuing, use a voltmeter toensure the power is off by confirmingthat NO VOLTAGE is present at theservice wiring or terminals.

2. Use a non-conductive object to adjust theDIP switches to the appropriate gridsetting and circuit breaker sharing setting(refer to Set the Operating Current onpage 20).

3. Use a small flathead screwdriver to set therotary switch to position "0" to put theWall Connector into Test Mode.

Warning: Power MUST remain OFFbefore setting or changing the DIP orrotary switches. Changing theseswitches with the power ON will notbe recognized by the system and isdangerous due to the risk of electricshock.

4. Reattach the ribbon cable to the sealingcover.

5. Use a T20 security pin Torx driver tolightly secure the sealing cover byinstalling only the top screw.

6. Turn ON the circuit breaker.7. Watch for any Red LEDs to be ON after a

sequence of LED display; if so, there is afault in the installation.

8. Listen for the click of a contactor or relayclosing and opening.

9. Watch for Green streaming LEDs (for 5seconds).

LEDs will revert to top Green LED ON andRed LEDs flashing (3 times).

Note: To review the pattern of blinkinglights, press and hold the Reset button for5 seconds.

10. Turn OFF the circuit breaker.11. Remove the sealing cover screw, sealing

cover. Disconnect the ribbon cable.

Caution: Do not allow the sealingcover to hang from the ribbon cable.Doing so can damage the ribboncable or its connectors.

12. Reposition the rotary switch to theappropriate setting (refer to Set theOperating Current on page 20).

13. Reattach the ribbon cable to the sealingcover.

14. Replace all the screws and reinstall theouter cover (refer to Secure the Cover andPower Up on page 21).

Appendix A: Testing for Proper Operation

Appendix A: Testing for Proper Operation 27

The Wall Connector includes a featurewhereby Wall Connector to Wall Connectorcommunication allows you to split themaximum available load over a maximum of 4Wall Connectors. The wire used for this localnetwork must share the main power cableconduit or be housed in a separate conduit. Inother words, the high voltage wires must bebranched to a junction box from eachindividual unit.

Warning: When load sharing, high voltage(L1, L2, Neutral, Earth) cabling must bespliced in a separate NEMA ratedenclosure.

Warning: A 600V rated, minimum 18 AWG(1 mm), 2 conductor shielded twisted-pairwire must be used when creating a localnetwork for load sharing.

Note: Take additional precautions intoconsideration to prevent water ingress at theWall Connectors when installing themoutdoors.

Note: Consult with an electrician to ensurethat the installation meets local regulations.

Distribution Panel

Junction Box

Surface-mounted conduit

Master WC Slave WC 1 Slave WC 2 Slave WC 3

Line 1Line 2GroundCOMM

Terminal Block1 incoming terminal2-4 outgoing terminals

Daisy Chaining Multiple WallConnectors

Each Wall Connector has one terminal blockdedicated for the communication wiring asshown below. The left hand side of theterminal block is the input terminal and theright hand side the output terminal.

1. Form a daisy-chained network byconnecting the cables from OUT to IN andalways from positive to positive andnegative to negative between each of theparticipating Wall Connectors (refer to Example of the Communication Wiring onpage 29).

• The signal wires between each WallConnector should run in signalconduit. Use a 1/2" (13 mm) ULapproved conduit hub to seal thesignal conduit opening.

• If the signal wire is routed in thepower conduit with the power wires,the insulation rating of the signal wireshould be equal to or greater thanthat of the power wires.

• The maximum distance between WallConnectors is 49 ft (15 m).

• Use twisted pair cable for the signalwire.

2. Set one Wall Connector as the master bysetting the Rotary Switch Position from 1through D, depending on the maximumavailable output current. Set up to 3 WallConnectors as slaves by setting the Rotary

Appendix B: Optional Connection for Load Sharing

28

Switch Positions to F. In the load sharingnetwork, only one unit can be designatedas the master (refer to Set the OperatingCurrent on page 20).

3. Confirm that the load sharing network isproperly installed by observing the LEDindicators in the Wall Connector. Whenstarting up the circuit breaker for the firsttime, green lights turning ON for 5seconds indicate a proper installation. Thefinal display is:

GreenLights

YellowLight

RedLight

What itMeans...

On (topandbottom)

Off Off Masterunit

On(bottom)

Off Off Slave unit

Example of the Communication Wiring

Wall Connector 1MASTER

Wall Connector 2SLAVE

Wall Connector 3SLAVE

Wall Connector 4SLAVE

8

Rotary Switch

D+ D- D+ D-In Out

FRotary Switch

D+ D- D+ D-In Out

FRotary Switch

D+ D- D+ D-In Out

FRotary Switch

D+ D- D+ D-In Out

Appendix B: Optional Connection for Load Sharing

Appendix B: Optional Connection for LoadSharing

29

General Terms

Subject to the exclusions and limitationsdescribed below, the Charging EquipmentLimited Warranty covers the refund, repair orreplacement necessary to remedy anymanufacturing defects in Tesla manufacturedand supplied Wall Connector that occur undernormal use for a period of 48 months, andMobile Connector or charging adapter thatoccur under normal use for a period of 12months from the date of invoice to thecustomer. Any Tesla connector or adapterincluded in the initial purchase and delivery ofa Tesla vehicle by Tesla is covered under theBasic Vehicle Limited Warranty section of theNew Vehicle Limited Warranty for 4 years or50,000 miles (80,000 km), whichever comesfirst, subject to the terms and conditions ofthe New Vehicle Limited Warranty.

This Charging Equipment Limited Warrantydoes not cover any damage or malfunctiondirectly or indirectly caused by, due to, orresulting from, normal wear or deterioration,abuse, misuse, negligence, accident, lack of orimproper use, maintenance, storage ortransport, including, but not limited to, any ofthe following:

• Failure to follow the instructions,maintenance and warnings published inthe documentation supplied with yourTesla connector or adapter;

• External factors, including but not limitedto, objects striking the Tesla connector oradapter, faulty or damaged electricalwiring, junction boxes, circuit breakers,receptacles or power outlets, theenvironment or an act of God, including,but not limited to, fire, earthquake, water,lightning and other environmentalconditions;

• General appearance or damage to paint,including chips, scratches, dents andcracks;

• Failure to contact Tesla upon discovery ofa defect covered by this ChargingEquipment Limited Warranty;

• Any repair, alteration or modification tothe Tesla connector or adapter or anypart, or the installation or use of any partsor accessories, made by a person orfacility not authorized or certified to doso;

• Lack of or improper repair ormaintenance, including use of non-genuine Tesla accessories or parts; and

• Use for commercial purposes.

Although Tesla does not require you toperform all maintenance, service or repairs ata Tesla Service Center or Tesla authorizedrepair facility, this Charging EquipmentLimited Warranty may be voided, or coveragemay be excluded, due to lack of or impropermaintenance, service or repairs. Tesla ServiceCenters and Tesla authorized repair facilitieshave special training, expertise, tools andsupplies with respect to Tesla connectors andadapters and, in certain cases, may employthe only persons, or be the only facilitiesauthorized or certified to work on Teslaconnectors and adapters. Tesla stronglyrecommends that you have all maintenance,service and repairs done at a Tesla ServiceCenter or Tesla authorized repair facility inorder to avoid voiding, or having coverageexcluded under, this Charging EquipmentLimited Warranty.

Charging Equipment Limited Warranty

30

Limits of Liability

This Charging Equipment Limited Warranty isthe only express warranty made in connectionwith your Tesla connector or adapter. Impliedand express warranties and conditions arisingunder applicable local laws, federal statute orotherwise, in law or in equity, if any, including,but not limited to, implied warranties andconditions of merchantability or merchantablequality, fitness for a particular purpose,durability, or those arising by a course ofdealing or usage of trade, are disclaimed tothe fullest extent allowable by your local law,or limited in duration to the term of thisCharging Equipment Limited Warranty. To thefullest extent allowable by your local law, theperformance of necessary repairs and/orreplacement of new, reconditioned, orremanufactured parts by Tesla for the covereddefects is the exclusive remedy under thisCharging Equipment Limited Warranty or anyimplied warranties. To the maximum extentpermissible under your local law, liability islimited to the reasonable price for repair orreplacement of the applicable Tesla connectoror adapter, not to exceed the manufacturer’ssuggested retail price. Replacement may bemade with parts of like kind and quality,including non-original manufacturer’s parts, orreconditioned or remanufactured parts, asnecessary.

Tesla shall not be liable for any defects underthis Charging Equipment Limited Warrantythat exceed the fair market value of theapplicable Tesla connector or adapter at thetime immediately preceding the discovery ofthe defect. In addition, the sum of all benefitspayable under this Charging EquipmentLimited Warranty shall not exceed the priceyou paid for the applicable Tesla connector oradapter.

Tesla does not authorize any person or entityto create for it any other obligations or liabilityin connection with this Charging EquipmentLimited Warranty. The decision of whether torepair or replace a part or to use a new,reconditioned or remanufactured part will bemade by Tesla, in its sole discretion.

To the maximum extent permissible underlocal law, Tesla hereby disclaims any and allindirect, incidental, special and consequentialdamages arising out of, or relating to, theTesla connector or adapter, including, but notlimited to, transportation to and from a TeslaAuthorized Service Center, loss of the Teslaconnector or adapter, loss of vehicle value,loss of time, loss of income, loss of use, loss ofpersonal or commercial property,inconvenience or aggravation, emotionaldistress or harm, commercial loss (includingbut not limited to lost profits or earnings),towing charges, bus fares, vehicle rental,service call charges, gasoline expenses,lodging expenses, damage to tow vehicle, andincidental charges such as telephone calls,facsimile transmissions, and mailing expenses.

The above limitations and exclusions shallapply whether your claim is in contract, tort(including negligence and gross negligence),breach of warranty or condition,misrepresentation (whether negligent orotherwise) or otherwise at law or in equity,even if Tesla is advised of the possibility ofsuch damages or such damages arereasonably foreseeable.

Nothing in this Charging Equipment LimitedWarranty shall exclude, or in any way limit,Tesla’s liability, for death or personal injurysolely and directly caused by Tesla’snegligence or that of its employees, agents orsub-contractors (as applicable), fraud orfraudulent misrepresentation, or any otherliability to the extent the same is proven in acourt of competent jurisdiction in a finalnonappealable judgment and may not beexcluded or limited as a matter of local law.

Warranty Enforcement Laws andDispute Resolution

To the fullest extent allowed by local law, Teslarequires that you first provide writtennotification of any manufacturing defectwithin a reasonable time, and within theapplicable coverage period specified in thisCharging Equipment Limited Warranty, andallow Tesla an opportunity to make anyneeded repairs before submitting a dispute toour dispute settlement program (describedbelow). Please send written notification ondispute resolution to the following address:

Charging Equipment Limited Warranty

Charging Equipment Limited Warranty 31

United States:Tesla Motors, Inc.3500 Deer Creek RoadPalo Alto, California 94304Telephone: 1-877-798-3752

Canada:Tesla Motors Canada ULC1325 Lawrence Avenue EastToronto, ON M3A 1C6Telephone: 1-877-798-3752

Please include the following information:

• Tesla connector or adapter invoice date;• Your name and contact information;• Name and location of the Tesla Store

and/or Tesla Service Center nearest you;• Description of the defect; and• History of the attempts you have made

with Tesla to resolve the concern, or ofany repairs or services that were notperformed by Tesla.

In the event any disputes, differences orcontroversies arise between you and Teslarelated to this Charging Equipment LimitedWarranty, Tesla will explore all possibilities foran amicable settlement. In case an amicablesettlement is not reached, Tesla offers adispute settlement program through:

NATIONAL CENTER FOR DISPUTESETTLEMENT (“NCDS”)P.O. Box 526Mt. Clemens, MI 480461-866-629-3204

Tesla requires that you submit your dispute toour dispute settlement program and wait for adecision to be issued prior to pursuing anyremedy under federal or state laws (including15 U.S.C. Section 2310 or California Civil CodeSection 1793.22(b)), although you may beentitled to pursue a remedy withoutsubmitting under certain state laws or if youpursue any rights or remedies not created bythese laws. This dispute settlement programadministered by NCDS is free of charge to youand is conducted by local NCDS professionalswho are trained and experienced in mediationand arbitration.

NCDS resolves disputes involving thisCharging Equipment Limited Warranty whicharise during the applicable warranty periodspecified in this Charging Equipment LimitedWarranty. You must file a request forarbitration with NCDS within 60 days (or 6months in certain jurisdictions) of theexpiration of the applicable warranty period,provided you sent written notice to Tesla ofthe alleged defect was brought to theattention of Tesla during the applicablewarranty period.

To initiate arbitration, you must contact NCDSat 1-866-629-3204 or P.O. Box 526, Mt.Clemens, MI 48046, and complete an NCDScustomer claim form and mail it to NCDS.Please also provide a copy of your writtennotification sent to Tesla and/or allinformation required in such notificationspecified above, your desired resolution, andall receipts if requesting reimbursement. Uponreceipt of your request, NCDS will contact youregarding the status of your case and provideyou with additional details about the program.

When NCDS receives your request, it will beforwarded to Tesla for response. Afteranalyzing all information pertaining to yourcase, NCDS will schedule a technicalevaluation if applicable. If you request it, anoral hearing will be held prior to a decisionbeing rendered. At this hearing, all evidence isadmissible. After considering all testimony anddocuments, the arbitrator will review theapplicable legal standards and render adecision. A settlement satisfactory to allparties may be negotiated at any time,including prior to or after the arbitrator’sdecision.

NCDS’s decision is binding on Tesla but not onyou. If you accept NCDS’s decision, Tesla willcomply with the decision in a reasonable timenot to exceed 30 days after Tesla receivesnotice of your acceptance. Remedies includebut are not limited to repairs; reimbursementfor repairs and incidental expenses, such astransporting costs; and repurchase orreplacement of the applicable Tesla connectoror adapter. NCDS decisions do not includeattorney fees or punitive, multiple, orconsequential damages, except incidentaldamages as required by applicable law. NCDSfindings and decisions are admissible asevidence in any legal proceedings concerningthe applicable Tesla connector or adapter.

Charging Equipment Limited Warranty

32

The description provided above is only a briefsummary of the dispute settlement programadministered by NCDS. The dispute settlementprogram may be changed at any time withoutprior notice. Contact NCDS at the above listedaddress or phone number for the most currentinformation concerning the dispute settlementprogram.

Charging Equipment Limited Warranty

Charging Equipment Limited Warranty 33

Bbottom or rear entry

configurations, dimensions and spacing10example of the service wiring 18installing the low profile bracket for 15

Ccardboard template, using the 15cautions 3check the box contents 12circuit breaker

corresponding rotary switch settings 20requirements 8

circuit ratings, optional 6communications regulations 2conduit, about 10connect the wiring 18copyrights 2cover

removing the outer 17removing the sealing 17securing the outer 21

Ddimensions 5DIP switches, configuring 20documentation errors, sending feedback 2

Ffeatures

circuit ratings, optional 6load sharing 6recovery from power outages 6self-monitoring and recovery 6

Iinstallation

for rear or bottom entry wiring 15for top entry wiring 16information, about 2planning your 7preparing for 17tools and materials required 14torque recommendations 18

installation overview 14installation, testing 27

Llights, diagnostic 6lights, LED 22load sharing

about 6configuring the DIP and rotary switches20example of the communication wiring 29

low profile bracketinstalling the 15

Mminimum requirements 7

Nnotes 4

Pplanning your installation

circuit breaker requirements 8location of the wall connectors 9minimum requirements 7service wiring 7types of installations 10

power outages, recovery from 6power ratings 5power up 21

Rremoving the outer cover 17reset button 6, 25, 27rotary switches, configuring 20

Ssafety instructions 3, 4securing the outer cover 21self-monitoring and recovery 6service wiring 7, 18set the operating current 20specifications

dimensions 5power ratings 5temperature limits 5

Index

34

Ttemperature limits 5terminal blocks

connecting the service wiring to the 18torque recommendations 18

Tesla, contacting 26testing for proper operation 27top entry

bracket, installing the 16configurations, dimension and spacing 10example of the service wiring 18wiring, installing the top entry bracket for16

trademarks 2troubleshooting 22, 25, 26, 28

Wwall connectors

checking the box contents 12connecting the terminal blocks 28daisy chaining 28example of the communication wiring 29location of 9optional configuration 28power up 21reset 25, 27troubleshooting 28

warnings 3wiring for load sharing 28

Index

Index 35

P/N: 1069742-00-C

MNL, USER GUIDE,NA,1PH 80A HW,WC GEN2

(P) PN:1069742-00-C

(T) TLN:TT80AMP1NA