why grounding is used-8th vis rc

80
BOARD OF ELECTRICAL ENGINEERING INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC. Why GROUNDING!!! Is Used? Jaime V. Mendoza, PEE, MTM Jaime V. Mendoza, PEE, MTM Board Member Board Member 8 th Visayas IIEE Region VII Conference 2007 Cebu International Convention Center Mandaue City, Sept. 28-29, 2007

Upload: danvir-vicente-miclat

Post on 03-Dec-2014

114 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Why Grounding is Used-8th Vis RC

BOARD OF ELECTRICAL ENGINEERINGINSTITUTE OF INTEGRATED ELECTRICAL

ENGINEERS OF THE PHILIPPINES, INC.

Why GROUNDING!!!Is Used?

Jaime V. Mendoza, PEE, MTMJaime V. Mendoza, PEE, MTM

Board MemberBoard Member

8th Visayas IIEE Region VII Conference 2007Cebu International Convention Center

Mandaue City, Sept. 28-29, 2007

Page 2: Why Grounding is Used-8th Vis RC

2

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

TERMINOLGY

In Britain people have “earth” and in North America they have “ground”.

They are exactly the same thing, only different terms are used in different countries.

For example: Earth Leakage Circuit Interrupter and Ground-Fault Circuit Interrupter

Page 3: Why Grounding is Used-8th Vis RC

3

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

To limit voltage imposed by

1. Lightning

2. Line surges

3. Unintentional contact with higher voltage lines

Stabilize the voltage to ground during normal operations.

Facilitate overcurrent device operation in case of ground fault on a solidly grounded system.

PEC- 2000 Section 2.50.1.2(a)

Page 4: Why Grounding is Used-8th Vis RC

4

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

To limit the voltages imposed by lightning or line surge

PEC-2.50.1.2(a)

Page 5: Why Grounding is Used-8th Vis RC

5

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

To limit the voltages imposed by lightning or line surge

Page 6: Why Grounding is Used-8th Vis RC

6

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Facilitate overcurrent device operation in case of ground fault

Metal parts of premises wiring are bonded to an effectiveground-fault current path that has sufficiently low impedanceto quickly clear line-to-case faults by opening the circuit protection device.

240V240V

Page 7: Why Grounding is Used-8th Vis RC

7

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Earth is Not an Effective Ground-Fault Current Path

I = E/R, E = 240V, R = 25 , I = 240/25 = 9.6 AInsufficient current to trip overcurrent protection device

240

9.6

Page 8: Why Grounding is Used-8th Vis RC

8

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Ground Fault Circuit Interrupter

GFCI – A device intended for the protection of personnel that functions to deenergize a circuit or portion thereof within an established period of time when a current to ground exceeds the values established for a device.

The GCFI does not protect someone against receiving an electrical shock, but it does limit the time hazards exists. Hazard exist only during period of time fault is there.

Page 9: Why Grounding is Used-8th Vis RC

9

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GCFI CAN ELIMINATE THIS!

Ground Fault Circuit Interrupter

Page 10: Why Grounding is Used-8th Vis RC

10

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Ground Fault Circuit Interrupter

Page 11: Why Grounding is Used-8th Vis RC

11

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Ground Fault Circuit Interrupter

Page 12: Why Grounding is Used-8th Vis RC

12

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Ground Fault Circuit Interrupter

A GFCI is designed to protect persons against electric shock.It operates on the principles of monitoring the unbalanced currentBetween the ungrounded and the grounded neutral conductor.

Page 13: Why Grounding is Used-8th Vis RC

13

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel1. Dwelling Bathroom Receptacle

and /or 250 V

Page 14: Why Grounding is Used-8th Vis RC

14

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel2. Dwelling Garage Receptacle

[Sec. 2.10.1.8(a)(2)Ex 1]

All 15/20A, 125/250V receptacles installed in a

dwelling unit garage must have GFCI protection.

Page 15: Why Grounding is Used-8th Vis RC

15

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel2. Dwelling Garage Receptacle

All 15 and 20 A, 125/250 V receptacles in accessory

buildings and similar work areas must be GFCI protected.

Page 16: Why Grounding is Used-8th Vis RC

16

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel3. Dwelling Outdoor Receptacle

Section 2.10.1.8(3)

Page 17: Why Grounding is Used-8th Vis RC

17

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel4. Dwelling Basement Receptacle

All 15/20A, 125/250V receptacles in unfinishedareas of basements must be GFCI protected.

Page 18: Why Grounding is Used-8th Vis RC

18

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel5. Dwelling Unfinished Basement

All 15/20A, 125/250V receptacles in unfinishedAreas of basements must be GCFI protected.

Page 19: Why Grounding is Used-8th Vis RC

19

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel6. Kitchens for Countertop Appliances

All 15/20A, 125/250V, receptacles thatserve dwelling unit kitchen countertopsurfaces must be GFCI protected.

Page 20: Why Grounding is Used-8th Vis RC

20

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel6. Dwelling Laundry or Utility Sink

All 15/20A, 250V receptacles located within 6 ft or 1.8 m of a laundry or utility sink must be GFCI protected.

Page 21: Why Grounding is Used-8th Vis RC

21

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

GFCI Protection for Personnel7. Dwelling Wet Bar Sinks

GFCI protection required

if within 1.8 m of sink

Page 22: Why Grounding is Used-8th Vis RC

22

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

PEC 2000- Section 2.10.1.8 (a)

a) Dwelling Units 1. Bathrooms

2. Garages 3. Outdoors 4. Crawl spaces at or below grade

level 5. Unfinished

basements 6. Kitchens for

countertop appliances 7. Wet bar sinks

GFCI Protection for Personnel

Page 23: Why Grounding is Used-8th Vis RC

23

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Electric Shock Severity

1. Path of Current through Body

2. Length of Time Current Flows

3. Amount of Current through Body

Electric Shock

Page 24: Why Grounding is Used-8th Vis RC

24

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effects of AC Electric Shock

RMS Current Effects

1- 5 mA Threshold of sensation

10-20 mA Involuntary muscle contractions

20-100 mA Pain, breathing difficulties

100 - 300 mA Ventricular fibrillation, possible death

> 300 mA Respiratory paralysis, burns, unconsciousness

Page 25: Why Grounding is Used-8th Vis RC

25

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Identification of Equipment Grounding Conductors

PEC 2.50.6.10

Page 26: Why Grounding is Used-8th Vis RC

26

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

But, for a grounding conductor larger than No. 6 AWG or 14 mm2, an insulated conductor of other than green color or green with yellow stripes may be used provided one of the following steps is taken: PEC-2.50.6.10(a)

1. Stripping the insulation from an insulated conductor of another color (say black) for the entire length that is exposed on the box or other enclosure so that the conductor appear as a bare conductor.

2. Painting the exposed insulation green for its entire length within the enclosure.

3. Wrapping the entire length of exposed insulation with green-colored tape or green-colored

adhesive labels.

Identification of Equipment Grounding Conductors

Page 27: Why Grounding is Used-8th Vis RC

27

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing Equipment Grounding Conductors (Sec. 2.50.6.13)

The regulations for calculating the size of equipment grounding conductor are:1. Table 2.50.6.13 shall be used to size the equipment

conductor. ( Based on the rating of the protective device ahead of the equipment.)

2. When ungrounded conductors are increased in size and an equipment grounding is installed with them, the equipment grounding conductor is required to be proportionately increased in size according to the circular mil area of the ungrounded conductors.

Page 28: Why Grounding is Used-8th Vis RC

28

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Page 29: Why Grounding is Used-8th Vis RC

29

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing Equipment Grounding Conductors

The regulations for calculating the size of equipment grounding conductor are:3. Where more than one circuit is installed in a

single raceway or cable, one equipment grounding conductor can be installed in the raceway or cable; it will be sized for the largest overcurrent device protecting conductors in the raceway or cable.

4. An equipment grounding conductor not smaller than 18 AWG copper(0.75 mm2) is permitted for flexible cords when the flexible cord is protected at or over 20 amperes.

Page 30: Why Grounding is Used-8th Vis RC

30

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing Equipment Grounding Conductors

The regulations for calculating the size of equipment grounding conductor are:5. The equipment grounding conductor is never

required to be larger than the circuit conductors.

6. Where the overcurrent protection is an instantaneous circuit breaker or a motor protector, the equipment grounding conductor is sized according to the size of the motor overload protective device.

Page 31: Why Grounding is Used-8th Vis RC

31

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing Equipment Grounding Conductors

The regulations for calculating the size of equipment grounding conductor are:7. When conductors are run in parallel in more

than one raceway or cable , as permitted in Sec. 3.10.1.4, the equipment grounding conductor is run in parallel. Each of the paralleled equipment grounding conductors is sized according to the ampere rating of the overcurrent device protecting the conductors in the raceway or cable.

Page 32: Why Grounding is Used-8th Vis RC

32

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Section 2.50.6.9

Page 33: Why Grounding is Used-8th Vis RC

33

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

European Coloring

Ground wire – green wire with yellow stripe color

Neutral wire – blue color

Live wire – brown

black and black with white strip (for 3-

phase)

European Coding of Grounded Conductor

Page 34: Why Grounding is Used-8th Vis RC

34

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

In the US, Black is the hot wire, white is the neutral or common wire and green is the equipment grounding.

US Coding of Grounded Conductor

Page 35: Why Grounding is Used-8th Vis RC

35

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

The basic rule in PEC- 2.1.1.6(a) requires the grounded conductor Sizes 14 mm2 or smaller to be identified by:

1. A white color

2. A gray color

3. Three continuous white stripes, on other than green insulation, extending

along the entire length of the conductor

Prior to the PEC-2000 Code, the gray color was permitted to be used as a hot conductor.

Means of Identifying Grounded Conductor

Page 36: Why Grounding is Used-8th Vis RC

36

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

This means that you can use either white or gray to identifythe grounded neutral conductor of a single wiring system

Means of Identifying Grounded Conductor

PEC 2.1.1.6(a)

Page 37: Why Grounding is Used-8th Vis RC

37

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Means of Identifying Grounded Conductor

PEC 2.1.1.6(a)

Page 38: Why Grounding is Used-8th Vis RC

38

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Insulated grounded conductor larger than 6 AWG or 14 mm2 to be identified by the one of the following methods: PEC 2.1.1.6(b)

1. By a white or gray outer finish

2. By three continuous white stripes, on other than green insulation, running along the entire length of conductor

3. By a distinctive white marking ,encircling the conductor, placed there at the

time of installation, and the identifying the grounded conductor at each

termination (The identification may be by tagging, marking, painting or other effective means)

Means of Identifying Grounded Conductor

Page 39: Why Grounding is Used-8th Vis RC

39

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Means of Identifying Grounded Conductor

Page 40: Why Grounding is Used-8th Vis RC

40

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Identifying Grounded Neutral Conductors of Different Systems

PEC 2.1.1.6(d)

Page 41: Why Grounding is Used-8th Vis RC

41

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Identifying Grounded Neutral Conductors of Different Systems

Page 42: Why Grounding is Used-8th Vis RC

42

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Identifying Grounded Neutral Conductors of Different Systems

Page 43: Why Grounding is Used-8th Vis RC

43

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Means of Identifying Grounded Conductor

Page 44: Why Grounding is Used-8th Vis RC

44

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

When sizing electrical conductors, the ampacity of the main consideration. This is not the case when sizing electrode conductor, it is sized according to cross-sectional area of the service-entrance conductor.

The size of the grounding electrode conductor is taken directly from Table 2.50.3.1.17 of PEC, when the size of the service entrance conductors is not larger than 1100 kcmil cu. Or 1750 kcmil aluminum.

Sizing the AC Grounding Electrode Conductors

Page 45: Why Grounding is Used-8th Vis RC

45

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Page 46: Why Grounding is Used-8th Vis RC

46

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

When the service entrance conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor shall be 12 ½ % of the largest phase conductor.

Sizing the AC Grounding Electrode Conductors

Page 47: Why Grounding is Used-8th Vis RC

47

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing the AC Grounding Electrode Conductors

Page 48: Why Grounding is Used-8th Vis RC

48

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing the AC Grounding Electrode Conductors

What are the sizes of the grounding electrode conductors of the following if the service entrance conductors used are:

1. 500 kcmil copper

2. 500 kcmil aluminum

3. 1/0 copper

4. 2 copper

Page 49: Why Grounding is Used-8th Vis RC

49

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Installation of Grounding Rods

Basic Requirements for a rod or pipe electrode are: Section 2.50.3

1. Minimum length of 2.5 m or 8 ft

2. When metal pipe or conduit is used for electrode, it is required to be not smaller than trade size ¾ conduit.

3. Iron or steel pipe electrodes are required to have a galvanized surface or other corrosive resistant material.

4. Rod electrode may be iron, steel, or stainless steel and are required to have a minimum diameter of 5/8 inch (16mm) diameter.

5. Nonferrous rods, or their equivalent are required to have a minimum diameter of ½ inch (13 mm).

Page 50: Why Grounding is Used-8th Vis RC

50

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Installation of Grounding Rod

Section 2.50.13.15(G)*

Page 51: Why Grounding is Used-8th Vis RC

51

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Main Bonding Jumper

Page 52: Why Grounding is Used-8th Vis RC

52

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Main Bonding Jumper

Page 53: Why Grounding is Used-8th Vis RC

53

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Bonded

Page 54: Why Grounding is Used-8th Vis RC

54

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing the Main Bonding Jumper (Sec. 2.50.2.9(d))

Three methods for sizing the main bonding jumper are given in Table 2.50.3.17.

When sizing the main bonding jumper, the size and material of service entrance conductors and material used for the main bonding conductor are taken into consideration.

Page 55: Why Grounding is Used-8th Vis RC

55

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing the Main Bonding Jumper

Three methods for sizing the main bonding jumper are:1. Basic Rule: Use Table 2.50.3.17, the

grounding electrode conductor table, is also used for the main bonding jumper.

2. 12 ½ Percent Rule for Large Conductors. When the total circular area of any service entrance phase conductor exceeds the maximum circular-mil area listed in Table 2.50.3.17, the main bonding jumper shall not be smaller than 12 ½ % of the service phase conductors.

Page 56: Why Grounding is Used-8th Vis RC

56

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing the Main Bonding Jumper

Three methods for sizing the main bonding jumper are:

3. Rule for Using Different Materials. This rule applies when the main bonding jumper is a different material than the service-entrance conductors. One could be aluminum and the other copper for example. In this case, the minimum size of the main bonding jumper is based on assuming that the service entrance conductors are of the same material as the main bonding jumper and that ampacity is equivalent to the installed phase conductors.

Page 57: Why Grounding is Used-8th Vis RC

57

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Sizing the Main Bonding Jumper (Sec. 2.50.5.13(c))

325 mm2 conductors

2.50.5.13, Table 2.50.3.1750 mm2 EquipmentBonding Jumper

Page 58: Why Grounding is Used-8th Vis RC

58

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

What is Effective Grounding?

Page 59: Why Grounding is Used-8th Vis RC

59

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effective Grounding

A violation of PEC Art. 2.50.3.11 which prohibits using the same grounding electrode for a lightning rod system and a system supply.

VIOLATION!!!

Page 60: Why Grounding is Used-8th Vis RC

60

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effective Grounding

PEC Art. 250.5.17 Lightning Protection System. The bonding of a system grounding electrode and a lightning rod grounding electrode.

BONDING

REQUIRED!!!

Page 61: Why Grounding is Used-8th Vis RC

61

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effective Grounding

When different grounding electrodes are used for abuilding and are not bonded together, a voltage hazard will exist!!!

Page 62: Why Grounding is Used-8th Vis RC

62

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Older designs, have independent grounding systems.

The more recent trend is to bond all the ground systems.

Effective Grounding

Page 63: Why Grounding is Used-8th Vis RC

63

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

How surges enter facilities

Effective Grounding

Page 64: Why Grounding is Used-8th Vis RC

64

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Understanding the Lightning DischargeCloud electrification –

charge particle separation, quasi static

E Field est. between cloud & ground

Downleader approaches, E Field increases to point of

initiation of upward streamers

Upward leader propagates toward

downleader to complete ionised path between

cloud & ground

Page 65: Why Grounding is Used-8th Vis RC

65

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effective Grounding

Section 2.50.5.17

Page 66: Why Grounding is Used-8th Vis RC

66

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effective Grounding

Page 67: Why Grounding is Used-8th Vis RC

67

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Effective Grounding

Page 68: Why Grounding is Used-8th Vis RC

68

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Ground Noncurrent-Carrying Conductive Materials Enclosing Electrical Equipment?

Page 69: Why Grounding is Used-8th Vis RC

69

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Ground Noncurrent-Carrying Conductive Materials Enclosing Electrical Equipment?

EQUIPMENT GROUNDING

Page 70: Why Grounding is Used-8th Vis RC

70

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Potential Difference

Potential difference between a grounded

water pipe and an ungrounded motor.

Page 71: Why Grounding is Used-8th Vis RC

71

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Potential Difference

Motor ground-fault. A hazard now exists.

Page 72: Why Grounding is Used-8th Vis RC

72

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Potential Difference

The hazard results in an electric shock.

There is a Voltage!

Page 73: Why Grounding is Used-8th Vis RC

73

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Potential Difference

Another shock hazard exists.

There is a Voltage!!

Page 74: Why Grounding is Used-8th Vis RC

74

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Potential Difference

Shock hazard eliminated by installing

a bonding jumper.

Page 75: Why Grounding is Used-8th Vis RC

75

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Neutral Conductor (PEC2.50.2.17(b))

The neutral conductor from the neutral point of the transformer or the generator to its connection point to the grounding impedance shall be fully insulated.

The neutral conductor shall have an ampacity of not less than the maximum current rating of the grounding impedance. In no case shall the neutral conductor be smaller than 8.0 mm2 copper or 14 mm2 aluminum or copper-clad aluminum.

Page 76: Why Grounding is Used-8th Vis RC

76

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Neutral Conductor (PEC 2.50.2.17(b))

Page 77: Why Grounding is Used-8th Vis RC

77

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Grounded Conductor

Not a “neutral” because it is not a 3 0r 4 wire system.

Page 78: Why Grounding is Used-8th Vis RC

78

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Grounded Conductor

Page 79: Why Grounding is Used-8th Vis RC

79

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Grounding and bonding at the service equipment

Page 80: Why Grounding is Used-8th Vis RC

80

Why Grounding is Used? BOARD OF ELECTRICAL ENGINEERING

8th Visayas IIEE Region VII Conference – Sept. 28, 2007

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.