Drawing Set for
Project Number: 500408
The Forsyth County
Water Treatment Plant Expansion
12.0 MGD - ZEEWEED 1000
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
EQUIPMENT SYMBOLS
MUFFLER
MEMBRANE MODULES
& HOUSING
(IF REQ’D)
PLC ALARM FUNCTION WITH
MULTIPLE TRIGGER POINTS
INSTRUMENTS SHARING
COMMON HOUSING
PILOT LIGHT
UNDEFINED
INTERLOCK LOGIC
SYSTEMS WITH
MULTIPLE PLC’S
F
WATER SOFTENER
CAPILLARY TUBING
PNEUMATIC SIGNAL
SOFTWARE LINK
INSTRUMENT CONNECTION
TERMINATION TAG
REVISION TRIANGLE
FLEXIBLE HOSE
FLOOR DRAIN
CALCULATED VALUE
THERMOWELL
MECHANICAL LINK
I
P
ULTRASONIC/ELECTROMAGNETIC
PI
PIG TAIL
RT
T
EX.
SKID BOUNDARY
EQUIPMENT/LINE
SUPPLIED BY OTHERS
OPTIONAL ITEM
FUTURE EQUIPMENT
PIPING SPOOL TAG
MAIN PROCESS LINE
PROCESS LINE
CONTINUATION SYMBOLS
DIAPHRAGM
SEAL
CALIBRATION
COLUMN
ROTAMETER
(VARIABLE AREA
FLOWMETERS)
PORTABLE
EXCHANGE TANK
CAMLOCK CONNECTION
XXXXXX-D-XXX
PERMEATE
TO STORAGE TANK TK-XX
XX USGPM
INJECTION QUILL
NORMALLY
CLOSEDNORMALLY
OPEN
DIAPHRAGM
BUTTERFLY
BALL
GATE OR OTHER
IN-LINE TYPE
NOT OTHERWISE
IDENTIFIED
GLOBE
NEEDLE
CHECK
KNIFE GATE
THREE WAY
RUPTURE DISC
(PRESSURE)
RUPTURE DISC
(VACUUM)
VACUUM BREAKER
AUTOMATIC AIR VENT
PRESSURE REGULATOR
PRESSURE RELIEF/
MULTI FUNCTION VALVE
FLOAT CONTROLLED
SLIDING GATE
VALVE & GATE ACTUATOR SYMBOLS
VALVE & GATE SYMBOLS
UV STERILIZER
CARTRIDGE
FILTER
GRANULAR ACTIVATED
CARBON FILTER (GAC)
OR MULTI MEDIA
FILTER (MMF)
HEAT
EXCHANGER HEATER
FLOW
STRAIGHTENING
DEVICE
STATIC MIXER
PULSATION
DAMPENER
MIXER
BACKFLOW
PREVENTER
DIFFUSER GRID
HH
H
L
LL
LA
I/P CONVERTER
(ELECTRIC ANALOG TO
PNEUMATIC SIGNAL CONVERTER)
RESIN TRAP
Y STRAINER
STEAM TRAP
CYLINDRICAL STRAINER
BACK PRESSURE REGULATOR
VENT AND
FILTER
LINE SYMBOLS & MISC.
PLC-X
PNEUMATIC DIAPHRAGM
SPRING CLOSE PNEUMATIC
CYLINDER (INST.AIR LINES
NOT ALWAYS SHOWN)
SPRING OPEN PNEUMATIC
CYLINDER (INST.AIR LINES
NOT ALWAYS SHOWN)
SOLENOID
ELECTRIC MOTOR
(ANALOG - CONTROL)
VALVE POSITIONER
ELECTRIC MOTOR
(DIGITAL- OPEN/CLOSED)
NOTE: ON LOSS OF PRIMARY POWER
(PNEUMATIC, ELECTRICAL OR HYDRAULIC)
XX: FC = FAIL CLOSED
FO = FAIL OPEN
FL = FAIL TO LAST POSITION
IF NOT SPECIFIED ASSUME FC.
DOUBLE ACTING PNEUMATIC
CYLINDER (INST.AIR LINES
NOT ALWAYS SHOWN)
TRAVEL STOP
DISCRETE
INSTRUMENTS
FIELD
MOUNTED
AUXILIARY
LOCATION
NORMALLY
ACCESSIBLE TO
OPERATOR
PROGRAMMABLE
LOGIC CONTROL
COMPUTER/DCS
FUNCTION
LOCATED ON
SKID CONTROL
PANEL
PINCH
VENTURI
FLOWMETER
FLOWMETER
VORTEX OR
MAGNETIC
(TYPE INDICATED)
PADDLEWHEEL
FLOWMETER
POSITIVE-
DISPLACEMENT-
TYPE FLOW
TOTALIZING
INDICATOR
FLUME
FIXED
SCREEN
VICTAULIC CONNECTION
FLANGED CONNECTION
BLIND FLANGE
NON-FLEX CONNECTION
INSTRUMENTATION LINES
P&ID TIE - INS
HEATING/
COOLING
COIL
ORIFICE PLATE
ORIFICE PLATE
IN QUICK-CHANGE
FITTING
GENERAL INSTRUMENT AND FUNCTION SYMBOLS
SEE INSTRUMENT LETTERS
SUMMING
AVERAGING
LOW
SELECTING
HIGH
SELECTING
S
S/n
I
PLUG OR ANGLE
SEAT
SILENCER
OR FILTER
P&ID LINE TYPES
LOCAL PANEL
CONICAL OR
TEMPORARY STRAINER
REVISED ITEM
FOUR WAY
MUD
WASHPACTOR
WPR-
M-
M-
GRIT WASHER/
CLASSIFIER
M- M-
PERFORATED
TRAVELLING
BAND SCREEN
M- M-
f(x)
HUMAN MACHINE
INTERFACE HMI
OTHER COMBINATIONS OF ANALOG/DIGITAL & DATA HIGHWAY
COMMUNICATION MUST ALSO BE SHOWN AS REQUIRED
SIGNAL
FROM
SIGNAL
TO
CLIENT INTERFACE SIGNALS
(SIZE,SCHEDULE,MATERIAL)
LINE DESIGNATION
SIZE (x"), SCHEDULE, MATERIAL
EX.4", SCH.80, PVC
SCH.80, PVC
SCH.80, CPVC
SCH.40, C.S.
P.E. TUBING
SCH.10, 316L SS
SCH.40, 316L SS
SS TUBING
SCH.10, 304L SS
SCH.40, 304L SS
MOST COMMON MATERIAL’S
NYLON TUBING
COMMON ABBREVIATIONS
MCC MOTOR CONTROL CENTER
MAG MAGNETIC
LOR LOCAL-OFF REMOTE
E-STOP EMERGENCY STOP
AI ANALOG INPUT
DO DIGITAL OUTPUT
FF FOUNDATION FIELD BUS
D.NET DEVICE NET
KK
BALL (MANUAL)
R
CAPPED CONNECTION
BASKET STRAINER
(MOTOR OPTIONAL)
ROTAMETER WITH
BUILT-IN HAND
CONTROL VALVE
EDUCTOR/
EJECTOR
UNSPECIFIED
FUNCTION
ELECTRIC SIGNAL (ANALOG OR
DIGITAL)
ELECTRIC TRACE
& INSULATION
S
M
M
HAND OVERRIDE
ACTUATOR WITH
TRAVEL STOP
SAMPLE VALVE
SSOLENOID VALVE
S
M M
IAS INSTRUMENT AIR SUPPLY
SP SET POINT
HOA HAND-OFF AUTO
DI DIGITAL INPUT
AO ANALOG OUTPUT
AIR DRYER
TURBINE
LOBE BLOWER
CENTRIFUGAL
BLOWER
CENTRIFUGAL
PUMP
POSITIVE
DISPLACEMENT
PUMP
REGENERATIVE
BLOWER
DIAPHRAGM
PUMP
VACUUM PUMP
(WET OR DRY)
TURBINE
PUMP
METERING
PUMP
COMPRESSOR
ROTARY SCREW
COMPRESSOR
PISTON
CAN
PUMP
DESICCANT
DRYER
AXIAL FLOW
PUMP
SUBMERSIBLE
PUMP
BLOWER
(GENERIC)
PUMP
(GENERIC)
07/04/20
0
07/04/20
07/09/12
07/09/12
A.P.L.
1:1
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. ISA SYMBOLOGY COVER SHEET
500408-L-001
500408L1 1.DGN
SHEET
1 OF 2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
HAND
POWER
MECHANICAL OR INSTRUMENT DEVICE TAG IDENTIFICATION PREFIX
AV AIR VENT
AIR DRIER
HAND VALVE
RESIN TRAP
STRAINER
WASHPACTOR
AC
B
CV
DR
F
FG
FI
FO
FV
FX
H
HC
HE
HV
LG
LI
MX
P
PD
PI
RT
SG
SV
TI
TK
UV
VB
YY
AIR COMPRESSOR
ANALYSIS ELEMENT WITH ANALYSIS INDICATING TRANSMITTER AE/AIT
AE/AT ANALYSIS ELEMENT WITH ANALYSIS TRANSMITTER
BLOWER
BPV BACK PRESSURE VALVE
CHECK VALVE/INJECTION QUILL
FILTER
FCV FLOW CONTROL VALVE
FLOW ELEMENT WITH FLOW INDICATING TRANSMITTERFE/FIT
FE/FT FLOW ELEMENT WITH FLOW TRANSMITTER
FLOW SIGHT GLASS
FLOW INDICATOR
ORIFICE PLATE
AUTOMATIC VALVE
FLOW STRAIGHTENING DEVICE
GWC GRIT WASHER/CLASSIFIER
HEATER
HEATING COIL
HCV HAND CONTROL VALVE
HEAT EXCHANGER
LCV LEVEL CONTROL VALVE
LE/LIT LEVEL ELEMENT WITH LEVEL INDICATING TRANSMITTER
LE/LT LEVEL ELEMENT WITH LEVEL TRANSMITTER
LEVEL SIGHT GLASS
LEVEL INDICATOR
LS* LEVEL SWITCH
MFV MULTI FUNCTION VALVE (COMBINATION RELIEF & BACKPRESSURE VALVE FOR METERING PUMPS)
MIXER
STATIC MIXERMXS
PUMP
PULSATION DAMPENER
PE/PIT PRESSURE ELEMENT WITH PRESSURE INDICATING TRANSMITTER
PE/PT PRESSURE ELEMENT WITH PRESSURE TRANSMITTER
PRESSURE INDICATOR
PRESSURE REGULATING VALVE
PRESSURE SWITCH
PRV
PS*
PSE RUPTURE DISC
PRESSURE RELIEF VALVEPSV
SCR SCREEN
SIGHT GLASS
STR
SAMPLE VALVE
TEMPERATURE CONTROL VALVETCV
TE/TIT TEMPERATURE ELEMENT WITH TEMPERATURE INDICATING TRANSMITTER
TE/TT TEMPERATURE ELEMENT WITH TEMPERATURE TRANSMITTER
TEMPERATURE INDICATOR
TANK
TEMPERATURE SWITCHTS*
TURBINETURB
UV STERILIZER
VACUUM BREAKER
VIBRATION SWITCHVS*
WPR
SOLENOID FOR PNEUMATIC CONTROL OF AUTOMATIC VALVE
* ADD THE SUFFIX HH (HIGH HIGH), H (HIGH), L (LOW), LL (LOW LOW) AS REQUIRED FOR THESE ITEMS.
ISA TEXT ABBREVIATIONS
MEASURED OR
INDICATING VARIABLEMODIFIER
READOUT OR
PASSIVE FUNCTIONMODIFIEROUTPUT FUNCTION
ANALYSIS
BURNER, COMBUSTION
USERS CHOICE
USERS CHOICE
VOLTAGE
FLOW RATE
USERS CHOICE
CURRENT (ELECTRICAL)
TIME, TIME SCHEDULE
LEVEL
LOG REMOVAL
USERS CHOICE
USERS CHOICE
PRESSURE, VACUUM
QUANTITY
RADIATION
SPEED, FREQUENCY
TEMPERATURE
MULTIVARIABLE
VIBRATION, MECHANICAL
ANALYSIS
WEIGHT, FORCE
UNCLASSIFIED
POSITION, DIMENSION
DIFFERENTIAL
RATIO (FRACTION)
SCAN
TIME RATE OF CHANGE
MOMENTARY
INTEGRATE, TOTALISE
SAFETY
X AXIS
Y AXIS
Z AXIS
AVERAGE
MULTIFUNCTION
WELL
RECORD
POINT (TEST)
CONNECTION
LIGHT
ORIFICE, RESTRICTION
USERS CHOICE USERS CHOICE USERS CHOICE
INDICATE
GLASS, VIEWING DEVICE
SENSOR
(PRIMARY ELEMENT)
USERS CHOICE
ALARM
USERS CHOICE USERS CHOICE
CONTROL
CONTROL STATION
SWITCH
TRANSMIT
MULTIFUNCTION
VALVE, DAMPER,
LOUVER
UNCLASSIFIED UNCLASSIFIED
MULTIFUNCTION
EVENT, STATE OR
PRESENTRELAY, COMPUTE,
CONVERT
DRIVER, ACTUATOR,
UNCLASSIFIED FINAL
CONTROL ELEMENT
HIGH
LOW
MIDDLE, INTERMEDIATE
Z
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
07/04/20
0
07/04/20
07/09/12
07/09/12
A.P.L.
1:1
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. ISA SYMBOLOGY COVER SHEET
500408-L-001
500408L1 2.DGN
SHEET
2 OF 2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
0
07/04/20
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PROCESS FLOW DIAGRAM 500408A001.DGN
500408-A-001SHEET
1 OF 1 1:1
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
CLARIFIED WATER
CLEARWELL
BACKWASH WASTE
TO BACKWASH
RECOVERY BASINS
ELECTRIC
WATER
HEATER
SODIUM
BISULFITE
SODIUM
HYDROXIDE
P-9700A/B
CIP PUMPS
FEED
CHANNEL
(BY OTHERS)
TK-3500-1 TO 6
(7 TO 11 FUTURE)
MEMBRANE TANK
(BY OTHERS)
B-8500A/B
NEUTRALIZED
CHEMICAL WASTE
TO RESIDUALS
HOLDING BASINS
TK-9700
CIP TANK
TK-8800
BACKPULSE TANK
P-3500-1 TO 6
(7 TO 11 FUTURE)
PROCESS PUMP
SEALWEIR
SODIUM
HYPOCHLORITE
CITRIC
ACID
STR-7600 A
STR-7600 B
STR-7600 C
STR-7600 A - SELF-CLEANING STRAINER
STR-7600 B - BASKET STRAINER
STR-7600 C - SELF-CLEANING STRAINER (FUTURE)
P-5300 A/B P-5500 A/B
P-5100 A/B P-6500 A/B
P-6600 A/B
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
SCREEN WASH WATER
FROM PLANT SERVICE
CLARIFIED WATER
FROM SEDIMENTATION
TANK OR SUPERPULSATOR HV-7587
6"
500408-D-001 SHT.2
SCREENED CLARIFIED
WATER
500408-D-015
SCREENED CLARIFIED
SAMPLE
36", SCH.10, 304L SS
FV-7637
1/2"
S
DO
S
HIS
YS
TYP. SOLENOID VALVE CONTROL DETAIL
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
07/04/27
3
07/04/20
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM PRE-TREATMENT 500408D1 1.DGN
500408-D-001SHEET
1 OF 2 1:1
36" CLD1
08/03/11 1 G.C. M.D. REVISED AS NOTED
08/04/01 2 X.C. M.D. REVISED AS NOTED
12 MGD
24 MGD (FUTURE)
STR-A
STR-C
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. STRAINER CONTROLLED BY LOCAL
PANEL, NOT ZENON PLC.
3. INCLUDED WITH STRAINER PACKAGE
4. 900 GPM @ 40 PSIG NEEDED FOR
BACK WASHING.
5. STRAINER SYSTEM SUPPLIED AND
CONTROLLED BY OTHERS.
09/11/04 3 X.C. M.D. REVISED AS NOTED
3
3
PI
7641B
HV-7641B
1
2"
2
HV-7680B
M-7600B
HV-7640B
1
2"
PI
7640B
HV-7660B
2"
30" 30"
STR-7600B
0.5mm
BASKET STRAINER
RATED FLOW: 9365 GPM
CLEAN PRESSURE DROP:
0.40 PSIG @ 12410 GPM
STANDBY
HV-7681B
(SEE NOTE 5)
(SEE NOTE 5)
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/20
2
07/04/20
07/09/12
07/09/12
A.P.L.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM DISTRIBUTION CHANNEL 500408D1 2.DGN
500408-D-001SHEET
2 OF 2 1:1
OVERFLOW
TO BACKWASH
RECOVERY BASINS
LIT
7626
LE
7626
AI
LI
7626
MULTIPLE
LINES
LY
7626
500408-D-001,SHT.1
SCREENED CLARIFIED
WATER
TK-7600
FEED CHANNEL
30", SCH.10, 304L SS
18", SCH.10, 304L SS
42", SCH.10, 304L SS
NOTE:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
500408-D-003
SCREENED CLARIFIED
WATER
TO MEMBRANE TANKS
LA
7626
LL
7626
HV-7626
1�"
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
2
08/03/11 1 G.C. M.D. REVISED AS NOTED
08/04/01 2 X.C. M.D. REVISED AS NOTED
10", SCH.10, 304 SS 500408-D-013
PERMEATE
BY OTHERS
RANGE: 0-60"
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM P.D. BLOWERS & ASSOC. EQUIPMENT 500408D002.DGN
500408-D-002SHEET
1 OF 1 1:1
FLL
8506B
PI
8540A
FSL
8506B
PI
8540B
PSV-8582A
PSV-8582B
INLET FILTER
AND SILENCER
DI
HV-8580A
HV-8580B
CV-8585B
CV-8585A
INLET FILTER
AND SILENCERDISCHARGE
SILENCER
DISCHARGE
SILENCERMULTIPLE
LINES
DI
FAL
8506B
B-8500A
B-8500B
3", SCH.10, 304L SS
3", SCH.10, 304L SS
3", SCH.10, 304L SS
ACCUSTIC HOOD
ACCUSTIC HOOD
500408-D-003
AIR SCOUR
TO TK-3400
FLL
8506A
FSL
8506A
FAL
8506A
S.P.= 110 SCFM
DECREASING
S.P.= 110 SCFM
DECREASING
�"
�"
S.P.= 11 PSIG
(SEE NOTE 3)
S.P.= 11 PSIG
(SEE NOTE 3)
B-8500A/B
MEMBRANE BLOWERS
131-223 SCFM @ 5.32 TO 5.75 PSIG
10 HP 3600 RPM
480 V/ 3 PH/ 60 HZ
HV-8540A
1/2"
HV-8540B
1/2"
HOA
SMY
8500A
DI DO AODI
YS
8500A
YA
8500A
SC
8500A
HA
8500A
HIS
8500A
YL
8500A
M-8500A
JS
8500A
SC
8500A
HS
8500A
KQI
8500A
KQ
8500A
HOA
SMY
8500B
DI DO AODI
YS
8500B
YA
8500B
SC
8500B
HA
8500B
HIS
8500B
YL
8500B
M-8500B
JS
8500B
SC
8500B
HS
8500B
KQI
8500B
KQ
8500B
(SEE NOTE 4)
(SEE NOTE 4)
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
3",SCH.10, 304L SS
3",SCH.10, 304L SS
2
08/03/11 1 G.C. M.D. REVISED AS NOTED
08/04/01 2 G.V.K. M.D. REVISED AS NOTED
NOTE:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS.
2. ZENON TRAIN 1 TAGS SHOWN.
3. INCLUDED WITH BLOWER PACKAGE.
4. ESTIMATED BLOWER DISCHARGE AIR
TEMPERATURE IS 150^F. PROVIDE
PROTECTION ON PIPING IS NECESSARY
(BY OTHERS).
5. LOW POINT DRAINS & HIGH VENT POINTS
BY OTHERS.
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM MEMBRANES & ASSOC. EQUIPEMENT 500408D003.DGN
500408-D-003SHEET
1 OF 1 1:1
PDIC
3423-1
PDIC
8823-1
PDL
8823-1
PDL
3423-1
H
L
LL
H
L
LL
H
PDL
8123-1
H
TMP
BACKWASH WASTE
TO BACKWASH
RECOVERY BASINS
CA
SS
ET
TE
B-1
CA
SS
ET
TE
A-1
HV-3484A-1
2"
HV-3484B-1
2"
FV-3473-1
HV-3426-1
1�"
AI
HH
H
L
LL
HH
H
L
LL
IASIP
AO
HIS
3463-1
ZC
3463-1
LIC
3426-1
LI
3426-1
LL
3426-1
LY
3426-1
LA
3426-1
LIT
3426-1
LE
3426-1
HV-3482A-1
10"
HV-3482B-1
10"
FV-9761C-1
2"
FV-9761B-1
FV-3467-1
PDC
3423-1
PDC
8823-1
PDA
8823-1
PDA
3423-1
PDA
8123-1
LC
3426-1
HV-3466-1
FV-9761A-1
FCV-3463-1
IASIP
AO
ZC
3463-1
HIS
3463-1
BAFFLE PLATE
(BY OTHERS)
TK-3400-1
MEMBRANE TANK
HIS
HIS
F.O.
3", SCH.10, 304L SS
6", SCH.80, CPVC
18", SCH.10, 304L SS
1", SCH.10, 304L SS
12", SCH.10, 304L SS
18", SCH.10, 304L SS
12", SCH.10, 304L SS
3", SCH.10, 304L SS
2 ZW-1000 v3 CASSETTES OF 51/60 MODULES PER TRAIN
CONCRETE CONSTRUCTION
HV-3887-1
1"
DO EXHAUST
IAS
S
YS
DO
S
YS
FC
ANGLE SEAT VALVE CONTROL DETAIL
TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL
500408-D-010
CIP / DRAIN
RECIRCULATION RETURN/
TANK DRAIN FOR CLEAN
500408-D-001,SHT.2
SCREENED CLARIFIED
WATER
FROM DISTRIBUTION
CHANNEL
500408-D-005
PERMEATE/BACKPULSE
TO P-3500/FROM
BACKPULSE SYSTEM
RANGE:
4 TO 140 IN
(SEE NOTE 4)500408-D-002
AIR SCOUR
FROM B-8500 A/B
FCV-3863-1
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
S
DO
YS
9267-1
FV-9267-1
�"
HV-9291-1
1"
FV-9268-1
1"
P-9200-1
VACUUM EJECTOR
(FOR PRIMING)
�",SCH.40, 304L SS
HV-9290-1
�"
EJECTOR ASSEMBLY AIR SUPPLY ASSEMBLY
EXHAUST
1" FLEX HOSE
OR PVC
(BY OTHERS)
F-9200-1
�"
AIR SUPPLY
�"
NPS-F
�" ODT,
PP TUBING
(BY OTHERS)PI
9240-1
1"
1",SCH.40,
304L SS
500408-D-012
MIT AIR
FROM AC-9100 A/B
500408-D-012
INSTRUMENT AIR
13.5 SCFM @ 80 PSIG
FROM AC-9100 A/B
NOTE 3
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS.
2. DRAWING TYPICAL FOR TRAINS 1 TO 6.
ZENON TRAIN 1 TAGS SHOWN.
3. EJECTORS TO BE LOCATED AT HIGH POINT
IN PIPING
4. A PORTION OF THE AIR HEADER NEEDS
TO BE LOCATED ABOVE THE HIGHEST
WATER LEVEL IN THE MEMBRANE TANK.
08/03/11 1 G.C. M.D. REVISED AS NOTED
08/04/01 2 G.V.K. M.D. REVISED AS NOTED
HV-3463-1
OVERFLOW TO
DISTRIBUTION
CHANNEL
2
2
2
2
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM PROCESS PUMP & ASSOC. EQUIPMENT 500408D005.DGN
500408-D-005SHEET
1 OF 1 1:1
FV-3560-1
FV-8860-1
CV-3585-1
FV-8861-1
HV-3586-1
1" HV-3587-1
1"
PI
3541-1
PI
3540-1
HV-3541-1
�"
HV-3540-1
�"
PE
3523-1
PIT
3523-1
M-3500-1
FE
3520-1
H
L
H
L
FQJ
3522-1
FQM
3522-1
FC
3522-1
FQ
3522-1
FY
3522-1
FQJI
3522-1
FQMI
3522-1
FIC
3522-1
FQI
3522-1
FL
3522-1
FIC
8820-1
FL
8820-1
FQMI
8820-1
FQJI
8820-1
HH
H
L
LL
AI
FIC
3520-1
FL
3520-1
FJI
3520-1
FQI
3520-1
HH
H
L
LL
FIT
3520-1
FC
3520-1
FA
3520-1
FJ
3520-1
FFMY
3520-
FQ
3520-1
FQM
8820-1
FQJ
8820-1
FA
8820-1
FC
8820-1
H
L
H
L
MAG
PLH
8807-1
PAH
8807-1
PSH
8807-1
DI
AI
PY
3523-1
PI
3523-1
HH
H
L
LL
PL
3523-1
PA
3523-1
HH
H
L
LL
10", SCH.10, 304L SS 10", SCH.10, 304L SS
10", SCH.10, 304L SS
12", SCH.10, 304L SS
12", SCH.10, 304L SS
FV-3561-1
TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL
DO EXHAUST
IAS
S
HIS
YS
500408-D-013
PERMEATE
TO COMMON PERMEATE
HEADER
500408-D-007
BACKPULSE WATER
FROM BACKPULSE TANK
500408-D-015
PERMEATE SAMPLE
500408-D-003
PERMEATE/
BACKPULSE
FROM/TO MEMBRANES
1/2", P.E. TUBING
(SEE NOTE 3)
8"10"
S.P.= 11 PSIG
INCREASINGRANGE:
-15 TO 15 PSIG
AO
P-3500-1
PROCESS PUMP
1871 GPM @ 41.2 FT
30HP, 880 RPM
480 V/ 3 PH/ 60 HZ
DO
S
HIS
YS
TYP. SOLENOID VALVE CONTROL DETAIL
S
FV-3536A
�"
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. DRAWING TYPICAL FOR TRAINS 1 TO 6.
ZENON TRAIN 1 TAGS SHOWN.
3. 5 PIPE DIAMETERS UPSTREAM, 3 PIPE
DIAMETERS DOWNSTREAM, STRAIGHT PIPE
RUN RECOMMENDED FOR MAXIMUM ACCURACY.
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
2
HIS
3500-1
YL
3500-1
YA
3500-1
YS
3500-1
SC
3500-1
I
HOA
JS
3500-1
DI DO DI
TLH
3500-1
SM
3500-1
HA
3500-1
KQI
3500-1
SC
3500-1
HS
3500-1
YL
3500-1
HOA
TAH
3500-1
JC
3500-1
TSH
3500-1 RANGE:
0 TO 2000 GPM
08/03/11 1 G.C. M.D. REVISED AS NOTED
08/04/01 2 G.V.K. M.D. REVISED AS NOTED
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
HV-8884
HV-8895
4"
LY
8826
LA
8826
LL
8826
LI
8826
LE
8826
LIT
8826
HH
H
L
LL
F
CV-8898
FV-8870
POTABLE WATER
FROM PLANT SERVICE
WATER SOURCE
HV-8890
HH
H
L
LL
AI
MULTIPLE LINES
2"(50mm), SCH.80 PVC
HV-5696
FV-5677
CV-5685
VENT C/W
AIR FILTER
F-8800
STR-8800
6", SCH.10, 304L SS
12", SCH.10, 304L SS
�", SCH.80, CPVC
TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL
DO EXHAUST
IAS
S
HIS
YS
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. PIPE SPOOL FOR STRAINER MAINTENANCE/
REMOVAL AND ISOLATION VALVE ACTUATION.
500408-D-005
BACKPULSE WATER
TO MEMBRANES
500408-D-013
PERMEATE
FROM COMMON
PERMEATE HEADER
FROM P-5100
SODIUM HYPOCHLORITE
FOR BIOGROWTH PREVENTION
500408-D-011,SHT.1
(SEE NOTE 2)
HV-8826
1�"
RANGE:
12" TO 100"
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM BACKPULSE TANK & ASSOC. EQUIPMENT 500408D007.DGN
500408-D-007SHEET
1 OF 1 1:1
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
8",
SC
H.80,
PV
C
08/03/11 1 G.C. M.D. REVISED AS NOTED
HV-8871
HV-5697
�"
TK-8800
BACKPULSE TANK
2,000 USGAL
CT - 2000
PE CONSTRUCTION
08/04/01 2 G.V.K. M.D. REVISED AS NOTED
2
22
2
2
2
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
1
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM VACUUM PUMPS & ASSOC. EQUIPMENT 500408D009.DGN
500408-D-009SHEET
1 OF 1 1:1
FV-9261A
TO
ATMOSPHERE
TO
ATMOSPHERE
PI
9241
HV-9241
�"
FV-9261B
HCV-9292A
FROM
ATMOSPHERE
MULTIPLE LINES
FROM ATM.
TO
ATMOSPHERE
FV-9261C
VACUUM PUMPS
LSH
9202-1
LAH
9202-1
LLH
9202-1
TK-9200
DI
P-9200A
M-9200A
M-9200B
M-9200C
P-9200C
P-9200B
S
FV-9292A
�"
S
FV-9292B
�"
S
FV-9292C
�"
SEE NOTE 2
(TYP.)
LIQUID
RESERVOIR
30 GAL
LG
92-1
PI
9243
HV-9243
�"
FV-9200A
FV-9200B
FV-9200C
1�", SCH.80, CPVC 3", SCH.80, CPVC 3", SCH.80, CPVC
2", SCH.80, CPVC 2", SCH.80, CPVC
2", SCH.80, CPVC 2", SCH.80, CPVC
2", SCH.80, CPVC 2", SCH.80, CPVC
TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL
DO EXHAUST
IAS
S
HIS
YS
TYP. BLOWER CONTROL DETAIL
YS
YA
HA
DI DO DI
HIS
YL
M-
HOA
KQI
JS
HS
YL
DO
S
HIS
YS
TYP. SOLENOID VALVECONTROL DETAIL
500408-D-003
AIR/VACUUM
FROM AIR RELEASE VALVE
(SEE NOTE 5)
(TYP.)(SEE NOTE 6)
(TYP.)
(SEE NOTE 4)
(TYP.)
FV-9262A
FV-9262D
1"
FV-9262B
FV-9262C
2"
2"2"
�"
(SEE NOTE 3)
(TYP.)
(SEE NOTE 3)
(TYP.)
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. DISCHARGE AIR MAY BE HOT AND HUMID, PROTECT
OPERATORS APPROPRIATELY.
3. TO BE INSTALLED AS CLOSE TO LIQUID RESERVOIR
AS POSSIBLE.
4. VACUUM LINES TO BE SLOPED DOWN TOWARDS TK-9200
SUCH THAT LIQUID IS NOT ALLOWED TO COLLECT IN LINES.
WHERE LOW POINTS IN PIPING CANNOT BE AVOIDED, AN
AUTOMATED DRAIN MUST BE INSTALLED. DISCUSS DESIGN
REQUIREMENTS WITH ZENON BEFORE INSTALLING.
5. FILTER TO BE INSTALLED IN HORIZONTAL ORIENTATION.
REFER TO VACUUM PUMP VENDOR DATA.
6. VACUUM PUMP MUST BE MOUNTED ON A STEEL FRAME FOR
ANCHOR BOLT ACCESS.
2 DUTY + 1 STANDBY
67 CFM @ 25.12" HG @ 1206 FASL
7.5 HP, 3600 RPM
480 V / 3 PH / 60 Hz
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
08/04/01 1 G.V.K. M.D. REVISED AS NOTED
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM CLEANING SYSTEM TK-97 500408D010.DGN
500408-D-010SHEET
1 OF 1 1:1
CV-9785A
HV-9781A
HV-9786A
HV-9787A
HV-9780A
CV-9785B
HV-9781B
HV-9786B
HV-9787B
HV-9780B
FIT
9720
HH
H
L
LL
HH
H
L
LL
AI
FV-9760
NEUTRALIZED
CHEMICAL WASTE
TO RESIDUALS
HOLDING BASINS
FV-9745
FV-9765
CV-9745
HV-9734
HCV-9734
HV-9732
HCV-9732
AE
9734
AIT
9734
AE
9732
AIT
9732
S
TIT
9730
TE
9730
RESIDUAL
CHLORINE
ANALYZERRANGE:
0 TO 14RANGE:
TO ppm
HH
H
L
LL
HH
H
L
LL
LIT
9726
LE
9726
FV-9770A
FV-9775
MAG
SEE NOTE 3
SEE NOTE 2
(MULTIPLE
LINES)
FV-9762
HH
H
L
LL
HH
H
L
LL
M-9700A
P-9700A
P-9700B
M-9700B
DIDODI
TSH
9709
IYL
9709
JS
9709
HS
9709
YLH
9709
HOA
YS
9709
HA
9709
YA
9709
YL
9709
HIS
9709
HK
9709
TEMP.
HV-5196
CV-5198
FV-5160
HV-6696
CV-6698
HV-6698
HV-5396
HV-5596
CV-5398
CV-5598
HV-5398
HV-5598
HV-6596
CV-6598
HV-6598
pH Cl
-
AI
AI
9734
AY
9734
AL
9734
AA
9734
HH
H
L
LL
HH
H
L
LL
AI
AI
9732
AY
9732
AL
9732
AA
9732
HH
H
L
LL
HH
H
L
LL
AI
TI
9730
TY
9730
TL
9730
TA
9730
AI
LL
9726
LA
9726
LI
9726
LY
9726
FL
9720
FI
9720
FA
9720
FY
9720
PI
9741A
PI
9740AFE
9720
PI
9740BPI
9741B
6", SCH.80, CPVC
6", SCH.10, 304L SS
6", SCH.80, CPVC
6", SCH.80, CPVC
6", SCH.80, CPVC
�", SCH.80, CPVC
�", SCH.80, CPVC
1", SCH.80, CPVC
�", SCH.80, CPVC
1", SCH.80, CPVC
8", SCH.10, 304L SS
CV-9798
HV-9795
HV-9799
POTABLE WATER
FROM PLANT SERVICE
WATER SOURCE
2", SCH.10, 304L SS
HV-9790
TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL
DO EXHAUST
IAS
S
HIS
YS
500408-D-013
PERMEATE
FROM COMMON
PERMEATE HEADER
500408-D-003
CIP / DRAIN
TO/FROM TK-3400
500408-D-011,SHT.1
SOLUTION FOR
RECOVERY CLEANS
FROM P-6600
SODIUM HYPOCHLORITE
500408-D-011,SHT.1
SOLUTION FOR
MAINTENANCE CLEANS
FROM P-5100
SODIUM HYPOCHLORITE
CITRIC
500408-D-011,SHT.1
ACID SOLUTION
FOR CLEANS
FROM P-6500
500408-D-011,SHT.2
SODIUM BISULPHITE
FOR NEUTRALIZATION
FROM P-5300
500408-D-011,SHT.2
SODIUM HYDROXIDE
FOR NEUTRALIZATION
FROM P-5500
DO
S
YS
TYP. SOLENOID VALVECONTROL DETAIL
HIS
DI DO AO DI
HOA
KQI
9700A
JS
9700A
SC
9700A
HS
9700A
YL
9700A
YA
9700A
YS
9700A
SC
9700A
SMY
9700A
HA
9700A
HIS
9700A
YL
9700A
DI DO AO DI
HOA
KQI
9700B
JS
9700B
SC
9700B
HS
9700B
YL
9700B
YA
9700B
YS
9700B
SC
9700B
SMY
9700B
HA
9700B
HIS
9700B
YL
9700B
RANGE:
TO INHV-9726
RANGE:
TO ^F
HV-9741A
1/2" 6"4"
HV-9741B
1/2"
HV-9740B
1/2"6"
4"
CIP/RECIRC./NEUTRALIZATION PUMPS
1 DUTY + 1 STANDBY
306 GPM @ 22.5 FT
5 HP @ 1180 RPM
480 V / 3 PH / 60 Hz
FV-9732
1/2"
�", SCH.80, CPVC
HV-9740A
1/2"
RANGE:
0 TO 1000 GPM
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
08/03/11 1 I.B. M.D. REVISED AS NOTED
8"
TK-9700
CIP TANK
2000 USGAL
PE CONSTRUCTION
CT-2000
08/04/01 2 X.C. M.D. REVISED AS NOTED
FV-9771
6"
VENT
HX-9700
ELECTRIC HEATER
37 KW
NO
TE 6
BPV-6594
BPV-5394
BPV-5594
BPV-5194
BPV-6694
HV-5198
PANEL
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. PROVIDE AIR GAP.
3. 5 PIPE DIAMETERS UPSTREAM, 3 PIPE
DIAMETERS DOWNSTREAM, STRAIGHT PIPE
RUN RECOMMENDED FOR MAXIMUM ACCURACY.
4. ADD GOOSE NECK TO PREVENT DURING OF
CELLS PROBE.
5. DO NOT INSTALL PROBES UNTIL COMMISSIONING
BEGINS.
6. INJECTION LINES TO BE LOCATED ON UNDERSIDE
OF PIPES.
2
NOTE 5 NOTE 4
2
2
2
2
2
2
2
2
2
2
2
2
2 2
2NOTE 6
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
DO
S
HIS
YS
TYP. SOLENOID VALVE CONTROL DETAIL
HIS
6500B
YL
6500B
YA
6500B
YS
6500B
YY
6500B
YL
6500A
HIS
6500A
YS
6500A
YA
6500A
YY
6500A
DI DO DO DI
HIS
5100B
YL
5100B
YA
5100B
YS
5100B
YY
5100B
YL
5100A
HIS
5100A
YS
5100A
YA
5100A
YY
5100A
DI DO DO DI
HIS
6600B
YL
6600B
YA
6600B
YS
6600B
YY
6600B
YL
6600A
HIS
6600A
YS
6600A
YA
6600A
YY
6600A
DI DO DO DI
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM CLEANING CHEMICALS 500408D11 1.DGN
500408-D-011SHEET
1 OF 2 1:1
500408-D-010
CITRIC ACID
FOR RECOVERY CLEANS
TO P-9700 DISCHARGE
500408-D-010
SODIUM HYPOCHLORITE
FOR MAINTENANCE CLEANS
TO P-9700 DISCHARGE
500408-D-010
SODIUM HYPOCHLORITE
FOR RECOVERY CLEANS
TO P-9700 DISCHARGE
500408-D-007
SODIUM HYPOCHLORITE
FOR BIOGROWTH PREVENTION
TO BACKPULSE TANK
TK-8800
AI
LI
5100
LY
5100
LIT
5100
LE
5100
LT-5100
RANGE: TBD
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
08/03/11 1 G.C. M.D. REVISEE AS NOTED
CHEMICAL FILL LINE
FROM CHEMICAL
TRANSFER PUMPS
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. VENT ALL CHEMICAL TANKS APPROPRIATELY
3. CHEMICAL PUMP SYSTEM WIRED TO LOCAL
JUNCTION BOX
4. TEMPORARY GAUGE CONNECTIONS FOR COMMISSSING
ONLY
08/04/01 2 G.V.K. M.D. REVISEE AS NOTED
2
2
2
2
2
2
2
2
2
2
2
(SEE NOTE 2)
CALIBRATION
COLUMN
FQMI-6548 P-6500B
HV-6581B
HV-6586B
PSV-6583B
HV-6587B
HV-6580BHV-6580A
HV-6587A
PSV-6583A
P-6500A
HV-6581A
HV-6586A
�", SCH.80, CPVC
�
",
SC
H.80,
CP
VC
�", SCH.80, CPVC
�
",
SC
H.80,
CP
VC
(SEE NOTE 2)
CALIBRATION
COLUMN
FQMI-5148 P-5100B
HV-5181B
HV-5186B
PSV-5183B
HV-5187B
HV-5180BHV-5180A
HV-5187A
PSV-5183A
P-5100A
HV-5181A
HV-5186A
SODIUM HYPOCHLORITE
�", SCH.80, CPVC
�
",
SC
H.80,
CP
VC
�", SCH.80, CPVC
�
",
SC
H.80,
CP
VC
CALIBRATION
COLUMN
FQMI-5248 P-5200B
HV-6681B
HV-6686B
PSV-6683B
HV-6687B
HV-6680BHV-6680A
HV-6687A
PSV-6683A
P-6600A
HV-6681A
HV-6686A
1", SCH.80, CPVC
1",
SC
H.80,
CP
VC
1",
SC
H.80,
CP
VC
PANEL LIMITS
PANEL LIMITS
PANEL LIMITS
CITRIC ACID TOTE
(BY OTHERS)
1", SCH.80, CPVC
TK-6500
P-6600A/B
SODIUM HYPOCHLORITE PUMPS
FOR RECOVERY CLEANS
1.27 GPM @ 58 PSIG MAX.
120 V/ 1 PH/ 60 HZ
TK-5100
�"
�"
�"
P-5100A/B
SODIUM HYPOCHLORITE PUMPS
FOR MAINTENANCE CLEANS
0.13 GPM @ 58 PSIG MAX.
120 V/ 1 PH/ 60 HZ
P-6500A/B
CITRIC ACID PUMPS
FOR RECOVERY CLEANS
0.1 GPM @ 58 PSIG MAX.
120 V/ 1 PH/ 60 HZ
(SEE NOTE 4)
( BY OTHERS )
NOTE 4
NOTE 4
NOTE 4
1"
1"
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM NEUTRALIZATION CHEMICALS 500408D11 2.DGN
500408-D-011SHEET
2 OF 2 1:1
DO
S
HIS
YS
TYP. SOLENOID VALVE CONTROL DETAIL
HIS
5300B
YL
5300B
YA
5300B
YS
5300B
YY
5300B
YL
5300A
HIS
5300A
YS
5300A
YA
5300A
YY
5300A
DI DO
DO DI
HIS
5500B
YL
5500B
YA
5500B
YS
5500B
YY
5500B
YL
5500A
HIS
5500A
YS
5500A
YA
6400A
YY
5500A
DI DO
DO DI
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. VENT ALL CHEMICAL TANKS APPROPRIATELY.
3. BACK PRESSURE VALVE WILL BE SHIPPED LOOSE
FOR INSTALLATION CLOSE TO INJECTION POINT.
4. CHEMICAL PUMP SYSTEM WIRED TO LOCAL
JUNCTION BOX.
500408-D-010
SODIUM BISULFITE
TO P-9700 DISCHARGE
500408-D-010
SODIUM HYDROXIDE
TO P-9700 DISCHARGE
LT-5100
RANGE: TBD
AI
LI
5500
LY
5500
LIT
5500
LE
5500
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
08/03/11 1 G.C. M.D. REVISED AS NOTED
CHEMICAL FILL LINE
FROM CHEMICAL
TRANSFER PUMPS
(BY OTHERS)
08/04/01 2 G.V.K. M.D. REVISED AS NOTED
2
2
2
2
2
2
(SEE NOTE 2)
CALIBRATION
COLUMN
FQMI-5348 P-5300B
HV-5381B
HV-5386B
PSV-5383B
HV-5387B
HV-5380BHV-5380A
HV-5387A
PSV-5383A
P-5300A
HV-5381A
HV-5386A
�", SCH.80, CPVC
�
",
SC
H.
80,
CP
VC
�", SCH.80, CPVC
�
",
SC
H.
80,
CP
VC
(SEE NOTE 2)
SODIUM HYDROXIDE
�", SCH.80, CPVC
CALIBRATION
COLUMN
FQMI-5548 P-5500B
HV-5581B
HV-5386B
PSV-5583B
HV-5587B
HV-5580BHV-5580A
HV-5587A
PSV-5583A
P-5500A
HV-5581A
HV-5586A
�", SCH.80, CPVC
�
",
SC
H.80,
CP
VC
�
",
SC
H.80,
CP
VC
PANEL LIMITS
SODIUM BISULFITE TOTE(BY OTHERS)
PANEL LIMITS
TK-5500
TK-5300
�"
�"
P-5300A/B
SODIUM BISULFITE PUMPS
FOR NEUTRALIZATION
0.010-0.102 GPM @ 58 PSIG MAX.
120 V/ 1 PH/ 60 HZ
(SEE NOTE 4)
P-5500A/B
SODIUM HYDROXIDE PUMPS
FOR NEUTRALIZATION
0.005-0.235 GPM @ 58 PSIG MAX.
120 V/ 1 PH/ 60 HZ
(SEE NOTE 4)
1"
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/26
2
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM AIR SYSTEM FOR PDT EQUIP. & VALVES 500408D012.DGN
500408-D-012SHEET
1 OF 1 1:1
PSL
9108
PLL
9108
I
PSL
9100A
PI
9140A
HOA
INSTRUMENT AIR
DI
HV-9183
PRV-9586
PSV-9564
CV-9580
HV-9580
PSV-9182A
M-9182A
S.P.= 110 PSIG
DECREASING
PI
9541
HV-9181A
HV-9182A
HV-9184
DPI
9141
HV-9185
DPI
9542
HV-9582
HV-9583
MULTIPLE LINES
(1 PER TRAIN)
(SEE NOTE 2)
REGULATOR
(SEE NOTE 3)
PSL
9100B
PI
9140B
YS
9100B
YA
9100B
YL
9100B
DI
PSV-9182A
M-9182B
HV-9181B
HV-9182B
AC-9100B
KQI
9100B
JS
9100B
HS
9100B
YL
9100B
AC-9100A
F-9100B
F-9100A
TK-9100B
TK-9100A
F-9100
PRIMARY COALESCING
FILTER W/ INTEGRAL
AUTO-DRAIN
F-9500
SECONDARY COALESCING
FILTER W/ INTEGRAL
AUTO-DRAIN
ACF-9500
ACTIVATED CARBON
FILTER W/ INTEGRAL
MANUAL DRAIN
I
HOAKQI
9100A
JS
9100A
HS
9100A
YL
9100A
LOCAL
DI
YS
9100A
YA
9100A
YL
9100A
DI DI
SEE NOTE 7
PAL
9108
500408-D-003
MIT AIR
TO MEMBRANES
S.P.= 70 PSIG
DECREASING
S.P.= 80 PSIG
S.P.= 10 PSIGS.P.= 11 PSIG
AUTO-DRAIN
INTEGRAL
TO DRYER
(SEE NOTE 6)
AUTO-DRAIN
INTEGRAL
TO DRYER
(SEE NOTE 6)
120USGAL
(SEE NOTE 6)
120USGAL
(SEE NOTE 6)
ELECTRICAL
AUTO-DRAIN
120 V/ 1 PH/ 60 HZ
(SEE NOTE 5)
S.P.= 90 PSIG
DECREASING
7.5 HP, 1034 RPM
22.6 ACFM @ 175 PSIG MAX.
480 V/ 3 PH/ 60HZ
(SEE NOTE 4,6,8)
AC-9100A/B
AIR COMPRESSORS
1 DUTY + 1 STANDBY
u 1 m
COMPRESSED AIR
RECEIVER TANK
COMPRESSED AIR
RECEIVER TANK
ELECTRICAL
AUTO-DRAIN
120 V/ 1 PH/ 60 HZ
(SEE NOTE 5)
u0.01 mu0.01 m
PRV-9182
1/2"
HV-9598
1/2"
HV-9541
1/2"
DRAIN
HV-9180A
3/4"
DR-9182 A/B
REFRIGERATED AIR DRYER
MAX. 35 CFM @ 100 PSIG
1/3 HP
120 V / 1 PH / 60 Hz
HV-9180B
3/4"
�" �"
�" �" �" �"
1" 304
L
S.
S.
TU
BI
NG
�" �"
MULTIPLE LINES
(1 PER TRAIN)
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. AT LEAST 1 ISOLATION VALVE PER
TRAIN (BY OTHERS).
3. HANDLE FOR BYPASS VALVE TO BE REMOVED
OR VALVE LOCKED IN CLOSED POSITION.
4. FOOD GRADE OIL TO BE USED.
5. AUTO-DRAIN PLUGS INTO LOCAL OUTLET.
WALL GFCI PLUG REQUIRED BY OTHERS.
6. NOT CONTROLLED BY PLC.
7. DRAIN VALVES TO BE LOCATED AT ANY LOW
POINTS IN PIPING WHERE MOISTURE MAY
ACCUMULATE. EXTRA VALVES BY OTHERS.
8. LOCAL CONTROL PANEL INCLUDED WITH
COMPRESSOR.
1" 304
L
S.
S.
TU
BI
NG
1" 304
L
S.
S.
TU
BI
NG
1" 304L S.S. TUBING
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
2
08/03/11 1 G.C. M.D. REVISED AS NOTED
08/04/01 2 G.V.K. M.D. REVISED AS NOTED
2
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
1
07/04/23
07/09/12
07/09/12
A.P.L.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM PERMEATE STORAGE TANK 500408D013.DGN
500408-D-013SHEET
1 OF 1 1:1
TI
7530
TY
7530
TIT
7530
TE
7530
MULTIPLE LINES
AI
AI
LE
7526
LY
7526
LI
7526
LL
7526
LA
7526
HH
H
L
LL
HH
H
L
LL
LIT
7526
VACUUM BREAKER
30", SCH.10, 316L SS
6", SCH.10, 304L SS
6", SCH.10, 304L SS
10", SCH.10, 316L SS
TK-7500
CLEARWELL
SEAL WEIR
NOTE:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. VACUUM BREAKER TO BE INSTALLED
AT HIGH POINT IN PIPING.
RANGE:
TO IN
TBD
(SEE NOTE 2)
RANGE: 32 TO 120^F
�"
500408-D-007
PERMEATE
TO TK-8800
500408-D-010
PERMEATE
TO TK-9700
500408-D-005
PERMEATE
FROM PERMEATE PUMPS
500408-D-015
COMMON PERMEATE
SAMPLE
FV-7537
1/2" S
DO
S
HIS
YS
TYP. SOLENOID VALVE CONTROL DETAIL
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
08/04/01 1 X.C. M.D. REVISED AS NOTED
10", SCH.10, 304L SS
PERMEATE
500408-D-001,SHT.2
BYOTHERS
BYOTHERS
2
2
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.
07/04/27
1
07/04/23
07/09/12
07/09/12
I.B.
THE FORSYTH COUNTY - 12.0 MGD WTP
K.S.
N.K.
M.D. PIPING & INSTRUMENTATION DIAGRAM PARTICLE COUNTER & TURBIDIMETER 500408D015.DGN
500408-D-015SHEET
1 OF 1 1:1
TO DRAIN
PARTICLE
COUNTER
VENT
HH
H
HH
H
F
HH
H
S
HH
H
L
LL
HH
H
L
LL
AI
�",P.E., TUBING
S
HH
H
L
LL
HH
H
L
LL
AI
TO DRAIN
�",P.E., TUBING500408-D-001,SHT.1
SCREENED CLARIFIED
SAMPLE
AE
7637
AIT
7637
7637
AY
7637
AA
AI
7637
AL
7637
TURB
TURB
PART
HH
H
L
LL
AI
TO DRAIN
�",P.E., TUBING
AE
7537
AIT
7537
7537
AY
7537
AA
TURB
500408-D-013
COMMON
PERMEATE SAMPLE
AE
3537-1
AIT
3537-1
AA
3537-1
AY
3537-1
AL
3537-1
AI
3537-1
1 -3536B-1
HCV-3536B-1
FE
3536B-1
TK-3536-1
DEGASSING
CYLINDER
HCV-3536A-1
FV-3536A-1
AE
3536-1
AJIT
3536-1
A1
3536-1
AA
3536-1
AJI
3536-1
AI1
3536-1
AJI
3536-1
AL1
3536-1
HV-3537-1
(NOTE 2)
AI
7537
HH
H
L
LL
AL
7537
DO
S
HIS
YS
TYP. SOLENOID VALVECONTROL DETAIL
500408-D-005
PERMEATE SAMPLE
(PER TRAIN)
RANGE:
0 - 1,000 mNTU
RANGE:
0 - 1,000 mNTU
RANGE:
0 - 1,000 mNTU
F-3536-1
HV-3536C-1
1/2"
�"
HV-7637
HV-7537
(SEE NOTE 2)
07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL
NOTES:
1. ALL DOTTED LINES/EQUIPMENT
BY OTHERS
2. DRAWING TYPICAL FOR TRAINS 1 TO 6.
08/04/01 1 G.V.K. M.D. REVISED AS NOTED
PANEL
PANEL
PANEL
2
2
2
789101112D (24x36)
D
DATEREV. DESCRIPTION
REV.
DATEAPPROVAL
SCALE: DRAWING NO.
TITLE:
CUSTOMER:
(Y/M/D)
DSGNZONE APPD
SIZE:
CADD FILE:
6 5 4 3 2 1
B
A
C
D
G
H
F
E
B
A
C
D
G
H
F
E
789101112 6 5 4 3 2 1
DRWN:
DSGN:
CHKD:
APPD:
THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.
IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE
DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF
THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.