wanjii proposed single line diagram

5
Generator Differential Protection: Negative phase sequence, Over current, Under excitatio, Reverse power, AVR Instruments Stator Earth fault Synchronizing, AVR, Over/under voltage, Over/under frequency, under excitation Generator Differential Gen TX Differential Synchronizing NVD Gen TX Differential Over current REF, Earth Fault To station auxiliary OVERCURRENT Station Transformer 1 (new stx) Metering Metering Metering - TO STATION AUXILIARIES BOARD Alternative Feeder (old Stx) Metering TANA FEEDER 2 TANA FEEDER 1 Generator Metering GEN 1 GEN 2 GEN 3 GEN 4 11kV OVERHEAD BUSBAR Stx Overcurrent DRAWING No.1 PROPOSED SINGLE LINE DIAGRAM FOR WANJII POWER STATION

Upload: tsyamprasad

Post on 28-Apr-2015

49 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Wanjii Proposed Single Line Diagram

Generator Differential

Protection: Negative phase sequence, Over

current, Under excitatio, Reverse power,

AVR

Instruments

Stator Earth fault

Synchronizing, AVR, Over/under

voltage, Over/under frequency,

under excitation

Generator

Differential

Gen TX Differential

Synchronizing

NVD

Gen TX Differential

Over current

REF, Earth Fault

To station

auxiliary

OVERCURRENT

Station

Transformer 1 (new

stx)

Metering

Metering

Metering

-

TO STATION

AUXILIARIES BOARD

Alternative Feeder

(old Stx)

Metering

TANA

FEEDER 2TANA

FEEDER 1

Generator Metering

GEN 1GEN 2 GEN 3 GEN 4

11kV OVERHEAD BUSBAR

Stx Overcurrent

DRAWING No.1 PROPOSED SINGLE LINE DIAGRAM FOR WANJII POWER

STATION

Page 2: Wanjii Proposed Single Line Diagram

11 kV POWERHOUSE SWITCHBOARD

-

TO

MAIN 415VAC

SWITCHBOARD

TANA FEEDER 2TANA FEEDER 1

GENERATOR

TX 2GENERATOR

TX 1

STATION TX 1

ALTERNATIVE

FEEDER

(OLD STX)

MATHIOYA RIVER UNITSMARAGUA RIVER UNITS

TO

MAIN 415VAC

SWITCHBOARD

DRAWING NO 2. PROPOSED POWER EVACUATION DIAGRAM

Page 3: Wanjii Proposed Single Line Diagram

MAIN AUXILIARY POWER SWITCHBOOARD

415VAC INCOMERS

STATION TX 1 ALTERNATIVE

FEEDER

DIESEL

GENERATOR

MCC 1 MCC 2 DRAINAGE

PUMPS

MCC 2MCC 1 WINCH

BUS

COUPLER

CB 1 CB 2 CB3

STATION

AUX. BOARD

STATION

AUX. BOARD

EMERGENCY

LIGHTING

DRAWING NO 3. PROPOSED MAIN AUXILIARY POWER SWITCHBOARD

Page 4: Wanjii Proposed Single Line Diagram

INCOMER 1 INCOMER 2

GOVERNOR

PUMP 1 & 2

GENERATOR

HEATER 1LEAKAGE

PUMP1

LUBRICATING

PUMP 2

COOLING

PUMP 1

COOLING

PUMP 2

GOVERNOR

PUMP 2

LEAKAGE

PUMP 2

GENERATOR

HEATER 2LUBRICATING

PUMP 1

DRAWING NO 4. PROPOSED STATION AUXILLIARY MOTOR CONTROL CENTER LINE

DIAGRAM

MOTOR CONTROL CENTRES 1 OR 2

(MCC 1 OR 2)

Page 5: Wanjii Proposed Single Line Diagram

INCOMER 1 INCOMER 2

POWER

HOUSE

LIGHTING

OFFICES

DISTRIBUTION

BOARD

POWER

OUTLETS-

WORKSHOP

POWER

HOUSE

CRANE

BATTERY

CHARGERSSECURITY

LIGHTING

POWER

OUTLETS-

POWER

HOUSE

TAILRACE

HOIST

PORTAL VALVE/

INTAKE GATE

STATION MOTOR CONTROL CENTRE

(STATION MCC)

DRAWING NO 5. PROPOSED MOTOR CONTROL CENTER LINE DIAGRAM