P/N 003-982-AEN Issue 5 Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 1 of 5 Wall-Mountable Connector Housing (WCH-02P/-04P/-06P) 1. Carton Contents Wall-mountable connector housing (WCH) WCH-02P hardware kit: (1) Laser warning label (2) Fiber identification labels (3) Cable ties (4) Mounting screws WCH-04P/-06P (x2) hardware kit: (1) Laser warning label (6) Fiber identification labels (3) Cable ties (4) Mounting screws DIMENSIONS WCH-02P 18.8 cm x 42.2 cm 10.7 cm ( 74 in x 16.1 in x 4.2 in) WCH-04P 35.8 cm x 42.2 cm x 10.7 cm (14.1 in x 16.1 in x 4.2 in) WCH-06P 35.8 cm x 42.2 cm x 10.7 cm (14.1 in x 16.1 in x 4.2 in) 2. Tools and Materials Phillips screwdriver Slotted screwdriver Needle-nose pliers Pencil, pen or marker 3. Additional Materials (Purchased Separately) May or may not be required depending on your application CCH pigtailed cassettes (CCH-CS12-59-P00RE) CCH cassette (CCH-CS, CCH-CF) Pigtailed panels (CCH-CPXX-YY-P03ZZ) Connector panels (CCH-CPXX-YY) Mounting hardware appropriate for your installation Grounding kit (FDC-CABLE-GRND) for armored cable Buffer tube fan-out kits (FAN-XX25-YY) TPA-4724 Door latch Panel door Main door Internal strain-relief Transitional strain-relief Panel door TPA-4725 Main door

Upload: others

Post on 18-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Wall-Mountable Connector Housing (WCH-02P/-04P/-06P) · Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 3 of 5 6. Prepare Cable If present, remove applicable

P/N 003-982-AENIssue 5

Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 1 of 5

Wall-Mountable Connector Housing (WCH-02P/-04P/-06P)

1. Carton Contents• Wall-mountable connector housing (WCH)• WCH-02P hardware kit:

• (1) Laser warning label• (2) Fiber identification labels• (3) Cable ties• (4) Mounting screws

• WCH-04P/-06P (x2) hardware kit:• (1) Laser warning label• (6) Fiber identification labels• (3) Cable ties• (4) Mounting screws

DIMENSIONSWCH-02P 18.8 cm x 42.2 cm 10.7 cm ( 74 in x 16.1 in x 4.2 in)WCH-04P 35.8 cm x 42.2 cm x 10.7 cm (14.1 in x 16.1 in x 4.2 in)WCH-06P 35.8 cm x 42.2 cm x 10.7 cm (14.1 in x 16.1 in x 4.2 in)

2. Tools and Materials• Phillips screwdriver• Slotted screwdriver

• Needle-nose pliers• Pencil, pen or marker

3. Additional Materials (Purchased Separately)May or may not be required depending on your application

• CCH pigtailed cassettes (CCH-CS12-59-P00RE)• CCH cassette (CCH-CS, CCH-CF)• Pigtailed panels (CCH-CPXX-YY-P03ZZ)• Connector panels (CCH-CPXX-YY)• Mounting hardware appropriate for your installation• Grounding kit (FDC-CABLE-GRND) for armored cable• Buffer tube fan-out kits (FAN-XX25-YY)

TPA-4724

Door latch

Panel door

Main door

Internal strain-reliefTransitional strain-relief Panel doorTPA-4725 Main door

Page 2: Wall-Mountable Connector Housing (WCH-02P/-04P/-06P) · Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 3 of 5 6. Prepare Cable If present, remove applicable

Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 2 of 5

4. PrecautionsCAUTION: Fiber optic cable is sensitive to excessive pulling, bending, and crushing forces. Consult the cable specification sheet for the cable you are installing. Do not bend the cable more sharply than the minimum recommended bend radius. Do not apply more pulling force to the cable than specified. Do not crush the cable or allow it to kink. Doing so may cause damage that can alter the transmission characteristics of the cable; the cable may have to be replaced.

WARNING: Never look directly into the end of a fiber that may be carrying laser light. Laser light can be invisible and can damage your eyes. Viewing it directly does not cause pain. The iris of the eye will not close involuntarily as when viewing a bright light. Consequently, serious damage to the retina of the eye is possible. Should accidental eye exposure to laser light be suspected, arrange for an eye examination immediately.

CAUTION: Cleaved or broken glass fibers are very sharp and can pierce the skin easily. Do not let these pieces of fiber stick to your clothing or drop in the work area where they can cause injury later. Use tweezers to pick up cleaved or broken pieces of glass fibers and place them on a loop of tape kept for that purpose alone. Good housekeeping is very important.

CAUTION: Recommend the use of safety glasses (spectacles) conforming to ANSI Z87 for eye protection from accidental injury when handling chemicals, cables, or working with fiber. Pieces of glass fiber are very sharp and have the potential to damage the eye.

5. Mount Housing to a WallStep 1: Open doors with quarter-turn latches.Step 2: Using the housing as a template, mark the mounting hole locations.

NOTE: Use the pre-installed bubble level for mounting accuracy.

• WCH-02P: L = 11.985 in (30.44 cm) • WCH-04P/-06P L = 11.985 in (30.44 cm)H = 4.050 in (10.287 cm) H = 11.130 in (28.27 cm)

Step 3: Drive mounting hardware into the wall at these locations, leaving a 1/8-in gap between the wall and screw head.

Step 4: Place housing onto the mounting hardware and then tighten.

11.985

TPA-4726

4.050

11.985

11.130

TPA-4727

Page 3: Wall-Mountable Connector Housing (WCH-02P/-04P/-06P) · Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 3 of 5 6. Prepare Cable If present, remove applicable

Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 3 of 5

6. Prepare CableIf present, remove applicable knockout by placing needle-nose pliers as close as possible to the “bottom” of the knockout and slowly flex the knockout until it breaks free of the housing.CAUTION: Be careful not to damage the pre-installed dust brushes when removing a knockout.

Loose tube cable Tight-buffered cableAramid yarn (if present)8 in (20 cm)

Strength member4 in (10 cm)

Fiber for BTF assemblies35 in (85 cm) Buffer tube to BTF body

54 in (137 cm)KPA-0178

*Recommend 25-in buffer tube fan-out kit.

Central member4 in (10 cm)

Yarn4 in (10 cm)

900 µm or tight-buffered fibers28 in (71 cm)

TPA-4704

NOTE: Ground armored cable according to instructions provided with the kit;

• Use (1) FDC-CABLE-GRND per armored cable.

IMPORTANT: If you are installing outside plant cable or if temperature fluctuates widely along any part of the cable, the strength members of the cable must be strain-relieved. Failure to do so may result in damage to the cable as temperature varies. Other situations only require the cable to be strain-relieved by sheath retention only.

7. Strain-relieve CableTo ease cable installation, you can remove strain-relief bracket by lifting the plunger and sliding the bracket out of the housing. Reverse process to reinstall the bracket with the cable attached.

TPA-4728

TPA-4729

Plunger

Page 4: Wall-Mountable Connector Housing (WCH-02P/-04P/-06P) · Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 3 of 5 6. Prepare Cable If present, remove applicable

Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 4 of 5

8. Route Unconnectorized or Preterminated Cable

Step 1: Remove blank adapter panel and install connector panel.Step 2: If fiber is unconnectorized, terminate connectors onto the fiber.Step 3: Secure buffer tube or buffer tube fan-out body to the transitional holder.Step 4: Route fibers inside the routing guides.Step 5: Remove dust caps, clean, and mate connectors.

9. Install Pigtailed Cassettes

Step 1: Bring cable and cassette to work surface and splice per standard company practices and instructions provided with the splicing equipment.

Step 2: Route fiber slack in the slack storage area inside the cassette.

Step 3: Remove blank adapter panels, panel clips, routing guides, and transitional strain-relief.

Step 4: Install cassette guides in the base of the housing.Step 5: With clear cover facing inward, slide CCH cassette

onto the cassette guide in the base of the housing and lock in place.

NOTE: To orient clear cover outward, operator must be aware of fiber/adapter port orientation.

TPA-4730

Bubble level

Press buffer tube fan-out bodies into transitional holder.

OR Secure loose tube cable to the transitionalholder with cable ties.

Remove panel clips

Install cassette guidesRemove transitionalstrain-relief androuting guides

TPA-4740

TPA-4742

Page 5: Wall-Mountable Connector Housing (WCH-02P/-04P/-06P) · Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 3 of 5 6. Prepare Cable If present, remove applicable

Standard Recommended Procedure 003-982-AEN | Issue 5 | April 2020 | Page 5 of 5

Step 6: Route subunit slack in the cable entry area. Restrain with cable ties or hook-and-loop straps, if necessary.

Step 7: Strain-relieve cable to the internal strain-relief bracket as described in Section 7.Step 8: Route cable out of the housing through side cable entry cutout.

10. Install CCH Cassettes for SplicingStep 1: Bring cable and cassette to work surface and splice per standard company practices and instructions

provided with the splicing equipment.Step 2: Route fiber slack in the slack storage area inside the cassette.Step 3: Remove blank adapter panels, panel clips, routing guides, and transitional strain-relief.

Step 4: With the clear cover of the cassette facing outward, slide CCH cassette onto the cassette guide in the base of the housing and lock in place.

Step 5: Route subunit slack in the cable entry area. Restrain with cable ties or hook-and-loop straps, if necessary.

Step 6: Strain-relieve cable to the internal strain-relief bracket as described in Section 7 if not already done.

Step 7: Route cable out of the housing through side cable entry cutout.

11. Secure HousingClose and latch both doors.

Corning Optical Communications LLC • 4200 Corning Place• Charlotte, NC 28216 USA 800-743-2675 • FAX: 828-325-5060 • International: +1-828-901-5000 • www.corning.com/opcomm

Corning Optical Communications reserves the right to improve, enhance, and modify the features and specifications of Corning Optical Communications products without prior notification. A complete listing of the trademarks of Corning Optical Communications is available at www.corning.com/opcomm/trademarks. All other trademarks are the properties of their respective owners. Corning Optical Communications is ISO 9001 certified. © 2014, 2017, 2020 Corning Optical Communications. All rights reserved.