Wet Pipe Sprinkler System

Expansion ChamberSales Presentation October 2004

FIRE-X-TROLFIRE-X-TROLFeatures & BenefitsFeatures & Benefits

FIRE-X-TROLFIRE-X-TROLFeatures & BenefitsFeatures & Benefits

• Absorbs expanded antifreeze solution

• Diaphragm expansion chamber (4X cycles of a bladder style tank)

• Protects system and components from thermal expansion

• UL listed

– for use with fire protection antifreeze systems per NFPA 13

• ASME

– Designed, constructed, and tested per ASME Section VIII, Division 1 Standards

– Available code and non-code

FIRE-X-TROLFIRE-X-TROLFeatures & BenefitsFeatures & Benefits

FIRE-X-TROLFIRE-X-TROLFeatures & BenefitsFeatures & Benefits

• Pre-charge is separated from system fluid

• 5X safety factor by design

• Protects system and components from thermal expansion

• Helps prevent system hydraulic lock-up

• Required when backflow prevention device is used (most local regulations)

• Seismic restraints available (vertical models)

• Antifreeze compatible

– (Glycerine and Propylene Glycol)

• Broad range of sizes

– 4 to 90 gallons (15 – 341 ltr.)

FIRE-X-TROLFIRE-X-TROL How does the Fire-X-Trol work?How does the Fire-X-Trol work?

FIRE-X-TROLFIRE-X-TROL How does the Fire-X-Trol work?How does the Fire-X-Trol work?

1. It is installed between the backflow preventer and fill cup

2. It’s sealed-in dry air/nitrogen pre-charge chamber prevents antifreeze solution from entering it until the system pressure exceeds the pre-charge pressure.

3. As the antifreeze solution temperature rises, expanded system fluid enters the Fire-X-Trol non-corrosive reservoir.

4. The Fire-X-Trol absorbs the pressure increase, keeping system pressure below maximum system rating.

5. As the fluid temperature decreases, pressure in the dry air /nitrogen chamber forces system fluid out of the expansion chamber and back into the system.

FIRE-X-TROLFIRE-X-TROLFIRE-X-TROLFIRE-X-TROL

• Materials of Construction– All steel body construction with stainless steel system

connection

– Polypropylene Liner Material

– Diaphragm Material: UL certified high-performance elastomeric compound

– Coating: FPT Red

• Maximum Operating Conditions– Maximum Working Pressure: 175 psig (12 bar)

– Operating Temperature: -20 F (-29 C) to 200 F (93 C)

– Factory pre-charge: 25 psig (1.7 bar)

FIRE-X-TROL ModelsFIRE-X-TROL ModelsFIRE-X-TROL ModelsFIRE-X-TROL Models

FIRE-X-TROL Installation FIRE-X-TROL Installation SchematicSchematic

FIRE-X-TROL Installation FIRE-X-TROL Installation SchematicSchematic

In-Line ModelsIn-Line Models

Stand ModelsStand Models

FIRE-X-TROL Installation FIRE-X-TROL Installation SchematicSchematic

FIRE-X-TROL Installation FIRE-X-TROL Installation SchematicSchematic

Isolate expansion Isolate expansion chamber during system chamber during system hydro test.hydro test.

Install in supply line Install in supply line between backflow between backflow preventer and fill cup preventer and fill cup connection.connection.

FIRE-X-TROL Installation FIRE-X-TROL Installation SchematicSchematic

FIRE-X-TROL Installation FIRE-X-TROL Installation SchematicSchematic

Isolate expansion Isolate expansion chamber during system chamber during system hydro test.hydro test.

Install in supply line Install in supply line between backflow between backflow preventer and fill cup preventer and fill cup connection.connection.

Fire-X-Trol used with Backflow Fire-X-Trol used with Backflow PreventerPreventer

Fire-X-Trol used with Backflow Fire-X-Trol used with Backflow PreventerPreventer

• NFPA 13 requirement

As stated in NFPA 13, 7.5.3.3:

“Where the connection between the antifreeze solution and the wet pipe incorporates a backflow prevention device, a listed expansion chamber of appropriate size and pre-charged air pressure shall be provided to compensate for thermal expansion of the antifreeze solution…”

1. Visually inspect FIRE-X-TROL for any damage.

2. Hydraulic system pressure must be at zero.

3. Attach nitrogen or dry air supply to expansion chamber charging valve

• Dry air: -50 F / -46 C dew point or lower

4. Pre-charge to 2 psig (0.14 bar) below system static pressure at tank location.

• Never pre-charge below 25% of the system maximum rated pressure.

5. Remove charging hose. Carefully test charging valve for leakage.

6. Replace plastic cap.

FIRE-X-TROLFIRE-X-TROL Installation InstallationFIRE-X-TROLFIRE-X-TROL Installation Installation

Antifreeze Solution TableAntifreeze Solution TableAntifreeze Solution TableAntifreeze Solution Table

Sizing ChartSizing ChartSizing ChartSizing Chart

Note1:Note1: AMTROL recommends installing a pressure reducing valve before the AMTROL recommends installing a pressure reducing valve before the backflow preventer.backflow preventer.

Note 2: Note 2: The system pressure is too close to the maximum working pressure. The system pressure is too close to the maximum working pressure. NFPA 13 recommends installing a pressure reducing valve before the NFPA 13 recommends installing a pressure reducing valve before the backflow preventer.backflow preventer.

Sizing ChartSizing ChartSizing ChartSizing Chart

Note1:Note1: AMTROL recommends installing a pressure reducing valve before the AMTROL recommends installing a pressure reducing valve before the backflow preventer.backflow preventer.

Note 2: Note 2: The system pressure is too close to the maximum working pressure. The system pressure is too close to the maximum working pressure. NFPA 13 recommends installing a pressure reducing valve before the NFPA 13 recommends installing a pressure reducing valve before the backflow preventer.backflow preventer.

• Warranty

– Limited (1) year warranty

• Lead-time

– 10 working days

– Safety stock inventory for quicker delivery if required

FIRE-X-TROLFIRE-X-TROL Warranty and Lead-time Warranty and Lead-time

FIRE-X-TROLFIRE-X-TROL Warranty and Lead-time Warranty and Lead-time

Q: What division does Fire suppression systems fall under?

A: Division 13.

Q: What does NFPA stand for?

A: National Fire Protection Agency

Q: What fluids can be used with the Fire-X-Trol expansion chamber?

A: Glycerine-water and propylene glycol-water mixtures.

Q: What is a Wet Pipe Antifreeze system?

A: Antifreeze systems are typically used as subsystems of a wet pipe system and are intended to protect small areas that could be exposed to freezing temperatures.

FIRE-X-TROLFIRE-X-TROL FAQ’s FAQ’s

FIRE-X-TROLFIRE-X-TROL FAQ’s FAQ’s

Q: What happened to the recommended 40-gallon (151 liter) limit for antifreeze systems?

A: This recommendation has been deleted in the NFPA 13 2002 edition. There is no limit to the size of an

antifreeze system.

Q: Is a reduced-pressure zone backflow prevention device required in an antifreeze system?

A: Many local regulations require that a backflow prevention device be used in the system to guard against any potential contamination of the public water supply.

Q: Is an expansion chamber required when a backflow prevention device is used?

A: Yes. Section 7.5.3.3 of NFPA 13 requires the use of an expansion chamber.

FIRE-X-TROLFIRE-X-TROL FAQ’s FAQ’s

FIRE-X-TROLFIRE-X-TROL FAQ’s FAQ’s

Q: Does antifreeze-water solution expand and contract?

A: Yes. The solution will expand and contract with changes in temperature. The amount of expansion and contraction depends upon total temperature change and the density of the specific solution used.

Q: Is the Fire-X-Trol UL Listed?

A: Yes. The Fire-X-Trol is UL listed and was subject to extensive UL testing for compatibility with antifreeze solutions and to assure that the quality of the

Fire-X-Trol meets fire protection standards.

Q: What are the advantages of an AMTROL diaphragm tank?

A: In extensive cyclic testing and with the performance proven AMTROL diaphragm technology, a diaphragm can typically accommodate 4X the cycles of a bladder style tank.

FIRE-X-TROLFIRE-X-TROL FAQ’s FAQ’s

FIRE-X-TROLFIRE-X-TROL FAQ’s FAQ’s