AUSTRALIA SEPTEMBER 2020 WEATHERTEX CONSTRUCTION DETAILS SELFLOK WEATHERBOARDS CAVITY & STEEL FRAME CONSTRUCTION

Upload: others

Post on 10-Sep-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

AUSTRALIA SEPTEMBER 2020

WEATHERTEX CONSTRUCTION

DETAILS

SELFLOK WEATHERBOARDS

CAVITY & STEEL FRAME

CONSTRUCTION

Page 2: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

INTERNAL LINING

INSULATION

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

TIMBER/STEEL STUD FRAME

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

SMALL EXTERNAL LF

ALUMINIUM CORNER TRIM

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - SMALL EXTERNAL LF CORNER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 21.07.20 CD-CF-1 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 3: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

INSULATIONINTERNAL LINING

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

TIMBER/STEEL STUD FRAME

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

SMALL INTERNAL LF

ALUMINIUM CORNER TRIM

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - SMALL INTERNAL LF CORNER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-2 A421.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 4: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

SMALL TRADITIONAL EXTERNAL

ALUMINIUM CORNER TRIM

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

INTERNAL LINING

INSULATION

TIMBER/STEEL STUD FRAME

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - SMALL EXTERNAL TRADITIONAL CORNER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 07.07.20 CD-CF-3 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 5: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

SMALL TRADITIONAL INTERNAL

ALUMINIUM CORNER TRIM

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

TIMBER/STEEL STUD FRAME

INSULATIONINTERNAL LINING

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - SMALL INTERNAL TRADITIONAL CORNER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-4 A421.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 6: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

SMALL END STOP (SELFLOK, WEATHERGROOVE, ECOWALL, RUBIC RANGES)

LARGE END STOP (PRIMELOK, CLASSIC RANGES)

POLYURETHANE SEALANT APPLIED TO

MANUFACTURERS REQUIREMENTS

ALTERNATIVE BUILDING MATERIAL

E.G. MASONRY, CONCRETE ETC.

9.5mm WEATHERTEX CLADDING

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

TIMBER/STEEL STUD FRAME

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

6mm CONTROL GAP

9mm BACKING ROD

PACKING

DAMPCOURSE

CAVITY CLOSER INSTALLED

AT BASE OF WALL

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

DRAWING NAME:

CAVITY FIX INSTALLATION - END STOP SEPARATION FROM

ALTERNATIVE BUILDING MATERIALS (ALL RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 21.07.20 CD-CF-7 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 7: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

WINDOW REVEAL

PACKING

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

INTERNAL LININGARCHITRAVE

INSULATION

WINDOW FRAME

POLYURETHANE SEALANT

WEATHERTIGHT

SEALING TAPE

DECORATIVE TRIM (IF REQUIRED)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED

AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - WINDOW FRAME JAMB

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-8 A4

WINDOW MEMBRANE TRIM DETAIL TO BE INSTALLED TO AS4200.2:2017 Fig 4.7

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 8: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

ARCHITRAVE

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

WEATHERTIGHT SEALING TAPE

INSULATION

PACKING

DECORATIVE TRIM (IF REQUIRED)

TIMBER/STEEL STUD FRAME

INTERNAL LINING

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

RUBBER SILL FLAP

WINDOW FRAME

POLYURETHANE

SEALANT

WINDOW REVEAL

DRAWING NAME:

CAVITY FIX INSTALLATION - WINDOW FRAME SILL

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-9 A4

WINDOW MEMBRANE TRIM DETAIL TO BE INSTALLED TO AS4200.2:2017 Fig 4.7

27.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 9: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

WINDOW REVEAL

WINDOW HEAD

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

WEATHERTIGHT SEALING TAPE

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

WEATHERTIGHT SEALING TAPE

DECORATIVE TRIM (IF REQUIRED)

CAVITY CLOSER

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGE)

ARCHITRAVE

INTERNAL LINING

HEAD FLASHING MIN 15 °

(TO EXTEND 50mm EITHER SIDE OF WINDOW)

10mm MIN BOARD CLEARANCE

FROM FLASHING

DRAWING NAME:

CAVITY FIX INSTALLATION - WINDOW FRAME HEAD

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-10 A4

WINDOW MEMBRANE TRIM DETAIL TO BE INSTALLED TO AS4200.2:2017 Fig 4.7

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 10: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

TIMBER/STEEL STUD FRAME

METER BOX

INSULATION

POLYURETHANE SEALANT

INTERNAL LINING

SMALL END STOP

POLYURETHANE SEALANT

(WHERE METER BOX EXTENDS

THROUGH INTERNAL WALL)

GAP FILLER ROD

GAP FILLER ROD

(WHERE METER BOX EXTENDS

THROUGH INTERNAL WALL)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED

AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - METER BOX JAMB

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-14 A4

METER BOX TRIM DETAIL TO BE INSTALLED TO AS4200.2:2017 Fig 4.7

21.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 11: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

POLYURETHANE SEALANT

POLYURETHANE SEALANT

(WHERE METER BOX EXTENDS

THROUGH INTERNAL WALL)

FLASHING MIN 15°

INSULATION

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

METER BOX

GAP FILLER ROD

(WHERE METER BOX EXTENDS

THROUGH INTERNAL WALL)

GAP FILLER ROD

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

INTERNAL LINING

TIMBER/STEEL STUD FRAME

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

WEATHERTIGHT SEALING TAPE

CAVITY CLOSER TO RUN LENGTH OF METER BOX

10mm BOARD CLEARANCE

FROM FLASHING

DRAWING NAME:

CAVITY FIX INSTALLATION - METER BOX HEAD

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-15 A4

METER BOX MEMBRANE TRIM DETAIL TO BE INSTALLED TO AS4200.2:2017 Fig 4.7

21.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 12: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

METER BOX

POLYURETHANE SEALANT

SMALL END STOP

INSULATION

INTERNAL LINING

POLYURETHANE SEALANT

(WHERE METER BOX EXTENDS

THROUGH INTERNAL WALL)

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

GAP FILLER ROD

GAP FILLER ROD

(WHERE METER BOX EXTENDS

THROUGH INTERNAL WALL)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

TIMBER/STEEL STUD FRAME

DRAWING NAME:

CAVITY FIX INSTALLATION - METER BOX SILL

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 21.07.20 CD-CF-16 A4

METER BOX MEMBRANE TRIM DETAIL TO BE INSTALLED TO AS4200.2:2017 Fig 4.7

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 13: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER

10mm MIN BOARD CLEARANCE

FROM FLASHING

FOLDED METAL HEAD FLASHING MIN 10°

TAPE FLASHING IF INSTALLED AFTER MEMBRANE

PACKING BLOCK

EXTERNAL DOOR JAMB

ARCHITRAVEEXTERNAL DOOR

TIMBER STUD FRAME

INSULATION

INTERNAL LINING

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

DRAWING NAME:

CAVITY FIX INSTALLATION - DOOR HEAD

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-20 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 14: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

INTERNAL LINING

TIMBER STUD FRAME

100mm CLEARANCE

SEALED GROUND

225mm CLEARANCE

UNSEALED GROUND

GROUND

INSULATION

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

CAVITY CLOSER

20-30mm

SLAB OVERHANG

CONCRETE SLAB

DRAWING NAME:

CAVITY FIX INSTALLATION - CONCRETE SLAB GROUND CLEARANCE

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-22 A421.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 15: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

SUSPENDED FLOOR

LOAD BEARING FRAME

TIMBER/STEEL STUD FRAME

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

CAVITY CLOSER

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

WEATHERTEX CLADDING TO EXTEND MIN 50mm

PAST LOWEST PART OF THE SUSPENDED

FLOOR FRAME

INSULATION

INTERNAL LINING

ANT CAPPING

EMBOSSED POLYTHENE

DAMPCOURSE

PACKING PLATE

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

DRAWING NAME:

CAVITY FIX INSTALLATION - CLADDING OVER PIER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 22.07.20 CD-CF-24 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 16: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

DO NOT CONNECT WEATHERTEX

CLADDING TO MASONRY

PACKING PLATE

SUSPENDED FLOOR FRAME

INTERNAL LINING

TIMBER/STEEL STUD FRAME

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

MASONRY VENEER

TIMBER FRAME

DAMPCOURSE

CLADDING

INSULATION

WEATHERTEX CLADDING TO EXTEND MIN 50mm

PAST LOWEST PART OF THE SUSPENDED

FLOOR FRAME

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

DRAWING NAME:

CAVITY FIX INSTALLATION - FLUSH WITH VENEER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 22.07.20 CD-CF-26 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 17: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

BRICK VENEER

10mm BOARD CLEARANCE

FROM FLASHING

FLASHING

FLOOR FRAME

TIMBER/STEEL STUD FRAME

WEEP HOLES @ MAX 1200 CENTRES

ABOVE FLASHING

CAVITY CLOSER

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE,

ECOWALL, RUBIX RANGES)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

INTERNAL LINING

INSULATION

60mm WEATHERTIGHT SEALING TAPE

DRAWING NAME:

CAVITY FIX INSTALLATION - SET BACK OVER BRICK VENEER

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 22.07.20 CD-CF-28 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 18: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

EAVE/SOFFIT

TIMBER/STEEL STUD FRAME

INTERNAL LINING

FLOOR FRAME

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

INSULATION

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE,

ECOWALL, RUBIX RANGES)

CAVITY CLOSER

DRIP EDGE

QUAD QUAD

DRAWING NAME:

CAVITY FIX INSTALLATION - CANTILEVER ROOF

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-30 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 19: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, WEATHERGROOVE

ECOWALL, RUBIX RANGES)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER

TIMBER/STEEL STUD FRAME

INSULATION

INTERNAL LINING

70mm MIN CLEARANCE

FROM ROOF

RAFTER

ROOFING

METAL FLASHING BY BUILDER 10° MIN

TO EXTEND 50mm BEHIND CLADDING

TAPE IF MEMBRANE CONTINUES BEHIND FLASHING

DRAWING NAME:

CAVITY FIX INSTALLATION - ROOF CLEARANCE

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-32 A427.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 20: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

ROOFING

TIMBER STUD FRAME

INTERNAL LINING

INSULATION

ROOFING

EAVE/SOFFIT QUAD

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(PRIMELOK, CLASSIC RANGES)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

DRAWING NAME:

CAVITY FIX INSTALLATION - EAVE/SOFFIT

(SELFLOK, WEATHERGROOVE, ECOWALL, RUBIX RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-34 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 21: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

INSULATION

TRADITIONAL SELFLOK

OFF STUD JOINER

INTERNAL LININGTIMBER/STEEL STUD FRAME

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK RANGE)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED

AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - TRADITIONAL JOINER

(SELFLOK RANGE)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-38 A427.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 22: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

ALUMINIUM LONG VERTICAL JOINER

(VERTICAL JOINTS ONLY)

(CAN BE SUPPORTED BY 600mm

NOGGINGS FOR SELFLOK INSTALLATION)

INTERNAL LINING INSULATION

TIMBER/STEEL STUD FRAME

(DOUBLE OR ROTATED STUD REQUIRED

FOR ECOWALL INSTALLATION)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK, ECOWALL RANGES)

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED

AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - LONG VERTICAL JOINER

(SELFLOK, ECOWALL RANGES)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-41 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 23: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

3mm BUTT JOIN (LEFT OPEN)

INTERNAL LINING INSULATION

TIMBER/STEEL STUD FRAME

(MIN 45mm FACE)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK RANGE)

POLYURETHANE SEALANT

100mm ALCOR FLASHING

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED

AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - BUTT JOIN

(SELFLOK RANGE)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART 27.07.20 CD-CF-44 A4

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.

Page 24: WEATHERTEX CONSTRUCTION DETAILS · 2020. 9. 11. · steel frame construction. internal lining insulation 9.5mm weathertex cladding (selflok, weathergroove ecowall, rubix ranges) timber/steel

45 ° MITRE JOIN (3mm GAP LEFT OPEN)

INTERNAL LINING INSULATION

TIMBER/STEEL STUD FRAME

(MIN 45mm FACE)

FASTENING PATTERN REFER TO

PRODUCT INFORMATION IN

WEATHERTEX EXTERNAL CLADDING

INSTALLATION MANUAL

VAPOUR PERMEABLE MEMBRANE

AS SPECIFIED IN WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

9.5mm WEATHERTEX CLADDING

(SELFLOK RANGE)

POLYURETHANE SEALANT

100mm ALCOR FLASHING

CAVITY BATTEN (TIMBER FRAME)

THERMAL BREAK (STEEL FRAME)

REFER TO WEATHERTEX EXTERNAL

CLADDING INSTALLATION MANUAL

CAVITY CLOSER INSTALLED

AT BASE OF WALL

DRAWING NAME:

CAVITY FIX INSTALLATION - MITRE JOIN

(SELFLOK RANGE)

SCALE: DRAWN BY: SHT SIZEDATE: DRAWING No.:CHECKED BY:

NTS A.MOATE R.STUART CD-CF-45 A427.07.20

These drawings are for information only. They donot contain full details required for constructionand must be used in conjunction with the currentissue Weathertex Installation Manual, NationalConstruction Code and any other State and LocalRegulations. Weathertex recommends gainingprofessional advice to ensure the drawings aresuitable for your project. Weathertex accepts noliability in respect to the use of these drawings.