watts_per_sq_foot

2
 REDDING LINDEN BURR Consulting Engineers Watts Per Square Foot  Eight is more than enough Many wonder why modern office tenants continue to request six to eight watts per square foot of low voltage power when studies show actual needs to be nearer one watt per square foot. Will a better understanding of office equipment loads resolve the difference between a tenant’s request and what is actually needed? In an effort to comprehend office electrical loads, a recording power monitor was connected to typical office equipment. The results of that survey are shown in Table 1, which clearly shows the disparity between loads derived from full load am ps and average operating loads. W hich should be used for design? The answ er is both. Electrical systems must be designed to handle the total conne cted load. Tech nically, these load s are the actual operating values for the eq uipm ent to be installed. Un fortunately, not all computers or printers are alike, and there isn’t time to connect a power m onitor to each one. Therefore, standards based o n w orst- case scenarios are used. The standard values also contain a reasonable margin of error to ensure adequate electrical service capacity. Table l might give the mistaken impression that total connected load based on design standard watts will render a product near eight times the pow er of average usag e. This is the case only if each person is lucky enough to have printer, fax, copier, refrigerator and coffeepot at their desk. Using e quipm ent quan tities typical for a 10,000-square-foot-office, total connected load and average usage per square foot are calculated in Table 2. The resulting design value is very near the 3 watts per  square foot available wh en typical lighting pow er requiremen ts of  1.5 watts per square foot are subtracted from the 4.5 watts per  square foot specified for offices by the National Electrical Code (NEC) for lighting and receptacle power. Table 2 makes it clear that power requirements for a modern office are considerably less than the 8 watts per square foot requested by m any tenants. Lease dem ands for pow er quantities significantly greater than the NEC minimum should therefore be reserved for special use facilities such as call centers or computer  equipment rooms. As stated previously, both total connected load and average powe r requiremen ts should be used in design. W hen does average electrical loading apply? HVAC requirem ents are best calculated with average electrical equipm ent loads. Doesn’t air conditioning equipment also have to meet worst-case conditions? The co oling output in BTU hours m ust match the heat gen erated per hour by the electrical equipment. If  the heat generated exceeds cooling capability for the instant that all printers run at the same time, the HVAC will continue to operate instead of tripping off-line like an overloaded electrical circuit breaker. More efficient HVACsystems result from design based on averag e electrical equipme nt load rater than total conne cted loads. Using the sample 10,000-square-foot office space, the 9.4 tons of cooling required for total connected loads are reduced to 3.1 tons if the air conditioning system is sized for average electrical pow er usage . It would require 22.7 tons of air conditioning to compensate for electrical equipment loads if 8 watts per square foot are specified for the example office. In new building construction, air conditioning cost goes up at a rate near $2,500 per ton. Oversized air conditioning equipmen t uses more energy, causes greater temperature swings in controlled areas, and provides less satisfactory humidity control. Money spent on oversized equipment and added operating expen ses can better reside on the corporate bottom line. W hen specifying powe r for standard office environm ents, stick to the recomm endations of the NEC . Wh en sizing HV AC equipment, think averag e rather than connected electrical loads. Table 1 Equipment Design Std Active St andby %  Avg. Usage Watts Watts Watts Activ e Watts Com puter 250 242 161 10 169 Laser Printer 1,000 650 15 20 142 Copier 1,500 950 30 20 214 Fax 1,000 400 15 20 92 Refrigerator 1,000 525 0 33 173 Microwave 1,500 1,493 10 5 84 Coffeepot 1,500 1,469 159 5 224 Total s 7,750 5,729 1,098 Table 2 Design Std.  Avg. Usage Design Std.  Avg. Usage Equipment Quantity Watts Watts Connected Total Watts Watts Computer 50 250 169 12,500 8,450 Laser Printer 5 1,000 142 5,000 710 Copier 3 1,500 214 4,500 642 Fax 3 1,000 92 3,000 276 Refrigerator 2 1,000 173 2,000 346 Microwave 2 1,500 84 3,000 168 Coffeepot 2 1,500 224 3,000 449 Total s 33,000 11,041 Watts/sq.ft. 3.30 1.10 This publication is intended as a service to building owners, architects and facilities managers by presenting topics of general interest to the industry. For more information please contact Stephen Redding at 713-237-9800. The information originat es from established industry publications and other informed sources. Every effort has been made to ensure the reliability of this information, but it cannot be guaranteed. For further information, contact the appropriate authorities. 801 Travis, Suite 2000 • Houston, Texas 77002 • Phone 713-237-9800 • Fax 713-237-9801 • www.rlbengineers.com  

Upload: ricky-respondo-tindoc

Post on 09-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

8/7/2019 watts_per_sq_foot

http://slidepdf.com/reader/full/wattspersqfoot 1/1

 

REDDING LINDEN BURR Consulting Engineers

Watts Per Square Foot

 Eight is more than enough Many wonder why modern office tenants continue to

request six to eight watts per square foot of low voltage power whenstudies show actual needs to be nearer one watt per square foot.Will a better understanding of office equipment loads resolve thedifference between a tenant’s request and what is actually needed?

In an effort to comprehend office electrical loads, arecording power monitor was connected to typical office equipment.The results of that survey are shown in

Table 1, which clearly shows the disparity between loadsderived from full load amps and average operating loads. Which

should be used for design? The answer is both.Electrical systems must be designed to handle the total

connected load. Technically, these loads are the actual operatingvalues for the equipment to be installed. Unfortunately, not allcomputers or printers are alike, and there isn’t time to connect apower monitor to each one. Therefore, standards based on worst-case scenarios are used. The standard values also contain areasonable margin of error to ensure adequate electrical servicecapacity.

Table l might give the mistaken impression that totalconnected load based on design standard watts will render aproduct near eight times the power of average usage. This is thecase only if each person is lucky enough to have printer, fax, copier,

refrigerator and coffeepot at their desk. Using equipment quantitiestypical for a 10,000-square-foot-office, total connected load andaverage usage per square foot are calculated in Table 2.

The resulting design value is very near the 3 watts per square foot available when typical lighting power requirements of 1.5 watts per square foot are subtracted from the 4.5 watts per square foot specified for offices by the National Electrical Code(NEC) for lighting and receptacle power.

Table 2 makes it clear that power requirements for amodern office are considerably less than the 8 watts per square footrequested by many tenants. Lease demands for power quantitiessignificantly greater than the NEC minimum should therefore bereserved for special use facilities such as call centers or computer equipment rooms.

As stated previously, both total connected load andaverage power requirements should be used in design. When doesaverage electrical loading apply? HVAC requirements are best

calculated with average electrical equipment loads.Doesn’t air conditioning equipment also have to meet

worst-case conditions? The cooling output in BTU hours mustmatch the heat generated per hour by the electrical equipment. If the heat generated exceeds cooling capability for the instant that allprinters run at the same time, the HVAC will continue to operateinstead of tripping off-line like an overloaded electrical circuitbreaker. More efficient HVAC systems result from design based onaverage electrical equipment load rater than total connected loads.

Using the sample 10,000-square-foot office space, the 9.4tons of cooling required for total connected loads are reduced to 3.1tons if the air conditioning system is sized for average electricalpower usage. It would require 22.7 tons of air conditioning to

compensate for electrical equipment loads if 8 watts per square footare specified for the example office.

In new building construction, air conditioning cost goes upat a rate near $2,500 per ton. Oversized air conditioning equipmentuses more energy, causes greater temperature swings in controlledareas, and provides less satisfactory humidity control.

Money spent on oversized equipment and addedoperating expenses can better reside on the corporate bottom line.When specifying power for standard office environments, stick to therecommendations of the NEC. When sizing HVAC equipment, thinkaverage rather than connected electrical loads.

Table 1

EquipmentDesignStd Active Standby %

 Avg.Usage

Watts Watts Watts Activ e Watts

Computer 250 242 161 10 169

Laser Printer 1,000 650 15 20 142

Copier 1,500 950 30 20 214

Fax 1,000 400 15 20 92

Refrigerator 1,000 525 0 33 173

Microwave 1,500 1,493 10 5 84

Coffeepot 1,500 1,469 159 5 224

Total s 7,750 5,729 1,098

Table 2

DesignStd.

 Avg.Usage

DesignStd.

 Avg.Usage

Equipment Quantity Watts Watts ConnectedTotalWatts

WattsComputer 50 250 169 12,500 8,450

Laser Printer 5 1,000 142 5,000 710

Copier 3 1,500 214 4,500 642

Fax 3 1,000 92 3,000 276

Refrigerator 2 1,000 173 2,000 346

Microwave 2 1,500 84 3,000 168

Coffeepot 2 1,500 224 3,000 449

Totals 33,000 11,041

Watts/sq.ft. 3.30 1.10

This publication is intended as a service to building owners,architects and facilities managers by presenting topics of generalinterest to the industry. For more information please contactStephen Redding at 713-237-9800. The information originatesfrom established industry publications and other informed sources.

Every effort has been made to ensure the reliability of this information, but it cannot be guaranteed. For further information, contact the appropriate authorities.

801 Travis, Suite 2000 • Houston, Texas 77002 • Phone 713-237-9800 • Fax 713-237-9801 • www.rlbengineers.com