water spray system presentation

15

Upload: basil-oguaka

Post on 29-Sep-2015

151 views

Category:

Documents


4 download

DESCRIPTION

FIRE

TRANSCRIPT

  • What is WATER SPRAY?Water spray" systems are operationally identical to a deluge system, but the piping and discharge nozzle spray patterns are designed to protect a uniquely configured hazard.

    Examples of hazards protected by water spray systems are electrical transformers containing oil for cooling or turbo-generator bearings.

  • NFPA-850: Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations

    Identification of and Protection Against Hazards -Transformers

    Oil filled main, station service and start-up transformers not meeting the separation or fire barrier recommendations or as determined by the Fire Protection Design Basis should be protected with automatic water spray or foam-water spray systems.

  • NFPA-15:Standard for Water Spray Fixed Systems for Fire Protection

    Defines a water spray system as:

    an automatic or manually actuated fixed pipe system connected to a water supply and equipped with water spray nozzles designed to provide a specific water discharge and distribution over the protected surfaces or area.

  • How Does a Water Spray System Work?The Deluge Valve is an integral part of a deluge system:

    Specialty fire protection valveHolds water supply back behind a clapper or diaphragmWater is released via an electric or pneumatic detection system throw solenoid valve

  • The layout of nozzles is based upon spray characteristics:

    Angle of spray and associated positioning angle.

    Orifice size (how much water can be sprayed out of each nozzle.

  • Typical Nozzles

  • Manual DetectionManual detection is used as a back up for automatic detection.

    Draining the system will automatically open the deluge valve.

  • Process and Output Cross-Zoning Cross zoning:helps reduce unwanted water dischargesDivides detectors into two zones

    Water will not release unless detectors of two zones are activated.Two zones provides releasing

  • Different Response Stages Cross zoning:

    Allows escalating responseCalls fire departmentInitiates alarm condition on building Fire Alarm SystemReleases water

  • Interaction with Building Fire Alarm System Water Spray System must report:

    AlarmSupervisoryCommon Trouble

  • Inspection, Testing and Maintenance A deluge systems ITM program should be developed in accordance with NFPA 25: Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems.

    Detection system ITM should follow the requirements set forth in NFPA 72: National Fire Alarm and Signaling Code

    Documentation of all ITM work should be meticulously maintained and readily available for review by the AHJ

  • Critical elements of an ITM program include:Annual tripping of deluge valve at full flow

    Observation of water discharge patterns to confirm proper positioning and absence of obstructions

    Verification of water flow alarms

  • Annual operation of annual actuation devices

    Cleaning of interior of deluge valve during annual testing

    Draining of system low points

    Internal inspection of strainers every five years at a minimum

  • Summary A transformer fire is not a frequent occurrence but the impact is tremendous

    In a fire the transformer will likely be destroyed immediately but damage to adjacent equipment/structures can be mitigated

    The consequences of an uncontained fire include:Costly damage to the facilityLoss of revenue due to an unscheduled outageCompromising the safety of facility inhabitants

    **