WESTERN REGION GAS CONFERENCE AUGUST 21, 2012 CORROSION 101 BASIC CORROSION MADE CLEAR AS MUD PRESENTED BY John Brodar P.E. of the Salt River Project

Upload: jadyn

Post on 24-Jan-2016

31 views

Category:

Documents


1 download

DESCRIPTION

WESTERN REGION GAS CONFERENCE AUGUST 21, 2012 CORROSION 101. BASIC CORROSION MADE CLEAR AS MUD PRESENTED BY John Brodar P.E. of the Salt River Project. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WESTERN REGION GAS CONFERENCE AUGUST 21, 2012

CORROSION 101

BASIC CORROSIONMADE

CLEAR AS MUDPRESENTED BY John Brodar P.E. of the Salt River Project

Page 2: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

IGNITION SOURCE

FUEL OXYGEN

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

FIRE TRIANGLE CORROSION RECTANGLE

Page 3: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

IGNITION SOURCE

FUEL OXYGEN

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

FIRE TRIANGLE CORROSION RECTANGLE

Just as Fire requires all three conditions (Fuel, Oxygen and an Ignition Source) to burn, several conditions must be present for Corrosion to occur.

Corrosion requires an anode, a cathode, an electrolyte and a metallic path connecting the anode and cathode. If any one of these conditions is not present or prevented, corrosion will not occur. Corrosion is electrochemical in nature: the electrolyte and metallic path are necessary for current to flow. If there is no current flow there is no corrosion.

Page 4: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

Page 5: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

ACMECAMEMECAECAM … REMOVE ANYONE AND THERE IS NO CORROSION.

Page 6: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

REMOVE THE ANODEREMOVE THE CATHODE

REMOVE THE METALLIC PATHREMOVE THE ELECTROLYTE AND YOU

STOP CORROSION.

Page 7: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

REMOVE THE ANODEREMOVE THE CATHODE

REMOVE THE METALLIC PATHREMOVE THE ELECTROLYTE AND YOU

STOP CORROSION.

Page 8: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

REMOVE THE ANODEREMOVE THE CATHODE

REMOVE THE METALLIC PATHREMOVE THE ELECTROLYTE AND YOU

STOP CORROSION.

Page 9: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

REMOVE THE ANODEREMOVE THE CATHODE

REMOVE THE METALLIC PATHREMOVE THE ELECTROLYTE AND YOU

STOP CORROSION.

Page 10: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

REMOVE THE ANODEREMOVE THE CATHODE

REMOVE THE METALLIC PATHREMOVE THE ELECTROLYTE AND YOU

STOP CORROSION.

Page 11: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT MAKES SOMETHING AN ANODE?

Page 12: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT MAKES SOMETHING AN ANODE?

WHAT MAKES SOMETHING A CATHODE?

Page 13: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT MAKES SOMETHING AN ANODE?

WHAT MAKES SOMETHING A CATHODE?

DIFFERENCES!

Page 14: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT MAKES SOMETHING AN ANODE?

WHAT MAKES SOMETHING A CATHODE?

DIFFERENCES!

Page 15: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT MAKES SOMETHING AN ANODE?

WHAT MAKES SOMETHING A CATHODE?

DIFFERENCES!

Page 16: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT MAKES SOMETHING AN ANODE?

WHAT MAKES SOMETHING A CATHODE?

DIFFERENCES!

Page 17: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ +

E = 1 volt

R = 1000 ohmsI

milliampsorampsohms

volt1001.

1000

1I

Page 18: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ +

I

milliampsorampsohms

volt1001.

1000

1I

Page 19: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ +

I

Page 20: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ + The “I” is

conventional current.

I

Page 21: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ + The “I” is

conventional current.

Conventional current always

leaves the positive side of

the battery.

I

Page 22: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ + The “I” is

conventional current.

Conventional current always leaves the positive side of the

battery.

I

In Cathodic Protection the direction of conventional current is incredibly

important!

Page 23: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

Page 24: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Electrochemical Circuits

C

e-Metallic Path

+ ions

- ions

Electrolytic Path

Conventional Current Flow

A C

Metallic Path

+ ions

ions

Electrolytic Path

Conventional Current Flow

Page 25: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Components of a Corrosion Cell

• Anode (oxidation reaction)

– corrosion

• Cathode (reduction reaction)

– no corrosion

• Electrolyte (cations and anions)

• External path (usually metallic)

Page 26: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Electron and Ion Flow

++

+

+

ELECTROLYTE

e-

e-

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Electron Flow

ELECTROLYTEELECTROLYTE

CATHODE ANODE

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Electron Flowe-

e-

e-e-e- e- e-

e-

+

Page 27: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Electron and Ion Flow

++

+

+

ELECTROLYTE

e-

e-

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Electron Flow

ELECTROLYTEELECTROLYTE

CATHODE ANODE

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Electron Flowe-

e-

e-e-e- e- e-

e-

+

Direction of Conventional Current Flow

Page 28: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Direction of Conventional Current Flow

++

+

+

ELECTROLYTE

e-

e-

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Electron Flow

ELECTROLYTEELECTROLYTE

CATHODE ANODE

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Electron Flowe-

e-

e-e-e- e- e-

e-

+

Direction of Conventional Current Flow

Page 29: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

IN THE ELECTROLYTE, AS CONVENTIONAL CURRENT

LEAVES THE ANODE

IT TAKES IRON IONS INTO SOLUTION:

CORROSION OCCURS

Page 30: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Fe++

Fe++

Fe++

Fe++

Fe++

Fe++

Fe++

Fe++

Fe++

e-

e- e-

e-

e-e-

e-

e-

e-

e-

e-

e-

e-e-

e-

e-e-

e-

ANODE

ELECTROLYTE

Anodic Process (half reaction)

Page 31: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

AS CONVENTIONAL CURRENT LEAVES THE ANODE IN THE ELECTROLYTE CORROSION OCCURS

++

+

+

ELECTROLYTE

e-

e-

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

Direction of Conventional Current Flow

ELECTROLYTEELECTROLYTE

CATHODE ANODE

e-

e-

e-

e-e-

e-

e-

e-

e-e-

e-e-

e-

e-e-

e-e-e- e- e-

e-

+

Page 32: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Illustration of Ohm’s Law_ + The “I” is

conventional current.

Conventional current always leaves the positive side of the

battery.

I

In Cathodic Protection the direction of conventional current is incredibly

important!

Page 33: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Voltmeter Circuit Connection

+ _

+_

VOLTS

Parallel Connection

RA RBRC

E

I

Page 34: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Voltage Sign

Current

+_

Voltage measurement is positive20 mV

20 mV

Page 35: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Potential Measurement Between Two Reference Electrodes

+ Reading

+ _

ReferenceElectrode

Voltmeter with+ Reading

ReferenceElectrode

Current

Page 36: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Sign of Voltage for Dissimilar Metals

Noble Active

+_

Voltage measurement is positive

.600 V

Page 37: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Sign of Voltage for Dissimilar Metals

Noble Active

+_

Voltage measurement is positive

.600 V

ANODENEGATIVE -OXIDATIONRUSTLOSE ELECTRONSLOSE POSITIVE IONSGAIN NEGATIVE IONS

CATHODEPOSITIVE +REDUCTIONDOES NOT RUSTGAINS ELECTRONSGAINS POSITIVE IONSREPELS NEGATIVE IONS

Page 38: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Electrochemical Circuits

C

e-Metallic Path

+ ions

- ions

Electrolytic Path

Conventional Current Flow

A C

Metallic Path

+ ions

ions

Electrolytic Path

Conventional Current Flow

Page 39: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Voltmeter ConnectionsPipe-to-Soil Potential Measurement

.900 v

+_

Pipe

Electrolyte

ReferenceCell

Voltmeter Meter display is apostive reading.Record a negativeP/S Potential.

-.900 v

+ _

Pipe

Electrolyte

ReferenceCell

Voltmeter Meter display is anegative reading.Record a negativeP/S Potential.

Page 40: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

Page 41: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

STEEL (IRON)

Page 42: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

STEEL (IRON)

COPPER

Page 43: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

STEEL (IRON)COPPER

GALVANIZED STEEL (ZINC)

Page 44: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

STEEL (IRON)COPPER

GALVANIZED STEEL (ZINC)

MAGNESIUM

Page 45: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

STEEL (IRON)COPPER

GALVANIZED STEEL (ZINC)MAGNESIUM

Page 46: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

WHICH IS AN ANODE?

Page 47: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

WHICH IS AN ANODE?WHICH IS A CATHODE?

Page 48: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT ARE THE FOUR MOST COMMONLY USED METALS

UNDERGROUND?

WHICH IS AN ANODE?WHICH IS A CATHODE?

ALL OF THEM CAN BE EITHER!

Page 49: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

DID YOU KNOW THAT EACH OF THESE METALS HAS A

DIFFERENT NATURAL VOLTAGE OR POTENTIAL?

STEEL (IRON)COPPER

GALVANIZED STEEL (ZINC)MAGNESIUM

Page 50: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

COMPARE OTHER METALS TO STEEL

INTRODUCE THE REFERENCE CELLTYPICAL POTENTIALS RELATIVE TO

CSE

Page 51: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101
Page 52: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Reference Electrodes (Half Cells)Reference Electrodes (Half Cells)

Page 53: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Portable Reference Electrodes

Page 54: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Copper-Copper Sulfate Reference Electrode

Copper Rod

Saturated CopperSulfate Solution

Undissolved CopperSulfate Crystals

PorousPlug

ClearWindow

Removal Cap

Connection for Test Lead

Page 55: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

CORROSION IS AN ELECTRO-CHEMICAL PHENOMENON.

IN WATER IMMERSION SERVICE IT IS RELATIVELY EASY, UNDER SOME CONDITIONS, TO WORK WITH THE CHEMICAL PORTION

OF THIS PHENOMENON.

Page 56: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

ITS CALLED WATER TREATMENT AND IS USED IN MANY DIFFERENT

INDUSTRIES.

Page 57: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

CORROSION IS AN ELECTRO-CHEMICAL PHENOMENON. IN WATER IMMERSION SERVICE IT IS RELATIVELY EASY, UNDER

SOME CONDITIONS, TO WORK WITH THE CHEMICAL PORTION OF THIS PHENOMENON.

UNDERGROUND IT IS VERY DIFFICULT TO WORK WITH THE CHEMICAL PORTION. THAT’S WHY IT IS SO

IMPORTANT TO UNDERSTAND AND BE ABLE TO WORK WITH THE ELECTRICAL

PORTION.

Page 58: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

LET’S LOOK AT IRON

Page 59: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN AN IRON ATOM CORRODES SEVERAL THINGS HAPPEN AT THE

SAME TIME

Page 60: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN AN IRON ATOM CORRODES SEVERAL THINGS HAPPEN AT THE

SAME TIME

THE IRON ATOM GIVES OFF TWO ELECTRONS AND BECOMES POSITIVE

Page 61: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN AN IRON ATOM CORRODES SEVERAL THINGS HAPPEN AT THE

SAME TIME

THE IRON ATOM GIVES OFF TWO ELECTRONS AND BECOMES POSITIVE

THE IRON IS NO LONGER CALLED AN ATOM IT IS NOW AN ION WITH A

PLUS TWO VALIANCE.

Page 62: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN AN IRON ATOM CORRODES SEVERAL THINGS HAPPEN AT THE

SAME TIME

THE IRON ATOM GIVES OFF TWO ELECTRONS AND BECOMES POSITIVE

THE IRON IS NO LONGER CALLED AN ATOM IT IS NOW AN ION WITH A PLUS TWO VALIANCE.

THE IRON ION NO LONGER STICKS TO THE OTHER IRON ATOMS, IT GOES

INTO SOLUTION.

Page 63: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN AN IRON ATOM CORRODES SEVERAL THINGS HAPPEN AT THE

SAME TIME

THE IRON ATOM GIVES OFF TWO ELECTRONS AND BECOMES POSITIVE

THE IRON IS NO LONGER CALLED AN ATOM IT IS NOW AN ION WITH A PLUS TWO VALIANCE.

THE IRON ION NO LONGER STICKS TO THE OTHER IRON ATOMS, IT GOES INTO SOLUTION.

THE IRON ATOM CORRODES AND THE CORROSION PRODUCT IS AN IRON ION.

Page 64: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

CORROSION 101

FREE SAMPLES:LET’S MAKE RUST

PRESENTED BY John Brodar P.E. of the Salt River Project

Page 65: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN AN IRON ATOM CORRODES SEVERAL THINGS HAPPEN AT THE

SAME TIME

THE IRON ATOM GIVES OFF TWO ELECTRONS AND BECOMES POSITIVE

THE IRON IS NO LONGER CALLED AN ATOM IT IS NOW AN ION WITH A PLUS TWO VALIANCE.

THE IRON ION NO LONGER STICKS TO THE OTHER IRON ATOMS, IT GOES INTO SOLUTION.

THE IRON ATOM CORRODES AND THE CORROSION PRODUCT IS AN IRON ION.

Page 66: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

++ ++ ++ ++ ++++ ++ ++ ++ ++ ++ ++ ++ +++ ++ ++ ++

++ ++ ++ ++ ++ ++ ++++ ++ ++ ++ ++ ++ ++

Page 67: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHEN WILL THIS END?++ ++ ++ ++ ++ ++ ++ ++ +++ ++ ++ ++

++ ++ ++ ++ ++ ++ ++++ ++ ++ ++ ++ ++ ++

Page 68: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHAT CAN WE DO?++ ++ ++ ++ ++ ++ ++ ++ +++ ++ ++ ++

++ ++ ++ ++ ++ ++ ++++ ++ ++ ++ ++ ++ ++

Page 69: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

METALLIC PATH

ELECTROLYTE

ANODE CATHODE

CORROSION RECTANGLE

YOU’RE RIGHT. THE FIRST LINE OF DEFENSE AGAINST CORROSION IS COATINGS.

THEY ARE RELATIVELY CHEAP AND AMAZINGLY EFFECTIVE.

EXCEPT..

Page 70: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

COATINGS ARE EFFECTIVE EXCEPT

AT HOLIDAYS (COATING DEFECTS AT THE TIME OF APPLICATION).

OR AT DAMAGED AREAS.DAMAGE MAY OCCUR DURING

MANUFACTURE, TRANSPORTATION, INSTALLATION OR IN SERVICE.

Page 71: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

HOW BAD CAN THE CORROSION AT A

DAMAGED AREA OF THE COATING BE?

Page 72: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

FARADAY’S LAW

FOR STEEL FARADAY’S LAW SAYS THAT ONE AMPERE OF CURRENT FLOWING OFF OF STEEL FOR ONE

YEAR WILL CAUSE THE CORROSION OF 20 POUNDS OF STEEL.

Page 73: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

FARADAY’S LAW IS VERY MUCH A MATHEMATICAL RELATIONSHIP.

½ AMP FOR ONE YEAR WILL CONSUME 10 POUNDS OF STEEL

½ AMP FOR TWO YEARS WILL CONSUME 20 POUNDS OF STEEL

2 AMPS FOR ½ YEAR WILL CONSUME 20 POUNDS OF STEEL

Page 74: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

CURRENT FLOWING OFF OF YOUR PIPELINE WILL CONSUME STEEL.

HOW MUCH DOES A ½” DIAMETER HOLE IN A ¼” WALL PIPE WEIGH?

NOT MUCH!

JUST 0.0558 LBS.

Page 75: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

HOW MUCH CURRENT DOES IT TAKE TO MAKE THAT ½” HOLE?

1 YEAR @ 0.0028 AMPS

2 YEARS @ 0.0014 AMPS OR 1.4 MILLIAMPS

5 YEARS @ 0.6 ma

10 YEARS @ 0.28 ma that’s little more than ¼ ma

Page 76: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Why coatings?

Page 77: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Why coatings?

BECAUSE COATINGS ARE THE CHEAPEST THING WE CAN DO

TO STOP CORROSION.

Page 78: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Why cathodic protection?

Page 79: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Why cathodic protection?

Since coatings are not perfect we have to do something to protect

the holidays and damaged areas. AND

Page 80: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Why cathodic protection?

CATHODIC PROTECTION IS THE EASIEST THING TO DO TO A PIPELINE

AFTER IT IS INSTALLED.

Page 81: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

DEMO PROTECTED PIPE

Page 82: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

AnodeCathode

Microscopic Corrosion Cell on the Surface of a Pipeline

Microscopic View of a Corrosion Cell

Page 83: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

AnodeCathode

Metallic Connection

Electrolyte

Cathodic Protection Anode

Cathodic Protection Current Applied

Cathodic Protection on a Structure (Macroscopic

view)

Page 84: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

84 of 40

-.5 -.6 -.65 -.6 -.7 -.58

-.5 -.6 -.65 -.6

-.6

-.5

NativePotentials

CorrosionMitigated

Polarization of a Structure

NATURALLY OCCURING CATHODE. MORE POSITIVE

NATURALLY OCCURING ANODE. MORE NEGATIVE

-.7 -.58

Page 85: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

APPLY (PARTIAL) CATHODIC PROTECTION!!

Prepare to duck.

Page 86: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

86 of 40

-.5 -.6 -.65 -.6 -.7 -.58

-.58 -.6 -.65 -.6 -.7 -.58

NativePotentials

CorrosionMitigated

Polarization of a Structure

Page 87: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

APPLY (PARTIAL) CATHODIC PROTECTION!!

APPLY MORE CATHODIC PROTECTION

Page 88: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

88 of 40

-.5 -.6 -.65 -.6 -.7 -.58

-.58 -.6 -.65 -.6 -.7 -.58

-.6 -.6 -.65 -.6 -.7 -.6

NativePotentials

CorrosionMitigated

Polarization of a Structure

Page 89: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

APPLY (PARTIAL) CATHODIC PROTECTION!!

APPLY MORE CATHODIC PROTECTION

APPLY EVEN MORE CATHODIC PROTECTION

Page 90: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

90 of 40

-.5 -.6 -.65 -.6 -.7 -.58

-.58 -.6 -.65 -.6 -.7 -.58

-.6 -.6 -.65 -.6 -.7 -.6

-.65 -.65 -.65 -.65 -.7 -.65

NativePotentials

CorrosionMitigated

Polarization of a Structure

Page 91: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

APPLY (PARTIAL) CATHODIC PROTECTION!!

APPLY MORE CATHODIC PROTECTION

APPLY SUFFICIENT CATHODIC PROTECTION

Page 92: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

92 of 40

-.5 -.6 -.65 -.6 -.7 -.58

-.58 -.6 -.65 -.6 -.7 -.58

-.6 -.6 -.65 -.6 -.7 -.6

-.65 -.65 -.65 -.65 -.7 -.65

-.7 -.7 -.7 -.7 -.7 -.7

NativePotentials

CorrosionMitigated

Polarization of a Structure

Page 93: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

AnodeCathode

Metallic Connection

Electrolyte

Cathodic Protection Anode

Cathodic Protection Current Applied

Cathodic Protection on a Structure (Macroscopic

view)

Page 94: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

9 of 40

-.5 -.6 -.65 -.6 -.7 -.58

-.58 -.6 -.65 -.6 -.7 -.58

-.6 -.6 -.65 -.6 -.7 -.6

-.65 -.65 -.65 -.65 -.7 -.65

-.7 -.7 -.7 -.7 -.7 -.7

NativePotentials

CorrosionMitigated

Polarization of a Structure

Cathodic ProtectionCathodic protection is the cathodic polarization of all noble potential areas (cathodes) to the most active potential on the metal surface. Cathodic protection is achieved by making the structure the cathode of a direct current circuit. The flow of current in this circuit is adjusted to assure that the polarized potential is at least as active as the most active anode site on the structure. NACE CP 1

When the potential of all cathode sites reach the open circuit potential of the most active anode site, corrosion on the structure is eliminated. NACE CP2 Slides

Cathodic protection is the polarization of the most cathodic areas on a structure to a potential equal to or more negative than the most anodic potential on the structure. When all areas are polarized to a potential equal to or more negative than -850 mv relative to a copper copper sulfate reference electrode, all corrosion has been halted.

Page 95: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101
Page 96: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

DEMO TEST REELS

Page 97: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Close Interval Potential Survey Close Interval Potential Survey Reading

+_

Cu/Cu SO4

Ref. Cell

Voltmeter

Pipe

Electrolyte

Page 98: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

CIS Potential ProfileCIS Potential Profile

Page 99: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

DEMO TWO WIRES

Page 100: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Shunts

Page 101: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Current Shunts

• Measure voltage drop across a known resistance.

• Current is calculated using Ohm’s Law.

Page 102: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Shunt Measurement

Vmeasured

Rshunt

Icalculated =+ _

+_

VOLTS

RA

RB

RC

E

I

Current Shunt with known resistance value is in series with the circuit

Voltmeter is connected in parallel across the current shunt

Vmeasured

Rshunt

Icalculated =Vmeasured

Rshunt

Icalculated =+ _

+_

VOLTS

RA

RB

RC

E

I

Current Shunt with known resistance value is in series with the circuit

Voltmeter is connected in parallel across the current shunt

+ _

+_

VOLTS

RA

RB

RC

E

I

Current Shunt with known resistance value is in series with the circuit

Voltmeter is connected in parallel across the current shunt

+ _

+_

VOLTS

RA

RB

RC

E

I

Current Shunt with known resistance value is in series with the circuit

Voltmeter is connected in parallel across the current shunt

Page 103: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Current Shunt Calculations #1

Given:Shunt = .01 ohmsVoltage across shunt = 50 mV

Calculate Current:1. Convert units of voltage, 50mV = .05 v2. Calculate current using Ohm’s Law,

I = .05 v /.01 ohms = 5 amps

Page 104: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Current Shunt Calculations #2

I = 28 mV x 15 amps 50 mV

= 8.4 amps

Given:Shunt = 15 amps 50 millivoltsVoltage across shunt = 28 mV

Calculate Current:

Page 105: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Direction of Current Flow

+ _

+_

VOLTS

RA

RB

RC

E

I

Current Flow is from Left to Right

Up Scale Deflection

Page 106: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Typical Current MeasurementsTypical Current Measurements

There are several current measurements commonly made in cathodic protection surveys:

• Current output of a galvanic anode system• Rectifier current output• Test current for determining current

requirement of a structure• Current on a structure (this is a voltage

measurement, and current is calculated)• Current across a bond

Page 107: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Current Along a Pipeline

+_

+_

Voltage measurement is positive20 mV

Page 108: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

2-Wire Line Current Test

Pipe Span in Feet

Wires must be color coded

0.17 mV

+ _

Pipe size and wall thickness or weight per foot must be known

Pipeline

N

West East

Pipe Span in Feet

Wires must be color coded

0.17 mV

+ _

Pipe size and wall thickness or weight per foot must be known

Pipeline

N

Pipe Span in Feet

Wires must be color coded

0.17 mV

+ _

Pipe size and wall thickness or weight per foot must be known

Pipeline

Pipe Span in Feet

Wires must be color coded

0.17 mV

+ _

Pipe size and wall thickness or weight per foot must be known

Pipeline

N

West East

Page 109: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Example of 2-Wire Current Line CalculationsExample of 2-Wire Current Line Calculations

• Pipe span = 200 feet• Pipe is 30-inch weighing 118.7 pounds/ foot • Voltage drop across span = 0.17 millivolts• Determined resistance of span = 4.88 x 10-4 ohms• Calculated current flow = 348 milliamps from west to

east

Page 110: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

4-Wire Line Current Test4-Wire Line Current Test

Pipe Span for Measuring Current

Wires must be color coded

0.17 mV

+ _

Pipeline

PowerSource

+_

CurrentInterrupter +

_

AMPS

VOLTS

Page 111: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

CLEARLLY THE 4 WIRE LINE CURRENT TEST IS MORE COMPLEX. YOU ONLY HAVE TO DO IT ONCE

FOR ANY PARTICULAR PIPE SEGMENT TO DETERMINE THE

RESISTANCE.

IT IS A MULTI STEP PROCESS.

Page 112: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

AFTER YOU BECOME AN OHM’S LAWYER AND CAN WORK WITH

E=IRI=E/RR=E/I

Page 113: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

YOU WILL UNDERSTAND THAT IF YOU PASS A KNOWN CURRENT

AND MEASURE A VOLTAGE YOU CAN USE OHM’S LAW TO CALCULATE RESISTANCE.

Page 114: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

ONCE YOU KNOW THE RESISTANCE FOR A SECTION OF PIPE, YOU CAN NOW MEASURE A VOLTAGE DROP AND, AGAIN USING OHM’S LAW,

CALCULAE THE ACTUAL CURRENT FLOWING IN THE PIPE.

Page 115: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

4-Wire Line Current Test4-Wire Line Current Test

Pipe Span for Measuring Current

Wires must be color coded

0.17 mV

+ _

Pipeline

PowerSource

+_

CurrentInterrupter +

_

AMPS

VOLTS

Page 116: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Example of 4-Wire Current Line Calculations

Example of 4-Wire Current Line Calculations

• Test current = 10 amps• Potential shift due to test current (ON= 5.08millivolts

and OFF = 0.17 millivolts) = 4.91 millivolts• Calibration factor (10/4.91) = 2.04 amps/millivolts• Voltage drop across span = 0.17 millivolts• Calculated current flow (2.04 x 0.17) = 347 milliamps

from east to west

Page 117: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

WHY ARE ANODES SOMETIMES NEGATIVE

AND SOMETIMES POSITIVE?????

Page 118: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Galvanic Anode Cathodic Protection SystemA Cathodic Protection System

ANODE

CURRENT

Page 119: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Impressed Current Cathodic ProtectionImpressed Current System

ANODE

CU

RR

EN

T

PowerSource

+-

CU

RR

EN

T

Page 120: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

APPLY (PARTIAL) CATHODIC PROTECTION!!

APPLY MORE CATHODIC PROTECTION

APPLY SUFFICIENT CATHODIC PROTECTION

OVER PROTECT A SEGMENT OF PIPELINE

Page 121: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Electrical Shielding due to Shorted Casing

Pipe Lying on Casing due toPipe Lying on Casing due toLack of Insulating SpacersLack of Insulating Spacers

Vent PipeVent Pipe

End SealCasingCasing

PavementPavement

Page 122: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

4-Wire Line Current Test4-Wire Line Current Test

Pipe Span for Measuring Current

Wires must be color coded

0.17 mV

+ _

Pipeline

PowerSource

+_

CurrentInterrupter +

_

AMPS

VOLTS

Page 123: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Criteria for Cathodic Protection

• Cathodic protection is a polarization phenomenon.• Cathodic protection is achieved when the open circuit

potential of the cathodes are polarized to the open circuit potential of the anodes.

• Practical application makes use of structure-to-electrolyte potentials.

Page 124: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

NACE Standards for Underground or Submerged Iron and Steel

• SP0169 Control of External Corrosion on Underground or Submerged Metallic Piping Systems

• SP0285 Corrosion Control of Underground Storage Tank Systems by Cathodic Protection

Page 125: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Criteria for Underground or Submerged Iron or Steel Structures

• –0.850 volt potential--Negative (cathodic) potential of at least 850 mV with the cathodic protection applied

• –0.850 volt polarized potential--Negative polarized potential of at least 850 mV

• 100 millivolts polarization--Minimum of 100 mV of cathodic polarization

Page 126: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Resistances

Measuring Lead (+)

Contact Lead (+)/Ref. Cell

Reference Cell

Contact Reference Cell

to Electrolyte

Electrolyte

Polarization

Structure

Contact Test Lead/Structure

Test Lead

Contact Test/Measuring Lead

Measuring Lead (-)

Internal Meter

Voltage (IR) Drops Across a Measuring CircuitVoltage (IR) Drops Across a Measuring Circuit

Cathodic Protection Tutorial Three NACE International, 2001

.900 v

+ _

PolarizationFilm Structure

Electrolyte

ReferenceCell

Voltmeter

Measurement & C.P. current across electrolyte

Page 127: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

IR Drops Across Electrolyte

• Reference electrode placement• Current interruption

Page 128: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Time

Pote

nti

al

+

-

t=0

-850 mV On

-850 mV Instant Offor IR Corrected

IR

Depolarization

Depolarized Potential

100 mVPolarization

Pipe-to-Soil PotentialsPipe-to-Soil Potentials

Page 129: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.81 0.81

0.74

0.69

0.680.675

0.67

0.74

0.75

0.76

0.77

0.78

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Page 130: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State (48 Amps) Rectifier Turned Off

Page 131: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off Potential

Rectifier Turned Off

Page 132: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Page 133: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Depolarization Occurs Over Time

Page 134: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Depolarization Occurs Over Time

Rectifier Turned On (Adjusted to 36 Amps)

Page 135: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Depolarization Occurs Over Time

Rectifier Turned On

IR

DROP

Page 136: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Depolarization Occurs Over Time

Rectifier Turned On

IR

DROP

Instant On Potential

Page 137: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Depolarization Occurs Over Time

Rectifier Turned On

IR

DROP

Instant On Potential

Polarization Increases Over Time.

Page 138: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank Potentials 8/2/79

0.6

0.65

0.7

0.75

0.8

0.85

0 10 20 30 40 50 60 70 80 90

Time in Minutes

Po

ten

tial

to

Cu

Cu

So

4 (N

egat

ive

Nu

mb

ers)

Steady State

Instant Off

IR

DROP

Depolarization Occurs Over Time

Rectifier Turned On

IR

DROP

Instant On Potential

THIS POTENTIAL INCREASE IS CATHODIC PROTECTION !

Page 139: WESTERN REGION GAS CONFERENCE AUGUST 21, 2012  CORROSION 101

Santan Raw Water Tank On Potentials

0

5

10

15

20

25

30

35

40

45

0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90

Potential to CuSO4 (Negative Numbers)

Hei

gh

t o

f T

ank

In F

eet

11 V 33.5 Amps 10/19/79 Water Flowing 1800 GPM 11 V 36 A 8/20/79 No Flow