water spray system presentation
DESCRIPTION
FIRETRANSCRIPT
-
What is WATER SPRAY?Water spray" systems are operationally identical to a deluge system, but the piping and discharge nozzle spray patterns are designed to protect a uniquely configured hazard.
Examples of hazards protected by water spray systems are electrical transformers containing oil for cooling or turbo-generator bearings.
-
NFPA-850: Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations
Identification of and Protection Against Hazards -Transformers
Oil filled main, station service and start-up transformers not meeting the separation or fire barrier recommendations or as determined by the Fire Protection Design Basis should be protected with automatic water spray or foam-water spray systems.
-
NFPA-15:Standard for Water Spray Fixed Systems for Fire Protection
Defines a water spray system as:
an automatic or manually actuated fixed pipe system connected to a water supply and equipped with water spray nozzles designed to provide a specific water discharge and distribution over the protected surfaces or area.
-
How Does a Water Spray System Work?The Deluge Valve is an integral part of a deluge system:
Specialty fire protection valveHolds water supply back behind a clapper or diaphragmWater is released via an electric or pneumatic detection system throw solenoid valve
-
The layout of nozzles is based upon spray characteristics:
Angle of spray and associated positioning angle.
Orifice size (how much water can be sprayed out of each nozzle.
-
Typical Nozzles
-
Manual DetectionManual detection is used as a back up for automatic detection.
Draining the system will automatically open the deluge valve.
-
Process and Output Cross-Zoning Cross zoning:helps reduce unwanted water dischargesDivides detectors into two zones
Water will not release unless detectors of two zones are activated.Two zones provides releasing
-
Different Response Stages Cross zoning:
Allows escalating responseCalls fire departmentInitiates alarm condition on building Fire Alarm SystemReleases water
-
Interaction with Building Fire Alarm System Water Spray System must report:
AlarmSupervisoryCommon Trouble
-
Inspection, Testing and Maintenance A deluge systems ITM program should be developed in accordance with NFPA 25: Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems.
Detection system ITM should follow the requirements set forth in NFPA 72: National Fire Alarm and Signaling Code
Documentation of all ITM work should be meticulously maintained and readily available for review by the AHJ
-
Critical elements of an ITM program include:Annual tripping of deluge valve at full flow
Observation of water discharge patterns to confirm proper positioning and absence of obstructions
Verification of water flow alarms
-
Annual operation of annual actuation devices
Cleaning of interior of deluge valve during annual testing
Draining of system low points
Internal inspection of strainers every five years at a minimum
-
Summary A transformer fire is not a frequent occurrence but the impact is tremendous
In a fire the transformer will likely be destroyed immediately but damage to adjacent equipment/structures can be mitigated
The consequences of an uncontained fire include:Costly damage to the facilityLoss of revenue due to an unscheduled outageCompromising the safety of facility inhabitants
**