v = is the speed of waves in the medium
vs = is the velocity of the source
Approximate relationship between fluid velocity and measured time. Does not include clamp on transducer delays.
The general principle of Doppler flow measurement.
Doppler Flow Measurement
• Continuous frequency is transmitted
• Sound bounces off gas bubbles or particles in the fluid• Reflected sound returns at an altered frequency
How it Works:
Modes of operation
• - Single head Transmit and
Receive Crystals in same Head
• - Dual-Head Transmit and
Receive Crystals in separate Heads
Doppler Sensor MountingAvoid Turbulent Flow
• Locate the Doppler Sensor 6 to 10 pipe diameters from Pipe Elbows or Tees
• Avoid highly Turbulent Flow locations
FLO W
Doppler Sensor MountingAvoid Laminar Flow
• Viscous or solids-bearing liquids develop a laminar profile
• Take readings at several locations and mount Sensor where flow is evenly distributed
Doppler Sensor MountingAvoid Velocity-Increasing Devices
• Locate the Doppler Sensor 25 to 40 Pipe Diameters from Pumps, Controlling Valves, Orifice Plates, Pipe Discharges or any other Velocity-Increasing Devices
25 - 40 Pipe Diameters
PUMP
Doppler Sensor MountingAvoid Flow in Branch Lines
• Doppler ultrasonic signals can travel long distances in clean, non-aerated liquids
• Mount the Doppler Sensor 25 to 50 diameters from branch lines with flow