X-MIST® SYSTEM extinguishes or controls fires by cooling, oxygen displacement by water vapor and radiant heat attenuation. The exceptional cooling effect of water mist is a result of the division of water into very fine droplets, which increase the total surface area available to absorb heat and maximizes the evaporation rate of the water.
Nozzle Specification
Type Width(m) Height (m) Pressure (bar) Flow (Lpm) K-Factor
ELL 3.0 0.5~8.0 9~12 33~38 11.0
LL 3.0 1.5~4.0 7~10 15~18 5.6
HL 3.0 4.0~13.5 8~11 14~17 5.0ELL LL HL
Local Water Mist Fire Fighting System for Machinery Space
Applied Rule & Regulation Ⅱ
Major Component
Main Control Panel
Fire Monitor (Repeat Panel)
Receive fire signal from alarm control panel.Operate pump/motor and section valve.Check an error of system.
Receive fire data from main control panel. Display the state of fire at each section.
Alarm Control Panel Smoke / Flame Detector
Receive fire data from detector consisted loop.
Addressable type
The panel is installed at each section. Manual release of water mist.
Local Control Panel
Supply water to each protected area. Composed of pump/motor, MOV valve, motor starter panel.
Extinguishment
Burning of fuel before water spray.
Water spray through nozzle after detection of flame & smoke.
The flame reduction results by cooling, oxygen depletion and wetting of the fuel.
The fire is completely extinguished.
Ignition Suppression
Pump Unit (MOV type)
Water Mist Fire Fighting System
Benefits■Motor operation valve with manual override■No leakage while pump‘s running■Easy maintenance
We are always thinking safety and environment for you
[ International patented ]
www.tanktech.co.kr
This system is fire extinguishing system to protect machinery space of category A and cargo pump room.This system should be capable of manual release and continuously supplying water for at least 30min.This system should be supplied by both main and emergency sources of power and should be provided with
an automatic change-over switch.The capacity and design of system should be based on the complete protection of the space demanding
the greatest volume of water.The operation controls should be available at easily accessible positions outside the space.
Nozzle Specification Type Horizontal spacing(m) Longitudinal spacing(m) height(m) Pressure(bar) Flow rate(Lpm) K-Factor
TC 4.0 3.0 13.5 10.0 18.7 5.9
TB 2.0 3.0 0.65 9.0 48.0 16.0
Applied Rule & Regulation
Benefits- Friendly Environmental and Future Oriented Fire Extinguish System- Secure Safety for Crew and Machinery- The Latest high technology Fire Fighting System for Engine Room that can replace CO2 and Foam System.- No need to recharging and inspection
Application- Maximum ceiling height of protected space : 15.5m- Maximum volume of protected space : 4374m3
This will in general be accepted as the maximum net volume for any protection space ( corresponding to a typical gross volume of 5100m3 )
4m2 tray under mock- up Flowing fire 0.25kg/s from top of mock-up
Test No.7 for ceiling
Class A fires wood crib in 2 m2 pool fire with 30 sec. pre-burn.
Total Water Mist Fire Fighting System for Machinery Space
TC TB
System Diagram
CO2 System Form System