Page 1: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

WattMaster VAV SystemOperator Interfaces

Technical Guide

Page 2: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Table Of ContentsIntroduction ..................................................................................................................................................... 3

Modular Service Tool .................................................................................................................................................................. 3Modular System Manager ........................................................................................................................................................... 3

System Connections........................................................................................................................................ 4Modular Service Tool .................................................................................................................................................................. 4Modular System Manager ........................................................................................................................................................... 5

General Programming Information ................................................................................................................. 6Operator Interfaces Comparison ................................................................................................................................................ 6Service Tool And System Manager ............................................................................................................................................ 7Modular System Manager ........................................................................................................................................................... 7Modular Service Tool ................................................................................................................................................................ 10

Programming The WMVAV Controller ........................................................................................................... 12Configuration ............................................................................................................................................................................ 12Setpoints ................................................................................................................................................................................... 16Status ........................................................................................................................................................................................ 22Scheduling ................................................................................................................................................................................ 24Setting Time & Date .................................................................................................................................................................. 25Damper Force Modes ............................................................................................................................................................... 26Outputs Force ........................................................................................................................................................................... 26

Programming The VAVBOX Controller .......................................................................................................... 28Configuration ............................................................................................................................................................................ 28Setpoints ................................................................................................................................................................................... 29Status ........................................................................................................................................................................................ 32Damper Force Modes ............................................................................................................................................................... 34

Programming The MiniLink PD ...................................................................................................................... 35Configuration ............................................................................................................................................................................ 35

WattMaster Controls Inc.8500 NW River Park Drive · Parkville , MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.wattmaster.comForm: WM-SMST-TGD-01CCopyright 2004 WattMaster Controls, Inc.WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.This document is subject to change without notice.

WattMaster Controls Inc.8500 NW River Park Drive · Parkville , MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.wattmaster.comForm: WM-SMST-TGD-01CCopyright 2004 WattMaster Controls, Inc.WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.This document is subject to change without notice.

WattMaster Controls Inc.8500 NW River Park Drive · Parkville , MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.wattmaster.comForm: WM-SMST-TGD-01CCopyright 2004 WattMaster Controls, Inc.WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.This document is subject to change without notice.

Page 3: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces 3

Technical Guide

Modular System Manager

ENTER

CLEARESC

PREV NEXT

DOWN

UP

654

DEC

7

0

8

1 32

9

MINUS-

STATUS

SETPOINTS

SCHEDULES

ALARMS

OVERRIDES

9.00"

6.25"

1.81"

Figure 2: Modular System Manager Dimensions

DescriptionThe OE392-05 – Modular System Manager provides a direct link toenable the system operator to view the status and to adjust the setpointsof any controller on the control system communications loop. The Modu-lar System Manager is designed to be used with the WattMaster VAVControl System. The System Manager is housed in an attractive off-white colored plastic enclosure. The System Manager is equipped witha four line by 20 character backlighted display panel and a 24 key mem-brane keypad for data selection and entry. All keypad operations aresimple and straight forward, utilizing non-cryptic plain English languagemessages. Menu driven programming allows for easy setup and opera-tion without the need for specialized training. The System Manager alsohas 2 integral LED’s for user notification of system alarm conditionsand override initiations. Protection from unauthorized users is providedby the System Manager’s integral multi-level passcode authorizationprogramming.

On WattMaster VAV Systems, the Modular System Manager is wired tothe communications and power loop of the system via a pigtail cablewith modular connectors on one end and stripped wire ends on the otherthat is provided with the System Manager. This pigtail cable allowsconnection of power to the Modular System Manager from a 24 VACpower source and communications wiring from the HVAC unit control-ler communication wiring terminals.

The Modular System Manager is designed for wall mounting. Mount-ing holes are provided to attach the Modular System Manager to a stan-dard handy box. It is recommended that the System Manager be mountedat approximately eye level to allow for ease of programming and read-ing of the display. The System Manager is typically mounted in thebuilding manager or superintendent’s office or in an equipment room.The attractive enclosure is quite suitable for mounting in any locationor with most decors.

IntroductionModular Service Tool

Mode

Selection

ENTER

CLEARESC

PREV NEXT

DOWN

UP

654

DEC

7

0

8

1 32

9

MINUS-

STATUS

SETPOINTS

SCHEDULES

CONFIGURATION

ALARMS

ON

OVERRIDES

BALANCE - TEST

10.00”

4.75”

2.02"

1.63"

Figure 1: Modular Service Tool Dimensions

DescriptionThe OE391-05 Modular Service Tool is a system operator interfacethat provides a direct link to enable the system operator to view thestatus, configure and to adjust the setpoints of any controller on thecontrol system communications loop. The Modular Service Tool ishoused in an attractive beige colored plastic enclosure. The displayarea is covered with a clear plastic bezel for protection of the displayscreen. The Modular Service Tool has a four line by 20 character dis-play panel with adjustable contrast control and a 27 key membranekeypad for data selection and entry. All keypad operations are simpleand straight forward, utilizing non-cryptic plain English languagemessages. Menu driven programming allows for easy setup and op-eration without the need for specialized training. The OE391-05 Modu-lar Service Tool is supplied with (4) AA (1.5V) Volt alkaline batteriesa wall mount DC power supply and a communication cable terminatedwith an 8 pin DIN connecter for connection to the Service Tool. Thecable allows the user to setup and program any WattMaster VAV con-troller with a 8 pin DIN connector socket by simply plugging in theservice tool to the socket on the controller. An adapter is also providedto allow connection to the 3 pin communications terminal block oncontrollers which do not have the 8 pin DIN connector.

The Modular Service Tool is designed to be carried by the system in-staller or service technician. Its rugged plastic housing, provides supe-rior protection for the electronic components housed inside. The OE391-05 Modular Service Tool is a top quality service tool that will stand upto the demands of the typical job site environment for many years.

Page 4: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces4

Modular Service ToolWether you have a Stand Alone, Interconnected or Networked System,the Modular Service Tool always connects to an HVAC unit controllervia a prefabricated cable that is supplied with the service tool. The Modu-lar Service Tool cable is terminated on both ends with a mini DIN con-nector. Attach one end to the Modular Service Tool and the other end tothe mini DIN connector on the HVAC unit controller. If this is an Inter-connected System, all controllers that are interconnected with commu-

System Connectionsnications cable can be programmed from any HVAC unit controller onthe loop. If this is a Networked System, all controllers on the entireNetworked System can be programmed from one HVAC unit control-ler.

Be sure that the Modular Service Tool has fresh batteries installed orthat it is connected to a power source using the supplied power packbefore attempting any programming of the controller. See Figure 3 forconnection details.

Figure 3: Modular Service Tool

Typical Controller Board

Connector Cable

Modular Service Tool

Female DIN Connector

T Block Baseerminal(Remove Terminal Block)

PL101904 Adapter Board

Optional Connection ForControllers Without DIN Connector

Male DIN Connector

Mode

Selection

ENTER

CLEARESC

PREV NEXT

DOWN

UP

654

DEC

7

0

8

1 32

9

MINUS-

STATUS

SETPOINTS

SCHEDULES

CONFIGURATION

ALARMS

ON

OVERRIDES

BALANCE - TEST

Be Sure The Modular ServiceTool Is Connected To TheSupplied Power Pack Or HasFresh Batteries Installed BeforeAttempting Programming Of TheController. Be Sure The Power IsTurned Off On The ModularService Tool Before ConnectingThe Cable To The Controller.

The Modular Service Tool Can Be Connected To MostControllers By Plugging One End Of The SuppliedCable Into the Modular Service Tool DIN ConnectorAnd The Other End Into The DIN Connector On TheControllers.

Some Controllers Without DIN Connectors RequireUse Of The Supplied PL101904 Adapter Board ShownAbove. To Connect With Adapter Board, First UnplugCOMM Terminal Block From Controller Board. PlugPL101904 Adapter Board Terminal End Into TerminalBlock Base On Controller. Plug DIN Connector CableInto DIN Connector On PL101904 Adapter Board . SeeOptional Connection For Controllers Without DINConnector Above For Illustration Of This Connection.

Power On Button

TSHLDR

COMM

Page 5: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

5

Modular System ManagerPower and communications are supplied to the System Manager via amodular/pigtail cable that is supplied with the System Manager. Thiscable has a male Molex connector on one end for connection to thefemale Molex connector on the System Manager. On the other end are 5insulated wires with a drain wire which are used for connection to the

communication and power wiring from the transformer and from thelocal loop communications terminal on the WMVAV controller or anyVAVBOX controller’s communication terminal. A class II, 24 VACtransformer (by others) rated at 6 VA or greater load capacity is requiredfor powering the System Manager.

See Figure 4 & 5 for System Manager connection and wiring details.

Use Supplied ModularCable With Stripped EndsFor Connection To TerminalBlock And Transformer

Modular System ManagerBack of Front Cover

P1

P2

VAR1

U1

3

RS-485PCOMM

R14

U6

V62C518256L-70PV62C518256L-70P

CX

11

CX

12

CX

12

U12

U11

CX7

PA

L

EPRO

MRA

M

CX

13

CX

13

75176

U8

74HC573

CX

8

RN1

SC1

YS101830PREV.2PMODULARPSYSTEMMANAGER

PC

B8

0C

55

2-5

-16

WPP4

42

86

0=

2/5

PC

B8

0C

55

2-5

-16

WPP4

42

86

0=

2/5

PD

fD9

72

2V7

YPD

fD9

72

2V7

YC2

U7

X1

C1

R1

R4

EW

DO

G

PH

ILIP

S

X2

C3

PH

ILIP

SPH

ILIP

S

U3

CX5

R3

R9

85

83

CX6

D3

U424

C1

28

24

C1

28

CX4

74HC259

U1

U2

CX

2

R3

R2

U14

C8

CX

9

C7

47

0uF5

0v

10

00

uF1

0v

47

0uF5

0v

47

0uF5

0v

10

00

uF1

0v

R12

R11

CO

MM

OU

TC

OM

MO

UT

CO

MM

INC

OM

MIN

D6

C4

R13

MC

34

06

4A

MC

34

06

4A

U9

99

36

D5

L1

U1

0

74HC54074HC540

CX

14

C6

P3

CX10

C5

74

HC

92

3

R10

D4

CX

3

82B715

PJ1

D2

R6

R5

D1

U3

DSPY1

R7

RV1

WHITE (T)

DRAIN WIRE (SHLD)

BLACK (R)RED (24 VAC)

BROWN (GND)

GREEN (GND)

Class 2 TransformerRated For 6 VA Minimum

WMVAV Controller BoardConnection Shown

May Also Be Connected To AnyVAVBOX Controller On Loop

TSHLDR

Figure 4 Schematic for Wiring System ManagerUsing Modular Cable Pigtail

Figure 5: Detailed Typical System Manager WiringUsing Modular Cable Pigtail

Modular System ManagerBack of Front Cover

P1

P2

VAR1

U1

3

RS-485PCOMM

R14

U6

V62C518256L-70PV62C518256L-70P

CX

11

CX

12

U12

U11

CX7

PA

L

EPRO

MRA

M

CX

13

75176

U8

74HC573

CX

8

RN1

SC1

YS101830PREV.YS101830PREV.2PMODULARPSYSTEMMANAGER

PC

B8

0C

55

2-5

-16

WPP4

42

86

0=

2/5

PC

B8

0C

55

2-5

-16

WPP4

42

86

0=

2/5

PD

fD9

72

2V7

YPD

fD9

72

2V7

YC2

U7

X1

C1

R1

R4

EW

DO

GEW

DO

G

PH

ILIP

S

X2

C3

PH

ILIP

SPH

ILIP

S

U3

CX5

R3

R9

85

83

CX6

D3

U424

C1

28

24

C1

28

CX4

74HC259

U1

U2

CX

2

R3

R2

U14

C8

CX

9

C7

47

0uF5

0v

10

00

uF1

0v

47

0uF5

0v

10

00

uF1

0v

R12

R11

CO

MM

OU

TC

OM

MO

UT

CO

MM

INC

OM

MIN

D6

C4

R13

MC

34

06

4A

MC

34

06

4A

U9

99

36

D5

L1

U1

0

74HC540

CX

14

C6

P3

CX10

C5

74

HC

92

37

4H

C9

23

R10

D4

CX

3

82B71582B715

PJ1

D2

R6

R5

D1

U3

DSPY1DSPY1

R7

RV1

Class 2 TransformerRated For 6 VA Minimum

(By Others)

Handy Box , Conduit,Fittings, Wire Nuts,Butt Splices Etc.,

( By Others)

Controller Board

TSHLDR

HZ000121Modular Pigtail CableSupplied With System Manager

WH

ITE

(T)

BL

AC

K(R

)

RED(2

4 VAC)

BROWN

(GND)

GR

EE

N(G

ND

)

Drain Wire (Shld)

LINEVOLTAGE

LINE VOLTAGE

2-Conductor Shielded18-GuageCommunications Wire

Page 6: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces6

General Programming InformationThe Modular Service Tool or the System Manager allow the user toview any temperature or output condition and change any setpoint tofine tune the operations of the total system. All keypad operations aresimple and straightforward, utilizing non-cryptic plain English messages.

Display Screens & Data Entry KeysThe System Manager display screens and the Modular Service Tooldisplay screens are very similar. For most setpoints and modes the onlydifference between using the Service Tool and the System Manager is afew differences in the function of the keypads. In this manual where adifference in the keypad input or the screens displayed exists betweenthe two operators interfaces, both screens or keypads will be shown.See the chart below for a list of the keypad descriptions and functions.

Key FunctionKeypadDescription

System Manager Modular Service Tool

ESC Used to exit from screensor from data entry. Usethis screen to return to themain menu from anyscreen in the system

Same function asSystem Manager

ENTER This key is used to close adata entry field and

advance to the next itemor screen

Same function asSystem Manager

Clear If a data entry mistake ismade, press this key to

clear the data entry fieldand start over

Same function asSystem Manager but

also turns off thepower to the Service

Tool when on themain menu screen

Minus If a setpoint with anegative value is required,

press this key for theminus sign

Same function asSystem Manager

DEC Press this key whenentering data that requires

a decimal point

Same function asSystem Manager

⇐ ⇒ Steps the user to the nextcontroller on the loop on

interconnected ornetworked systems

Same function asSystem Manager

⇑⇓

Steps the user backward orforward through the

screens

Same function asSystem Manager

Mode Selection ButtonsBoth the System Manager and the Modular Service Tool are providedwith “Mode Selection Buttons” . These buttons give the user instantaccess to the specific mode desired without having to scroll throughseveral menu screens to get there. The Modular Service Tool has 2extra function keys (“Configuration” and “Balance-Test”) that are notavailable on the System Manager.

Operator Interfaces ComparisonIn order to configure and program the WattMaster VAV System control-lers you must have a central operators interface or a personal computerwith the Prism computer front end software installed. Two different cen-tral operators interfaces are available for programming of the WattMas-ter VAV Controls System. You may use either the Modular Service Tooland/or the Modular System Manager to access the status and set-points of any controller on your communications loop.

Mode

Selection

ENTER

CLEARESC

PREV NEXT

DOWN

UP

654

DEC

7

0

8

1 32

9

MINUS-

STATUS

SETPOINTS

SCHEDULES

CONFIGURATION

ALARMS

ON

OVERRIDES

BALANCE - TEST

ENTER

CLEARESC

PREV NEXT

DOWN

UP

654

DEC

7

0

8

1 32

9

MINUS-

STATUS

SETPOINTS

SCHEDULES

ALARMS

OVERRIDES

System Manager

Modular Service Tool

Modular System Manager

Page 7: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

7

Mode Selection ButtonsButtonDescription

Modular Service Tool System Manager

STATUS Pressing this buttontakes you directly to

the controller“Status” screens

Pressing this buttontakes you directly to

the controller“Status” screens

SETPOINTS Pressing this buttontakes you directly to

the controller“Setpoints” screens

Pressing this buttontakes you directly to

the controller“Setpoints” and“Configuration”

Menu

SCHEDULES Pressing this buttontakes you directly to

the controller“Schedules” screens

Pressing this buttontakes you directly to

the controller“Schedules” screens

OVERRIDES Pressing this buttontakes you directly to

the controller“Overrides” screen.See the “OverrideButton” section ofthis manual for adescription of this

function.

See Note 1 below.

Pressing this buttontakes you directly to

the controller“Overrides” screen.See the “OverrideButton” section ofthis manualfor a

description of thisfunction.

See Notes 1 & 2below.

ALARMS Pressing this buttontakes you directly to

the controller“Alarms” screen.See the “Alarms

Button” section ofthis manual for adescription of this

function.

See Note 1 below.

Pressing this buttontakes you directly to

the controller“Alarms” screen.See the “Alarms

Button” section ofthis manual for adescription of this

function.

See Notes 1 & 2below.

CONFIGURATION Pressing this buttontakes you directly to

the controller“Configuration”

screens

Not AvailableUse “Setpoints”

Button To AccessMenu

BALANCE-TEST Pressing this buttontakes you directly to

the controller“Balance-Test”

screens

Not Available

Notes:1.) This button only functions when the system is configuredfor “Network Mode” or “Multiple MGRS Mode”. It will notfunction in ‘Stand Alone Mode”.

2.) The “Search For Units” function must be performed on theSystem Manager upon initial system setup before this functionwill be available. See the “System Manager NM & MM LoopSearch” section of this manual for complete instructions onperforming a loop search.

Service Tool And System Manager

Entering Unit ID (Address)

With both the Modular Service Tool and the Modular System ManagerYou must enter the ID (Address) of the controller you wish to program

Unit Selection Enter Unit ID# Selected ID#: xxxx

With the main menu screen displayed, press the function key associatedwith the operation (setpoints, configuration, etc.) you want to perform.The screen shown above will appear asking you to enter a unit I.D.#(controller address). Put in the ID# of the controller you wish to com-municate with then press the “ENTER” key.

If this is Multiple Loop Network System the Unit ID is actually twoseparate numbers, combined into one value. The first part of the num-ber contains the Loop Address at which the controller is located. Thesecond part of the number contains the actual controller address. SeeExamples #1 & #2 below.

EXAMPLE #1You would like to view the 3rd controller on the 5th loop. Enter “503”as the Unit ID.

EXAMPLE #2You would like to view the 12th controller on the 24th loop. Enter “2412”as the Unit ID

EXAMPLE #3You would like to view the only controller on the loop. Enter 1 as theUnit ID. No loop number is required since there is only one loop.

Hit the “Enter” key after entering the unit ID. If you are using the ModularService Tool you will be taken directly to the first screen for the opera-tion you are trying to program.

Modular System Manager

System Manager Initialization Screens

When the System Manager is powered up, the first screen displays thecurrent version of the software installed in your System Manager andwhether your system is configured for Network or Stand-Alone opera-tion. On a Networked System, all controllers on the communicationsloop are available for programming by entering their loop address (ID).

If the System Manager is configured for Stand-Alone operation, onlythe HVAC unit controller that the System Manger is connected to isavailable for programming. The Stand-Alone feature is only used forservicing and testing. For normal operation the System Manager mustbe configured for Network mode.

Page 8: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces8

InitializingSystem Manager vX.XX Wattmaster Controls Network Mode

System Manager vX.XX Monday Operations 09/09/99 04:26 PM NM Outdoor Air 87°F

The screen above will appear a few seconds later. The last line of thedisplay will have the letters SA (Stand Alone Mode), MM (MultipleSystem Manager Mode) or NM (Network Mode) followed by the cur-rent outdoor air temperature. The System Manager normally ships fromthe factory set for NM (Network Mode). If you have only one SystemManager, the system must be set for NM (Network Mode). If you havemultiple System Managers on your system, the system must be set forMM (Multiple System Managers Mode). If you believe your system isincorrectly configured, please follow the instructions that follow. If yoursystem is configured correctly, proceed to the System Manager Net-work Mode Loop

Configuring For Stand-Alone Mode, MultipleSystem Managers Mode or Network Mode

As previously described the System Manager must be configured forthe correct mode of operation for your system. Again, there are 3 modesof operation available for the WattMaster VAV System. They are “StandAlone Mode”, “Multiple MGRS Mode” or “Network Mode”.

Look at the bottom line of the display as mentioned in the previousparagraph and determine which one your System Manager is currentlyset for. If you have a single System Manager for your entire system,then you need to operate in “Network Mode” and the first two charac-ters on the bottom line of the display should be “NM”. If you havemultiple System Managers on your system then you need to operate in“Multiple MGRS Mode” and the first two characters on the bottomline of the display should be “MM”. The System Manager should neverbe set to “Stand-Alone” mode unless you have been instructed to con-figure this setting by WattMaster Technical Support.

If your display indicates a different mode than the one you need, pressthe “Enter” key and the following screen will appear.

1) Set Time & Date 2) Communications ->) Next MenuESC) Exit Menu

Press the “2” key on the keypad to enter the communications screen.

THIS ACTION REQUIRESA SPECIAL HIGH LEVEL PASSCODE CLEARANCE Enter: xxxxxxx

Enter the seven digit passcode “2337377” to access the next screen.These seven digits spell the word “ADDRESS” on your telephone key-pad if you forget what they are.

You will then see the screen below displayed. You must use the keypadto enter the correct number for the mode of operation needed for yoursystem.

0) Stand Alone1-60) Multiple MGRS 63) Network SystemEnter Mode Of Op:.xx

For “Multiple MGRS Mode” enter the address at which you want thisparticular System Manager to be set. When multiple System Managersare used on a local loop, each must be set with a unique address differ-ent from any other device on that loop. You must perform this sameoperation again for each System Manager installed. If you want one ofthese System Managers to be able to indicate alarms and overrides forthe entire system you must enter “63” for “Network Mode” on thatparticular System Manager.

For “Network Mode” (or as explained above for Multiple SystemManagers when one is to be set to indicate alarms and overrides) enter“63”.

For “Stand Alone Mode” enter “0”.

Once you have the correct number per the display above displayed,press the ENTER key. The following screen will appear telling you thatyou have changed the system mode. Press any key on the keyboard toexit this screen.

You Have Changed The System Manager Mode Press Any Key To Continue

General Programming Information

Page 9: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

9

System Manager NM & MM Mode Loop Search

When the System Manager is configured for Network Mode a loop searchmust initially be performed for the System Manager to recognize alarmsor overrides. Also, when you have a system that has multiple SystemManagers and you have one of the System Managers set to (63) Net-work Mode for alarm and override indication, you must also perform aloop search for that System Manager. This allows the System Managerto be aware of all alarms and overrides for all local loops on the entiresystem. .

Note: The Loop Search function is only required when usingthe System Manager(s), not the Modular Service Tool.

To access the Loop Search screen, do the following. From the mainmenu screen press enter to display the following screen.

1) Set Time & Date 2) Communications ->) Next MenuESC) Exit Menu

Press the “Next” arrow key. The following screen will be displayed.

1) Change Passcodes 2) Loop Search<-) Prev. MenuESC)Exit Menu

Press the “2” .The following screen will be displayed.

Loop Search Current Loop = XX Loops Found = XX Searching

The System Manager will now proceed to search all loops to find theMiniLink Polling Devices that are connected to the system. The screenwill display the current loop being searched and the number of loopscurrently found.

Once the search is completed the following screen will be displayed.

Loop Search Finished Loops Found = XX Press ESC to Exit

The screen will display the number of loops found on your system. Theinformation will be saved into the System Manager’s memory. No fur-ther loop searches will be required unless an additional MiniLink Poll-ing Device is added to the Network System.

System Manager Alarm Search

The System Manager can be used to search for all active alarms on thesystem. The MiniLink PD must be configured to allow for “Alarm Poll-ing” for each controller that alarming is desired on for this function towork. See the MiniLink PD programming section of this manual forsetting information. Press the “Alarm” key. The Unit Selection screenbelow will be displayed. Enter the Unit ID of any unit on the system andpress “Enter”. This is the unit ID of where the alarm search begins. Theentire system is searched from this point.

Unit Selection Enter Unit ID# Selected ID#: xxxx

The following screen will appear. The System Manager will search forany active alarms on the entire system.

Alarm Screen

SEARCHING!

After the System Manager completes it’s search, it will list the first uniton the system that currently has an active alarm. Press “Enter” to scrollthrough all the alarms on that particular unit. To move to the next unit orback to the previous unit use the “Prev” or “Next” arrows to move be-tween units with alarms.

Alarm Search ScreenLoop = 1 Unit = 59Space Sensor Failure

To clear any alarms that are found you must fix the problem indicated inthe alarm. Once the problem is fixed, the alarm will clear from the screenthe next time the unit is polled.

Page 10: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces10

System Manager Override Search

When a space sensor with override option is used with any VAVBOXcontroller or WMVAV controller, the System Manager can determineand report any controllers which are currently operating in an overridecondition. The MiniLink PD must be configured to allow for “AlarmPolling” for each controller that alarming is desired on for this functionto work. See the MiniLink PD programming section of this manual forsetting information

To access the Space Sensor Overrides screen, press the “Override” but-ton located on the System Manager . A screen will appear asking you toenter a unit ID. Enter an ID for any active controller on the system andpress "Enter". The following screen will appear.

Overrides Screen

SEARCHING!

After the System Manager completes its search, it will list the first uniton the system that is currently in the override mode. Press the previousor next button to scroll through all units that are in the Override Mode.

Overrides ScreenLoop = 1 Unit = 59 Override Unit

Anytime you enter a unit ID with the Modular System Manager youwill be asked for a passcode. Passcodes are not required to view StatusScreens. The screen below will appear if this action requires passcodeclearance.

System Manager Passcodes

Anytime you enter a unit ID with the Modular System Manager youwill be asked for a passcode. Passcodes are not required to view StatusScreens. The screen below will appear if this action requires passcodeclearance.

THIS ACTION REQUIRES PASSCODE CLEARANCEEnter Passcode: xxxx

The System Manager has two levels of user access. Level 1 users arelimited to viewing or changing the Time, Date, Operating Schedulesand Heating and Cooling Setpoints. Level 2 users have complete sys-tem access. Any status or setpoint field can be read or reset from theSystem Manager.

These two levels of passcodes are programmable by any Level 2 user.The default Level 1 passcode is “1111” and the default Level 2 passcodeis “2222.”

If you wish to change either Level 1 or Level 2 passcodes please see theinstructions that follow.

From the main status screen press "Enter", The following screen willappear.

1) Set Time & Date 2) Communications ->) Next MenuESC) Exit Menu

Press the “Next” arrow key. The following screen will be displayed.

1) Change Passcodes 2) Loop Search<-) Prev. MenuESC)Exit Menu

Press the “1” .The following screen will be displayed.

Enter New Passcode Level 1.....: xxxx Level 2.....: xxxx [Must Be 4 Digits]

This screen allows you to enter new Level 1 or Level 2 passcodes. Theactual digits in your passcodes are never displayed. An “X” is used as aplace holder for each digit entered. Passcodes must always be four dig-its in length, so the usable range of numbers is 1000 to 9999.

Caution: If you change the Level 2 passcode and cannotremember what it is, you will be locked out ofyour system!

Modular Service ToolThe Modular Service Tool is very similar to the System Manager in itsoperations as stated previously. Two exceptions to this are that the Ser-vice Tool unlike the System Manager does not check the entire systemwhen performing an “Alarm” or “Override” search and it does not haveany passcoding capability.

Note: When the Alarms or Overrides buttons are pressed onthe Modular Service Tool it will search only the loopnumber of the unit ID that has been entered, thereforeeach local loop must be searched individually to accessall alarms or overrides on the system.

General Programming Information

Page 11: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

11

Modular Service Tool Initialization Screen

After connecting the Service Tool to the controller with the suppliedcable, press the “On” key. The following screen will appear.

Service Tool vX.XX Monday Operations 09/09/02 04:26 PM Stand Alone Mode

Configuring The Modular Service Tool ForNetwork Or Stand-Alone Operation

As with the System Manager described previously, you must determineif the mode displayed is correct for your system. Normally for mostapplications the words “Network Mode” should be displayed in thewindow. If it has been configured for Stand Alone mode you will seethe words “Stand Alone Mode” on the bottom line of the display. StandAlone Mode is only used when servicing or troubleshooting and is nor-mally not used for general setup and programming as it only allows theuser to access the controller it is attached to and not the entire net-worked system

If your display indicates a different mode than the one you need, pressthe "Enter" key and the following screen will appear.

1) Set Time & Date2) Communications3) Energy SavingESC) Exit Menu

Press the “2” key on the keypad to enter the communications screen.

0) Stand Alone 1) Network System

Enter Mode Of Op:.xx

As the screen indicates, press the right or left arrow keys to select theproper mode of operation. When you are finished press “Enter” tomove back to the main menu screen.

You Have Changed The System Mode Press Any Key To Continue

Modular Service Tool Alarm Search

First, press the “Alarm” key. The Unit Selection screen below will bedisplayed. Enter the Unit ID of any controller on the system and press“Enter”. This is the unit ID of the loop where the alarm search will bedone. Unlike the System Manager, only the alarms on this loop will besearched, not the entire system.

Unit Selection Enter Unit ID# Selected ID#: xxxx

The following screen will appear. The System Manager will search forany active alarms on the local loop.

Alarm Screen

SEARCHING!

After the Modular Service Tool completes it’s search, it will list the firstunit on the local loop, whose ID was entered, that currently has an ac-tive alarm. Press “Enter” to scroll through all the alarms for controllerson that particular loop. To move to the next controller or back to theprevious unit use the “Prev” or “Next” arrows to move between con-trollers with alarms on the loop.

Alarm Search ScreenLoop = 1 Unit = 59Space Sensor Failure

To clear any alarms that are found you must fix the problem indicated inthe alarm. Once the problem is fixed, the alarm will clear from the screenthe next time the unit is polled.

Modular Service Tool Override Search

When a space sensor with override option is used with any VAVBOXcontroller or WMVAV controller, the Modular Service Tool can deter-mine and report any controllers which are currently operating in an over-ride condition on the local loop whose ID (Address) has been enteredbefore running the search.

To access the Space Sensor Overrides screen, press the “Override” but-ton located on the Modular Service Tool . A screen will appear askingyou to enter a unit ID. Enter an ID for any active controller on theparticular local loop you wish to search and press "Enter". Unlike theSystem Manager, only the overrides on this loop will be searched, notthe entire system. The following screen will appear.

Page 12: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces12

ConfigurationIn order to correctly setup the WMVAV controller you must first con-figure several parameters in regard to the type of HVAC unit and systemyou have installed. Most of these values and operating parameters areonly set once, at the initial system setup and are never changed.

System Manager InstructionsFrom any menu screen press the “Setpoint” key. The unit selection screenwill appear requesting that you enter the unit ID number. Enter the cor-rect unit ID number of the WMVAV controller you want to configureand hit the “Enter” key. You will see the screen shown below.

1)Change Setpoint2)Configure Unit3)Damper ForceESC) Exit Menu

Press “2” on the keypad to enter Configuration Screen #1.

Modular Service Tool InstructionsFrom any menu screen press the “Configuration” key. The unit selec-tion screen will appear requesting that you enter the unit ID number.Enter the correct unit ID number of the WMVAV controller you want toconfigure and hit the “Enter” key. You will then see unit configurationscreen #1.

Configuration Screen #1

WMVAV Config ID 59Constant Volume Mode Active : NO [0=NO 1=Yes]

This HVAC unit can be configured to operate as a Constant Volume orVAV unit. The Constant Volume Mode does not provide Static PressureControl. You can install a Duct Pressure Sensor on a Constant Volumeunit and only monitor the Static Pressure. This is the only mode thatsupports dehumidification.

Configuration Screen #2

WMVAV Config ID 59 Controlling Sensor SUPPLY AIR Press”0” to Change

Press the “0” key to select the desired method of control and the thirdline of the display will change text to show which sensor has been se-

lected as the Controlling Temperature for the WMVAV controller. Avail-able selections are:

SUPPLY AIR Supply Air Sensor(Occupied Cooling withMorning Warm-up)

*RETURN AIR Return Air Sensor(Occupied Cool, Heat &Vent)

SPACE TEMPERATURE Space Temperature Sensor(Occupied & UnoccupiedCool, Heat & Vent)

OUTSIDE AIR Outdoor Temperature Sensor(Occupied Cool, Heat &Vent)

LOCAL ANALOG VALUE Local Analog Value

* On WMVAV controller codes earlier than version 1.01, if youselect “RETURN AIR” you will have Occupied Cool, Heat &Vent as opposed to Occupied Cooling & Venting Only as theprevious code provided.

Configuration Screen #3

WMVAV Config ID 59 Economizer Control By This AHU: YES [0=NO 1=YES]

If your AHU has outside air dampers, it is recommended that you allowthe WMVAV controller to modulate these dampers in the economizermode so that it can be used as the first stage of cooling. If you don’thave outside air dampers, or you decide to let a separate controller main-tain these dampers, select NO for this option.

Configuration Screen #4

WMVAV Config ID 59 Fan Cycle Mode Needed: Yes [0=NO 1=Yes]

If you need proof of airflow before allowing any heating or coolingstages to operate, install a differential pressure switch with a contactclosure that is connected to analog input #7 and select this option. Ifthis option is not selected, the WMVAV controller assumes there is ad-equate airflow anytime the fan is running and ignores this signal.

Programming The WMVAV Controller

Page 13: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

13

Configuration Screen #5

WMVAV Config ID 59Proof of Flow Switch Installed: No [0=NO 1=Yes]

If you need proof of airflow before allowing any heating or coolingstages to operate, install a differential pressure switch with a contactclosure that is connected to analog input #7 and select this option. Ifthis option is not selected, the WMVAV controller assumes there is ad-equate airflow anytime the fan is running and ignores this signal.

Configuration Screen #6

WMVAV Config ID 59 OA Humidity Sensor Installed: No [0=NO 1=Yes]

If your economizer control requires the use of the Wetbulb Temperatureto enable or disable it, you must install a humidity sensor on analoginput #5 and select this option. If you require the Remote Signal todetermine the occupied mode of operation, you will need to move theremote signal to Input #2 on the Analog Input Expansion Board.

Configuration Screen #7

WMVAV Config ID 59 Dehumidification Installed: No [0=NO 1=Yes]

You can monitor a wet contact closure on the first binary input on the 4Binary Input expansion board and whenever it closes, the Gas Reheatrelay will be activated. This assumes you are in a cooling mode. TheGas Reheat does not activate if the WMVAV controller is in the heatingmode. The option is only available on units that are configured for Con-stant Volume Mode. If you are controlling static pressure (VAV Mode)then this option is ignored.

Configuration Screen #8

WMVAV Config ID 59 Relief Pr. Control Installed: No [0=NO 1=Yes]

If you need to control building pressure, select this option by entering a‘1’ and connect the Relief Pressure Sensor to the Analog ExpansionInput #4. The Relief Fan VFD Signal is also found on the Analog InputExpansion module as the only analog output on that board.

Configuration Screen #9

WMVAV Config ID 59 Relief Pr. Control Reverse Acting: No [0=NO 1=Yes]

The Relief Pressure Control described in the previous paragraph can beconfigured for reverse acting operation by setting this selection to “Yes”.With the standard configuration (“No”) a relief fan VFD and/or Ex-haust Damper would modulate towards its maximum high speed and/oropen position to decrease building pressure. If you select reverse actingoperation (“Yes”) on a decrease in building pressure the HVAC unit OAdamper would be modulated towards its maximum open position toincrease building pressure.

Configuration Screen #10

WMVAV Config ID 59Reset Setpoint UsingInput Voltage SignalPress “0” To Change

Press the “0” key to select the desired method of resetting the Coolingand Heating Mode Supply Setpoint and the third line of the displaywill change text to show what type of method has been selected to con-trol the Reset Setpoint. Available selections are:

Input Voltage SignalOutdoor Air SensorSpace SensorFan VFD PercentageLocal Analog ValueReturn Temp Sensor

Configuration Screen #11

WMVAV Config ID 59CO2 Sensor Installed Sensor Type: 0[0=NONE 1=ma 2=vdc]

You can install a CO2 Sensor on this HVAC unit to monitor the Carbon

Dioxide levels and/or to provide for Indoor Air Quality (IAQ) control.If you just want to monitor the level, enter the same Maximum Econo-mizer Position that you set for the Minimum Position and it will not bereset as the CO

2 level increases. If you do want IAQ control, set the

desired Maximum Economizer Position to reset up to during high lev-els of CO

2. The factory supplied sensor provided for the CO

2 readings is

a 0-10 VDC, 0 to 2000 PPM sensor. Be sure you enter a “2” if you areusing the default sensor.

Page 14: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces14

Programming The WMVAV ControllerConfiguration Screen #12

WMVAV Config ID 59 CO2 Sensor Maximum Reading: 2000 PPMEnter 0 If No Sensor

If you install the default CO2 sensor, it will be a 0-10 VDC device that

provides 0-2000 PPM readings. Make sure this is set to the 2000 PPMlevel unless you have installed your own sensor with a different scalingrange.

Configuration Screen #13

WMVAV Config ID 59Air to Air Heat Pump Control: NO [0=NO 1=YES]

The WMVAV controller can be configured to operate as an Air To AirHeat Pump Controller. If you make this selection, the same relays areused to stage the compressors in both the heating and cooling modes.The only difference is that a separate Reversing Valve relay will acti-vate in the heating mode to enable heating to occur. You must configureat least one relay for the reversing valve.

You can also configure for an Auxiliary Heat relay that will activatewhenever the supply air drops below the supply setpoint by 5°F, toprovide heat when the outdoor air is too cold for the heating mode tooperate correctly.

Configuration Screen #14

WMVAV Config ID 59Broadcast Time Clockto Loop Units: NO [0=NO 1=YES]

This enables the WMVAV Controller to send its real time clock infor-mation to all controllers on the local loop. This must be used whenconnecting VAVBOX Controllers on the local loop, but can be used tosynchronize clock time in all controllers on the local loop.

Configuration Screen #15

WMVAV Config ID 59 Broadcast Outside Temperature: NO [0=NO 1=YES]

This enables the WMVAV Controller to send its outdoor air tempera-ture reading to all other controllers on the entire system. It is specifi-cally used when more than one HVAC unit is installed, and only oneoutdoor air sensor is used to supply its signal to all controllers.

Configuration Screen #16

WMVAV Config ID 59 Broadcast Supply Temperature: NO [0=NO 1=YES]

This enables the WMVAV Controller to send its supply air temperaturereading to all controllers that do not have there own sensor on the localloop. This is standard for VAVBOX applications.

Configuration Screen #17

WMVAV Config ID 59 Broadcast Humidity Reading: NO [0=NO 1=YES]

This enables the WMVAV Controller to send its relative humidity read-ing to all other controllers on the entire system. It is specifically usedwhen more than one HVAC unit is installed, and only one relative hu-midity sensor is used to supply its signal to all controllers.

Configuration Screen #18

WMVAV Config ID 59 Broadcast Internal Schedule: NO [0=NO 1=YES]

This enables the WMVAV Controller to send its Occupied and Unoccu-pied status to the VAVBOX Controllers on the local loop.

Configuration Screen #19

WMVAV Config ID 59 Broadcast Status Fan & Heat: NO [0=NO 1=YES]

This enables the WMVAV Controller to send status information onwhether the HVAC unit main fan is running, or if it is in heat mode, tothe VAVBOX Controllers on the local loop. This enable is requiredwhen VAVBOX Controllers have heating stages or are fan-powered.

Page 15: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

15

Configuration Screen #20

WMVAV Config ID 59Broadcast VAV Boxes Force To Max: NO [0=NO 1=YES]

When “1=YES” is selected all VAVBOX controllers connected to thisWMVAV controller will be forced to their “Maximum Airflow” posi-tion during the Morning Warm-up mode of operation. Select “0=NO” ifyou do not want this to occur. See the VAVBOX controller setpointscreens for setting of the “Maximum Airflow” position.

Configuration Screen #21

WMVAV Config ID 59Broadcast VAV Boxes Force To Fix: NO [0=NO 1=YES]

When “1=YES” is selected all VAVBOX controllers connected to thisWMVAV controller will be forced to their “Fixed Airflow” positionduring the Morning Warm-up mode of operation. Select “0=NO” if youdo not want this to occur. See the VAVBOX controller setpoint screensfor setting of the “Fixed Airflow” position.

Configuration Screen #22- #41

WMVAV Config ID 59Stage Configurations Rly xx: Not UsedPress “0” to Change

The following 20 screens allow you to set the four relays on the WMVAVcontroller board and up to sixteen additional relays when relay expan-sion board(s) are used.

The first relay on the WMVAV controller is always reserved for theSupply Fan. The remaining four relays on the main board and the addi-tional sixteen relays on the expansion relay modules can be configuredby pressing the “0” key to change the relay to the desired configuration.Available relay configurations are listed in the table that follows.

Available RelayConfigurations

Description Of Use

Heat Stage On/Off Control Of A Heating Stage(8 Stages Max)

Cool Stage On/Off Control Of A Cooling Stage(8 Stages Max)

Rev Valve On/Off Control Of A Reversing Valve

Exhaust Fan On/Off Control Of An Exhaust Fan orExhaust Damper

Re-Heat On/Off Control Of A Re-heat Device

Warm-up Mode On/Off Signal That CausesWattMaster Controlled VAV Boxes To

Drive Open to Maximum Airflow

Pre-heater On/Off Control Of A Pre-heat Device

Economizer On/Off Control Of An Economizer

Alarm Relay On/Off Indication Of Alarms

Override On/Off Indication Of The Unit BeingIn Override Mode

Occupied On/Off Indication Of The Unit BeingIn Occupied Mode

The WMVAV controller does not require that you start configuring yourheating or cooling stages first and it doesn’t require that you utilizeconsecutive relays until all heating or cooling stages have been defined.All relays can be used for any of the above options in any order youdesire. This method allows the greatest flexibility in the field, but itrequires close attention to the wiring of the heating and cooling stagesto prevent incorrect and possibly harmful operation.

The controller assumes there will only be one relay configured for Morn-ing Warm-up Mode although it doesn’t prevent multiple relays frombeing selected. Since this relay is used to send a signal to VAV boxes todrive to their maximum airflow position, redundant relays are not re-quired.

Relays #2 through #21 can be individually configured. This should beenough to handle up to 8 stages of heating and 8 stages of cooling onlarge HVAC units. Only the heating and cooling relays can be config-ured with multiple outputs. If any other option is selected more thanonce, it will simply activate redundant relays but no multiple stagingwill occur.

Page 16: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces16

Setpoint Screen #2

WMVAV Spts ID 59Unoccupied SetbacksCooling SetUp: xx°FHeating SetBk: xx°F

During the unoccupied mode these values will be added to the coolingsetpoint and subtracted from the heating setpoint. These settings areonly used if the controller has been configured to utilize a Space Tem-perature Sensor.

Description Minimum Default Maximum

Cooling SetUp 0° F 10° F 30° FHeating SetBk 0° F 0° F -30° F

Setpoint Screen #3

WMVAV Spts ID 59 HVAC Mode SelectDeadband....: xx.x°F

The HVAC Mode Select Deadband is the amount of error from set-point required to activate the heating or cooling mode of operation.This assumes the Return Air or Space Temperature are the controllingsensors. If the Supply Air is the controlling sensor then this setpoint isnot used.

Description Minimum Default Maximum

Deadband 0.1° F 1.0° F 10.0° F

Setpoint Screen #4

WMVAV Spts ID 59Supply Air SetpointsCooling....: xx°FHeating....: xx°F

This is the Supply Air Temperature that the HVAC unit will try to main-tain when in heating or cooling mode. The Heating Supply Air Setpointwill also be used for the Morning Warm-up Supply Air Temperature.

Description Minimum Default Maximum

Cooling 50° F 55° F 70° FHeating 60° F 140° F 200° F

SetpointsSystem Manager InstructionsFrom any menu screen press the “Setpoint” key. The unit selection screenwill appear requesting that you enter the unit ID number. Enter the cor-rect unit ID number of the WMVAV controller you want to changesetpoints for and hit the “Enter” key. You will see the screen shownbelow.

1)Change Setpoint2)Configure Unit3)Damper ForceESC) Exit Menu

Press “1” on the keypad to enter the first unit setpoint screen.

Modular Service Tool InstructionsFrom any menu screen press the “Setpoint” key. The unit selection screenwill appear requesting that you enter the unit ID number. Enter the cor-rect unit ID number of the WMVAV controller you want to changesetpoints and press the “Enter” key. You will then see setpoint screen#1.

Setpoint Screen #1

WMVAV Spts ID 59HVAC Mode SetpointsCooling......: xx°FHeating......: xx°F

If the controller is configured for Space Temperature, Return Air Tem-perature or Return Air with Day Heating control, the unit attemptsto maintain these Cooling and Heating setpoints.

If you are using a remote BAS to activate the heating or cooling modeswith contact closures on the binary input board, set these two setpointsto zero and select the supply air as the controlling sensor.

Description Minimum Default Maximum

Cooling 0° F 74° F 90° FHeating 0° F 65° F 90° F

Programming The WMVAV Controller

Page 17: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

17

Setpoint Screen #5

WMVAV Spts ID 59Both Heating/Cooling Supply Control Use Deadband Of.: xx°F

All heating and cooling stages are staged up and down based on theHeating/Cooling Supply Control Staging Deadband setpoint that is en-tered on this screen. The value that is entered here will be added to theSupply Air Temperature Setpoint to determine the high end of the rangeand subtracted from the Supply Air Temperature Setpoint to determinethe low end of the range. Staging of Heating/Cooling will occur aboveand below this deadband range. When the temperature is within thisdeadband range, no staging will occur.

Description Minimum Default Maximum

Deadband 0° F 1° F 20° F

Setpoint Screen #6

WMVAV Spts ID 59Morning WarmUp Setup Target Temp: xx°FMax Length.: xxx Min

If you need a Morning Warm-up period on your HVAC unit enter aTarget Temp you want the Return Air Temperature to achieve and theMax Length of time you want to spend in warm-up mode trying toachieve the target temperature. If you don’t need morning warm-up,simply ignore the Target Temp setpoint and enter a ‘0’ for the MaxLength value.

Description Minimum Default Maximum

Target Temp 50° F 72° F 90° FMax Length 0 Min 60 Min 240 Min

Setpoint Screen #7

WMVAV Spts ID 59Outdoor Air Lockouts Cooling:.....: xx°F Heating:.....: xx°F

If the Outdoor Air Temperature drops below the Cooling lockout set-point by 1°F, the DX cooling will be locked out until the Outdoor AirTemperature rises 1°F back above the lockout setpoint. The same 1°Fdeadband applies to the Heat lockout setpoint except the Outdoor Airlocks out the heating when it is above the lockout instead of below thelockout.

Description Minimum Default Maximum

Cooling -30° F 50° F 80° FHeating 50° F 75° F 90° F

Setpoint Screen #8

WMVAV Spts ID 59All Cooling Cuts Off If Supply Air Temp Drops Below: xx°F

If the Supply Air Temperature ever drops below this value, all coolingstages are immediately cutoff, regardless of run time. If the economizeris being controlled, it is also closed completely to prevent freezing.

Description Minimum Default Maximum

Low Cutoff 30° F 40° F 60° F

Setpoint Screen #9

WMVAV Spts ID 59All Heating Cuts Off If Supply Air Temp Exceeds....: xxx°F

If the Supply Air Temperature ever exceeds this value, all heating stagesare immediately cutoff, regardless of run time.

Description Minimum Default Maximum

High Cutoff 60° F 170° F 250° F

Page 18: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces18

Setpoint Screen #13

WMVAV Spts ID 59Economizer SetpointsMin Position.: xx %Control Rate.: xx

If the Economizer is not enabled or currently required during the occu-pied mode of operation, the outside air dampers will maintain the MinPosition setpoint to provide ventilation into the space.

The Control Rate can be used to speed up or slow down the operationof the outside air dampers to prevent hunting. Unless you actually wit-ness this damper hunting it is not recommended that the Control Ratevalue be changed. Large values speed up the damper, and small valuesslow down the damper.

Description Minimum Default Maximum

Min Position 0 % 10 % 100 %

Control Rate 10 90 99

Setpoint Screen #14

WMVAV Spts ID 59Static Spt..: x.xx”Deadband....: x.xx”Control Rate: xx Sec

The WMVAV controller uses the Fan VFD signal to maintain the StaticSpt (duct static pressure) value plus or minus the Deadband value.Adjustments to the signal are made at a rate equal to the Control Ratesetpoint, which can be used to speed up or slow down the signal toprevent hunting.

Description Minimum Default Maximum

Static Spt 0.10” WG 0.50” WG 3.0” WG

Deadband 0.01” WG 0.10” WG 1.0” WG

Control Rate 1 Sec 10 Sec 30 Sec

Setpoint Screen #10

WMVAV Spts ID 59 Heating Stages OffIf Supply Fan VFD IsBelow:.........: xx%

If the Supply Fan VFD drops below this value, the heat will stage off.The Supply Fan VFD will not be allowed to drop below this value whilethe unit is in Heating Mode unless the static pressure rises 0.5” abovethe static setpoint.

Description Minimum Default Maximum

Below SP 0 % 30 % 100 %

Setpoint Screen #11

WMVAV Spts ID 59Pre-Heat Output ONContinuous Below OATLevel........: xx°F

If your air handler has at least one heating stage and you require a lowambient protection or preheating of the air stream, you can enter a sup-ply temperature value that causes one stage of heating to come on andremain on continuous if the outdoor air drops below this level. If youdon’t want this protection do not configure any relays for this function.

Description Minimum Default Maximum

Low Ambient Level -50° F 0° F 70° F

Setpoint Screen #12

WMVAV Spts ID 59Economizer SetpointsOAT/WB Enable: xx°F

If the Outdoor Air Temperature drops below the OAT/WB Enable(Outdoor Air Temperature or the optional Wetbulb Temperature, ifit’s available), the Economizer will be enabled to operate as the firststage of cooling anytime there is a demand for cooling. If the econo-mizer is currently in a control mode, it will attempt to maintain theSupply Air Temperature at the Supply Air Cooling Setpoint.

Description Minimum Default Maximum

OAT/WB Enable -30° F 55° F 80° F

Programming The WMVAV Controller

Page 19: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

19

Setpoint Screen #15

WMVAV Spts ID 59Relief Spt..: x.xx”Deadband....: x.xx”

The WMVAV controller uses the Relief Fan VFD signal to maintain theRelief Spt value plus or minus the Deadband value. Adjustments to thesignal are made at a rate equal to the Control Rate setpoint on theprevious Static Pressure screen. If you don’t require relief pressure con-trol, simply ignore these settings.

Description Minimum Default Maximum

Relief Spt -0.20” WG 0.10” WG +0.20” WG

Deadband 0.01” WG 0.02” WG 0.10” WG

Setpoint Screen #16 & 17

WMVAV Spts ID 59 Set SAT Cool Reset VLT=0V Spt=55 VLT=10V Rst=55

WMVAV Spts ID 59 Set SAT Heat Reset VLT=0V Spt=140 VLT=10V Rst=140

These screens allow you to set values for resetting the supply air tem-perature when the unit is in cooling and/or heating mode. You canconfigure the HVAC unit to reset the supply air temperature setpointbased on the Outdoor Air Temperature, Input Voltage Signal, SpaceTemperature, Return Air Temperature or Fan VFD Percentage. Theseare the reset values that cause the supply setpoint to reset from itsminimum to its maximum value. Please note that the Supply AirSetpoint value (Spt) must be set using Setpoint Screen #4 and cannotbe changed from this screen.

*Space temperature setpoints are 74 COOL, and 72 HEAT

Space Temperature Cool Reset Example:Space Temperature (SPC) = 76 F SAT Setpoint (Spt) = 55 F

Space Temperature (SPC) = 74 F SAT Setpoint (Rst) = 65 F

Space Temperature Heat Reset Example:Space Temperature (SPC) = 72 F SAT Setpoint (Spt) = 90 F

Space Temperature (SPC) = 70 F SAT Setpoint (Rst) = 120 F

VFD Percentage Cool Reset Example:VFD Percentage (VFD) = 70% SAT Setpoint (Spt) = 55 F

VFD Percentage (VFD) = 30% SAT Setpoint (Rst) = 65 F

VFD Percentage Heat Reset Example:VFD Percentage (VFD) = 30% SAT Setpoint (Spt) = 90 F

VFD Percentage (VFD) = 70% SAT Setpoint (Rst) = 120 F

Input Voltage Cool Reset Example:Input Voltage (VLT) = 0 Volts SAT Setpoint (Spt) = 55 F

Input Voltage (VLT) = 10 Volts SAT Setpoint (Rst) = 65 F

Input Voltage Heat Reset Example:Input Voltage (VLT) = 0 Volts SAT Setpoint (Spt) = 90 F

Input Voltage (VLT) = 10 Volts SAT Setpoint (Rst) = 120 F

Setpoint Screen #18

WMVAV Spts ID 59 Start Fan Delay Timer...:10 Sec

This is the amount of time that the main HVAC unit fan will delaybefore starting after an occupied signal is initiated or after a power fail-ure. The default value is 999. With the default value the delay will beequal to the unit address multiplied by 5.

Example: Controller ID (address) 18 would cause a 90 second delaywhen the default value of 999 is used. Controller ID (address) 30 wouldcause a 150 second delay when the default value of 999 is used.

Description Minimum Default Maximum

Timer 0 Sec 999 Sec 999 Sec

Setpoint Screen #19

WMVAV Spts ID 59Mechanical Heat/CoolFailures Occur AfterNo Change For xxx M

Once a heating or cooling stage is activated, the Supply Air must changeaccordingly by 5° before this amount of time elapses, or a mechanicalfailure is assumed and an alarm is generated.

Description Minimum Default Maximum

Alarm Delay 0 Min. 15 Min. 300 Min.

Page 20: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces20

Setpoint Screen #23

WMVAV Spts ID 59Push-Button OverrideDuration....: x.x Hr

If the Space Temperature sensor contains the optional push-button over-ride then this is the amount of time the unit will revert to occupiedoperation whenever the button is pressed during the unoccupied mode.

Description Minimum Default Maximum

Duration 0.0 Hr 2.0 Hr 8.0 Hr

Setpoint Screen #24

WMVAV Spts ID 59 Slide Offset Sensor Setpoint....: x°F

If Space Temperature is used as the controlling sensor for the HVACunit and it is supplied with the optional Setpoint Slide Adjust, this isthe maximum amount the user can adjust the heating and cooling set-points up or down as the slide is moved from the center position to itsfull up or down position.

Description Minimum Default Maximum

Slide Offset Setpoint 0° F 0° F 6° F

Setpoint Screen #25

WMVAV Spts ID 59Air to Air Heat Pump Delay Before Using Aux Heating.: xx M

If you configured this air handler to control as an Air to Air Heat Pumpunit and you have auxiliary heating on this unit, you can adjust howlong the unit uses the compressor to attempt to provide heating beforeit activates the Aux Heat to supplement the compressor.

Note: On Air to Air Heat Pumps you must configure one of therelays to be used as the Reversing Valve. This output isactive anytime the unit is in the heating mode and thismode is the only time the Aux Heat will be activated, ifneeded.

Description Minimum Default Maximum

Aux Heating Delay 0 Min 3 Min 30 Min

Setpoint Screen #20

WMVAV Spts ID 59 AHU Scheduled By Schedule Number: x 0=AHU 1-7=Scheduler

Normally, the HVAC unit will use its own internal time clock and weekschedules to set the occupied mode of operation. If you have several airhandlers you can connect an external scheduling device to the commu-nications loop and program the air handler for the desired schedule tofollow. If the HVAC unit is using its internal schedule, enter a ‘0’ for theSchedule Number.

Description Minimum Default Maximum

Schedule Number 0 0 1 to 7

Setpoint Screen #21

WMVAV Spts ID 59 Maximum EconomizerPosition if High CO2Level Occurs.: xxx %

If you have configured the air handler to read a CO2 sensor, it will

override the minimum economizer position up to this position if theCO

2 level rises above its setpoint by the adjustable Reset Rng amount.

See Setpoint Screen #22.

Note: Minimum Position determined by user adjustable MinPosition Setpoint on Setpoint Screen #13.

Description Minimum Default Maximum

Max Position See Note 100% 100%

Setpoint Screen #22

WMVAV Spts ID 59CO2 Protection LimitMax Level.: xxxx PPMReset Rng.: xxxx PPM

If you configure the air handler to read a CO2 Sensor, the Max Level is

the point at which the economizer minimum position starts to resetupward. As the CO

2 level rises above the Max Level by the Reset Rng

amount, the economizer will have reset its minimum position propor-tionally up to the previously defined economizer maximum damperposition setpoint.

Description Minimum Default Maximum

Max Level 0 PPM 900 PPM 5000 PPM

Reset Rng 0 PPM 100 PPM 1000 PPM

Programming The WMVAV Controller

Page 21: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

21

Setpoint Screen #26

WMVAV Spts ID 59 Internal Schedule Optimal Start Soak Multiplier: X.X

If you have decided to use the AHU internal schedule and entered a ‘0’on the previous screen for the schedule number, you can enable thisinternal schedule to perform an optimal start. This feature requires aSpace Sensor input for the optimal start calculations. If you don’trequire optimal start or you are not using a space sensor, enter a ‘0’ forthis multiplier. If you do have a space sensor and want optimal start,enter a value greater than ‘1.0’ to enable the calculations. The soakmultiplier is used to increase the normal optimal start calculation when-ever the building has been in the unoccupied mode for 24 consecutivehours or more. If you used a 1.5 multiplier and the optimal start hadcalculated a 30 minute pre-start, the soak multiplier would add an ad-ditional 15 minutes to the pre-start for a total of 45 minutes (1.5 x 30).The system would then start 45 minutes earlier than the normally sched-uled occupied mode schedule to bring the space temperature undercontrol.

Description Minimum Default Maximum

Multiplier 0.0 0.0 5.0

Setpoint Screen #27-30

WMVAV Spts ID 59Cooling Stage DelaysStaging Up..: xx MinStaging Down: xx Min

WMVAV Spts ID 59Cooling Stage DelaysMin Run Time: xx MinMin Off Time: xx Min

WMVAV Spts ID 59Heating Stage DelaysStaging Up..: xx MinStaging Down: xx Min

WMVAV Spts ID 59Heating Stage DelaysMin Run Time: xx MinMin Off Time: xx Min

Both the Heating Stages and the DX Cooling Stages utilize Staging Upand Down delay periods between stages and Minimum Run Times andOff Times.

Both modes have their own set of staging and run delay times. TheHeating timer screens look exactly the same as the cooling except theyreference the Heating instead of Cooling.

See the Sequence of Operation Manual for information on how thesedelays and run times are used.

Description Minimum Default Maximum

Cooling Stage Up 3 Min 3 Min 15 Min

Cooling Stage Down 1 Min 1 Min 15 Min

Cooling Min Run Time 5 Min 5 Min 15 Min

Cooling Min Off Time 3 Min 3 Min 15 Min

Heating Stage Up 3 Min 3 Min 15 Min

Heating Stage Down 1 Min 1 Min 15 Min

Heating Min Run Time 2 Min 2 Min 15 Min

Heating Min Off Time 1 Min 1 Min 15 Min

Setpoint Screen #31 & 32

Sensor CalibrationSPC: xx.x° xx.x°SAT: xx.x° xx.x°RAT: xx.x° xx.x°

Sensor CalibrationOAT: xx.x° xx.x°

The Thermistor Type III sensor readings can be calibrated. Enter a Posi-tive value to increase a reading and a Negative value to decrease a read-ing.

Description Minimum Default Maximum

Space Sensor SPC -100.0° F 0.0° F +100.0° FSupply Sensor SAT -100.0° F 0.0° F +100.0° FReturn Sensor RAT -100.0° F 0.0° F +100.0° F

Outdoor Sensor OAT -100.0° F 0.0° F +100.0° F

Page 22: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces22

Programming The WMVAV ControllerStatusThe WMVAV controller status screens are accessed by pressing the“Status” button on either the System Manager or the Modular ServiceTool. Following are the available status screens and a description oftheir functions.

Status Screen 1

WMVAV v1.00 ID 59 Occupied Mode Venting Mode Normal Operation

Line 2 Line displays one of the following:Unoccupied Mode Remote Signal ON

Occupied Mode Override Mode

Holiday Mode Zone Demand!

Forced Schedule Mode OUTPUT FORCE MODE!

SUPPLY AIR CUTOFF! High CO2 Level Mode!

Line 3 If you selected Supply Air as the controlling sensor, thisline will display:Supply Air Control

If you select Space Temp or Return Air Control thedisplay will show one of the following:Venting Mode Cooling Mode

Heating Mode Dehumidify Mode

Line 4 Line displays one of the following:Normal Operation

Fan Starting Delay

xx Left in WarmUp (Number of Minutes Left)

Status Screen 2

WMVAV v1.00 ID 59 Cooling Enabled Heating Disabled Economizer Enabled

Line 2 Line displays one of the following:Cooling Enabled

Cooling Disabled

Line 3 Line displays one of the following:Heating Enabled

Heating Disabled

Line 4 Line displays:Economizer Enabled

Economizer Disabled

Status Screen 3

WMVAV v1.00 ID 59Temperature: x°FCooling Spt: xx.x°FHeating Spt: xx.x°F

Line 2 Current Controlling TemperatureCan be Supply Air, Return Air or Space Temperature

Line 3 Currently active Cooling SetpointBased on the current Occupied / Unoccupied mode ofoperation.

Line 4 Currently active Heating SetpointBased on the current Occupied / Unoccupied mode ofoperation. If the Supply Air Sensor is the controllingsensor, this will indicate the Night Setback temperature thatthe Space Temperature uses to bring on heat during theunoccupied mode.

Status Screen 4

WMVAV v1.00 ID 59H/C Demand: xx.x°FSpace Temp: xx.x°FCO2 Level.: xxxx PPM

Line 2 Current Heating or Cooling DemandBased on the comparison between the ControllingTemperature and the Heating and Cooling Setpoints. Apositive number indicates a cooling demand and anegative number indicates a heating demand.

Line 3 Current Space Temperature reading. This sensor is only used during unoccupied hours unless ithas been configured as the Controlling Sensor.

Line 4 Current CO2 Level.

If you configured for a CO2 Sensor, this line will display the

CO2 Level. Otherwise, it will remain blank.

SSSSStatus Screen 5

WMVAV v1.00 ID 59Outdoor Air: xx.x°FHumidity...: xx.x %Wetbulb....: xx.x°F

Line 2 Current Outdoor Air Temperature.

Page 23: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

23

Line 3 Current Outdoor Air Relative HumidityIf this unit is configured for a humidity sensor a value willappear on this line. If a humidistat is configuredthis line will display “Humidistat Open” or “HumidistatClose”. If neither is configured, this line will be blank.

Line 4 Displays calculated Wetbulb TemperatureIf this unit is configured for a humidity sensor a value willappear on this line. If no humidity sensor is configured,this line will be blank.

SSSSStatus Screen 6

WMVAV v1.00 ID 59Supply Air.: xx.x°FReturn Air.: xx.x°FSupply Spt.: xx.x°F

Line 2 Current Supply Air Temperature.

Line 3 Current Return Air Temperature

Line 4 Current Supply Air SetpointCan be reset from an external signal if this option isselected

Status Screen 7

WMVAV v1.00 ID 59Static Pr..: x.xx”Fan VFD....: xxx %Economizer.: xxx %

Line 2 - Current Static Pressure Reading.

Line 3 - Current Fan VFD Signal percentage

Line 4 - Current Economizer damper percentage open.

Status Screen 8

WMVAV v1.00 ID 59 Relief Pr..: xx.xx” Relief VFD.: xxx %[Relief is Optional]

Line 2 Current Relief PressureIf the unit is configured for Relief Pressure control.

This will display 0.00” if you don’t control relief pressure.

Line 3 Current Relief Fan VFD Signal.This will display 0 % if the unit is not configured for reliefpressure control.

Line 4 Just a reminder that this is an optional control outputand may or may not have live data to display.

Status Screen 9-15

WMVAV v1.00 ID 59Fan Relay.....: OFFCoolStage 1...: OFFHeatStage 1...: OFF

Line 2 - Current Supply Fan Relay statusThe letters FRC will appear before the colon if this relay isin a force mode. On screens 10 to 14 this line will indicatethe relays use as a Heating / Cooling, Warm-up Mode,Reversing Valve, etc., and the ON/OFF condition for thatrelay. Possible options are:

HeatStage CoolStage Warm-up ModeRev. Valve Re-Heat Exhaust FanPre-Heater Economizer AlarmOverride Occupied

Line 3 - Current relay status and description of what it isconfigured for.

The letters FRC will indicate the relay is forced to itscurrent condition.

Line 3 - Current relay status and description of what it isconfigured for.

The letters FRC will indicate the relay is forced to itscurrent condition.

Status Screen 16

WMVAV v1.00 ID 59

NO ALARMS

Line 2 - Blank Line

Line 3 - NO ALARMSThis is displayed if no alarms are detected. If there are oneor more alarms active, the possible messages are shownbelow:

BAD SPACE SENSOR

FAN PROVING FAILURE!

MECHCOOLING FAILURE

MECH HEATING FAILURE

DIRTY FILTER ALARM

CONTROL TEMP ALARM

If you press "Enter" the screen will scroll through all theactive alarms.

Line 4 - Blank Line

Page 24: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces24

Programming The WMVAV ControllerSchedulingThe WMVAV controller scheduling screens are accessed by pressingthe “Schedule” button on either the System Manager or the ModularService Tool. Press the number button for the scheduling function youwish to view.

1)Schedule Override2)Week Schedules3)HolidaysESC) Exit Menu

Week Schedules

Event #1

WMVAV Schd ID 59 Sunday Event #1 Start Time..: xxxx Stop Time..: xxxx

Event #2

WMVAV Schd ID 59 Sunday Event #2 Start Time..: xxxx Stop Time..: xxxx

If you are using the internal scheduling capability of the WMVAV con-troller, set the schedule hours and holiday periods from the menu shownabove. You can also force the unit to operate continuously in occupiedor unoccupied mode by selecting the Schedule Override menu item andentering the desired command.

If you are using an external contact closure to signal the occupied mode,you must access the Week Schedule screens and set all start and stoptimes to zero to prevent the internal schedule from bringing the equip-ment on when you don’t want it to operate.

The screens will step through the Start Time and then the Stop Time foreach day of the week. You can quit at any point in the process by press-ing the “Escape” key. There are two Start/Stop events available per dayso the screen will show which event is being programmed. If you needonly one event, leave Event #2 times to ZERO.

All times are in 24-hour military format, so 5:00 PM would be enteredas 1700.

If both the Start and Stop Times are ZERO, the schedule is in a continu-ous OFF mode. (Use for Remote Signal Contact)

If both the Start and Stop Times are 2359, the schedule is in a continu-ous ON mode.

Note: The second line displays which day of the week is cur-rently being programmed. This automatically incrementsas you finish the Event #2 screen and continue to thenext days Event #1 screen.

Caution: The controller ships with all schedules set to zero sothat the controller will not attempt to heat or coolbefore the user has configured his system.

Holiday Start/Stop Day Selection

WMVAV Hldy ID 59 Holiday # 1Start Mon/Day.: xxxx [ July 4th = 704 ]

WMVAV Hldy ID 59 Holiday # 1Stop Mon/Day.: xxxx [ July 4th = 704 ]

The screens will step through the fourteen possible holidays, one pe-riod at a time. Line 2 shows which holiday is currently being pro-grammed. Since a holiday period can encompass more than one day,you need to program the day the holiday starts and the day the holidayends. If your holiday only lasts one day simply set both the Start Dayand the Stop Day to the same value. Remember to combine the monthand day into a single four-digit value.

EXAMPLE: 704 = July 4th (Note : Leading zero not required)

1225 = December 25th

Page 25: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

25

Holiday Start/Stop Times

WMVAV Hldy ID 59 Holiday ScheduleStart Event #1: xxxxStop Event #1: xxxx

WMVAV Hldy ID 59 Holiday ScheduleStart Event #2: xxxxStop Event #2: xxxx

The fourteen holidays all use the same Start and Stop times which areentered on this screen and then next. It is entered in 24-hour militaryformat, the same as a regular week schedule.Normally the holidays will operate in an unoccupied mode or a reducedschedule mode. There are two start/stop events available on holidays tomatch the standard schedule number of events.

Schedule Override

WMVAV Ovrd ID 59 Schedule OverrideEnter Override...: x[0=Auto 1=ON 2=OFF]

If you want to force the unit to operate in a continuous Occupied orUnoccupied mode, select this menu item to activate the desired method.If a Schedule Override is active, all other methods of schedule controlare ignored. (Push-Button, Internal or Remote)

As you can see on the last line of the display you enter a ‘1’ to runcontinuously in the Occupied Mode or a ‘2’ to run continuously in theUnoccupied Mode.

To restore normal schedule operations, make sure a ‘0’ is entered here.This override remains in effect until canceled by the user and does nottime-out like the Output Overrides do after 10 minutes of no communi-cations.

Note: Do not use the Force OFF mode in place of setting allthe week schedules to ZERO if you are using a RemoteSignal for your scheduling since the Override has pri-ority over the Remote Signal.

Setting Time & DateBoth the Modular Service Tool and Modular System Manager areequipped with a real time clock chip allowing it to maintain the cor-rect time. Once the correct time and date are entered, the informationis broadcast globally to all controllers on the entire system. The Sys-

tem Manager will also broadcast this information once every day atmidnight to synchronize all the controllers on the system.

Programming Times

From the main menu press the “Enter” key. The following screen willappear.

1) Set Time & Date 2) Communications ->) Next MenuESC) Exit Menu

Press “2” on your keypad to access the “Set Time & Date” screens.

Although the times are displayed on the Main Screen in a standard 12-hour format, they are programmed using the 24-hour military format. Ifthe WMVAV controller was configured to use its own Internal Sched-ules, the Occupied/Unoccupied modes are calculated on the basis of thecurrent real time clock reading.

Program Time/DateDay (Sunday=0): xEnter Hr. (0-23): xxEnter Minutes : xx

Day Enter the Day of the Week (0 to 6)Sunday = 0

Hours (Hr) Enter Hours in 24-Hour Military Format(1700 = 5:00 PM)

Minutes - Enter the Minutes(0 to 59)

Programming Date

Program Time/DateMonth (1-12): xxDay (1-31): xxYear (00-99): xx

Month Enter the Month (1 to 12)

Day Enter the Day of the Month (1 to 31)

Year Enter the current Year with two digits (00 to 99)

After the date is programmed the Daylight Savings Time Auto AdjustScreen will be displayed. If you want the time to be automatically ad-justed for daylight savings time select yes, if not select no.

Daylight SavingsAuto Adjustment: Yes

Use Left/Right Arrow

Page 26: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces26

Damper Force ModesDamper Force Modes are available for testing or balancing the system.These Force Modes can be accessed and programmed from either theSystem Manager or the Modular Service Tool.

System Manager InstructionsTo access the Damper Force Modes from the System Manager, pressthe “Setpoints” key. You will then see the unit ID screen. Enter the unitID of the controller you wish to access and press "Enter". The followingscreen will appear.

1)Change Setpoint2)Configure Unit3)Damper ForceESC) Exit Menu

Press “3” on the keypad and then the "Enter" key. You will then see theunit ID screen. Enter the unit ID of the controller you wish to accessand press "Enter". At this time the password screen will be displayed.Enter your level 2 password. Press "Enter" and the damper force modesscreen will be displayed.

Modular Service Tool InstructionsWhen using the Modular Service Tool simply press the “Balance-Test”key. You will then see the unit ID screen. Enter the unit ID of the con-troller you wish to access and press "Enter". The following screen willbe displayed.

1)Outputs Force 2)Dampers Force

Press the “2” key to access the Damper Force Modes screen.

Damper Force Mode ScreensIf the unit ID you entered is for a WMVAV controller that has VAVBOXcontrollers connected to its communication loop, the Damper ForceMode will act as a “Global” Damper Force Mode. That is, all VAVBOXcontrollers on that WMVAV controllers communication loop will beforced to the same Damper Force Mode setting. If the unit ID you en-tered is for a VAVBOX controller, the Damper Force Mode setting willonly apply to that VAVBOX controller.

Damper Force ID 159Enter Force Mode.: 00=Auto 1=Open 2=Clsd 3=Max 4=Min 5=Fixd

Set the appropriate Damper Force Mode by entering numbers 0 through5. Following is a list of the force modes and their meaning..

0 = Auto This is the default setpoint. With this settingthe damper will operate normally and modulateaccording to the controller setpoints.

1= Open This setting will force the dampers to their fullyopen position.

2= Clsd This setting will force the damper to it’s fullyclosed position.

3= Max This setting will force the damper to it’s VentMode Maximum position setpoint. See VAVBOXcontroller Setpoint Screen #4 for availablesetpoint information.

4= Min This setting will force the damper to it’s VentMode Minimum position setpoint. See VAVBOXcontroller Setpoint Screen #4 for availablesetpoint information.

5=Fixed This setting will force the damper to a fixedposition based on the fixed position setpoint.

See VAVBOX controller Setpoint Screen #7 foravailable setpoint information.

Caution: The Damper Force Modes should only be used by quali-fied service personnel. Serious damage to the ductworkcould result if the dampers are all forced closed andthe HVAC unit fan is operating.

Outputs ForceOutput Force settings are available for testing or troubleshooting thesystem. These Force settings can only be accessed and programmedfrom the Modular Service Tool, the System Manager does not allow forprogramming of this function.

Caution: The Output Force settings should only be applied byqualified service personnel. Serious damage to theHVAC unit could result from improper use of theseOutputs Force settings.

To access the Output Force settings simply press the “Balance-Test”key on the Modular Service Tool. You will then see the unit ID screen.Enter the unit ID of the WMVAV controller you wish to access andpress "Enter". The Output Force settings are only available for theWMVAV controller. They are not supported for the VAVBOX control-ler. If you enter a unit ID for any other type of unit except a WMVAVcontroller the following screen will be displayed.

Programming The WMVAV Controller

Page 27: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

27

Unit xxx Does NotSupport The Function Press Any Key To Continue

If you entered the unit ID of a WMVAV controller the following screenwill be displayed.

1)Outputs Force 2)Dampers Force

Press the “1” key to access the Outputs Force screen.

Supply Fan OverrideEnter Override...: 0

[0=Auto 1=ON 2=OFF]

The first Outputs Force screen allows the Supply Fan relay to be set forAuto, ON or OFF by entering a 0, 1 or 2 as desired. The default settingis 0=Auto. After completion of all troubleshooting or testing proce-dures all relays should be changed back to this setting. The 1=ON set-ting will force the relay to the ON (energized) position. The 2=OFFselection will force the relay to the OFF (de-energized) position.

The next screen displays the Relay Overrides for Relay 2. After press-ing the "Enter" key the next relay will be displayed. All 20 Relay Over-ride screens (including the AHU fan relay) are available by pressing the"Enter" key after each setting is made.

Relay OverridesRelay 2 Override: 0

[0=Auto 1=ON 2=OFF]

After the screen for relay 20 is displayed, the first Analog Output Over-ride screen will be displayed.

Analog Output 1 Screen

Economizer Overrides Analog Output #1Override Volts: -1.0 [-1.0=Auto]

Press “Enter” and the next screen will appear for Analog Output #2.

Analog Output 2 Screen

Supply VFD Override Analog Output #2Override Volts: -1.0 [-1.0=Auto]

Press “Enter” and the next screen will appear for Analog Output #3.

Analog Output 3 Screen

Relief VFD Override Analog Output #3Override Volts: -1.0 [-1.0=Auto]

The default setting for normal operation is -1.0 volts. Voltages between0 to 10.0 can be set for any of the Analog Output Overrides. Press “En-ter” after making a setting change and the next Analog Output Overridescreen will be displayed.

Page 28: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces28

Programming The VAVBOX ControllerConfigurationIn order to correctly setup the VAVBOX controller you must first con-figure several parameters in regard to the type of system and operatingparameters for the VAVBOX controller you have installed. Most of thesevalues are and operating parameters are only set once, at the initial sys-tem setup and are never changed.

System Manager InstructionsFrom any menu screen press the “Setpoint” key. The unit selection screenwill appear requesting that you enter the unit ID number. Enter the cor-rect unit ID number of the VAVBOX controller you want to configureand hit the “Enter” key. You will see the screen shown below.

1)Change Setpoint2)Configure Unit3)Damper ForceESC) Exit Menu

Press “2” on the keypad to enter the first unit configuration screen.

Modular Service Tool InstructionsFrom any menu screen press the “Configuration” key. The unit selec-tion screen will appear requesting that you enter the unit ID number.Enter the correct unit ID number of the VAVBOX controller you wantto configure and hit the “Enter” key. You will then see unit configura-tion screen #1.

Configuration Screen #1

HC Box Cnfg IDxxxx Box Control Method COOLING ONLY BOX [Enter Type 0 - 3]

This Box Control code will operate in one of four possible modes:

0 = COOLING ONLY BOX1 = H/C CHANGEOVER BOX2 = SERIES FAN BOX3 = PARALLEL FAN BOX

Configuration Screen #2

HC Box Cnfg IDxxxx Damper Operating Mode: DIRECT ACTING[0=Direct 1=Reverse]

Enter a ‘0’ for DIRECT ACTING or a ‘1’ for REVERSE ACTING.

If the damper opens in a clockwise direction, it is DIRECT ACTINGIf the damper opens in a counterclockwise direction, it is REVERSEACTING

CAUTION: If you change this setting, you MUST cycle powerto the controller to allow it to re-calibrate thedamper feedback positions for its’ new directionof control!

Configuration Screen #3

HC Box Cnfg IDxxxxPr Independent Boxes Airflow @ 1" WGConstant..: 1200 CFM

If this is a Pressure Independent Box, you must enter this airflow con-stant so that the CFM readings can be correctly calculated. This airflowconstant is provided by the box manufacturer and depends on the diam-eter of the duct.

Configuration Screen #4

HC Box Cnfg IDxxxx Expansion Relays [Optional]Steps of Re-Heat: 2

If you require the VAVBOX Controller to control reheat for the zone itis installed in, you must include a relay expansion board and then con-figure the number of heating stages ( 1, 2 or 3 ) that it will be controllingwhenever there is a heating demand in the space. Enter ‘0’ if you don’trequire this option.

Configuration Screen #5

HC Box Cnfg IDxxxxProportional HeatingSignal..: 0 - 10 VDC[0 = 0-10 1 = 2-10]

Select this option to change the range of the proportional heat outputfrom 0-10 VDC to 2-10 VDC.

Configuration Screen #6

HC Box Cnfg IDxxxxAllow Box Heat With AHU Heat....: NO [0=NO 1=YES]

Set this option to 1 = YES to allow the heating relays controlling boxheat to remain on even when the AHU is in Supply Air Heating Mode.This is used as a method to provide supplemental heat if for some rea-son the AHU heat cannot satisfy the heating demand

Page 29: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

29

Configuration Screen #7

HC Box Cnfg IDxxxxThis Unit Needs MainFan Status...: NO [0=NO 1=YES]

This setting only applies to the unoccupied mode of operation. Select1=YES to activate the heating stages only when the main fan is operat-ing on non fan terminal units. For series fan terminal units if this set-ting is set to 1=YES the series box fan will only run when the mainHVAC unit fan is running or when a space heating demand is made. Forseries fan terminal units if this setting is set to 0=NO the series box fanwill only run when a space heating demand is made. This setting has noeffect on the parallel flow fan terminal unit.

Configuration Screen #8

HC Box Cnfg IDxxxxPush-Button Override Group ID #.: 1

During Unoccupied Mode, all zones with a corresponding Group ID #will resume Occupied operation whenever any of the zones in that grouphas its push-button depressed to initiate an override condition. This al-lows you to group zones in various areas of the building. For example,individual tenants with several offices could restore occupied mode forjust their zones and not affect other zones in the building.

If you don’t want a specific zone to be a part of any group, enter a ‘0’ forits Group ID #.

Configuration Screen #9

HC Box Cnfg IDxxxxIs This A Dump Zone?(No Actuator): NO [0=NO 1=YES]

A “Dump Zone” is used when you want to control a duct heater orbaseboard heater independently. A VAVBOX Controller board with arelay expansion board is used for this purpose. No damper or actuatoris used. If you need to control an auxiliary heater select 1=YES other-wise be sure it is set to 0=NO.

Setpoints

Setpoint Screen #1

HC Box Spts IDxxxx Occupied SetpointsCooling......: xx°FHeating......: xx°F

Enter the Occupied Cooling Setpoint as the maximum temperatureyou would like the zone to reach before modulating the damper opento bring in more cold air to cool the space. Enter the Occupied Heat-ing Setpoint as the minimum temperature you would like the zone toreach before activating the Reheat Stages on the optional ExpansionRelay board. If this is a Cooling Only box that doesn’t contain reheat,this setpoint will be ignored.

Description Minimum Default MaximumCooling Spt 50°F 74°F 90°FHeating Spt 50°F 70°F 90°F

Setpoint Screen #2

HC Box Spts IDxxxxUnoccupied SetbacksCooling SetUp: xx°FHeating SetBk: xx°F

During unoccupied hours, the Occupied Cooling Setpoint is adjustedup by the amount entered for the Cooling SetUp. The Occupied Heat-ing Setpoint is adjusted down by the amount entered for the HeatingSetBk.

Description Minimum Default MaximumCooling SetUp 0°F +10°F +30°FHeating SetBk 0°F -10°F -30°F

Setpoint Screen #3

HC Box Spts IDxxxx AHU Heat CallSpace Temp...: xx°F

This setpoint allows the user to set a Space Temperature that will causethe Box Controller to send a call for heat to the HVAC unit.

Page 30: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces30

Programming The VAVBOX ControllerSetpoint Screen #4

HC Box Spts IDxxxx Damper/Airflow SptIntegral [Ki]..: xxx

The Box Controller normally opens it’s damper based on a ProportionalError from Setpoint. That means if the zone temperature is 4°F fromsetpoint, the damper would be 100% open or it would be modulating toprovide the Maximum CFM on Pressure Independent boxes. If the er-ror is less than 4°F, the damper may stagnate at that position and neversatisfy the zone. If you add Integral into the damper calculation pro-cess, this will cause the damper or airflow calculations to continue toincrease as long as the zone temperature is still above the setpoint. Thatmeans it can provide 100% or Maximum CFM before the 4°F error isachieved, bringing the zone under control faster than it normally would.Start with a small ( 5 or 10 ) value, if you use this, and monitor the effectit has. If you enter too large a value, you can create “hunting” situationsthat can cause the damper actuator to prematurely wear out.

Description Minimum Default MaximumIntegral 0 0 100

Setpoint Screen #5

HC Box Spts IDxxxx Damper/Airflow SptMaximum..: xxx %Vent Min.: xxx %

The Box Controller will not allow the damper or airflow calculation toexceed the Maximum setpoint while it is allowing the damper to modu-late. During Vent mode when there is no heating or cooling demand, thedamper or airflow will maintain at least the Vent Min amount of airflowinto the zone for ventilation.

Description Minimum Default Maximum

Maximum0% or0 CFM

100% or1000 CFM

100% or30000 CFM

Vent Min.0% or0 CFM

25% or250 CFM

100% or30000 CFM

Setpoint Screen #6

HC Box Spts IDxxxx Damper/Airflow SptCool Min.: xxx %Heat Min.: xxx %

During Supply Air Cooling Mode if the space being served by this damperis satisfied and has no cooling demand the damper will close to thisCool Min setting. This provides a minimum amount of airflow into the

space for ventilation, even if the space does not require additional cool-ing. During Supply Air Heating Mode if the space being served by thisdamper is satisfied and has no heating demand the damper will close tothis Heat Min setting. This provides a minimum amount of airflow intothe space for ventilation, even if the space does not require additionalheating.

Description Minimum Default Maximum

Cool Min0% or0 CFM

10% or100 CFM

100% or30000 CFM

Heat Min0% or0 CFM

10% or100 CFM

100% or30000 CFM

Setpoint Screen #7

HC Box Spts IDxxxx Damper/Airflow SptNt/Rh Min.: xxx %Fan On Min: xxx %

The Nt/Rh Min (Night or Reheat Minimum Damper Position) has dif-ferent functions depending on whether the VAVBOX controller is inthe occupied or unoccupied mode and whether the VAVBOX controlleris used on a fan powered or non-fan powered terminal unit.

Occupied ModeIf the VAVBOX controller is used on a non-fan-powered terminal unitthat has reheat, the VAVBOX damper will move to the Nite/Reheat po-sition whenever a Space Heating demand occurs and the HVAC unit isin Supply Air Cooling or Vent modes. When the HVAC unit is in Sup-ply Air Heating mode the VAVBOX damper will modulate as requiredto maintain the Space Heating setpoint. This setting has no effect on fanpowered terminal units when they are in the occupied mode.

Unoccupied ModeWhen using non-fan powered terminal units, the VAVBOX damper willposition itself in the Nite/Reheat minimum position. In order for fanpowered terminal units to position the damper to the Nite/Reheat mini-mum position, the check for main fan status must be selected and theHVAC unit fan must be operating.

The Fan On Min is used for Parallel Fan boxes only. This is the damperposition that will cause the Parallel Fan to start if the damper/airflowdrops below this value. Normally the Parallel Fan only operates whenthe Reheat stages are activated. If this is not a Parallel Fan box, the lastline will remain blank. Series Fan boxes are not affected by this settingas the fan is always on anytime the HVAC unit fan is running.

Description Minimum Default Maximum

Nt/Rh Min0% or0 CFM

0% or0 CFM

100% or30000 CFM

Fan On Min0% or0 CFM

0% or250 CFM

100% or30000 CFM

Page 31: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

31

Setpoint Screen #8

HC Box Spts IDxxxx Damper/Airflow SptFixed Pos: xxx %

Many times while troubleshooting a system, it is useful to have the zonedamper set to a specific damper position or airflow setting. This set-point can be used to determine where the damper/airflow will remainwhen the box controller receives a Force to Fixed Position commandfrom the user.

Description Minimum Default MaximumFixed Pos 0% or

0 CFM0% or0 CFM

100% or 30000CFM

Setpoint Screen #9

HC Box Spts IDxxxx Zone Alarm OffsetsHi Zone......: xx°FLo Zone......: xx°F

The VAV Box Controller can be setup to generate an alarm anytimethe Zone Temperature exceeds the user defined alarm limits for a userdefined period of time. A High Temperature Alarm Setpoint is createdby adding the Hi Zone Alarm offset to the current Cooling Setpoint.The Low Temperature Alarm Setpoint is created by adding the Lo ZoneAlarm offset to the current Heating Setpoint. If the zone temperatureexceeds either of these limits for a period defined by the Alarm Delaysetpoint, the controller can generate an alarm callout if all the optionsrequired for this to occur are installed.

Description Minimum Default MaximumHi Zone Alarm +1°F +30°F +50°FLo Zone Alarm -1°F -30°F -50°F

Setpoint Screen #10

HC Box Spts IDxxxx Zone Alarm Delay Must Be Out OfLimits For.: xxx Min

As mentioned above, if the user configures the controller to generatezone temperature alarms, this is the amount of time the temperaturemust be outside the alarm limits before an alarm is generated.

Description Minimum Default MaximumOut Of Limits 1 Min 30 Min 300 Min

Setpoint Screen #11

HC Box Spts IDxxxx Day/Night Schedule Control #: x0=AHU 1-7=Scheduler

This screen allows you to set the VAVBOX controller to operate on aremote schedule instead of the schedule that is contained in the WMVAVcontroller.

Description Minimum Default Maximum

Schedule Number 0 0 1 to 7

Setpoint Screen #12

HC Box Spts IDxxxxMaximum Slide OffsetEffect on Spt.: x°F

If the Flush Mount Wall Sensor has the optional Setpoint Slide Adjust,this is the maximum amount the user can adjust the heating and coolingsetpoints up or down as the slide is moved from the center position toits full up or down position

Description Minimum Default MaximumEffect on SP 0°F 0°F 6°F

Setpoint Screen #13

HC Box Spts IDxxxxPush-Button OverrideDuration : x.x Hr

If the Flush Mount Wall Sensor has the optional Push-Button Override,this is the amount of the Box Controller will resume using its OccupiedSetpoints during unoccupied mode. This will generate a call for the AirHandler to start its fan and provide heating or cooling, depending onhow the user configures the Air Handler.

Description Minimum Default MaximumDuration 0.0 Hr 0.0 Hr 8.0 Hr

Page 32: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces32

Setpoint Screen #14

HC Box Spts IDxxxxMaximum EMS Setpoint Offset...: xx°F

This screen is currently not used for this application.

Description Minimum Default MaximumEMS Setpoint x x x

Setpoint Screen #15

Sensor CalibrationSPC: xxx.x° xxx.x°SAT: xxx.x° xxx.x°[SAT Only if Sensor]

The Thermistor Type III sensor readings can be calibrated. Enter a Posi-tive value to increase a reading and a Negative value to decrease a read-ing.

Note: The Supply Air Temperature calibration offset only op-erates on the reading when the Box Controller has it’s’own Supply Air Temperature sensor installed on theAUX2 input. If the supply temperature is received froma global broadcast, you will need to go to the air handlerto calibrate the temperature reading.

Description Minimum Default MaximumSPC [ Space Temp ] -100.0°F 0.0°F +100.0°FSAT [ Supply Air ] -100.0°F 0.0°F +100.0°F

Status

Status Screen #1

HC Box v1.04 IDxxxx Occupied Mode Vent ModeBelongs to Group # 1

Line 2 Unoccupied Mode

Occupied Mode

Override Mode

Override Pending

Damper Calibration

Remote Signal ON

Group Override

Line 3 OFF Mode

Vent Mode

Cooling Mode

Heating Mode

Warm-up Mode

Sensor Fail Mode

Line 4- Belongs to Group # xx

No Group Affiliation

Status Screen #2

HC Box v1.04 IDxxxxZone Temp..: xx.x°FCooling Spt: xx.x°FHeating Spt: xx.x°F

Line 2 Current Zone Temperature

Line 3 Currently active Cooling Setpoint based on the currentOccupied / Unoccupied mode of operation.

Line 4 Currently active Heating Setpoint based on the currentOccupied / Unoccupied mode of operation.

Status Screen #3

HC Box v1.04 IDxxxxSlide Offset..: xx°FH/C Demand.: xx.x°F

Line 2 If the optional Setpoint Slide Adjust is installed on theFlush Mount Wall Sensor, this line will display thecurrent amount the Slide Offset is affecting theHeating and Cooling Setpoints.

Line 3 Current Heating or Cooling Demand in the Zonebased on the current Heating and Cooling Setpointswhen compared to the current Zone Temperature.

Line 4 Current Supply Air Temperature received viabroadcast from the WMVAV controller or from theVAVBox Controllers own installed Supply Air Sensoron the AUX2 input.

Programming The VAVBOX Controller

Page 33: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

33

Status Screen #4

HC Box v1.04 IDxxxxSupply Air.: xx.x°FDuct Air...: xx.x°F

Line 2 Current Supply Air Temperature received viabroadcast from the WMVAV controller or from theVAVBox Controllers own installed Supply Air Sensoron the AUX2 input.

Line 3 Current Duct Air Temperature at theduct air temperature sensor location if a ducttemperature sensor is installed and connected to theVAVBOX controller. If a duct air temperature sensor isnot installed this line will display the same supply airtemperature as on Line 2 above.

Status Screen #5

HC Box v1.04 IDxxxxDamper FRC: xxx %Airflow...: xxxx CFMDesired...: xxxx CFM

Line 2 Current Zone Damper Position If the user has entereda FORCE command, the letters FRC will appear. Ifthis is normal damper operation, the FRC is notdisplayed.

Line 3 If this is a Pressure Independent box, the currentAirflow will be displayed. If not, this line will displaythe current damper position.

Line 4 If this is a Pressure Independent box, this line willdisplay the Desired CFM the box would like toprovide to the zone. If not, this line will display[Controls to +/- 3%] to indicate how accurately thedamper will maintain the desired position.

Status Screen #6

HC Box v1.04 IDxxxxFan Status : OFF 1 Reheat Stages On

Line 2 If this is a Fan Powered box, this line will display theFan On/Off Status. On non fan powered boxes, thisline will display: Exp Relay 1 Not Used

Line 3 If your VAV Box Controller has been configured tocontrol reheat stages, this line reflects the On/OffStatus of the first stage of Reheat. If proportionalheating is used this line will display “HeatingSignal: xxx %”. If you have 3 stages of reheat thisline will display the total number of active heatingstages.

Example:

“1 Reheat Stages On” or

“2 Reheat Stages On” or

“3 Reheat Stages On”

Line 4 Blank

Status Screen #7

HC Box v1.04 IDxxxx

NO ALARMS!

Line 2 Blank

Line 3 NO ALARMS!This is displayed if no alarms are detected. If there areone or more alarms active, the possible messages areshown below:

SPACE SENSOR FAILURECFM SENSOR FAILUREDAMPER OPENING ALARMDAMPER CLOSING ALARMHI SPACE TEMP ALARMLO SPACE TEMP ALARMDPR FEEDBACKFAILURE

Line 4 Blank

Page 34: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Technical Guide

Operator Interfaces34

Damper Force ModesDamper Force Modes are available for testing or balancing the system.These Force Modes can be accessed and programmed from either theSystem Manager or the Modular Service Tool.

System Manager InstructionsTo access the Damper Force Modes from the System Manager, pressthe “Setpoints” key. You will then see the unit ID screen. Enter the unitID of the controller you wish to access and press "Enter". The followingscreen will appear.

1)Change Setpoint2)Configure Unit3)Damper ForceESC) Exit Menu

Press “3” on the keypad and then the "Enter" key. You will then see theunit ID screen. Enter the unit ID of the controller you wish to accessand press "Enter". At this time the password screen will be displayed.Enter your level 2 password. Press "Enter" and the damper force modesscreen will be displayed.

1)Outputs Force 2)Dampers Force

Press the “2” key to access the Damper Force Modes screen. OutputsForce is not available with the System Manager.

Modular Service Tool InstructionsWhen using the Modular Service Tool simply press the “Balance-Test”key. You will then see the unit ID screen. Enter the unit ID of the con-troller you wish to access and press "Enter". The damper force modesscreen will be displayed.

1)Outputs Force 2)Dampers Force

Press the “2” key to access the Damper Force Modes screen. OutputsForce is available with the Modular Service Tool but is not used withthe VAVBOX controller.

Damper Force Mode ScreensIf the unit ID you entered is for a WMVAV controller that has VAVBOXcontrollers connected to its communication loop, the Damper ForceMode will act as a “Global” Damper Force Mode. That is, all VAVBOXcontrollers on that WMVAV controllers communication loop will beforced to the same Damper Force Mode setting. If the unit ID you en-tered is for a VAVBOX controller, the Damper Force Mode setting willonly apply to that VAVBOX controller.

Damper Force ID 159Enter Force Mode.: 00=Auto 1=Open 2=Clsd 3=Max 4=Min 5=Fixd

Set the appropriate Damper Force Mode by entering numbers 0 through5. The Force Modes for each of these settings is outlined below.

0 = Auto This is the default setpoint. With this settingthe damper will operate normally and modulateaccording to the controller setpoints.

1= Open This setting will force the dampers to their fullyopen position.

2= Clsd This setting will force the damper to it’s fullyclosed position.

3= Max This setting will force the damper to the dampersmaximum airflow position set under SetpointScreen #4

4= Min This setting will force the damper to the currentmodes, minimum position setpoint. These modesare Vent Mode, Heat Mode and Cool Mode. Theymay each have a different minimum depending onhow you configured the setpoints.

5=Fixd This setting will force the damper to a fixedposition based on the fixed position setpoint.

See VAVBOX controller Setpoint Screen #7 foravailable setpoint information.

Caution: The Damper Force Modes should only be used by quali-fied service personnel. Serious damage to the ductworkcould result if the dampers are all forced closed andthe HVAC unit fan is operating.

Programming The VAVBOX Controller

Page 35: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Operator Interfaces

Technical Guide

35

Programming The MiniLink PD

ConfigurationIn order to correctly setup the MiniLink PD you must first configureseveral parameters in regard to the type of system and operating param-eters for the system it is installed on. Most of these values and operatingparameters are only set once, at the initial system setup and are neverchanged.

System Manager InstructionsFrom any menu screen press the “Setpoint” key. The unit selection screenwill appear requesting that you enter the unit ID number. All MiniLinkPDs are set at address 60. Enter the correct unit loop number for theloop the MiniLink Polling Device is connected to (Loop 1 you wouldenter 1) and then enter 60. Press the “Enter” key. You will see thescreen shown below.

1)Change Setpoint2)Configure Unit3)Damper ForceESC) Exit Menu

Press “2” on the keypad to enter the first unit configuration screen.

Modular Service Tool InstructionsFrom any menu screen press the “Configuration” key. The unit selec-tion screen will appear requesting that you enter the unit ID number.Enter the correct unit ID number of the controller you want to configureand hit the “Enter” key. You will then see unit configuration screen #1.

Configuration Screen #1

Polling Unit Config Last Polled Zone Address: xx [Enter Last Zone]

Enter the address of the last controller (largest address number) for thelocal loop the MiniLink PD is connected to.

Configuration Screen #2

Polling Unit Config Optimal Start Zone Target Unit: xx [Enter Target Zone]

This is the unit ID of the Zone that you want to be satisfied by thenormally scheduled start time. If you enter “-1” into this box it willaverage all zones instead of picking a specific zone. If you do not re-quire optimal start enter “0”.

Configuration Screen #3-62

Polling Unit ConfigEnable Alarm Polling Unit xx : YES [0=NO 1=YES]

Enabling Alarm Polling for the controller whose unit ID you have en-tered, allows any alarm from that controller to be polled and reported bythe MiniLink Polling Device. If alarming is enabled when an alarmcondition is encountered, the alarm light on the System Manager willbe lit and the various alarms can be displayed for that controller at theSystem Manager by pressing the “Alarms” button. You must configurethis setting to “YES” for each controller on the loop that you wish toreceive alarms from.

Page 36: WattMaster VAV System Operator Interfaces Technical Guide · 2014. 4. 2. · Operator Interfaces 3 Technical Guide Modular System Manager ENTER ESC CLEAR PREV NEXT DOWN UP 4 5 6 DEC

Form: WM-SMST-TGD-01C Printed in the USA March 2004All rights reserved Copyright 2004