webstat™
DESCRIPTION
WebStat™. Programming and Configuration of Thermostats. WebStat Programming/Configuration. Login using a Contractor level user ID and password. WebStat Programming/Configuration. From the Overview screen, click on the “Thermostats” tab. Thermostat Discovery. - PowerPoint PPT PresentationTRANSCRIPT
WebStat™
Programming and Configuration of Thermostats
2
WebStat Programming/Configuration
• Login using a Contractor level user ID and password
3
WebStat Programming/Configuration
• From the Overview screen, click on the “Thermostats” tab
4
Thermostat Discovery
• Thermostats already on the network will show up• Click the “Discover” Button to discover new thermostats
- If there are any existing thermostats, you’ll see a warning stating that any devices with subnet/node conflicts will be re-commissioned.
5
Thermostat Discovery
• A status window will appear• When complete, the Thermostats screen will appear with
all of the discovered thermostats
6
WebStat Programming/Configuration
• Discovered thermostats are listed and a status of “Online” shows for all discovered thermostats
• The “Last Updated” column will read “Download Pending”• Click on the “Edit” button of a thermostat to begin
configuration
7
WebStat Programming/Configuration
• WebStat uses a wizard to configure the thermostats so it is not necessary to interface directly with the thermostat
• All configuration parameters are chosen from a list of pull down menus in 7 different screens- Properties
- Inputs
- Cooling Configuration
- Heating Configuration
- Outputs
- Setpoints
- Dehumidification
• WebStat also provides customized wiring diagrams for every thermostat configured
8
Properties• Thermostat name
- Add a meaningful thermostat name
• Choose the model- T7350H1009 for staged and T7350H1017 for modulating
• Equipment type- Conventional or Heat Pump
• Neuron ID- Already filled in via the auto discovery
• Keypad lockout- Choose to lockout keys on the thermostat
• System mode- Auto, Off, Cool or Heat
• Fan Switch- On or Auto
• Override duration- Choose from 1 to 8 hours for the override duration
• Transformers- Use only for wiring diagram purposes
9
Inputs• Room temperature input
- Choose local to use the on board sensor, select from different remote sensors or choose to network to get temperature from another T7350 If a remote sensor is selected, choose the number of remote sensors if averaging is
desired and a wiring diagram will be created detailing the correct wiring for sensors
• Relative humidity input- Choose local for the on board sensor, remote for a remote sensor or
network to get relative humidity from another T7350
• Outdoor temperature input- Choose remote if an outdoor air sensor is connected to this thermostat, or
choose network if another T7350 has the outdoor air sensor
• Occupancy sensor input- Choose none, remote or network for an occupancy sensor
• Discharge air temperature input- Choose none or remote
10
Cooling Configuration• Stages required
- Choose 1 to 4 stages of cooling To choose 4 stages of cooling, heating stages must be set to 2 or fewer
• Extended fan- You may extend the fan run time after the compressor shuts down by 40
seconds if desired
• Cycle rate- Choose 3 or 4 cycles per hour (cph)
• Advanced settings- Cooling OAT lockout
Pick an outdoor temperature at which to lock out cooling
- Cooling DAT lockout Pick a discharge air temperature at which to begin shutting down stages of cooling
11
Heating Configuration• Stages required
- Choose 1 to 3 stages of heating If 4 stages of cooling has been chosen, only 2 stages of heat are available
• Fan operation- Choose ON With Heat to turn the fan on immediately with a call for heat
- Choose OFF With Heat to let the equipment turn on the fan
• Extended fan- You may extend the fan run time after the heat shuts down by 90 seconds
if desired
• Cycle rate- Choose 3, 6, 9 or 20 cycles per hour (cph)
• Advanced settings- Heating OAT lockout
Pick an outdoor temperature at which to lock out heating
- Heating DAT lockout Pick a discharge air temperature at which to begin shutting down stages of heating
12
Outputs• Auxiliary output logic
- Time of Day (TOD) Output will energize during Occupied and de-energize during Unoccupied
- Economizer Same as TOD but will energize during Unoccupied on a call for cooling
- Simple Dehumid Output will close whenever humidity is higher than the high limit
• There is a 5 minuet minimum on timer and a 5% hysteresis for dehumidification
- Hot Gas Bypass Same as simple dehumid, but will not energize if a stage of cooling is on
• Reversing valve- Only for heat pumps, choose active on heating or cooling
• Advanced- Gives access to the PID control loop
Strongly recommended that these settings not be changed
13
Setpoints• Choose setpoints for Occupied, Unoccupied and Standby
- There is a minimum deadband of 2°F
- The heating setpoint must be lower than the cooling setpoint
• Advanced- Maximum and minimum stops can be set for heating and cooling
setpoints
- Recovery ramp rates for heating and cooling are set
14
Dehumidification• Dehumidification high limit
- This high limit may be changed via the keypad as well
• Minimum on time- Choose a minimum run time for the compressor when the humidity is
above the high limit
• Reheat- When humidity is above the high limit, the first stage of heating and
cooling will run at the same time
• Reset temperature setpoint- Choose to lower the cooling setpoint when humidity is above the high
limit
15
Wiring
• A list of terminal designations is provided• Click on View Wiring to see a wiring diagram• Click on View Sensor to see a sensor wiring diagram
- Only shown for thermostats with sensor averaging
16
Wiring
• Custom wiring diagrams for each thermostat configured
Subbase wiring
Remote sensor averaging wiring
17
Wiring
• Clicking the “Finish” button will bring you back to the Thermostats page
• Click on the “Schedules” tab to begin creating schedules
18
Schedules
• Existing Schedules will show in the left column• Click on “New Schedule” to create a new schedule
19
Schedules
• Type a name for the new schedule• Schedule events by clicking on endpoints and stretching
or shrinking the event• To shift events, hold down on the Shift key and drag
20
Schedules
• To change the type of event, click on the event and then choose Occupied, Unoccupied or Standby
• To delete an event, click on the event and click “Delete Event”
21
Special Events
• Choose a name for the new holiday• Choose Date, Date Range or Day and Week• Select the date(s) and choose Occupied or Unoccupied as
well as a start and end time of day for the event
22
Special Events
• Click the “Assign Thermostats” tab to assign thermostats to the newly created schedule
• Highlight the thermostat(s) and click the right arrow button to assign the thermostat to the schedule
23
Schedules
• Assigned thermostats will now show on the schedules tab
www.honeywell.com